Date: 18 JAN 2008

To,
Syndicate Bank
Sec-18
NOIDA
Dear Sir,
Kind Attn: Mr. Ashok (Branch Manager)
Sub: Report on testing of UPS batteries at your office (UPS 01)
We thank you very much for the courtesy extended to our service team during their
visit to your office to do online health check up for your UPS batteries. We also thank
you for giving us an opportunity to check the healthiness of your UPS batteries using
our online health monitor.
We are herewith enclosing the detailed report according to our observations based on
the testing for your kind reference.
UPS 1-BANK 1
1. 06 No. of Battery is showing very low voltage i.e. 9V. We infer that either that
particular battery has gone faulty or the batteries is not taking enough charge
hence this battery is getting discharged.
2. 10 Nos. of batteries is showing 12.0 V .This is good battery.
3. So based on our test reports we suggest you to that it is better to replace the
06Nos. of batteries which are showing low voltage in the battery bank, by giving a
shutdown and replace immediately for better backup.
UPS 1-BANK 2
4. 03No. of Battery is showing very low voltage i.e. 9V. We infer that either that
particular battery has gone faulty or the batteries is not taking enough charge
hence this battery is getting discharged.
5. 13 Nos. of batteries is showing 12.0 V .This is good battery.
6. So based on our test reports we suggest you to that it is better to replace the 03
Nos. of batteries which are showing low voltage in the battery bank, by giving a
shutdown and replace immediately for better backup.
Note: We suggest to you to replace the 16 Nos. of 12V/100AH battery for full backup.
Two separate one bank of 12V/100Ah battery for UPS.

If you have any clarifications regarding the above please feel free to contact us.
Thanking you and assuring you of our best services at all times,
Yours faithfully,
For Datum Technologies
Ram Namdeo
Mob-9313427208

AMARA RAJA BATTERIES LTD.,


Branch Office: 19 D, Mysore Deviation Road,
(Near Minerva Mills), Bangalore-560 023
Tel : 80 2310 2140, 23102141,23103811
Fax : 80 2310 2142

Ref: B-01/ACCENTURE/LK/BT-08/2003-04,
Date: Thursday, February 19, 2004
To,
M/s. Accenture Services (p) Ltd.
#71, Cunningham Road,
Bangalore 52.
Dear Sir,
Kind Attn:

Mr.Ravi Naidu/ Mr.Kamal Kannan

Sub: Report on testing of UPS batteries at your office.(UPS 02 )


We thank you very much for the courtesy extended to our service team during their visit to your office to do online
health check up for your UPS batteries. We also thank you for giving us an opportunity to check the healthiness of your
UPS batteries using our online health monitor.
We herewith enclosing the detailed report for your kind reference and our observations based on the testing.
UPS 2-BANK 1
1. 05 Nos of Batteries are showing high voltage i.e. above 14.5V. We infer that either that particular battery has gone
faulty or the neighboring battery is not taking enough charge hence this battery is getting over charged.
2. Remaining batteries are showing voltage of above 12V at the end of discharge. These are good batteries.
3. So based on our test reports we suggest you to that it is better to check the 05Nos of batteries which are showing
high voltage in the battery bank, by giving a shutdown and replace if necessary.
UPS 2-BANK 2
1. 04 Nos of Batteries are showing high voltage i.e. above 14.5V. We infer that either that particular battery has gone
faulty or the neighboring battery is not taking enough charge hence this battery is getting over charged.
2. Remaining batteries are showing voltage of above 12V at the end of discharge. These are good batteries.
3. So based on our test reports we suggest you to that it is better to check the 04Nos of batteries which are showing
high voltage in the battery bank, by giving a shutdown and replace if necessary.
If you have any clarifications regarding the above please feel free to contact us.
Thanking you and assuring you of our best services at all times,
Yours faithfully,
For Amara Raja Batteries Ltd.,

Madan Mohan.G.K.
Engineer Marketing (UPS Batteries)
AMARA RAJA BATTERIES LTD.,
Branch Office: 19 D, Mysore Deviation Road,
(Near Minerva Mills), Bangalore-560 023
Tel : 80 2310 2140, 23102141,23103811
Fax : 80 2310 2142

Ref: B-01/ACCENTURE/LK/BT-08/2003-04,
Date: Thursday, February 19, 2004
To,
M/s. Accenture Services (p) Ltd.
#71, Cunningham Road,
Bangalore 52.
Dear Sir,
Kind Attn:

Mr.Ravi Naidu/ Mr.Kamal Kannan

Sub: Report on testing of UPS batteries at your office.( UPS 03 )


We thank you very much for the courtesy extended to our service team during their visit to your office to do online
health check up for your UPS batteries. We also thank you for giving us an opportunity to check the healthiness of your
UPS batteries using our online health monitor.
We herewith enclosing the detailed report for your kind reference and our observations based on the testing.
UPS 3-BANK 1
1. 06 Nos of Batteries are showing high voltage i.e. above 14.5V. We infer that either that particular battery has gone
faulty or the neighboring battery is not taking enough charge hence this battery is getting over charged.
2. Remaining batteries are showing voltage of above 12V at the end of discharge. These are good batteries.
3. So based on our test reports we suggest you to that it is better to check the 06Nos of batteries which are showing
high voltage in the battery bank, by giving a shutdown and replace if necessary.
UPS 3-BANK 2
1. 01 battery is showing 10.1V at end of discharge. It is a faulty battery that needs to be replaced immediately.
2. 07 Nos of Batteries are showing high voltage i.e. above 14.5V. We infer that either that particular battery has gone
faulty or the neighboring battery is not taking enough charge hence this battery is getting over charged.
3. Remaining batteries are showing voltage of above 12V at the end of discharge. These are good batteries.
4. So based on our test reports we suggest you to that it is better to check the 07Nos of batteries which are showing
high voltage in the battery bank, by giving a shutdown and replace if necessary.
If you have any clarifications regarding the above please feel free to contact us.
Thanking you and assuring you of our best services at all times,
Yours faithfully,

For Amara Raja Batteries Ltd.,


Madan Mohan.G.K.
Engineer Marketing (UPS Batteries)
AMARA RAJA BATTERIES LTD.,
Branch Office: 19 D, Mysore Deviation Road,
(Near Minerva Mills), Bangalore-560 023
Tel : 80 2310 2140,2 3102141,23103811
Fax : 80 2310 2142

Ref: B-01/ACCENTURE/LK/BT-08/2003-04,
Date: Thursday, February 19, 2004
To,
M/s. Accenture Services (p) Ltd.
#71, Cunningham Road,
Bangalore 52.
Dear Sir,
Kind Attn:

Mr.Ravi Naidu/ Mr.Kamal Kannan

Sub: Report on testing of UPS batteries at your office.( UPS 04 )


We thank you very much for the courtesy extended to our service team during their visit to your office to do online
health check up for your UPS batteries. We also thank you for giving us an opportunity to check the healthiness of your
UPS batteries using our online health monitor.
We herewith enclosing the detailed report for your kind reference and our observations based on the testing.
UPS 4-BANK 1
1. 08 Nos of Batteries are showing high voltage i.e. above 14.5V. We infer that either that particular battery has gone
faulty or the neighboring battery is not taking enough charge hence this battery is getting over charged.
2. Remaining batteries are showing voltage of above 12V at the end of discharge. These are good batteries.
3. So based on our test reports we suggest you to that it is better to check the 08Nos of batteries which are showing
high voltage in the battery bank, by giving a shutdown and replace if necessary.
UPS 4-BANK 2
1. 07 Nos of Batteries are showing high voltage i.e. above 14.5V. We infer that either that particular battery has gone
faulty or the neighboring battery is not taking enough charge hence this battery is getting over charged.
2. Remaining batteries are showing voltage of above 12V at the end of discharge. These are good batteries.
3. So based on our test reports we suggest you to that it is better to check the 07Nos of batteries which are showing
high voltage in the battery bank, by giving a shutdown and replace if necessary.
If you have any clarifications regarding the above please feel free to contact us.
Thanking you and assuring you of our best services at all times,
Yours faithfully,
For Amara Raja Batteries Ltd.,

Madan Mohan.G.K.
Engineer Marketing (UPS Batteries)