INTRODUCTION
II.
225
2009 ACEEE
Transformer
deenergized
at this point
Transformer
reenergized at
this point
(a)
(b)
Fig.1. Energization (a) without inrush (b) with inrush
A. Fuse Protection:
Fuses are economical, require less maintenance, and
do not need external power supply. Fuses can protect some
power transformer against damage from primary and
secondary faults. Fuses are insensitive and relatively slow
except at higher current levels. It does not sense low level
faults.
In case of fault current magnitude is extremely high; a
fuse can be faster than a circuit breaker and can clear the
fault within 0.5 to 2 cycles. For fused transformer
protection, it is recommended to implement phase and
ground over current relays with a low side circuit breaker.
This is to provide back-up protection of secondary faults.
B. Differential Protection:
It compares currents entering and leaving the protected
zone and operates when the differential current exceeds
the predetermined value. The type of differential scheme
normally applied to a transformer is called the current
balance or circulating current scheme.
The CTs are connected in series and the secondary
current circulates between them as in fig. 2 (a). In case of
internal fault, the relay operates since both the CT
secondary currents add up and passes through the relay as
represented in fig. 2(b).
226
2009 ACEEE
Transformer
reenergized at
this point
CT 1
CT 2
A2
A1
a1
a2
Fault
(a)
CT 1
BW
BW
CT 2
C
Fault
(b)
Fig.2. (a) Differential connection for single phase transformer
(b) Differential relay operation for internal fault
227
2009 ACEEE
R
R
D. Overfluxing Protection:
The increase in input voltage increases the level of
working flux. This results in increasing magnetizing and
iron current. The core and core belt get heated leads to
weaken the interlamination insulation and core belt
insulation. Also, the same effect is observed in case of
reduction in supply frequency. In such cases V/f relays are
used to detect over fluxing in transformer. This
phenomenon is more in generator transformers. For 50 Hz
AC supply, setting of relay should be 1.0 to 1.3 on 110 V.
The relay is provided adjustable time delay so as to
prevent transient operation due to momentary
disturbances. The transformer over fluxing protection is
implemented for both sides of interconnecting transformer.
This is to cover all possible operating conditions. For other
transformers, over fluxing relay should be provided on the
untapped winding of transformer.
The requirement of over fluxing protection:
i) Phase to phase connection
ii) Operation on voltage to frequency ratio
iii) High resetting ration of 98 % or more
iv) Inverse time characteristics compatible with
transformer over fluxing
v) Independent alarm with definite time delay at value
voltage to frequency between 100-130%
a1
I OL
RCL
a2
I OL
I OL
Phase
Relays
3 IOL /
R
51
R
87
3 IOL /
R
228
2009 ACEEE
115 kV
50/51
P,N,Q
400:5
52
400:5
52
52
18/24/30
MVA
400:5
RG
400A
20
10 Sec
RG
51G
87N
Trip Dir
51
P.Q,N
Partial
Differential
2000:5
Bus BU
67/51
P,Q,N
32
52
E
Short
Turn
52
27 P,
59P/N,
47
L
O
A
D
2000:5
51
P.Q,N
Bus Tie
52
13.8 kV
2000:5
F1
F2
F3
F4
J. Thermal Protection
The conventional thermal relays measure the oil
temperature and transformer current to calculate hot-spot
temperature. It is usually supplied as a part of transformer.
It is used for monitoring and alarm, but may be used for
tripping.
K . Gas Detection:
Gas detection devices can be applied only to the
transformer units built with conservator tanks. A gas
accumulator device commonly known as Buchholz relay is
connected between the main and conservator tanks.
Failure of winding insulation will result in some form of
arcing. It collects any gas rising through oil. It decomposes
the oil into hydrogen, acetylene, methane. It can detect the
core fault. The intense localized heat damages the winding
insulation. Localized heating can also precipitate a
breakdown of oil into gas.
One part of this device accumulates gas over a time
period and provides sensitive indication of low energy
arcs. It is used for alarm. The other part of this device
229
2009 ACEEE
Auto Tap
Changer
87R
87U
230
2009 ACEEE