website http://www.lgservice.

com

LG

LG
Multi Type Air Conditioner
SERVICE MANUAL
MODEL
Indoor Unit:

Room Type
AMNH076LQL0
AMNH096LQL0
AMNH096LRL0
AMNH126LRL0
AMNH186LTL0
AMNH246LTL0
AMNH07GD4L0
AMNH09GD4L0
AMNH12GD4L0
AMNH18GD5L0
AMNH24GD5L0
Art Cool Type
AMNH096AP*1
AMNH126AP*1
Art Cool Deluxe Type
AMNH076DZ*0
AMNH096DU*0
AMNH126DU*0
AMNH186D3*0
AMNH246D3*0
AMNH07GDZ*0
AMNH09GDU*0
AMNH12GDU*0
AMNH18GD3*0
AMNH24GD3*0
AMNH07GDE*0
AMNH09GDE*0
AMNH12GDE*0

Outdoor Unit: A2UW146FA0


A2UW146FA1
A2UW146FA2
A2UW166FA0
A2UW166FA1
A2UW186FA0
A3UW186FA0
A3UW186FA1
A3UW246FA0
A4UW246FA0
A4UW306FA0
A6UW406FA0

Duct Type
AMNH096BTG0
AMNH126BTG0
AMNH186BTG0
AMNH096BPA0
AMNH126BPA0
AMNH186BHA0
AMNH246BHA0
AMNC246BHA0
AMNH306BGA0
AMNC306BGA0
AMNH366BGA0
AMNC366BGA0
CVT
AMNH096VEA0
AMNH126VEA0
AMNH186VBA0
AMNH246VBA0

1 Way CST
AMNH096TCC0
AMNC096TCC0
AMNH126TCC0
AMNC126TCC0
AMNH09GTCC0
AMNH12GTCC0
4 Way CST
AMNH096TEC0
AMNH126TEC0
AMNH186TEC0
AMNH246TFC0
AMNH306TFC0
AMNH366TDC0
AMNH306TFA0
AMNC306TFC0
AMNC366TDC0
AMNH09GTEF0
AMNH12GTEF0
AMNH18GTEF0
AMNH24GTHF0

CAUTION
BEFORE SERVICING THE UNIT, READ THE SAFETY
PRECAUTIONS IN THIS MANUAL.
ONLY FOR AUTHORIZED SERVICE PERSONNEL.

Multi type Air Conditioner Service Manual

TABLE OF CONTENTS
Model Number Nomenclature ....................................................................................................................3
Symbols Used in this Manual ...................................................................................................................5
Safety Precautions......................................................................................................................................6
Dimensions................................................................................................................................................12
Indoor Unit..............................................................................................................................................12
Outdoor Unit ...........................................................................................................................................21
Product Specifications ............................................................................................................................22
Installation .................................................................................................................................................33
Select the best location of indoor unit ....................................................................................................33
How to fix ...............................................................................................................................................36
Piping and Drainage of Indoor Unit ........................................................................................................43
Connection of indoor unit piping.............................................................................................................44
Remote Controller Installation ................................................................................................................67
Connecting Pipings and the cable to Outdoor unit .................................................................................69
Checking the Drainage and Pipe forming...............................................................................................71
Maximum Length of Pipe and Extra Charge of Refrigerant Charge.......................................................76
Test Running ..........................................................................................................................................81
System Layout and Piping Length..........................................................................................................84
Installation ..............................................................................................................................................85
Installation of The Main Unit...................................................................................................................86
Connection of Piping ..............................................................................................................................87
Connection of Wiring ..............................................................................................................................88
Operation ..................................................................................................................................................89
Function of control..................................................................................................................................89
Function of Indoor Unit ...........................................................................................................................94
Function of Outdoor Unit ......................................................................................................................100
Remote Control Operation ...................................................................................................................101
Control Devices and Function ...............................................................................................................109
Simple Central Control .........................................................................................................................109
Term of Each part and Function ...........................................................................................................109
Electrical wiring ....................................................................................................................................110
Deluxe Central Control .........................................................................................................................116
Disassembly of the parts (Indoor unit) .................................................................................................122
Indoor unit ............................................................................................................................................122
Schematic Diagram.................................................................................................................................137
Electronic Control Device .....................................................................................................................137
Wiring Diagram.....................................................................................................................................148
Components Locations.........................................................................................................................153
Troubleshooting Guide ...........................................................................................................................171
Refrigeration Cycle Diagram ................................................................................................................171
Self-diagnosis Function ........................................................................................................................177
Cycle Troubleshooting Guide................................................................................................................178
Electronic Parts Troubleshooting Guide ...............................................................................................179
General Information..............................................................................................................................184
(3-way) Valve ...........................................................................................................................................200
Exploded View & Replacement Parts List ............................................................................................204
Indoor Unit ...........................................................................................................................................204
Outdoor Unit ........................................................................................................................................244

2 Multi type Air Conditioner

Model Number Nomenclature

Model Number Nomenclature


Indoor Unit
AMN

07

0
Serial Number
Function
A : Basic, L : Nano Plasma + Auto Clean(Wall Mounted)
C: Plasma(Ceiling Cassette), G: Low Static Motor

ART COOL(DELUXE) Type Front Panel Color


B : Blue, D : Wood, M : Meta, R : Mirror, W : White

Chassis Name
Indoor Unit Type
L : Wall Mounted , A : ART COOL
D : ART COOL DELUXE, T : Ceiling Cassette
B : Ceiling Concealed Duct
V : Ceiling & Floor(Convertible) D : D Look (Wall Mounted)

Electrical Rating
6 : 1, 220-240V, 50Hz G : 220~240V, 50/60Hz

Nominal Cooling Capacity in Btu/h


Ex) 7,000 Btu/h '07', 18,000 Btu/h '18'

Model Type
H : Heat Pump

TPS Inverter Multi System Indoor Unit

Outdoor Unit
A2U

18

0
Serial Number
Function
A : Basic

Multi Type
F : Free Joint Multi Type

Electrical Ratings
6 : 1, 220-240V, 50Hz
8 : 3, 380-415V, 50Hz

Nominal Cooling Capacity in Btu/h


Ex) 18,000 Btu/h '18', 48,000 Btu/h, 50Hz '48'

Model Type
W : DC Inverter Heat Pump

R410A TPS Inverter Multi System Outdoor Unit.


And No. of Connectable Indoor Units
Ex) A2U : Connectable max. 2 Indoor Units
A6U : Connectable max. 6 Indoor Units

Service Manual 3

Model Number Nomenclature

Panel (Cassette, Built in Duct)


Category

CHASSIS

TF

TC,TC1
CST PANEL
TE(family look)

TE1(family look)

TD(family look)

PANEL P/NO.

Remark

PT-CFA

3721A10072B

8435002992862

COOLING

PT-CFC

3721A10072G

8435002992879

COOLING + PLASMA

PT-HFA

3821A10072A

8435002992886

HEATING

PT-HFC

3721A10072E

8435002992893

HEATING + PLASMA

PT-CCA

3721A10023Z

8435002994095

COOLING

PT-CCC

3721A10023W

8435002994101

COOLING + PLASMA

PT-HCA

3721A10023Y

8435002994118

HEATING

PT-HCC

3721A10023V

8435002994125

HEATING + PLASMA

PT-HEA

3721A10105A

8435002992978

HEATING

PT-HEC

3721A10105B

8435002992985

HEATING + PLASMA

PT-CEA

3721A10105C

8435002992954

COOLING

PT-CEC

3721A10105D

8435002992961

COOLING + PLASMA

PT-HEA1

3721A10105M

HEATING

PT-HEC1

3721A10105N

HEATING + PLASMA

PT-HAD

3721A10106A

8435002994057

HEATING

PT-HDC

3721A10106B

8435002994064

HEATING + PLASMA

PT-CDA

3721A10106C

8435002994071

COOLING

PT-CDC

3721A10106D

8435002994088

COOLING + PLASMA

PT-HDA1

3721A10106X

HEATING

3721A10106Z

HEATING + PLASMA

BP

PB-HPA

3721A20168A

9K/12K

BQ

PB-HQA

3721A20168B

18K/24K

6. Function
Function
Basic

Number
1, 2
3
4
5
6

SERIAL NO.

PT-HDC1

TH(family look)
BUILT IN DUCT

PANEL NAME

Contents
Panel for Cassette
Cooling/Heatpump
Chassis Name
Function

5. Chassis Name
Chassis
Abbrevation
TC
C
TB
B
TD
D
TE
E
TF
F
TH
H
TJ
J
BP
P
BQ
Q

4 Multi type Air Conditioner

Plasma Filter
Elevation Grille
Elevation Grille + Plasma Filter
TE/TB/TD Before 2003 : Basic
TE/TD Before 2003 : Plasma Filter

A
B
C
D
E
F
0
1

Model Number Nomenclature

Indoor Units
Category

Wall
Mounted

Type

General

Chasiss

SQ

2.1
(7000)
AMNH
076LQL0

SR

2.6
(9000)
AMNH
096LQL0
AMNH
096LRL0

Model Name
Capacity, kW(Btu/h)
3.5
5.3
(12000)
(18000)

ART
Cool

Mirror

AMNH
126LRL0

AMNH
186LTL0

AMNH
246LTC0

AMNH
18GD5L0
-

AMNH
24GD5L0
-

S4

AMNH
07GD4L0

AMNH
09GD4L0

AMNH
12GD4L0

SP1

AMNN
096AP*1

AMNN
126AP*1

SZ

AMNH
076DZ*0
07GDZ*0

Ceiling
Cassette

4Way

Ceiling &
Floor

AMNH
126DU*0
12GDU*0

SE

AMNH
07GDE*0

AMNH
09GDE*0
AMNH/C
096TCC0
AMNH09
GTCC0
AMNH
096TEC0
AMNH
09GTEF0

AMNH
12GDE*0
AMNH/C
126TCC0
AMNH12
GTCC0
AMNH
126TEC0
AMNH
12GTEF0

TC,TC1
TE

TE1

AMNH
186D3*0
18GD3*0

AMNH
246D3*0
24GD3*0

AMNH
186TEC0
AMNH
18GTEF0

AMNH
246TFC0
AMNH
24GTHF0

AMNH/C
306TF*0

TF

TH

TD

Ceiling
Concealed
Duct

AMNH
096DU*0
09GDU*0

S3

1Way

BH

10.6
(36000)

ST

SU

8.8
(30000)

S5
General

7.0
(24000)

AMNH/C
366TDC0

AMNH
186BHA0

AMNH
246BHA0

AMNH
366BGA0

High
Static

BG

AMNH/C
306BGA0

Low
Static

BT

BP

VE

AMNH
126BTG0
AMNH
126BPA0
AMNH
126VEA0

AMNH
186BTG0

Built in

AMNH
096BTG0
AMNH
096BPA0
AMNH
096VEA0

AMNH
186VBA0

AMNH
246VBA0

Convertible
VB

Outdoor Units
TPS Inverter Multi Series

Multi Piping Type

Heat Pump
Rated Capacity

Model Name
A2UW146FA0/1/2 A2UW166FA0/1 A2UW186FA0 A3UW186FA0/1 A3UW246FA0 A4UW246FA0
Cooling
kW(Btu/h)
4.1(14000)
4.7(16000)
5.3(18000)
5.3(18000)
7.0(24000)
7.0(24000)
Heating
kW(Btu/h)
4.7(16000)
5.3(18000)
6.3(21600)
6.3(21600)
8.2(28000)
8.2(28000)
Number of Indoor Units to be Connected
Max.2 Units
Max.2 Units
Max.2 Units
Max.3 Units
Max.3 Units
Max.4 Units
Indoor Units
kW
2.1~6.2
2.1~7.0
2.1~7.0
2.1~8.8
2.1~9.7
2.1~11.4
Connectable Capacity
Btu/h
7000~21000 7000~24000 7000~24000
7000~30000 7000~33000
7000~33000
Power Supply
1, 220-240V, 50Hz

Distributor Type
A4UW306FA0 A6UW406FA0
8.8(30000)
11.7(40000)
10.1(34500)
13.5(46000)
Max.4 Units
Max.6 Units
2.1~11.4
4.7~15.2
7000~39000 16000~52000

A7UW486FA0 A8UW566FA0
14.0(48000) 16.4(56000)
16.2(55200) 18.9(64400)
Max.7 Units
Max.8 Units
5.6~18.3
6.6~21.3
19200~62400 22400~72800

Notes :
A2UW146FA0/1/2, A2UW166FA0/1, A2UW186FA0 and A3UW186FA0/1 are not TPS inverter system but one inverter compressor system.

Symbols Used in this Manual


This symbol alerts you to the risk of electric shock.
This symbol alerts you to hazards that could cause harm to the
air conditioner.
NOTICE

This symbol indicates special notes.

Service Manual 5

Safety Precautions

Safety Precautions
To prevent injury to the user or other people and property damage, the following instructions must
be followed.
Incorrect operation due to ignoring instruction will cause harm or damage. The seriousness is
classified by the following indications.

WARNING

This symbol indicates the possibility of death or serious injury.

CAUTION

This symbol indicates the possibility of injury or damage to properties only.

Meanings of symbols used in this manual are as shown below.

Be sure not to do.


Be sure to follow the instruction.

WARNING
Installation
Do not use a defective or underrated circuit breaker. Use this
appliance on a dedicated circuit.
There is risk of fire or electric
shock.

Install the panel and the cover


of control box securely.
There is risk of fire or electric
shock.

6 Multi type Air Conditioner

For electrical work, contact the


dealer, seller, a qualified electrician,
or an Authorized Service Center.
Do not disassemble or repair the
product. There is risk of fire or
electric shock.

Always install a dedicated circuit and breaker.


Improper wiring or installation may
cause fire or electric shock

Always ground the product.

There is risk of fire or electric


shock.

Use the correctly rated breaker or fuse.


There is risk of fire or electric
shock.

Safety Precautions
Do not modify or extend the
power cable.
There is risk of fire or electric
shock.

For installation, always contact the dealer or an


Authorized Service Center.
There is risk of fire, electric shock,
explosion, or injury.

Do not let the air conditioner


run for a long time when the
humidity is very high and a
door or a window is left open.

Do not install, remove, or reinstall the unit by yourself


(customer).
There is risk of fire, electric shock,
explosion, or injury.

Do not install the product on a


defective installation stand.
It may cause injury, accident, or
damage to the product.

Take care to ensure that


power cable could not be
pulled out or damaged during
operation.

Moisture may condense and wet or There is risk of fire or electric


damage furniture.
shock.

Be cautious when unpacking


and installing the product.
Sharp edges could cause injury.
Be especially careful of the case
edges and the fins on the condenser and evaporator.

Be sure the installation area


does not deteriorate with age.
If the base collapses, the air conditioner could fall with it, causing
property damage, product failure,
and personal injury.

Do not place anything on the


power cable.

There is risk of fire or electric


shock.

Service Manual 7

Safety Precautions
Do not plug or unplug the
power supply plug during
operation.
There is risk of fire or electric
shock.

Do not allow water to run into


electric parts.
It may cause There is risk of fire,
failure of the product, or electric
shock.

Do not touch(operate) the


product with wet hands.
There is risk of fire or electrical
shock.

Do not store or use flammable


gas or combustibles near the
product.
There is risk of fire or failure of
product.

Do not place a heater or other


appliances near the power
cable.
There is risk of fire and electric
shock.

Do not use the product in a


tightly closed space for a long
time.
Oxygen deficiency could occur.

Gasolin

When flammable gas leaks,


turn off the gas and open a
window for ventilation before
turn the product on.
Do not use the telephone or turn
switches on or off. There is risk of
explosion or fire

8 Multi type Air Conditioner

If strange sounds, or small or


smoke comes from product.
Turn the breaker off or disconnect the power supply cable.
There is risk of electric shock or
fire.

Stop operation and close the


window in storm or hurricane.
If possible, remove the product from the window before
the hurricane arrives.
There is risk of property damage,
failure of product, or electric shock.

Safety Precautions
Do not open the inlet grill of the product
during operation. (Do not touch the electrostatic filter, if the unit is so equipped.)
There is risk of physical injury,
electric shock, or product failure.

When the product is soaked


(flooded or submerged), contact
an Authorized Service Center.
There is risk of fire or electric
shock.

Ventilate the product from time to time when


operating it together with a stove, etc.
There is risk of fire or electric shock.

Be cautious that water could


not enter the product.
There is risk of fire, electric shock,
or product damage.

Turn the main power off when cleaning or


maintaining the product.
There is risk of electric shock.

When the product is not be used for a long time, disconnect the power supply plug or turn off the breaker.

Take care to ensure that nobody could step on


or fall onto the outdoor unit.

There is risk of product damage or failure, or unintend- This could result in personal injury and product damed operation.
age.

CAUTION
Installation
Always check for gas (refrigerant) leakage after installation or repair of product.
Low refrigerant levels may cause
failure of product.

Install the drain hose to ensure that


water is drained away properly.

Keep level even when


installing the product.

A bad connection may cause water To avoid vibration or water leakleakage.


age.

90

Service Manual 9

Safety Precautions
Do not install the product
where the noise or hot air
from the outdoor unit could
damage the neighborhoods.
It may cause a problem for your
neighbors.

Use two or more people to lift


and transport the product.

Avoid personal injury.

Do not install the product


where it will be exposed to
sea wind (salt spray) directly.
It may cause corrosion on the
product. Corrosion, particularly on
the condenser and evaporator fins,
could cause product malfunction or
inefficient operation.

Operational
Do not expose the skin directly to cool air for
long periods of time.
(Don't sit in the draft.)
This could harm to your health.

Do not block the inlet or outlet


of air flow.
It may cause product failure.

Do not use the product for special purposes,


such as preserving foods, works of art, etc. It
is a consumer air conditioner, not a precision
refrigeration system.
There is risk of damage or loss of property.

Use a soft cloth to clean. Do


not use harsh detergents, solvents, etc.
There is risk of fire, electric shock,
or damage to the plastic parts of
the product.

x
Wa Thinner

10 Multi type Air Conditioner

Do not touch the metal parts of


the product when removing the
air filter. They are very sharp!
There is risk of personal injury.

Safety Precautions
Do not step on or put anyting
on the product. (outdoor
units)

Always insert the filter securely. Clean the filter every two
weeks or more often if necessary.

Do not insert hands or other


objects through the air inlet or
outlet while the product is
operated.

There is risk of personal injury and


failure of product.

A dirty filter reduces the efficiency


of the air conditioner and could
cause product malfunction or damage.

There are sharp and moving parts


that could cause personal injury.

Do not drink the water drained


from the product.

Use a firm stool or ladder


when cleaning or maintaining
the product.

Replace the all batteries in the


remote control with new ones
of the same type. Do not mix
old and new batteries or different types of batteries.

It is not sanitary and could cause


serious health issues.

Be careful and avoid personal


injury.

Do not recharge or disassemble the batteries.


Do not dispose of batteries in a fire.

They may burn or explode.

There is risk of fire or explosion

If the liquid from the batteries gets onto your


skin or clothes, wash it well with clean water.
Do not use the remote if the batteries have
leaked.
The chemicals in batteries could cause burns or other
health hazards.

Service Manual 11

Dimensions

Dimensions
Indoor Unit
1. Split Type Indoor

2. Art Cool Type Indoor Unit


W

Pipe Hole

Hanger Hole

Fix Hole

Installation plate

Model
Dimension

SQ
7k, 9k

SR
9k, 12k

ST
18k, 24k

S4
7k, 9k, 12k

S5
18k, 24k

SP
9k, 12k

mm

824

900

1080

840

1090

570

mm

260

285

314

270

300

568

mm

155

156

172

153

178

137

12 Multi type Air Conditioner

Dimensions

3. Art Cool Deluxe Type


SZ,SU,S3

SE

H
H

D
W

Installation plate
Installation plate

MODEL
DIM

Unit

SZ
7K

SU
9K, 12K

S3
18K, 24K

SE
7K, 9K, 12K

mm

900

1030

1170

895

mm

272

290

315

282

mm

135

153

173

165

Service Manual 13

Dimensions

4. Duct Type

BH/BG

D
W

H
H

BP

BT/BT1

BT
9K/12K

BT1
18K

BH
18K/24K

BG
30K/36K

BP
9K/12K

W(mm)

708

1060

880

1180

580

H(mm)

230

230

260

298

300

D(mm)

537

357

450

450

750

MODEL
DIM

14 Multi type Air Conditioner

Dimensions

5. CVT Type
VB(18K/24K)

W
H

D
63mm
38mm

39

26

2m

5m

250mm

mm

36

46

8m

175mm

mm

76

10

(Installation Plate)

(Rear Side)
mm

36

VE(8K/12K)
D

Installation plate

MODEL
DIM

Unit

VE
9K/12K

VB
18K/24K

mm

900

1200

mm

285

615

mm

156

205

Service Manual 15

Dimensions

6. CST Type - TC,TC1 (9K/12K)


1,000 (Ceiling opening)

4
16.7
7

30.8

931.6
893.4
860
846

328.4 (Hanging bolt) 30.8

430 (Ceiling opening)


390

931.6
893.4 (Hanging bolt)
860

155

164

194.4

390
328.4

50
42.7

37

91.6
97.7
116.3

80

180

430

141.8
91.6

130

55

180

180

1050
694.5

480

(unit : mm)
Number
1
2
3
4
5
6

16 Multi type Air Conditioner

Name
Liquid pipe connection
Gas pipe connection
Drain pipe connection
Power supply connection
Air discharge grill
Air suction grill

Descripition
6.35 flare
9.52 flare

Dimensions

7. CST Type - TE(1) (9K/12K/18K)


600 (Ceiling opening)
521(Hanging bolt)

269
570 Unit size

570 Unit size

670

75

670

600 (Ceiling opening)

39.5

450 (Hanging bolt) 75

39.5

Unit:mm

570

670

450

521

670

570

CLOSE

OPEN

OPEN

CLOSE

40
4

30

160

52

190.5

110
90

90

120.4

30

269

110

(unit : mm)
Number
1
2
3
4
5
6

Name
Liquid pipe connection
Gas pipe connection
Drain pipe connection
Power supply connection
Air discharge grill
Air suction grill

Descripition
6.35 flare
9k: 9.52, 12k: 9.52, 18k: 12.7 flare

Service Manual 17

Dimensions

8. CST Type - TF (24K/30K)


790 (Ceiling opening)
572(Hanging bolt)

109

744 Unit size


744 Unit size

292
850

66

850

790 (Ceiling opening)

658 (Hanging bolt)

66

109

Unit:mm

658

744

850

850

572
744
6

70
4

(unit : mm)

18 Multi type Air Conditioner

Name
Liquid pipe connection
Gas pipe connection
Drain pipe connection
Power supply connection
Air discharge grill
Air suction grill

Descripition
6.35 flare
12.7 flare-24K, 15.88 flare-30K

212

150

90

Number
1
2
3
4
5
6

110

54

192

30

110
90

292

117

Dimensions

9. CST Type - TH (24K)


862 (Ceiling opening)
688(Hanging bolt)

87

806 (Hanging bolt)

840

255

840

950

28

950

862 (Ceiling opening)

28

87

Unit:mm

608

840

950

950

688
840
6

70
4
2

212

150

90

110

54

192

30

110
90

225

117

(unit : mm)
Number
1
2
3
4
5
6

Name
Liquid pipe connection
Gas pipe connection
Drain pipe connection
Power supply connection
Air discharge grill
Air suction grill

Descripition
6.35 flare
12.7 flare-24K, 15.88 flare-30K

Service Manual 19

Dimensions

10. CST Type - TD(36K)


875 (Ceiling opening)
785 (Hanging bolt)

288

840 Unit size


840 Unit size

950
950

875 (Ceiling opening)

45

101.5 672 (Hanging bolt) 101.5

45

950

Unit:mm
840

840

785

950

678

55

40

Fresh Air Inlet

20 Multi type Air Conditioner

Name
Liquid pipe connection
Gas pipe connection
Drain pipe connection
Power supply connection
Air discharge grill
Air suction grill

Descripition
6.35 flare
15.88 flare

210.5

52 180
3

(unit : mm)
Number
1
2
3
4
5
6

110
90

110
90

140

290

30

Dimensions

Outdoor Unit
D

L1

L2

L3

30K/40K

L4

L6

L5

L7

18K/24K
MODEL
DIM

UL
14K, 16K

UE
14K, 18K

UE1
24K

UE2
30K

UH
40K

mm

770

870

870

870

900

mm

540

655

800

1060

1165

mm

245

320

320

320

370

L1

mm

287

370

370

360

460

L2

mm

21

25

25

20

45

L3

mm

530

775

775

1040

1135

L4

mm

10

25

25

20

30

L5

mm

518

546

546

550

550

L6

mm

126

160

160

160

175

L7

mm

126

160

160

165

175

Service Manual 21

Product Specifications

Product Specifications
Indoor Unit
Indoor Unit Type

Wall Mounted

Model
Rated Cooling Capacity
Rated Heating Capacity
Air Circulation
H/M/L
Setting temperature range
Fan motor
Output
Model
No. of Poles
Input
Running Current
Capacitor
Fan
Type
No. Used / Diameter
Fan RPM
Cooling(H/M/L)
Heating(H/M/L)
Noise Level(Sound Press,1m) H/M/L
Temperature controller
Coil
Tube Size (OD)
Fins per inch
No. of Rows & Column
Dehumidification Rate
Dimensions (W*H*D)
Net Weight
Piping
Liquid
Connection
Gas
Drain hose (ID )
Packing Dimension (W*H*D)
Stuffing Quantity
Without S/Parts
Front Panel Color
"" Position

AMNH076LQL0
kcal/hr(W)
Btu/hr
kcal/hr(W)
Btu/hr
CMM(CFM)
C
W

W
A
F/Vac
EA/inch(mm)
rpm
rpm
dBA
inch(mm)

l/h
inch(mm)
kg(lbs)
inch(mm)
inch(mm)
mm
inch(mm)
20/40ft

AMNH096LQL0

AMNH096LRL0

AMNH126LRL0

AMNH186LTL0

AMNH246LTL0

1764(2051)
2267(2638)
7000
9000
2016(2343)
2520(2929)
8000
10000
5.5(194)
8.5(300)
18~30 / 16~30
18~30 / 16~30
8.4
8.4
IC-8415LG62A IC-8415LG62A
4
4
25
25
0.11
0.11
0.9 / 400
0.9 / 400
Cross Flow Fan Cross Flow Fan
1/3.43(87)
1/3.43(87)
1080 / 970 / 880
1170 / 1100 / 1020
1080 / 970 / 880
1170 / 1100 / 1020
35 / 32 / 29
37 / 33 / 31
Thermistor
Thermistor
0.197(5.0)
0.197(5.0)
19
19
2R,10C
2R,10C
1.0
1.2
32.4*10.2*6.1(824*260*155) 32.4*10.2*6.1(824*260*155)
7(15.4)
7(15.4)
1/4 (6.35)
1/4 (6.35)
3/8 (9.52)
3/8 (9.52)
20
20
35.4*9.2*13.4(900*233*340) 35.4*9.2*13.4(900*233*340)
354/774 (360/780) 354/774 (360/780)
Morning Beige
Morning Beige

2267(2638)
9000
2520(2929)
10000
8.5(300)
18~30 / 16~30
14.4
IC-8420LG48A
4
37
0.16
0.9 / 400
Cross Flow Fan
1/3.43(87)
1200/1100/1000
1200/1100/1000
35 / 33 / 31
Thermistor
0.197(5.0)
20
2R,12C
1.4
35.4*11.2*6.1(900*285*156)
8(17.6)
1/4 (6.35)
3/8 (9.52)
20
38.4*9.2*14.6(976*233*372)
338/714 (340/720)
Morning Beige

3024(3515)
12000
3326(3867)
13200
9.0(318)
18~30 / 16~30
14.4
IC-8420LG48A
4
37
0.16
0.9 / 400
Cross Flow Fan
1/3.43(87)
1290 / 1200 / 1120
1290 / 1200 / 1120
39 / 36 / 34
Thermistor
0.197(5.0)
20
2R,12C
1.8
35.4*11.2*6.1(900*285*156)
8(17.6)
1/4 (6.35)
3/8 (9.52)
20
38.4*9.2*14.6(976*233*372)
338/714 (340/720)
Morning Beige

4536(5275)
18000
4990(5803)
19800
13(459)
18~30 / 16~30
22
AMR-023E2
4
54
0.21
2.0 / 370
Cross Flow Fan
1/3.74(95)
1140 / 1040 / 940
1140 / 1040 / 940
42 / 39 / 36
Thermistor
0.276(7.0)
20
2R,13C
2.0
42.9*12.4*6.8(1090*314*172)
12(26.5)
1/4 (6.35)
1/2 (12.7)
20
45.9*10.0*15.3(1165*255*388)
264/536 (270/540)
Morning Beige

5544(6446)
22000
6099(7091)
24200
14(494)
18~30 / 16~30
29
AMR-023E5
6
59
0.21
2.0 / 370
Cross Flow Fan
1/3.74(95)
1260 / 1140 / 1000
1260 / 1140 / 1000
46 / 43 / 39
Thermistor
0.276(7.0)
20
2R,13C
2.5
42.9*12.4*6.8(1090*314*172)
12(26.5)
1/4 (6.35)
1/2 (12.7)
20
45.9*10.0*15.3(1165*255*388)
264/536 (270/540)
Morning Beige

Indoor Unit Type

ART COOL DELUXE

Model
Rated Cooling Capacity
Rated Heating Capacity
Air Circulation
H/M/L
Setting temperature range
Fan motor
Output
Model
No. of Poles
Input
Running Current
Capacitor
Fan
Type
No. Used / Diameter
Fan RPM
Cooling(H/M/L)
Heating(H/M/L)
Noise Level(Sound Press,1m) H/M/L
Temperature controller
Coil
Tube Size (OD)
Fins per inch
No. of Rows & Column
Dehumidification Rate
Dimensions (W*H*D)
Net Weight
Piping
Liquid
Connection
Gas
Drain hose (ID )
Packing Dimension (W*H*D)
Stuffing Quantity
Without S/Parts
Front Panel Color
"" Position

AMNH076DZ*0
kcal/hr(W)
Btu/hr
kcal/hr(W)
Btu/hr
CMM(CFM)
C
W

W
A
F/Vac
EA/inch(mm)
rpm
rpm
dBA
inch(mm)

l/h
inch(mm)
kg(lbs)
inch(mm)
inch(mm)
mm
inch(mm)
20/40ft

1764(2051)
7000
1940(2257)
8000
5.5(194)
18~30 / 16~30
4.7
OBM-1547P2
4
27
0.12
0.9/400
Cross Flow Fan
1/3.43(87)
1330/1230/1130
1330/1230/1130
35 / 32 / 29
Thermistor
0.197(5.0)
19
2R,12C
1.0
42.9*12.4*6.8(1090*314*172)
8.1(17.9)
1/4 (6.35)
3/8(9.52)
20
38.8*8.7*14.3(985*220*363)
340/720

AMNH096DU*0

Note : 1. See the page "Combination Table"


2. Due to our policy of innovation some specifications may be changed without notification.

22 Multi type Air Conditioner

AMNH126DU*0

AMNH186D3*0

AMNH246D3*0

2267(2638)
2772(3224)
4536(5275)
5796(6740)
9000
12000
18000
23000
2495(2901)
3049(3546)
4990(5803)
6426(7472)
10000
13200
19800
25500
8.5(300)
9.0(318)
13(459)
14(494)
18~30 / 16~30
18~30 / 16~30
18~30 / 16~30
18~30 / 16~30
7.8
7.8
25.6
25.6
OBM-1547P2
OBM-1547P2
OBM-2510P2
OBM-2510P2
4
4
4
4
40
40
58
58
0.18
0.18
0.15
0.21
0.9/400
0.9/400
2.0 / 370
2.0 / 370
Cross Flow Fan
Cross Flow Fan
Cross Flow Fan
Cross Flow Fan
1/3.43(87)
1/3.43(87)
1/3.74(95)
1/3.74(95)
1320/1220/1120
1400/1300/1200
1320/1220/1120
1400/1300/1200
37 / 33 / 31
39 / 36 / 34
40/38/36
44/42/40
Thermistor
Thermistor
Thermistor
Thermistor
0.197(5.0)
0.197(5.0)
0.276(7.0)
0.276(7.0)
19
19
20
20
2R,12C
2R,12C
2R,13C
2R,13C
1.2
1.5
2
2.5
35.4*10.7*5.3(900*272*135)
40.6*11.4*6.0(1030*290*153) 46.1*24.4*6.81 (1170*315*173) 46.1*24.4*6.81 (1170*315*173)
9.5(20.9)
9.5(20.9)
13(28.7)
13(28.7)
1/4 (6.35)
1/4 (6.35)
1/4 (6.35)
1/4 (6.35)
3/8(9.52)
3/8(9.52)
1/2 (12.7)
1/2 (12.7)
20
20
20
20
44.0*8.9*14.8(1117*225*377)
44.0*8.9*14.8(1117*225*377) 49.4*15.3*10.2 (1255*388*258) 49.4*15.3*10.2 (1255*388*258)
324/684
324/684
234/495
234/495
R:Mirror, M:Metal, N:Walnut, W:White, B:Blue, C:Cherry

Product Specifications
Indoor Unit Type

ART COOL Mirror

Model
Power supply
Cooling capacity
Heating capacity
Current
Fan

Nominal running current


Motor type
Fan type
Motor output x Number of unit
Air flow rate
(H/M/L)
Capacitor
Drive
Row x column x FPI
Body
Body

Coil
Dimensions (WxHxD)
Weight
Air filter
Sound level (H/M/L)
Piping
Liquid
connections
Gas
Dehumidification rate
Safety devices
Temperature sensor
Referigerant
Referigerant control
Connectable outdoor unit
Power and transmission interunit cable

AMNH07GDE*0[MC07AH*NE0]

AMNH09GDE*0[MC09AH*NE0]

AMNH12GDE*0[MC12AH*NE0]

dB(A)+3
mm(inch)
mm(inch)
l/h

1/ 220~240/ 50
2.05
7,000
2.34
8,000
0.10
BLDC
Cross Flow Fan
4.7 X 1
7/6/4
247/212/141
Direct Drive
2R x 12C x 19
915x282x165 (36.0*11.1*6.5)
8.1(17.9)
Long Life Filter
30/25/21
6.35 (1/4)
9.52 (3/8)
1.0

1/ 220~240/ 50
3.52
12,000
3.87
13,200
0.15
BLDC
Cross Flow Fan
7.8 X 1
10/8/6
353/283/212
Direct Drive
2R x 12C x 19
915x282x165 (36.0*11.1*6.5)
9.5(20.9)
Long Life Filter
35/28/24
6.35 (1/4)
9.52 (3/8)
1.5

No.x mm2

Thermistor
R410A
LEV(in Outdoor unit or BD)
Multi F /F DX series
4*0.75

1/ 220~240/ 50
2.64
9,000
2.93
10,000
0.15
BLDC
Cross Flow Fan
7.8 X 1
8/7/5
282/247/177
Direct Drive
2R x 12C x 19
915x282x165 (36.0*11.1*6.5)
9.5(20.9)
Long Life Filter
31/26/22
6.35 (1/4)
9.52 (3/8)
1.2
Fuse, Thermal Protector for Fan Motor
Thermistor
R410A
LEV(in Outdoor unit or BD)
Multi F /F DX series
4*0.75

/V/Hz
kW
Btu/h
kW
Btu/h
A

cmm
cfm
F/Vac
mm
mm(inch)
kg(lbs)

Indoor Unit Type

Wall Mounted

Model
Nominal Cooling Capacity
Nominal Heating Capacity
Air Circulation
H/M/L
Setting temperature range(cool/heat)
Fan motor
Output
Model
Fan
Type
No. Used / Diameter
Fan RPM
Cooling(H/M/L)
Heating(H/M/L)
Noise Level (Sound Press,1m) H/M/L
Temperature controller
Coil
Tube Size (OD)
Fins per inch
No. of Rows & Column
Dehumidification Rate
Dimensions (W*H*D)
Net Weight
Piping Connection
Liquid
Gas
Drain hose (ID )
Packing Dimension (W*H*D)
Stuffing Quantity
With(Without) S/Parts
Front Panel Color
"" Position

Thermistor
R410A
LEV(in Outdoor unit or BD)
Multi F /F DX series
4*0.75

AMNH07GD4L0
kcal/h(W)
Btu/h
kcal/h(W)
Btu/h
CMM(CFM)
C
W

EA/inch(mm)
rpm
rpm
dBA
inch(mm)

l/h
inch(mm)
kg(lbs)
inch(mm)
inch(mm)
mm
inch(mm)
20/40ft

AMNH09GD4L0

1764(2051)
2267(2638)
7000
9,000
2016(2343)
2520(2929)
8000
10,000
5.5(194)
8.2(290)
18~30 / 16~30
18~30 / 16~30
20
20
SIC-37CV-FI30-3
SIC-37CV-FI30-3
Cross Flow Fan
Cross Flow Fan
1/3.74(95)
1/3.74(95)
1000/870/750
1140/1000/800
1000/870/750
1140/1000/800
29 / 25 / 20
33 / 29 / 22
Thermistor
Thermistor
0.197(5.0)
0.197(5.0)
20
20
2R,15C
2R,15C
0.9
1.1
33.0*10.6*6.0(840*270*153) 33.0*10.6*6.0(840*270*153)
7(15.4)
7(15.4)
1/4 (6.35)
1/4 (6.35)
3/8 (9.52)
3/8 (9.52)
20
20
35.7*13.1*8.8(906*332*223) 35.7*13.1*8.8(906*332*223)
437/906 (432/896)
437/906 (432/896)
Morning Beige
Morning Beige

AMNH12GD4L0

AMNH18GD5L0

AMNH24GD5L0

3024(3515)
4536(5275)
5796(6740)
12,000
18,000
23,000
3326(3867)
4990(5803)
6426(7472)
13,200
19,800
25,500
9.0(318)
13(459)
14(494)
18~30 / 16~30
18~30 / 16~30
18~30 / 16~30
20
20
20
SIC-37CV-FI30-3
SIC-37CV-FI30-3
SIC-37CV-FI30-3
Cross Flow Fan
Cross Flow Fan
Cross Flow Fan
1/3.74(95)
1/3.94(100)
1/3.94(100)
1250/1080/970
1200/1100/1000
1360/1260/1100
1250/1080/970
1200/1100/1000
1360/1260/1100
36 / 32 / 29
37 / 34 / 31
41 / 39 / 34
Thermistor
Thermistor
Thermistor
0.197(5.0)
0.276(7.0)
0.276(7.0)
20
20
20
2R,15C
2R,15C
2R,15C
1.2
2.3
3.0
33.0*10.6*6.0(840*270*153) 42.9*11.8*7.0(1090*300*180) 42.9*11.8*7.0(1090*300*180)
7(15.4)
13(28.7)
13(28.7)
1/4 (6.35)
1/4 (6.35)
1/4 (6.35)
3/8 (9.52)
1/2 (12.7)
1/2 (12.7)
20
20
20
35.7*13.1*8.8(906*332*223) 45.9*15.2*9.7(1165*387*246) 45.9*15.2*9.7(1165*387*246)
437/906 (432/896)
270/558 (267/552)
270/558 (267/552)
Morning Beige
Morning Beige
Morning Beige

Service Manual 23

Product Specifications
Indoor Unit Type

ARTCOOL DELUXE

Model
Nominal Cooling Capacity
Nominal Heating Capacity
Air Circulation
H/M/L
Setting temperature range(cool/heat)
Fan motor
Output
Model
Fan
Type
No. Used / Diameter
Fan RPM
Cooling(H/M/L)
Heating(H/M/L)
Noise Level (Sound Press,1m) H/M/L
Temperature controller
Coil
Tube Size (OD)
Fins per inch
No. of Rows & Column
Dehumidification Rate
Dimensions (W*H*D)
Net Weight
Piping Connection
Liquid
Gas
Drain hose (ID )
Packing Dimension (W*H*D)
Stuffing Quantity
With(Without) S/Parts
Front Panel Color
"" Position

AMNH07GDZ*0
kcal/h(W)
Btu/h
kcal/h(W)
Btu/h
CMM(CFM)
C
W

EA/inch(mm)
rpm
rpm
dBA
inch(mm)

l/h
inch(mm)
kg(lbs)
inch(mm)
inch(mm)
mm
inch(mm)
20/40ft

AMNH09GDU*0

AMNH12GDU*0

AMNH18GD3*0

AMNH24GD3*0

1764(2051)
2267(2638)
3024(3515)
4536(5275)
5796(6740)
7000
9000
12000
18,000
23,000
2016(2343)
2520(2929)
3326(3867)
4990(5803)
6426(7472)
8000
10000
13200
19,800
25,500
5.5(194)
8.5(300)
9.0(318)
13(459)
14(494)
18~30 / 16~30
18~30 / 16~30
18~30 / 16~30
18~30 / 16~30
18~30 / 16~30
20
20
20
20
20
SIC-37CV-FI30-3
SIC-37CV-FI30-3
SIC-37CV-FI30-3
SIC-37CV-FI30-3
SIC-37CV-FI30-3
Cross Flow Fan
Cross Flow Fan
Cross Flow Fan
Cross Flow Fan
Cross Flow Fan
1/3.43(87)
1/3.43(87)
1/3.43(87)
1/3.74(95)
1/3.74(95)
1150/1032/940
1280/1208/1147
1345/1273/1213
1330/1254/1123
1400/1332/1188
1150/1032/940
1280/1208/1147
1345/1273/1213
1330/1254/1123
1400/1332/1188
31/29/27
33/31/29
35/31/29
39/37/35
43/41/38
Thermistor
Thermistor
Thermistor
Thermistor
Thermistor
0.197(5.0)
0.197(5.0)
0.197(5.0)
0.276(7.0)
0.276(7.0)
19
19
19
20
20
2R,12C
2R,12C
2R,12C
2R,13C
2R,13C
1.0
1.2
1.5
2.0
2.5
35.4*10.7*5.6 (900*272*143) 40.6*11.4*6.0 (1030*290*153)
40.6*11.4*6.0 (1030*290*153) 46.1*24.4*6.81(1170*315*173)" "46.1*24.4*6.81(1170*315*173)
8.1(17.9)
9.5(20.9)
9.5(20.9)
13(28.7)
13(28.7)
1/4 (6.35)
1/4 (6.35)
1/4 (6.35)
1/4 (6.35)
1/4 (6.35)
3/8(9.52)
3/8(9.52)
3/8(9.52)
1/2 (12.7)
1/2 (12.7)
20
20
20
20
20
38.8*14.3*8.7 (985*363*220) 44.0*14.8*8.9 (1117*377*225) 44.0*14.8*8.9 (1117*377*225) "49.4*15.3*10.2(1255*388*258)" "49.4*15.3*10.2(1255*388*258)"
340/720
324/684
324/684
234/495
234/495
R:Mirror,M:Metal,N:Walnut,W;White,B:Blue,C:Cherry

Note : 1. See the page "Combination Table"


2. Due to our policy of innovation some specifications may be changed without notification.

Indoor Unit Type

ART COOL

Model
Rated Cooling Capacity
Rated Heating Capacity
Air Circulation
H/M/L
Setting temperature range
Fan motor
Output
Model
No. of Poles
Input
Running Current
Capacitor
Fan
Type
No. Used / Diameter
Fan RPM
Cooling(H/M/L)
Heating(H/M/L)
Noise Level(Sound Press,1m) H/M/L
Temperature controller
Coil
Tube Size (OD)
Fins per inch
No. of Rows & Column
Dehumidification Rate
Dimensions (W*H*D)
Net Weight
Piping
Liquid
Connection
Gas
Drain hose (ID )
Packing Dimension (W*H*D)
Stuffing Quantity
Without S/Parts
Front Panel Color
"" Position

AMNH096AP*1
kcal/hr(W)
Btu/hr
kcal/hr(W)
Btu/hr
CMM(CFM)
C
W

W
A
F/Vac
EA/inch(mm)
rpm
rpm
dBA
inch(mm)

l/h
inch(mm)
kg(lbs)
inch(mm)
inch(mm)
mm
inch(mm)
20/40ft

Note : 1. See the page "Combination Table"


2. Due to our policy of innovation some specifications may be changed without notification.

24 Multi type Air Conditioner

AMNH126AP*1

2267(2638)
9000
2520(2929)
10000
7.5(264)
18~30 / 16~30
24
SIC-39CV-D828-1
8
18
0.08
Turbo Fan
1/24.32(617.7)
510/350/290
510/350/290
38 / 35 /32
Thermistor
0.197(5.0)
20
2R,20C
1
22.4*22.4*5.4 (570*568*137)
9(19.84)
1/4 (6.35)
3/8 (9.52)
20
25.7*25.2*8.5(653*641*216)
239/539

2772(3224)
12000
3049(3546)
13200
8.5(300)
18~30 / 16~30
24
SIC-39CV-D828-1
8
18
0.08
Turbo Fan
1/24.32(617.7)
560/460/360
560/460/360
43 / 40 / 33
Thermistor
0.197(5.0)
20
2R,20C
1.2
22.4*22.4*5.4 (570*568*137)
9(19.84)
1/4 (6.35)
3/8(9.52)
20
25.7*25.2*8.5(653*641*216)
239/539
M:Metal, B:Blue, D:Wood

Product Specifications
Indoor Unit Type

Ceiling Cassette - 1way

Model

AMNH096TCC0

Rated Cooling Capacity

AMNH126TCC0

2267(2638)
3024(3515)
9000
12000
2520(2929)
3326(3867)
Rated Heating Capacity
10000
13200
9(317)
10(353)
Air Circulation
H/M/L
External Static Pressure
18~30 / 16~30
18~30 / 16~30
Setting temperature range
14
14
Fan motor
Output
AMR-023E7
AMR-023E7
Model
4
4
No. of Poles
50
50
Input
W
0.56
0.56
Running Current
A
0.9/400
0.9/400
Capacitor
F/Vac
Cross Flow Fan Cross Flow Fan
Fan
Type
1/4(102)
1/4(102)
No. Used / Diameter
EA/inch(mm)
900 / 800 / 700 1000 / 900 / 800
Fan RPM
Cooling(H/M/L)
rpm
900 / 800 / 700 1000 / 900 / 800
Heating(H/M/L)
rpm
35 /32 / 28
37 / 33 / 29
Noise Level(Sound Press,1m) H/M/L
dBA
Thermistor
Thermistor
Temperature controller
0.275(7)
0.275(7)
Coil
Tube Size (OD)
inch(mm)
18
18
Fins per inch
2R11C
2R11C
No. of Rows & Column
1.2
1.5
Dehumidification Rate
l/h
33.8*15.3*7(860*390*190)
33.8*15.3*7(860*390*190)
Dimensions (W*H*D)
Indoor
inch(mm)
Panel
inch(mm) 41.3*18.9*1.2(1050*480*30) 41.3*18.9*1.2(1050*480*30)
22(48.5)
22(48.5)
Net Weight
kg(lbs)
1/4 (6.35)
1/4 (6.35)
Piping
Liquid
inch(mm)
3/8(9.52)
3/8(9.52)
Connection
Gas
inch(mm)
32
32
Drain hose (ID )
mm
38.6*10.0*18.1
38.6*10.0*18.1(980*255*460)
Packing Dimension (W*H*D)
inch(mm)
263/539
263/539
Stuffing Quantity
Without S/Parts
20/40ft
kcal/hr(W)
Btu/hr
kcal/hr(W)
Btu/hr
CMM(CFM)
mmAq
C
W

Ceiling Cassette - 4way


AMNH126TEC0

Current
Fan

Coil
Dimensions
(WxHxD)
Weight

Nominal running current


Motor type
Fan type
Motor output x Number of unit
Air flow rate(H/M/L)
Capacitor
Drive
Row x Column x FPI
Body
Decorative panel
Body
Decorative panel

Air filter
Sound level (H/M/L)
Piping
Liquid
connections
Gas
Drain
OD/ID
Dehumidification rate
Safety devices
Temperature sensor
Referigerant
Referigerant control
Connectable outdoor unit
Power and transmission interunit cable

AMNH(C)306TFC0 AMNH(C)366TDC0
9072(10551)
36000
9979(11600)
39600
25/23/21(883/812/742)
18~30 / 16~30
52.5
IC-1630LGPJ
6
175
0.8
4/450
Turbo Fan
1/15.0(382)
550/510/470
550/510/470
40/38/36
Thermistor
0.275(7)
21
2R12C
4
33.0*33.0*11.3(840*840*288)
37.4*37.4*1.2(950*950*30)
32(70.5)
1/4 (6.35)
1/2 (12.7)
32
36.4*13.8*36.4(925*350*925)
30/64(36/72)

Ceilling Cassette - 4way

Model

Heating capacity

AMNH246TFC0

3024(3515)
4536(5275)
6048(7033)
7056(8206)
12000
18000
24000
28000
3326(3867)
4990(5803)
6653(7736)
7761(9027)
13200
19800
26400
30800
11(353)
13(459)
15/14/13(53/494/459)
18(636)
18~30 / 16~30
18~30 / 16~30
18~30 / 16~30
18~30 / 16~30
18.4
22.4
40.3
45
IC-9630LGAE
IC-9630LGAC
OBM-350292
OBM-401592
6
6
6
6
75
90
121
146
0.35
0.75
0.53
0.67
2.5/440
2.5/440
4/440
4/440
Turbo Fan
Turbo Fan
Turbo Fan
Turbo Fan
1/13.0(330)
1/13.0(330)
1/15.0(382)
1/15.0(382)
670 / 620 / 550 720 / 670 / 620
600/540480
660/590/530
670 / 620 / 550 720 / 670 / 620
600/540480
660/590/530
38 / 35 / 32
41 /39 / 37
43/41/39
44/41/39
Thermistor
Thermistor
Thermistor
Thermistor
0.275(7)
0.275(7)
0.275(7)
0.275(7)
19
19
21
21
2R11C
2R11C
2R12C
2R12C
1.2
2.4
3
3.5
22.4*10.5*22.4 (570*269*570) 22.4*10.5*22.4 (570*269*570) 29.3*11.5*29.4 (744*292*744) 29.3*11.5*29.4 (744*292*744)
26.4*26.4*1.2(670*670*30) 26.4*26.4*1.2(670*670*30) 33.5*33.5*1.2(850*850*30) 33.5*33.5*1.2(850*850*30)
19(41.9)
19(41.9)
24(52.9)
24(52.9)
1/4 (6.35)
1/4 (6.35)
1/4 (6.35)
1/4 (6.35)
3/8(9.52)
1/2 (12.7)
1/2 (12.7)
1/2 (12.7)
32
32
32
32
25.2*13.0*25.2(640*330*640) 25.2*13.0*25.2(640*330*640) 32.6*14.4*32.6 (828*365*828) 32.6*14.4*32.6 (828*365*828)
189/378
189/378
84/168
84/168

Indoor Unit Type

Power supply
Cooling capacity

AMNH186TEC0

AMNH09GTEF0[MT10AH NE1]
/V/Hz
kW
Btu/h
kW
Btu/h
A

cmm
cfm
F/Vac
mm
mm(inch)
mm
kg(lbs)
kg(lbs)
dB(A)+3
mm(inch)
mm(inch)
mm
l/h

No.x mm2

AMNH12GTEF0[MT12AH NE1]

AMNH18GTEF0[MT18AH NE1]

AMNH24GTHF0[MT24AH NHO]

1/ 220~240/ 50
2.64
9000
2.93
10000
0.35
BLDC
Turbo Fan
18.4 X 1
8.5/7.5/6.5
300/265/230
Direct Drive
2R x 11C x 18
570*265*570(22.4*10.5*22.4)
670*30*670(26.4*1.2 *26.4)
19(41.9)
3(6.6)
Long Life Filter
33/29/24
6.35 (1/4)
9.52 (3/8)
32/25
1.1

1/ 220~240/ 50
1/ 220~240/ 50
1/ 220~240/ 50
3.52
5.28
7.03
12000
18000
24000
3.87
5.8
7.74
13200
19800
26400
0.35
0.75
0.8
BLDC
BLDC
BLDC
Turbo Fan
Turbo Fan
Turbo Fan
18.4 X 1
22.4 X 1
40.3 X 1
9.5/8/6.5
12/10/9
17/15/13
336/283/230
424/353/318
600/530/459
Direct Drive
Direct Drive
Direct Drive
2R x 11C x 18
2R x 11C x 18
2R x 9C x 18
570*265*570(22.4*10.5*22.4)
570*265*570(22.4*10.5*22.4)
840*840*225 (33.1*33.1*8.8)
670*30*670(26.4*1.2 *26.4)
670*30*670(26.4*1.2 *26.4)
950*950*30 (37.4*37.4*1.2)
19(41.9)
19(41.9)
26(126.5)
3(6.6)
3(6.6)
5(11)
Long Life Filter
Long Life Filter
Long Life Filter
36/34/27
41/35/30
32/29/26
6.35 (1/4)
6.35 (1/4)
6.35 (1/4)
9.52 (3/8)
12.7(1/2)
12.7(1/2)
32/25
32/25
32/25
1.2
2.4
3
Fuse, Thermal Protector for Fan Motor
Thermistor
Thermistor
Thermistor
Thermistor
R410A
R410A
R410A
R411A
LEV(in Outdoor unit or BD) LEV(in Outdoor unit or BD) LEV(in Outdoor unit or BD) LEV(in Outdoor unit or BD )
Multi F /F DX series
Multi F /F DX series
Multi F /F DX series
Multi F /F DX series
4*0.75
4*0.75
4*0.75
4*0.75

Service Manual 25

Product Specifications

Indoor Unit Type

Ceiling Cassette - 1way

Model
Rated Cooling Capacity
Rated Heating Capacity

AMNH09GTCC0
kcal/hr(W)
Btu/hr
kcal/hr(W)
Btu/hr
CMM(CFM)
mmAq
C
W

Air Circulation
H/M/L
External Static Pressure
Setting temperature range
Fan motor
Output
Model
No. of Poles
Input
W
Running Current
A
Capacitor
F/Vac
Fan
Type
No. Used / Diameter
EA/inch(mm)
Fan RPM
Cooling(H/M/L)
rpm
Heating(H/M/L)
rpm
Noise Level(Sound Press,1m) H/M/L
dBA
Temperature controller
Coil
Tube Size (OD)
inch(mm)
Fins per inch
No. of Rows & Column
Dehumidification Rate
l/h
Dimensions (W*H*D)
Indoor
inch(mm)
Panel
inch(mm)
Net Weight
kg(lbs)
Piping
Liquid
inch(mm)
Connection
Gas
inch(mm)
Drain hose (ID )
mm
Packing Dimension (W*H*D)
inch(mm)
Stuffing Quantity
Without S/Parts
20/40ft

26 Multi type Air Conditioner

2267(2638)
9000
2520(2929)
10000
9(317)
18~30 / 16~30
14
AMR-023E7
4
50
0.56
0.9/400
Cross Flow Fan
1/4(102)
900 / 800 / 700
900 / 800 / 700
35 /32 / 28
Thermistor
0.275(7)
18
2R11C
1.2
33.8*15.3*7(860*390*190)
41.3*18.9*1.2(1050*480*30)
22(48.5)
1/4 (6.35)
3/8(9.52)
32
38.6*10.0*18.1
263/539

AMNH12GTCC0
3024(3515)
12000
3326(3867)
13200
10(353)
18~30 / 16~30
14
AMR-023E7
4
50
0.56
0.9/400
Cross Flow Fan
1/4(102)
1000 / 900 / 800
1000 / 900 / 800
37 / 33 / 29
Thermistor
0.275(7)
18
2R11C
1.5
33.8*15.3*7(860*390*190)
41.3*18.9*1.2(1050*480*30)
22(48.5)
1/4 (6.35)
3/8(9.52)
32
38.6*10.0*18.1(980*255*460)
263/539

Product Specifications
Indoor Unit Type

Ceiling Cassette - 4way

Model
Nominal Cooling Capacity
Nominal Heating Capacity
Air Circulation
H/M/L
Setting temperature range(cool/heat)
Output
Fan motor
Model
No. of Poles
Input
Running Current
Capacitor
Type
Fan
No. Used / Diameter
Noise Level
H/M/L
(Sound Press,1.5m)
Temperature controller
Tube Size (OD)
Coil
Fins per inch
No. of Rows & Column
Dehumidification Rate
Indoor Unit
Dimensions (W*H*D)
Decorative Panel
Body
Net Weight
Panel
Liquid
Piping Connection
Gas
Drain hose (ID )
Packing Dimension
Indoor Unit
(W*H*D)
Decorative Panel
Stuffing Quantity
With(Without) S/Parts

AMNH096TEC0

EA/inch(mm)

2267(2638)
9000
2520(2929)
10000
9.5/8/7(336/283/247)
18~30 / 16~30
18.4
IC-9630LGAE
6
75
0.35
2.5/440
Turbo Fan
1/13.0(330)

dBA

38 / 35 / 32

kcal/h(W)
Btu/h
kcal/h(W)
Btu/h
CMM(CFM)
C
W

W
A
F/Vac

Thermistor
0.275(7)
19
2R11C
1.2
22.4*10.5*22.4 (570*269*570)
26.4*1.2*26.4 (670*30*670)
19(41.9)
3(6.6)
1/4 (6.35)
3/8 (9.52)
1.26(32)
"25.2*13.0*25.2 (640*330*640)
"29.5*3.1*29.5 (750*80*750)
189/378(189/378)

inch(mm)

l/h
inch(mm)
inch(mm)
kg(lbs)
kg(lbs)
inch(mm)
inch(mm)
inch(mm)
inch(mm)
inch(mm)
20/40ft

Notes : 1. Capacities are based on the following conditions:


Cooling: - Indoor Temperature 27C(80.6F) DB /19C(66.2F) WB
- Outdoor Temperature 35C(95F) DB /24C(75.2F) WB
- Interconnecting Piping Length 7.5m
- Level Difference of Zero.
Heating: - Indoor Temperature 20C(68F) DB / 15C(59F) WB
- Outdoor Temperature 7C(44.6F) DB / 6C(42.8F) WB
- Interconnecting Piping Length 7.5 m
- Level Difference of Zero.
2. Capacities are Net Capacities.
3. Due to our policy of innovation some specifications may be changed without notification.
4. : See the page "Combination Table"
Indoor Unit Type

Ceiling Concealed Duct

Model
Rated Cooling Capacity
Rated Heating Capacity
Air Circulation
H/M/L
External Static Pressure
Setting temperature range
Fan motor
Output
Model
No. of Poles
Input
Running Current
Capacitor
Fan
Type
No. Used / Diameter
Fan RPM
Cooling(H/M/L)
Heating(H/M/L)
Noise Level(Sound Press,1m) H/M/L
Temperature controller
Coil
Tube Size (OD)
Fins per inch
No. of Rows & Column
Dehumidification Rate
Dimensions (W*H*D)
Net Weight
Piping
Liquid
Connection
Gas
Drain hose (ID )
Packing Dimension (W*H*D)
Stuffing Quantity
Without S/Parts
Front Panel Color
"*" Position

AMNH096BTG0
kcal/hr(W)
Btu/hr
kcal/hr(W)
Btu/hr
CMM(CFM)
mmAq
C
W

W
A
F/Vac
EA/inch(mm)
rpm
rpm
dBA
inch(mm)

l/h
inch(mm)
kg(lbs)
inch(mm)
inch(mm)
mm
inch(mm)
20/40ft

AMNH126BTG0

AMNH186BTG0

2268(2637)
3024(3516)
4536(5274)
9000
12000
18000
2520(2930)
3326(3868)
4990(5802)
10000
13000
19800
8/7/6(282/246/211)
10/9/8(352/317/282)
13.5/12/10(477/424/353)
2
2
2
18~30 / 16~30
18~30 / 16~30
18~30 / 16~30
35
35
47
YDK110-35-4L
YDK110-35-4L
YSK110-70-4L
4
4
4
68
68
126
0.31
0.31
0.58
2.5/400
2.5/400
2.5/370
Sirocco Fan
Sirocco Fan
Sirocco Fan
1/7.8(197)
1/7.8(197)
2/7.8(197)
930/840/810
950/850/780
1000/900/800
930/840/810
950/850/780
1000/900/800
34/32/30
37/34/31
38/36/34
Thermistor
Thermistor
Thermistor
0.276(7.0)
0.276(7.0)
0.276(7.0)
18
18
18
2R,12C
3R,12C
2R, 12C
1
1.2
2
25.6*9.0*21.1(650*230*535) 25.6*9.0*21.1(650*230*535) 39.4*9.0*21.1(1000*230*535)
22(48.5)
22(48.5)
29(63.9)
1/4 (6.35)
1/4 (6.35)
1/4 (6.35)
3/8 (9.52)
3/8 (9.52)
1/2 (12.7)
25.4
25.4
25.4
29.9*24.6*11.8(760*625*300) 29.9*24.6*11.8(760*625*300) 29.9*24.6*11.8(760*625*300)
172/356
172/356
123/251
-

AMNH096BPA0

AMNH126BPA0

2268(2637)
9000
2520(2930)
10000
11.5/10/8.5
4
18~30
118
IC-13450LG31A
4
180
4.3
6/370
Sirocco Fan
1/177
1125/990/870
1125/900/870
38/36/34
Thermistor
0.276(7.0)
18
2R14C
1.6
750*300*580(695*56.5*396)
30(6)
1/4(6.35)
3/8(9.52)
25.4(OD)
845*370*760(735*90*435)
228/468
NOBEL WHITE

3024(3516)
12000
3326(3868)
13200
11.5/10/8.5
4
18~30
118
IC-13450LG31A
4
180
4.3
6/370
Sirocco Fan
1/177
1125/990/870
1125/990/870
38/36/34
Thermistor
0.276(7.0)
18
3R14C
2
750*300*580(695*56.5*396)
30(6)
1/4(6.35)
3/8(9.52)
25.4(OD)
845*370*760(735*90*435)
228/468
NOBEL WHITE

Note : 1. See the page "Combination Table"


2. Due to our policy of innovation some specifications may be changed without notification.

Service Manual 27

Product Specifications

Indoor Unit Type

Ceiling Concealed Duct

Model
Rated Cooling Capacity
Rated Heating Capacity
Air Circulation
H/M/L
External Static Pressure
Setting temperature range
Fan motor
Output
Model
No. of Poles
Input
Running Current
Capacitor
Fan
Type
No. Used / Diameter
Fan RPM
Cooling(H/M/L)
Heating(H/M/L)
Noise Level(Sound Press,1m) H/M/L
Temperature controller
Coil
Tube Size (OD)
Fins per inch
No. of Rows & Column
Dehumidification Rate
Dimensions (W*H*D)
Net Weight
Piping
Liquid
Connection
Gas
Drain hose (ID )
Packing Dimension (W*H*D)
Stuffing Quantity
Without S/Parts

AMNH186BHA0
kcal/hr(W)
Btu/hr
kcal/hr(W)
Btu/hr
CMM(CFM)
mmAq
C
W

W
A
F/Vac
EA/inch(mm)
rpm
rpm
dBA
inch(mm)

l/h
inch(mm)
kg(lbs)
inch(mm)
inch(mm)
mm
inch(mm)
20/40ft

Indoor Unit Type

Rated Heating Capacity


Air Circulation
H/M/L
External Static Pressure
Setting temperature range
Fan motor
Output
Model
No. of Poles
Input
Running Current
Capacitor
Fan
Type
No. Used / Diameter
Fan RPM
Cooling(H/M/L)
Heating(H/M/L)
Noise Level(Sound Press,1m) H/M/L
Temperature controller
Coil
Tube Size (OD)
Fins per inch
No. of Rows & Column
Dehumidification Rate
Dimensions (W*H*D)
Net Weight
Piping
Liquid
Connection
Gas
Drain hose (ID )
Packing Dimension (W*H*D)
Stuffing Quantity
Without S/Parts

AMNH096VEA0
kcal/hr(W)
Btu/hr
kcal/hr(W)
Btu/hr
CMM(CFM)
mmAq
C
W

AMNH(C)366BGA0

W
A
F/Vac
EA/inch(mm)
rpm
rpm
dBA
inch(mm)

l/h
inch(mm)
kg(lbs)
inch(mm)
inch(mm)
mm
inch(mm)
20/40ft

AMNH126VEA0

AMNH186VBA0

AMNH246VBA0

2268(2637)
3024(3516)
4536(5274)
6048(7032)
9000
12000
18000
24000
2520(2930)
3326(3867)
4990(5801)
6350(7384)
10000
132000
19800
25200
7.8/6.4/5.0(276/226/177)
10.0/8.3/6.5(353/293/230)
135./12/11(477/424/388)
15/13.5/12(530/477/424)
18-30/16-30
18-30/16-30
18~30 / 16~30
18~30 / 16~30
14.5
17.5
30
35
IC-18422LG31B
IC-18422LG31A
IC-9430LGCM
IC-9430LGCM
4
4
4
4
35
43
53
63
0.18
0.23
0.23
0.27
1.5/370
1.5/370
1.5/370
1.5/370
Cross Flow Fan
Cross Flow Fan
Cross Flow Fan
Cross Flow Fan
1/3.7(95)
1/3.7(95)
1/3.1(80)
1/3.1(80)
960/870/760
1240/1120/900
1090/990/890
1160/1060/960
960/870/760
1240/1120/900
1090/990/890
1160/1060/960
36/32/28
40/36/31
43 / 40 / 37
45 / 42 / 39
Thermistor
Thermistor
Thermistor
Thermistor
0.197(5)
0.197(5)
0.275(7)
0.275(7)
20
20
18
20
2R 12C
2R 12C
2R 12C
2R 14C
1
1.2
2.3
3.2
35.4*7.9*19.3 (900*200*490)
35.4*7.9*19.3 (900*200*490) 47.24*24.21*8.07(1200*615*205) 47.24*24.21*8.07(1200*615*205)
12(26.5)
12(26.5)
30(66.1)
30(66.1)
1/4 (6.35)
1/4 (6.35)
1/4(6.35)
1/4(6.35)
3/8 (9.52)
3/8 (9.52)
1/2(12.7)
1/2(12.7)
20
20
20
20
38.2*11.2*22.2 (970*285*565) 38.2*11.2*22.2 (970*285*565)
50*10.9*27(1272*278*686)
50*10.9*27(1272*278*686)
189/383
189/383
102/219
102/219

Note : 1. See the page "Combination Table"


2. Due to our policy of innovation some specifications may be changed without notification.

28 Multi type Air Conditioner

AMNH(C)306BGA0

Ceiling & Floor(Convertible)

Model
Rated Cooling Capacity

AMNH(C)246BHA0

4536(5275)
6048(7034)
7560(8792)
9072(10551)
18000
24000
30000
36000
4990(5803)
6653(7737)
8316(9671)
9979(11606)
19800
26400
33000
39600
16.5/14.5/13(583/512/459)
18/16.5/14(636/583/494)
28/25/23(989/883/812)
32/29/26.5(1130/1024/936)
8
8
8
8
18~30 / 16~30
18~30 / 16~30
18~30 / 16~30
18~30 / 16~30
118
118
124
272
IC-13450LG13C
IC-13450LG13C
IC-13450LG13J
IC-13450LG13A
4
4
4
4
180
180
250
323
0.92
0.92
1.1
1.42
6/370
6/370
6/370
6/370
Sirocco Fan
Sirocco Fan
Sirocco Fan
Sirocco Fan
2/6.97(177)
2/6.97(177)
2/6.97(177)
2/6.97(177)
1356/-/1270
1417/1350/1255
1415/1360/1290
1415/1360/1290
1356/-/1270
1417/1350/1255
1415/1360/1290
1415/1360/1290
36/34/32
37/35/33
40/38/36
42/40/38
Thermistor
Thermistor
Thermistor
Thermistor
0.275(7)
0.275(7)
0.275(7)
0.275(7)
21
21
21
21
3R10C
3R10C
3R 12C
3R 12C
2.0
2.5
3
3.5
34.6*10.2*17.7 (880*260*450) 34.6*10.2*17.7 (880*260*450) 46.4*11.7*17.7(1180*298*450) 46.4*11.7*17.7(1180*298*450)
35(77.2)
35(77.2)
38(83.8)
38(83.8)
1/4(6.35)
1/4(6.35)
1/4(6.35)
1/4(6.35)
1/2(12.7)
1/2(12.7)
5/8(15.88)
5/8(15.88)
25.4(OD)
25.4(OD)
25.4(OD)
25.4(OD)
44.7*13.4*23.0(1135*340*585) 44.7*13.4*23.0(1135*340*585) 18.5*14.8*23.0(1435*375*585) 18.5*14.8*23.0(1435*375*585)
120/252
120/252
95/191
95/191

Product Specifications
Outdoor Unit - Multiple piping models
A2UW146FA0

A2UW146FA1

A2UW186FA0

A3UW186FA0

A3UW246FA0

A4UW246FA0

kcal/hr

1159~4031

1159~4031

1159~5443

1159~5443

1159~7257

1159~7257

1159~9072

1348~4688

1348~4688

1348~6330

1348~6330

1348~8,440

1348~8,440

1348~10549

Model
Cooling Capacity

Heating Capacity

A4UW306FA0

Btu/hr

4600~16000

4600~16000

4600~21600

4600~21600

4600~28800

4600~28800

4600~36000

kcal/hr

1210~4535

1210~4535

1210~6249

1210~6249

1210~8063

1210~8063

2116~10332

1407~5274

1407~5274

1407~7268

1407~7268

1407~9376

1407~9376

2461~12014

Btu/hr

4800~18000

4800~18000

4800~24800

4800~24800

4800~32000

4800~32000

8,400~41,000

Input

Cooling/Heating

Running Current

Cooling/Heating

1.6~6.5/2.0~5.8

1.6~6.5/2.0~5.8

3.5~11.5/4~12

3.5~11.5/4~12

Starting Current

Cooling/Heating

28

28

28

Power Supply

,V,Hz

1,220~240,50

1,220~240,50

1,220~240,50

1,220~240,50

1,220~240,50

1,220~240,50

1,220~240,50

Power Factor

94~98

94~98

94~98

94~98

94~98

94~98

95~98

Max. Number of Connectable Indoor Units

e-Scroll

Rotary

e-Scroll

e-Scroll

e-Scroll

e-Scroll

e-Scroll

380~1450/450~1350 380~1450/450~1350 420~2400/480~2600 420~2400/480~2600 440~2970/560~2950 440~2970/560~2950 450~3580/620~3580


3.08~13.0/4.6~12.9 3.08~13.0/4.6~12.9 3.2~15.7/4.6~15.7

Compressor

Type

(Invertor)

O.L.P Type(model name)

Compressor

Type

Rotary

Rotary

Rotary

(Constant)

O.L.P Type(model name)

Refrigerant

Charge

g(oz), type

Type
Control
Coil

Tube Size (OD)

inch(mm)

Fins per inch


No. of Rows & Column/No.
Fan Motor

Model

Fan

Discharge
Air Circulation
Noise Level(Sound Press,1m)

1650(59.97) at 7.5m

MRA99150-9090 MRA99150-9090
1950(68.78) at 7.5m

1950(68.78) at 7.5m

2500(88.18) at 7.5m

INTERNAL

R-410A

R-410A

R-410A

R-410A

R-410A

R-410A

R-410A

L.E.V

L.E.V

L.E.V

L.E.V

L.E.V

L.E.V

L.E.V

0.276(7.0)

0.276(7.0)

0.276(7.0)

0.276(7.0)

0.276(7.0)

0.276(7.0)

0.276(7.0)

18

18

18

18

18

18

18

1R,28C

1R,28C

2R,28C

2R,28C

2R,36C

2R,36C

2R,48C
IC9625LGSY

IC28640LG28S

IC28640LG28J

IC28640LG28J

120

120

130

130

65 * 2

F/Vac

6/370

6/370

6/370

6/370

6/370

6/370

2.0/370

Propeller

Propeller

Propeller

Propeller

Propeller

Propeller

Propeller

EA/inch(mm)

1/18.1(460)

1/18.1(460)

1/18.1(460)

1/18.1(460)

1/18.1(460)

1/18.1(460)

2/16.5(420)

IC28640LG28S IC28640LG28S IC28640LG28S

Side / Top

Side Discharge

Side Discharge

Side Discharge

Side Discharge

Side Discharge

Side Discharge

Side Discharge

CMM(CFM)

49(1730)

49(1730)

49(1730)

49(1730)

53(1872)

53(1872)

31(1094)*2

dBA

50/47

50/47

51/48

51/48

51/48

51/48

50/46

Invertion cycle

Invertion cycle

Invertion cycle

Invertion cycle

Invertion cycle

Invertion cycle

Invertion cycle

Defrosting
SVC Valve

1650(59.97) at 7.5m

120

Type
No. Used / Diameter

1650(59.97) at 7.5m

120

Output
Capacitor

1650(59.97) at 7.5m

Liquid

inch(mm)

1/4 (6.35)*2EA

1/4 (6.35)*2EA

1/4 (6.35)*2EA

1/4 (6.35)*3EA

1/4 (6.35)*3EA

1/4 (6.35)*4EA

1/4 (6.35)*4EA

Gas

inch(mm)

3/8 (9.52)*2EA

3/8 (9.52)*2EA

3/8 (9.52)*2EA

3/8 (9.52)*3EA

3/8 (9.52)*3EA

3/8 (9.52)*4EA

3/8 (9.52)*4EA

inch(mm)

34.3*31.5*12.6 (870*800*320)

34.3*31.5*12.6 (870*800*320)

34.3*31.5*12.6 (870*800*320)

34.3*31.5*12.6 (870*800*320)

34.3*31.5*12.6 (870*808*320)

34.3*31.5*12.6 (870*808*320) 34.3*31.5*12.6 (870*1038*320)

Dimensions (W*H*D)

kg(lbs)

52(115)

52(115)

57(125.6)

75(165)

75(165)

75(165)

84(185)

Power Supply Cable

No.* mm2

3*3.5

3*3.5

3*3.5

3*3.5

3*2.5

3*2.5

3*2.5

Interunit Cable

No.* mm2

Net Weight

4*0.75 (Includes earth) 4*0.75 (Includes earth) 4*0.75 (Includes earth) 4*0.75 (Includes earth) 4*0.75 (Includes earth) 4*0.75 (Includes earth) 4*0.75 (Includes earth)

Max. Interunit

Total of Each Room

40

40

40

40

50

50

70

Piping Length

For One Room

25

25

25

25

25

25

25

Max. Installation

Indoor Unit~Outdoor Unit

15

15

15

15

15

15

15

Height Difference

Indoor Unit~Indoor Unit

7.5

7.5

7.5

7.5

7.5

7.5

7.5

inch(mm)

34.2*25.8*12.6(870*655*320)

34.2*25.8*12.6(870*655*320)

34.2*25.8*12.6(870*655*320)

34.2*25.8*12.6(870*655*320)

20/40ft

81/171

81/171

81/171

81/171

Packing Dimension (W*H*D)


Stuffing Quantity

Without S/Parts

40.1*34.2*17.3 (1020*870*440) 40.1*34.2*17.3 (1020*870*440) 40.1*34.2*17.3 (1045*1140*440)


54/114

54/114

51/111

Notes: 1. Capacities are based on the following conditions:


Cooling: - Indoor Temperature 27C(80.6F) DB /19C(66.2F) WB
Heating: - Indoor Temperature 20C(68F) DB / 15C(59F) WB
- Outdoor Temperature 35C(95F) DB /24C(75.2F) WB
- Outdoor Temperature 7C(44.6F) DB / 6C(42.8F) WB
- Interconnecting Piping Length 7.5m
- Interconnecting Piping Length 7.5 m
- Level Difference of Zero.
- Level Difference of Zero.
2. Capacities are Net Capacities.
3. : See the page "Combination Table"
4. Due to our policy of innovation some specifications may be changed without notification.

Service Manual 29

Product Specifications
Outdoor Unit - Multiple piping models
Model

A2UW146FA2

4600-14000-16000
1348-4100-4688
1159-3526-4031
4800-16000-18000
Heating Capacity
1407-4700-5274
1210-4042-4535
380-1280-1500
Input
Cooling
450-1220-1262
Heating
1.7-5.7-6.9
Running Current
Cooling
2.1-5.9-6.9
Heating
8
Starting Current
Cooling/Heating
1,220~240,50
Power Supply
94~98
Power Factor
2
Max. Number of Connectable Indoor Units
Rotary
"Compressor(Inverter)" Type
5RS102XAA
Model
DC Brushless Motor
Motor Type
1
Quantity
Ea
980
Motor Input
W
320
Oil Charge
cc
RB68A
Oil Type
O.L.P Type(model name)
"Compressor(Constant)" Type
Model
Motor Type
Quantity
Ea
Motor Input
W
Oil Charge
cc
Oil Type
O.L.P Type(model name)
950(33.5) "at 7.5m"
Refrigerant charge
Charge
g(oz)
R410A
Type
L.E.V
Control
0.276(7.0)
Coil
Tube Size (OD)
inch(mm)
18
Fins per inch
2R,24C
No. of Rows & Column/No.
OBM-3018P2
Fan motor
Model
47
Output
W
2.0/400
Capacitor
F/Vac
Propeller
Fan
Type
1/16.5(420)
No. Used / Diameter
EA/inch(mm)
Side Discharge
Discharge
Side / Top
35(1236)
Air Circulation
Outdoor
CMM(CFM)
51
Noise Level(H/L)
Sound Press,1m
dB(A)1
Invertion cycle
Defrosting
1/4 (6.35)*2EA
SVC Valve
Liquid
inch(mm)
3/8 (9.52)*2EA
Gas
Dimensions
W*H*D
inch(mm) 30.3*21.3*10 (770*540*245)
37(81.6)
Net Weight
Outdoor
kg(lbs)
3*2.5
Power Supply Cable
No.*mm2
4*0.75 (Includes earth)
Interunit Cable
30
Max. Interunit Piping Length Total of Each Room
m
20
For One Room
m
15
"Max. Installation
Indoor Unit~Outdoor Unit
m
7.5
Height Difference"
Indoor Unit~Indoor Unit
m
36.2*22.8*14.2(920*580*360)
Packing Dimension
W*H*D
inch(mm)
AMNH096LRL0+AMNH126LRL0
Testing Combinations
144/312
Stuffing Quantity
20/40ft
Cooling Capacity

Btu/hr
W
kcal/hr
Btu/hr
W
kcal/hr
W
W
A
A
A
,V,Hz
%

A2UW166FA0
4600-16000-17500
1348-4688-5128
1159-4031-4410
4800-18000-19500
1407-5274-5714
1210-4535-4914
380-1380-1600
450-1400-1550
1.7-6.3-7.3
2.1-6.4-7.1
8
1,220~240,50
94~98
2
Twin Rotary
GKT141NAA
Synchronous Reluctance Motor
1
1451
570
FVC68D
950(33.5) "at 7.5m"
R410A
L.E.V
0.276(7.0)
18
2R,24C
OBM-3018P2
47
2.0/400
Propeller
1/16.5(420)
Side Discharge
35(1236)
51
Invertion cycle
1/4 (6.35)*2EA
3/8 (9.52)*2EA
30.3*21.3*10 (770*540*245)
37(81.6)
3*2.5
4*0.75 (Includes earth)
30
20
15
7.5
36.2*22.8*14.2(920*580*360)
AMNH126LRL0+AMNH126LRL0
144/312

A2UW166FA1

A3UW186FA1

4600-16000-17500
4600-18000-21600
1348-4688-5128
1348-5300-6329
1159-4031-4410
1159-4558-5443
4800-18000-19500
4800-21600-24800
1407-5274-5714
1407-6300-7268
1210-4535-4914
1210-5418-6249
380-1380-1600
480-1550-2350
450-1400-1550
550-1650-2320
1.7-6.3-7.3
2.3-6.9-10.4
2.1-6.4-7.1
2.6-7.3-10.3
8
8
1,220~240,50
1,220~240,50
94~98
94~98
2
3
eScroll
Twin Rotary
5CS130X
GKT141NAA
DC Brushless Motor
Synchronous Reluctance Motor
1
1
1405
1451
480
570
RB68A
FVC68D
950(33.5) "at 7.5m"
1550(54.7) "at 7.5m"
R410A
R410A
L.E.V
L.E.V
0.276(7.0)
0.276(7.0)
18
18
2R,24C
2R,28C
OBM-3018P2
IC28640LG28S
47
120
2.0/400
6/370
Propeller
Propeller
1/16.5(420)
1/18.1(460)
Side Discharge
Side Discharge
35(1236)
53(1766)
51
51/45
Invertion cycle
Invertion cycle
1/4 (6.35)*2EA
1/4 (6.35)*3EA
3/8 (9.52)*2EA
3/8 (9.52)*3EA
30.3*21.3*10 (770*540*245) 34.3*25.8*12.6 (870*655*320)
37(81.6)
52(115)
3*2.5
3*2.5
4*0.75 (Includes earth)
4*0.75 (Includes earth)
30
40
20
25
15
15
7.5
7.5
36.2*22.8*14.2(920*580*360) 40.2*28.1*17.3 (1020*715*440)
AMNH126LRL0+AMNH126LRL0 AMNH096LRL0*2 + AMNH126LRL0
144/312
0

Notes: 1. Capacities are based on the following conditions:


Cooling: - Indoor Temperature 27C(80.6F) DB /19C(66.2F) WB
Heating: - Indoor Temperature 20C(68F) DB / 15C(59F) WB
- Outdoor Temperature 35C(95F) DB /24C(75.2F) WB
- Outdoor Temperature 7C(44.6F) DB / 6C(42.8F) WB
- Interconnecting Piping Length 7.5m
- Interconnecting Piping Length 7.5 m
- Level Difference of Zero.
- Level Difference of Zero.
2. Capacities are Net Capacities.
3. : See the page "Combination Table"
4. Due to our policy of innovation some specifications may be changed without notification.

30 Multi type Air Conditioner

Product Specifications
Outdoor Unit - Distributor type models
Model
Cooling Capacity

Heating Capacity

Input
Cooling/Heating
Running Current
Cooling/Heating
Starting Current
Cooling/Heating
Power Supply
Power Factor
Max. Number of Connectable Indoor Units
Compressor
Type
(Invertor)
O.L.P Type(model name)
Compressor
Type
(Constant-1)
O.L.P Type(model name)
Compressor
Type
(Constant-2)
O.L.P Type(model name)
Refrigerant charge
Charge
Type
Control
Coil
Tube Size (OD)
Fins per inch
No. of Rows & Column/No.
Fan motor
Model
Output
Capacitor
Fan
Type
No. Used / Diameter
Discharge
Air Circulation
Outdoor
Noise Level(H/L)
Sound Press,1m
Defrosting
SVC Valve
Liquid
Gas
Dimensions
W*H*D
Net Weight
Outdoor
Power Supply Cable
Interunit Cable
Max. Interunit
Total Piping
Piping Length
Total Main Piping
Total Branch Piping
For One Room
Max. Installation
Indoor Unit~Outdoor Unit
Height Difference
Indoor Unit~Indoor Unit
Packing Dimension
W*H*D
Stuffing Quantity
Without S/Parts

Btu/h
W
kcal/h
Btu/h
W
kcal/h
W
A
A
,V,Hz
%

g(oz)

inch(mm)

W
F/Vac
EA/inch(mm)
Side / Top
CMM(CFM)
dB(A)1
inch(mm)
inch(mm)
inch(mm)
kg(lbs)
No.* mm2
No.* mm2
m
m
m
m
m
m
inch(mm)
20/40ft

A6UW406FA0
5000~48000
1465~14067
1260~12095
5500~53000
1612~15533
1386~13356
600~4980/950~4810
2.9~22.0/4.6~21.5
67
1,220~240,50
91 ~ 98
6
e-Scroll
Rotary
Internal
4100(144.6) "at 5m"
R410A
L.E.V
0.276(7.0)
18
2R,52C
IC28640LG28J
120 * 2
6/370
Propeller
2/18.1(460)
Side Discharge
53(1872) *2
58/54
Invertion cycle
3/8 (9.52)
3/4 (19.05)
35.4*45.8*14.5 (900*1,165*370)
105(231)
3*5.0
4*0.75 (Includes earth)
100
50
50
15
30
10
41.7*48.0*18.3(1060*1220*465)
27/55

A7UW486FA0
5000~57600
1465~16878
1260~14515
5800~63600
1700~18636
1462~16027
750~5800/1450~5430
3.4~26.0/6.6~24.3
43
1,220~240,50
90 ~ 97
7
e-Scroll
Rotary
Internal
Rotary
Internal
7100(250.4) "at 5m"
R410A
L.E.V
0.276(7.0)
18
2R,53C*2
ARE676E01
270
10/370
Propeller
1/20.7(526)
Top Discharge
90(3179)
59/56
Invertion cycle
3/8 (9.52)
3/4 (19.05)
31.7*59.5*28.7 (806*1,512*730)
142(312)
3*5.0
4*0.75 (Includes earth)
110
50
60
15
30
10
33.9*61.0*28.7(860*1,550*730)
20/42

A8UW566FA0
5000~67200
1465~19691
1260~16934
5800~75600
1700~22152
1462~19051
750~6600/1550~6800
3.4~29.6/7.1~30.5
74
1,220~240,50
90 ~ 97
8
e-Scroll
Rotary
Internal
Rotary
Internal
7100(250.4) "at 5m"
R410A
L.E.V
0.276(7.0)
18
2R,53C*2
ARE676E01
270
10/370
Propeller
1/20.7(526)
Top Discharge
90(3179)
59/56
Invertion cycle
3/8 (9.52)
3/4 (19.05)
31.7*59.5*28.7 (806*1,512*730)
148(326)
3*5.0
4*0.75 (Includes earth)
120
50
70
15
30
10
33.9*61.0*28.7(860*1,550*730)
20/42

Notes: 1. Capacities are based on the following conditions:


Cooling: - Indoor Temperature 27C(80.6F) DB /19C(66.2F) WB
Heating: - Indoor Temperature 20C(68F) DB / 15C(59F) WB
- Outdoor Temperature 35C(95F) DB /24C(75.2F) WB
- Outdoor Temperature 7C(44.6F) DB / 6C(42.8F) WB
- Interconnecting Piping Length 7.5m
- Interconnecting Piping Length 7.5 m
- Level Difference of Zero.
- Level Difference of Zero.
2. Capacities are Net Capacities.
3. : See the page "Combination Table"
4. Due to our policy of innovation some specifications may be changed without notification.

Service Manual 31

Product Specifications
LG Branch Distributor
Connectable Indoor Units
Casing color
Powre Source
Power Consumption
Runing Current
Dimensions
Packing Dimension
Net Weight
Connecting Cable
Piping Connection
(To Outdoor Unit)
Piping Connection
(To Indoor Unit)
Piping length
Piping Elevation
Drain hose
Heat Insulation
Accessories

PMBD3640

Model
Number of Indoor Units
Capacity

W*H*D
W*H*D
Direction Indoor Unit
Direction Outdoor Unit
Liquid
Gas
Liquid
Gas

W
A
inch(mm)
inch(mm)
kg
No. * mm2
No. * mm2
inch(mm)
inch(mm)
inch(mm)
inch(mm)
m
m

1~4
7k/9k/12k/18k/24k
Paintingless
1 , 50/60Hz ,220~240/220V
10
0.05
11.9*5.6*9.9(302*143*252)
16.6*8.0*11.8(422*202*300)
5.0
4*0.75 (Includes earth)
4*0.75 (Includes earth)
3/8 (9.52)
3/4(19.05)
1/4 (6.35)*4EA
3/8 (9.52)*4EA
-

EA
EA
EA

4
8
1

Btu/h

Hanger
Screw
Manual

PMBD3630

Note :
1. BD unit or Indoor Unit Max. Height - BD unit or Indoor Unit Min. Height - Max.10m
Set up the BD unit and Indoor Unit in 15m.
2. The piping connection must be suit the piping sizes of the indoor unit which will be connected.
(If need, use the connector which is included in the indoor unit)
3. The BD should be installed inside the building.

32 Multi type Air Conditioner

PMBD3620

1~3
1~2
7k/9k/12k/18k/24k
7k/9k/12k/18k/24k
Paintingless
Paintingless
1 , 50/60Hz ,220~240/220V 1 , 50/60Hz ,220~240/220V
10
10
0.05
0.05
11.9*5.6*9.9(302*143*252)
11.9*5.6*9.9(302*143*252)
16.6*8.0*11.8(422*202*300)
16.6*8.0*11.8(422*202*300)
4.9
4.8
4*0.75 (Includes earth)
4*0.75 (Includes earth)
4*0.75 (Includes earth)
4*0.75 (Includes earth)
3/8 (9.52)
3/8 (9.52)
3/4(19.05)
3/4(19.05)
1/4 (6.35)*3EA
1/4 (6.35)*2EA
3/8 (9.52)*3EA
3/8 (9.52)*2EA
Unusable
Both Liquid and Gas pipes
4
4
8
8
1
1

PMBD7230

1~3
18k/24k/30k/36k
Paintingless
1 , 50/60Hz ,220~240/220V
10
0.05
11.9*5.6*9.9(302*143*252)
16.6*8.0*11.8(422*202*300)
5.0
4*0.75 (Includes earth)
4*0.75 (Includes earth)
3/8 (9.52)
3/4(19.05)
1/4 (6.35)*3EA
1/2 (12.7), 3/8 (15.88)*2EA
-

4
8
1

Installation

Installation
Read completely, then follow step by step.

Select the best location of indoor unit


1. Split Type Indoor Unit

Front

There should not be any heat source or steam near the

unit.
There should not be any obstacles to prevent the air
circulation.
A place where air circulation in the room will be good.
A place where drainage can be easily obtained.
A place where noise prevention is taken into consideration.
Do not install the unit near the door way.
Ensure the spaces indicated by arrows from the wall,
ceiling, fence, or other obstacles.

Left
Rear left
Down right
Right

Rear right

Connecting
cable

Drain hose

2. Art Cool Type Indoor Unit


Do not have any heat or steam near the unit.
Select a place where there are no obstacles in front
of the unit.
Make sure that condensation drainage can be conveniently routed away.
Do not install near a doorway.
Ensure that the space around the left and right of the
unit is more than 50cm. The unit should be installed
as high on the wall as possible, allowing a minimum
of 10cm from ceiling.
Use a stud finder to locate studs to prevent unnecessary damage to the wall.

More than 10cm


More than 50cm

More than 50cm

More than 2m

Service Manual 33

Installation

3. Art Cool Deluxe Type Indoor unit


Do not have any heat or steam near the unit.
Select a place where there are no obstacles in front of the
unit.
Make sure that condensation drainage can be conveniently
routed away.
Do not install near a doorway.
Ensure that the space around the left and right of the unit is
more than 20cm. The unit should be installed as high on the
wall as possible, allowing a minimum of 30cm from ceiling.
Use a stud finder to locate studs to prevent unnecessary
damage to the wall.

More than 30cm

More than 20cm

More than 30cm


More than 2.3m

CAUTION

Install the indoor unit on the wall where the height


from the floors more than 2.3 meters.

4. Duct Type Indoor Unit


Install the air conditioner in the location that satisfies the
following conditions.
The place shall easily bear a load exceeding four times
the indoor units weight.

Inspection hole
(600X600)
Control box

Top view
(unit: mm)

The place where the unit shall be leveled.

1000

The place shall be able to inspect the unit as the figure.


600

The place shall allow easy water drainage.(Suitable


dimension H is necessary to get a slope to drain as figure.)

600

Front

The place shall easily connect with the outdoor unit.


The place where the unit is not affected by an electrical
noise.

Front view

The place where air circulation in the room will be good .


There should not be any heat source or steam near the
unit

5. CST Type Indoor Unit


There should not be any heat source or steam near the
unit.
There should not be any obstacles to the air circulation.

Do not install the unit near the door way.


Ensure the spaces indicated by arrows from the wall,
ceiling, or other obstacles.
The indoor unit must have the maintenance space
around.

50 or
more

50 or
more

Unit:cm
Floor

34 Multi type Air Conditioner

Ceiling Board
30 or less

Ceiling
Ceiling Board

Above 250
330 or less

A place where noise prevention is taken into consideration.

100
or more

A place where drainage can be easily obtained.

30 or more

A place where air circulation in the room will be good.

Installation

6. CVT Type Indoor Unit


There should not be any heat source or steam near
the unit.
There should not be any obstacles to prevent the air
circulation.
A place where air circulation in the room will be good.

More than
20cm
More than
20cm

More than eye-level

A place where drainage can be easily obtained.


A place where noise prevention is taken into consideration.

More than
20cm

(Ceiling installation)

Do not install the unit near the door way.


Ensure the spaces indicated by arrows from the wall,
ceiling, or other obstacles.
R

More than
20cm

(Floor/Wall installation)

Service Manual 35

Installation

How to fix
1. Room Type Indoor Unit Installation
Installation Plate

The mounting wall should be strong and solid


enough to protect it from the vibration.

Thread
Weight

The lower left and the right side of


Installation Plate

Installation plate
B

2) Drill the piping hole with 70mm dia. holecore


drill.
Line according to the arrows marked on lower
the left and the rght side of the Installation Plate.
The meeting point of the extended line is the
center of the hole.
Drill the piping hole at either the right or the left
and the hole should be slightly slant to the outdoor side.

marking-off line

Type "A" screw

1) Mount the installation plate on the wall with


four Type "A" screws.
(If mounting the unit on the concrete wall, consider using anchor bolts.)
Always mount the Installation plate horizontally
by aligning the marking-off line by means of the
thread and a level.

70mm

Left rear piping

Distance(mm)

CHASSIS
(Grade)

SQ(7/9k)

75

12

80

12

SR(9/12k)

40

20

40

ST(18/24k)

105

210

Installation plate

70mm

B
A

C
Left rear piping

CHASSIS
(Grade)
S4
SE
S5

36 Multi type Air Conditioner

70mm

Right rear piping

70mm

Right rear piping

Distance (mm)
A
50
65
95

B
105
110
122

C
59
85
235

D
105
110
122

Installation

2. Art Cool Type Indoor Unit


The wall you select should be strong and solid enough
to prevent vibration
1) Open panel front
First,Pull the grille bottom, then remove screws
(2 pieces), and close grille bottom again.
The moment of lifting the both lower parts of panel
front, you can hear sound this panel came out, In
this time panel front is separated
After pull down this panel a bit, and separate connecting wire with product.

2) Cover pipe and cover side remove


Remove two screws(for fixing cover pipe)
Pull up the cover side of desired connecting direction, then cover side is separated.
In case connecting direction is left or right, path
through the hole of cover side.

CAUTION: After removing the pipe


hole, cut the burr for safety.

Pipe hole

NOTE: When connecting pipe path through rear


wall, dont remove the hole.
3) Drain hose junction
Remove the rubber stopple of desired drain direction.
As the following picture, Insert drain hose in the handle of drain pan, and join drain hose and connecting
hose.

Panel Front
Connector

Service Manual 37

Installation
Sticking the installation guide map and
fixing Indoor unit
1. Put an Installation Guide Map on the desired
surface.

7. Drill the piercing part for connecting pipe as


diameter 50mm. (In case of piercing rear surface)

INSTALLATION GUIDE MAP

Refer to No. 5 on this page when making a hole in the wall.

2. Make a hole with diameter of 6mm and depth of


30-35mm when piercing a screw point.
IN
ST
AII
AT
IO
N

8. First, Drive the two points of the upper parts by


screws. (Leave 10mm for hanging product)

GU
ID
EM
AP

mm

10

IN
ST
AL
LA
TIO
N

3. Drive the fore plastic anchors into drilled points.


IN
ST
AL
LA
TIO
N

GU
ID
EM
AP

GU

9. Drive the lower parts after facing the hole of


product with plastic anchors, and fix completely
the upper screws.
Plastic anchors

Plastic anchors

4. Hang the hole of product at the upper screws.


(In this time, Remove the map)
INS
TAL
LAT
ION
GUID
EM
AP

(Falling attention)

In case of nothing wrong in the matter,


connect the pipe and the wire.
(Installation manual reference)

Hanger hole
(Rear side of
product)

5. Check the fixed product with light power.

Drill a hole in the wall


Drill the piping hole with a 50mm hole core drill. Drill
the piping hole at either the right or the left with the hole
slightly slanted to the outdoor side.

WALL
Indoor

Outdoor

IN
ST
AL
LA
TIO
N

GU
ID
EM
AP

38 Multi type Air Conditioner

(0.2~0.3")

Horizontality

5-7mm

6. Look at suited horizon by horizontal meter on


the horizontal setting line, and Fix lightly the
map by adhesive tape.

Installation

The wall you select should be strong and solid enough


to prevent vibration
1) Mount the installation plate on the wall with four
type A screws. If mounting the unit on a concrete
wall, use anchor bolts.
Mount the installation plate horizontally by aligning
the centerline using a level.

3). Drill a hole in the wall


Drill the piping hole with a 70mm hole core drill. Drill
the piping hole at either the right or the left with the
hole slightly slanted to the outdoor side.

WALL
Indoor

Outdoor

5-7mm

Installation Plate

(3/16"~5/16")

3. Art Cool Deluxe Type Indoor Unit

Type "A" screw

2) Measure the wall and mark the centerline. It is


also important to use caution concerning the
location of the installation plate-routing of the
wiring to power outlets is through the walls typically. Drilling the hole through the wall for piping
connections must be done safely.
(SU)
C
B

Installation plate
A

70mm

Left rear piping

70mm

Right rear piping

(SZ)

Installation plate
C

Left rear piping

CHASSIS
(Grade)

Right rear piping

Distance (mm)
A

SU
(9k, 12k)

92

44

67

44

SZ
(7k)

35

33

156

33

Service Manual 39

Installation

4. Duct Type Indoor Unit


- BH chassis

Install the unit above the ceiling correctly.

CASE 1
C
E

POSITION OF SUSPENSION BOLT

Apply a joint-canvas between the unit and duct to


absorb unnecessary vibration.
Apply a filter Accessory at air return hole.

(G)

(Unit:mm)
Dimension
A B
C D
E F (G) H
I
Capacity
18k, 24k 932 880 355 45.5 450 30 87 750 163

1-3 mm

87 830 186

30k, 36k 1232 1180 355 45.5 450 30

Install the unit leaning to a drainage hole side as a


figure for easy water drainage.

H
Drainage hole

CASE 2
POSITION OF CONSOLE BOLT
A place where the unit will be leveled and that can
support the weight of the unit.
A place where the unit can withstand its vibration.
A place where service can be easily performed.

M10 Nut

X4

(Local
M10 SP. washer X 4 supply)
M10 washer
X4

NOTE:

M10 washer

Throughly study the following installation locations:


1. In such places as restaurants and kitchens, considerable
amount of oil steam and flour adhere to the fan, the fin of
the heat exchanger, resulting in heat exchange reduction,
spraying, dispersing of water drops, etc.
In these cases, take the following actions:
Make sure that the ventilation fan for smoke-collecting
hood on a cooking table has sufficient capacity so that
it draws oily steam which should not flow into the suction of the air conditioner.
Make enough distance from a cooking room to install
the air conditioner in such a place where it may not
suck in oil steam.
2. Avoid installing air conditioner in such circumstances
where cutting oil mist or iron powder is in suspension in
factories, etc.
3. Avoid places where inflammable gas is generated, flows
in, is stored or vented.
4. Avoid places where sulfurous acid gas or corrosive gas
is generated.
5. Avoid places near high frequency generators.

(Local
M10 SP. washer X 4 supply)
M10 Nut
X4

40 Multi type Air Conditioner

X4

Installation

- BT chassis
A

Install the unit above the ceiling correctly.

CASE 1
POSITION OF SUSPENSION BOLT

C
E

Apply a joint-canvas between the unit and duct to


absorb unnecessary vibration.
Apply a filter Accessory at air return hole.
(Unit:mm)

18K

708

678

434

51

537

455 230

172

1060 1030 434

51

535

805 230

175

Install the unit leaning to a drainage hole side as a


figure for easy water drainage.

1-3 mm

9/12K

G
H

Dimension
Capacity

F
Drainage hole

CASE 2
POSITION OF CONSOLE BOLT
A place where the unit will be leveled and that can
support the weight of the unit.
A place where the unit can withstand its vibration.
A place where service can be easily performed.

M10 Nut

X4

(Local
M10 SP. washer X 4 supply)
M10 washer
X4

M10 washer

X4

(Local
M10 SP. washer X 4 supply)
M10 Nut
X4

Service Manual 41

Installation
C
A

- BP chassis
Install the unit above the ceiling correctly.
G

CASE 1

D
E

Apply a joint-canvas between the unit and duct to


absorb unnecessary vibration.
Apply a filter Accessory at air return hole.

POSITION OF SUSPENSION BOLT

(Unit:mm)
Capacity

Dimension

1-3 mm

9k/12k BTU/h 633 580 695 660 750 45 369 797 20 232 372

Install the unit leaning to a drainage hole side as a


figure for easy water drainage.

H
Drainage hole

CASE 2
POSITION OF CONSOLE BOLT
A place where the unit will be leveled and that can
support the weight of the unit.
A place where the unit can withstand its vibration.
A place where service can be easily performed.

M10 Nut

X4
(Local
M10 SP. washer X 4 supply)
M10 washer
X4

M10 washer

X4

(Local
M10 SP. washer X 4 supply)
M10 Nut
X4

42 Multi type Air Conditioner

Installation

Piping and Drainage of Indoor Unit


1. Preparation of pipings

Pipe cutter

1) Cut the pipes and the cable.


Use the accessory piping kit or the pipes purchased locally.
Measure the distance between the indoor and
the outdoor unit.
Cut the pipes a little longer than the measured
distance.
Cut the cable 1.5m longer than the length of the
pipe.

Slanted

90

Rough

Pipe
2) Remove burrs.
Remove burrs from cut edges of pipes.
Turn the pipe end toward down to avoid the
metal powder entering the pipe.

3) Flaring the pipes.


Insert the flare nuts, mounted on the connection
ports of both indoor and outdoor unit, onto the
copper pipes. Some refrgerant gas may leak,
when the flare nuts are removed from the indoor
unit, as some gas is charged to prevent the
inside of the pipe from rusting.
Fit the copper pipe end into the Bar of flare tool
about 0~0.5mm higher. (See illustration)
Flare the pipe ends.

Point down

"A": 15.88 mm (5/8") 0~1.0 mm


12.7 mm (1/2") 0~0.5 mm
9.52 mm (3/8") 0~0.5 mm
6.35 mm (1/4") 0~0.5 mm

Handle

Bar
Bar

Copper pipe

4) Tape the flaring portion to protect it from the


dust or damages.

Yoke

"A"

CAUTION: If burrs are not removed,


they may cause a gas leakage.

Reamer

Cone

Clamp handle

Red arrow mark

= Improper flaring =

Inclined

Surface
damaged

Cracked

Uneven
thickness

When properly flared, the internal surface flare will


evenly shine and be of even thickness.
Since the flare part comes into contact with the connectors, carefully check the flare finish.

Service Manual 43

Installation

Connection of indoor unit piping


1. Split Type Indoor Unit
Preparing the indoor unit's piping and drain hose
for installation through the wall.

3. Tape the tubing, drain hose and the connecting


cable. Be sure that the drain hose is located at the
lowest side of the bundle. Locating at the upper side
can cause drain pan to overflow inside the unit.

Remove the plastic tubing retainer(see illustration


below) and pull the tubing and drain hose away
from chassis.
Replace the plastic tubing holder in the original
position.

Loop
Connecting
cable

Gas side
piping

Drain hose

Liquid side
piping

Tubing holder

To remove the holder,


press the bottom of
chassis near the holder
upward and pull the tab
out of its hole.

2 Pull
1 Press

CAUTION
When install, make sure that the
remaining parts must be removed
clearly so as not to damage the
piping and drain hose, especially
power cord and connecting cable.

NOTE: If the drain hose is routed inside the room,


insulate the hose with an insulation material* so that
dripping from "sweating"(condensation) will not
damage furniture or floors.
*Foamed polyethylene or equivalent is recommended.
4. Indoor unit installation
Hook the indoor unit onto the upper portion of the
installation plate.(Engage the two hooks of the
rear top of the indoor unit with the upper edge of
the installation plate.) Ensure that the hooks are
properly seated on the installation plate by moving
it left and right.

For left rear piping

Connecting
cable

1. Route the indoor tubing and the drain hose in the


direction of rear left.
Drain hose

Press the lower left and right sides of the unit


against the installation plate until the hooks engage
into their slots(clicking sound).
5. Connecting the pipings to the indoor unit and
drain hose to drain pipe.
Drain hose

Align the center of the pipings and sufficiently


tighten the flare nut by hand.

2. Insert the connecting cable into the indoor unit


from the outdoor unit through the piping hole.
Do not connect the cable to the indoor unit.
Make a small loop with the cable for easy connection later.

44 Multi type Air Conditioner

Indoor unit tubing

Flare nut

Pipings

Installation
When extending the drain hose at the indoor unit,
install the drain pipe.

For right rear piping


1. Route the indoor tubing and the drain hose to the
required piping hole position.

Drain pipe

Indoor unit
drain hose
Vinyl tape(narrow)
Adhesive

6. Wrap the insulation material around the connecting portion.


Overlap the connection pipe insulation material
and the indoor unit pipe insulation material. Bind
them together with vinyl tape so that there is no
gap.
Plastic bands

2. Insert the piping, drain hose and the connecting


cable into the piping hole.

Connecting cable
Drain pipe

Insulation material

3. Insert the connecting cable into the indoor unit.


Don't connect the cable to the indoor unit.

Wrap the area which accommodates the rear piping housing section with vinyl tape.

Make a small loop with the cable for easy connection later.
4. Tape the drain hose and the connecting cable.
Connecting cable

Indoor
unit pipe
Wrap with vinyl tape

Connection
pipe
Vinyl tape
(wide)
Connecting cable

Pipe
Vinyl tape(narrow)

5. Indoor unit installation


Bundle the piping and drain hose together by
wrapping them with vinyl tape over the range within which they fit into the rear piping housing section.

Hang the indoor unit from the hooks at the top of


the installation plate.
Insert the spacer etc. between the indoor unit and
the installation plate and separate the bottom of
the indoor unit from the wall.

Wrap with vinyl tape


Pipe

Vinyl tape(wide)
Drain hose

Service Manual 45

Installation
6) Connecting the pipings to the indoor unit and the
drain hose to drain pipe.

8) Reroute the pipings and the drain hose across the


back of the chassis.

Align the center of the pipings and sufficiently


tighten the flare nut by hand.

Indoor unit tubing

Flare nut

Pipings

When extending the drain hose at the indoor unit,


install the drain pipe.

Piping for
passage through
piping hole

9) Set the pipings and the drain hose to the back of


the chassis with the tubing holder.

Drain hose

Indoor unit drain hose

Hook the edge of tubing holder to tap on chassis


and push the bottom of tubing holder to be
engaged at the bottom of chassis.

Vinyl tape (narrow)


Adhesive

7) Wrap the insulation material around the connecting portion.


Overlap the connection pipe heat insulation and
the indoor unit pipe heat insulation material. Bind
them together with vinyl tape so that there is no
gap.
Plastic bands

Tubing holder

Insulation material
1 Hook
2 Push

Wrap the area which accommodates the rear piping housing section with vinyl tape.
Connection
pipe
Vinyl tape
(wide)

Indoor
unit piping

10) Indoor unit installation


Remove the spacer.
Ensure that the hooks are properly seated on the
installation plate by moving it left and right.

Wrap with vinyl tape

Pipe

Connecting
cable

Vinyl tape
(narrow)

Connecting
cable
Drain hose

Bundle the piping and drain hose together by


wrapping them with cloth tape over the range within which they fit into the rear piping housing section.
Pipe
Drain hose
Vinyl tape
(narrow)

Wrap with
vinyl tape(wide)

46 Multi type Air Conditioner

Press the lower left and right sides of the unit


against the installation plate until the hooks engage
into their slots(clicking sound).

Installation
2. Art Cool Type Indoor Unit
Preparing the indoor unit's piping and drain hose for
installation through the wall.
1) Route the indoor tubing and the drain hose in the
direction of rear left or right.
2) Tape the tubing, drain hose, and the connecting
cable. Be sure that the drain hose is located at the
lowest side of the bundle. Locating at the upper
side can cause drain pan to overflow inside the
unit.

When extending the drain hose at the indoor unit,


install the drain pipe.

Drain pipe

Indoor unit drain hose


Adhesive

Vinyl tape(narrow)

4) Wrap the insulation material around the connecting


portion.
Overlap the connection pipe insulation material and
the indoor unit pipe insulation material. Bind them
together with vinyl tape so that there is no gap.
Plastic bands Insulation material

Loop

Gas side piping

Connecting
cable

Liquid side piping


Drain hose

NOTE: If the drain hose is routed inside the room,


insulate the hose with an insulation material* so that
dripping from "sweating"(condensation) will not damage
furniture or floors.
*Foamed polyethylene or equivalent is recommended.

Wrap the area which accommodates the rear piping


housing section with vinyl tape.

Indoor
unit pipe

Connection
pipe
Vinyl tape
(wide)

3) Connecting the pipings to the indoor unit and drain


hose to drain pipe.
Align the center of the pipes and sufficiently tighten
the flare nut by hand.

Wrap with vinyl tape

Connecting cable

Pipe
Vinyl tape(narrow)

Indoor unit tubing

Flare nut

Pipes

Bundle the piping and drain hose together by wrapping them with vinyl tape for enough to cover where
they fit into the rear piping housing section.

Tighten the flare nut with a wrench.

Wrap with vinyl tape

Open-end wrench (fixed)


Pipe
Flare nut
Wrench
Indoor unit tubing

Connection pipe
Vinyl tape(wide)
Drain hose

Service Manual 47

Installation
Panel Assembly
1. First, Check the side cover assembly exactly, Fix
power cord in the bottom groove of cover side
left.

2. Assemble connecting lead wire with controller


and first fix the upper part of panel front, then
match the lower part of panel front

Panel Front
Connector

3. Drive two screws.

48 Multi type Air Conditioner

Installation
3. Art Cool Deluxe Type Indoor Unit
Connection of piping Indoor
Preparing the indoor unit's piping and drain hose for
installation through the wall.
Remove the plastic tubing retainer(see illustration
below) and pull the tubing and drain hose away from
chassis.
Replace the plastic tubing holder in the original position.
(Optional)

NOTE: If the drain hose is routed inside the room,


insulate the hose with an insulation material* so that
dripping from "sweating"(condensation) will not damage
furniture or floors.
*Foamed polyethylene or equivalent is recommended.
4. Indoor unit installation
Hook the indoor unit onto the upper portion of the
installation plate.(Engage the two hooks of the rear
top of the indoor unit with the upper edge of the installation plate.) Ensure that the hooks are properly seated on the installation plate by moving it left and right.

Connecting
cable

Drain hose

Press the lower left and right sides of the unit against
the installation plate until the hooks engage into their
slots(clicking sound).

For right rear piping


1. Route the indoor tubing and the drain hose in the
direction of rear right.

Drain hose

4. Connecting the pipings to the indoor unit and drain


hose to drain pipe.
Align the center of the pipes and sufficiently tighten
the flare nut by hand.

Indoor unit tubing

Flare nut

Pipes

Tighten the flare nut with a wrench.

2. Insert the connecting cable into the indoor unit


from the outdoor unit through the piping hole.
Do not connect the cable to the indoor unit.
Make a small loop with the cable for easy
connection later.
3. Tape the tubing, drain hose, and the connecting
cable. Be sure that the drain hose is located at the
lowest side of the bundle. Locating at the upper
side can cause drain pan to overflow inside the
unit.

Open-end wrench (fixed)


Flare nut
Connection pipe

Wrench
Indoor unit tubing

Outside diameter
mm
6.35
9.52
12.7

inch
1/4
3/8
1/2

Torque
kg.m
1.8
4.2
5.5

When extending the drain hose at the indoor unit,


install the drain pipe.
Tape
Connecting
pipe
Drain hose

Connecting cable

Service Manual 49

Installation
5. Wrap the insulation material around the connecting
portion.
Overlap the connection pipe insulation material and
the indoor unit pipe insulation material. Bind them
together with vinyl tape so that there is no gap.

4. Tape the drain hose and the connecting cable.


Connecting cable

Plastic bands Insulation material

Wrap the area which accommodates the rear piping


housing section with vinyl tape.
Indoor
unit pipe

Connection
pipe

5. Indoor unit installation


Hang the indoor unit from the hooks at the top of the
installation plate.
Insert the spacer etc. between the indoor unit and the
installation plate and separate the bottom of the
indoor unit from the wall.

Vinyl tape
Wrap with vinyl tape
(wide)
Connecting cable

Indoor unit
Spacer
Pipe

Installation plate
Vinyl tape(narrow)

8cm

Bundle the piping and drain hose together by wrapping them with vinyl tape for enough to cover where
they fit into the rear piping housing section.
Wrap with vinyl tape

6. Connecting the pipings to the indoor unit and the


drain hose to drain pipe.
Align the center of the pipes and sufficiently tighten
the flare nut by hand.

Pipe

Vinyl tape(wide)

Indoor unit tubing

Flare nut

Pipes

Drain hose

Tighten the flare nut with a wrench.

For left rear piping

Open-end wrench (fixed)

1. Route the indoor tubing and the drain hose to the


required piping hole
position.

Flare nut
Connection pipe

Wrench
Indoor unit tubing

2. Insert the piping, drain hose, and the connecting


cable into the piping hole.

Connecting cable

Outside diameter
mm
inch
6.35
1/4
9.52
3/8
12.7
1/2

Torque
kg.m
1.8
4.2
5.5

When extending the drain hose at the indoor unit,


install the drain pipe.

Drain pipe
Drain hose

3. Insert the connecting cable into the indoor unit.


Don't connect the cable to the indoor unit.
Make a small loop with the cable for easy connection later.

50 Multi type Air Conditioner

Indoor unit drain hose


Adhesive

Vinyl tape (narrow)

Installation
7. Wrap the insulation material around the connecting portion.
Overlap the connection pipe heat insulation and the
indoor unit pipe heat insulation material. Bind them
together with vinyl tape so that there is no gap.

9. Set the pipings and the drain hose to the back of


the chassis with the tubing holder.
Hook the edge of tubing holder to tap on chassis and
push the bottom of tubing holder to be engaged at the
bottom of chassis.

Plastic bands Insulation material

Tubing holder

Wrap the area which accommodates the rear piping


housing section with vinyl tape.
Indoor
unit piping

Connection
pipe
Vinyl tape
(wide)

Wrap with vinyl tape

10. Indoor unit installation


Remove the spacer.
Ensure that the hooks are properly seated on the
installation plate by moving it left and right.

Pipe
Vinyl tape(narrow)
Connecting cable

Connecting
cable

Drain hose

Bundle the piping and drain hose together by wrapping them with cloth tape over the range within which
they fit into the rear piping housing section.
Pipe

Press the lower left and right sides of the unit against
the installation plate until the hooks engage into their
slots(clicking sound).

Drain hose
Vinyl tape(narrow)

Wrap with
vinyl tape(wide)

8. Reroute the pipings and the drain hose across the


back of the chassis.

Piping for
passage through
piping hole

Service Manual 51

Installation

CAUTION

Installation Information (For left piping)


Good case
For left piping. Follow the instruction below.
Press on the upper side of clamp. ( )

Bend the tubing to the left side of chassis.

Bend the tubing to the left side of chassis.

52 Multi type Air Conditioner

Bad case
Following bending type from right to left could cause problem
of pipe damage.

Installation

4. Duct Type Indoor Unit


1) Indoor Unit Installation
Select and mark the position for fixing bolts.
Drill the hole for set anchor on the face of ceiling.

Old building
Insert the set anchor and washer onto the suspension bolts for locking the suspension bolts on the ceiling.
Mount the suspension bolts to the set anchor firmly.
Secure the installation plates onto the suspension
bolts (adjust level roughly) using nuts, washers and
spring washers.

New building

1 Set anchor
2 Plate washer
3 Spring washer
4 Nut

CAUTION: Tighten the nut and bolt to


prevent unit falling.

5 Suspension
bolts
Local supply
Set anchor
Plate washer
Spring washer
Nut
Suspension bolt

- M10
- M10
- W3/8 or M10
- W3/8 or M10

Service Manual 53

Installation

5. CVT Type Indoor Unit


- VB chassis
Before Installing, prepare Installation Plates
'Installation Plates' are attached at the bottom of
indoor unit.
Detach them by removing each 3 screws at both
sides.
Detach 'Side Plate (R,L)' by removing each 2 screws
on both sides.
Pull the upper right and left side of 'Inlet Grille' to the
front, and it will stop at slightly tilted position.
Unhook the 'Inlet hanger' from the 'Hanger screw' on
the both left and right side.
Detach the 'Inlet Grille' from the Indoor Unit.

Side Plate
R

Install Plate

Inlet hanger

1) Installation on the ceiling

Measure and mark the position for the


Suspension bolts and the piping hole.
Drill the hole for anchor nut on the ceiling.

Hanger
screw

Inlet Grille

1)

265

1076

Suspension
bolt

Before secure the Installation Plates, select the bent


direction of the Installion Plate to the inside or the
outside according to the installation circumstances.

2)

1236

Center-line for the


piping hole
265

Drill the piping hole on the wall slightly tilted to the


outdoor side using a 70 hole-core drill.
Indoor

WALL

Outdoor
5~7mm

54 Multi type Air Conditioner

Installation

Insert the nuts and washer onto the suspension bolts


for locking the suspension bolts on the ceiling.
Mount the suspension bolts to the anchor-nuts firmly.
Secure the Installation plates onto the Suspension
bolts (adjust level roughly.) using nuts, washers and
spring washers.

Anchor nut

1)

Ceiling
Nut

Washer

Suspension
bolts

Suspension
bolts
Spring
washer

max.
12mm

Nut

Washer

2)

Engage 2 hooks on the both left and right side


of the unit to the lower slot of Installation Plates.
Adjust a level with a level gauge on the direction
of left-right, back-forth by adjusting suspension
bolts.
Move the hooks on the unit to the upper slot of
Installation Plates. Then the unit will be declined
to the bottomside so as to drain well.

Lower slot
Level gauge

Suspension
bolt

Adjust a level

Installation plate

Upper slot

Service Manual 55

Installation

- VE chassis
The wall you select should be strong and solid
enough to prevent vibration

Installation Plate

1. Mount the installation plate on the wall with


type "A" screws. If mounting the unit on a concrete wall, use anchor bolts.
Mount the installation plate horizontally by aligning
the centerline using a level.
Type "A" screw

2. Measure the wall and mark the centerline. It is


also important to use caution concerning the
location of the installation plate-routing of the
wiring to power outlets is through the walls typically. Drilling the hole through the wall for piping
connections must be done safely.

70

70
Installation plate
70mm
Left rear piping

120
more than 200
Floor

Mounting the anchor Nut & Bolt


(Ceiling Mounting)
Prepare 4 suspension bolts (Each bolts length
should be same.)
Measure and mark the position for the Suspension
bolts and the piping hole.
Insert the nuts and washer onto the suspension
bolts for locking the suspension bolts on the ceiling.
Mount the suspension bolts to the anchor-nuts
firmly.

56 Multi type Air Conditioner

70mm
Right rear piping

Installation
Secure the Installation plates onto the Suspension
bolts (adjust level roughly.) using nuts, washers and
spring washers.
Engage 2 hooks on the both left and right side of the
unit to the lower slot of Installation Plates.

Anchor nut
Ceiling
Nut
Suspension
bolts

Adjust a level with a level gauge on the direction of


left-right, back-forth by adjusting suspension bolts.
Move the hooks on the unit to the upper slot of
Installation Plates. Then the unit will be declined to
the bottomside so as to drain well.

Washer

235
820

Suspension bolt

Center-line for the


piping hole

Suspension
bolts
Spring
washer
Hangen
Max.
12mm

Nut

Washer

Drill a Hole in the Wall


WALL
Outdoor

(3/16"~5/16")

Indoor

5-7mm

Drill the piping hole with a 70mm hole core drill.


Drill the piping hole at either the right or the left with
the hole slightly slanted to the outdoor side.

Service Manual 57

Installation

CAUTION: Installation Information


For Declination
CAUTION

1. Install declination of the indoor unit is very important for the drain of the convertible type air
conditioner.
2. Minimum thickness of the insulation for the connecting pipe shall be 7mm.
3. If the Installation Plates are fixed to horizontal line, the indoor unit after installing will be declined
to the bottomside.

Front of view
The unit must be horizontal or declined to the drain hose connected when finished installation.

Ceiling

Drain hose
Ceiling

Side of view
The unit must be declined to the bottomside of the unit when finished installation.

Ceiling

58 Multi type Air Conditioner

Installation
Secure the unit to the Installation Plates with four M8
bolts and washers.

Before working, refer to "Connecting pipe


and cable to Indoor Unit".
Hook up the Inlet Grille Hook to the cabinet.
Hang the Inlet Hanger to the screw.

Inlet hanger

Hook
Cabinet Bottom

Fit the projection hooks of the side plates to the 'Side


Panel' and the 'Front Panel' by lifting it.
Fasten the screws.

Service Manual 59

Installation
2) Installation on the Wall
Select and mark the position for fixing bolts and piping
hole.
Decide the position for fixing bolts slightly tilted to the
drain direction after considering the direction of drain
hose.
Drill the hole for anchor nut on the wall.

1076
mor
e th
260 an

265

Drill the piping hole on the wall slightly tilted to the outdoor side using a 70 hole-core drill.
Wall
Outdoor

5~7mm

Indoor

Secure the 'Install Plate' onto the wall with four anchor
bolts, washers and spring washers.
Spring
washer

Wall

Nut

Washer
Anchor nut

Less than
12mm

Before secure the Install Plates, select the bent direction of the 'Install Plate' to the inside or outside according to the installation circumstances.

60 Multi type Air Conditioner

123

Installation
Install the Indoor unit onto Installation Plate.
Insert 2 hooks on the both left and right side of the unit
to the inner slot (wall side) of the Installation Plate.

Inner slot

Secure the unit to the Installation Plate with four M8


bolts and washers.

Before working, refer to "Connecting pipe


and cable to Indoor Unit".
Hook up the Inlet Grille Hook to the cabinet.
Hang the Inlet Hanger to the screw.

Fit the projection hooks of the side plates to the 'Side


Panel' and the 'Front Panel' by lifting it.
Fasten the screws.

Service Manual 61

Installation
3) Installation on the floor

From the left wall


more than 760mm

Installation of Mount Bracket.


Select and mark the position for Mount Brackets and
the piping hole.
Drill the hole for the anchor nut on the wall.
Drill the piping hole using a 70 hole-core drill.
Secure the Mount Brackets on the wall with four M4
screws.
Install the indoor unit onto the Mount Brackets.
Engage the slot at the back of the unit with Mount
Bracket.

From the
right wall
more than 840mm

448mm

Slot
Floor mount
bracket

Drill the piping hole with 70mm dia, hole core drill.
Piping hole should be slightly slant to the outdoor side.

Wall
Outdoor

5~7mm

Indoor

After Installing, reassemble detached parts.


Hang the 'Inlet Grille' and hook the 'Inlet Hanger' to the
Hanger Screw.
Assemble the 'Side Plates(R,L)' with 2 screws on both
left and right side.

Slot
Wall

Floor mount
bracket
Install plate
Piping hole

62 Multi type Air Conditioner

Installation
6. Ceiling Cassette Type Indoor Unit

- TC, TC1 chassis


1) Ceiling opening dimensions and hanging bolt location
The dimensions of the paper model for installing are
the same as those of the ceiling opening dimensions.

328.4 (Hanging bolt) 30.8

Level gauge

931.6
893.4 (Hanging bolt)
860
430 (Ceiling opening)
390

Ceiling

1,000 (Ceiling opening)

CAUTION
This air-conditioner uses a drain pump.
Install the unit horizontally using a level gauge.
During the installation, care should be taken not to
damage electric wires.
Select and mark the position for fixing bolts and piping hole.
Decide the position for fixing bolts slightly tilted to
the drain direction after considering the direction of
drain hose.
Drill the hole for anchor bolt on the wall.

Ceiling board

NOTE:
Avoid the following installation location.
1. Such places as restaurants and kitchen where considerable amount of oil steam and flour is generated.
These may cause heat exchange efficiency reduction, or water drops, drain pump mal-function.
In these cases, take the following actions;
Make sure that ventilation fan is enough to cover all noxious gases from this place.
Ensure enough distance from the cooking room to install the air conditioner in such a place where it may
not suck oily steam.

Air conditioner

Take enough
distance
Use the ventilation fan
for smoke-collecting
hood with sufficient
capacity.
Cooking table

2. Avoid installng air conditioner in such places where cooking oil or iron powder is generated.
3. Avoid places where inflammable gas is generated.
4. Avoid place where noxious gas is generated.
5. Avoid places near high frequency generators.

Service Manual 63

Installation

2) Indoor Unit Installation

Nut
(W3/8 or M10)
Spring washer
(M10)

103mm

Ceiling
Hanging bolt
(W3/8 or M10)

Keep the length of the bolt


from the bracket to 40mm
Flat washer for M10
(accessory) Ceiling board

Flat washer for M10


(accessory)
Nut
(W3/8 or M10)

Air Conditioner body

Paper model
for installation

Adjust the same height

The following parts are local purchasing.


Hanging Bolt - W 3/8 or M10
Nut
- W 3/8 or M10
Spring Washer - M10
Plate Washer - M10

Ceiling board

Set screw of
paper model (4 pieces)
Open the ceiling board
along the outer edge of the
paper model

Drill the piping hole on the wall slightly tilted to the


outdoor side using a 70 hole-core drill.

Wall
Indoor

Outdoor

Tighten the nut and bolt to prevent unit from


falling off.

64 Multi type Air Conditioner

5~7mm

CAUTION

Installation
7. Ceiling Cassette Type Indoor Unit

- TE(1)/TF/TH/TD chassis
1) Ceiling opening dimensions and hanging bolt location
600 (Ceiling opening)
521(Hanging bolt)

39.5

Level gauge

CAUTION

450 (Hanging bolt)

570 Unit size

570 Unit size

75

Ceiling

600 (Ceiling opening)

39.5

TE(1)

75

The dimensions of cardboard for installing are the


same as those of the ceiling opening dimensions.

Unit:mm
790 (Ceiling opening)
109

572(Hanging bolt)

TF
109

66

744 Unit size

744 Unit size

790 (Ceiling opening)

Select and mark the position for fixing bolts and piping hole.
Decide the position for fixing bolts slightly tilted to the drain
direction after considering the direction of drain hose.
Drill the hole for anchor bolt on the wall.

658 (Hanging bolt)

66

This air-conditioner uses a drain pump.


Install the unit horizontally using a level gauge.
During the installation, be careful not to damage
electric wires.

Unit:mm

785 (Hanging bolt)

840 Unit size


840 Unit size

45

TH/TD
45

875 (Ceiling opening)

875 (Ceiling opening)

101.5 672 (Hanging bolt) 101.5

Ceiling board

Unit:mm

Service Manual 65

Installation

NOTE:
Avoid the following installation location.
1. Such places as restaurants and kitchen where considerable amount of oil steam and flour is generated.
These may cause heat exchange efficiency reduction, or water drops, drain pump mal-function.
In these cases, take the following actions;
Make sure that ventilation fan is enough to cover all noxious gases from this place.
Ensure enough distance from the cooking room to install the air conditioner in such a place where it may
not suck oily steam.
Air conditioner

Take enough
distance
Use the ventilation fan
for smoke-collecting
hood with sufficient
capacity.
Cooking table

2. Avoid installng air conditioner in such places where cooking oil or iron powder is generated.
3. Avoid places where inflammable gas is generated.
4. Avoid place where noxious gas is generated.
5. Avoid places near high frequency generators.

2) The Indoor Unit Installation


Ceiling

Nut
(W3/8 or M10)

Flat washer for M10


(accessory)
Ceiling board

Spring washer
(M10)

Flat washer for M10


(accessory)
Nut
(W3/8 or M10)

Air Conditioner body

Ceiling board

Cardboard
for installation

Set screw of
cardboard (4 pieces)
Open the ceiling board
along the outer edge of the
paper model

Adjust the same height

The following parts are local purchasing.


Hanging Bolt - W 3/8 or M10
Nut
- W 3/8 or M10
Spring Washer - M10
Plate Washer - M10

150mm

Keep the length of the bolt


from the bracket to 40mm

Hanging bolt
(W3/8 or M10)

Drill the piping hole on the wall slightly tilted to the


outdoor side using a 70 hole-core drill.

Wall
Indoor

Outdoor

Tighten the nut and bolt to prevent the unit from


falling off.

66 Multi type Air Conditioner

5~7mm

CAUTION

Installation

Remote Controller Installation


Although the room temperature sensor is in the indoor unit, the remote controller should be installed
in such places away from direct sunlight and high humidity.
Installation of the remote controller
Select places that are not splashed with water.
Select control position after receiving customer approval.
The room temperature sensor is built in the indoor unit.
This remote controller equipped with liquid crystal display. If this position is higher or lower, display is difficult
to see.(The standard height is 1.2 ~ 1.5m high)
Routing of the remote controller cord
Keep the remote controller cord away from the refrigerant piping and the drain piping.
To protect the remote controller cord from electrical noise, place the cord at least 5cm away from other power
cables (audio equipment, television set, etc.)
If the remote controller cord is secured to the wall, provide a trap at the top of the cord to prevent water
droplets from running.

WIRED REMOTE CONTROL INSTALLATION


DISASSEMBLING
Separate the under plate from Remote control box.

Front case
Th

el

ow
er

pa

rt

Lever carefully
the box open
using a screw
driver, etc.

Remote control
box body

Fix the under plate on the wall

Fix the cord clamps on the wall by 3 tapping


screws (accessory).
Fix the remote control cord.

Face of wall
Cord clamp
(accessory)

Under plate

Screw (accessory)

ELECTRICAL WIRING

Remote controller
(Main board)
CN REMO

Wire and make sure that teminal


numbers are matched on unit side and
remote controller side.
The maximum length of the cord is 100m.
If the length of the cord exceeds 50m,
2
use a wire size greater than 0.5mm .

Service Manual 67

Installation
REMOTE CONTROL PREPARATION(OPTIONAL)
HOW TO MOUNT ONTO A WALL

HOW TO INSERT BATTERIES


Remove the battery cover from the remote controller.
Slide the cover according to the arrow direction.
Insert the two batteries.
Be sure that the (+) and (-) directions are correct.
Be sure that both batteries are new.
Re-attach the cover.
Slide it back into position.

68 Multi type Air Conditioner

Do not use rechargeable batteries,


such batteries differ from standard dry
cells in shape, dimensions, and performance.
Romove the batteries from the remote
controller if the air conditioner is not
going to be used for some long time.

Installation

Connecting Pipings and the cable to Outdoor unit


1. Connecting the pipings to the Outdoor
unit

2) Align the center of the pipings and sufficiently tighten the flare nut by hand

1) When piping installation work you must be used the


connector.
Indoor Units

Gas
AB

Liquid

18K/24K
30K/36K

9.5212.7
9.52 15.88

Not available
Not available

Connector

3) Finally, tighten the flare nut with torque wrench until


the wrench clicks.
When tightening the flare nut with torque wrench,
ensure the direction for tightening follows the arrow on
the wrench.

Outdoor unit

A-UNIT
Gas side piping

*Connecting pipe size


Indoor Units
7K/9K/12K
18K/24K
30K/36K

Gas side
9.52(3/8)
12.7(1/2)
15.88(5/8)

Liquid side
6.35(1/4)
6.35(1/4)
6.35(1/4)

B-UNIT
Liquid side piping

Torque wrench

CAUTION: After the confirmation of the above conditions, prepare the wiring as
follows:
1) Never fail to have an individual power specialized for the air conditioner. As for the method of wiring,
be guided by the circuit diagram pasted on the inside of control box cover.
2) The means for disconnection from a power supply shall be incorporated in the fixed wiring and
have an air gap contact separation of at least 3mm in each active(phase) conductors.
3) The screw which fasten the wiring in the casing of electrical fittings are liable to come loose from
vibrations to which the unit is subjected during the course of transportation. Check them and
make sure that they are all tightly fastened. (If they are loose, it could give rise to burn-out of the
wires.)
4) Specification of power source.
5) Confirm that electrical capacity is sufficient.
6) See to that the starting voltage is maintained at more than 90 percent of the rated voltage marked
on the name plate.
7) Confirm that the cable thickness is as specified in the power sources specification.
(Particularly note the relation between cable length and thickness.)
8) Never fail to equip a leakage breaker where it is wet or moist.
9) The following troubles would be caused by voltage drop-down.
Vibration of a magnetic switch, damage on the contact point there of, fuse breaking, disturbance to the
normal function of a overload protection device.
Proper starting power is not given to the compressor.

Service Manual 69

Installation

CAUTION: If a power plug is not to be used, provide a circuit breaker between


power source and the unit as shown below.
Main power source

Air
Conditioner

Circuit Breaker
Circuit Breaker
Use a 30A circuit
breaker or time
delay fuse.

18k~30k Btu

25A

31k~40k Btu

60A

CAUTION

GN

NORMAL CROSSSECTIONAL AREA


3.5mm2

/YL
20

mm

70 Multi type Air Conditioner

The connecting cable connected to the indoor


and outdoor unit should be complied with the
following specifications (Rubber insulation, type
H07RN-F approved by HAR or SAA).
7.5mm

8.5mm

The power cord connected to the outdoor unit


should be complied with the following specifications (Rubber insulation, type H05RN-F
approved by HAR or SAA).

GN

NORMAL CROSSSECTIONAL AREA


0.75mm2

/YL
20

mm

Installation

Checking the Drainage and Pipe forming


1. Split Type Indoor Unit
1) Remove the Grille from the cabinet
Set the up-and-down air direction louver to
open position(horizontally) by finger pressure.
Remove the securing screws.
To remove the Grille, pull lower the left and
right side of the grille toward you (slightly tilted)
and lift it straight upward.

Screw
Pull the right and
the left side.

2) Check the drainage


Pour a glass of water on the evaporator.
Ensure if water flows drain hose of indoor unit
without any leakage.

2. Art Cool Type Indoor Unit


Pour a glass of water on the evaporator.
Ensure the water flows through the drain hose of
the indoor unit without any leakage and goes out
the drain exit.

Service Manual 71

Installation

3. Art Cool Deluxe Type Indoor Unit


1) To remove the front panel from the indoor unit.
Set the air direction louvers up-and-down to the position(horizontally) by hand.
Remove the securing screws that retain the front
panel. Pull the lower left and right sides of the grille
toward you and lift it off.

3) Drain piping
The drain hose should point downward for easy drain
flow.
Downward slope

Do not make drain piping.


Air
filter
Do not raise

Inlet Grille
Water
leakage

2) To check the drainage.


Pour a glass of water on the evaporator.
Ensure the water flows through the drain hose of the
indoor unit without any leakage and goes out the drain
exit.

Accumulated
drain water
Air

Water
leakage

Connecting area
drain hose

Leakage
checking

Waving

Tip of drain hose


dipped in water
Water
leakage

Ditch

Less than
50mm gap

72 Multi type Air Conditioner

Installation

4. Convertible Type Indoor Unit


To remove the front panel from the indoor
unit.
1. Set the air direction louvers up-and-down to the position(horizontally) by hand.
2. Remove the securing screws that retain the front
panel. Pull the lower left and right sides of the grille
toward you and lift it off.

Pull the right and


the left side.

To check the drainage.


1. Pour a glass of water on the evaporator.
2. Ensure the water flows through the drain hose of the
indoor unit without any leakage and goes out the
drain exit.

Drain piping
1. The drain hose should point downward for easy drain
flow.

Downward slope

2. Do not make drain piping like the following.

Accumulated
drain water
Air

Do not raise

Water
leakage

Water
leakage

Waving

Tip of drain hose


dipped in water
Water
leakage

Less than
50mm gap

Ditch

Service Manual 73

Installation

5. Duct Type Indoor Unit


1. Install declination of the indoor unit is very important for the drain of the duct type air conditioner.
2. Minimum thickness of the insulation for the connecting pipe shall be 5mm.

Front of view
The unit must be horizontal or declined to the drain hose connected when finished installation.

1~3mm

Ceiling

CORRECT

INCORRECT

Drainage hole

CAUTION FOR GRADIENT OF


UNIT AND DRAIN PIPING
Always lay the drain with downward inclination
(1/50 to 1/100).
Prevent any upward flow or reverse flow in any part.
5mm or thicker formed thermal insulator shall
always be provided for the drain pipe.

Drainage hole

Lay the drain hose with a downware


inclination so water will drain out.
Thermal insulator
(Local supply)
Drainage pipe
(Local supply)

Unit

Make sure to be closed.

Drainage hole

Upward routing not


allowed

700mm

(Drain pump model only)

CORRECT

Install the P-Trap (or U-Trap) to prevent


a water leakage caused by the blocking
of intake air filter.

74 Multi type Air Conditioner

INCORRECT
Applied U-Trap Dimension
A 70mm
B 2C
C 2 x SP
SP = External Pressure
(mmAq)
Ex) External Pressure
= 10mmAq
A 70mm
B 40mm
C 20mm

B
C
U-Trap
A

Installation

6. CST Type Indoor Unit


Drain piping must have down-slope (1/50 to 1/100):
be sure not to provide up-and-down slope to prevent
reversal flow.
During drain piping connection, be careful not to
exert extra force on the drain port on the indoor
unit.
The outside diameter of the drain connection on
the indoor unit is 32mm.

Pipe clamp

Upward
routing
not allowed

Indoor unit

Maintenance
drain port

Piping material: Polyvinyl chloride pipe VP-25


and pipe fittings
Be sure to install heat insulation on the drain piping.
Heat insulation material: Polyethylene foam with
thickness more than 8 mm.

1/50~1/100
MAX 700mm

Drain test
The air conditioner uses a drain pump to drain water.
Use the following procedure to test the drain pump operation:

Feed water

Flexible drain hose


(accessory)
Main
drain pipe

Drain Pump

Drain
port

Glue the joint

Drain hose connection


Use the clip (accessory)

Connect the main drain pipe to the exterior


and leave it provisionally until the test comes
to an end.
Feed water to the flexible drain hose and
check the piping for leakage.
Be sure to check the drain pump for normal
operating and noise when electrical wiring is
finished.
When the test is completed, connect the flexible drain hose to the drain port on the indoor
unit.

Drain pan

Service Manual 75

Installation

Maximum Length of Pipe and Extra Charge of Refrigerant Charge


1. TPS Inverter Multi -Multi Piping Type
1.1 The maximun allowable level and piping length

[Outdoor Unit]

It does not matter which unit is higher.

[Indoor Unit]
A

B
15m
C

7.5m

Model
[Outdoor Unit]

Max piping length each indoor unit

Standard Length

Max total piping length

A,B,C,D

7.5m

20m

20m

30m(A+B)

7.5m

25m

25m

40m(A+B)

A3UW246FA0
A4UW246FA0

7.5m

25m

25m

25m

50m(A+B+C)

A4UW306FA0

7.5m

25m

25m

25m

25m

70m(A+B+C+D)

A2UW146FA0/1/2
A2UW166FA0/1
A2UW186FA0
A3UW186FA0/1

1.2 Refrigerant Charge


Indoor Unit Capacity
(Btu/h)

Pipe Size
Liquid

Rated
Length

Max
Length

Additional
Refrigerant

Gas

7k, 9k, 12k

3/8"(9.52mm)

1/4"(6.35mm)

7.5m

25m

25g/m

18k, 24k

1/2"(12.7mm)

1/4"(6.35mm)

7.5m

25m

35g/m

Extra refrigerant = (Extended length - Rated length) x Additional refrigerant

76 Multi type Air Conditioner

Installation

2. TPS Inverter Multi - Distributor Type


2.1 The maximum allowable level and piping length
Outdoor Unit
Installation of the outdoor unit
in an upper position

BD Unit

L1

Place the BD unit and


indoor units within a
level distance of 10m
from each other.

L2

L3
30m
B

BD Unit

L4

10m

L5
Main piping
Branch piping

L6

Total main piping length : 50m( A + B )


Total branch piping length : 50m(L1+L2+ L3+L4 +L5+L6)
Each branch piping length : 15m(L1,L2,L3,L4 ,L5,L6)
Total system piping length : 100m(40+60)
R

BD Unit

10m

Place the BD unit and


indoor units within a
level distance of 10m
from each other.

BD Unit
30m

Outdoor Unit

Installation of the outdoor unit


in a lower position

Service Manual 77

Installation
2.2 Refrigerant charge
The calculation of the additional charge should be taken in account for the length of pipe.

A6UW406FA0 charge = 4100g


A7UW486FA0 charge = 7100g
A8UW566FA0 charge = 7100g

Additional charge (g)


=

Total Main pipe length - rated length

x 50g/m

7,9,12 k Branch pipe length - rated length

x 20g/m

18,24 k Branch pipe length - rated length

x 30g/m

30,36 k Branch pipe length - rated length

x 35g/m

CF(Correction Factor) x 100


Rated length = 5m,
CF = Max. number of connectable indoor unit
Total Amount (g)

Total number of connected indoor unit

= A + B

Note : If total additional charge value after calculation comes out to be negative, then do not
consider additional charge.

2.3 Refrigerant charge


The calculation of the additional charge should be taken in account for the length of pipe.
Total main pipe(A+B+C) = 30m
Each branch pipe
a = 10m
b = 8m
c = 5m
d = 3m
e = 10m
CF = 6-5 = 1

ex) A6UW406FA0
A

A
C

7k

9k

9k

9k

18k

Caution

Additional Charge
= (30-5) x 50
+ (10-5) x 20
+ (8-5) x 20
+ (5-5) x 20
+ (3-5) x 20
+ (10-5) x 30
- (1 x 100)
= 1250+100+60+0-40+150-100 =

1420 g

Regulation for refrigerant leakage(in Europe)


: the amount of refrigerant leakage should satisfy the following equation for human safety.
Total amount of refrigerant in the system
Volume of the room at which indoor unit of the least capacity is installed

78 Multi type Air Conditioner

0.3 ( kg / m3 )

Installation
If the above equation can not be satisfied, then follow the following steps.
- Selection of air conditioning system: select one of the next
1. Effective opening part Installation
2. Reconfirmation of outdoor unit capacity and piping length
3. Reduction of the amount of refrigerant
4. 2 or more security device installation of alarm for gas leakage
- Change indoor unit type
: installation position should be over 2m from the floor (Wall mounted type Cassette type)
- Adoption of ventilation system
: choose ordinary ventilation system or building ventilation system
- Limitation in piping work
: design for earthquake-proof and prevention against thermal stress

2.4 Piping connection size


A
Liquid

mm

9.52

Gas

mm

19.05

B
Adjust to indoor unit
piping size

BD Unit

A6UW406FA0

Y-Branch

2.5 Necessity of a trap


Since there is fear of the oil held inside the riser piping
flowing back into the compressor when stopped and
causing liquid compression phenomenon, or cases of
deterioration of oil return, it will be necessary to provide a trap at an appropriate place in the riser gas piping.

In case more then 5m

CAUTION
Capacity is based on standard length and maximum
allowance length is on the basis of reliability.
Oil trap should be installed every 5~7 meters.

Service Manual 79

Installation
2.6 Y-Branch(Standard accessory)
[unit:mm]

Gas Pipe

Liquid Pipe

19.05

19.05

9.52

9.52

9.52

19.05

Y branch
A To Outdoor Unit
B

B To BD Unit

Ensure that the branch pipes are attached horizontally or vertically (see the diagram below.)
Horizontal
plane

Facing upwards

Within +/- 10

A
Viewed from point A
in direction of arrow

There is no limitation on the joint mounting configuration.


If the diameter of the refrigerant piping selected by the procedures described is different from the size
of the joint, the connecting section should be cut with a pipe cutter.
Branch pipe should be insulated with the insulator in each kit.

Tape
(field supply)

Insulator
(included with kit)

80 Multi type Air Conditioner

Liquid and gas


pipe joints

Insulator for
field piping

Installation

Test Running
SPLIT, ART cool, ART cool deluxe Type
1. Check that all tubing and wiring have been properly connected.
2. Check that the gas and liquid side service valves are
fully open.
1) Prepare remote controller
Remove the battery cover by pulling it according to
the arrow direction.
Insert new batteries making sure that the (+) and ()
of battery are installed correctly.
Reattach the cover by pushing it back into position.

Bolt

Tubing connection

4) Evaluation of the performance


Operate unit for 15~20 minutes, then check the system
refrigerant charge:
1. Measure the pressure of the gas side service valve.
2. Measure the temperature of the intake and discharge of
air.
3. Ensure the difference between the intake temperature
and the discharge is more than 8C (Cooling) or reversely (Heating).

NOTE:
Use 2 AAA(1.5volt) batteries. Do not use rechargeable
batteries.
Remove the batteries from the remote controller if the system is not going to be used for a long time.

Intake temperature

Discharge air

2) Precautions in test run


The initial power supply must provide at least 90% of
the rated voltage.
Otherwise, the air conditioner should not be operated.
For test run, carry out the cooling operation firstly
even during heating season. If heating operation is
carried out firstly, it leads to the trouble of compressor. Then attention must be paid.
Carry out the test run more than 5 minutes without
fail. (Test run will be cancelled 18 minutes later automatically)
The forced operation is started by pressing button for
2 seconds. (Cassette Type)
The test run is started by pressing button for 5 seconds. (Cassette Type)
The test run is started by pressing timer cancel button
five times continuously. (Room type)
To cancel the test run, press any button.

Discharge
temperature
Intake temperature
Discharge air

Discharge
temperature

Intake temperature

3) Settlement of outdoor unit


Anchor the outdoor unit with a bolt and nut(10mm)
tightly and horizontally on a concrete or rigid mount.
When installing on the wall, roof or rooftop, anchor the
mounting base securely with a nail or wire assuming the
influence of wind and earthquake.
In the case when the vibration of the unit is conveyed to
the hose, secure the unit with an anti-vibration rubber.

Discharge air

Discharge
temperature

Service Manual 81

Installation
CVT Type
1) Connection of power supply
1. Connect the power supply cord to the independent power supply.
Circuit breaker is required.
2. Prepare the remote control.
Insert two batteries provided.
Remove the battery cover from the remote controller.
Slide the cover according to the arrow direction.
Insert the two batteries.
(Two "R03" or "AAA" dry-cell batteries or equivalent.)
Be sure that the (+) and (-) directions are correct.
Be sure that both batteries are new.
Re-attach the cover.
Slide it back into position.
3. Operate the unit for fifteen minutes or more.

2) Evaluation of the performance


1. Measure the temperature of the intake and discharge air.
2. Ensure the difference between the intake temperature and the discharge one is more than 8C
(Cooling) or reversely (Heating).

Thermometer

3) Selection of the slide switch according


to installation method
1. In case the indoor unit is installed on the floor,
please change the side switch which is on the
Main PCB Assembly to the 'BOTTOM' state.
2. In case the indoor unit is installed under the ceiling, please change the slide switch which is on
the Main PCB Assembly to the ' CEILING' state.
The initial state of the slide switch is set for
the bottom installation.

CN_INSTALL

CEILING BOTTOM

82 Multi type Air Conditioner

Installation
Ceiling Cassette Type
1) PRECAUTIONS IN TEST RUN
The initial power supply must provide at least 90% of the rated voltage.
Otherwise, the air conditioner should not be operated.
For test run, carry out the cooling operation first even during winter season. If heating operation is
Caution
carried out first, it leads to the trouble of compressor.
Carry out the test run more than 5 minutes without stopping.
(Test run will be cancelled 18 minutes later automatically)
The test run is started by pressing the room temperature checking button and down timer button for 3 seconds at the same time.
To cancel the test run, press any button.

CHECK THE FOLLOWING ITEMS WHEN INSTALLATION IS COMPLETE


After completing work, be sure to measure and record trial run properties, and store measured data, etc.
Measuring data are room temperature, outside temperature, suction temperature, blow out temperature,
air velocity, air volume, voltage, current, presence of abnormal vibration and noise, operating pressure, piping
temperature.
As to the structure and appearance, check following items.
Is the circulation of air adequate?
Is the drainage OK?
Is the heat insulation complete
(refrigerant and drain piping)?
Is there any leakage of refrigerant?

Does the romote controller works properly?


Is there any error on wiring?
Aren't terminal screws loosened?

M4......118N.cm{12kgf.cm} M5......196N.cm{20kgf.cm}
M6......245N.cm{25kgf.cm} M8......588N.cm{60kgf.cm}

Service Manual 83

Installation
5. Branch Distributor
PRECAUTIONS FOR SELECTING THE LOCATION
The BD unit is for indoor use. Install in a location such as above a ceiling or behind a wall in accordance with the
following conditions:
That the unit is fully supported, and is in a location with little or no vibration.
That the refrigerant pipes for the indoor and outdoor units can be repaired with ease, and that the units are
placed well within the distance from each other allowed by the pipe length.
That there is nothing nearby that produces heat or steam(gas).
When installing, that there is enough carity for servicing the unit.
Do not install in location that is hot or humid for long periods of time.
A well-ventilated area.
Do not install near bedrooms. The sound of refrigerant flowing through the piping may sometimes be audible.
For restrictions on installation, refer to "INSTALLATION".

System Layout and Piping Length


For installation of the indoor units. Follow the instructions in the installation manual for each unit.

System Layout
Distributor Unit
For 2 rooms : PMBD3620 (9.52, 6.35)
For 3 rooms : PMBD3630 (9.52, 6.35)
For 4 rooms : PMBD3640 (9.52, 6.35)
For 3 rooms : PMBD7230 (A: 12.7, 6.35)
(B: 15.88, 6.35)
(C: 15.88, 6.35)
Do not connect more than 8 indoor
units together choose the distributor
unit type (2rooms,3rooms or 4rooms)
according to the installation pattern

Branch
Distributor
A

Branch
Pipe
L1
L2

L3

L4

h2
Branch
Distributor

L5

L6

L7

L8

h1

Y Branch Pipe
- Included in outdoor unit
- Can not be purchased separately

Main Pipe

B
40K(6rooms)

84 Multi type Air Conditioner

48K~56K(7~8rooms)

Installation
Piping length and elevation
(m)

No.

Length

6 room

7 room

8 room

(1)

Total main piping length

A+B

50

50

50

(2)

Total branch piping length

L1+L2+L3+L4+L5+L6+(L7)+(L8)

50

60

60

(3)

Max. each branch piping length

L1, L2, L3, L4, L5, L6, L7,L8

15

15

15

(4)

Total system piping length

(Total main) + (Tatal branch)

100

110

120

(5)

Maxium Level in - out

h1

30

30

30

(6)

Maxium Level in - in

h2

10

10

10

Installation
This unit may be installed suspended from the ceiling or mounted on the wall.
This unit may only be installed horizontally , as shown in the diagram below. (Side B is facing up) However, it may
be freely installed in any direction, forward or backward, and to the sides.
Be sure to secure a 600mm square opening for service and inspection as shown in the diagram below, for both
ceiling - suspended installation and wall-mounted installation.
BD unit does not require drain treatment as it uses internal insulation.
Service direction is the side B and C
The piping for the indoor unit may be led around in direction A
The inclination of side B must be within 5 degree forward or backward or to the sides.

Min 30

(Servicing space)

9.52

(337)

250

(298)

19.05

Min 400
Min 400

(Side view)

(LEV service)

245
Suspension bolt pitch.

Main Pipe

30 50

432

(56) 50 50 50

Branch Pipe

300

60
Cover Control

C
(Controller service)

250 or more

72

600

(111)

(38) 50

(150)

(36) 50 50 50

Inspection opening
600
(Bottom view)

Service Manual 85

Installation

Installation of The Main Unit


NOTICE

This unit has two different installation types:


(1) Ceiling-suspended type and (2) wall-mounted type.
Choose the proper installation pattern according to the
location of installation.
The installation location for printed wiring board can be
changed.
Follow the procedure specified in the "CONNECTING
THE WIRING" section to change the location.
(1) Ceiling-suspended type

(1) Ceiling-suspended type

(2) Wall-mountde type

Procedure
(1) Fix the fumished hanger metal with two screws.(4 locations in total).
(2) Using an insert-hole-in- anchor, hang the hanging bolt.
(3) Install a hexagon nut and a flat washer (locally-procured)to the hanging bolt as
shown in the figure in the left, and ift the main unit to hang on the hanger metal.
(4) After checking with a level that the unit is level, tighten the hexagon nut.
* The tilt of the unit should be within 5 in front/back and left/right.

BD unit
Six-sided Nut
(M10 or M8)

15.00

Hanger metal
Flat washer

Hanging bolt
(M10 or M8)

(2) Wall-mounted type


Procedure
(1) Fix the fumished hanger metal with two screws.
(3 locations in total).
Screws(M5)
(locally procude)

(2) After checking with a level that the unit is level, fix the unit with the
furnished wood screws.
* The tilt of the unit should be within 5 in front/back and left/right.
* Block up the parts of hanger holes (2 places) by using insulation
PE after installing the hanger.

CAUTIONS
Once a screw-hole on the main unit has had a screw hammered in, make sure to either hammer it again or cover it with
alumium tape.(This is to prevent condensation)
Be sure to install the unit with the ceiling-sie up.
Do not install near bedrooms. the sound of refrigerant flowing through the piping may sometimes be audible.

86 Multi type Air Conditioner

Installation

Connection of Piping
When connecting indoor units, make sure to connect refrigerant pipes and connection wires to the appropriate connection ports maked with matching alphabets. (A, B, C, D)
NOTICE

Be sure to mark all the local refrigerant piping(liquid


pipes, gas pipes, etc.) for each indoor unit designating
clearly which room it belongs in.(A, B, C, D)

:
For flaring work the piping, follow the instructions in the installation manual to each unit.
NOTICE

Connecting the pipings to the indoor unit


and drain hose to drain pipe
1. Align the center of the pipings and sufficiently tighten
the flare nut by hand.

BD Unit Socket

Flare nut

Pipes

2. Tighten the flare nut with a wrench.


Outside diameter
mm
inch
6.35
1/4
9.52
3/8
12.7
1/2
15.88
5/8
19.05
3/4

Torque
kg.m
1.8
4.2
5.5
6.6
6.6

Wrap the insulation material around the


connecting portion.
1. Overlap the connection pipe insulation material and
the indoor unit pipe insulation material. Bind them
together with vinyl tape so that there is no gap.
2. Wrap the area which accommodates the rear piping
housing section with vinyl tape.

Open-end wrench (fixed)


Flare nut
Wrench

Connection pipe

BD Unit Socket

Indoor unit pipe

BD Unit

Wrap with vinyl tape


Vinyl tape (wide)
Connecting cable
Pipe
Vinyl tape(narrow)

Close up a socket for unoccupied room


with a brass cap.
1. Align the center of the piping and sufficiently tighten
the brass cap by hand.
2. Tighten the brass cap with a wrench.

BD Unit Socket Brass cap Pipe sealed


or welded

3. Wrap the joint part with insulation.


CAUTIONS
Never use the plastic cap for sealing.
Make sure to use brass cap with the end of
pipe sealed or welded tightly.

Service Manual 87

Installation

Connection of Wiring
Connect refrigerant pipes and connection wires to the appropriate ports maked with matching alphabets (A, B and
C) on this unit.
Follow the instructions on the wiring nameplate to connect the connection wires of indoor/outdoor units to terminal
board numbers.(1, 2 and 3) Always fix each ground wire separately with a ground screw.(See the figure below.)
After completing the wiring, fix the outer coating of wires securely with wire clamps. The wire clamp on indoor unit
side is furnished. Follow the procedure below to install.
Refer to the circuit diagram on the control cover inside outdoor unit.

:
The terminal board numbers are arranged from top to bottom in order of 1, 2 and 3.
NOTICE

In Case of 3 rooms
Warning

C room

Do not use tapped wires, stand wires,


extensioncords, or starbust connections, as they may cause overtheating,
electrical shock, or fire.

B room

A room

C
CN-PWR

Connection wire for indoor units


(H05VV, 4wires, 0.75mm)

Connection wire for outdoor units


(H05RV, 4wires, 1.2mm)

(1) Remove the control cover. Loosen the two screws,


and slide thecover in thedirection of thearrow.

(3) Put in the cover in the direction of the arrow then


tighten the screws.

(2) Perform wiring with reference the wiring diagram on


a control cover of outdoor unit. Allow 300 mm for the
pulling-out section of harness. Fix the wires completely with wire clamps(4 locations).

88 Multi type Air Conditioner

Operation

Operation
Function of control
1. MAIN UNIT FUNCTION
DISPLAY
Operation Indicator
On while in appliance operation, off while in appliance pause
Flashing while in disconnection or short in Thermistor (3 sec off / 0.5 sec on)
Sleep Timer Indicator
On while in sleep timer mode, off when sleep timer cancel or appliance operation pause
Timer Indicator
On while in timer mode (on/off), off when timer mode is completed or canceled
Defrost Indicator
Off except when hot start during heating mode operation or while in defrost control

Cooling Mode Operation


When the intake air temperature reaches 0.5C below the setting temp, the compressor and the outdoor fan
stop.
When it reaches 0.5C above the setting temp, they start to operate again.
Compressor ON Temp
Setting Temp+0.5C
Compressor OFF Temp
Setting Temp-0.5C
While in compressor running, operating with the airflow speed set by the remote control. While compressor is
off fan operates at low speed regardless of the setting.

Soft Dry Operation Mode


When the dehumidification operation input by the remote control is received, the intake air temperature is
detected and the setting temp is automatically set according to the intake air temperature.
26C Intake Air Temp
25C
24C Intake Intake Air Temp<26C
Intake Air Temp-1C
18C Intake Intake Air Temp<24C
Intake Air Temp-0.5C
Intake Air Temp<18C
18C
While compressor off, the indoor fan repeats low airflow speed and stop.
While the intake air temp is between compressor on temp. and compressor off temp., 10-min dehumidification
operation and 4-min compressor off repeat.
Compressor ON Temp.
Setting Temp+0.5C
Compressor OFF Temp. Setting Temp-0.5C
In 10-min dehumidification operation, the indoor fan operates with the low airflow speed.

Heating Mode Operation


When the intake air temp reaches +3above the setting temp, the compressor is turned off. When below the
setting temp, the compressor is turned on.
Compressor ON Temp.
Setting Temp.
Compressor OFF Temp. Setting Temp.+3C
While compressor on, the indoor fan is off when the indoor pipe temp. is below 20C, when above 27C , it

Service Manual 89

Operation
operates with the low or setting speed. When the indoor pipe temp is between 20C and 27C, it operates with
Super-Low(while in sleep mode, with the medium airflow speed).
While compressor off, the indoor fan is off when the indoor pipe temp is below 33C, when above 35C , it
operates with the low airflow speed.
While in defrost control, the indoor is outdoor fans are turned off.

Defrost Control(Heating)
Defrost operation is controlled by timer and sensing temperature of outdoor pipe.
The first defrost starts only when the outdoor pipe temperature falls below -6C after 35 minutes passed from
starting of heating operation and more than 4 minutes operation of compressor.
Defrost ends after 12 minutes passed from starting of defrost operation when the outdoor pipe temperature
rises over 15C even before 12 minutes.
The second defrost starts only when the outdoor pipe temperature falls below -6C after 35 minutes passed
from ending of the first defrost and more than 4 minutes operation of compressor.

Fuzzy Operation
When any of operation mode is not selected like the moment of the power on or when 3 hrs has passed since
the operation off, the operation mode is selected.
When determining the operation mode, the compressor, the outdoor fan, and the 4 way valve are off and only
the indoor fan is operated for 15 seconds. Then an operation mode is selected according to the intake air
temp at that moment as follows.
24C Inatake Air Temp
Fuzzy Operation for Cooling
21C Inatake Air Temp<24C
Fuzzy Operation for Dehumidification
Inatake Air Temp<21C
Fuzzy Operation for Heating
If any of the operation modes among cooling / dehumidification / heating mode operations is carried out for 10
sec or longer before Fuzzy operation, the mode before Fuzzy operation is operated.
1) Fuzzy Operation for Cooling
According to the setting temperature selected by Fuzzy rule, when the intake air temp is 0.5C or more below
the setting temp, the compressor is turned off. When 0.5C or more above the setting temp, the compressor is
turned on.
Compressor ON Temp
Setting Temp +0.5C
Compressor OFF Temp
Setting Temp + 0.5C
At the beginning of Fuzzy mode operation, the setting temperature is automatically selected according to the
intake air temp at that time.
26C Intake Air Temp
25C
24C Intake Air Temp<26C
Intake Air Temp + 1C
22C Intake Air Temp<24C
Intake Air Temp + 0.5C
18C Intake Air Temp<22C
Intake Air Temp
Intake Air Temp<18C
18C
When the Fuzzy key (Temperature Control key) is input after the initial setting temperature is selected, the
Fuzzy key value and the intake air temperature at that time are compared to select the setting temperature
automatically according to the Fuzzy rule.
While in Fuzzy operation, the airflow speed of the indoor fan is automatically selected according to the temperature.

90 Multi type Air Conditioner

Operation
2) Fuzzy Operation for Dehumidification
According to the setting temperature selected by Fuzzy rule, when the intake air temp is 0.5C or more below
the setting temp, the compressor is turned off. When 0.5C or more above the setting temp, the compressor
is turned on.
Compressor ON Temp
Setting Temp + 0.5C
Compressor OFF Temp
Setting Temp+0.5C
At the beginning of Fuzzy mode operation, the setting temperature is automatically selected according to the
intake air temp at that time.
26C Intake Air Temp
25C
24C Intake Air Temp<26C
Intake Air Temp+1C
22C Intake Air Temp<24C
Intake Air Temp+0.5C
18C Intake Air Temp<22C
Intake Air Temp
Intake Air Temp<18C
18C
When the Fuzzy key (Temperature Control key) is input after the initial setting temperature is selected, the
Fuzzy key value and the intake air temperature at that time are compared to select the setting temperature
automatically according to the Fuzzy rule.
While in Fuzzy operation, the airflow speed of the indoor fan repeats the low airflow speed or pause as in
dehumidification operation.
3) Fuzzy Operation for Heating
According to the setting temperature selected by Fuzzy rule, when the intake air temp is 3C or more above
the setting temp, the compressor is turned off. When below the setting temp, the compressor is turned on.
Compressor ON Temp
Setting Temp
Compressor OFF Temp
Setting Temp + 3C
At the beginning of Fuzzy mode operation, the setting temperature is automatically selected according to the
intake air temp at that time.
20CIntake Air Temp
Intake Air Temp + 0.5C
Intake Air Temp<20C
20C
When the Fuzzy key (Temperature Control key) is input after the initial setting temperature is selected, the
Fuzzy key value and the intake air temperature at that time are compared to select the setting temperature
automatically according to the Fuzzy rule.
While in Fuzzy operation, the airflow speed of the indoor fan is set to the high or the medium according to the
intake air temperature and the setting temperature.

Airflow Speed Selection


The airflow speed of the indoor fan is set to high, medium, low, or power (auto) by the input of the airflow
speed selection key on the remote control.

On-Timer Operation
When the set time is reached after the time is input by the remote control, the appliance starts to operate.
The timer LED is on when the on-timer is input. It is off when the time set by the timer is reached.
If the appliance is operating at the time set by the timer, the operation continues.
While in Fuzzy operation, the airflow speed of the indoor fan is automatically selected according to the temperature.

Off-Timer Operation
When the set time is reached after the time is input by the remote control, the appliance stops operating.
The timer LED is on when the off-timer is input. It is off when the time set by the timer is reached.
If the appliance is on pause at the time set by the timer, the pause continues.

Service Manual 91

Operation
Off-Timer <=> On-Timer Operation
When the set time is reached after the on/off time is input by the remote control, the on/off-timer operation is
carried out according to the set time.

Sleep Timer Operation


When the sleep time is reached after <1,2,3,4,5,6,7,0(cancel) hr> is input by the remote control while in appliance operation, the operation of the appliance stops.
While the appliance is on pause, the sleep timer mode cannot be input.
While in cooling mode operation, 30 min later since the start of the sleep timer, the setting temperature
increases by 1C. After another 30 min elapse, it increases by 1C again.
When the sleep timer mode is input while in cooling cycle mode, the airflow speed of the indoor fan is set to
the low.
When the sleep timer mode is input while in heating cycle mode, the airflow speed of the indoor fan is set to
the medium.

Chaos Swing Mode


By the Chaos Swing key input, the upper/lower vane automatically operates with the Chaos Swing or they are
fixed to the desired direction.
While in Chaos Swing mode, the angles of cooling and heating cycle operations are different.

Chaos Natural Wind Mode


When the Chaos Natural Wind mode is selected and then operated, the high, medium, or low speed of the airflow mode is operated for 2~15 sec. randomly by the Chaos Simulation.

Jet Cool Mode Operation


While in heating mode or Fuzzy operation, the Jet Cool key cannot be input. When it is input while in the
other mode operation (cooling, dehumidification, ventilation), the Jet Cool mode is operated.
In the Jet Cool mode, the indoor fan is operated at super-high speed for 30 min at cooling mode operation.
In the Jet Cool mode operation, the room temperature is controlled to the setting temperature, 18C.
When the sleep timer mode is input while in the Jet Cool mode operation, the Jet Cool mode has the priority.
When the Jet Cool key is input, the upper/lower vanes are reset to those of the initial cooling mode and then
operated in order that the air outflow could reach further.

Auto Restarting Operation


When the power is restored after a sudden power failure while in appliance operation, the mode before the
power failure is kept on the memory and the appliance automatically operates in the mode on the memory.

92 Multi type Air Conditioner

Operation
Forced Operation
To operate the appliance by force in case that the remote control is lost, the forced operation selection switch
is on the main unit of the appliance to operate the appliance in the standard conditions.
When the power is supplied while the slide switch is on the forced operation position, or when the slide switch
position is switched to the Auto Restarting (or test operation) position or switched from the remote control
position to the forced operation position while the power is on, the forced operation is carried out.
When the slide switch position is switched from the forced operation position to the Auto Restarting position or
the remote control position, the forced operation is canceled and the appliance stops operating.
In the forced operation mode, the indoor fan is operated at low speed for around 15 sec and then the operation condition is set according to the intake air temperature as follows.
24CIntake Air Temp
Cooling Mode Operation, 22C, High Speed
21CIntake Air Temp<24C
Dehumidification Operation, 23C, High Speed
Intake Air Temp<21C
Heating Mode Operation, 24C, High Speed

Buzzer Sounding Operation


When the appliance-operation key is input by the remote control, the short "beep-beep-" sounds.
When the appliance-pause key is input by the remote control, the long "beep" sounds.

Service Manual 93

Operation

Function of Indoor Unit


Split Type Indoor Unit
Operation ON/OFF by Remote controller
Sensing the Room Temperature
Room temperature sensor. (THERMISTOR)
Room temperature control
Maintains the room temperature in accordance with the Setting Temp.
Starting Current Control
Indoor fan is delayed for 5 seconds at the starting.
Time Delay Safety Control
Restarting is delayed for approx. 3 minutes.
Indoor Fan Speed Control
High, Med, Low, Chaos
Operation indication Lamps (LED)
--- Lights up in operation
--- Lights up in Sleep Mode
--- Lights up in Timer Mode
--- Lights up in Deice Mode

Soft Dry Operation Mode


Intermittent operation of fan at low speed.
Sleep Mode Auto Control
The fan is switched to low(Cooling), med(Heating) speed.
The unit will be stopped after 1, 2, 3, 4, 5, 6, 7 hours.
Natural Air Control by CHAOS Logic
The fan is switched to intermittent or irregular operation
The fan speed is automatically switched from high to low speed.
* Airflow Direction Control
The louver can be set at the desired position or swing
up and down automatically.(Model base)
"Wall Mounted Type is standard"
* Functions is dependent on model type.

94 Multi type Air Conditioner

Deice (defrost) control (Heating)


Both the indoor and outdoor fan
stops during deicing.
Hot start after deice ends.
Hot-start Control (Heating)
The indoor fan stops until the
evaporator piping temperature will
be reached at 27C.

Operation
Art Cool Type Indoor Unit
Operation ON/OFF by Remote controller
Sensing the Room Temperature
Room temperature sensor. (THERMISTOR)
Room temperature control
Maintains the room temperature in accordance with the Setting Temp.
Starting Current Control
Indoor fan is delayed for 5 sec at the starting.
Time Delay Safety Control
Restarting is inhibited for approx. 3 minutes.
Indoor Fan Speed Control
High, Med, Low, CHAOS, JET COOL
Operation indication Lamps (LED)
--- Lights up in operation
--- Lights up in Sleep Mode
--- Lights up in Timer Mode
--- Lights up in Defrost Mode (for Heating Model)
OUTDOOR--- Lights up in compressor operation (for Cooling Model)
Soft Dry Operation Mode
Intermittent operation of fan at low speed.
Sleep Mode Auto Control
The fan is switched to low(Cooling), med(Heating) speed.
The unit will be stopped after 1, 2, 3, 4, 5, 6, 7 hours.
Natural Air Control by CHAOS Logic
The fan is switched to intermittent or irregular operation
The fan speed is automatically switched from high to low speed.
Airflow Direction Control
The louver can be set at the desired position or swing
up and down automatically.

PLASMA
The function will be operated while in any
operation mode with selecting the function.
The function is to be stopped while it is
operating with selecting the function.
Defrost(Deice) control (Heating)
Both the indoor and outdoor fan stops during defrosting.
Hot-start Control (Heating)
The indoor fan stops until the
evaporator pipe temperature will be reached
at 28C.

Service Manual 95

Operation
Art Cool Deluxe Type Remote Controller
Operation ON/OFF

Operation Mode Selection


Cooling Operation Mode.(
(Cooling
(Heating
model only) model only)

Healthy Dehumidification Operation Mode.(

Auto Operation Mode.(


) Heating Operation Mode.(

)
)

Fan Speed Selection


(Low)

(Med)

(High)

Room, Temperature Checking

: (High:39C

Low:11C)

Temperature Setting
TEMPERATURE

LOW

HIGH

Cooling

Down to 18C
Up to 30C

Heating

Down to 16C
Up to 30C

JET COOL

Setting the Time or Timer

Timer Selection

: OFF, ON, OFF


ON

ON

OFF

Timer Setting
SET

Timer Cancel
CANCEL

: Cancel Sleep Mode, Timer ON or Timer OFF

Sleep Operation

: 1, 2, 3, 4, 5, 6, 7, Off Timer
Airflow Direction Control
2nd F
Air Circulation

: Fan Operates without cooling or heating.


Horizontal Airflow Direction Control Button(Optional)

96 Multi type Air Conditioner

Reset

Operation

Duct Type Remote Controller


Operation ON/OFF

Operation Mode Selection

(Cooling
(Heating
model only) model only)

Cooling Operation Mode (


Heating Operation Mode (

Soft Dry Operation Mode (


Auto Operation Mode (
)

)
)

Fan Speed Selection

LO (Low)

MED (Med)

HI (High)

Room Temperature Display


: High:39C LOW:11C
Temperature Setting
Cooling

Down to 18C
Up to 30C

Heating

Down to 16C
Up to 30C

Setting the Timer


Timer

Cancel

Weekly Program
Program

Week

Hour

Min

Holiday

SET/CLR

Fan Operation Mode

: Fan Operates without cooling & heating

Phase Control Setting


Timer

Service Manual 97

Operation

CST Type Remote Controller


Operation ON/OFF

Operation Mode Selection

(Cooling
(Heating
model only) model only)

Cooling Operation Mode (


Heating Operation Mode (

)
)

Soft Dry Operation Mode (


Auto Operation Mode (
)

Fan Speed Selection

SLO (Super Low)

LO (Low)

MED (Med)

HI (High)

Room Temperature Display


: High:39C LOW:11C
Temperature Setting
Cooling

Down to 18C
Up to 30C

Heating

Setting the Timer


Timer

Cancel

Weekly Program
Program

Week

Holiday

: Fan Operates without cooling & heating


SET/CLR
Hour

Min

Fan Operation Mode

98 Multi type Air Conditioner

Down to 16C
Up to 30C

JET

AUTO

Operation

Convertible Type Remote Control


Operation ON/OFF

Operation Mode Selection


Cooling Operation Mode.(
(Cooling
(Heating
model only) model only)

Healthy Dehumidification Operation Mode.(

Auto Operation Mode.(


) Heating Operation Mode.(

)
)

Fan Speed Selection


(Low)

(Med)

(High)

(CHAOS)

Heating

Down to 16C
Up to 30C

Room, Temperature Checking

: (High:39C

Low:11C)

Temperature Setting
TEMPERATURE

LOW

HIGH

Cooling

Down to 18C
Up to 30C

JET COOL

PLASMA(Optional)

Setting the Time or Timer

Timer Selection
ON

OFF

: OFF, ON, OFF

ON

Timer Setting
SET

Timer Cancel
CANCEL

: Cancel Sleep Mode, Timer ON or Timer OFF

Sleep Operation

: 1, 2, 3, 4, 5, 6, 7, Off Timer
Airflow Direction Control

Air Circulation

: Fan Operates without cooling or heating.


Horizontal Airflow Direction Control Button(Optional)

2nd F
Reset

Service Manual 99

Operation

Function of Outdoor Unit


Outdoor Unit
Two Comp algorithm
Inverter Comp is first priority and then Constant Comp is turning on responding to load condtion.
Operating Frequency
Inverter Frequency varies considering condition such as room temp,outdoor temp, operating room
number,Temp gap between room temp and set temp and so on.
LEV Control
LEV pulse is modulated to keep constant superheat or subcooling.
Out door Fan Control
Outdoor fan operates at High/Low or Off to respond to the load condition.
R/Valve Control
Convert R/Valve to change cooling to heating, heating to cooling.
Comp Pre-Heat Logic
Checking outdoor temp, D-Pipe temp,Heat Sink Temp, operate compressor at low frequency upto
5min to preheat oil.
Defrost Function
After 35 min heating operation, check the defrost condition and if outdoor pipe temp is below -6C and
released from deice operation in case outdoor pipe temp is over 15C or 7 min cooing mode.
To deice outdoor heat exchanger in low temp condtion, convert operating mode from heating to
cooling, in this case, indoor and outdoor fan is off.
Oil Return System
In heating operation, every 3 hours, changes from heating to cooling for 5 min to return the oil in piping
to compressor.
IPM Over Heat Protection
To protect IPM overheat, down comp Hz.
Comp Overload Protection
To protect comp from being overload, down comp Hz.
Low Pressure Protection
If cylce pressure is low (around 0.3kgf/cm2), turn off comp and outdoor fan.

100 Multi type Air Conditioner

Operation

Remote Control Operation


The Remote Controller transmits the signals to the system.

START/STOP BUTTON
Operation starts when this button is pressed and
stops when the button is pressed again.

OPERATION MODE SELECTION BUTTON


Used to select the operation mode.

ROOM TEMPERATURE
SETTING BUTTONS
Used to select the room temperature.

INDOOR FAN SPEED SELECTOR


Used to select fan speed in four steps
low, medium, high and CHAOS.

JET COOL
Used to start or stop the speed cooling/heating.
(Speed cooling/heating operates super high fan
speed.)

CHAOS SWING BUTTON


Used to stop or start louver movement and set the
desired up/down airflow direction.

ON/OFF TIMER BUTTONS


Used to set the time of starting and stopping operation.

TIME SETTING BUTTONS


Used to adjust the time.

TIMER SET/CANCEL BUTTON


Used to set the timer when the desired time is
obtained and to cancel the Timer operation.

Signal transmitter

5
6

1
3

4
2
7
11
8
13

10
CANCEL
ON

OFF

9
16

SET
AUTO CLEAN

12
15

14

17
Flip-up door
(opened)

10 SLEEP MODE AUTO BUTTON


Used to set Sleep Mode Auto operation.

Operation Mode

11 AIR CIRCULATION BUTTON


Used to circulate the room air without cooling or
heating.

Cooling Operation

12 ROOM TEMPERATURE CHECKING BUTTON

Auto Operation

Used to check the room temperature.

13 PLASMA(OPTIONAL)

Healthy Dehumidification Operation

Used to start or stop the plasma-purification function.

Heating Operation

Cooling Model(

), Heat Pump Model(

14 RESET BUTTON
Initialize remote controller.

15 2nd F Button
Used prior to using modes printed in blue at the bottom of buttons.

16 AUTO CLEAN (Model Base)


Used to set Auto Clean mode.

17 HORIZONTAL AIRFLOW DIRECTION CONTROL


BUTTON (OPTIONAL)
Used to set the desired horizontal airflow direction.

Service Manual 101

Operation

Duct Type Remote Controller


AUTO SWING

OPERATION

SET TEMP
Room Temp

Operation unit
03

SUB FUNCTION

AUTO Heater Preheat


JET Defrost Humidify
Filter Out door
ZONE
1 2 3 4

HI
MED
LO

Time
Timer

On Off
Set no. Time 01

FAN SPEED

Program set
05

07

09

11

13

15

17

19

21

23

3
Signal
receiver
7
8
9
10
11
12

2
Timer

Cancel

Program

Week

Hour

Min

5
6
4

Holiday

14

SET/CLR
RESET

15

13

Operation display
Displays the operation conditions.

On/Off Button
Operation starts when this button is pressed, and
stops when the button is pressed again.

Timer Set Button


Used to set the timer when the desired time is
obtained.

Week Button
Used to set a day of the week.

Set Temperature Button


Used to set the temperature when the desired
temperature is obtained.

10

Program Button
Used to set the weekly timer.

11

FAN Operation Button


Used to circulate room air without cooling or heating.

Holiday Button
Used to set a holiday of the week.

12

Time Set Button


Used to set the time of the day and change the
time in the weekly timer Function.

13

Set and Clear Button


Used to set and clear the weekly timer.

14

Room Temperature Checking Button


Used to check the room temperature.

15

Reset Button
Used to set the current time and clear the setting
time.

Fan Speed Button


Used to set desired fan speed.

Operation Mode Selection Button


Used to select the operation mode.
Auto Operation Mode.
Cooling Operation Mode.
Soft Dry Operation Mode.
Heating Operation Mode.(except cooling model)

Timer Cancel Button


Used to cancel the timer.

102 Multi type Air Conditioner

Operation

CST Type Remote Controller


1Way

AUTO SWING

OPERATION

SET TEMP
Room Temp

Timer

Operation unit

On Off
Set no. Time 01

03

2ndF

Time

No Func

Program set

05

07

09

11

FAN SPEED

SUB FUNCTION

AUTO Heater Preheat


JET Defrost Humidify
SLO Filter Out door
ZONE
1 2 3 4

HI
MED
LO

13

15

17

19

21

Heat Pump Model

23

3
4Way,1Way(06 Model)

17
10
11
12
13
14
15

2
Timer

Cancel

2ndF

Program

Week

Holiday
Plasma
Set/Clr

Hour

Min

16
18

1 Operation display

Displays the operation conditions.


2 On/Off Button

Operation starts when this button is pressed, and


stops when the button is pressed again.
3 Set Temperature Button

4
5

7
8

RESET

Cooling Model

4
7
8
9

9 Plasma Air Clean Button (Option)/Heater(Option)


10 Timer Cancel Button

Used to cancel the timer.


11 Timer Set Button

Used to set the timer when the desired time is


obtained.

Used to set the temperature when the desired temper12 Week Button
ature is obtained.
Used to set a day of the week.
FAN Operation Button
13 Program Button
Used to circulate room air without cooling or heating.
Used to set the weekly timer.
Fan Speed (Jet Cool Button: 4 Way)
14 Holiday Button
Used to set the desired fan speed or select Jet cool
Used to set a holiday of the week.
mode.
15 Time Set Button
Operation Mode Selection Button
Used to set the time of the day and change the time in
Used to select the operation mode.
the weekly timer Function.
Auto Operation Mode
16 Set and Clean/Ventilation(Option)
Cooling Operation Mode
Used to set and clear the weekly timer.
Soft Dry Operation Mode
Heating Operation Mode(except cooling model)
17 Swirl Button (4 Way)
Used to select swirl mode.
Auto Swing Button
Jet Cool Button
Used to swing up and down/right and left(option)
Auto Swing Button(1 Way 06 Model)
Room Temperature Checking Button/Filter sign
18 Reset Button
Release(Option)
Used to set the current time and clear the setting time.
Used to check the room temperature.

Display temperature can be different from actual room temperature if the remote controller is installed at the
place where sun-rays are falling directly or the place nearby heat source.
Note : 06 Model - AMNH09GTCC0, AMNH12GTCC0

Service Manual 103

Operation
1) Two Thermistor System
(1) Open the rear cover of the wired remote-controller to set the mode.
(2) Select one of three selectable modes as follows.
Position 1:
The room temperature is controlled by the thermistor of the main body.
Position 2:
The room themperature is controlled by the thermistor of the wired remote-controller, control the
temperature according to the position of wired remote-controller.
Position 3:
The room temperature is controlled by lower temperature between the temperature of main body and of
remote-controller sensor.
(3) Move the slide switch to set position.

Room Temp. sensor


Slide switch for 2 Thermistor
TH

R14H OP3
SW TH

REMO
MAIN
2TH

OP2

REMO
MAIN
2TH

R12H

CO1H

OP1
R19H
R11H

OP5R16H

OP4

R15H

OP7
R18H

R17H
OP6
LO
STAND

C070

Position 2
Position 1
Position 3

R13H

R03S

HI
R04S
HIGH

R01S

R02S

SW

(4) Close the rear cover and check if it works normally.

CAUTION: Select the position after counselling with a customer.


In case of cooling mode, room temperature is controlled by the
main body sensor.
To control the room temperature by a wired remote controller,
install controller(room temp. sensor) to sense the temperature
more accurately.
Maunfactured in the position 1.

104 Multi type Air Conditioner

Operation
2) Group Control(Optional Wiring)
You can use a group control operation after connecting the brown and yellow wire of each air-conditioner.
Remove the resistor "OP 7" in remote controller.
It operates maximum 16 Units by only one Wired Remote Controller,
and each Unit starts sequentially to prevent overcurrent.

Wiring design

Main PCB

RED(12V)
YL(SIGNAL)
BR(GND)

Indoor Unit 1

Indoor Unit 2

Terminal(Local Supply)
Block
Connector

Terminal(Local Supply)
Block
Connector

RED(12V)
YL(SIGNAL)
BR(GND)

Main PCB
#1

YL(SIGNAL)
BR(GND)

YL(SIGNAL)
BR(GND)

Indoor Unit 16
Terminal(Local Supply)
Block
Connector

Main PCB
#2

....

....

AUTO SWING

OPERATION

SET TEMP
Room Temp

Operation unit
03

FAN SPEED
HI
MED
LO

Time
Timer

On Off
Set no. Time 01

ZONE

Slide Switch

SUB FUNCTION

AUTO Heater Preheat


JET Defrost Humidify
Filter Out door
1 2 3 4

Program set
05

07

09

11

13

15

17

19

21

23

Wired Remote Controller

YL(SIGNAL)
BR(GND)

YL(SIGNAL)
BR(GND)

Main PCB
#16

Connecting Cable(Local Supply)

OP7
Remote
Controller
PCB

Features
Use Only One Wired Remote Controller with several air conditioners(max. 16 Units)
Random starting to prevent overcurrent.

CAUTION: Be careful not to exchange the color of wires.


The maximum length of connecting wire should be below
200m(25) on connecting each units.
Use a wire more than 0.5mm2

Service Manual 105

Operation
3) E.S.P.(External Static Pressure) Setting
(1) Open the rear cover of the wired remote-controller to set the mode.
(2) Select one of three selectable modes as follows.
Without Zone System
1. Position V-H, F-H:
This position sets the maximum E.S.P as a default set.
2. Position V-L:
This position sets the minimum E.S.P as a default set.
With Zone System
1. Position V-H:
Maximum E.S.P setting & Fan speed is varied according to the state of dampers by micom.
2. Position F-H:
Maximum E.S.P setting & Fan speed doesn't vary according to the opening & Closing of dampers.
3. Position V-L:
Minimum E.S.P setting & Fan speed is varied according to the state of dampers by micom.
* Maximum : 8mmAq
Minimum : 0mmAq
(3) Move the slide switch to set position.

TH

R14H OP3
SW TH

V-H

R13H

OP2

REMO
MAIN
2TH

OP1
R19H
R11H

OP7
R18H
OP6

STAND

C070

LO

R03S

HI
R04S

(4) Close the rear cover and check if it works normally.

106 Multi type Air Conditioner

HIGH

R02S

SW

Slide switch for ceiling height

CO1H

R17H

F-H
V-L

R12H

R01S

OP5R16H

OP4

R15H

Operation
4) How to Set E.S.P?
Procedure of RPM change:
Ex) External Static pressure is 4mmAq for Model 36K.
To protect the unit, compressor is designed to be off during E.S.P. setting.

Push the"On/Off"button.
The unit will start.
AUTO SWING

OPERATION

SET TEMP

FAN SPEED

Room Temp

HI
MED
LO

Time
Operation unit
Set no. Time 01

03

ZONE

Program set
05

07

09

11

13

15

17

19

21

23

Push the "Timer" and "Wind" button simultaneously for more then 3 seconds.
Timer

AUTO SWING

OPERATION

SET TEMP
Room Temp

FAN SPEED
HI
MED
LO

Time
Operation unit
Set no. Time 01

SUB FUNCTION

AUTO Heater Preheat


JET Defrost Humidify
Filter Out door

03

SUB FUNCTION

AUTO Heater Preheat


JET Defrost Humidify
Filter Out door

ZONE

Program set
05

07

09

11

13

15

17

19

21

23

Push the "Up" of "Down" button for E.S.P adjustment.


And, adjust the number which you want.(In this example, the number is "225". Refer to the
table 1 on the next page.)
AUTO SWING

OPERATION

SET TEMP
Room Temp

FAN SPEED

AUTO Heater Preheat


JET Defrost Humidify
Filter Out door
ZONE
2

Time
Operation unit
Set no. Time 01

03

SUB FUNCTION

HI
MED
LO

Program set
05

07

09

11

13

15

17

19

21

23

Note: The range of selection is from 1~254. Since, the display is two Digit only.
If the range selection is above 100 then the third digit will appear in the screen as shown.

Shift the fan speed mode by pressing the fan speed button.
And then, Adjust numbers of next steps by repeating the stage 3.
(In this example, the numbers are "237" and "243" respectly)

Push the "Timer" and "Wind" button simultaneously for more than 3 seconds.
Then, Wind Data is memorized by the EEPROM of the main PCB.
AUTO SWING

OPERATION

SET TEMP
Room Temp

HI
MED
LO

Timer
Time
Operation unit
Set no. Time 01

03

FAN SPEED

SUB FUNCTION

AUTO Heater Preheat


JET Defrost Humidify
Filter Out door

ZONE

Program set
05

07

09

11

13

15

17

19

21

23

Service Manual 107

Operation

Duct ESP control table


Chassis

Static Pressure(mmAq)

Ca(Btu/h)

12K

18K

Chassis

8 CMM

220

215

210

7 CMM

240

235

230

6 CMM

255

250

245

10 CMM

175

170

150

9 CMM

200

190

185

8 CMM

220

215

210

14 CMM

170

150

130

13 CMM

185

165

145

12 CMM

220

180

160

Step(Hi/Med/Lo)

Setting Value

10.5 CMM

225

220

210

9 CMM

245

240

230

8.5 CMM

254

253

250

11.5 CMM

210

200

100

10 CMM

235

230

220

8.5 CMM

254

215

245

9K

BP
12K

Chassis

Static Pressure(mmAq)

Ca(Btu/h) Step(Hi/Med/Lo)
18K

BH
24K

Chassis

36K

10

Setting Value
235

230

225

215

180

14.5 CMM

245

238

235

230

215

13 CMM

254

252

248

245

240

18 CMM

220

205

190

170

16.5 CMM

235

230

220

200

100

14 CMM

250

240

235

230

210

10

Ca(Btu/h) Step(Hi/Med/Lo)

BG

16.5 CMM

Static Pressure(mmAq)

30K

Setting Value

Static Pressure(mmAq)

Ca(Btu/h)

Step(Hi/Med/Lo)

9K

BT

Setting Value

26.5 CMM

153

150

150

148

130

23 CMM

173

173

175

175

170

155

20 CMM

195

195

193

193

190

190

32 CMM

230

230

225

220

150

29 CMM

240

238

237

235

230

220

26.5 CMM

245

245

243

243

240

240

108 Multi type Air Conditioner

Control Devices and Function

Control Devices and Function


Simple Central Control
Features
Easy operation button.
Independent operation for 16 indoor units each.
Simultaneous turn ON/OFF for all of indoor units connected.
Easy change operation mode to cooling or heating
Set and clear lock-mode for each indoor unit
Simultaneously set and clear lock-mode for all of indoor units
connected.
Display function for all of indoor units connected.

Term of Each part and Function


On/Off display LED
(TOTAL 16EA)

Individual On/Off button


Control ON/OFF of a unit.

On pressing individual on/off


button, display the present
operation state.
-Operation : green.
-Stop : off
-Error mode : blinking

Power display LED


Indicate the state of DC
Power supply in central
control unit.
- On : red(Heating), green(Cooling)
- Off : no signal
- Error mode : blinking with red color

TOTAL Off button


Stop all linked units sequentially.

TOTAL On button
Operate all linked units sequentially.

Service Manual 109

Control Devices and Function

Electrical wiring
PICTORIAL VIEW OF THE CONNECTION

Outdoor
Outdoor unit
unit
PI485

: PNF-P14A0M

MAIN PCB
L

PI485

MAIN PCB

Control Box

CN_CENTRAL

MAIN PCB
N

CN_CENTRAL

10
G
A
B

PI485

CENTRAL
CONTROL
UNIT

VCC
GND
C
D

CN OUT

Special purchase: Central control, PI485(PNF-P14A0M)

ONE SIMPLE CENTRAL CONTROL CONNECTION


INDOOR UNIT 1

INDOOR UNIT

INDOOR UNIT 2

SET The Address(Group No. & Indoor No.)

INDOOR UNIT 3

OUTDOOR
MAIN PCB

INDOOR UNIT 4

* Refer to The Following sheet


(1.3.5 Indoor unit Address setting method)

INDOOR UNIT 5

GND

Vcc

INDOOR UNIT 6

CN-POWER
GND

BUS
B
BUS
A

CN-COM B
CN-POWER

CN-COM A
S2

S1

GND

S4

LED2
LED4

LED3

+10V

IC1P

S5

S6

LED7

LED8

S3

LED5

C GND VCC

Outdoor
Outdoor unit
unit

S9

LED9

LED10

LED13

Group Number 0
Master Mode

LED14

S10

LED12

LED11
S14

S15

LED15

+
LED16

PWB:6870A10001A
ASM:6711A20005E
S15

+
LED17

S18

ON KSDO4H
L1 2 3 4
S19

All the connections are to be done as shown above.


A and B are the communication lines for the indoor and
C and D are the communication lines for the Central Control.
Use two shield lines for C/D connecting line.(Earth the shield line)

110 Multi type Air Conditioner

TX1
S12

S11

VCC
CENTRAL
GND
CONTROL
C
UNIT
D

S16

Control Devices and Function


2 OR MORE SIMPLE CENTRAL CONTROL CONNECTION
INDOOR UNIT 1
INDOOR UNIT 2
INDOOR UNIT 3

OUTDOOR
MAIN PCB

INDOOR UNIT 4

<Group Number 0>


INDOOR UNIT 5
INDOOR UNIT 6

GND

Vcc

BUS
B
BUS
A

Master

CN-POWER
GND
CN-COM B
CN-POWER

CN-COM A
S2

S1

DIP SWITCH

S4

LED2

GND

IC1P

S5

S9

LED9

S10

S14

TX1

1. Adhere the PI485 Module(For connecting central control) to the Control Box.
2. Connect the PI485 Module to central control.
3. In the case of connecting two more than central control, set the Master/Slave mode
and then connect each communication lines(C,D) <Refer to above fig>.
*Special purcharse: Central control(P/No.:4995A20105F),
PI485 Module(PNF-P14A0M)
* It can be added to 15 Central controls for the slave control.

S12

LED12
S15

S16

LED16

LED15

LED14

S3

LED8
S11

+
LED11

LED10

+
LED13

LED4

+
LED7

LED5

+10V

LED3
S6

PWB:6870A10001A
ASM:6711A20005E

C GND VCC

LED17

ON KSDO4H
L1 2 3

Outdoor unit 1

S18

S15

S19

Master Mode

Group Number 0

INDOOR UNIT 1
INDOOR UNIT 2
INDOOR UNIT 3

OUTDOOR
MAIN PCB

Note

INDOOR UNIT 4

<Group Number 1>

INDOOR UNIT 5
INDOOR UNIT 6

GND

Vcc

BUS
B
BUS
A

001

C
CN-POWER
GND

CN-COM B
CN-POWER

CN-COM A
S2

S1

S4

LED2

IC1P

S5

S6

S9

C GND VCC

LED13

LED14

S14

Group No.

S3

LED8

Indoor No.

LED12
S15

TX1
S12

S11

+
LED11

S16

LED16

LED15

PWB:6870A10001A
ASM:6711A20005E
S15

+
LED17

Outdoor unit 2

S10

LED10

+
LED7

LED5

LED9

DIP SWITCH

LED4

LED3

GND
+10V

Slave

S18

ON KSDO4H
L1 2 3

S19

Master Mode

Group Number 0

PI485 setting method(LG Aircon Network unit)

Selection of product
unit type

Selection of network type

ON KS DO 4H
L1 2 3

Settings method of TPS Inverter Multi Type


ON KS DO 4H
L1 2 3

1 ON + All OFF : Connection of "TPS Inverter Multi Connection + General Central


Controller" Case.

ON KS DO 4H

1,4 ON + All OFF : Connection of


L1 2 3

"TPS Inverter Multi Connection +

Central Controller applied LGAP" Case.


* LGAP : LG Air conditioners Protocol

Function of LG Network
- It is possible to connect the network of LG air conditioners and to connect various contents of the network
system, which is simple, deluxe and PC central control.
- Please refer to "LG Control System Manual" about the detail functions and the products possible to network.
- As the Interface for networking, PNF-P14A0M/R/C is applied.

Service Manual 111

Control Devices and Function


Indoor Unit Address setting Method

1. Press 13(program) and 16(set and clear) key more


than 3 second then "Address Setting Mode" starts.
2. Set the address of indoor unit by using "Temperature
setting" key.
Range of address : 00 ~ FF

Using Wired Remocon

AUTO SWING

OPERATION

SET TEMP
Room Temp

Timer

Operation unit
03

SUB FUNCTION

HI
MED
LO

AUTO Heater Preheat


JET Defrost Humidify
Filter Out door
ZONE
1 2 3 4

Time
On Off
Set no. Time 01

FAN SPEED

Program set
05

07

09

11

13

15

17

19

21

23

3
17
10
11
12
13
14
15

Timer

Program

6
4

Holiday
Plasma

7
8
9

Set/Clr
Hour

Cancel

Week

Ex)

Min

RESET

16
18

Group Room(Indoor Unit)


No.
No.
3. After setting address, press 13(program) and 16(set
and clear) key more than 3 second then "Address
Setting Mode" is finished.

Heat Pump Model

Using Wireless Remocon


1. Address setting Method
Signal transmitter

1) Press 5(Jet Cool) & 13(Reset) key at the same time more
than 3 seconds then
"Address Setting Mode" starts.
2) Set the address of indoor unit by using
"Temperature setting" key.
Range of address : 00 ~ FF

6
3

Ex)

4
2
7
11
8
13
14

10
CANCEL
ON

OFF

SET
AUTO CLEAN

9
16
12
15

Flip-up door
(opened)

2.

Group Room(Indoor Unit)


No.
No.
3) After address setting, pressing 1(On/Off) key, address
setting is finished. The address that is set is displayed on a
display window of indoor unit.
* notice : The mothod of display and time is different
according to indoor unit type.
4) If the remote control is reset, normal mode starts.

2. Address Monitoring
1) Press 6(Chaos Swing) & 13(Reset) key at the same time then "Address Monitoring Mode"
starts.
2) At the address monitoring mode, pressing 1(On/Off) key, The address that is set is displayed
on a display window of indoor unit.
* notice : The mothod of display and time is different according to indoor unit type.
3) If the remote control is reset, normal mode starts.

* Notice : Confirm that wired and wireless remote control are able to select the address or not.

112 Multi type Air Conditioner

Control Devices and Function

Test run method


1. Set the wiring of system and indoor unit.
2. Apply power to the setting.
3. Do auto addressing to the outdoor unit.
4. After addressing, initialize the central controller(Manual initialize: Total on + total off + 16 key).
Cooling: Setting basically(Total On + Total Off + 4 key)
Heating: Total On + Total Off + 8 key Red power lamp 'On'
6. Check up On/Off with a related indoor key pressing.

Installation
CAUTIONS

Do not install in this area


Dont install near elevator, computer, automatic door. (High noise area).

Keep in mind
Dont operate with wet hands.

Dont install near high moisture & high oscillation area.

Dont pull the connected wire.

Dont install near direct sunlight or heat


source.

Service Manual 113

Control Devices and Function


INSTALLATION ORDER
1. Remove upper & lower case.

2. Fixate screw in the holes of the

3. For Dip switch, and Rotary

case bottom.

4. For wiring connection, refer page

switch setting, refer to the page


How to Install.

5. Adjust the upper case in accor-

Installation Procedure

6. Check the operation by supply-

dance with back case while


assembling as shown in the figure.

ing the power.

LINK OF CONNECTING WIRE


1. First, separate the front case from rear case of controller, connect terminal
C, D,Vcc, GND on PCB referring to the following table.
Between controller and outdoor unit : 220m(25

Out door unit Terminal Block


GND
Vcc
C
D

Wire Color
BLUE
Red
Brown
Yellow

Central Control Terminal


GND
Vcc
C
D

2. After attaching the supplied wire to terminal, link the connecting wire.
If necessary, Cut the indicated part of front case to draw the lead wire.

114 Multi type Air Conditioner

D
C

Maximum length of connecting wire


Between controllers : 220m(25

GND
Vcc

Control Devices and Function


. ROTARY SWITCH SETTING(INSTALLATION FOR 2 OR MORE SIMPLE CENTRAL CONTROL)
The setting of Group Number in the Central Control is done by the rotary switch as shown in the figure below.

It is possible to set 0~15 Group(Total 16 Groups). All the numbers on the rotary switch represent the different
Group Numbers. By changing the knob we can set rotary switch to the group number we want to control. The
above fig. Shows the control of group number 0. Similarly we can control all the 16 Groups.

. DIP SWITCH SETTING(INSTALLATION FOR 2 OR MORE SIMPLE CENTRAL CONTROL)


CAUTION
Dip switch is now used only for the setting of master or slave mode.( In the case of two more
than central controls.)
Set one to Master, the others to slave.

Master Mode
Rotary Switch
Dip Switch
ON

Slave Mode

OFF

. ACCEASSORY PARTS
Central control and sub

(with wire ass'y) should be purchased as optional.

Central Control(1EA)

PI485(PQNFP14A0M)
Wire Assembly 1

Screw(4EA)

Wire Assembly 2

Service Manual 115

Control Devices and Function

Deluxe Central Control


2.1.1 Summary
Deluxe Central control is a product available for individual and integrated monitoring and control of maximum
256 of TPS Inverter Multi air conditioner systems. Specially, operation status of the individual air conditioner
can be particularly checked. Individual or simultaneous operation of the air conditioner, operation mode, wind
quantity, user locking and temperature setup are also available.
Specially for this system, installation is simple and user's environment is excellent. Central control is available
by a simple manipulation. In addition, this system have the self-battery built-in and can stably operate in spite
of outside disturbance such as temporary power failure. This system has no need of additional peripheral
equipment like UPS (Undisturbed Power System) and AVR to be purchased for stability when composing the
existing PC central control system, and has so attractive advantage in installation costs.
Using the Deluxe Central control enables the management room to setup lock of each air conditioner and
prevent indoor control of the individual air conditioner and restrain the necessary use. In case of releasing the
lock, you may control the system by using the wire/wireless remote control at the place where the individual
air conditioner is installed.
Setup of a weekly schedule is available and detailed schedule of the individual air conditioner can be easily
setup through the GUI. Details of schedule setup can be immediately checked with a graph. This system is a
product to meet energy saving and convenience at the same time at a place like a school by using this schedule function.
Depending on installation environment, location and conditions of use, you can setup groups. With this setup,
more efficient operation at the center is available. Setup without requiring other equipment is available by
using the GUI and change by the consumer is also available after installation.
You can reduce development time to configure special system upon the request by the consumer and conveniently this system by using the touch panel.
Where needs from a new customer occur or where purchase of additional air conditioner is done, the Deluxe
Central control can be smoothly installed.

Deluxe
Central control

Outdoor Unit

CNU
PI485

Outdoor Unit

PI485

116 Multi type Air Conditioner

Control Devices and Function

Major Characteristics

Figure 2) Deluxe Central control

1. Individual/Integrated Operation/Monitoring
You can identify operation status of the air conditioner, operation mode, wind quantity, wind direction, locking, temperature setting and error, etc by selecting the installed air conditioner through individual selection,
group selection or all selection. Individual setup and operation of the detailed functions are available.
Therefore, managing with Deluxe Central control installed at the control room at a building where a number
of air conditioners are installed, is a convenient way.

2. Group Management
Group management for the installed air conditioners is available. Group can be seperated by their nature,
location and size of each air conditioner which enables convenient use. In addition, allotment of respective
name to the setup group allows further intuitive management.

3. Self-diagnosis Function
The air conditioner installed can self-diagnosed its error status and then transmits the result to the central
control. Therefore, a rapid countermeasure against failure of the air conditioner allows easy management
and increases the usage life of air conditioner.

4. Semi-permanent Life / Convenient Maintenance


Since the Deluxe Central control is designed for the semi-permanent use, this system can be used semipermanently after installation, different from the existing PC or a large central control system requiring a
continuous management due to the life of peripheral and other PC.

5. Management Costs Down


In absence of the Central Control System, the manager controls a number of air conditioners. In addition,
even if management was done at the center, there is only function of on/off management at best and thus 2
or 3 building managers were actually required. However, manipulation of all functions can be now done at
a control room for the Deluxe Central control and so a manager can easily control all air conditioners.
Automatic operation is also allowed without a manager, by using schedule function.

Service Manual 117

Control Devices and Function


6. Convenient GUI / Touch Screen
Not requires special education for using the Deluxe Central control, conveniently used only by pressing the
buttons on the screen, and its function can be understood with intuitive pictogram. Especially schedule setting
is done by simply by dragging, different from the existing system requiring to press the button by more than
average 30 times to enter a schedule.

7. Schedule Automatic Operation Management / Energy Saving


For the Schedule Automatic Operation, weekly setting is available. Enlisting of the schedule exception processing schedule (national holiday) is done for a year prevents the air conditioner from an unnecessary operation of air conditioner, allowing the system to be controlled at the center so that it can be only used for a necessary case and enabling to obtain excellent energy saving effect. Fixed schedule places like elementary
school, middle school, high school and college or university will get its excellent working effect.

8. Power Failure Backup Function / Powerful Stability


For the existing Central Control System, additional purchase of expensive UPS equipment in provision for a
temporary power failure must be done in the past but for the Deluxe Central control, since the self-power failure compensation battery is built-in, power is automatically converted by maximum 2 hours. Therefore, there
is almost no malfunction due to a temporary power failure because stable operation is available.

9. Mobility
A wireless radio system may be installed at the Deluxe Central control, it will control the Airconditioners
directly while going around the building with the wireless radio system and its self-battery function (100 m
where there is no obstacle).

10. Convenient Installation


This system can be freely fixed to the wall surface because of its small size, light weight and thin thickness. It
can also stood up on the desk by using, its dedicated cradle. It is not subjected to spatial restriction in installation space and location since this system communicates on the basis of the I-GW and the Ethernet.

11. Stable Date Storage/Backup


Setup information is saved as it is, even if no power is supplied then also all data is saved in the built-in flash
memory.

12. Scalability
Scalability of the system is easy in case of additionally purchasing equipment since scalable slot such as
USB, Serial (RS-232c), PCMCIA, CF Type is prepared. This system is designed considering sufficient scalability in provision for special request by the customer.

13. Upgrade
Additional installation of a new program is available via the CF memory card and the existing program can be
upgraded to a new program. Using such upgrade function always enables to construct a modern type of
Central Control System.

118 Multi type Air Conditioner

Control Devices and Function

Figure 3) Deluxe Central control


Table 1) Comparison Between Central control Characteristics
Deluxe
Central control

Internet Central control

PC Central control

Dedicate PC

Non-required

Required

Configuration

User S/W

User S/W, Engine S/W

Position of program

Download to i-GW

Installation

Built-in

256 sets (Less than 128 sets


recommended)

256 sets1)

256 sets

Remote control

Available

Control & monitoring

Available

Available

Available

Schedule management

Available

Available

Available

Available

Available

Available

Users lock

Available

Available

Available

Upgrade

Available

Available

Available

Touch screen

Built-in

Built-in Flash DB (backup)

Built-in

Wireless LAN (movable)

Available (option)

Non-interruption device

Max. installation set


numbers

System setup
System monitoring(overview)

Available(Configure file
modification)

Non-required
Main Body of Web Pad
Deluxe Central control

Separately add

Built-in
-

Requirements

Browser supporting JAVA

2)
JVM (provided by MS)

Life

Semi-permanent

Peripheral devices & PC life

Semi-permanent

1) For the PC central control, installation set numbers may respond up to 1024 sets upon users request.
2) JVM (Java Virtual Machine) is basically installed at the Windows but some versions of Window XP may be
manually installed.

Service Manual 119

Control Devices and Function

Major Function of Deluxe Central Control


[ System Control ]
To check general monitor function of the air con central control
system such as selection of group and air conditioner, air
conditioner control monitor function etc.

PQCSW501A0, PQCSW502A0

[ System Monitor ]
To check the ctual time status of all air conditioners.

PQCSW501A0, PQCSW502A0

[ System Set-up ]
To manage the air conditioner through grouping and record setup
of group and installation position, etc.

PQCSW501A0, PQCSW502A0

[ Time Schedule ]
Setup of a weekly schedule for all, group and individual air
conditioner enabled operation of the system. Processing through
enlist of extra schedule for a year is available.

PQCSW502A0

120 Multi type Air Conditioner

Control Devices and Function

System Configuration
Scenario 1 : In case of not using Internet access function

B part

A part

Product

Control System
Interface

Delux Central
Control

CNU
PI485

PI485
Cross UTP Cable
(Cross LAN Cable)
RS-485 Cable

PI485

PI485

* CNU: Central control Network interface Unit


PI485: Product Interface unit for IEEE485 transmission.

Main Specifications
1. Control System
- Centralized control of maximum 256 indoor units
- Simple Touch PAD method
- GUI setting considering convenience of use
- Power failure compensation with independent Battery Built-in (Max. 2 hours)

2. CNU
- Combination of maximum 8 outdoor units
- 485 to Ethernet Converter Built-in

3. PI485
- 1 pcs per outdoor units
Note: - GUI(Graphic User Interface) may be changed without any notice, for improvement or options.

Service Manual 121

Disassembly of the parts

Disassembly of the parts (Indoor unit)


Indoor unit
1. Split Type Indoor unit
CAUTION: Disconnect the unit
from power supply before making
any checks.
Be sure the power switch is set to
OFF.

To remove the Grille from the Chassis.


Set the up-and-down air discharge louver to open
position (horizontally) by finger pressure.
Remove the securing screws
To remove the Grille, pull the lower left and right
side of the grille toward you (slightly tilted) and lift
it straight upward.

Screw

1) To remove the sensor, housing connect,


earth conductor & step motor conductor with
sensor holder, Motor, Evaporator & P.C.B.

Motor
Conductor

Earth
Conductor

122 Multi type Air Conditioner

Power
Conductor
Sensor
Conductor
Step Motor
Conductor

Disassembly of the parts


2) To remove the Control Box.
Remove securing screws.
Pull the control box out from the chassis carefully.

3) To remove the Discharge Grille.


Pull the discharge grille out from the chassis
carefully.

4) To remove the Evaporator.


Remove screws securing the evaporator and
the holder eva.

Unhook the tab on the right inside of the chassis at the same time, slightly pull the evaporator toward you until the tab is clear of the slot.

5) To remove the Cross-Flow Fan


Loosen the screw securing the cross-flow fan
to the fan motor (do not remove).
Lift up the right side of the cross-flow fan and
the fan motor, separate the fan motor from the
cross-flow fan.

Remove the left end of the cross-flow fan from


the self-aligning bearing.

Service Manual 123

Disassembly of the parts


2. Art Cool Type Indoor Unit
CAUTION: Disconnect the unit from
power supply before making any
checks.
Be sure the power switch is set to
OFF.

1. To remove the Grille from the Chassis.


- Pull the grille bottom, the remove 2 securing screws.
- Lift the both lower parts of panel front.
- After pull down this panel a bit, separate connecting
wire with product.

2. To remove the Control Box.


- Before removing the control box, be sure to
disconnect the wires from PWB.
- Pull the cover control out from the control box
and disconnect other wires.
- Remove securing screws.
- Pull the control box out from the chassis carefully.

Panel Front
Connector

Step Motor Connectors


Sensor Connector

4Way/Fan Connector
Comp Connector
Power Connector
Power Connector
Comp Connector

124 Multi type Air Conditioner

Motor
Connector

Disassembly of the parts


3) To remove the Evaporator.
- Remove 4 screws securing the evaporator.
- Pull the evaporator out from the chassis carefully.

4) Before removing the Turbo Fan.


- Remove the securing screws from the chassis.
- Pull the pipe cover, top cover and the air guide.

Air Guide

Top Cover

Pipe Cover

5) To remove the Motor.


- Remove the securing bolt from the motor shaft.
- Pull the fan out from the motor shaft.
- Remove 4 screws securing motor mount from the
chassis and lift up the motor mount and the bracket.

Bracket

Turbo Fan

Bolt

Motor Mount

Service Manual 125

Disassembly of the parts


3. Art Cool Deluxe Type Indoor Unit(SZ,SU,S3)
CAUTION: Disconnect the unit from
power supply before making any
checks.
Be sure the power switch is set to
OFF.

To remove the Grille from the Chassis.


Hold up Inlet Grille Horizentally.
To remove the Grille, pull the lower left and right
side of the grille toward you (slightly tilted) and lift it
straight upward.
To seperate connecter assembly and than to
remove Inlet Grille assembly.

1) Before removing the control box, be sure to


take out the wire screwed at the other end.

126 Multi type Air Conditioner

Disassembly of the parts


4. Art Cool Deluxe Type Indoor Unit(SE)
CAUTION: Disconnect the unit from
power supply before making any
checks.
Be sure the power switch is set to
OFF.

To remove the Grille from the Chassis.


Hold up Inlet Grille Horizentally.
To remove the Grille, pull the lower left and right
side of the grille toward you (slightly tilted) and lift it
straight upward.
To seperate connecter assembly and than to
remove Inlet Grille assembly.

1) Before removing the control box, be sure to


take out the wire screwed at the other end.

Earth
Conductor

Service Manual 127

Disassembly of the parts


2) To remove the Control Box.
Remove securing screws.
Pull the control box out from the chassis carefully.

3) To remove the Discharge Grille.


Unhook the discharge grille and pull the discharge grille out from the chassis carefully.

4) To remove the Evaporator.


Remove 3 screws securing the evaporator(at the
left 2EA in the Eva Holder, at the right 1EA).

128 Multi type Air Conditioner

Disassembly of the parts


Unhook the tab on the right inside of the chassis
at the same time, slightly pull the evaporator
toward you until the tab is clear of the slot.

5) To remove the Motor Cover


Remove 2 securing screw.
Pull the motor cover out from the chassis
carefully.

Motor cover
6) To remove the Cross-Flow Fan
Loosen the screw securing the cross-flow fan to
the fan motor (do not remove).
Lift up the right side of the cross-flow fan and the
fan motor, separate the fan motor from the
cross-flow fan.

Remove the left end of the cross-flow fan from


the self-aligning bearing.

Service Manual 129

Disassembly of the parts


3. CVT Type - VB chassis
Warning : Disconnect the unit from power
supply before making any checks.
Be sure the power switch is set to OFF.

1. Remove the air filter.


Pull the inlet grille slightly toward you.
Pull out the air filter. (2 pieces)

Inlet Grille

2. Remove the girlle from chassis


Remove the screws securing the side plate and
push to the bottom-side.
Unhook the hanger from the hanger screw at the
left and the right side.
Pick out the inlet grille.

1
4

Hanger
Hanger
Screw

3. Remove the lower air guide


Remove a screw of both side fixing "barrier airguide".
Remove the screws of both sides of the lower
air-guide.
Remove the lower air-guide toward arrow mark
by turning upwards as shown in figure.

Barrier Air guide


Lower Air guide

130 Multi type Air Conditioner

Disassembly of the parts

VE chassis
Warning :
Disconnect the unit from power supply before making
any checks.
Be sure the power switch is set to OFF.

To remove the Grille from the Chassis.


Set the up-and-down air discharge louver to open
position (horizontally) by finger pressure.
Remove the securing screws.
To remove the Grille, pull the lower left and right
side of the grille toward you (slightly tilted) and lift it
straight upward.

1. Before removing the control box, be sure to


take out the wire screwed at the other end.

Service Manual 131

Disassembly of the parts


2. To remove the Control Box.
Remove securing screws.
Pull the control box out from the chassis
carefully.

3. To remove the Discharge Grille.


Unhook the discharge grille and pull the
discharge grille out from the chassis carefully.

4. To remove the Evaporator.


Remove 3 screws securing the evaporator(at the
left 2EA in the Eva Holder, at the right 1EA).

Caution label
When repair, do not damage the
Caution label.

132 Multi type Air Conditioner

Disassembly of the parts


Unhook the tab on the right inside of the chassis
at the same time, slightly pull the evaporator
toward you until the tab is clear of the slot.

5. To remove the Motor Cover


Remove 2 securing screw.
Pull the motor cover out from the chassis
carefully.

6. To remove the Cross-Flow Fan


Loosen the screw securing the cross-flow fan to
the fan motor (do not remove).
Lift up the right side of the cross-flow fan and the
fan motor, separate the fan motor from the
cross-flow fan.

Remove the left end of the cross-flow fan from


the self-aligning bearing.

Service Manual 133

Disassembly of the parts


4. Remove air guide upper, crossflow fan and
motor.
Remove the screws of both sides and center
securing the upper air-guide.
Remove 2 screws fastening the bracket of door
switch.

Door
Switch
R

Remove a bearing assembly by removing a


screw and the bearing cover.
Remove 4 screws securing the motor cover.
Loosen the screw securing the crossflow fan to
the fan motor shaft. (do not remove)
Remove the crossflow fan by sliding it out from
the shaft of fan motor.

Bearing
Cover

Bearing

Motor
Cover

5. Remove the control box Assembly.


Disconnect the step motor connector, fan motor
connector, display PCB connector, thermistor
connector and door switch connector from the
main PCB.
If necessary, disconnect power supply cord and
connecting cable from the terminal block and
remove the cord clamp screw.
Remove 2 screws securing the control box and
pick out the control box carefully.

134 Multi type Air Conditioner

Disassembly of the parts


6. Remove the front panel.
Remove the screws of both sides fixing the front
panel.
Push the upper side of front panel strongly to pull
out the front panel from the inner hook of diffuser
frame.
Pull down the front panel carefully not so as to
harm the display PCB wires and thermistor
wires.

7. Remove the diffuser assembly.


Remove the screws of both side of diffuser
assembly. (4 pieces)
Push the upper side of cabinet strongly to pull
out the inner hook of diffuser frame from the cabinet hole.
Take up the diffuser frame carefully not so as to
harm the display PCB wires and the step motor
wires.

Diffuser frame
Diffuser
frame
Hook
Front
Panel
Front
Panel
R

Diffuser
frame
Hook
Cabinet

8. Remove display PCB assembly.


Remove the screws at the both side of display
cover.
If necessary, disconnect the display PCB connector from PCB assembly.
Remove 2 screws of PCB assembly.

Display Cover

Service Manual 135

Disassembly of the parts


9. Remove the vane-upper, vane-lower and step
motor.
Remove 2 screws securing the step motor
assembly and pull it out from the vanes carefully.
Unhook the vanes from the vane supporter and
remove the upper vane and lower vane by
pulling the center of vanes with care.

Step Motor
Vane Supporter

Lower Vane

Upper Vane

10. Remove the drain pan assembly.


Remove the both side of screws. (4 pieces)
Pull out the drain pan assembly.
Be careful not to harm to the EPS packing of
drain pan and the tubings of evaporator.

11. Remove the evaporator.


Remove the screws of both sides securing the
EVA barrier-R/L on the side cabinet.
Remove the screws which fasten the barrier on
the evaporator and take out the barrier assembly.
Remove the evaporator assembly by sliding
toward arrow mark. (As shown in figure)

EVA. Barrier-L

Side Cabinet

EVA. Barrier-R

136 Multi type Air Conditioner

Schematic Diagram

Schematic Diagram
Electronic Control Device
1. Indoor Unit

5V

1%

12.1K

R02H

1%

6.2K

R04H
12.1K

R16H
12.1K

R15H
12.1K

R14H
12.1K

R13H
12.1K

R12H
12.1K

R11H

C01M

0.01
50V

Vdd

Wt

RD

R32 62

R31 63

R30 64

MICOM
GMS81516

R/W

R34 60

R33 61

MP

AVss
AVref

3
4

SYNC

R61/AN1

D4

D3

D2

R06 50

R05 51

R04 52

R03 53

R02 54

RESET'

A15 R26 34

A14 R25 35

A13 R24 36

A12 R23 37
29

XIN

28 R40/INT0

30

A16 R27 33

R03K
1K

ZNR01K
14D271

C02F,0.01/50V

R15G,6.8K

R13G,6.8K

R11G,,6.8K

5V
R04F,10K

R03F,1K

Q13G

14

15

16

10

11

12

NF01J

SLIDE S/W
REMO

Vout

GND

DISPLAY

LED3

LED1

LED2

FAN
MOTOR

INDOOR

PRE AMP
ASSY
TFMS2380B

Vcc

LIVE

NEUTRAL

LED4

CN-DISP1

REMOCON

C02L

CN-DISP2

10V

220uF

DC 12V

CN-POWER

COM

CN-FAN

CN-SUB

DC 5V

NF01M

ZNR01J
INR14D471K
SVC561D-14A

FUSE
250V/T2A

C01M,0.1,AC275V

SSR-MOTOR

ZNR01M
INR14D471K

DC 5V

DC 5V

DC 5V

R03G,220

R05G,220

R04G,220

R02G,220

R07G,220

R01G,220

R06G,220

R02F,10K

KTA1270Y

Q12G

13

NF01M

R01M,120,1/2W

C01J
0.1, AC275V

R05T,10K

R01F,1K

R16G,6.8K

R14G,6.8K
KTA1270Y

Q11G
KRA1270Y

IC02M
KID65004AP

R12G,6.8K

8 VCC
7 DU

EEPROM

6 ORG
5 Vss

DC 12V

S 1
C 2

6171AQ3124C

POWER TRANS

FREQUENCY

SSR-MOTOR

D 3
Q 4

C01F,0.01/50V

Q01M
KRC107M

D02D-05D
1SR139-600

D02K
1SR139-600

R05K
25K,3W,1%

D01K
1SR139-600

XOUT

VSS

C01D
2200uF
35V

D01D
1SR139-600

IC02K(TLP627)

31

R04K
680

32

5V

I
+

R02T,10K

R67/AN7

R60/AN0

D5

R07 49

R02K,1K
R01K
10K
DC

IC02D
7805

IC01D
7812

C02D
0.1
50V

R01T,10K

11

R57/PWM1

D6

R10 48

BRK R35 59

12

R56/PWM0

D7

R11 47

BRQ R36 58

13

R55/BUZ

A0

R12 46

HALT R37 57

14

R54/WDTO

A1

R13 45

R66/AN6

15

R53/Srdy

A2

R65/AN5

16

R52/Sclk

A3

R64/AN4

17

R51/Sout

R14 44

18

R50/Sin

A4

R16 42

R15 43

19

R47/T30

A6

A5

R17 41

CN-TH

20

R46/T10

A7

R20 40

R00 56

R03H,1K
R01H,1K

21

R45/EC2

A8

D0

OP1
XXXK

22

R44/EC0

A10 R21 39

R63/AN3

OP2
XXXK

23

R43/INT3

A11 R22 38

OP3
XXXK

24

R42/INT2

OP4
XXXK

25

R41/INT1

TX

26

C05D
470uF
16V

O
C03D
470uF
25V

IC01K(TLP621)

27

R01 55

R02A,4.7K

OSC01B

C01K
0.001
25V

Q01K
KRC102M

CST-8.00MTW

RX

D1

OP5
XXXK

R01A,1K

R01B,1M

R62/AN2

0.01
50V

11
7

10

12

5V
R03A,100
C02A
10uF/50V

TX

RX

KIA7036P
IC01A

DC 5V

C01A
0.01
50V

10

C02H

OP6
XXXK

C01H

DC12V

13

14
15

17
1

16

18

C01C
0.01
25V

2
3
4

CN-U/D

DC 12V

IC01M

Q01C
KTC3198Y

R01C,1K

C01L
680pF
50V

R01L,1K

R01E,1K

R02E,20

KID65084AP

R03C,20K

R02C,4.7K

R02L,10K

BZ01E

R04C,10K

M
C02C
0.015
50V

C06D
0.01
25V

R04T,10K

5V

REMOCON

5V
FREQUENCY

R05C
4.7K

DC 12V
C04D
0.01
25V

R03T,10K

PIPE-TH

BL

PK

YL

OR

RD

ROOM-TH

STEP MOTOR
UP/DOWN

1) Split Type

Service Manual 137

Schematic Diagram
2) Art Cool Type

138 Multi type Air Conditioner

Schematic Diagram
3) Art Cool Deluxe Type
A/C MOTOR

Service Manual 139

Schematic Diagram
3) Art Cool Deluxe Type
BLDC MOTOR

140 Multi type Air Conditioner

CN-OUT

250V/
T3.15A,3A

ZNR01J
INR14D561K

M_RTX

C03J
10nF
275V

AC_L

RY-M

RY-L

RY-LOUV

RY-D/PUMP

RY-HEATER

RY-4WAY

RY-OUTFAN

RY-COMP

SIGNAL

NEUTRAL

LIVE

CN-POWER

RY-OUTFAN

RY-4WAY
RY-HEATER

CN-D/PUMP
Drain
Motor

CN-LOUVER
1
3

2
3

SSR

RY-H
NF01M

5V

AC_N

NTC01D
10D-9

C01D
10uF/
400V

IC02M
KID65004AF

DC310V

ZD01D
P6KE200A

D02D
UF4005

S/Trans

BP

EN

C05D
681

C06D
470uF/35V

D03D
UF5402

6,7

4,5
IC02D(TLP521)

12V
L01D

3.3uH
R04D

39
C07D
330uF/35V

P75

63

64

ZD02D
11V

R03D
150

P76
P74

62

C03D
103

D
5
4
TNY
255P
2 1

1
P77
P73

61

2
P00
P72

C04D
103/250VA

3
P01

59

60

P02
P70

P71

4
P03

5
6

58

P04

VDD

57
55

56
54

(AIN7)/P67

(AIN5)/P65

(AIN6)/P66

(AIN4)/P64

53

P05

P07

52

P06

P10(INT0)

(AIN3)/P63

51

11

10
P11(INT1)

(AIN1)/P61

(AIN2)/P62

12

P12(INT2/TC1)
P13(DVO)

13

C09D
220uF/50V

C11D
223/1KV

C
S

SB1
SB0

C10D
103

DC 12V

STEP M

C12D
103/1KV

IC02M
KID65004AF

IC03D
KID78L05BP
I
O
7805
C08D
104

HEATER
4WAY
OUTFAN

COMP

A/C

STEP M4

5V

OPTION6
OPTION5

OPTION3

OPTION4

OPTION2
PIPE TH
ROOM TH

5V

14

OPTION 1

49

GND

P14(PPG)

48

50
VARF

47

(AIN0)/P60
P15(TC2)

VASS

46

15
16

P54

45

P16

P53

44

SB3

17

P17

(PWM/PDO)/P52

3,7,8

IC01D
TNY255P

DC 12V

STEP M5
MED
D/PUMP

P20(INT5/STOP)

(INT4/TC4)/P51

S_B3

18

TEST

SB2

19

P21(XTIN)

PHASE

C02L
681

REMO

FREQ

IC01M
KID65004AF

LOW

HIGH

LOUVER

STEP M2

R02E
20
EERROM

VCC

DU

20

5V

R07H
12.1K
1%
R08H
12.1K
1%

R05H
12.1K
1%
R06H
12.1K
1%

R01U
10K

R03H
12.1K
1%
5V

R02H
6.2K R01H
1% 12.1K
1%

OR1 C02H C01H


103
103

R04H
12.1K
1%

OR6 OR5 OR4 OR3 OR2

5V
Multi_TX

12V
5V
GND

M_RTX

M_RTX

CN-PIPE

D12K
1SR139-400

C01U
103

C02U
103

P32

NC

NC

NC

33

34

35

36

12V

SCK1

SI1

SO1

IC11K(TLP621)

1
R14K
1K

5V

R01C
200K/2W

R02C
1K

R11K
10K

C11K
102

Q11K

KRC104M

RX

Multi_RX

DC 5V

D02K

2
1

50/60Hz

DC12V
3
Signal
2
GND
1

CN-REMO

L02K

L03K

TX Multi_TX

R16K
10K

C03K
102

DAN212K

5V

Q01C

5V

C01C
103

R06C
10K

R05C
1K

R04C
4.7K

R03C
10K

KRA104M

Q04K

C05K
C04K C06K
104 103

4.7K

R02K

L01K
D01K
DAN212K 100nH

12V

IC01C

C02K
102

Q03K
KRC104M

R12K,1K

DC 5V

DC 5V

12V

Q02K
KRC104M

KRA104M

Q01K

AC_N

AC_L

C01K
102

1K

R01K

5V

IC12K(TLP627)

_RX

_TX

R13K
1.5K

PLC_SEL

Multi_TX

GND

GND

Multi_RX

5V

CS0

12V

CS1

5V

R15K
82K/3W

D11K
1SR139-400

CN-ROOM

P33

NC

29

P34

CN_M C

2
3

GND
5V

Multi_RX

42

_RX

12V

_TX

_RX

S_B0

S_B1

S_B2

21

CC RX
(SO2)/P47

41

_TX

CC TX
(SI2)/P46

40

43

(SCK2)/P45

SI1/MULTI TX
SCK1/MULTI RX

4
(SO1)/P44

39

SO1/PLC
(SI1)/P43

38

(INT3/TC3)/P50

NC

RESET
XIN

P22(XTOUT)

24

XOUT

22

25

23

GND

NC

XOUT

XIN

RESET

Q 4

ORG

5 VSS

STEP M3

5V

STEP M

DC 12V

50/60Hz
REMO

BZ01E

R01E
1K

R01L
10K
R02L 1K
REMO

STEP M

STEP M

DC 12V

R01J
D01D
1M,1/2W 1N4007

C02J
100nF
275V

NF

NF01J
22mH/3A

C01J
100nF
275V

R01A 1K

R01B

1.0M

VSS

(SCK)/P42

30

P35

P31

P30

26
27

NF01M

ZNR01M

C02A
102

3
4

4
5

OSC01B
8.00MHZ

LED1
LED2

37

31

28

CN_ZONE

32

CSO

2
3

R02A 10K

C01A

KIA7036P
2

3.3uF
/50V

R03L 1K
R04L 1K

5V

CN-DISP

LED4

LED3

LOUVER
FLOAT

CSI

Louver
Motor

IC01A
3.6V

DISPLAY

LED1
LED2

R05L 1K

6
7

6
7

5V

R01F

C01F
103

R02F

LED3

C02F
103

1K

R06L 1K

1K

LED4

CN-MOTOR1

FAN
MOTOR

CN-MOTOR2

FAN
MOTOR

5V

GND

Vcc

Vout

PRE AMP
TFMS-2380B

Force
SW

CN-LOUVER

CN-FLOAT

Schematic Diagram
4) Duct Type

Service Manual 141

Telecontrol

RD

OR

YL

PK

BL

RD

OR

YL

PK

BL

HVB

1
CN-12V

1
CN-CONT

3
2

CN-HVB

6
7

6
7

6
8

5
7

1
2

12V

12V

12V

DC12V

DC 5V

DC 5V

R06T,10K

5V

+ C09D
220
10V SD
C08D
103
50V

O
7805

IC04D
S78DL05L 1W
I

R05T,10K

C07D
104
50V

12V

AC PART FOR NORMAL

HVB OUT

DC 5V

C02L
4.7
50V

R01G,330,1/4W

R02G,330,1/4W

R03G,330,1/4W

R04G,330,1/4W

DC 12V

FORCE

RECEIVER

Option

CN-CC

6
7
8

LED1

LED2

LED3

PRE AMP
ASSY
TFMS2380B

Vcc

Vout

CN-U/D1

CN-U/D2

CN-LEV

WH YL OR BL BR RD

GND

LED4

(UP/DOWN)

STEPPING MOTOR

DISPLAY

(UP/DOWN)

STEPPING MOTOR

3
2

4
3

R02T,10K

L1
ZBF503D

R03T,10K

R04T,10K

DC LOW
VOLTAGE GND

ZD02D
BZX55C11

R02D
20K

C06D
330
25V SD

4WAY

FAN

COMP

D/PUMP

1
2

IC02M

12V

SEL

R02E,20

D07D
UG2D

C03D
681

C04D
470/35V/SD

COMP

5V

12V

CN-ACDC

JP2

JP1

C02D
104

SMPS

33 P51/NRE

DC HIGH
VOLTAGE GND

IC01D
TNY266P
S 2,3,7,8

6
7

Vref+
Vdd

MMOD

C01D
15uF
450V/SG

13

XI 11

Vss 10

OSC1

FAN
4WAY
INDOOR FAN
INT

D/PUMP

10

10

D/PUMP

Rx

Tx
FAN

4WAY

12,26,31,45,46
54~56

SD01D
STO2D-200

JP6

JP5

JP4

JP3

NU

23 P11/TM1IO

21

53

27

28

OSC2

NRST/P27

D7/P87

IRQ0/P20

22 P10/TMOIO

35 P53/A16

34 P52/NCS

D 5

BP 1

EN 4

14 P00/SBO0

Tx

15 P01/SBI0

Rx

29

IRQ2/P22
IRQ1/P21

24

25

30

IRQ3/P23

TM3IO/P13

P54 36

17

18

19

3
4

TM2IO/P12

32 P50/NWE

16 P02/SBT0

SEL

60 P80/D0

59 P81/D1

2
1

58 P82/D2

57 P83/D3

52 P77/A15

PA7/AN7

PA5/AN5
PA6/AN6

SBT1/P05
SBI1/P04
20 BUZZER/P06
SBO1/P03

49 P74/A12

48 P73/A11

47 P72/A10

44 P67/A7

43 P66/A6

50 P75/A13
51 P76/A14

R01E
1K

41 P64/A4
42 P65/A5

12V

5V

COMP

DC HIGH
VOLTAGE GND

C05D
472M

9
IC03M

IC02D
TLP181(V4 BL)

7
6
5

61 Vref-

40 P63/A3
PA3/AN3
PA4/AN4

PA2/AN2

63
64

PA1/AN1

38 P61/A1
39 P62/A2

37 P60/AO

62

PA0/AN0

MICOM

MN101C30A QFP64

3
4

CN-ACDC

R03D
39
1/8W 2012

9
IC01M

BZ01E
PKM13EPY-4002

12V

12V

INDOOR FAN
INT

HVB OUT

INDOOR FAN

R01T,10K

1M
R01B

R03A
100

IC03D
TLP181(V4 BL)
DC LOW
VOLTAGE GND

SCL

5V

1
2

RY-D/PUMP

RY-COMP

RY-4WAY

RY-FAN

D08D
LL4148

R05D
300K
1/4W
3216

DC HIGH
VOLTAGE GND

5V

D05D
1N4007

OSC01B

3.6V

EEPROM
IC 1

R05G
1K

R06D
300K
1/4W 3216

BD01D
DF08M

C01G
103

5V

R11G
1K

5V

IC01A

SDA

Force

R04D
27k
1/8W 2012

NTC SCK-102

1K/1W

D/PUMP

5V

C02G
103

MODE/WC

R01P
10K

OR4H

OR3H
F3

R02F
10K

R02A,4.7K

FAN
4WAY
COMP

12V

5V

INT

C01Z
103

50V

C01A
10/

R01A
1K

C01F
103

OR2H
F2

R01F,1K

OR1H
F1

12.1K, 1%
R23H

12.1K, 1%
R22H

12.1K, 1%
R21H

3
5

C03J
100nF
275V/436D

R01J
120, 1/2W

C12K
103

D03K

NF01J
15mH/1A

IC01J
TLP762JF

C01L
680pF/50V

R07D
12K

NF02J

RY-D/PUMP
G5N-1A(G5NB-1A)

R02J
100,1/2W

TR01J
SM1L43

ZNR01J
TVR10561

FUSE
250V/T2A

RY-4WAY
G5N-1A(G5NB-1A)

OR6H

CN-TAB1

2
1

T-BLOCK

2
1

3
2

3
4

3
4

CN-MOTOR

CN-FLOAT

RY-COMP
G4A-1A-E-LG
4

CN-DOOR

CN_INSTALL

receiver

5V
R01L
5.1K

INT

L02K

L03K

DC PART

R08D
56K

103

C01H

CN-TH1

CN-TH2

CN-REMO

5V

R01H
R02H
6.2K
12.1K
1%
1%

RY-FAN
G5N-1A(G5NB-1A)

C01J
METAL FILM
100nM/275V/436D

NF02J

ZNR02J
TVR10561

R03J
680
1/2W

R02L,1K

Q01C
KTC3198-Y
2SC5343

5V

R06F,1K

R08F,1K

C04F

103

103

5V

C02H

C03H

R07F R05F
1K
1K

1K R06H

1K R05H

R03H
6.2K
1%

5V

1K R04H

12V

DAN212K

C03F

D02K
DAN212K

C10K
102

R04J
560
1/4W 3216

10K
R10G

12.1K
R06G

L01K

5V

10K
R16G

12.1K
R12G

100nH

R03F,10K

C02J
METAL FILM
47nM/275V/435D

INDOOR FAN

12V

R04F,1K

12V

C11K
104

40K
R09G

40K
R15G

Q04K
KRA104M
C09K
102

Q02K
KRC104M

4.2K
R09K

4 5

3
2

D
F 0 1

9 8 7

B
C
E

SW-LOW

5V

4
4 5

F 0 1

3
E

9 8 7

SW-HIGH

B
C

Q03K
KRC104M

20K
R08G

20K
R14G

5V

C02F,103

C08K
102

R08K
1K

KRA104M

Q01K

OR5H

80K
R07G

80K
R13G

T2

142 Multi type Air Conditioner


T1

LEV

1(L)

2(N)

AC220~240V
50/60Hz

CN-POWER

FAN MOTOR

OUTDOOR

CN-D/PUMP

SH-CAPACITOR

COMPRESSOR

4-WAY

Drain
Motor

INDOOR
FAN
MOTOR

PIPE-TH

ROOM-TH

PIPE-OUT_TH

Schematic Diagram
5) Convertible Type

IC01K(TLP181-BL)

IC02K(TLP181-BL)

R14K
680

R01K
10K

C01K
102

D01D
UG2D

OUT_RX

OUT_TX

C02D
470uF
35V

6
3

L2
12uH(DIP)

R06D
1K
1/2W

L1
12uH(DIP)

R22D
1K

C05D
220uF
35V

C07D
220uF
25V
C08D
104
50V

IC04D
7805

S78DL05L,1W(DIP)

C04D
104
50V

12V

C03D
220uF
10V

5V

3
2

2
1

CN_HVB

SMW-250-04P

R01E,1K

R02E
1M

R03E,0K

DC12V

5
4
2
1

3
1

RD
OR
YL
BL

PK
RD
OR
YL
PK
BL

HVB_S

7 SM22

D/PUMP

A/C_OUT

6 SM23
5

4WAY
COMP
COMP

OUTFAN

4
3
2
1
8

12V

10 10

CN-UD1

SMW-250-10P

BL

PK

10 10

CN-UD2
RD
OR
YL

RD
OR
YL
PK
BL

C04M
103

12V

12V

C05M
103

C09M C08M C07M C06M


103
103 103 103

IC02M
KID65004AF

C01E
104

10
11
12
13
14
15
16
9

CN-LEV

WH YL OR BL BR RD

SMW-250-6P

STEPPING MOTOR

STEPPING MOTOR

+5V

B2

B1

B0

COMP

B4

B3

SM13

SM12

SM20
SM21

8
7
6
5
4
3
2
1

SM40

SM33

SM32

B7

IC1

4
5

B2

B1

P30

17

18

19

16

IC2

A6

A7

A5

A6
A5
A4
A3

A1

A2

CS4

A4

A5

A6

A1

A2

A3

A4

A5

A6

A7

A3

A0

A1

A2

A0

CS5

A3

A2

A1

A0

CS1

A0
A1
A2
A3
A4

CS1

A7

A6

A5

CS2
CS3

CS4
CS5
A6

A1

A0

A7

A3

A4

A5

CS6

A6

A3

A4

A3

A2
A1

A2

A0

10K

R03F

10K

R04F

CS6

CS3

CS2

A1

CS6

A0
GND

CS1

A2

A5

A7

GND

A0

A1

A3

A4

A7

A7

A2

A0
GND

13

10

12

15

C02M/102

IC3

14

11

20
19

15

16

17

18

13

14

10

C03M/102

11

1K

R02F

12

49
50
51
52
53
54
55
56
57
58
59
60

R01M 10K
R02M 10K
R03M 10K
R04M 10K
R05M 10K
R06M 10K
R07M 10K
R08M 10K
R09M 10K
R10M 10K
R11M 10K

R12M 10K
R13M 10K
R14M 10K

12V
5V

104*2

+5V

12V
5V

104*2

FLASH:TMP86FS49FG

MICOM

C04H

C06H

C04H

100uF/25V

5V

12V

5V

12V

C03H
47uF/25V
C02H
104*2

A0
A1
A2
A3

A5

A4

1
3

12V

A7
GND

NF01J

3
4

IC1

19

20

18
17

13

14

15

16

12

11

NF01J
22mH/3A

74HC574

12

13

14

B0
B1
B2
B3

5V

IC3

AC

RY-HEATER1
RY-HEATER2
RY-HEATER3

CN_LEFT_SW

CN_RIGHT_SW

RY-HEATER4

3
4

CS2

19
18

16

17
5

15

B7

B6

B5

B4

B3

B2

B1

B0

CS3

5V

C03H~C06H
103*4

R05H~R06H
1K*4

C08H
103

1
2
3

12

14

11

13
9

10

R01H~R04H
10K*4

A0
A1
A2
A3
A4
A5
A6
A7
GND

R09H~R14H
12.1K*6
1%

OR1 OR2

5V

12V

OR5

Error

Data_IN

+5V

12V

D02J
1N4148

5V

LED1

4.7K
R03Y

U05Y
MAX253

5V

R01Y

0.62K

R07Y

0.33K
(2012)

C06Y
104

4.7K

R05Y

6N137

U03Y

6N137

U02Y

TRANS01Y
1
6

C01Y
104

R01B

1.0M

10K

CC_SB1

COMP

L
1
N 2

0.62K

R06Y

104

22uF/35V

C03Y

YW-396-02V
CN-COMM

OR1

OR2

OR4

OR5

OR6

OR7

OR8

OR10

OR11

ZNR01Y

OUT

C04Y

C05Y

22uF/35V

104

L02Y
12uH

L01Y
12uH

CN-PIPE1

SMW-250-03P

CN-ROOM

OR9

11

10

CN-PIPE2

11

10

SMW-200-11P

CN_OPTION

U01Y
SN65LBC176

C02Y

IN GND

7805
VR01Y

ISOLATED GROUND PLANE

R04Y
5.1K

C08Y
104

R02Y
5.1K

C07Y
104

SS14

D02Y

SS14

D01Y

MULTI-V 485 SUB PCB

TX

SEL

RX

Fuse

250V/1.0A

S1

RY01J
G5NB-1A

Power
Y/N

D01J
1N4148

12V

C03H C02H C01H


103
103 103

RY02J
G5NB-1A

Q01K
KRC104S

ZNR01J
INR14D561K

R02J
150K/1W

C01J
0.01uF
400V

R01J
150K/1W

Q02K
KRC104S

R03J
10K

CN_A5

R04J
100

C02J
104

PC01J
TLP421

BMS ON/OFF SUB_PCB


Hotel card key pad SUB_PCB

5V
_ TX

State

12V

OR4

R04H,R05H,R07H,R08H
12.1K*5
1%

OR8 OR9 OR10 OR11


R01H R02H R03H
12.1K 6.2K 6.2K
1%
1% 1%

OR6 OR7

20

12V

PTC_HEATER
SUB_PCB

KID65004

+5V

+5V

PIPE_TH1

PIPE_TH2

ROOM_TH

IC2

CS1

10

11

12

13

B6
B7

R10H
1K

R09H
10K

+5V

B5

CS2

FP_R_DOWN

FP_R_UP

FP_L_DOWN

FP_L_UP

12V

KID65004

IC3

5V

B4

R10M
1M

R02H
1K

C01D

B5

5V

KRA104M

B0
B1
B2
B3
B4

B6
B7

AD_CH8

AD_CH9

AD_CH10

AD_CH11

AD_CH12

AD_CH13

- SUB PCB

11

AD_CH11

Q01H

TRB

19

20

NF

10

C01D

FP_L_UP

250V/
T3.15A,3A

ZNR01D

FP_L_DOWN

C07H
103

FP_R_DOWN

FP_R_UP

IC1

18

15

16

17

INR14D561K

A3

NF02J

A0
A1

A5

A4

A2

R14H

5V

R13H

A6

104*2

R12H

A7

10

P73(AIN13)

AD_CH7

AD_CH10

AD_CH6

AD_CH9

AD_CH7

AD_CH8

AD_CH6

AD_CH3

AD_CH0

AD_CH1

AD_CH2

C21D
104

AD_CH0

AD_CH1

AD_CH3

P67(AIN07/STOP3)

R05B 10K
R06B 10K

AD_CH2

P66(AIN06/STOP2)
P65(AIN05/STOP1)
P64(AIN04/STOP0)
P63(AIN03)
P62(AIN02)
P61(AIN01)
P60(AIN0)
AVDD

R04B 10K

AD_CH4

P72(AIN12)

AD_CH12

AD_CH13

GND

R11H
1K*4

A6

A0

A2
A3
+5V

Q01H
KRA104M

AC(N)

AC(L)

CN-GRIL_LEFT
FRONT
PANNEL
UP_DOWN
Motor

C02H

220uF/25V
C22H

FRONT
PANNEL
UP_DOWN
Motor

CN-GRIL_RIGHT

A1

A0

47uF/25V

C21H
C01H

R01H
10K

A1

C01H

CN_PTC1

CS1

CN_GRILL

CN_PTC2

SMW-200-8P

C05H

C07H

TRB

CS3

A2

A3

10

7
8

10

+5V

AD_CH4

P71(AIN11)

G/C

H/S1

P70(AIN10)

P74(AIN14)

SMW-200-10P

HVB_S

32
31
30
29
28
27
26
25
24
23
22
21
20
19

VAREF
P07(INT2)

74HC245

P31

10

13

11

12

C01M/102

SM22

B3

B0

SM21

B4

20

14

15

16

17

18

19

20

+5V

SM20

B6

B5

SM23

SM13

B7

SM11

SM12

SM10

+5V

B0
B1

SM43

B3

B2

B4

SM42

SM33

SM40

SM41

B6

B5

B7

SM32
SM31

P32

C02F
103

10K

R01F

SM30

C03F
103

C04F
103

OFF_ON

P33

61
62

SM42

SM41

SM11

SM10

SM43

B6

2
1

4
3

6
5

8
7

B5

A
A

A
A
A
A
A
A

SM31

D/PUMP

OUTFAN

4WAY

SM30

5V

A/C_OUT

9
10
11
12

13
14
15
16

13

10
11
12

IC03M
KID650004AF

12V

14
15
16

IC04M
KID65004AF

R01G

GT-250-3P-TS

CN-FLOAT

(2012)

R02C,20

12V

5V

R01C
1K
(2012)
BZ01C
PKM13EPP-4002

A0

74HC574

H/S2

H/S1

PWM

on/off

+15V

DC LOW
VOLTAGE GND

DC310V

R13D 1K

R14D 1K

R09D 1K

R08D 1K

103 (DIP)

CY7

ZD03D
BZX55C11

R21D
39

R07D
1K
1/4W

IC02D
PC-17K1

DC HIGH
VOLTAGE GND

D03D
UG2D

C22D
104(DIP)

5V

D07D
1N4148

D06D
1N4148

5V

A1

74HC574

C06D
470uF
25V

SMPS(6170A90026A)

R03K,1K

Q04
KRC102S

R20D
110K,2W

IC05D
TLP181-BL

1BP

4 EN

D08D
1N4937

2 S

5 D

DC 5V

IC01D
TNY267P

R17D
470

C19D
103,630V

CN_PN
YW-396-03

IC07D

IC06D
TLP181-BL

1K

R02G

PWM

A2

P34

18
17

74HC574

68V/1W

D01K
BZX55C68

R02K C03K
1K 103
1.5K 104

D02K
1SR139-600
1N4007 CHANGE

DC310V

ZD02D
UZP-11B

Q01D
KRC104S

R18D
200K,2W

R19D
5.6K
C18D
104

1/2W

C01D
220UF
450V
or
680UF
NTC
400V
DSC8D11M

R017D
560K

BD01D (DIP)
D3SBA60

+15V

D04D
1N4148

D05D
1N4148

10K

C02G
103

74HC574

CY3~4
472M

Q04G
KRA223S

KRA223S
Q05G

TLP181-BL

IC08D
TLP181-BL

3
2
1

SW2

YFW254-03
(INT3/TC2)P15
(PDO5/PWM5/TC5)P16

(SDA)P51

(SCL)P50

P52
P53

A3

P35

63
64

10K*6

5V

_RX

C01J

CY6
332M

10nF
275VAC DELET
(DIP)
R05K
15K,3W

C02N
0.33uF
275VAC
(DIP)

DC310G

R10D

4.7K 1%
R11D
5.1K
R15D
2.7K

C14D
103
R16D
2.7K

C15D
103

CS4

LED1

(PDO6/PWM6/PPG6/TC6)P17

LED2
LED3
LED4

A4

P36

P54

A5

P37

CS5

WR_RX

A6

CC_TX
CC_RX

S_B1
S_B2

U04Y 8
6N137 7
6

CN-D/PUMP
35328-0210-NA(molex)

RY-D/PUMP

N/F01N
11mH/1.5A

1/2W

R018D
1M

DC 311V

10K
C12D
100UF
25V

R12D

+5V

R01L
10K
R02L 1K
C02L
681

WR_TX

WR_RX

A7

5V
CC_SB1
CC_SB2

S_B3

1
3

AC(COM)

ZNR01N
SVC561D-14A

C11D
473
630V
(TM)

ZD01D
6.8V

1
2

LED2

1
2

LED3

LED1

5V

R06H
12.1K

CC_SB3

1
3

3
(DIP)
FUSE
250V/T3.15A

C03N
0.33UF
275VAC
(DIP)

4
5
6

CN-MOTOR2(BL)

CN-MOTOR1(WH)

SMW-250-07P

3
4

5
6
7

R03L 1K

5V

C18K
103

Q01K
KRA102S

C16K
103

SW1

YFW254-03

R16M
1K

OR3

Drain
Motor

CN-POWER
YW396-07AV

AC(N)

AC(L)

RD

BK

BL
7

LED1

+5V

LED4

12V

Q03K
KRC102S

C17K
102

4.7K

R11K

G/C

C15M
103

DRY_CONTACT SUB_PCB

CN_Contact
BR-762C-4P

2WAY SUB M
OTOR

IN DOOR

YL

BL

WH

RD

BK
WH

YL

SMW-250-07P

DISPLAY

R07L 330,1/6W

R06L 1K

R05L 1K

R04L 1K

20

R12K

L01K
100nH

C12H 103

FAN
MOTOR

MOTOR

FAN

IN DOOR

GND
Vout

Vcc

LED2
LED3
LED4

CN-DISP

SMW-200-7P

CN-REMO
3
2
1

R29H 10K

C12K
102

12V

C20D
104

16

C15K
103 C14K
104

15

C13K
102

OSC01B
16MHZ

14

D12K

R01A 1K

P77(AIN17)

13

P40

35
(SI1)P04

(SO1)P05

36
(INT1)P03

OUT_RX

(SCK1)P06

P41(RxD2)

12

37
(TxD1)P02

OUT_TX

11

8
RESET

P42(TxD2)

10

(RxD1)p01

P44(SI2)

9
(STOP/INT5)P20

P75(AIN15)

P45(SO2)

40
7

P76(AIN16)

33

41
(XTOUT)P22

WR_TX

34

SCL

5 SDA

P43

38

2
EERROM
M24C01-BN6
WC

P46(SCK2)

1
8

P47

42

43
(XTIN)P21

2.2K
DELET

C11K
103

R03A 200

CN-CC
SMW-200-9P

CN_POWER
BR-762C-2P

39
(INT0)P00
H/S2

5
+5V

Q04K
KRA102S

R02A 10K
3

C02A
103

R05T

P10(TC1)

44
4

VDD

R15K

1N4148
DAN212K

Q02K
KRC102S

105

C01A

+5V

R01T

P11(DVO)

3
1

R04T

P12(PPG)

45
2
1

R06T

P13(TC3/PDO3/PWM3)

46
1

XIN

C11H 103

R16K
4.7K
DELET

5V
1

KIA7036P
IC01A
3.6V

SMW-200-03P

CN-UPG

R03T

P14(TC4/PDO4/PWM4/PPG4)

47
VSS

XOUT

R30H 10K

5V

C06F
103

48

TEST

PRE AMP
TFMS-2380B

Force
SW

DC12V
3
Signal
2
GND
1

GT-250-3P-TS

Schematic Diagram
6) CST Type

BUS(B)

BUS(A)

Service Manual 143

R02B
CS3

CS2

CC_RX

CC_TX

CS1

CC_SB3

CC_SB2

U_

V_

W_

Fo

Discharge
Suction
OUT_Air

1
3

1
C11H~C15H

+5V

2
3

1UF/50V

1
3

5
6

R11H
18K

C01H
104

R12H
6.2K

C02H
104

R13H
12.1K

C03H
104

R01T
10k

R14H
6.2K

C04H
104

R15H
6.2K

C05H
104

12V

7
8

1K

R05T

R06T

C05D
220UF
16V

5V

R01H~R05H
1K

D01M
EG01C

18

15

16

14

13

Q01M
KRC107M

C02N
103

CT_AD

U1

U1

U1

U1

U1

U1

+5V

C01N
100UF

D06N
1N4148
R02N,1.65K,1%
+

D01N~D04N
1SR139-600

R01N
680, 1%

IC01M
GMS81516
64

CT01N

VDD

63

61

P67(AIN07)

60

P71(AIN11)

P65(AIN05)

P64(AIN04)

62

P74(AIN14)

P73(AIN13)

P66(AIN06)
4

P72(AIN12)

59
58

P63(AIN03)
6

7 P76(AIN16)

55

57

54

P61(AIN01)

53

8 P77(AIN17)

VREF

52

56

VASS

P60(AIN00)
10 P01(V)

P54

51

P53(HPWM0)

50

13 P04(V)

P51(INT4/TC4)

P52(PWM4/PDO4)

11 P02(U)

15 P06(EMG1)

14 P05(U)

48

49

45

46

47

P47(SDA/SO)

P50(INT3/TC3)

44

P46(SCL/SI)

17 P10(INT0)

P44(TxD)

P45(SCK)

43

P43(RxD)

21 P14(PPG)

P42

19 P12(INT2/TC1)

22 P15(DVO/TC2)

42

+5V
TSUP_E
TSUP_D
TSUP_C
TSUP_B

GND
TX_E

5V

TSUP_A
RX_F
TX_F
RX_E
+5V

RX_D
TX_D
RX_C
TX_C
TX_B

RX_B

C17D
103

5V

R06H~R10H
1K

LEV_CTL_C

TX_A

RX_A

LEV_CTL_A

LEV_CTL_B

R16H

R17H

R18H

6.2K

R19H

6.2K

R20H

C10H
104

6.2K

C09H
104

12.1K

C08H
104

BUS_ADDR_LEV

R12M~R22M
4.7K

5V

C16H~C20H

1UF/50V

311V

R31K
1M,1/2W

C31K
15uF,450V

C13K
471,250V

RY-SV

RY-4WAY

RY-HEATER

RY-FAN2_L

CN-SV

CN-4WAY

CN-HEATER

RY-FAN2_H

CN-FAN2

FAN2

MOTOR

FAN1

MOTOR

RED

WHITE

GND

BLACK

G/Y

CN-FAN1

3 ,380V,60Hz
CN-INPUT

G/Y

RY-FAN1_L

RC04M

RY-FAN1_H

CN-POWER

2
2

D13K 100D-9
NTC01K
1SR139-600

R04M~R20M
68K

C07H
104

6.2K

C06H
104

BUS_COM

5V

R06V
1K

Q01Z
KRA107M

Q01V
C3198

R05V
10K

R04V
10K

H/Press INT

LEV_ENABLE
LEV_B_1
LEV_B_2
LEV_B_3
LEV_B_4
LEV_A_1
LEV_A_2
LEV_A_3
LEV_A_4

+5V

R03V
33K

C01V
102

FUSE
250V/5A

RY-START

PTC
CN-AC
1

561

39

41

38

40

P36

37

P41

P35

36

P40
26 TEST

P34

35

P37
27 P21

34

23 P16(PDV1)

28 P22

P33

33

24 P17(PDU1)

29 RESET

P30

P31

CN-PWR

IC01V
TLP621-BL

P32

D01V
1SR139-600

30 XIN

1/4W

R02V
1K

31 XOUT

25 P20(INT5/STOP)

20 P13

18 P11(INT1)

16 P07(CL1/PDW1)

12 P03(W)

9 P00(W)

P62(AIN02)

P75(AIN15)

1 P70(AIN10)

D05N
1N4148

DISCHARGE
SUCTION
OUT_AIR
OUT_PIPE
TSUP_F
CT_AD
DC_LINK
H/Press INT
W2

U1
RY-PWR
F0_IPM
IPM_5V_ENB
RY-HEATER
RY-4WAY

RY-FAN_1L

RY-FAN_1H

RY-SV

RY-FAN_2H
RY-FAN_2L

RY-START
R30M

+5V

4.7K

R01V
62K,3W

32 VSS

RY-DISC

RC05M

DSA-362MA

L1:2.0mH

1W/1M
2.0uF

500V,25A

500V,25A
561

500V,25A

U1

U1

R01B,1M

+12V

R01Y
70K,3W

R02Y
70K,3W

OSC01B
16MHz

C01Y
222

RY-DISC

RY-PWR

R11Y,R12Y
56K,3W

CN-DC

1uF

821
(102)

821
(102)

821
(102)

11

12

10

C04M
104

R03Y
82K
1/4W
Q01Y
C3198

ZD01Y
20V
1W

LED01Y(GREEN)

Q02Y
C3198

2
2

472
332

L2:1.5mH

1W/1M
2.0uF

1W/1M
2.0uF

+5V 1/4W

IC01Y
TLP621

R04Y
2.2K
1/4W

ZNR01D
ZNR561D14

1
1

HIGH
PRESS

1uF

1uF

1uF

R06Y,10K

R07Y,1K

NF01J

C01J
104,275V

Power
Relay

472
332

10K

R02T

R07T

+5V

R08T

107M

LED01T
(RED)

10K

+5V

56K
LED02T
(YELLOW)

1K

C01A
102

R01A,1K

7805

IC04D

C15D C16D
103
104

4
D01D~D04D
1SR139-600
R01D
27,5W

C02J
104,275V

17

1K

R04T

R03A,100
+

D09D
1SR139-400

C04D
680UF

IC01D

G6551

TEST S/W

47uF/50V

C03T

C02T
103

V2

R03T,1K

Q01T
C04T
103

IC04M
KIA65084

U2

C01T
103

W1

R02A,4.7K
IC01A
KIA7036P

+12V

R09D
1K

D06D
1N4937

IC02D
TLP621-BL

FB01D
FBA04HA900

IC03D,SE012N

C03A
10uF/50V

R08D
1.2K

D08D
RU2YX

C04A
102

C03D
2200UF
35V
C14D
473

C11D,473,630V

C12D,100P,1KV

R05D
5.6K
1/4W

R00D
1M,1/2W

R05Y
15K

V1

CN-IPM

2
3
4

3
4

R10T~R15T, 270

2
1

OUT_Pipe

5V

+5V

R03D
47K
3W

R04D
10,1/4W

D05D
EG01C

C02D
47UF
50V

FB02D

5
R06D
680,1/4W
3
C13D
680P D07D
1N4937
50V
R07D
1 ,1W

R02D
82K,1W

Comp
OLP

1uF

472
332

472
332

CN_TH3

CN_TH4

CN_TH5

Pipe F

8
8

+5V

16

15

14 1

12

13

11

C01D
68UF
400V

RM20TPM-2H
AC440V/DC1600V, 40A

CT01N/30A 1:3000

1uF

RC03M

CN_TH1
CN_TH2

IC07S

IC06S

D11D

17

S-TRANS
D10D

C06D
220UF
35V

C07D
220UF
35V
D12D
C08D
220UF
35V

D13D
C09D
10

REACTOR
28A 0.68mH

DC LINK

IC05S

IC04S

IC03S

IC08S

IC02S

CN-GATE2
15
V

15
V

15
V

15
V

330UF
35V

CN-GATE1

100K,2W

MAGNETIC S/W
480V /40A

RC01M

RC02M

IC01S

IC09S

GND

Fo

100K,2W

IC10S

In

6 5 4 3 2 1

CN_TH3

C12S
R06S
104
20K

C06S
10UF

C11S
R05S
104
20K

C05S
10UF

Vcc

Out Si GND

6 5 4 3 2 1
7

C10S
R04S
104
20K

C04S
10UF

GND

Fo

Br
Wn
F0
Vnc
13
18
15 19

In

Out Si GND

Vcc

Vn1
14

GND

Fo

Vn
17

In

TEMP

Vcc

R03S
20K

GND

Out Si GND

IPM
PM50CSD120

7 6 5 4 3 2 1

C09S
104

Un
16

Fo

Vcc
In

Vcc

Out Si GND

B
NC

7 6 5 4 3 2 1

9 8

In
Fo

GND

CN_Test
2

9 8

GND

Out Si

R02S
20K

C03S
10UF

C08S
104

C02S
10UF

GND

GND In Vcc
Fo

Out Si

R01S
20K

GND

GND In Vcc
Fo

Out Si

TLP559*6
TLP521*4

C07S
104

C01S
10UF
+

Vupc
Up Vup1 Vvpc Vp Vvp1 Vwpc Wp Vwp1
1 2
3
4
5 6
7
8
9 10 11 12
Vfo
Ufo
Wfo

COMP

400V
2200uF

144 Multi type Air Conditioner

800V,0.27uF

400V
2200uF

Schematic Diagram

2. Outdoor Unit

1) A2UW146FA0/1/2, A2UW166FA0/1, A2UW186FA0, A3UW186FA0/1, A3UW246FA0, A4UW246FA0, A4UW306FA0

1 1
2 2

2
3

2
3

2
3

2
3

CN-TH4

CN-TH3

CN-TH2

CN-TH1

WCN-W
YL

LONG
NORMAL

R14H
18K,1%
2012

R13H
1.5K,1%
2012

R09H

+5V

R10H

20K
2012

R07P

R06P

R08H
R07H

R05H

R06H

R04H
R03H
R02H
R01H

+15V

R01H~R08H
1K 2012

+5V

C07H

R15P~R17P

R18P

C08H

C09H

C10H

C11H

+5V

C12H

G
A2

C01L
103
2012
+5V

SCL

WP

Vcc

+5V

2012

R02L
4.7K

C.T
R03N
20K
2012

INPUT VOLT

C09D
104

LOW-V

L03D
12uH

+5V

C02N
102K
2012

92

89

88

87

90

91

86

+5V

JIG POINT

R14T
1K
2012

R04T
4.7K

84

83

82
P05/AN05

81
P07/AN07

P04/AN04

P06/AN06

INT4

INT3

P14

PCB Auto Check

85

P95

P96

P93

P94

P91

P92

P90

Vref

7
8

P10/AN0
AVss

CLK1/P65

P101/AN1

P103/HEAT_SINK

P102/AN2

P105/PIPE

P107/DISCHARGE1

P01/AN01

P104/OUT_AIR

P106/SUCTION

P00/DISCHARGE2

P02/AN02

P03/AN03
CE/P50

P47 47

P20/AN20

INT5

P22/AN22

P21/AN21

P23/AN23

CNVss

P24/AN24
P25/AN25

P27/A7

P26/AN26

Vss

P46 48

P31/A9

EPM/P24

P32/A10

P60

P33/A11

Vcc2

P30/A8

P80/U

P82/INT0

P73/V

P74/W

P75/W

P41/A17

P40/A16

P37/A15

P36/A14

RXD1/P66
TXD1/P67

34

RST1/P64

35

TXD-5

36

RXD0/P62

RXD-4

P61 37

TXD-4

38

RXD-3

P26 39

TXD-3

P25 40

RXD-2

P23 42

33
RX_Flash

TXD-2

RXD-1

P21 44

41

TXD-1

P51 45

46
4.7K

VDC

9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 27 28 29 30

R17T
4.7K

R16T

50

R15T

4.7K

RXD-5

C02T
102K
2012

TX_JIG_S

LED1

LED0

RX_JIG_S

IPM Fault Signal

INT_HP
PSC F/Signal
Phase Control
DC Fan On/off
RY-PWR

RY-OIL/S

RY-C/COMP

RY-HOT GAS

RY-HEATER

RY-P/ICE

RY-4WAY

PTC
40 OHM

RY-PWR
G4A-1A-PE

G4A-1A-E

ZD03K
68V
R12K
1.5K
1/4W
1%

R13K
1.5K
1/4W
1%

ZD04K
68V

ZD05K
68V
R26K
1.5K
1/4W
1%

R27K
1.5K
1/4W
1%

ZD06K
68V

ZD07K
68V
R28K
1.5K
1/4W
1%

ZD08K
68V
R29K
1.5K
1/4W
1%

COMP
(single)

COMP_AC_IM

RY-C/COMP

AC (L1)

IC12K
TLP421(Dip)

IC11K
TLP421(Dip)

IC10K
TLP421(Dip)

IC09K
TLP421(Dip)

IC08K
TLP421(Dip)

IC07K
TLP421(Dip)

IC06K
TLP421(Dip)

IC05K
TLP421(Dip)

IC04K
TLP421(Dip)

IC03K
TLP421(Dip)

IC02K
TLP421(Dip)

IC01K
TLP421(Dip)

ENABLE3

ENABLE2

ENABLE1

RY-FAN(A)_L

RY-FAN(A)_H

PSC(On/off)

RY-FAN(B)_L

RY-FAN(B)_H

2012

680

R41K

2012

R40K
680

2012

680

R39K

2012

680

R38K

2012

680

R07K

2012

680

R06K

80 79 78 77 76 75 74 73 72 71 70 69 68 67 66 65 64 63 62 61 60 59 58 57 56 55 54 53 52 51
+5V

+5V

R23K
10K

R19K
1K 2012

+5V

+5V

R22K
10K

R18K
1K 2012

+5V

+5V

R11K
10K

R09K
1K 2012

+5V

+5V

R10K
10K

R08K
1K 2012

+5V

+5V

P43/A19
P45 49
2012

2012

R24K
10K

R20K
1K 2012

+5V

+5V

R25K
10K

R21K
1K 2012

AC (L)

RY-HOT GAS
G5NB-1A

+5V

2012

C06K
102K

C07K
102K

2012

C08K
102K

2012

C09K
102K

2012

C10K
102K

2012

C11K
102K

2012

C12K
102K

2012

C13K
102K

C14K
102K

2012

C15K
102K

2012

C16K
102K

2012

C17K
102K

RY-OIL/S
G5NB-1A

P44

TX_Flash

31

32

RY-HEATER
G5NB-1A

RXD-6

TXD-6

P22 43

RY-4WAY
G5NB-1A

TXD0/P63

RY-P/ICE
G5NB-1A

CN-HOT GAS

CN-OIL/S

CN-HEATER

CN-4WAY

CN-P/ICE

P42/A18

P72/V

P35/A13

P34/A12

P81/U

P83/INT1

P84/INT2

P85/NMI

Vcc1

Xin

Vss

Xout

RESET

P86

MITSUBISHI
M16C/62P Group
IC02A

P87

BYTE

93

TX_JIG_PC

RX_JIG_PC

RESET

C03F
102

RXD-6
TXD-6

4.7K

R01T

+5V

R01B
0

R07F
1K

R02T
4.7K

Phase Freq
Q01C
KTC3198Y
(DIP)

INPUT VOLT

PWM

FAN FG

R01L
4.7K

1
2
3

C01C
103K
50V

C.T

R01C
12K,1%

+5V

+5V

OSC01B
4MHz

R18T
4.7K

2012

+5V

R03A
1K
2012
C02A
102
2012

TX-CC

RX-CC

R02C
47K,1/4
1%

R07C
1K,1/4
5%

C02C
102

10V(RN)

220uF

C01N

D02N
1N4148

+5V

R06C
2.7K,1%

CN-WRITER

SDA

C07H~C12H
C102*7

1
2
3
5

EEPROM
M24C08

R06Z

R05Z

R01Z~R06Z
100
2012

R02N
1.65K 1%
1/6W

D01N
1N4148

R02V~R05V
47K,1/4W,5%

94

A1
A0

2012

R01A
4.7K
R02A
IC01A
100
2012
KIA7036P
3
C01A
3.3UF,50V
2

R02Z

R01Z

R03Z
R04Z

D01V
1N4007

R05C
12K,1%

D02C
1N4148

+5V

R03C
10K,1%

R04C
4.7K,1/4
1%

C03C
25V,47uF

D01C
1N4007

C03A
104

BD01N
DF08M

R01V
47K,1W,5%

AVcc

BD01C
DF08M

R01N
1K 1%
1/6W

IC01V
TLP421_BL

R06V
1K,1/4
5%

95

R19P

C06P~C08P
102M

+5V

R07V
10K

R12Z
4.7K

C05Z C06Z
122
471

R11Z
2K

+5V

4.7K
1/4W(or 2012)

C04Z
122

R10Z
4.7K

R20P
R18P~R20P
1K 2012

R09Z
2K

C03Z
471

TRANS1
50Hz,DC12V

R08V
1K

2012

+5V

2012

1/4W

C01V
102K

R06F
4.7K
FAN FG

6.8V
ZD01F

12

14

C05P
102
2012

IC01P
KIA339A

R07Z R08Z
4.7K
2K

C02Z
122

CT01N
Current Trans

INT_HP

2012

R05F
10K

2012

R03F
4.7K

CN-FAN(B)

96

R08P

R05P

R09P

2012

C04P
104

R10P

R14P
7.5K
1/4W 1%

R05P~R10P

50V

10uF

C01H

12.1K,1%
2012

2012

C01P~C03P
331

50V

10uF

C02H

R11H

R21P
7.5K
1/2W 1%
R11P~R13P
15K
1/4W 1%

R01P~R04P
470K
1/2W 1%

50V

10uF

C03H

6.2K,1%
2012

R12H

50V

10uF

C04H

6.2K,1%
2012

+15V
R13Z

R14Z

R15Z

C01Z
471

AC(L)

AC(N)

+15V

AC (L)

AC (L1)

Q03F

Q04F

C08Z

D02Z

+
C10Z

C12Z

D03Z

3.9K,1/4W,1%

R17Z

R16Z
20A :47,1/4W,1%
30A :56,1/4W,1%

18K,1%
2012

50V

10uF

C05H

R15H

12.1K,1%
2012

50V

10uF

C06H

4.7K
2012

OR1

R16H

1
2
3

SW1

PIPE LENGTH
5V : NORMAL
GND : LONG

C07Z

C09Z

D01Z

C07Z,09Z,11Z : 104K 2012

21
20
23
18
17
16
15
19
13
12
C11Z

R20Z
390, 2012

C08Z,10Z,12Z : 47uF 50V


R13Z~R15Z : 20 1/4W

VS(W)

22

D01Z~D03Z : 1N4937

VB(W)

IN(WH)

VCC(WH)

VB(V)
VCC(VH)
COM(H)

VB(U)

VS(V)

IN(VH)

VCC(UH)

IPM Fault Sig.

Q02F

Q01F

FAN ON/OFF

2012

2012

R02F
1K

COM

VCC

VB

IN

COM

VCC

VB

SPM2
FairChild
FSAM30SM60A
FSAM20SM60A

VS

OUT

OUT
VS
IN

VB
VCC

11
14

10

2012

C18Z
102

PSC F/Signal

1K

R01F

PWM

CN-FAN(A)

P97

CSC

RSC

+5V

2012

102

C08S

C05D
220uF
35V

C03D
220uF
10V

CN-PRESS

97

W
V
U

31

32

30

IN(UH)
VS(U)

C13Z 102K,2012
C14Z 104,2012

R18Z
R19Z
20K
2012

PSC On/Off

2012

R07S
20K

+15V

+5V

C01F
103k
630V

98

WCN-V
BL
WCN-U
RD

COM
IN

C(SC)
8
7
6
5
4
3

1
4.7k
2012

2012

C17Z
102

C04S
680UF
400WV

2012

102K

C07S

50V

C08D
103

50V

C07D
103

GND

99

OUT
VS

OUT(WL)

VFO

CFOD

COM(L)
IN(WL)
IN(VL)
IN(UL)

COM(L) 2
VCC(L)

C16Z
47uF
50V

C03S
680UF
400WV

+5V

R03S
1.2K
1/4W

2012

7805

IC04D

LOW-V

R06S
4.7K

TLP421

IC02S

+15V

R03Y

D01Y
1N4148

IC01S
TLP251

C02S
680UF
400WV

D01S
1N4007

+5V

L02D
12uH

4.7K,1%

R02D

+15V

2K
1/2W

50V

C06D
103

Vcc

FAN
MOTOR(R)

100

Nw

VCC

C15Z
104Z
25V
2012

R02S
220
1/4W

2012

C05S
104

+15V

C01S
680UF
400WV

R01S
10k
1/4W

C06S
152J

C01Y
50V,2012

103K

C04D
470UF
35V

L01D
12uH

C02F
10UF
/10V

FG

DISCHARGE2

DISCHARGE1

PIPE

SUCTION

OUT AIR

HEAT SINK

YL

BL

29

VFO

C(FOD)
OUT(VL)

IN(VL)

IN(WL)
OUT(UL)

IN(UL)
COM(L)

D1

D3

D01D
1N4937

1%

R04S
0.05 R05S
71.5k

IGBT
GT50J102

C09S
152J

R02Y
270K
1/2W

13

12
9

R04F
5.1K
1/4W

Vs

RY-FAN(B)-L
JQ1A-12V

C19Z
1.5uF

Nv

Nu

C09S
0.1uF
+120

GND

OUT

R202

OUT

400VAC

28

27

26

D2

D4

D1

1%

R201

D201

PC201

25 NC
24 NC

VDC

D2

C101

270K
1/2W

R01Y

~ D3

BD01S
RBV2506
RBV1506

BD02S
RBV1506

D4

R102

BP

TNY
268

D101

R101

FB

Q03F,04F
KRA106S(Chip)

FAN
MOTOR(L)

RY-FAN(B)-H
JQ1A-12V

CN-COIL2

CN-COIL1

AC (N)

AC (L1)

IN

PC201

RD

Inv._COMP_BLDC

REACTOR
26.8mH/ 9A
11mH/ 14A

D202

Q01F,02F
KRC104S(Chip)

RY-FAN(A)-L
JQ1A-12V

+
C02D
470uF
25V

L/P

+
C01D
1000UF
35V

RD

NC

NC

C102

GND

MOTOR

RY-FAN(A)-H
JQ1A-12V
H/P

102M

C10D
6

5
YL

GND

uRM1515-2B

6
BL

u-POWER MODULE

CN-MOTOR1

BK
DC FAN

WH

+5V

CS-1
CS-2
CS-3

AC_COM

R15K
30K
1W

R14K
30K
1W

AC_COM

R16K
30K
1W

R17K
30K
1W

R30K
30K
1W

AC_COM

R31K
30K
1W
AC_COM

R32K
30K
1W

R33K
30K
1W
AC_COM

R34K
30K
1W

R35K
30K
1W
AC_COM

R36K
30K
1W

R37K
30K
1W

C09J

D08K

D07K

D06K

D05K

D04K

D03K

LED1

LED0

D03K~D08K
1N4007

AC (N)

1uF/ 275VAC

LED01G : RED_10

ER_CODE, INDICATOR

10

11

12

13

14

+15V

LED02G

LED01G

2012

R02J
20
1/4W,5%

J21~J26

C02M 104

J27~J32

NF02J

RY-FAN(A)_L

RY-FAN(A)_H

PSC (On/off)

RY-FAN(B)_L

RY-FAN(B)_H

RY-4WAY

RY-HOT GAS

2012

C01M 104

RY-HEATER

RY-P/ICE

RY-OIL/S

RY-C/COMP

RY-PWR

18

15

R02G
17 1.5K

14

16

R01G
1.5K

LED02G : GREEN_1

IC01M
KID65004AP

13

12

11

15

16

10

IC02M
KID65004AP

C07J
472M

C08J
472M

WCN_GND2

R03J
20
1/4W,5%

BK

R01K~R04K
11K/3W*4

R01M~R08M
68K

332M

C05J

C06J
332M

C04J
275VAC

1UF

D01K
1N4007

D02K
1N4007

QE
A0
A1
A2
A3
A4
A5
A6
A7
GND

QE
A0
A1
A2
A3
A4
A5
A6
A7
GND

QE
A0
A1
A2
A3
A4
A5
A6
A7
GND

ZNR01J,02J
SVC561

R04J
1M
1/2W

SURGE
DA-38-302MT-A21

R09M
10K
IC04M
74HC245AF

10

11

12

13

14

15

16

17

18

19

20

R10M
10K
IC05M
74HC245AF

VCC

CS-1

C03M
104

+5V

13

14

15

16

17

18

IC07M
KIA65084

B2

B1

B3

B0

CS

B4

11

B5

10

IC08M
KIA65084

C04M
104

+5V

17

18

12

B1

CS-2

B6

B7

VCC

CS

B0

16

20

15

19

14

18

17

B2

B3

B4

16

13

15

12

14

10

11

12

13

14

15

16

17

18

19

CS

IC09M
KIA65084

C05M
104

B3

10

11

12

13

14

15

16

17

18

B2

B1

B4

275VAC

C01J
1uF/

Q01T
KRA105

C03T
102K
2012

2012

R07T
1K

B5

RX_JIG_S

B6

R12T
4.7K

222M

C03J

222M

C02J

C02K
150uF/100V

+5V

R11T
1K
2012

20

R01J

WCN_GND1

1/4W,5%

AC_COM

B7

B0

+5V

11

12

VCC

B7

CS-3

B5
13
+5V
B6
9

11

20

10

R11M
10K
IC06M
74HC245AF

RX-CC

J51~J56

NF01J

R05K
50.5K/1W

36V,1W

ZD01K,02K

C01T
102K
2012

10

C01K
102/100V

J57~J62

BK

Schematic Diagram
2) A6UW406FA0

+15V

+15V

+5V

R06T
1K

+15V

+5V

R10T
1K

TX_JIG_S

TX_JIG_PC

RX_JIG_PC

R08T
10K

2012

+5V

+5V

TX-CC

+5V

TX

RX

TX

RX

TX

RX

TX

RX

R09T
4.7K

R05T
4.7K

C06M~C11M
104

TX_FLASH

RX_FLASH

FUSE

20A/250V

CN_LEV1

CN_LEV2

CN_LEV3

CN_LEV4

CN_LEV5

CN_CENTRAL

CN_FLASH

CN_JIG_S

CN_JIG_PC

CN_LEV6

2 2
3 3

2 2
3 3

2 2
3 3

CN-COM

4
5

2 2
3 3

WCN_P(L)
BR

CN-CP(N)

CN-CP(L)

4
5

WCN_P(N)
BL

LEV1

LEV2

LEV3

LEV4

LEV5

LEV6

C4

TB2

C4

C3

C3

C2

C2

C1

C1

GND GND

BK

WH

GR/YL

AC-POWER
AC220~240V/50,60Hz

TB1

Service Manual 145

Schematic Diagram

C10K
102
25V

C08K
102
25V

C06K
102
25V

C04K
102
25V

C02K
102
25V

BUS_COM

TX_D0

RX_D0

TX_D1

RX_D1

TX_D2

RX_D2

TX_D3

RX_D3

TX_D4

RX_D4

TX_D5

RX_D5
C12K
102
25V

5V

R07K,IK

R08K,IK

R09K,IK

R10K,IK

R11K,IK

R12K,IK

R13K
10K

R14K
10K

R15K
10K

R16K
10K

R17K
10K

R18K
10K

R01K
1.5K

R02K
1.5K

R03K
1.5K

R04K
1.5K

R05K
1.5K

R06K
1.5K

IC02K(TLP627)

IC01K(TLP621)

IC04K(TLP627)

IC03K(TLP621)

IC06K(TLP627)

IC05K(TLP621)

IC08K(TLP627)

IC07K(TLP621)

IC10K(TLP627)

IC09K(TLP621)

IC12K(TLP627)

IC11K(TLP621)

R19K
1K

R20K
1K

R21K
1K

R22K
1K

R23K
1K

R24K
1K

ERA15-06

D01K
R25K
82K/3W

ERA15-06

D02K
R26K
82K/3W

ERA15-06

D03K
R27K
82K/3W

ERA15-06

D04K
R28K
82K/3W

ERA15-06

D05K
R29K
82K/3W

ERA15-06

D06K
R30K
82K/3W

D07K
ERA15-06

D08K
ERA15-06

D09K
ERA15-06

D10K
ERA15-06

D11K
ERA15-06

D12K
ERA15-06

DC310V

A5

A4

BUS_ADDR_LEV

QE
A0
A1
A2

CN-DATA
2

A3

GND

A7

A6

2
4

3
5

QE
A0
A1
A2
A3
A4
A5
A6
A7
GND

QE
A0
A1
A2
A3
A4
A5
A6
A7
GND

R01M
10K

IC01M

19

20

12

13

14

15

16

17

18

1
245

11

10

R02M
10K

IC02M

19

20

12

13

14

15

16

17

18

1
245

11

10

R03M
10K

IC03M

19

20

12

13

14

15

16

17

18

1
245

11

10

VCC
CS_LEV12
B0
B1
B2
B3
B4

5V
C01M
104

IC05M
KIA65084

12V

15

16

17

18

14

12

13

11

6
B6

10

B5

12V

IC06M
KIA65084

5V
C002M
104

B7

VCC
CS_LEV12
B0
B1
B2

15

16

17

18

14

12

11

B4

B6

10

18

13

B3

12V

IC07M
KIA65084

B5

5V
C003M
104

14

17

13

12

16

11

15

B4

10

B5

B7

VCC
CS_LEV12
B0
B1
B2

B6

B3

B7

C07B
103

C08B
103

C09B
103

C10B
103

C11B
103

C12B
103

CN_LEV
5

CN_LEV
6

CN_LEV
3

CN_LEV
4

CN_LEV
1

CN_LEV
2

LEV5

LEV6

LEV3

LEV4

LEV5

LEV6

146 Multi type Air Conditioner

+12V

C07D
220uF
25V

1/2W

1K

R01D

L1
12uH

SEL

C06D
470UF
25V

13

12
9

GND

D202

PC201

R201

D201

OUT
OUT

R202

GND

C09D
102M

C101

IN
R101

PC201

GND

FB

D101

R102

TNY
267
BP
C102

42

41

u-POWER MODULE
uPM1512-C2

43

3 NC

TXD1

38

37

16

17

18

19

35

22

34

PA5

PA4

PA6

32
31

PA7

AGND

30
29
28
27

25

26

24
23

LED02G

LED01G

LED03G

2012

(DIP)

BD01D
DF08M

R04T
10K

R02G
470

R03T
1K

R03G
470

R01G
470

1/4W

R02D
300K

NTC D05D
SCK102 1N4007

36

21

33

+
C01D
4.7uF
450V

20

RXD1

39

5 NC
6

40

15

5V

2012

C01X
102K

5V

FUSE_1
250V/T3.15A

5V

TXD1

4.7K
R14K

RXD1

5V_EXT

GND

TX

RX

CN_OUT

12V_EXT

5V

GND

TX

RX

CN_JIG

7805

IC05D

5V_EXT

R15K
1K/0.62K

C04X
104

RXD2

TXD2

15pF
C03K

104
C01K

5V_EXT

CN_PWR

8
2

6N137

4
IC02K(6N137)

IC01K(6N137)

C10D
220uF
10V

15pF
C04K

5V

104
C02K

R13K
1K/0.62K

ZNR01N
SVC561D-14A

5V

R12K
1K/4.7k

C01N
104
275VAC

N/F01N
11mH/1.5A

R01X
1K
2012

5V_EXT

C08D
103
50V

5V

1
3

44

ATMEGA162

14

IC04D
7805

D05D
1N4007

C04Y
22uF/35V

2
4

13

C05Y

CN-COMM

12

C04D
103
50V

IC03D
KID78L05BP
I
O
7805

C03Y
22uF/35V

104

R08Y
1K

ZNR01Y
SVC220D-07B

R09Y
1K

SCK

PD2

10

C02Y
104

D05D
1N4007

D01Y
SS12

D02Y
SS12

U01Y
SN65LBC176

R02Y
5.1K

8
7
6
5

MOSI 1
MISO 2

RXD0 5

RESET 4

AVCC 6

PD3

11

R05T 10K

R06T 10K

6N137

C07Y
104

C08Y
104

1
2
3
4

RXD0
TXD0

5V

PD4

TXD0 7

PD5

SEL

5V

C09Y
104

Trans01Y

U02Y
6N137

8
7
6
5

R04Y
5.1K

RXD0

SEL
SCK

TXD0

5V

5 o o 6

3 o o 4

1 o o 2

BR1

7 o o 8
9 o o 10

CON5*2

S10R

S40R

S30R

S20R

C02H

R03X
1K
2012

C05D
220uF
10V

8
7
6
5

1
2
3
4
U03Y
6N137

8
7
6
5

R06Y
0.62K

R01A 1K

R05S

D05D
1N4007

1
2
3
4

R01Y
0.62K

R07Y
0.33K

1
2
3
4

4
3
2
1

U04Y
6N137

5
6
7
8

R03A 120

C02A
104

SWITCH

OMRON_B3WN

R06S

U05Y
MAX253

R03Y
4.7K

4.7uF

C01A

IN
SW4
SW3
SW2
SW1

C03H

2012

C02X
102K

TXD0
SEL
RXD0
LED1

C06Y
104

R02A 4.7K

R05Y
4.7K

1
2

KIA7036P

IC01A
3.6V

R02M 1K

OUT

C04H

VCC
TXD2

4*K1
W8/1

4*301

C05H

GND

RXD2

SW DIP-4

R08S

5V

C03A
102

V5

RXD1

VCC

C03X
104,2012

V5
V5

ON

TXD1

GND
1M

Xtal2
OSC01B

Xtal1

12uH
L01D
12uH
L02D
5V

R07S

4*K01
W8/1

R01B
14.7456

Schematic Diagram

3. Central control unit Schematic diagram

5V

Service Manual 147

Schematic Diagram

Wiring Diagram

DC PCB ASM
FAN
MOTOR

CN-ACDC1

THERMISTOR(IN-PIPE)
THERMISTOR(ROOM)

DC PWB ASM

ZNR

ZNR

CN-ACDC2

WH
BK
YL
RD

THERMISTOR(OUT-PIPE)

CN-GND1

AC PWB ASM
CN-MOTOR1

CN-MOTOR

CN-U/D CN-TH1 CN-TH2

AC PCB ASM

2. Art Cool Type Indoor Unit

CN-POWER

1(L) 2(N)

CN-POWER

RD

BL

BR

FUSE
250V 2A

GN/YL

FUSE
250V 3.15A

CN-D1(WH) CN-D2(WH)

THERMISTOR(OUT-PIPE)
THERMISTOR(IN-PIPE)
THERMISTOR(ROOM)

STEP
MOTOR

STEP
MOTOR
STEP
MOTOR
RD

H.V.
ASM BK

SAFETY S/W

STEP
MOTOR

3854A20135Y

PLASMA
AIR CLEAN

DISPLAY
PCB
ASM

CONNECT
PCB ASM

SAFETY S/W

TO OUTDOOR UNIT

CN-HVB(BL) CN-LR2(WH) CN-LR1(WH) CN-UD(BL) CN-TH1CN-TH2

1. Room Type Indoor Unit -SQ/SR/ST chassis

FORCE S/W

3854A20135W

3. Room Type Indoor Unit - S4/S5 chassis

4. Duct Type Indoor Unit - BG/BT chassis


ROOM.
IN-PIPE.
OUT-PIPE.
CENTRAL CONTROL
REMOTE
TELE CONTROL THERMISTOR CONTROL THERMISTOR THERMISTOR
DRY CONTACT

CN-PIPE1

CN-REMO CN-PIPE2

CN-ROOM

PTC
HEATER

CN-AIRC

CN-PTC

VENTILATION
E/HEATER

CN-POWER

TO OUTDOOR UNIT

BL
BR
FUSE

1(L) 2(N)

GN/YL

CN-PIPE1

FLOAT S/W

RD

CN-ZONE

ZONE CONTROL

CN-CC

A/CL
UNIT

CN-OUT

WIRING DIAGRAM

CN-DISP
CN-MOTOR

CN-DPUMP

OPTION
RF-REMOTE
CONTROL

3854A20419A

CN-L/R

STEP
MOTOR

STEP
MOTOR

TRIAC

BK

BR

ZNR

YL

CN-HVB

SH-CAPA

MOTOR

MAIN PCB
ASM

CN-U/D

OR

CN-MOTOR

5. Art Cool Deluxe Type Indoor Unit


A/C MOTOR

BK

A/CL

THERMISTOR(IN-PIPE)
THERMISTOR(ROOM)

CN-VFD

3 4

RD

BK

THERMISTOR(OUT-PIPE)

CN-TH1

CN-POWER

BR
BL
GN/YL
RD
1(L) 2(N)

FUSE
250V 2A

RD
H.V.B

CN-TH2

GN/YL

DISPLAY

CN-MAIN
CN-SW/1

FORCED
OPERATION
S/W

INDOOR WIRING DIAGRAM


3854A20135X

CONNECTOR
PCB ASM

CN-STEP1

CN-STEP2

SUC
STEP
MOTOR-1

SUC
STEP
MOTOR-2

CN-SW/2 CN-SW/3

TO OUTDOOR UNIT

148 Multi type Air Conditioner

LIMIT
S/W-1
LIMIT
S/W-2

BLDC MOTOR

Schematic Diagram

6. Duct Type Indoor Unit - BH/BP chassis 7. CVT Type Indoor Unit - VE chassis
WIRING DIAGRAM
WIRING DIAGRAM

CN-POWER

RD

CN-TH1

CN-TH2

CN-FLOAT

IN-PIPE.
THERMISTOR
ROOM
OUT-PIPE.
THERMISTOR THERMISTOR FLOAT S/W

CN-DPUMP

GN/YL

FUSE
CN-DISP

CNMOTOR

TO OUTDOOR UNIT

CN-ACDC

TO OUTDOOR UNIT

FUSE

HVB

CN-DISP
CN-MOTOR

AC PCB ASSY

5
4
BL

1(L) 2(N)

CN-PIPE1

GN/YL
BR

CN-UD1

DC PCB ASSY

A/CL UNIT

RD
FLOAT S/W

S/W1

VENTILATION
E/HEATER

GN/YL
BL

1(L) 2(N)

CN-PTC

CN-HVB

CN-ROOM

CN-OUT

CN-REMO CN-PIPE2

CN-ZONE

ZONE CONTROL

CN-PIPE1

CENTRAL CONTROL

CN-AIRC

S/W2

CN-CC

STEP
MOTOR

CN-ACDC

PTC
HEATER

CN-CC

A/CL
UNIT

CN-DOOR

ROOM.
IN-PIPE.
OUT-PIPE.
CENTRAL CONTROL
REMOTE
TELE CONTROL THERMISTOR CONTROL THERMISTOR THERMISTOR
DRY CONTACT

BR

CNDPUMP

OPTION

DISPLAY
PCB ASSY

3854A20419D

OPTION
RF-REMOTE
CONTROL

3854A20419B

8. CVT Type Indoor Unit - VB chassis

9. CST Type Indoor Unit - TE/TF/TD chassis

CN-TH1

CN-TH2

CN-FLOAT

IN-PIPE.
THERMISTOR
ROOM
OUT-PIPE.
THERMISTOR THERMISTOR FLOAT S/W

CN-DISP

DISPLAY
PCB ASSY

CNMOTOR

BR

3854A20419E

CN-REMO

REMOTE
CONTROL

STEP
MOTOR

CN-UD1 CN-UD2 CN-LR1 CN-LR2

GN/YL
BL
BR
FUSE

CNDPUMP

OPTION

STEP
MOTOR

BL

CN-HVB

CN-CC

FUSE

GN/YL

CENTRAL CONTROL
TELE CONTROL

3
GN/YL
1(L) 2(N)

CN-ACDC

CN-ACDC
CN-HVB

HVB

RD

TO OUTDOOR UNIT

CN-PIPE2 CN-ROOM CN-PIPE1


A/CL UNIT

STEP
STEP
MOTOR MOTOR

CN-PTC
PTC
HEATER

CN-FLOAT

CN-DISP

DISPLAY PCB ASSY

CN-MOTOR

TO OUTDOOR UNIT

CN-CC

A/CL UNIT

CN-UD1

1(L) 2(N)

S/W1

CENTRAL CONTROL

OUT-PIPE.
ROOM.
IN-PIPE.
THERMISTOR THERMISTOR THERMISTOR

CN-DOOR

S/W2

STEP
MOTOR

DOOR S/W

WIRING DIAGRAM

HVB

WIRING DIAGRAM

CN-DPUMP

OPTION

FLOAT S/W

3854A20419C

10. CST Type Indoor Unit - TE1 chassis

11. CST Type Indoor Unit - TH chassis

Service Manual 149

Schematic Diagram

12. CST Type Indoor Unit - TC chassis


INDOOR WIRING DIAGRAM
TEMP.
PIPE IN
THERMISTOR THERMISTOR

FLOAT S/W

CAPACITOR

GN/YL
GN/YL

DRAIN
PUMP

CN-FLOAT

OR

CN-POWER

CN-DISP

FUSE T3.15A

CN-AIRC

BK

REMOTE
CONTROL

(OPTION)
RD
BK

AIR
CLEANER

H.V.B

1(L) 2(N)

DOOR S/W

RD

RD
WH

BR BL

STEP
MOTOR

CN-REMO

CN-DPUMP

PIPE OUT
THERMISTOR

INDOOR
MOTOR

CN-PIPE1

MAIN PCB ASSY

CN-MOTOR

DISPLAY PCB ASSY

CN-ROOM

BK

CN-PIPE2

YL

CN-STEP

BR

TO OUTDOOR UNIT

P/N:3854A20405A

14. ART COOL MIRROR-SE

150 Multi type Air Conditioner

13. CST Type Indoor Unit - TC1 chassis

Schematic Diagram

5. Outdoor Unit
1. A2UW186FA0

2. A3UW246FA0
OUTDOOR WIRING DIAGRAM

INVERTER
COMPRESSOR

OUTDOOR WIRING DIAGRAM

INVERTER
COMPRESSOR

RD BL YL

REACTOR
RD BL YL

REACTOR

OR

CN-FAN(A)

BK

OR

BL
BK
BR
YL

FAN

RD

LEV

MAIN
PCB

LEV

YL

BK

CN-FAN(A)

BK

LEV

CN-TH3

(H/SINK)
(DISP-I/SUG)
LOW PRESS
SWITCH

CN-COM

BL
BK
BR
YL

4WV 4WAY VALVE

CN-4WAY

MAIN
PCB
CRANKCASE
HEATER

CN-HEATER
CN-TH2

CN-TH1

CN-TH3 CN-TH4

OPTION
DEFROST

SV (HEATING)

CN-P/ICE
(H/SINK)
(AIR/PIPE)
(DISP-I/SUG) (DISP-C)

LOW PRESS
SWITCH

CN-PRESS

SV OIL SEPERATOR

CN-OIL/S

CN-PRESS

FAN

CN-COIL1 CN-COIL2

CN-COM

RD

(AIR/PIPE)

4WAY
VALVE

BK

CN-TH2

CN-TH1

4WV

WH

CN-WRITER

CN-JIG-PC CN-CENTRAL

CN-4WAY

BL

CN-COIL1 CN-COIL2
CN-LEV2 CN-LEV1

LEV

BK

CN-JIG-PC CN-CENTRAL

LEV

YL

CN-LEV3

CN-LEV2 CN-LEV1

CN-WRITER

BL

RD

CONSTANT

RY-C/COMP

BR
BL
RD

N
CN-GND1 CN-GND2

OLP COMPRESSOR
C
R
S

BR

BK
BK

BL

BL

BR

BK
BL

BR

WH

BL

BR

GND-1 GND-2

BL

BL
BR

BR
1(L) 2(N) 1(L) 2(N) 3(A) 3(B)

1(L) 2(N) 3(L) 4(N) 5(A) 5(B) 3(L) 4(N) 5(C)


GN/YL
A ROOM B ROOM

POWER SUPPLY

A ROOM B ROOM C ROOM

POWER SUPPLY

TO INDOOR UNIT

3854A20354A

3. A4UW306FA0

3854A20354B

TO INDOOR UNIT

4. A6UW406FA0
INV-COMP

WIRING DIAGRAM

OUTDOOR WIRING DIAGRAM

INVERTER
COMPRESSOR

RD BL

RD BL YL

YL

REACTOR

REACTOR
OR

BL

RD

YL

BK

BL
BK

BK

LEV

FAN(B)

4WV 4WAY VALVE

MAIN
PCB
CN-TH2

CN-TH1

CN-TH3 CN-TH4

OPTION
SV

CN-P/ICE

CN-JIG-PC

(H/SINK)
(AIR/PIPE)
(DISP-I/SUG) (DISP-C)

CN-COM

RD

BK

BL

GND-1 GND-2

BR

BL

OPTION
CRANKCASE
HEATER

(I/SUC-DISP)

(DISP-C)

CN-OIL/S

SV OIL SEPERATOR(INV)
WH

LOW PRESSURE
SWITCH

CN-PRESS

NOISE FILTER
RELAY

GND-2

CONS-COMP
BL

GND-1

R
S C

RD

BR
GN/YL
BR

BL
BR

1(L) 2(N)

1(L) 2(N)

BL

BL
BR

T/B

BR

3(A) 3(B)

Power Supply
LEV
A

LEV
B

LEV
C

LEV
D

LEV
E

LEV
F

CN-LEV-A

CN-LEV-B

CN-LEV-C

CN-LEV-A

CN-LEV-B

CN-LEV-C

LED1

LED2

LED3

LED1

LED2

LED3

BL
BR

1(L) 2(N) 3(L) 4(N) 5(A) 5(B) 3(L) 4(N) 5(C) 5(D)

BRANCH DISTRIBUTOR-(A)
CN-ROOM-A CN-ROOM-B CN-ROOM-C
L N S
L N S
L N S

POWER SUPPLY

4WAY VALVE

4WV

CN-4WAY

TH4

(H/SINK)

GN/YL

C
R
S

BL

BL

BR

N
WH

YL

WH
BK

CONSTANT
COMPRESSOR
BR
BL
RD

CN-FAN(B)

BR

SV OIL SEPERATOR

BR

TH3

(AIR/PIPE)

LOW PRESS
SWITCH

CN-OIL/S
RY-C/COMP

TH1

TH2

FAN
(B)

BR

MAIN
PCB

FUSE
250V,20A

DEFROST
(HEATING)

YL
OR
BL
BK

CN-COIL1 CN-COIL2

YL

CN-PRESS

CN-HEATER

CN-COM

CRANKCASE
HEATER

CN-HEATER

BR

CN-LEV1

FAN(A)

CN-WRITER

CN-FAN(B)

CN-CENTRAL

CN-COIL1 CN-COIL2

CN-4WAY

CN-CENTRAL

LEV
LEV

BL
BK
BR
YL
OR
BL
BK
BR
YL

CN-FAN(A)

BK

BR

LEV

BK

CN-LEV3

LEV

CN-LEV2 CN-LEV2 CN-LEV1

YL

CN-JIG-PC

BL

CN-FAN(A)

BL

RD

FAN
(A)

BR

OR

A ROOM B ROOM C ROOM D ROOM

TO INDOOR UNIT

3854A20354C

TO INDOOR UNIT

BRANCH DISTRIBUTOR-(B)
L N S
CN-PWR

CN-ROOM-A CN-ROOM-B CN-ROOM-C


L N S
L N S
L N S

L N S
CN-PWR

TO INDOOR UNIT

3854A20354G

Service Manual 151

Schematic Diagram

5. A2UW146FA0, A2UW146FA1

6. A3UW186FA0, A3UW186FA1

OUTDOOR WIRING DIAGRAM

INVERTER
COMPRESSOR

OUTDOOR WIRING DIAGRAM

INVERTER
COMPRESSOR

RD BL YL

REACTOR
RD BL YL

REACTOR

OR

CN-FAN(A)

BK

OR

BL
BK
BR
YL

FAN

RD

YL

CN_FAN(A)

BK

4WV

4WAY
VALVE

LEV
LEV

CN-TH1

CN-TH3

(H/SINK)
(DISP-I/SUG)
(AIR/PIPE)

FAN

CN_COIL1 CN_COIL2

CN_4WAY

CN_JIG_PC CN_CENTRAL

CN-WRITER

CN-TH2

BL
BK
BR
YL

4WV 4WAY VALVE

MAIN
PCB
CN_TH2

CN_TH1

CN_TH3

CN_PRESS

(H/SINK)
(AIR/PIPE) (DISP_I/SUG)

BK

CN-COM
CN_COM

LOW PRESSURE
SWITCH

RD

LEV

CN-4WAY

CN-PRESS

BK

CN-COIL1 CN-COIL2

MAIN
PCB

CN-JIG-PC CN-CENTRAL

BL

WH

BK

CN_WRITER

LEV

YL

CN_LEV2 CN_LEV1

CN-LEV2 CN-LEV1

LEV

BL

CN_LEV3

RD

N
L

CN-GND1 CN-GND2

BL

BK

BR

BK
BL

BR

WH

BL

BR

GND_1 GND_2

BK
BL
BR

BL
BR

1(L) 2(N) 1(L) 2(N) 3(A) 3(B)


1(L) 2(N) 3(L) 4(N) 5(A) 5(B) 3(L) 4(N) 5(C)

GN/YL

POWER SUPPLY

A ROOM B ROOM

POWER SUPPLY

TO INDOOR UNIT

7. A4UW246FA0

INV-COMP(A)

WIRING DIAGRAM
RD BL

RD BL YL

YL

REACTOR

REACTOR

OR

RD

BL

YL

BK

BL
BK

CN-FAN(A)

BK

FAN
(A)

BR

YL

CN-LEV1

BK

LEV

FAN

CN-CENTRAL

BK

BL
BK
BR
YL

CN-COIL1 CN-COIL2

CN-COIL1 CN-COIL2

MAIN
PCB

CN-JIG-PC

CRANKCASE
HEATER

TH3

RD

TH4

CN-WRITER

CN-TH3 CN-TH4

OPTION
CN-P/ICE

(H/SINK)
(AIR/PIPE)
(DISP-I/SUG) (DISP-C)

RD

BK

WH

CN-COM

RY-C/COMP

DEFROST

OPTION
CRANKCASE
HEATER
OPTION
CRANKCASE
HEATER_2

BR
BL
RD

BL

BL
BR

SV SEPERATOR
LOW PRESSURE
SWITCH
CONS-COMP(B)

CN-PRESS

GND-2

RY-C/COMP

GND-1

WH
BK

BR

BK

1(L) 2(N)

C
R S

BL

RD

BL
BR

1(L) 2(N)

BL

T/B

GN/YL

BR

T/B

BL

3(A) 3(B)

Power Supply
LEV
A

LEV
B

LEV
C

LEV
D

LEV
E

LEV
F

LEV
G

LEV
H

CN-LEV-A

CN-LEV-B

CN-LEV-C

CN-LEV-D

CN-LEV-A

CN-LEV-B

CN-LEV-C

CN-LEV-C

LED-1

LED-2

LED-3

LED-4

LED-1

LED-2

LED-3

LED-4

BRANCH DISTRIBUTOR-(A)

1(L) 2(N) 3(L) 4(N) 5(A) 5(B) 3(L) 4(N) 5(C) 5(D)

BL

OIL
CN-OIL/S

GN/YL

C
R
S

BR

FM COOLING FAN

CN-C/FAN

CONSTANT
OLP COMPRESSOR

BL

BR

BL
BR

CN-HEATER2

(DISP-C)

NOISE FILTER

LOW PRESS
SWITCH
SV OIL SEPERATOR

GND-1 GND-2
BR

(SUC/DISP_I)

FUSE
250V,20A

SV (HEATING)

CN-PRESS
CN-OIL/S

(H/SINK)
(AIR/PIPE)

BL

CN-HEATER
CN-TH1

BR
C
BL R S

CN-C/COMP2

PTCR
TH1

TH2

CN-COM

MAIN
PCB
CN-TH2

4WV 4WAY VALVE

BR

CN-4WAY

CONS-COMP(C)

4WAY
4WV VALVE

CN-4WAY

CN-HEATER

CN-JIG-PC CN-CENTRAL

LEV

CN-LEV2 CN-LEV1

LEV

YL

CN-LEV3

LEV

BL

CN-FAN(A)

CN-WRITER

OR

RD

BRANCH DISTRIBUTOR-(B)

CN-ROOM-A CN-ROOM-B CN-ROOM-C CN-ROOM-D L N S


L N S
L N S
L N S
L N S
CN-PWR

CN-ROOM-A CN-ROOM-B CN-ROOM-C CN-ROOM-D L N S


L N S
L N S
L N S
L N S
CN-PWR

Only 8Rooms Model

POWER SUPPLY

A ROOM B ROOM C ROOM D ROOM

TO INDOOR UNIT

3854A20354J

8. A7UW486FA0, A8UW586FA0 9. A2UW146FA2, A2UW166FA0/1

OUTDOOR WIRING DIAGRAM

INVERTER
COMPRESSOR

A ROOM B ROOM C ROOM

TO INDOOR UNIT

3854A20354L

TO INDOOR UNIT

3854A20354M

152 Multi type Air Conditioner

TO INDOOR UNIT

3854A20354K

Schematic Diagram

Components Locations
1. Indoor Unit
MAIN P.C.B ASM
1) Split Type
DC part

AC part

Service Manual 153

Schematic Diagram
2) Art Cool Type
TOP VIEW

154 Multi type Air Conditioner

BOTTOM VIEW

Schematic Diagram
3) Art Cool Deluxe Type
A/C MOTOR
TOP VIEW

JP32
CN_MOTOR

C03J
CN_TH2
JP33

CN_L/R(BL)

JP34

CN_CC
FUSE

250V/T2A

CN

JP1

R01J

_U

/D

(W

H)

SMPS

CN

UC

(W

H)

JP43
D07D

EARTH
C05J

L1

CN

_H

VB

(B

C06D

JP29

L)
CN

C06J

_T

JP58

C04D

JP35

_V

IC01D
Q01V

OSC01B
IC01A

C02A

IC02D

JP55
JP50

IC01J

JP54

JP19

JP38

ZD02D

BD01D

JP53

D02D

C05D

IC02K

JP48

CN_CON(BL)

IC1

JP47

JP52

JP42

JP41
R02J

JP31

D05D

R03J

TR01J

H)

JP49

C01D

(W

JP46

PCB : 6870A90120C

NTC

JP51

JP30

ZNR02J

D01K

NF01J

FD

JP11

IC04D

C09D

C01E

BZ01E

IC01K

CN

SD01D

ASM : 6871A10111

D02K

R05K

H1

JP45

JP44

C01J

NF02J

JP40

JP39

ZNR01J

JP12

CN_POWER

JP28

_S

JP56

C04J

Q01C
IC03D

BOTTOM VIEW

H)

(B

R21G

R22G

IC04M

H)

FUSE
250V/T2A

C01F

IC02M
D07D
C10D
JP39

JP40

C07D

JP35

C01J

NF02J

SD01D

D02K

JP45

JP44

JP58

JP30

50

ZNR02J
C01D

NTC

R03E
Q02E

55

C08D

JP46

IC04D

R03V

ZNR01J

C01E

40

JP48

C04D

45

JP16

JP29

C06D

MICOM

R02H
R01H
R05H

C03V

C04V

R04V

-V

C06J

C05J

SMPS

L1

H)

JP3

CN

D(W

EARTH

JP43

H1

R02F
R01F

JP4

N-T

CN-POWER

VB

(W

C04J

R01J

JP28

-H

UC

JP57

CN

-S

JP34

IC01M

CN

L)

CN-CC
R23G

JP1

R24G

(W

JP27

/D

JP5

-U

JP33

CN-CH2

CN

C03J

CN-MOTOR

R04H
C03H
R03H

JP20
JP32
CN-L/R(BL)

C09D

D01K
R03J
R04J

IC01K

R04K
R02K
JP22

R03D
R02D

IC02K

IC03D

R06D

IC02D

ZD02D

JP36

D02D

JP37

Q02V

R08D
JP38

Q01C

JP23

JP21

JP51

IC1
JP52

JP53

JP54

R01P
R02A
JP50
R07D

JP19

L02X

L01X

C01X

C01G
R01G
JP55

IC01A
JP14

IC01J

Q01K

R05D

R05K

JP31

R02J

D05D

BC01D

JP17

Q01V

JP18
R05V
R06V
JP15

JP8
R01L
JP41

JP42

IC01D

C05D

JP56

JP12

JP10

20
15

R01A C01A

TR01J

JP24
R04E
JP26

30
25

R01B

JP49

R02G
OR1H
OR3H

10

OR2H

NF01J

C02D

R06H
C01H

R21H
R23H
R22H

CN-CON(BL)

JP25
JP9
R02L
JP2
Q03E
C01L R01E
R02E
Q01E

C02H

R03K

JP47

R04D

JP13

JP7 JP6

C01K

R01K

Service Manual 155

Schematic Diagram
3) Art Cool Deluxe Type
BLDC MOTOR
TOP VIEW

BOTTOM VIEW

156 Multi type Air Conditioner

Schematic Diagram
4) Duct Type
High static (BH/BG chassis)
Built in type (BP chassis)

Service Manual 157

Schematic Diagram
Low static (BT, BT1 chassis)

158 Multi type Air Conditioner

Schematic Diagram
5) Casset Type
1 way(TC Chasis)

Service Manual 159

Schematic Diagram
1 way(TC1 Chasis)
TOP VIEW

BOTTOM VIEW

160 Multi type Air Conditioner

Schematic Diagram
4 way(TE/TF/TD chassis)

58

4 way(TE1/TH chassis)
TOP VIEW

BOTOM VIEW

Service Manual 161

Schematic Diagram
6) Convertible type
VE chassis
AC part

TOP VIEW

BOTTOM VIEW

TOP VIEW

BOTTOM VIEW

DC part

162 Multi type Air Conditioner

Schematic Diagram
VB chassis

Service Manual 163

Schematic Diagram
VB chassis
TOP VIEW

BOTOM VIEW

164 Multi type Air Conditioner

Schematic Diagram
2. Display ASSEMBLY
1) Split Type

2) Convertible Type
VE chassis
TOP VIEW

PWB ASM:6871A20390

PCB:6870A90065K

BOTTOM VIEW

VB chassis

3) Art Cool Type

TOP VIEW

BOTTOM VIEW

Service Manual 165

Schematic Diagram
4) Art Cool Deluxe Type
TOP VIEW
REV1
R8
R7

R17
R5

1
C18

TP2

C19

R10

D1

C13
C8

C9 R13

Q1

C20

TP1

P/N 3210018043

R9

SVM-GP1119AI

Q2

SEJIN ELECTRON INC.

M43

TP3
TP4
C7

R18

R3 R4
C21

TP5
R19

TP6

R6

M42

M45
M44

R2
C14

C15

BOTTOM VIEW

TP1
TP2
TP4
TP3
TP7
TP8

5) Art Cool Mirror


TOP VIEW

BOTTOM VIEW

166 Multi type Air Conditioner

Schematic Diagram

3. Outdoor Unit
1) Component side

Service Manual 167

Schematic Diagram
2) Solder side

168 Multi type Air Conditioner

Schematic Diagram
3) Central control PCB)
1) Top View

2) Bottom View

Service Manual 169

Schematic Diagram

4. SUB P.W.B ASSEMBLY


1) Art Cool Type
TOP VIEW

BOTTOM VIEW

170 Multi type Air Conditioner

Refrigerant Flow
Cooling
Heating

Field Piping
Liquid

Field Piping
Gas

Room A

Room B

Room C

3 rooms model

Room A

Room B

Room C

3 rooms model

Header

LEV-A

LEV-B

LEV-C

Accumulator

Low Pressure
S/W

Th2

Drier

Compressor

Th1

Reversing
Valve

Th3

Exchanger
Heat

OUTDOOR UNIT

Troubleshooting Guide

Troubleshooting Guide

Refrigeration Cycle Diagram

1. A2UW146FA0/1/2, A2UW166FA0/1, A2UW186FA0, A3UW186FA0/1

Th3

Service Manual 171

172 Multi type Air Conditioner

Heating

Cooling

Refrigerant Flow

Field Piping
Liquid

Field Piping
Gas

Room A

Room B

Room C

Room D

4 room model

Room A

Room B

Room C

Room D

Header

LEV-A

LEV-B

LEV-C

LEV-D

Accumulator

Drier

Low Pressure
S/W

Constant
Compressor

Check
Valve(2)

Th3

Inverter
Compressor

Th2

Oil
Seperator
Th1

Valve(1)

Check

Reversing
Valve

Th4

Heat
Exchanger

OUTDOOR UNIT

Valve(2)
Solenoid

Valve(1)
Solenoid

4 room model

Troubleshooting Guide

2. A3UW246FA0, A4UW246FA0

Room A

Room B

Room C

Room D

Room A

Room B

Room C

Heating

Cooling

Refrigerant Flow

Liquid

Field Piping

Field Piping
Gas

Room D

Header

LEV-A

LEV-B

LEV-C

LEV-D

Accumulator

Drier

Low Pressure
S/W

Constant
Compressor

Check
Valve(2)

Th3

Inverter
Compressor

Th2

Oil
Seperator
Th1

Check
Valve(1)

Th4

Heat
Exchanger

Valve(2)
Solenoid

Reversing
Valve

OUTDOOR UNIT

Troubleshooting Guide

3. A4UW306FA0

Service Manual 173

Valve(1)
Solenoid

174 Multi type Air Conditioner


Field Piping
Liquid ( 9.52)

Field Piping
Gas( 19.05)

Cooling
Heating

Drier
Receiver

LowPressure
Pressure
Low
S/W
S/W

Constant
Compressor

Accumulator

Check
Check
Valve(2
Valve(2)
)

Th3

Inverter
Compressor

Th2

Oil
Seperator

L.E.V.

Th1

Check
Check
Valve(1
Valve(1)
)
Oil
Seperator

Reversing
Valve

Solenoid Valve(1)

Refrigerant Flow

Th4

Heat
Exchanger

OUTDOOR UNIT

Troubleshooting Guide

4. A6UW406FA0

Field Piping
Liquid ( 9.52)

Field Piping
Gas( 19.05)

Cooling
Heating

Refrigerant Flow

Th3

Check
Valve(2)

Drier

Low Pressure
S/W

Constant
Compressor 2 Constant
Compressor 1

Accumulator

Check
Valve(3)

Receiver

Th3

Inverter
Compressor

Th2

Check
Valve(1)

Th1

Oil
Seperator

Reversing
Valve

Solenoid Valve(1)
L.E.V.

Th4

Heat
Exchanger

OUTDOOR UNIT

Troubleshooting Guide

5. A7UW486FA0, A8UW566FA0

Service Manual 175

Troubleshooting Guide

C Liquid(9.52 or 12.7)

LEV-D

LEV-C

A Liquid(9.52 or 12.7)

LEV-B

B Liquid(9.52 or 12.7)

D Liquid(6.35)
C Liquid(6.35)
B Liquid(6.35)
A Liquid(6.35)

[Indoor Unit]

176 Multi type Air Conditioner

Outdoor Unit

Main Liquid
Main Gas
Piping ( 9.52) Piping ( 15.88)

LEV-A

D Liquid(9.52)

Cooling
Heating

Refrigerant Flow

6. BD Unit

Troubleshooting Guide

Self-diagnosis Function
Error Indicator
The function is to self-diagnoisis airconditioner and express the troubles identifically if there is any trouble.
Error mark is ON/OFF for the operation LED of evaporator body in the same manner as the following table.
If more than two troubles occur simultaneously, primarily the highest trouble fo error code is expressed.
After error occurrence, if error is released, error LED is also released simultaneously.
To operate again on the occurrence of error code, be sure to turn off the power and then turn on.
Having or not of error code is different from Model.

Indoor Error
Error code

Description

INV TPS

LED 1
(Red)

LED 2
(Green)

Indoor
Status

00

No Error

ON

01

Indoor Room themistor error

1time

OFF

02

Indoor in-piping sensor error

2times

OFF

03

Remote controller error

3times

OFF

04

Drain Pump error

4times

OFF

05

Communcation error between in and out

5times

OFF

06

Indoor Out-Piping sensor error

6times

OFF

07

Differnt mode operation

7times

OFF

Outdoor Error
Error Code

Description

INV TPS

LED 1
(Red)

LED 2
(Green)

Indoor
Status

21

DC Peak (IPM Fault)

2times

1time

OFF

22

CT 2(Max CT)

2times

2times

OFF

23

DC Link Low Volt.

2times

3times

OFF

24

L_P/Heater Sink

2times

4times

OFF

25

Low voltage / Over voltage

2times

5times

OFF

26

DC Comp Position Error

2times

6times

OFF

27

PSC Fault Error

2times

7times

OFF

28

DC Link High Volt

2times

8times

OFF

32

D-Pipe High (INV)

3times

2times

OFF

33

D-Pipe High (Normal)

3times

3times

OFF

40

CT Sensor (Open/Short)

4times

41

INV. D-PipeTh Error(Open/Short)

44

Outdoor air Th Error(Open/Short)

45
46

OFF

4times

1time

OFF

4times

4times

OFF

Cond. Pipe Th Error(Open/Short)

4times

5times

OFF

Suction Pipe Error(Open/Short)

4times

6times

OFF

47

Const D-pipe Th Error(Open/Short)

4times

7times

OFF

51

Capacity over

5times

1time

OFF

53

Signal error (Indoor Outdoor)

5times

3times

OFF

60

EEPROM Check Sum Error

6times

61

Cond. Pipe High

62

Heatsink High

63
65

OFF

6times

1time

OFF

6times

2times

OFF

Cond. Pipe Low

6times

3times

OFF

Heatsoml Th error (Open/Short)

6times

5times

OFF

Service Manual 177

Troubleshooting Guide

Cycle Troubleshooting Guide


Trouble analysis
1. Check temperature difference between intake and discharge air, and operating current.
Temp. difference
Current

: approx. 0C
: less than 80% of
rated current

All amount of refrigerant leaked out.


Check refrigeration cycle.

Temp. difference
Current

: approx. 8C
: less than 80% of
rated current

Refrigerant leakage
Clog of refrigeration cycle
Defective compressor

Temp. difference
Current

: less than 8C
: near the rated
current

Temp. difference

: over 8C

Temp. Difference

Operating Current
Excessive amount of refrigerant

Normal

Notice:
Temperature difference between intake and discharge air depends on room air humidity. When the room air
humidity is relatively higher, temperature difference is smaller. When the room air humidity is relatively lower
temperature difference is larger.
2. Check temperature and pressure of refrigeration cycle.
Suction pressure
(Compared with
the normal value)

Temperature
(Compared with
the normal value)

Cause of Trouble

Description

High

Defective compressor

Current is low.

Normal

Excessive amount of
refrigerant

High pressure does not quickly


rise at the beginning of operation.

Insufficient amount of
refrigerant(Leakage)
Clogging

Current is low.

Higher

Lower

Higher

Notice:
1. The suction pressure is usually 4.5~6.0 kg/cm G at normal condition.
2. The temperature can be measured by attaching the thermometer to the low pressure tubing and wrap it with
putty.
2

178 Multi type Air Conditioner

Troubleshooting Guide

Electronic Parts Troubleshooting Guide


1. A2UW146FA0/1/2, A2UW166FA0/1, A2UW186FA0, A3UW186FA0/1
Refer to electronic contorol device drawing & schematic diagram.

Trouble 1

The Product doesnt operate at all.

Turn off the main power and wait until LED on outdoor PCB is off.

Turn on the main power again.

Does "Beeping" sound is made from the indoor unit?


NO

YES

Check the voltage of power(AC220V/AC240V, 50Hz).


The voltage of main power.
The voltage applied to the unit.
The connecting method of Indoor/Outdoor connecting cable (each color)
The P.W.B. Ass'y
(Fuse, Noise Filter, Power Transformer, IC01D, IC02D, etc.)

Primarily, the operating condition of Micom is O.K.

Check CN-DISP1

The operation check of the P.C.B. Ass'y


Specification

Procedure

Remedy

1) The input voltage of power transformer.

1) AC230V 30V
: Check the rated voltage

1) Replace
power transfomer.

2) The output voltage of power


transformer.

2) 14V 3V

2) Replace
power transfomer.

3) IC01D(7812)

3) DC12V

3) Replace IC01D.

4) IC02D(7805)

4) DC5V

4) Replace IC02D.

5) IC01A(KIA7036)

5) The voltage of micom pin 29


: DC4.5V

5) Replace IC01A.

Service Manual 179

Troubleshooting Guide

Trouble 2

Product doesn't operate with the remote controller.


Turn on main power.

While the compressor has been stopped, the compressor does not operate
owing to the delaying function for 3 minutes after stopped.

When the compressor stopped Indoor Fan is driven by a low speed.


At this point the wind speed is not controlled by the remote controller.
(When operated in the Sleeping Mode, the wind speed is set to the low speed as force.)

Caused by the remote controller.

Caused by other parts except


the remote controller

When the mark (


) is displayed in LCD
screen, replace battery.

Check the contact of CN-DISP 1 connector

When the detect switch (double key) inside the


remote controller door is fault, it is impossible to
operate temperature regulating( / ) and wind
speed selecting.

Check DISP PWB Ass'y


-Voltage between CN1 - : DC +5V

Check the Display PWB Ass'y

180 Multi type Air Conditioner

Check receiver ass'y

Troubleshooting Guide

Trouble 3

The Compressor/Outdoor Fan are don't operate

Turn on the main power.

Operate Cooling Mode by setting the disired temperature of the remote controller is less
than one of the Indoor temperature by 1C at least.

When in air circulation mode, compressor/outdoor fan is stopped.

Check the sensor for Indoor temperature is attatched as close as to be effected by the
themperature of Heat Exchange (EVA.)

When the sensor circuit for Indoor temperature and connector are in bad connection or are
not engaged, Compressor/Outdoor fan is stopped.
Check the related circuit of R02H(12.1K), R01H(1K), R04H(6.2K), R03H(1K), C01H(102),
C02H(102), Micom(pin No. , ).
Check the Indoor temperature sensor is disconnected or not (about 10K at 25C).

Check the Relay(RY-PWR, RY-START) for driving Compressor.


Check the voltage between brown and blue cable of terminal to connect the Outdoor
(About AC220V / 240V).
Check the related circuit of relay in Outdoor PCB Ass'y.
Check Point

Comp. ON

Comp. OFF

Between Micom(No. 19) and


GND

DC 5V

DC 0V

Between IC01M(No. 10) and


GND

DC 1V

DC 12V

Turn off main power.

Check the electrical wiring diagram of Outdoor side.


Check the open or short of connecting wires between Indoor and Outdoor.

Service Manual 181

Troubleshooting Guide

Trouble 4

When indoor Fan does not operate.


Turn off main power.

Check the connection of CN-FAN.

Check the Fan Motor.

Check the Fuse(AC250V, T2A).

Check the related circuit of indoor Fan Motor.


The pin No. 38 of micom and the part for driving SSR.(Q01M)
Check the related pattern.
Check the SSR.
- SSR Open: Indoor Fan Motor never operate.
- SSR short: Indoor Fan Motor always operates in case of ON or OFF.

Turn on the main power

Check the SSR high speed operation by remote control.


(the Indoor Fan Motor is connected)
The voltage of Pin No 1(orange) and 3(black) of CN-FAN.

About AC 160V over

About AC 50V over

SSR is not damaged

Check SSR

182 Multi type Air Conditioner

Troubleshooting Guide

Trouble 5

When the louver does not operate.

Confirm that the vertical louver is normally geared with the shaft of Stepping Motor.
If the regular torque is detected when rotating the vertical louver with hands Normal

Check the connecting condition of CN-U/D or CN0L/R Connector


Check the soldering condition(on PCB) of CN-U/D or CN0L/R Connector

Check the operating circuit of the vertical louver


Confirm that there is DC +12V between pin of CN-U/D, CN0L/R and GND.
Confirm that there is a soldering short at following terminals.
- Between 17 , 18 , 19 and 20 of MICOM
- Between 1 , 2 , 3 and 4 of MICOM
- Between 4 , 5 , 6 and 7 of IC01M
- Between 5 , 6 , 7 and 8 of IC01M

If there are no problems after above checks.


Confirm the assembly condition that are catching and interfering parts in the link of the
vertical louver

Service Manual 183

Troubleshooting Guide

General Information
Error Indicator (Indoor)
The function is to self-diagnosis air conditioner and express the troubles if there is any trouble.
Error mark is displayed on display window of indoor units and wired-remote controller, and LED of outdoor unit
control board.
If more than two troubles occur simultaneously, lower number of error code is first displayed.
After error occurs, if error is released, error LED is also released simultaneously.

1 digit

10 digit

Indoor Error
Error
code
01

Contents

Case of error

Indoor

Air sensor (open/short)

Open / Short

Status
Off

02

Inlet pipe sensor

Open / Short

Off

03

Communication(Indoor Wired R/Control)

Communication Poorly

Off

04

Drain pump/ Float switch

Float switch Open

Off

05

Communication(Indoor Outdoor)

Communication Poorly

Off

06

Outlet pipe sensor

Open / Short

Off

07

Different operation mode

Different operation mode

Off

184 Multi type Air Conditioner

Troubleshooting Guide
Error Indicator (Outdoor)
Outdoor Error
Ex) Error 21 (DC Peack)
2 Times

2 Times

2 Times

LED01G
(RED)
1 Sec.

1 Sec.
1 Time

1 Sec.
1 Time

1 Time

LED02G
(GREEN)
2 Sec.

Error
code

2 Sec.

Contents

LED01G LED02G
(Green)
(Red)

Case of error

Outdoor
Status

21

IPM Fault (Compressor Over current)

2 times

1 time

Compressor malfunction,IPM Fault

Off

22

CT 2(Max. Current)

2 times

2 times

Current is 14A

Off

23

DC Link Low Volt.

2 times

3 times

DC Link volt. Is 140V

Off

24

Low / High press

2 times

4 times

Low / High press switch OPEN

Off

25

AC Low / AC High Volt.

2 times

5 times

Abnormal AC volt. Input.

Off

26

DC Compressor Position

2 times

6 times

Off

27

PSC Fault

2 times

7 times

Off

28

DC Link High Volt

2 times

8 times

Off

Off

32

Discharge Pipe Temp. High (INV)

3 times

2 times

Off

Off

33

Discharge Pipe Temp. High (Cons.)

3 times

3 times

Off

Off

Service Manual 185

Troubleshooting Guide
Error Indicator (Outdoor)
Outdoor Error

Error
code

LED01G LED02G
(Green)
(Red)

Contents

Case of error

Outdoor
Status

CT Circuit malfunction

Off

1 time

Open / Short

Off

4 times

4 times

Open / Short

Off

Cond. Pipe sensor (open/ short)

4 times

5 times

Open / Short

Off

46

Suction pipe sensor (open/ short)

4 times

6 times

Open / Short

Off

47

D-pipe sensor Cons. (open/ short)

4 times

7 times

Open / Short

Off

51

Over capacity

5 times

1 times

Over combination

Off

53

Communication (Indoor

5 times

3 times

Communication Poorly

Off

60

EEPROM check sum

6 times

Check sum mismatching

Off

61

Cond. Pipe sensor temp. high

6 times

1 time

Cond. Temp. high

Off

62

Heat sink sensor temp. high

6 times

2 times

Heat sink temp. high

Off

65

Heat sink sensor (open/ short)

6 times

5 times

Open / Short

Off

40

CT Circuit

4 times

41

D-pipe sensor INV. (open/ short)

4 times

44

Air sensor (open/ short)

45

Outdoor)

186 Multi type Air Conditioner

Troubleshooting Guide
1) Troubleshooting CH01, CH02, CH06
Display
code

Title

01

Indoor air sensor

Open / Short
Soldered poorly
Internal circuit error

Normal resistor : 10K/ at 25C (Unplugged)


Normal voltage : 2.5Vdc / at 25C (plugged)

02

Indoor inlet pipe sensor

Open / Short
Soldered poorly
Internal circuit error

Normal resistor : 5K/ at 25C (Unplugged)


Normal voltage : 2.5Vdc / at 25C (plugged)

Indoor outlet pipe sensor

Open / Short
Soldered poorly
Internal circuit error

Normal resistor : 5K/ at 25C (Unplugged)


Normal voltage : 2.5Vdc / at 25C (plugged)

06

Cause of error

Check point & Normal condition

10k

2.5Vdc

Check the resistance

Check the voltage

Check Point
1. Unplug the sensor on Indoor unit PCB.
2. Estimate the resistance of each sensor.
3. If the resistance of the sensor is 10K/ 5K at 25C, then sensor is normal.
4. If the resistance of the sensor is 0 K or , then sensor is abnormal. Change the sensor.
5. Plug the sensor on Indoor unit PCB and Power ON.
6. Estimate the voltage of each sensor.
7. If the voltage of the sensor is 2.5Vdc at 25C, then sensor is normal.
8. If the resistance of the sensor is 0 or 5Vdc, then sensor is abnormal. Repair or Change the PCB.

Service Manual 187

Troubleshooting Guide
2) Troubleshooting CH03
Display
code

Title

03

Communication
Wired R/C

Cause of error

Wired R/C
12V

Open / Short
Wrong connection

Indoor Unit

GND

12V

Connection of wire
Main PCB Volt. DC12V
Noise interference

CN-REMO

GND

12Vdc

12Vdc

Check the Volt.

Check point & Normal condition

Check the Volt.

Check Point
1. Check the wire connection. (Open / Short) Repair the connection
2. Check the soldering state of connector. (Soldered poorly) Repair or Change the PCB.
3. Check the volt. Of main PCB power source. (DC 12V, DC 5V) Repair or Change the main PCB.
4. Check the installation of wired remote controller. (Noise interference) Adjust the state of installation

188 Multi type Air Conditioner

Troubleshooting Guide
3) Troubleshooting CH04
Display
code

Title

04

Drain pump
/ Float switch

Cause of error

Float switch Open.


(Normal : short)

Check point & Normal condition


The connection of wire(Drain pump/ Float switch)
Drain pump power input. (220V)
Drain tube installation.
Indoor unit installation. (Inclination)

CN Float

CN-D/PUMP
CN-Float

Check the resistance

Check Point
1. Check the wire connection. (Open, Soldered poorly) Repair the connection or change the PCB.
2. Check the resistance of float switch (Abnormal : Open, Normal : short) Check the float switch.
3. Check the level of water
4. Check the volt. Of Drain pump power supply. (AC 230V) Repair or Change the main PCB.

Service Manual 189

Troubleshooting Guide
4) Troubleshooting CH05, CH53
Display
code

04
/
53

Title

Communication
(Indoor Outdoor)

Cause of error

Communication poorly

Check point & Normal condition


Power input AC 220V. (Outdoor, Indoor)
The connector for transmission is disconnected.
The connecting wires are misconnected.
The GND1,2 is not connected at main GND.
The communication line is shorted at GND.
Transmission circuit of outdoor PCB is abnormal.
Transmission circuit of indoor PCB is abnormal.

Check Point
1. Check the input power AC230V. (Outdoor, Indoor unit)
2. Check the communication wires are correctly connected.
Adjust the connection of wire
Confirm the wire of Live, Neutral
3. Check the resistance between communication line and
GND. (Normal : Over 2M)
4. Check the connector for communication is correctly
connected.
5. Check the connection of GND1, GND2, and main GND.
6. If one indoor unit is operated normally, outdoor PCB is no
problem.
Check the another indoor unit.
* CH05 is displayed at indoor unit, CH53 is displayed at outdoor unit.

190 Multi type Air Conditioner

Troubleshooting Guide
5) Troubleshooting CH21
Display
code

Title

21

Cause of error

Instant over current


Over Rated current
Poor insulation of IPM

DC Peak

Comp
U

Terminal
U-V
V-W
W-U

Comp

An instant over current in the U,V,W phase


- Comp lock
- The abnormal connection of U,V,W
Over load condition
- Overcharging of refrigerant
- Pipe length.
Poor insulation of compressor

Resistance() at 20C

Check point & Normal condition

Copper
pipe

Inverter Constant
comp.
comp.
0.64
0.64
0.64

0.8
0.8
0.8

Resistance() at 20C

Terminal
U-GND
V-GND
W-GND

Inverter Constant
comp.
comp.
2M
2M
2M

2M
2M
2M

Check Point
1. Check the wire connection. (U,V,W)
2. Check the load condition. (Refrigerant, Pipe length, ) Adjust the load condition
3. Check the electricity leakage of the compressor. Normal : Over 2M.
4. Check the resistance of compressor. Normal : 0.65(INV), 0.8(Cons.) No difference at each terminal.
5. Check the insulation from water at IPM part. Check the trace of water.
6. Check the IPM circuit.

Service Manual 191

Troubleshooting Guide
6) Troubleshooting CH22
Display
code

Title

Cause of error

21

Max. C/T

22

C/T
Internal circuit

Check point & Normal condition

Over current (14A )

Malfunction of compressor
Blocking of pipe
Low voltage input
Refrigerant, pipe length, blocked,

Initial current error

Malfunction of current detection circuit.


(Open / Short)
The voltage of C01N Is 4.0Vdc(25A) .

Check Point
1. Check the power source.
2. Check the fan operation is right.
3. Check the current.
4. Check the install condition.
5. Check the internal circuit. (C/T, Diode, Resistor)

192 Multi type Air Conditioner

Troubleshooting Guide
7) Troubleshooting CH23, CH28
Display
code

Title

23

DC Link
Low voltage.

DC link volt. is
140Vdc .

Check the power source.


Check the components.

28

DC Link
High voltage

DC link volt. is
420Vdc .

Check the power source.


Check the components.

Cause of error

Check point & Normal condition

Check Point
1. Check the power source.
2. Check the components
(B/Diode, Reactor, PSC Parts )

Service Manual 193

Troubleshooting Guide
8) Troubleshooting CH24, CH25
Display
code

Title

24

Press S/W Open

25

Input voltage

Cause of error

Check point & Normal condition

Low / High press


S/W open.

Check the connection of CN_Press.


Check the components.

Abnormal Input voltage


(140Vac , 300Vac .

Check the power source.


Check the components.

TRANS1
50Hz, DC12V

CN PRESS

CN TRNAS1

Check Point
CH 24

CH 25

1. Check the connection of CN_PRESS

1. Check the power source.

2. Check the install condition for over load.

2. Check the components


(Trans1, B/Diode, Diode, Resistance)

3. Check the SVC V/V open.


4. Check the leakage of refrigerant.

194 Multi type Air Conditioner

Troubleshooting Guide
9) Troubleshooting CH26, CH27
Display
code

Title

26

DC Compressor
Position

27

PSC Fault

Cause of error

Check point & Normal condition

Compressor
position detect error

Check the connection of comp wire U,V,W


Malfunction of compressor
Check the component of IPM, detection parts.

Over current at IGBT

Check the component of IGBT .


Check the components.

E
C
B

B
E

Check Point
CH 26

CH 27

1. Check the connection of U,V,W

1. Check the component of IGBT

2. Check the insulation of IPM part.

2. Check the components


(IGBT, R04S, NF1, BD02S)

3. Check the compressor. (same with CH21)

Service Manual 195

Troubleshooting Guide
10) Troubleshooting CH32, CH33
Display
code

Title

32

D-pipe (Inverter)
temp. high
(105C )

33

D-pipe (Constant)
temp. high
(105C )

Cause of error

Check point & Normal condition

Discharge sensor
(Inverter) temp. high

Check the discharge pipe sensor for INV.


Check the install condition for over load.
Check the leakage of refrigerant.
Check the SVC V/V open.

Discharge sensor
(Cons.) temp. high

Check the discharge pipe sensor for Cons.


Check the install condition for over load.
Check the leakage of refrigerant.
Check the SVC V/V open.

D-Pipe temp.
Toff(105) C
T2(95) C
T1(90) C

COMP Frequency
Normal
(Hz)
LEV Openness
(Pulse)

Normal

Normal

OFF

Normal

OFF Control

Check Point
CH 32

CH 33

1. Check the install condition for over load.

1. Check the install condition for over load.

2. Check the SVC V/V open.

2. Check the SVC V/V open.

3. Check the leakage of refrigerant.

3. Check the leakage of refrigerant.


4. Check the constant compressor. (same with CH21)

196 Multi type Air Conditioner

Troubleshooting Guide
11) Troubleshooting CH41, CH44, CH45, CH46, CH47, CH65
Display
code

Title

41

D-pipe sensor (Inverter)

Open / Short
Soldered poorly
Internal circuit error

Normal resistor : 200K / at 25C (Unplugged)


Normal voltage : 4.5Vdc / at 25C (plugged)

44

Air sensor

Open / Short
Soldered poorly
Internal circuit error

Normal resistor : 10K / at 25C (Unplugged)


Normal voltage : 2.5Vdc / at 25C (plugged)

45

Condenser Pipe sensor

Open / Short
Soldered poorly
Internal circuit error

Normal resistor : 5K / at 25C (Unplugged)


Normal voltage : 2.5Vdc / at 25C (plugged)

46

Suction Pipe sensor

Open / Short
Soldered poorly
Internal circuit error

Normal resistor : 5K / at 25C (Unplugged)


Normal voltage : 2.5Vdc / at 25C (plugged)

D-pipe sensor (Constant)

Open / Short
Soldered poorly
Internal circuit error

Normal resistor : 200K / at 25C (Unplugged)


Normal voltage : 4.5Vdc / at 25C (plugged)

Heat sink sensor

Open / Short
Soldered poorly
Internal circuit error

Normal resistor : 10K / at 25C (Unplugged)


Normal voltage : 2.5Vdc / at 25C (plugged)

47

65

Cause of error

Check point & Normal condition

Check Point
1. Estimate the resistance of each sensor.(Unplugged)
2. Estimate the voltage of each sensor.(Plugged)
3. If the resistance of the sensor is 0 k or , then sensor is abnormal.

If the voltage of the sensor is 0 V or 5Vdc, then sensor is abnormal.

Service Manual 197

Troubleshooting Guide
12) Troubleshooting CH51, CH60
Display
code

Title

51

Over capacity

60

EEPROM
Check sum

Cause of error

Check point & Normal condition

Over capacity
Combination

Check the indoor unit capacity.


Check the combination table.

Check sum error

Check the PCB ASM P/No.


Check the poor soldering.

Model

Gross max. capacity

Max. single indoor unit capacity

A2UW146FA0
A2UW146FA1
A2UW146FA2

21k

12k

A2UW166FA0
A2UW166FA1
A2UW186FA0

24k

12K

A3UW186FA0

30k

12k

A3UW246FA0
A4UW246FA0

33k

18K

A4UW306FA0

39k

18K

A6UW406FA0

52k

24K

Check Point
CH 51

CH 60

1. Check the indoor unit capacity.

1. Check the insertion condition of EEPROM.


2. Check the poor soldering

198 Multi type Air Conditioner

Troubleshooting Guide
13) Troubleshooting CH61, CH62
Display
code

Title

Cause of error

61

Condenser
pipe sensor
temp. high

Condenser pipe sensor


detected high
temp.(65C)

Check the load condition.


Check the sensor of Condenser pipe sensor.

62

Heat sink sensor


temp. high

Heat sink sensor


detected high
temp.(85C)

Check the fan is locked.


Check the sensor of heat sink.

Check point & Normal condition

Heat Sink temp.


Toff C
T2 C
T1 C

COMP Frequency
Normal
(Hz)

Normal

OFF

Normal

Check Point
CH 61

CH 62

1. Check the install condition for over load.


(Refrigerant, Pipe length, Blocked, )

1. Check the fan is locked.


2. Check the Outdoor temp. is very high.

Service Manual 199

(3-way) Valve

(3-way) Valve
3-way Valve (Liguid Side)

3-way Valve (Gas Side)

Valve cap

Valve cap

Open position
Closed position

Open position
Closed position

Pin

Pin
To piping
connection

Service Service
port cap port

To outdoor unit

1.

To piping
connection

Service Service
port cap port

To outdoor unit

Works

Shaft position

Service port

Shaft position

Service port

Shipping

Closed
(with valve cap)

Closed
(with cap)

Closed
(with valve cap)

Closed
(with cap)

Closed
(clockwise)

Open
(push-pin or with
vacuum pump)
Closed
(with cap)

Air purging
(Installation)

Open
Open
(counter-clockwise) (push-pin or with
vacuum pump)

Operation

Open
(with valve cap)

Closed
(with cap)

Open
(with valve cap)

Pumping down
(Transfering)

Closed
(clockwise)

Closed
(with cap)

Open
(counter-clockwise)

Open
(connected
manifold gauge)

Evacuation
(Servicing)

Open

Open
(connected
manifold gauge)

Open

3.

Open
(connected
manifold gauge)

Gas charging
(Servicing)

Open

Closed
(with cap)

Open

4.

Pressure check
(Servicing)

Open

Open
(connected
manifold gauge)

Open

5.

Open
(connected
manifold gauge)

Gas releasing
(Servicing)

Open

Open
(connected
manifold gauge)

Open

6.

Open
(connected
manifold gauge)

2.

200 Multi type Air Conditioner

Open
(with charging
cylinder)

(3-way) Valve

(1) Pumping down

Indoor unit

Liquid side
2-Way
valve

Close

Outdoor unit

Gas side
3-Way
valve

Indoor unit

Open

Liquid side
2-Way
valve

Close

Gas side
3-Way
valve

Open

manifold gauge

Lowhandle
(CLOSE)

Hi- handle
(CLOSE)

Procedure
1. Confirm that both the gas side and liquid side
valves are set to the open position.
- Remove the valve stem caps and confirm that the
valve stems are in the raised position.
- Be sure to use a hexagonal wrench to operate
the valve stems.
2. Operate the unit for 10 to 15 minutes.
3. Stop operation and wait for 3 minutes, then connect the manifold gauge to the service port of the
gas side valve.
- Connect the hose of the gauge with the push pin
to the service port.

6. Operate the air conditioner at the cooling cycle


and stop it when the gauge indicates 1kg/cm g.
2

7. Immediately set the gas side valve to the closed


position.
- Do this quickly so that the gauge ends up indicating 1kg/
g.
8. Disconnect the charge set, and mount the liquid
side and gas side valve caps and the service port
nut.
- Use torque wrench to tighten the service port nut
to a torque of 1.8kg.m.(4.2kg.m/5.5kg.m)
- Be sure to check for gas leakage.

4. Air purging of the charge hose.


- Open the Low-handle valve on the gauge
slightly to air purge from the hose.
5. Set the liquid side valve to the closed position.
Be sure to short pressure S/W. otherwise Low pressure S/W detect low pressure skete and stops the compressor.

Service Manual 201

(3-way) Valve

(2) Evacuation
(All amount of refrigerant leaked)

Indoor unit

Liquid side
2-Way
valve

Open

Outdoor unit

Gas side
3-Way
valve

Indoor unit

Open

Liquid side
2-Way
valve

Open

Gas side
3-Way
valve

Open

manifold gauge
Vacuum pump
Lowhandle
(OPEN)

Hi- handle
(OPEN)

Procedure
1. Confirm that both the liguid side valve and gas
side valve are set to the opened position.
2. Connect the vaccum pump to the center hose of
the manifold gauge.
3. Connect the service port of the gas side valve to
the low side of the gauge.
4. Evacuation for approximately one hour.
- Confirm that the gauge needle has moved
toward-76 cmHg (vacuum of 4 mmHg or less).
5. Close the Low handle of the gauge turn off the
vacuum pump, and confirm that the gauge needle
does not move(approximately 5 minutes after
turning off the vacuum pump).

202 Multi type Air Conditioner

6. Disconnect the charge hose from the vacuum


pump.
- Vacuum pump oil.
If the vacuum pump oil becomes dirty or depleted,replenish as needed.
7. Mount the valve caps and the service port caps.

(3-way) Valve

(3) Gas Charging


(After Evacuation)

Indoor unit

Liquid side
2-Way
valve

Open

Outdoor unit

Gas side
3-Way
valve

Indoor unit

Open

Liquid side
2-Way
valve

Open

Gas side
3-Way
valve
Charging
cylinder

Open

manifold gauge

Low-handle
Check valve (OPEN)

Hi- handle
(OPEN)

Procedure
1. Connect the gauge to the charging cylinder.
- Connect the charge hose which you disconnected from the vacuum pump to the valve at the
bottom of the cylinder.
- If you are using a gas cylinder, also use a scale
and reverse the cylinder so that the system can
be charged with liquid.
2. Purge the air from the charge hose.
- Open the valve at the bottom of the cylinder and
press the check valve on the charge set to purge
the air. (Be careful of the liquid refrigerant). The
procedure is the same if using a gas cylinder.
3. Open the low handle on the gauge and charge
the system with liquid refrigerant.
- If the system can not be charged with the specified amount of refrigerant, it can be charged
with a little at a time (approximately 150g each
time) while operating the air conditioner in the
cooling cycle; however, one time is not sufficient, wait approximately 1 minute and then
repeat the procedure(pumping down-pin).

4. Immediately disconnect the charge hose from


the gas side valve's service port.
This is different from previous procedures.
Because you are charging with liquid refrigerant
from the gas side, absolutely do not attempt to
charge with larger amounts of liquid refrigerant
while operating the air conditioner.
- Stopping partway will allow the gas to be discharged.
- If the system has been charged with liquid
refrigerant while operating the air conditioner
turn off the air conditioner before disconnecting
the hose.
5. Mount the valve stem nuts and the service port
nut.
- Use torque wrench to tighten the service port
nut to a torque of 1.8 kg.m.(4.2kg.m/5.5kg.m.)
- Be sure to check for gas leakage.

Service Manual 203

Exploded View & Replacement Parts List

Exploded View & Replacement Parts List


Indoor Unit
SQ/SR chassis
135316

152313

135314

152302
733010

131410
359011

342800
159830

354210

135316
352115
352116

159901
268712

346810

35211B
263230-2

135516
263230-1

352150

135311
146811

266090
267110

268715
249951

204 Multi type Air Conditioner

268716

W0CZZ

Exploded View & Replacement Parts List


Parts List (SQ, SR chassis)
LOCATION
No.

PART No.
AMNH076LQL0

AMNH096LQL0

AMNH096LRL0

AMNH126LRL0

SVC
CODE

131410 CHASSIS ASSEMBLY

3141A20006A

3141A20006A

3141A20005A

3141A20005A

135311 GRILLE ASSEMBLY,DISCHARGE(INDOOR)

3531A10127A

3531A10127A

3531A10230A

3531A10230A

135314 GRILLE ASSEMBLY,INLET SUB

3531A20100B

3531A20100B

3531A10117B

3531A10117B

135316 GRILLE ASSEMBLY,FRONT(INDOOR)

3531A20187M

3531A20187M

3531A10208N

3531A10208N

135516 COVER ASSEMBLY,MOTOR

3551A20050P

3551A20050P

3551A20099A

3551A20099A

146811 MOTOR ASSEMBLY,STEP

4681A20055A

4681A20055A

4681A20055A

4681A20055A

152302 FILTER(MECH),A/C

5230A10005A

5230A10005A

5230A20014C

5230A20014C

152313 FILTER ASSEMBLY,DEODORIZER

5231A20032C

5231A20032C

5231A20032C

5231A20032C

159830 AIR CLEANER ASSEMBLY

5983A10009V

5983A10009V

5983A10006V

5983A10006T

159901 VANE,HORIZONTAL

5990A10005A

5990A10005A

5990A20007A

5990A20007A

249951 CONTROL BOX ASSEMBLY,INDOOR 4995A20361A

4995A20361B

4995A20361C

4995A20361D

DESCRIPTION

263230-1 THERMISTOR ASSEMBLY

6323AQ3226T

6323AQ3226T

3623AQ3226T

3623AQ3226T

263230-2 THERMISTOR ASSEMBLY

6323A20004A

6323A20004A

6323A20004A

6323A20004A

266090 H.V ASSEMBLY

6609A10003J

6609A10003J

6609A10003H

6609A10003H

267110 REMOTE CONTROLLER ASSEMBLY

6711A20067J

6711A20067J

6711A20067J

6711A20067J

268712 PWB(PCB) ASSEMBLY,DISPLAY

6871A20194A

6871A20194A

6871A20390A

6871A20390A

268715 PWB(PCB) ASSEMBLY,MAIN(AC)

6871A20267B

6871A20267B

6871A20267B

6871A20267B

268716 PWB(PCB) ASSEMBLY,MAIN(DC)

6871A20440A

6871A20440B

6871A20440C

6871A20440D

342800 BEARING

4280A20004A

4280A20004A

4280A20004A

4280A20004A

346810 MOTOR ASSEMBLY,INDOOR

4681A20062A

4681A20062A

4681A20048A

4681A20048A

35211B TUBE ASSEMBLY,TUBING

5211A21399B

5211A21399B

5211A21400F

5211A21400F

352115 TUBE ASSEMBLY,EVAPORATOR IN

5211A20470J

5211A20470J

5211A20388H

5211A20388H

352116 TUBE ASSEMBLY,EVAPORATOR OUT

5211A20471D

5211A20471D

5211A20389F

5211A20389F

352150 HOSE ASSEMBLY,DRAIN

5251AR2575F

5251AR2575F

5251AR2575F

5251AR2575F

354210 EVAPORATOR ASSEMBLY, FIRST

5421A10024A

5421A10024A

5421A20086A

5421A20086A

359011 FAN ASSEMBLY,CROSS FLOW

5901A20007B

5901A20007B

5901A20007A

5901A20007A

733010 PLATE ASSEMBLY,INSTALL

3301A10003A

3301A10003A

1H00843A

1H00843A

3H01487A

3H01487A

3H1487A

3H1487A

W0CZZ CAPACITOR,DRAWING

Service Manual 205

Exploded View & Replacement Parts List


ST chassis

135316

267110

152313

135314

152302
733010

131410
359011

342800

159830
352111

135311

135316
159901-1

352115

159901-2

352116

268712
346810

35211B
263230-2

135516
263230-1

352150

268715
146811

249951
266090

268716

W0CZZ

206 Multi type Air Conditioner

Exploded View & Replacement Parts List


Parts List (ST chassis)
LOCATION
No.

PART No.
AMNH186LTL0

AMNH246LTL0

SVC
CODE

131410 CHASSIS ASSEMBLY

3141A10002A

3141A10002A

135311 GRILLE ASSEMBLY,DISCHARGE(INDOOR)

3531A10116A

3531A10116A

135314 GRILLE ASSEMBLY,INLET SUB

3531A20107W

3531A20107W

135316 GRILLE ASSEMBLY,FRONT(INDOOR)

3531A20207E

3531A20207E

135516 COVER ASSEMBLY,MOTOR

3551A20099C

3551A20099C

146811 MOTOR ASSEMBLY,STEP

4681A20055A

4681A20055A

152302 FILTER(MECH),A/C

5230A20001A

5230A20001A

159830 AIR CLEANER ASSEMBLY

5983A10006T

5983A10006T

159901-1 VANE,HORIZONTAL

5990A20008A

5990A20008A

159901-2 VANE,HORIZONTAL

5990A20009A

5990A20009A

4995A20361E

4995A20361F

263230-1 THERMISTOR ASSEMBLY

6323AQ3226T

6323AQ3226T

263230-2 THERMISTOR ASSEMBLY

6323A20004A

6323A20004A

266090 H.V ASSEMBLY

6609A10003L

6609A10003L

267110 REMOTE CONTROLLER ASSEMBLY

6711A20067J

6711A20067J

268712 PWB(PCB) ASSEMBLY,DISPLAY

6871A20194B

6871A20194B

268715 PWB(PCB) ASSEMBLY,MAIN(AC)

6871A20267B

6871A20267B

268716 PWB(PCB) ASSEMBLY,MAIN(DC)

6871A20440E

6871A20440F

342800 BEARING

4280A20004A

4280A20004A

346810 MOTOR ASSEMBLY,INDOOR

4681A20003D

4681A20067A

352111* TUBE ASSEMBLY,CONNECTOR

5211A20514G

5211A20514G

352115 TUBE ASSEMBLY,EVAPORATOR IN

5211A30058H

5211A30097J

352116 TUBE ASSEMBLY,EVAPORATOR OUT

5211A30057D

5211A30098G

352150 HOSE ASSEMBLY,DRAIN

5251AR2575F

5251AR2575F

359011 FAN ASSEMBLY,CROSS FLOW

5901A20008A

5901A20008A

733010 PLATE ASSEMBLY,INSTALL

3301A10002A

3301A10002A

35211B TUBE ASSEMBLY,TUBING

5211A30439E

5211A30439J

3H01487G

3H01487G

DESCRIPTION

249951 CONTROL BOX ASSEMBLY,INDOOR

W0CZZ CAPACITOR,DRAWING
NOTE) 35211* is for pipe fitting to SVC valve.

Service Manual 207

Exploded View & Replacement Parts List


S4, S5 chassis
135312

152302
135301

131410

733010

342800

359011
135311
354210

159901
346810
135500

35211B
268712

135516

266090

668713

146811
263230
267110

208 Multi type Air Conditioner

249951

268714

Exploded View & Replacement Parts List


Parts List (S4, S5 chassis)
LOCATION
No.

DESCRIPTION

PART No.
AMNH07GD4L0 AMNH09GD4L0 AMNH12GD4L0 AMNH18GD5L0 AMNH24GD5L0

SVC
CODE

131410

CHASSIS ASSEMBLY

3141A20019C 3141A20019C 3141A20019C 3141A20020B 3141A20020B

135311

GRILLE ASSEMBLY,DISCHARGE(INDOOR) 3531A10307A 3531A10307A 3531A10307A 3531A20252T 3531A20252T

135314

GRILLE ASSEMBLY,INLET SUB

3531A10312A 3531A10312A 3531A10312A 3531A20254A 3531A20254A

135316

GRILLE ASSEMBLY,FRONT(INDOOR)

3531A14002Z 3531A14002Z 3531A14002Z 3531A20299D 3531A20299D

135516

COVER ASSEMBLY,MOTOR

3551A20156B 3551A20156B 3551A20156B 3551A20154B 3551A20154B

146811

MOTOR ASSEMBLY,STEP

4681A20055A 4681A20055A 4681A20055A 4681A20055A 4681A20055A

152302

FILTER(MECH),A/C

5230A20051B 5230A20051D 5230A20051B 5230A20052B 5230A20052B

152313

FILTER ASSEMBLY,DEODORIZER

5231A20040A 5231A20040A 5231A20040A 5231A20040B 5231A20040B

159830

AIR CLEANER ASSEMBLY

5983A20017A 5983A20017A 5983A20017A 5983A20018A 5983A20018A

159901

VANE,HORIZONTAL

5990A20069A 5990A20069A 5990A20069A 5990A20071A 5990A20071A

249951

CONTROL BOX ASSEMBLY,INDOOR

4995A20632A 4995A20632B 4995A20632C 4995A20632D 4995A20632E

263230-1 THERMISTOR ASSEMBLY

6323AQ3226T 6323AQ3226T 6323AQ3226T 6323AQ3226T 6323AQ3226T

263230-2 THERMISTOR ASSEMBLY

6323A20004A 6323A20004A 6323A20004A 6323A20004A 6323A20004A

266090

H.V ASSEMBLY

6609A10003Z 6609A10003Z 6609A10003Z 6609A10008A 6609A10008A

267110

REMOTE CONTROLLER ASSEMBLY

6711A20107C 6711A20107C 6711A20107C 6711A20107C 6711A20107C

268712

PWB(PCB) ASSEMBLY,DISPLAY

6871A20574A 6871A20574A 6871A20574A 6871A20624A 6871A20624A

268714

PWB(PCB) ASSEMBLY,MAIN

6871A20156J 6871A20156K 6871A20156L 6871A20156M 6871A20156N

342800

BEARING

4280A20004B 4280A20004B 4280A20004B 4280A20004A 4280A20004A

346810

MOTOR ASSEMBLY,INDOOR

4681A20091J 4681A20091J 4681A20091J 4681A20091J 4681A20091J

35211B

TUBE ASSEMBLY,TUBING

5211A21363E 5211A21363E 5211A21363E 5211A21378G 5211A21378G

352115

TUBE ASSEMBLY,EVAPORATOR IN

5211A29010A 5211A29010A 5211A29010A 5211A30756B 5211A30756B

352116

TUBE ASSEMBLY,EVAPORATOR OUT

5211A22110A 5211A22110A 5211A22110A 5211A39010A 5211A39010A

352150

HOSE ASSEMBLY,DRAIN

5251A20011B 5251A20011D 5251A20011D 5251A20011D 5251A20011D

354210

EVAPORATOR ASSEMBLY,FIRST

5421A20218A 5421A20218A 5421A20218A 5421A20220A 5421A20220A

359011

FAN ASSEMBLY,CROSS FLOW

5901A20071F 5901A20071F 5901A20017F 5901A92441E 5901A92441E

733010

PLATE ASSEMBLY,INSTALL

3301A20020C 3301A20020C 3301A20020C 3301A20020B 3301A20020B

135500

COVER

3550A21008A 3550A21008A 3550A21008A 3550A21008A 3550A21008A

Service Manual 209

210 Multi type Air Conditioner

135314

135316

268717

159830

152302

268712

267110

266090

249951

146811

359012

144710-1

268714-1

268714-2

146811

144710-2
146811-2

135500-3

349600

346810

135311-1

147581

330870

354210

135311-3

146811-3

135500-2

352380

263230-1

135500-1

147581

263230-2

35211B

131410

352150

352116

352115

135515

146811-2

147581

135311-2

Exploded View & Replacement Parts List


SP1 chassis(Art cool type)

Exploded View & Replacement Parts List


Parts List (SP1 chassis)
LOCATION
No.

PART No.

DESCRIPTION

AMNH096AP*1 AMNC096AP*1 AMNH126AP*1 AMNC126AP*1

131410 CHASSIS ASSEMBLY

SVC
CODE

3141A20004N

3141A20004N

3141A20004N

3141A20004N

135500-1 COVER

3550A20123A

3550A20123A

3550A20123A

3550A20123A

135500-2 COVER

3550A20124A

3550A20124A

3550A20124A

3550A20124A

135500-3 COVER

3550A20060A

3550A20060A

3550A20060A

3550A20060A

135311-1 GRILLE ASSEMBLY,DISCHARGE(INDOOR)

3531A20069G

3531A20069G

3531A20069G

3531A20069G

135311-2 GRILLE ASSEMBLY,DISCHARGE(INDOOR)

3531A20069H

3531A20069H

3531A20069H

3531A20069H

135311-3 GRILLE ASSEMBLY,DISCHARGE(INDOOR)

3531A20069J

3531A20069J

3531A20069J

3531A20069J

M: Matal

3531A20212K

3531A20212K

3531A20212K

3531A20212K

B: Blue

3531A20212L

3531A20212L

3531A20212L

3531A20212L

D: Wood

3531A20212M

3531A20212M

3531A20212M

3531A20212M

135515 COVER ASSEMBLY,TOP(INDOOR)

3551A20031B

3551A20031B

3551A20031B

3551A20031B

135316 GRILLE ASSEMBLY,

M: Matal

3531A20213N

3531A20213R

3531A20213N

3531A20213R

B: Blue

3531A20213P

3531A20213S

3531A20213P

3531A20213S

D: Wood

3531A20213Q

3531A20213T

3531A20213Q

3531A20213T

4758A20014B

4758A20014B

4758A20014B

4758A20014B

146811-1 MOTOR ASSEMBLY,STEP

4681A20055C

4681A20055C

4681A20055C

4681A20055C

146811-2 MOTOR ASSEMBLY,STEP

4681A20055A

4681A20055A

4681A20055A

4681A20055A

152302 FILTER(MECH),A/C

5230A20032A

5230A20032A

5230A20032A

5230A20032A

159830 AIR CLEANER ASSEMBLY

5983A20007F

5983A20007F

5983A20007F

5983A20007F

249951 CONTROL BOX ASSEMBLY,INDOOR 4995A20372H

4995A20372N

4995A20372J

4995A20372P

249941 CONTROL BOX,INDOOR

4994A10046A

4994A10046A

4994A10046A

4994A10046A

268715 PWB(PCB) ASSEMBLY,MAIN(AC)

6871A20380D

6871A20380D

6871A20380D

6871A20380D

268716 PWB(PCB) ASSEMBLY,MAIN(DC)

6871A20381D

6871A20381G

6871A20381F

6871A20381G

266090 H.V ASSEMBLY

6609A10003S

6609A10003S

6609A10003S

6609A10003S

263230-1 THERMISTOR ASSEMBLY

6323AQ3226T

6323AQ3226T

6323AQ3226T

6323AQ3226T

263230-2 THERMISTOR ASSEMBLY

6323A20004N

6323A20004N

6323A20004N

6323A20004N

268712 PWB(PCB) ASSEMBLY,DISPLAY

6871A20388A

6871A20363D

6871A20388A

6871A20363D

267110 REMOTE CONTROLLER ASSEMBLY

6711A20073D

6711A20073E

6711A90031D

6711A20073E

330870 DRAIN PAN ASSEMBLY

3087A30004A

3087A30004A

3087A30004A

3087A30004A

346810 MOTOR ASSEMBLY,INDOOR

4681A20091A

4681A20091A

4681A20091A

4681A20091A

349600 MOUNT,MOTOR

4960A20016A

4960A20016A

4960A20016A

4960A20016A

352116 TUBE ASSEMBLY,EVAPORATOR OUT

5211A20301J

5211A20301J

5211A20301J

5211A20301J

352115 TUBE ASSEMBLY,EVAPORATOR IN

5211A20302J

5211A20302J

5211A20302J

5211A20302J

35211B TUBE ASSY,TUBING

5211AR7066F

5211AR7066F

5211AR7066F

5211AR7066F

352150 HOSE ASSEMBLY,DRAIN

5251AR1222R

5251AR1222R

5251AR1222R

5251AR1222R

352380 AIR GUIDE

5238A20020A

5238A20020A

5238A20020A

5238A20020A

354210 EVAPORATOR ASSEMBLY,FIRST

5421A20072A

5421A20072A

5421A20072A

5421A20072A

359012 FAN,TURBO

5900A00003A

5900A00003A

5900A00003A

5900A00003A

135314 GRILLE ASSEMBLY,


INLET

FRONT(INDOOR)
147581 LOUVER,HORIZONTAL

Service Manual 211

Exploded View & Replacement Parts List


Art Cool Deluxe Type(SU,SZ, S3 chassis - A/C Motor)
135316

146811

152302

668713-1
146811-1

145200

668713-2

135080-1

135313

135511

263020
135080-2

263230-2

263230-1

733010

267110

359011
159830
342800

266090
352111

131410
346810
352150

249951

352114
352118
W0CZZ
35211B

266090

146811
159901
135311
268714

212 Multi type Air Conditioner

249941

Exploded View & Replacement Parts List


Parts List(Art cool Deluxe Type A/C Motor)
PART No.

LOCATION
No.
131410
135080-1
135080-2
135311

DESCRIPTION

AMNH076DZ*0 AMNH096DU*0 AMNH126DU*0 AMNH186D3*0 AMNH246D3*0

CHASSIS ASSEMBLY
DECORATION (TOP)
DECORATION (BOTTOM)
GRILLE ASSEMBLY, DISCHARGE

135313

GRILLE ASSEMBLY, INLET

135316

GRILLE ASSEMBLY, FRONT

146811
146811-1
159830
152302
159901
249951
249941

MOTOR ASSEMBLY, STEP (Vane)


MOTOR ASSEMBLY, STEP (Door)
AIR CLEANER ASSEMBLY
FILTER (MECH), A/C
VANE, HORIZONTAL
CONTROL BOX ASSEMBLY
CONTROL BOX, INDOOR

263020

DIGITRON

263230-1
263230-2
266090
267110
268714
342800
346810
352114
352118
35211B
352150
354212
359011
668713
668713
733010
W0CZZ

THERMISTOR ASSEMBLY (Out)


THERMISTOR ASSEMBLY (Room, in)
HUB ASSEMBLY
REMOE CONTROLLER ASSEMBLY
PWB(PCB) ASSEMBLY, MAIN
BEARING
MOTOR ASSEMBLY, INDOOR
TUBE ASSEMBLY, DISTRIBUTOR
TUBE ASSEMBLY MANIFOLD
TUBE ASSEMBLY, TUBING
HOSE ASEMBLY, DRAIN
EVAPORATOR ASSEBLY, FINAL
FAN ASSEMBLY, CROSS FLOW
PWB ASSEMBLY, SUB
PWB ASSEMBLY, SUB
PLATE
CAPACITOR, DRAWING

W: White
M: Metal
R: Mirror
B: Blue
D: Wood
C: Cherry
W: White
M: Metal
R: Mirror
B: Blue
D: Wood
C: Cherry

W: White
M: Metal
R: Mirror
B: Blue
D: Wood
C: Cherry

3141A20009B
3508A20055B
3508A20056B
3531A20184C
3531A20196J
3531A20196E
3531A20195B
3531A20196F
3531A20244C
3531A20244D
3531A10214K
3531A10214H
3531A10214J
3531A10214Q
3531A20263W
3531A20263V
4681A20055A
4681A20055B
5983A10009V
5230A20033A
5990A20022B
4995A20323K
4994A20067A
6302A90003A
6302A90003A
6302A90003A
6302A90003A
6302A90003A
6302A90003A
6323Q3226T
6323A20004A
6609A10005B
6711A20073P
6871A10111E
4280A20004A
4681A20103C
5211A20569D
5211A20605B
5211A30596A
5251AR1222R
5421A20149E
5901A20016E
6871A20258B
6871A20259A
3301A10005A
3H01487A

3141A20007B
3508A20034E
3508A20034F
3531A20137B
3531A20118Z
3531A20118Y
3531A20118X
3531A20118W
3531A20244C
3531A20244D
3531A21026C
3531A21026B
3531A21026A
3531A21026D
3531A20263W
3531A20263V
4681A20055A
4681A20055B
5981A25003H
5230A20022A
5990A20015B
4995A20323L
4994A20067A
6302A90003A
6302A90003A
6302A90003A
6302A90003A
6302A90003A
6302A90003A
6323Q3226T
6323A20004A
6609A10005D
6711A20073C
6871A10111F
4280A20004A
4681A20048A
5211A20569D
5211A20605B
5211AR7066L
5251AR1222R
5421A20105H
5910A20016J
6871A20258B
6871A20259A
1H00843A
3H01487A

3141A20007B
3508A20034E
3508A20034F
3531A20137B
3531A20118Z
3531A20118Y
3531A20118X
3531A20118W
3531A20244C
3531A20244D
3531A21026C
3531A21026B
3531A21026A
3531A21026D
3531A20263W
3531A20263V
4681A20055A
4681A20055B
5983A25003H
5230A20022A
5990A20015B
4995A20232M
4994A20067A
6302A90003A
6302A90003A
6302A90003A
6302A90003A
6302A90003A
6302A90003A
6323Q3226T
6323A20004A
6609A10005D
6711A20073C
6871A10111G
4280A20004A
4681A20048A
5211A20569D
5211A20605B
5211AR7066L
5251AR1222R
5421A20105H
5901A20016J
6871A20258B
6871A20259A
1H00843A
3H01487A

3141A20012A
3531A20231C
3531A20244E
3531A20244A
3531A20232B
3531A20244B
3531A20244C
3531A20244D
3531A20263U
3531A20263S
3531A20263R
3531A20263T
3531A20263W
3531A20263V
4681A20055A
4681A20055D
5983A10006T
5230A20047A
5990A20042B
4995A20323X
4994A20067A
6871A20656C
6871A20656A
6871A20656A
6871A20656C
6871A20656C
6871A20656C
6323AQ3226T
6323A20004A
6609A10005D
6711A20107C
6871A20684A
4280A20004A
4681A20067C
5211A14007A
5211A10474D
5211A30038Z
5251AR1222R
5421A21004T
5901A20017C
6871A20258B
6871A20259A
3301A10002A
3H01487G

3141A20012A
3531A20231C
3531A20244E
3531A20244A
3531A20232B
3531A20244B
3531A20244C
3531A20244D
3531A20263U
3531A20263S
3531A20263R
3531A20263T
3531A20263W
3531A20263V
4681A20055A
4681A20055D
5983A10006T
5230A20047A
5990A20042B
4995A20323Y
4994A20067A
6871A20656C
6871A20656A
6871A20656A
6871A20656C
6871A20656C
6871A20656C
6323AQ3226T
6323A20004A
6609A10005D
6711A20107C
6871A20684B
4280A20004A
4681A20067C
5211A14007A
5211A10474D
5211A30038Z
5251AR1222R
5421A21004T
5901A20017C
6871A20258B
6871A20259A
3301A10002A
3H01487G

SVC
CODE
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R

Service Manual 213

Exploded View & Replacement Parts List


Art Cool Deluxe Type(SU,SZ, S3 chassis - BLDC)
135316

146811

152302

668713-1
146811-1

145200

668713-2

135080-1

135313

135511

263020
135080-2

263230-2

263230-1

733010

267110

359011
159830
342800

266090
352111

131410
346810
135500
352150

249951

352114
352118
266090

35211B

146811
159901
135311

214 Multi type Air Conditioner

268714

249941

Exploded View & Replacement Parts List


Parts List(Art cool Deluxe Type BLDC)
PART No.

LOCATION
No.

DESCRIPTION

131410
135080-1
135080-2
135311

CHASSIS ASSEMBLY
DECORATION (TOP)
DECORATION (BOTTOM)
GRILLE ASSEMBLY, DISCHARGE

135313

GRILLE ASSEMBLY, INLET

135316

GRILLE ASSEMBLY, FRONT

146811
146811-1
159830
152302
159901
249951
249941

MOTOR ASSEMBLY, STEP (Vane)


MOTOR ASSEMBLY, STEP (Door)
AIR CLEANER ASSEMBLY
FILTER (MECH), A/C
VANE, HORIZONTAL
CONTROL BOX ASSEMBLY
CONTROL BOX, INDOOR

263020

LCD

263230-1
263230-2
266090
267110
268714
342800
346810
352114
352118
35211B
352150
354212
359011
668713
668713
733010
135500

THERMISTOR ASSEMBLY (Out)


THERMISTOR ASSEMBLY (Room, in)
HUB ASSEMBLY
REMOE CONTROLLER ASSEMBLY
PWB(PCB) ASSEMBLY, MAIN
BEARING
MOTOR ASSEMBLY, INDOOR
TUBE ASSEMBLY, DISTRIBUTOR
TUBE ASSEMBLY MANIFOLD
TUBE ASSEMBLY, TUBING
HOSE ASEMBLY, DRAIN
EVAPORATOR ASSEBLY, FINAL
FAN ASSEMBLY, CROSS FLOW
PWB ASSEMBLY, SUB
PWB ASSEMBLY, SUB
PLATE
COVER

AMNH07GDZ*0 AMNH09GDU*0 AMNH12GDU*0 AMNH18GD3*0 AMNH24GD3*0

W: White
M: Metal
R: Mirror
B: Blue
W: White
M: Metal
R: Mirror
B: Blue

W: White
M: Metal
R: Mirror
B: Blue

3141A20009B
3508A20055B
3508A20056B
3531A20184C
3531A20196J
3531A20196E
3531A20195B
3531A20196F
3531A10214W
3531A10214U
3531A10214T
3531A10214V
4681A20055A
4681A20055B
5983A10009V
5230A20033A
5990A20022B
4995A20637A
4994A20067A
6306A90005A
6306A90005A
6306A90005A
6306A90005A
6323A3226T
6323A20004A
6609A10005B
6711A20107D
6871A20799A
4280A20004A
4681A20091J
5211A20569D
5211A20605B
5211A30596A
5251AR1222R
5421A20149E
5901A20016E
6871A20258B
6871A20259A
3301A10005A
3550A21008C

3141A20007B
3508A20034E
3508A20034F
3531A20137B
3531A10331B
3531A10331C
3531A10331A
3531A10331D
3531A21026V
3531A21026U
3531A21026T
3531A21026W
4681A20055A
4681A20055B
5983A25003H
5230A20022A
5990A20015B
4995A20637B
4994A20067A
6306A90005A
6306A90005A
6306A90005A
6306A90005A
6323A3226T
6323A20004A
6609A10005D
6711A20107C
6871A20799B
4280A20004A
4681A20091J
5211A20569D
5211A20605B
5211AR7066L
5251AR1222R
5421A20105H
5901A20016J
6871A20258B
6871A20259A
1H00843A
3550A21008D

3141A20007B
3508A20034E
3508A20034F
3531A20137B
3531A10331B
3531A10331C
3531A10331A
3531A10331D
3531A21026V
3531A21026U
3531A21026T
3531A21026W
4681A20055A
4681A20055B
5983A25003H
5230A20022A
5990A20015B
4995A20637C
4994A20067A
6306A90005A
6306A90005A
6306A90005A
6306A90005A
6323A3226T
6323A20004A
6609A10005D
6711A20107C
6871A20799C
4280A20004A
4681A20091J
5211A20569D
5211A20605B
5211AR7066L
5251AR1222R
5421A20105H
5901A20016J
6871A20258B
6871A20259A
1H00843A
3550A21008D

3141A20012A 3141A20012A
3531A20231C 3531A20231C
3531A20244A 3531A20244A
3531A20232B 3531A20232B
3531A30032B 3531A30032B
3531A30032A 3531A30032A
4681A20055A 4681A20055A
4681A20055D 4681A20055D
5983A10006T 5983A10006T
5230A20047A 5230A20047A
5990A20042B 5990A20042B
4995A20637D 4995A20637E
4994A20067A 4994A20067A
6306A90005A 6306A90005A
6306A90005A 6306A90005A
6306A90005A 6306A90005A
6306A90005A 6306A90005A
6323AQ3226T 6323AQ3226T
6323A20004A 6323A20004A
6609A10005D 6609A10005D
6711A20107C 6711A20107C
6871A20799D 6871A20799E
4280A20004A 4280A20004A
4681A20091J 4681A20091J
5211A14007A 5211A14007A
5211A10474D 5211A10474D
5211A30038Z 5211A30038Z
5251AR1222R 5251AR1222R
5421A21004T 5421A21004T
5901A20017C 5901A20017C
6871A20258B 6871A20258B
6871A20259A 6871A20259A
3301A10002A 3301A10002A
3550A21008A 3550A21008A

SVC
CODE
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R

Service Manual 215

Exploded View & Replacement Parts List


Art Cool Mirror Type(SE chassis - BLDC)

152302

263230-3

135312

159830

733010

354011

342800

267110

354210
131410
352150

346810

135516

266090

35211B
135500

159910
146810

135311

216 Multi type Air Conditioner

249951

263230-1

263230-2

Exploded View & Replacement Parts List


Parts List (SE chassis)
LOCATION
No.

PART No.
AMNH07GDER0

AMNH09GDER0

AMNH12GDER0

SVC
CODE

131410 CHASSIS ASSEMBLY

3141A20034C

3141A20034C

3141A20034C

346810 MOTOR UNCLASSIFIED

4681A20091J

4681A20091J

4681A20091J

135516 COVER ASSEMBLY,MOTOR

3551A20156B

3551A20156B

3551A20156B

342800 BEARING

4280A20004B

4280A20004B

4280A20004B

135311 GRILLE ASSEMBLY,DISCHARGE(INDOOR)

3531A10137C

3531A10137C

3531A10137C

359011 FAN ASSEMBLY,CROSS FLOW

5983A20018G

5983A20018G

5983A20018G

354210 EVA ASSEMBLY, FIRST

5421A20017H

5421A20017H

5421A20017H

159830 FILTER ASSEMBLY, CONTROL(INDOOR)

4995A20018G

4995A20018G

4995A20018G

249951 CASE ASSEMBLY, CONTROL(INDOOR)

4995A20495W

4995A20495X

4995A20495Y

135313 GRILLE ASSEMBLY,FRONT(INDOOR)

MIRROR

3531A10374H

SILVER

3531A10374J

BLUE

3531A10374K

733010 PLATE ASSEMBLY, FRONT(INDOOR)

3301A20020A

3301A20020A

3301A20020A

267110 REMOTE CONTROLLER ASSEMBLY

6711A90031C

6711A90031C

6711A90031C

135500 COVER

3550A30258A

3550A30258A

3550A30258A

263230-1 THERMISTOR ASSEMBLY(IN)

6323A30002F

6323A30002F

6323A30002F

263230-2 THERMISTOR ASSEMBLY(OUT)

6323AQ3226T

6323AQ3226T

6323AQ3226T

263230-3 THERMISTOR ASSEMBLY(ROOM)

6323A20042A

6323A20042A

6323A20042A

35211B TUBE ASSEMBLY TUBING

5211A25050C

5211A25050C

5211A25050C

352150 HOSE ASSEMBLY DRAIN

5251AR1222R

5251AR1222R

5251AR1222R

159901 LOUVER, HORIZONTAL

5990A20072A

266090 HVPS,

6609A10003Z

152302 FILTER, AIR

5230A20064A

146810-1 MOTOR, DC

4681A20055A

146810-2 MOTOR, DC

4681A20055B

6871A20974A

6871A20974B

6871A20974C

DESCRIPTION

268714 PCB ASSEMBLY, MAIN

Service Manual 217

Exploded View & Replacement Parts List


Duct Type - High Static

359012
237210

346810

359012
336610-1
336610-2

W0CZZ

249951
354210
152302

352111

268714

263230-1
263230-2
552111
352118
330860

218 Multi type Air Conditioner

263230-3
267110

Exploded View & Replacement Parts List


Parts List(Duct Type - High Static )
LOCATION
No.
152302
237210
249951
263230-1
263230-2
263230-3
267110
268714
330860
336610-1
336610-2
346810
352111*
352118
354210
359012-1
359012
552111
WOCZZ
LOCATION
No.
152302
237210
249951
263230-1
263230-2
263230-3
267110
268714
330860
336600-1
336600-2
346810
352111*
352118
354210
359012-1
359012
552111
W0CZZ

DESCRIPTION
FILTER (MECH), A/C
PANEL ASSEMBLY, UPPER
CONTROL BOX ASSEMBLY(INDOOR)
THERMISTOR ASSEMBLY(IN)
THERMISTOR ASSEMBLY(ROOM)
THERMISTOR ASSEMBLY (OUT)
REMOTE CONTROLLER ASSEMBLY
PWB(PCB) ASSEMBLY, MAIN
DRAIN PAN ASSEMBLY
HOUSING(MECH), WRAPPER
HOUSING(MECH), WRAPPER
MOTOR ASSEMBLY, INDOOR
TUBE ASSEMLBY, CONNECTOR
TUBE ASSEMBLY, MENIFOLD(INDOOR)
EVAPORATOR ASSEMBLY, FIRST
FAN ASSEMBLY, BLOWER(Single)
FAN ASSEMBLY, BLOWER(Motor)
TUBE ASSEMBLY, CAPILLARY
CAPACITOR, DRAWING
DESCRIPTION
FILTER(MECH),A/C
PANEL ASSEMBLY,UPPER
CONTROL BOX ASSEMBLY,INDOOR
THERMISTOR ASSEMBLY
THERMISTOR ASSEMBLY
THERMISTOR ASSEMBLY
REMOTE CONTROLLER ASSEMBLY
PWB(PCB) ASSEMBLY,MAIN
DRAIN PAN ASSEMBLY
HOUSING (MECH),WRAPPER
HOUSING (MECH),WRAPPER
MOTOR ASSEMBLY,INDOOR
SOCKET (MECH),FLARE
TUBE ASSEMBLY,MENIFOLD(INDOOR)
EVAPORATOR ASSEMBLY,FIRST
FAN,BLOWER
FAN ASSEMBLY,BLOWER
TUBE ASSEMBLY,CAPILLARY
CAPACITOR,DRAWING

PART No.

SVC
CODE
AMNH186BHA0 AMNH246BHA0 AMNH306BGA0 AMNC306BGA0 AMNH366BGA0
5230A90002A
3721A20177A
4995A14002A
6323AQ3226G
6323AQ3214E
6323AQ3226V
6711A10008X
6871A10140E
3087A10008B
3660A20017A
3660A20018A
4681A10013C
5211A20514G
5211A20465G
5421A20100A
5901A10026A
5901A10028B
5211A20466K
2A00986D

5230A90002A
3721A20177A
4995A14002B
6323AQ3226G
6323AQ3214E
6323AQ3226V
6711A10008X
6871A10140F
3087A10008B
3660A20017A
3660A20018A
4681A10013C
5211A20514G
5211A20465G
5421A20100B
5901A10026A
5901A10028B
5211A20466L
2A00986D

5230A30001L
3721A20180A
4995A14002C
6323AQ3226G
6323AQ3214E
6323AQ3226V
6711A10008X
6871A10131H
3087A10008A
3660A20019A
3660A20020A
4681A10013J
5211A20514J
5211A20416J
5421A10027A
5901A10026A
5901A10028J
5211A20693D
2A00986D

5230A30001L
3721A20180C
4995A14002C
6323AQ3226G
6323AQ3214E
6323AQ3226V
6711A20043E
6871A10131H
3087A10008A
3660A20019A
3660A20020A
4681A10013J
5211A20514J
5211A20416J
5421A10027A
5901A10026A
5901A10028J
5211A20693D
2A00986D

5230A30001L
3721A20180A
4995A14002D
6323AQ3226G
6323AQ3214E
6323AQ3226V
6711A10008X
6871A10131J
3087A10008A
3660A20019A
3660A20020A
4681A10013A
5211A20514J
5211A20416J
5421A10027A
5901A10026A
5901A10028A
5211A20693D
2A00986D

PART No.

R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R

AMNC246BHA0

AMNC366BGA0

SVC
CODE

5230A30001M
3721A20177C
4995A14002B
6323AQ3226G
6323AQ3214E
6323AQ3226V
6711A20043E
6871A10140F
3087A10008B
3660A20017A
3660A20018A
4681A10013C
5162A20011C
5211A20465G
5421A20100B
5901A10026A
5901A10028B
5211A20466L
2A00986D

5230A30001L
3721A20180C
4995A14002D
6323AQ3226G
6323AQ3214E
6323AQ3226V
6711A20043E
6871A10131J
3087A10008A
3660A20019A
3660A20020A
4681A10013A
5211A20514J
5211A20416J
5421A10027A
5901A10026A
5901A10028A
5211A20693D
2A00986D

R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R

NOTE) *5211A20514G is for connecting service valve pipe fitting.

Service Manual 219

Exploded View & Replacement Parts List


Duct Type - Low Static (BT, BT1 chassis)

152302

346810
336610
267111

359012-2

A/CL

W0CZZ
359012-1

267110

354210

249951

263230-1
268714

552111
352118

352111

263230-2

330860
263230-3

220 Multi type Air Conditioner

Exploded View & Replacement Parts List


Parts List (Duct Type - Low Static)
LOCATION
No.

PART No.
AMNH096BTG0

AMNH126BTG0

AMNH186BTG0

SVC
CODE

152302 FILTER(MECH), A/C

5230A30001Q

5230A30001Q

5230A30001P

237203 PANEL ASSEMBLY, UPPER

3721A20150B

3721A20150B

3721A20150A

249951 CONTROL BOX ASSEMBLY(INDOOR)

4995A20338F

4995A20338E

4995A20338J

263230-1 THERMISTOR ASSEMBLY (IN)

6323AQ3226G

6323AQ3226G

6323AQ3226G

263230-2 THERMISTOR ASSEMBLY (ROOM)

6323AQ3214E

6323AQ3214E

6323AQ3214E

263230-3 THERMISTOR ASSEMBLY (OUT)

6323A20025D

6323A20025D

6323A20025D

267110 REMOTE CONTROLLER ASSEMBLY

6711A10008U

6711A10008U

6711A10008U

267111 *REMOTE CONTROLLER ASSEMBLY

6711A20041E

6711A20041E

6711A20041E

268714 PWB(PCB) ASSEMBLY, MAIN

6871A10131A

6871A10131B

6871A10131G

330860 DRAIN PAN ASSEMBLY

3087A10015C

3087A10015C

3087A10015B

336610 HOUSING(MECH), WRAPPER

3660A20033A

3660A20033A

3660A20033A

346810 MOTOR ASSEMBLY, INDOOR

4681A10022B

4681A10022B

4681A10022A

352118 TUBE ASSEMBLY, MENIFOLD(INDOOR)

5211A10418B

5211A25011B

5211A10418C

354210 EVAPORATOR ASSEMBLY, FIRST

5421A20153B

5421A21002A

5421A20153A

359012-1 FAN ASSEMBLY, BLOWER(Single)

5901A20030A

5901A20030A

5901A20030A

359012-2 FAN ASSEMBLY, BLOWER(Single)

5901A20030B

352111 TUBE ASSEMBLY, CONNECTOR

5211A20514G

5211A10417B

5211A25010A

5211A10417B

3A02157K

3A02157K

3A02157H

DESCRIPTION

552111 TUBE ASSEMBLY, EVAPORATOR IN


WOCZZ CAPACITOR, DRAWING

NOTE) "*" For Ausrailia, Wireless Remote Controller is supplied.

Service Manual 221

Exploded View & Replacement Parts List


Built in Duct type (BP chassis)

137214

267110-2

249951
267110-1

263230-1

263230-2
336610-1
359012
263230-3
268714

137210

158591
346810

359012-1

352118

336610-2

352111
354210

330860

152302

137202

222 Multi type Air Conditioner

Exploded View & Replacement Parts List


Parts List(Built in Duct Type-BP chassis)
Part No.

Location
No.

Description

AMNH096BPA0

AMNH126BPA0

SVC CODE

237202

PANLE, FRONT

3720A20260B

3720A20260B

137210

PANEL ASSEMBLY, FRONT (SINGLE)

3721A20168A

3721A20168A

137214

PANEL, UPPER

3721A20188A

3721A20188A

152302

FILTER (MECH), A/C

5230A30001R

5230A30001R

158591

PUMP ASSEMBLY, WATER

5859A20002A

5859A20002A

249951

CONTROL BOX ASSEMBLY(INDOOR)

4995A20355C

4995A20355B

263230-1 THERMISTOR ASSEMBLY

6323AQ3226Y

6323AQ3226Y

263230-2 THERMISTOR ASSEMBLY

6323AQ3214E

6323AQ3214E

263230-3 THERMISTOR ASSEMBLY

6323AQ3226E

6323AQ3226E

267110

REMOTE CONTROLLER ASSEMBLY

6711A10008U

6711A10008U

268714

PWB(PCB) ASSEMBLY, MAIN

6871A10140G

6871A10140H

330860

DRAIN PAN ASSEMBLY

3086A10036A

3086A10036A

336610-1 HOUSING(MECH), WRAPPER

3660A20017A

3660A20017A

336610-2 HOUSING(MECH), WRAPPER

3660A20018A

3660A20018A

4681A10031A

4681A10031A

352118-1 TUBE ASSEMBLY, MENIFOLD(OUT)

5211A21171A

5211A21171A

352118-2 TUBE ASSEMBLY, MANIFOLD (IN)

5211A21172A

5211A21172A

R
R

346811

MOTOR ASSEMBLY, INDOOR

354210

EVAPORATOR ASSEMBLY, FIRST

5421A20178E

5421A20178E

359012

FAN ASSEMBLY, BLOWE

5901A10049A

5901A10049A

359012-1 FAN ASSEMBLY, BLOWER(SINGLE)

5901A10026A

5901A10026A

2A00986D

2A00986D

WOCZZ

CAPACITOR, DRAWING

Service Manual 223

224 Multi type Air Conditioner

135802

137211

267110-2

268712

267110-1

152302

146811

135312

152312

140570

330860

135500

352116

263230-1

359011

W1SZ

352115

346810

263230-2

263230-3

266090

266012

354212
158591

354210

159830

OW
NE
RS
MA
NU
AL

738290

268714

130911

INS
TA
LL
MA
NU
AL

738282

249951

Exploded View & Replacement Parts List

Cassette Type - 1 way (TC1 chassis)

Exploded View & Replacement Parts List


Parts List(Cassette Type - 1 way)
LOCATION
No.

DESCRIPTION

Part No.

REMARKS

AMNH09GTCC0

AMNH12GTCC0

135802 DOOR LOCK

3580A20010A

3580A20010A

268714 PWB(PCB) ASSEMBLY,MAIN

6871A10363C

6871A10363D

139011 CABINET ASSEMBLY,INDOOR

3091A10024A

3091A10024A

158580 PUMP ASSEMBLY,WATER

5859A10001A

5859A10001A

159830 AIR CLEANER ASSEMBLY

5983A10006A

5983A10006A

249951 CONTROL BOX ASSEMBLY,INDOOR

4995A10114C

4995A10114D

263230-1 THERMISTOR ASSEMBLY (IN)

6323AQ3226E

6323AQ3226E

263230-2 THERMISTOR ASSEMBLY (OUT)

6323AQ3226V

6323AQ3226V

263230-3 THERMISTOR ASSEMBLY (ROOM)

6323AQ3213E

6323AQ3213E

266012 SWITCH ASSEMBLY,FLOAT

6601A20001E

6601A20001E

266090 HVB ASSEMBLY

6690A20009K

6690A20009K

267110-1 REMOTE CONTROLLER ASSEMBLY

6711A20127A

6711A20127A

267110-2 REMOTE CONTROLLER ASSEMBLY (WIRELESS)

6711A20096B

6711A20096B

Option

330870 DRAIN PAN ASSEMBLY

3087A10005A

3087A10005A

352115 TUBE ASSEMBLY,EVAPORATOR IN

5211A20229E

5211A20229E

352116 TUBE ASSEMBLY, EVAPORATOR OUT

5211A20230E

5211A20230E

354210 EVAPORATOR ASSEMBLY,FIRST

5421A10011A

5421A10011A

354212 DRAIN ASSEMBLY,TUBE

5251A20001A

5251A20001A

359011 FAN ASSEMBLY,CROSS FLOW

5901AR2441A

5901AR2441A

346810 MOTOR ASSEMBLY,INDOOR

4681A20091K

4681A20091K

135500 COVER

3550A21008A

3550A21008A

W1SZ

5239A10004A

5239A10004A

AIR GUIDE ASSEMBLY

Service Manual 225

226 Multi type Air Conditioner

135802

137211

267110-2

268712

267110-1

152302

146811

135312

152312

140570

330860
352116

263230-1

359011

W1SZ

352115

346810

263230-2

263230-3

266090

266012

354212
158591

W0CZZ

354210

OW
NE
RS
MA
NU
AL

738290

159830

268714

130911

INS
TA
LL
MA
NU
AL

738282

249951

Exploded View & Replacement Parts List

Cassette Type - 1 way (TC chassis)

Exploded View & Replacement Parts List


Parts List(Cassette Type - 1 way)
LOCATION
No.

DESCRIPTION

Part No.
AMNH096TCC0 AMNC096TCC0 AMNH126TCC0 AMNC126TCC0

REMARKS

135802 DOOR LOCK

3580A20010A

3580A20010A

268714 PWB(PCB) ASSEMBLY,MAIN

6871A10140A

6871A10140A

6871A10140B

6871A10140B

139011 CABINET ASSEMBLY,INDOOR

3091A10024A

3091A10024A

3091A10024A

3091A10024A

158580 PUMP ASSEMBLY,WATER

5859A10001A

5859A10001A

5859A10001A

5859A10001A

159830 AIR CLEANER ASSEMBLY

5983A10006A

5983A10006A

5983A10006A

5983A10006A

249951 CONTROL BOX ASSEMBLY,INDOOR

4995A10114B

4995A10114B

4995A10114A

4995A10114A

263230-1 THERMISTOR ASSEMBLY (IN)

6323AQ3226E

6323AQ3226E

6323AQ3226E 6323AQ3226E

263230-2 THERMISTOR ASSEMBLY (OUT)

6323AQ3226V

6323AQ3226V

6323AQ3226V 6323AQ3226V

263230-3 THERMISTOR ASSEMBLY (ROOM)

6323AQ3213E

6323AQ3213E

266012 SWITCH ASSEMBLY,FLOAT

6601A20001E

6601A20001E

6601A20001E

6601A20001E

266090 HVB ASSEMBLY

6690A20005C

6690A20005C

6690A20005C

6690A20005C

267110-1 REMOTE CONTROLLER ASSEMBLY

6711A10008V

6711A10002Q

6711A10008V

6711A10002Q

267110-2 REMOTE CONTROLLER ASSEMBLY (WIRELESS)

6711A20096B

6711A20096B

Option

330870 DRAIN PAN ASSEMBLY

3087A10005A

3087A10005A

3087A10005A

3087A10005A

352115 TUBE ASSEMBLY,EVAPORATOR IN

5211A20229E

5211A20229E

5211A20229E

5211A20229E

352116 TUBE ASSEMBLY, EVAPORATOR OUT

5211A20230E

5211A20230E

5211A20230E

5211A20230E

354210 EVAPORATOR ASSEMBLY,FIRST

5421A10011A

5421A10011A

5421A10011A

5421A10011A

354212 DRAIN ASSEMBLY,TUBE

5251A20001A

5251A20001A

5251A20001A

5251A20001A

359011 FAN ASSEMBLY,CROSS FLOW

5901AR2441A

5901AR2441A

5901AR2441A 5901AR2441A

346810 MOTOR ASSEMBLY,INDOOR

4681A20003Y

4681A20003Y

4681A20003Y

4681A20003Y

3H00671E

3H00671E

3H00671E

3H00671E

5239A10004A

5239A10004A

5239A10004A

5239A10004A

W0CZZ CAPACITOR, DRAWING


W1SZ

AIR GUIDE ASSEMBLY

Service Manual 227

Exploded View & Replacement Parts List


Cassette Type - 4 way[TE(1) chassis]

266090
249951

263230-3

263230-2

263230-1

268714

159830

354211

352118

35211A

158591
266012
352111
330870

228 Multi type Air Conditioner

Exploded View & Replacement Parts List

137211
130411

346810

359011
146811
W4056
268712

152312

130911-1

135312-2

135802

130911-2
267110-1

352150

Service Manual 229

Exploded View & Replacement Parts List


Parts List(Cassette Type - 4 way - TE(1) 9K, 12K, 18K)
LOCATION
No.
130411

DESCRIPTION
BASE ASSEMBLY,WELD[INDOOR]

PART No.

SVC
AMNH096TEC0 AMNH126TEC0 AMNH186TEC0 AMNH09GTEF0 AMNH12GTEF0 AMNH18GTEF0 CODE
3041A10013A 3041A10013A 3041A10013A 3041A10073A 3041A10073A 3041A10073A

130911-1 CABINET ASSEMBLY,INDOOR

3091A10023C 3091A10023C 3091A10023C 3091A10023E 3091A10023E 3091A10023E

130911-2 CABINET ASSEMBLY,INDOOR

3091A10023D 3091A10023D 3091A10023D 3091A10023F 3091A10023F 3091A10023F

152312

FILTER ASSEMBLY, AIR CLEANER

5231A10005A 5231A10005A 5231A10005A 5231A10002A 5231A10002A 5231A10002A

158591

PUMP ASSEMBLY,WATER

5859A20001M 5859A20001M 5859A20001M 5859A10007A 5859A10007A 5859A10007A

159830

AIR CLEANER ASSEMBLY

5983A10002A 5983A10002A 5983A10002A 5983A10002A 5983A10002A 5983A10002A

249951

CONTROL BOX ASSEMBLY,INDOOR 4995A20168B 4995A14001D 4995A14001C 4995A10180B 4995A10180C 4995A10180D

263230-1 THERMISTOR ASSEMBLY (OUT)

6323AQ3226T 6323AQ3226T 6323AQ3226T 6323AQ3226T 6323AQ3226T 6323AQ3226T

263230-2 THERMISTOR ASSEMBLY (IN)

6323AQ3226F 6323AQ3226F 6323AQ3226F 6323AQ3226N 6323AQ3226F 6323AQ3226F

263230-3 THERMISTOR ASSEMBLY (ROOM)

6323A10002A 6323A10002A 6323A10002A 6323A10002A 6323A10002A 6323A10002A

266012

SWITCH ASSEMBLY,FLOAT

6601A20001G 6601A20001G 6601A20001G 6601A20001M 6601A20001M 6601A20001M

266090

H.V ASSEMBLY

6609A20005C 6609A20005C 6609A20005C 6609A20009J 6609A20009J 6609A20009J

268714

PWB(PCB) ASSEMBLY,MAIN

6871A10209Z 6871A10158D 6871A10158C 6871A10363E 6871A10363F 6871A10363Y

6711A20076N 6711A20076N 6711A20076N 6711A20127A 6711A20127A 6711A20127A

267110-1 REMOTE CONTROLLER ASSEMBLY

267110-2 REMOTE CONTROLLER ASSEMBLY (WIRELESS) 6711A20096B 6711A20096B 6711A20096B

330870

DRAIN PAN ASSEMBLY

3087A10002A 3087A10002A 3087A10002A 3087A10030D 3087A10030D 3087A10030D

346810

MOTOR ASSEMBLY,INDOOR

4681AC2026E 4681AC2026E 4681AC2026C 4681A20168B 4681A20168B 4681A20168B

352111* TUBE ASSEMBLY, CONNECTOR

5211A20514G

5211A20514G

352118

TUBE ASSEMBLY,MENIFOLD(INDOOR)

5211A20241S 5211A20241S 5211A20241R 5211A21463D 5211A21463A 5211A21463A

35211A

TUBE ASSEMBLY, SUCTION (INDOOR)

5211A20243M 5211A20243M 5211A20243M 5211A12312A 5211A21486A 5211A21486A

352150

DRAIN ASSEMBLY, TUBE

5251A20002A 5251A20002A 5251A20002A

354211

EVAPORATOR ASSEMBLY,BENDING 5421A10006A 5421A10006A 5421A10006A 5421A10060B 5421A10060A 5421A10060A

359011

FAN,TURBO

W0CZZ

CAPACITOR,DRAWING

W4056

LOCKER

5900A10004A 5900A10004A 5900A10004A 5900A20054A 5900A20054A 5900A20054A


3H00660N

3H00660N

3H00660N

4056A20001A 4056A20001A 4056A20001A

NOTE) 35211* is for pipe fitting the SVC valve.

230 Multi type Air Conditioner

4A01405H

4A01405H

4A01405H

Exploded View & Replacement Parts List


Cassette Type - 4 way(TF chassis)

266090

249951

268714

354211-2
354211-1

159830

263230-1
352118-2
263230-2

552111
352118-1

158591

266012

330870

Service Manual 231

Exploded View & Replacement Parts List

130411

268712
W0CZZ
146811
346810

359012

152312

130911-2

135314

137211

267110-2

267110-1

130911-1

232 Multi type Air Conditioner

Exploded View & Replacement Parts List


Parts List(Cassette Type - 4 way - TF 24K, 30K)
LOCATION
No.

DESCRIPTION

130411 BASE ASSEMBLY,WELD[INDOOR]

Part No.
AMNH246TFC0 AMNH306TFC0 AMNH306TFA0 AMNC306TFC0

REMARKS

3041A10030B

3041A10030B

3041A10030B

3041A10030B

130911-1 CABINET ASSEMBLY,INDOOR

3091A10051A

3091A10051A

3091A10051A

3091A10051C

130911-2 CABINET ASSEMBLY,INDOOR

3091A10051B

3091A10051B

3091A10051B

3091A10051D

137211 PANEL ASSEMBLY,FRONT(INDOOR)

3721A10072E

3721A10072E

135314 GRILLE ASSEMBLY,FRONT(INDOOR)

3531A10211C

3531A10211C

146811 MOTOR ASSEMBLY,STEP

4681A20055A

4681A20055A

152312 FILTER ASSEMBLY, AIR CLEANER

5231A10012A

5231A10012A

158591 PUMP ASSEMBLY,WATER

5859A20001K

5859A20001K

5859A20001K

5859A20001K

159830 AIR CLEANER ASSEMBLY

5983A10002A

5983A10002A

5983A10002A

5983A10002A

249951 CONTROL BOX ASSEMBLY,INDOOR

4995A10093K

4995A10093N

4995A10093N

4995A10131D

263230-1 THERMISTOR ASSEMBLY (OUT)

6323AQ3226Y

6323AQ3226Y

6323AQ3226Y 6323AQ3226Y

263230-2 THERMISTOR ASSEMBLY (IN)

6323AQ3226E

6323AQ3226E

6323AQ3226E 6323AQ3226E

263230-3 THERMISTOR ASSEMBLY (ROOM)

6323A10002A

6323A10002A

6323A10002A

6323A10002A

266012 SWITCH ASSEMBLY,FLOAT

6601A20001H

6601A20001H

6601A20001H

6601A20001H

266090 H.V ASSEMBLY

6609A20005E

6609A20005E

6609A20005E

6609A20005E

268712 PWB(PCB) ASSEMBLY,DISPLAY

6871A20096J

6871A20096J

268714 PWB(PCB) ASSEMBLY,MAIN

6871A10158B

6871A10158R

6871A10158R 6871A10338W

6711A20076N

6711A20076N

6711A20076N

6711A20076K

267110-2 REMOTE CONTROLLER ASSEMBLY (WIRELESS) 6711A20096B

6711A20096B

6711A20096B

option

267110-1 REMOTE CONTROLLER ASSEMBLY

330870 DRAIN PAN ASSEMBLY

3087A10010B

3087A10010B

3087A10010B

3087A10010B

346810 MOTOR ASSEMBLY,INDOOR

4681A20051Z

4681A20051W

4681A20051W 4681A20051W

352111* TUBE ASSEMBLY, CONNECTOR

5211A20514G

5211A20514J

5211A20514J

5211A20514J

352118-1 TUBE ASSEMBLY,MENIFOLD(INDOOR)

5211A20251Q

5211A20251Q

5211A20251U

5211A20251U

352118-2 TUBE ASSEMBLY, MANIFOLD (INDOOR)

5211A20251K

5211A20251K

5211A20251K

5211A20251K

552111 TUBE ASSEMBLY, CAPILLARY (INDOOR)

5211A21137B

5211A21137B

5211A21137B

5211A21137B

352150 DRAIN ASSEMBLY, TUBE

5251A20002B

5251A20002B

5251AP2984A

5251A20002B

354211-1 EVAPORATOR ASSEMBLY,BENDING

5421A10016G

5421A10016G

5421A10016G 5421A10016G

354211-2 EVAPORATOR ASSEMBLY, BENDING

5421A10016H

5421A10016H

5421A10016H

5421A10016H

5901A10036A

5901A10036A

5901A10036A

5901A10036A

3H00660M

3H00660M

3H00660M

3H00660M

4056A20001B

4056A20001B

4056A20001B

4056A20001B

359012 FAN,TURBO
W0CZZ CAPACITOR,DRAWING
W4056

LOCKER

NOTE) 35211* is for pipe fitting the SVC valve.

Service Manual 233

Exploded View & Replacement Parts List


Cassette Type - 4 way(TH chassis)

249951
249941
266090

249941

159830
268714

W6640

263230-3
249951
130412

135511

352114

352114
55211G

330870

234 Multi type Air Conditioner

263230-1
263230-2

352115
352118

Exploded View & Replacement Parts List

130412

W0CZZ

648600

349600

346810

359012

130911-2

140570

130911-3

152510-2

130911-4

152510-1
130911-1

Service Manual 235

Exploded View & Replacement Parts List


Parts List(Cassette Type - 4 way - TH)
LOCATION
No.

PART No.
AMNH24GTHF0

SVC
CODE

BASE ASSEMBLY,WELD[INDOOR]

3041A10069A

130911-1

CABINET ASSEMBLY, INDOOR

3091A10085A

130911-2

CABINET ASSEMBLY, INDOOR

3091A10075A

130911-3

CABINET ASSEMBLY, INDOOR

3091A10075B

158591

PUMP ASSEMBLY,WATER

5859A10006C

159830

FILTER ASSEMBLY, AIR CLEANER

5983A10003D

249951

CONTROL BOX ASSEMBLY,INDOOR

4995A11007W

263230-1

THERMISTOR ASSEMBLY (OUT)

6323A30002A

263230-2

THERMISTOR ASSEMBLY (IN)

6323AQ3226W

263230-3

THERMISTOR ASSEMBLY (ROOM)

6323A10002B

266012

SWITCH ASSEMBLY,FLOAT

6601A20001K

266090

H.V ASSEMBLY

6609A20009L

268714

PWB(PCB) ASSEMBLY,MAIN

6871A10363G

267110-1

REMOTE CONTROLLER ASSEMBLY

6711A20127A

267110-2

REMOTE CONTROLLER ASSEMBLY (WIRELESS)

130411

DESCRIPTION

330870

DRAIN PAN ASSEMBLY

3087A10035F

346810

MOTOR ASSEMBLY,INDOOR

4681A20168A

352118-1

TUBE ASSEMBLY,MENIFOLD(INDOOR)

5211A10600A

352118-2

TUBE ASSEMBLY, MANIFOLD (INDOOR)

552111

TUBE ASSEMBLY, CAPILLARY (INDOOR)

5211A10550B

354211-1

EVAPORATOR ASSEMBLY,BENDING

5421A10061A

354211-2

EVAPORATOR ASSEMBLY, BENDING

5900A10016A

4A01405C

359011

FAN,TURBO

W4056

LOCKER

NOTE) 35211* is for pipe fitting the SVC valve.

236 Multi type Air Conditioner

Exploded View & Replacement Parts List


Cassette Type - 4 way(TD chassis)

249951
266090

268714

159830

263230-1
263230-2

130411

263230-3

354211

352118-1

552111
352118-2

330870

158591

266012

Service Manual 237

Exploded View & Replacement Parts List

130411

W0CZZ

146811

268712

346810
152312
359012

140570
130911-2
130912-1
135313

135802
267110-1

137211
130912-2

130911-1
267110-2

238 Multi type Air Conditioner

352150-2

Exploded View & Replacement Parts List


Parts List(Cassette Type - 4 way - TD 36K)
LOCATION
No.

PART No.
AMNH366TDC0

AMNC366TDC0

SVC
CODE

BASE ASSEMBLY,WELD[INDOOR]

3041A10016A

3041A10016A

130911-1

CABINET ASSEMBLY, INDOOR

3091A10030A

3091A20034A

130911-2

CABINET ASSEMBLY, INDOOR

3091A10030B

3091A20034B

130912-1

CABINET ASSEMBLY, INDOOR

3091A10031A

3091A20035A

130912-2

CABINET ASSEMBLY, INDOOR

3091A10031B

3091A20035B

137211

PANEL ASSEMBLY,FRONT(INDOOR)

3721A10106B

135314

GRILLE ASSEMBLY,FRONT(INDOOR)

3531A10066A

135802

DOOR ROCK

3580A20005A

146811

MOTOR ASSEMBLY,STEP

4681A20055A

152312

FILTER ASSEMBLY, AIR CLEANER

5231A10004A

158591

PUMP ASSEMBLY,WATER

5859A20001D

5859A20001D

159830

AIR CLEANER ASSEMBLY

5983A10003D

5983A10003D

249951

CONTROL BOX ASSEMBLY,INDOOR

4995A22004L

4995A22004U

263230-1

THERMISTOR ASSEMBLY (OUT)

6323AQ3226V

6323AQ3226T

263230-2

THERMISTOR ASSEMBLY (IN)

6323AQ3226A

6323A30002A

263230-3

THERMISTOR ASSEMBLY (ROOM)

6323A10002B

6323A10002B

266012

SWITCH ASSEMBLY,FLOAT

6601A20001F

6601A20001F

266090

H.V ASSEMBLY

6609A20005D

6609A20005H

268712

PWB(PCB) ASSEMBLY,DISPLAY

6871A20096J

268714

PWB(PCB) ASSEMBLY,MAIN

6871A10158S

6871A10338X

267110-1

REMOTE CONTROLLER ASSEMBLY

6711A20076N

6711A20076K

267110-2

REMOTE CONTROLLER ASSEMBLY (WIRELESS)

6711A20096B

330870

DRAIN PAN ASSEMBLY

3087A10006A

3087A10006A

346810

MOTOR ASSEMBLY,INDOOR

4681A20006J

4681A20006J

352111*

TUBE ASSEMBLY, CONNECTOR

5211A20514J

5211A20514J

352118-1

TUBE ASSEMBLY,MENIFOLD(INDOOR)

5211A20251R

5211A20251R

352118-2

TUBE ASSEMBLY, MANIFOLD (INDOOR)

5211A20251B

5211A20251B

552111

TUBE ASSEMBLY, CAPILLARY (INDOOR)

5211A20316M

5211A20316M

354211-1

EVAPORATOR ASSEMBLY,BENDING

5421A10016A

5421A10016A

354211-2

EVAPORATOR ASSEMBLY, BENDING

5421A10016B

5421A10016B

359011

FAN,TURBO

5900A10003B

5900A10003B

738282

MANUAL, INSTALLATION

3828A20403F

738290

MANUAL,OWNERS

3828A20394D

W0CZZ

CAPACITOR,DRAWING

3H00660M

3H00660M

W4056

LOCKER

4056A20001B

4056A20001B

130411

DESCRIPTION

NOTE) 35211* is for pipe fitting the SVC valve.

Service Manual 239

Exploded View & Replacement Parts List


Convertible Type (VE chassis)

137211

135310
268712

147581

152302
135313
146811

733010
131410

267110
W0CZZ
330870

266000

135500
346810
263230-1

131410

354212
35211B

268715

352150
268716
263230-2

W4810
359011

266000
249951

342800
738282

738290

330780
159830

240 Multi type Air Conditioner

INS
TA
LL
MA
NU
AL

266090

OW
NE
RS
MA
NU
AL

Exploded View & Replacement Parts List


Parts List(Convertible Type-VE chassis)
LOCATION
No.

DESCRIPTION

PART No.
AMNH096VEA0 AMNH096VEL0 AMNH126VEA0 AMNH126VEL0

SVC CORD

137211

PANEL ASSEMBLY,FRONT(INDOOR)

3721A10092A

3721A10092A

3721A10092A

3721A10092A

146811

MOTOR ASSEMBLY,STEP

4681A20055A

4681A20055A

4681A20055A

4681A20055A

147581

LOUVER,HORIZONTAL

4758A10006A

4758A10006A

4758A10006A

4758A10006A

152302

FILTER(MECH),A/C

5230A10009A

5230A10009A

5230A10009A

5230A10009A

159830

AIR CLEANER ASSEMBLY

5983A20007F

5983A20007F

249951

CONTROL BOX ASSEMBLY,INDOOR

4995A20356F

4995A20356

4995A20356E

4995A20356

263230-1 THERMISTOR ASSEMBLY (IN, ROOM)

6323A20004T

6323A20004T

6323A20004T

6323A20004T

263230-2 THERMISTOR ASSEMBLY (OUT)

6323AQ3226V

6323AQ3226V

6323AQ3226V

6323AQ3226V

266000

SWITCH,PUSH

6600AP2059B

6600AP2059B

6600AP2059B

6600AP2059B

266090

H.V ASSEMBLY

6609A10003S

6609A10003S

267110

REMOTE CONTROLLER ASSEMBLY

6711A20096A

6711A20096A

6711A20096A

6711A20096A

268712

PWB(PCB) ASSEMBLY,DISPLAY

6871A20390D

6871A20390D

6871A20390D

6871A20390D

268715

PWB(PCB) ASSEMBLY,MAIN(AC)

6871A20359B

6871A20359B

6871A20359B

6871A20359B

268716

PWB(PCB) ASSEMBLY,MAIN(DC)

6871A20358E

6871A20358

6871A20358F

6871A20358

330780

CUT OFF

3078A20001A

3078A20001A

3078A20001A

3078A20001A

330870

DRAIN PAN ASSEMBLY

3087A10018A

3087A10018A

3087A10018A

3087A10018A

342800

BEARING

4280A20004A

4280A20004A

4280A20004A

4280A20004A

346810

MOTOR ASSEMBLY,INDOOR

4681A20131B

4681A20131B

4681A20131A

4681A20131A

35211B

TUBE ASSEMBLY,TUBING

5211A21217B

5211A21217B

5211A21217B

5211A21217B

352115

TUBE ASSEMBLY, EVAPORATOR IN

5211A25012B

5211A25012B

5211A25012B

5211A25012B

352116

TUBE ASSEMBLY EVAPORATOR OUT

5211A22007B

5211A22007B

5211A22007B

5211A22007B

352150

HOSE ASSEMBLY,DRAIN

5251AR2575Q

5251AR2575Q

5251AR2575Q

5251AR2575Q

354211

EVAPORATOR ASSEMBLY,FIRST

5421A30019B

5421A30019B

5421A30019B

5421A30019B

359011

FAN ASSEMBLY,CROSS FLOW

5901A20008E

5901A20008E

5901A20008E

5901A20008E

733010

PLATE ASSEMBLY,INSTALL

3301A10002A

3301A10002A

3301A10002A

3301A10002A

738282

MANUAL INSTALLATION

3828A20403K

3828A20403K

3828A20403K

3828A20403K

738290

MANUAL OWNER'S

3828A20394H

3828A20394H

3828A20394H

3828A20394H

W0CZZ

CAPACITOR,DRAWING

3H00671A

3H00671A

3H00671A

3H00671A

W4810

BRACKET

4810A21019A

4810A21019A

4810A21019A

4810A21019A

131410

CHASSIS ASSEMBLY

3141A10009A

3141A10009A

3141A10009A

3141A10009A

135500

COVER

3550A30201A

3550A30201A

3550A30201A

3550A30201A

135310

GRILL ASSEMBLY, DIFFUSER(INDOOR)

3531A10248A

3531A10248A

3531A10248A

3531A10248A

135313

GRILL ASSEMBLY, INLET

3531A10247A

3531A10247A

3531A10247A

3531A10247A

NOTE) *Please ensure GCSC since these parts may be changed depending upon the buyer's request.
(GCSC WEBSITE http://biz.LGservice.com)

Service Manual 241

242 Multi type Air Conditioner

267110

159911

159912

135303

135314

137211

352150

146811

235450
237900

268712

135310

152302

330870

354210

346810

352111

359010

268711

W0CZZ

166000

249951
352115

342800

35211A
263230-1
263230-2

130911

Exploded View & Replacement Parts List

Convertible Type (VB chassis)

Exploded View & Replacement Parts List


Parts List(Convertible Type-VB chassis)
Location
No.
130911
135303
135310
135314
137211
146811
152302
159911
159912
166000
235450
237900
249951
263230-1
263230-2
267110
268711
268712
330870
342800
346810
35211A
352111*
352115
352150
354210
359010
W0CZZ

Part No.
Description
CABINET ASSEMBLY
GRILLE, INLET
GRILLE ASSEMBLY, DIFFUSER (INDOOR)
GRILLE ASSEMBLY, INLET SUB
PANEL ASSEMBLY, FRONT (INDOOR)
MOTOR ASSEMBLY, STEP
FILTER(MECH), A/C
VANE ASSEMBLY, HORIZONTAL(UPPER)
VANE ASSEMBLY, HORIZONTAL(LOWER)
SWITCH, PUSH
DISPLAY ASSEMBLY (MECH)
WINDOW, DISPLAY
CONTROL BOX ASSEMBLY, INDOOR
THERMISTOR ASSEMBLY (ROOM, IN)
THERMISTOR ASSEMBLY (OUT)
REMOTE CONTROLLER ASSEMBLY
PWB(PCB) ASSEMBLY, MAIN
PWB(PCB) ASSEMBLY, DISPLAY
DRAIN PAN ASSEMBLY
BEARING
MOTOR ASSEMBLY, INDOOR
TUBE ASSEMBLY, SUCTION INDOOR
TUBE ASSEMBLY, CONNECTOR
TUBE ASSEMBLY, EVAPORATOR - IN
HOSE ASSEMBLY, DRAIN
EVAPORATOR ASSEMBLY, FIRST
FAN ASSEMBLY, CROSS FLOW
CAPACITOR, DRAWING

AMNH
186VBA0
3091AP2533A
5230AP1236A
3531A10272E
5237AP2817B
3720AP2767P
4681A20055A
5230AP7093A
5991AP2867B
5991AP7334C
6600AP2059B
3545AP7224B
3790AP7080A
4995A10107B
6323A20004Y
6323AQ3226Y
6711A20014S
3871A10159B
6871AQ3263A
3087AP7233A
3H02821B
4681AP2306M
5211AP2813G
5211A20514G
5211AP2810Q
5251AP2460B
5421AP2812B
5901AR2351E
3H00671A

AMNH
246VBA0
3091AP2533A
5230AP1236A
3531A10272E
5237AP2817B
3720AP2767P
4681A20055A
5230AP7093A
5991AP2867B
5991AP7334C
6600AP2059B
3545AP7224B
3790AP7080A
4995A10107C
6323A20004Y
6323AQ3226Y
6711A20014S
3871A10159A
6871AQ3263A
3087AP7233A
3H02821B
4681AP2306N
5211AP2813H
5211A20514G
5211AP2810R
5251AP2460B
5421AP2812A
5901AR2351E
3H00671A

SVC
CODE
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R

NOTE) 35211* is for pipe fitting the SVC valve.

Service Manual 243

244 Multi type Air Conditioner

435301

552112

552113-1

437211

559010

447910

546810

430410

W0CZZ
261704

554031

552113-2

554160

552203-2

552203-1

552203-2

552203-1

552200

561410

567480-2
661400-1
661400-2

567480-1

649950

435511

552116

268711

437212

Exploded View & Replacement Parts List

Outdoor Unit

A2UW146FA2, A2UW166FA0, A2UW166FA1

435301

435512
552112

437211

559010

552113-1

430411

447910

546810

658740

566000

W0CCZ

554031

552113-2

554160-1

552204-2

552204-1

552116

668711

435511

561410

263230-2

263230-1

552203-2

552203-1

552203-2

552203-1

561411

649950

437212

Exploded View & Replacement Parts List

A2UW146FA0, A3UW186FA1

Service Manual 245

435301

435512
552112

246 Multi type Air Conditioner


437211

559010

558511

552113-1

430411

447910

546810

261704

566000

W0CZZ

554031

552113-2

554160

661400-2

661400-1

552116

268711

137213-1

435300

561410

567480-2

567480-1

552203-2

552203-1

552203-2

552203-1

552200

649950

435511

137213-2

Exploded View & Replacement Parts List


A2UW146FA1, A2UW186FA0, A3UW186FA0

Exploded View & Replacement Parts List


Parts List(Single compressor inverter)
Part No.

Location
No.

Description

567480-1

THERMISTOR ASSEMBLY

567480-2

A2UW146FA2

A2UW166FA0

A2UW166FA1

SVC
CODE

6323A20037A

6323A20037A

6323A20037A

THERMISTOR ASSEMBLY

6323A20037B

6323A20037B

6323A20037B

430410

BASE ASSEMBLY,OUTDOOR

3041A20066A

3041A20066A

3041A20066A

435301

GRILLE,DISCHARGE

3530A20006G

3530A20006G

3530A20006G

435511

COVER ASSEMBLY,CONTROL(OUTDOOR)

3551A30115G

3551A30115G

3551A30115G

437211

PANEL ASSEMBLY,FRONT(OUTDOOR)

3721A20027Q

3721A20027Q

3721A20027Q

437212

PANEL ASSEMBLY,REAR(OUTDOOR)

3721A20026Y

3721A20026Y

3721A20026Y

447910

BARRIER ASSEMBLY,OUTDOOR

4791A30002G

4791A30002G

4791A30002G

546810

MOTOR ASSEMBLY,OUTDOOR

4681A20170A

4681A20170A

4681A20170A

552112

TUBE ASSEMBLY,CONDENSER IN

5211A23331A

5211A23331A

5211A23331A

552113-1

TUBE ASSEMBLY,CONDENSER OUT

5211A23336A

5211A23332A

5211A23336A

552113-2

TUBE ASSEMBLY,CONDENSER OUT

5211A23337A

5211A20927D

5211A23337A

TUBE ASSEMBLY,REVERSING

5211A23335A

5211A23330A

5211A23335B

552203-1

VALVE,SERVICE

5220A20001K

5220A20001K

5220A20001K

552203-2

VALVE,SERVICE

2H02479J

2H02479J

2H02479J

552204-1

HARNESS

6877A20050N

6877A20050N

6877A20050N

552204-2

HARNESS

6877A20050P

6877A20050P

6877A20050P

554031

CONDENSER ASSEMBLY,BENT

5403A20221A

5403A20221A

5403A20221A

554160

COMPRESSOR SET

5416A90029A

2520UGHN2AC

5416A90015A

558511

DRIER ASSEMBLY

5851A20003J

5851A20003J

559010

FAN ASSEMBLY,PROPELLER

5901A10033A

5901A10033A

5901A10033A

561410

COIL ASSEMBLY,REVERSING VALVE

6141AR3509L

6141AR3509L

6141AR3509L

552200

COIL ASSEMBLY,EXPANSION

6140A90001K

6140A90001K

6140A90001K

649950

CONTROL BOX ASSEMBLY,OUTDOOR

4995A21016B

4995A21016A

4995A21016C

658740

REACTOR

5874A90003A

5874A90003A

5874A90003A

668711
668713

PWB(PCB) ASSEMBLY,MAIN(OUTDOOR)
PWB(PCB) ASSEMBLY, SUB (CENTRAL CONTROL)

6871A10334A
6871A20484A

6871A10225A
6871A20484A

6871A10334B
6871A20484A

R
OPTION

W0CZZ

CAPACITOR,DRAWING

3A02157A

3A02157A

3A02157A

552116

NOTE) 35211* is for pipe fitting the SVC valve.

Service Manual 247

Exploded View & Replacement Parts List


Outdoor Unit Parts List (Single compressor inverter)
LOCATION
No.

DESCRIPTION

PART No.
A2UW146FA0 A2UW146FA1 A2UW186FA0 A3UW186FA0 A3UW186FA1

SVC
CODE

137213-1

PANEL ASSEMBLY, SIDE

1A00201D

1A00201D

1A00201D

137213-2

PANEL ASSEMBLY, SIDE

3A02284M

3A02284M

3A02284M

567480-1

THERMISTOR ASSEMBLY (ROOM, OUT)

6323A20020F 6323A20020F 6323A20037A 6323A20037A 6323A20020F

567480-2

THERMISTOR ASSEMBLY (DISCHARGE, SUCTION)

6323A20020G 6323A20020G 6323A20037B 6323A20037B 6323A20020G

430411

BASE ASSEMBLY, WELD[OUTDOOR]

3041A20022Q 3041A20022Q 3041A20022Q 3041A20022Q 3041A11002B

435301

GRILLE, DISCHARGE

3530A20007B 3530A20007J 3530A20007B 3530A20007B 3530A20007B

435511

COVER ASSEMBLY, CONTROL(OUTDOOR)

3A01919B

3A01919B

3A01919B

3A01919B

3A01919B

435512

COVER ASSEMBLY, TOP(OUTDOOR)

3H03266K

3H03266L

3H03266L

3H03266L

3H03266K

437211

PANEL ASSY, FRONT (OUTDOOR)

3721A20005P 3721A20004L 3721A23001A 3721A23001A 3721A30011G

437212

PANEL ASSEMBY, REAR

3720AP0003F

3720AP0003F

435300

GRILLE, REAR

1A00207B

1A00207B

1A00207B

447910

BARRIER ASSEMBLY, OUTDOOR

3H03307L

3H03307L

3H03307L

3H03307L

3H03307N

546810

MOTOR ASSEMBLY, OUTDOOR

548490

ACCUMULATOR ASSEMBLY

552112

4681A20028J 4861A20028S 4681A20028J 4681A20028J 4681A20028J


-

TUBE ASSEMBLY, CONDENSER IN

5211A24019A 5211A30298A 5211A30298A 5211A30298A 5211A21423A

552113-1

TUBE ASSEMBLY, CONDENSER OUT

5211A24018A 5211A30297Z 5211A23320A 5211A23320A 5211A21424A

552113-2

TUBE ASSEMBLY, COND OUT (SUPPORTER)

552200

VALVE, EXPANSION BODY

5220A90010A

552203-1

VALVE, SERVICE (9.52)

5220A20001K 5220A20001K 5220A20001K 5220A20001K 5220A20001K

552203-2

VALVE, SERVICE (6.35)

552204-1

COIL ASSEMBLY, EXPANSION (A)

6141A20018K 6877A20050A 6877A20050A 6877A20050A 6877A20050A

552204-2

COIL ASSEMBLY, EXPANSION(B)

6141A20018L 6877A20050B 6877A20050B 6877A20050B 6877A20050B

552204-3

COIL ASSEMBLY, EXPANSION (C)

552116

2A02479R

5211A20927A 5211A20927A 5211A21155C 5211A21155E


2A00468J

2H02479J

2H02479J

2H02479J

R
R
R

TUBE ASSEMBLY, REVERSING

5211A20493Q 5211A20493U 5211A20493H 5211A20493R 5211A21422A

554031

CONDENSER ASSEMBLY, BENT

5403A10013J 5403A20072N 5403A20072N 5403A20072N 5403A20072Y

554160

COMPRESSOR

5416A90008A 5416A90029A 5416A90015A 5416A90015A 2520UGHN2AC

558511

DRIER ASSEMBLY

559010

FAN ASSEMBLY, PROPELLER

5901A10032A 5901A10032A 5901A10032A 5901A10032A 5901A10032A

561410

COIL ASSEMBLY, REVERSING VALVE

6141AR3509L 6141AR3509L 6141AR3509L 6141AR3509L 6141AR3509L

561411

COIL ASSEMBLY, EXPANSION

6140A90001F 6140A90001K 6140A90001K 6140A90001K 6140A90001K

566000

SWITCH, PRESSURE (LOW PRESSURE)

649950

CONTROL BOX ASSEMBLY, OUTDOOR

4995A10101H 4995A10101M 4995A10101A 4995A10101J 4995A10101T

658740

REACTOR

5874A90003E 5874A90003A 5874A90003E 5874A90003E 5874A90003E

668711

PWB(PCB) ASSEMBLY, MAIN(OUTDOOR)

6871A10117K 6871A10182Y 6871A10117B 6871A10117L 6871A10196B

668713

PWB(PCB) ASSEMBLY, SUB (CENTRAL CONTROL)

6871A20484A 6871A20484A

W0CZZ

CAPACITOR, DRAWING

2A00986D

W49810

SUPPORT ASSEMBLY

498110019B

6877A20050K 6877A20050K

248 Multi type Air Conditioner

4849A20012E

5851A30004A 5851A20003J 5851A20003J

3A02524F

3A02524F

R
R

OPTION

2A00986D

2A00986D

2A00986D

2A00986D

435301

263230-3

263230-2

263230-1

566000

435512
558511

552115

437210

559010

552113

552204

430411

447910

546810

554160-1

658740

554031

649950

552113

554160-2

561410

561411

668711

548490

137213-1

552113-2

552113-1

435300

561411-4

561411-3

561411-2

561411-1

435511

137213-2

Exploded View & Replacement Parts List

A3UW246FA0, A4UW246FA0

Service Manual 249

Exploded View & Replacement Parts List


Parts List (A3UW246FA0, A4UW246FA0 - TPS Inverter)
Part No.

Location
No.

Description

137213-1
137213-2
263230-1
263230-2
263230-3
352113
430410
435300
435301
435511
435512
437210
447910
546810
548490
552111
552113
552115
552116
552203-1
552203-2
552204
554031
554160
554161
558511
559010
561410-1
561410-2
561410-3
561410
561411-1
561411-2
561411-3
561411-4
566000
649950
658740
668711
552201
W0CZZ-1
W0CZZ-2

PANEL ASSEMBLY, SIDE


PANEL ASSEMBLY, SIDE
THERMISTOR ASSEMBY (INV DISCHARGE, SUCTION)
THERMISTOR ASSEMBLY (CONST DISCHARGE)
THERMISTOR, ASSEMBLY (ROOM, COND OUT)
TUBE, ASSEMBLY, DISCHARGE
BASE ASSEMBLY, WELD
GRILLE, REAR
GRILLE, DISCHARGE
COVER ASSEMBLY, CONTROL (OUTDOOR)
COVER ASSEMBLY, TOP
PANEL ASSEMBLY, FRONT SUB
BARRIER ASSEMBLY, OUTDOOR
MOTOR ASSEMBLY, OUTDOOR
ACCUMULATOR ASSEMBLY
TUBE ASSEMBLY, CAPILLARY
TUBE ASSEMBLY, CONDENSER OUT
TUBE ASSEMBLY, MANIFOLD
TUBE ASSEMBLY, REVERSING
VALVE, SERVICE (9.52)
VALVE, SERVICE (6.35)
VALVE, SOLENOID (BODY)
CONDENSER ASSEMBLY, BENT
COMPRESSOR (INVERTER)
COMPRESSOR (CONSTANT)
DRIER, ASSEMBLY
FAN ASSEMBLY, PROPELLER
COIL ASSEMBLY, REVERSING VALVE
COIL ASSEMBLY, SOLENOID
COIL ASSEMBLY, SOLENOID
VALVE, EXPANSION BODY
COIL ASSEMBLY EXPANSION (A)
COIL ASSEMBLY EXPANSION (B)
COIL ASSEMBLY EXPANSION (C)
COIL ASSEMBLY EXPANSION (D)
SWITCH, PRESSURE
CONTROL BOX ASSEMBLY, OUTDOOR
REACTOR
PWB(PCB) ASSEMBLY, MAIN(OUTDOOR)
VALVE, CHECK
CAPACITOR, DRAWING (FAN)
CAPACITOR, DRAWING (COMP)

250 Multi type Air Conditioner

A3UW246FA0

A4UW246FA0

1A00202F
3A02284R
6323A20030G
6323A20001J
6323A20020F
5211A23013A
3041AP2741H
1A00208H
3530A20007J
3A01919B
3551A30113C
1A00197C
4791A30004M
4681A20028Y
4849A22003A
5211A22009A
5211A21155B
5211A20895A
5211A20896A
5220A20001K
2H02479J
5220A90002C
5403A20070B
5416A90015A
5416A90016A
5851A30004A
5901A20003J
6877A20052D
6877A20052E
6877A20052F
6140A90001K
6877A20050C
6877A20050D
6877A20050E
3A02524F
4995A10101B
5874A90003E
6871A10117C
5220A30004A
2A00986D
2H00841F

1A00202F
3A02284T
6323A20030G
6323A20001J
6323A20020H
5211A23013A
3041AP2741H
1A00208H
3530A20007J
3A01919B
3551A30113C
1A00197C
4791A30004M
4681A20028Y
4849A22003A
5211A22009A
5211A21155A
5211A20895A
5211A20896A
5220A20001K
2H02479J
5220A90002C
5403A20070B
5416A90015A
5416A90016A
5851A30004A
5901A20003J
6877A20052D
6877A20052E
6877A20052F
6140A90001K
6877A20050C
6877A20050D
6877A20050E
6877A20050L
3A02524F
4995A10101K
5874A90003E
6871A10117M
5220A30004A
2A00986D
2H00841F

SVC CODE
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R

435301

435512

566000

558511

352113

552116

548490

437210

559010

552115

552204

552111

546810-2

546810-1

430410

447910
554160

W0CZZ-2

649950

554031-2

668711

554031-1

552113

W0CZZ-1

137213-1

554161

561410

658740

552203-2

552203-1

561411-4

561411-3

561411-2

561411-1

135314

137213-2

435511

Exploded View & Replacement Parts List

A4UW306FA0

Service Manual 251

Exploded View & Replacement Parts List


Parts List (A4UW306FA0 - TPS Inverter)
Part No.
Location No.

Description

135301
137213-1
137213-2
263230-1
263230-2
263230-3
352113
430410
435300
435511
435512
437211
447910
546810-1
546810-2
548490
552111
552113
552115
552116
552201
552203-1
552203-2
552204
554031
554160
554161
558511
559010
561410
561410-1
561410-2
561410-3
561411-1
561411-2
561411-3
561411-4
566000
649950
658740
668711
668713
W0CZZ-1
W0CZZ-2

GRILLE,DISCHARGE
PANEL ASSEMBLY,SIDE
PANEL ASSEMBLY,SIDE
THERMISTOR ASSEMBLY (ROOM, COND, OUT)
THERMISTOR ASSEMBLY (DISCHARGE, SUCTION)
THERMISTOR ASSEMBLY (DISCHARGE, CONST)
TUBE ASSEMBLY, DISCHARGE SINGLE
BASE ASSEMBLY, OUTDOOR
GRILLE,REAR
COVER ASSEMBLY,CONTROL(OUTDOOR)
COVER ASSEMBLY,TOP(OUTDOOR)
PANEL ASSEMBLY,FRONT(OUTDOOR)
BARRIER ASSEMBLY,OUTDOOR
MOTOR ASSEMBLY,OUTDOOR
MOTOR ASSEMBLY, OUTDOOR
ACCUMULATOR ASSEMBLY(MECH)
TUBE ASSEMBLY, CAPILLARY
TUBE ASSEMBLY, CONDENSER OUT
TUBE ASSEMBLY, MANIFOLD
TUBE ASSEMBLY,REVERSING
VALVE, CHECK
VALVE,SERVICE(9, 52)
VALVE,SERVICE (6, 35)
VALVE, SOLENOID (BODY)
CONDENSER ASSEMBLY,BENT
COMPRESSOR (INVERTER)
COMPRESSOR (CONSTANT)
DRIER ASSEMBLY
FAN ASSEMBLY,PROPELLER
VALVE, EXPANSION (BODY)
COIL ASSEMBLY,REVERSING VALVE
COIL ASSEMBLY SOLENOID (P/ICE)
COIL ASSEMBLY SOLENOID (OIL/S)
COIL ASSEMBLY,EXPANSION (A)
COIL ASSEMBLY,EXPANSION (B)
COIL ASSEMBLY,EXPANSION (C)
COIL ASSEMBLY,EXPANSION (D)
SWITCH, PRESSURE (LOW)
CONTROL BOX ASSEMBLY,OUTDOOR
REACTOR
PWB(PCB) ASSEMBLY,MAIN(OUTDOOR)
PWB(PCB) ASSEMBLY, SUB (CENTRAL CONTROL)
CAPACITOR,DRAWING (COMP)
CAPACITOR,DRAWING (FAN)

252 Multi type Air Conditioner

A4UW306FA0
3530A20006B
3721A10110A
3721A10111A
6323A20020H
6323A20020J
6323A20001K
35211A23013A
3041AP2741H
3530A10176B
3A01919B
3551A30113C
3721A10109A
4791A10019A
4681AR1392Y
4681AR1392Z
4849A22003A
5211A22010A
5211A21155A
5211A20895B
5211A20896A
5220A30004A
5220A20001K
2H02479J
5220A90002C
5403A20168B
5416A90015A
5416A90021A
5851A30004A
5901A10033A
6140A90001K
6877A20052A
6877A20052B
6877A20052C
6877A20050F
6877A20050G
6877A20050H
6877A20050J
3A02524F
4995A10101C
5874A90003E
6871A10117D
6871A20484A
2A00986X
2H00660P

SVC CODE
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
Option
R
R

437210

137213

435511

435301

559010

435512

546810-2

546810-1

430410

447910

349600

566000

552113

35211A

W0CCZ-2

237200

554160-1

669200

658740

552203-1

554160-2

552116

554031-1

546810-1

W0CCZ-1

668711

552203-2
552115-2

554031-2

649950

552115-1

437212

561411

552113

352112

552112

55211G

552102

263230-3

263230-2

263230-1

558511

Exploded View & Replacement Parts List

A6UW406FA0

Service Manual 253

Exploded View & Replacement Parts List


Parts List (A6UW406FA0 - TPS Inverter)
Part No.
Location No.

Description

137213
263230-1
263230-2
263230-3
35211A
352112
430410
435301
435511
435512
437210
437212
447910
546810-1
546810-2
548490
552102
552112
552113
552115-1
552115-2
552116
552203-1
552203-2
554031-1
554031-2
554160-1
554160-2
558511
559010
561411
566000
649950
658740
668711
668713
669200
W0CZZ-1
W0CZZ-2
349600
237200
649950
55211G

PANEL ASSEMBLY SIDE


THERMISTOR ASSEMBLY (ROOM, COND OUT)
THERMISTOR ASSEMBLY (DISCHARGE SUCTION)
THERMISTOR ASSEMBLY (DISCHARGE CONSTANT)
TUBE ASSEMBLY, SUCTION (INDOOR)
TUBE ASSEMBLY, COUPLING
BASE ASSEMBLY, WELD
GRILLE, DISCHARGE
COVER ASSEMBLY, CONTROL
COVER ASSEMBLY, TOP
PANEL ASSEMBLY, FRONT SUB
PANEL ASSEMBLY, REAR
BARRIER ASSEMBLY, OUTDOOR
MOTOR ASSEMBLY, OUTDOOR
MOTOR ASSEMBLY, OUTDOOR
ACCUMULATOR ASSEMBLY
TUBE ASSEMBLY, EXPANSION
TUBE ASSEMBLY, CAPILLARY
TUBE ASSEMBLY, CONDENSER OUT
TUBE ASSEMBL, MANIFOLD(OUTDOOR) 19.05
TUBE ASSEMBL, MANIFOLD(OUTDOOR) 9.52
TUBE ASSEMBLY, REVERSING
VALVE, SERVICE (19, 05)
VALVE, SERVICE (9, 52)
CONDENSER ASSEMBLY, BENT
CONDENSER ASSEMBLY, BENT
COMPRESSOR SET (INVERTER)
COMPRESSOR SET (CONSTANT)
DRIER ASSEMBLY
FAN ASSEMBLY, PROPELLER
COIL ASSEMBLY, EXPANSION
SWITCH, PRESSURE
CONTROL BOX ASSEMBLY, OUTDOOR
REACTOR
PWB(PCB) ASSEMBLY, MAIN(OUTDOOR)
PWB(PCB) ASSEMBLY, SUB (CENTRAL CONTROL)
RELAY
CAPACITOR, DRAWING (FAN)
CAPACITOR, DRAWING (COMP)
BRACKET, MOTOR
PANEL CONTROL
CASE ASSEMBLY, CONTROL(OUTDOOR)
TUBE ASSEMBLY EXPANSION

254 Multi type Air Conditioner

A6UW406FA0
3721A20229A
6323A20020H
6323A20020J
6323A20020K
5211A21187A
5211A10433A
3041A20047K
3530AP1225D
3A01293X
3550AP1213B
3720AP1212B
3720AP1202C
4791A20012E
4681A20028J
4681A20028Q
4849A10003E
5211A22013A
5211A10430A
5211A23015A
5211A22018A
5211A22018B
5211A21188A
2A00499L
5220A20001E
5403A20166J
5403A20116K
5416A90015A
5416A90017A
5851A20002A
5901A10032A
6141A30003M
3A02524F
4995A10118A
5874A90003A
6871A10117E
6871A20484A
6920AP3400A
2A00986D
2A00986A
4960A10004A
3720A10074C
4995A10118A
5211A10434A

SVC CODE
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
OPTION
R
R
R
R
R
R
R

March, 2006
Printed in Korea
P/No.: 3828A20097W