Journal of Civil Engineering and Architecture, ISSN 1934-7359, USA
DAVID
PUBLISHING
1. Background
A construction claim and follow-on lawsuit was
filed by a homeowner in a city located in the Rocky
Mountain region of the U.S. The homeowner claimed
that nearby construction dewatering resulted in ground
settlement of the residence and consequential damage
to the house.
The description provided herein focuses on technical
details of the lawsuit and the seemingly disparate and
incongruous conclusions provided by experts involved
with the case. The plaintiff in this case was the
homeowner of the subject residence. The defendants of
the lawsuit included the project owner, the general
contractor, the lead civil engineer/designer of the
project, and the geotechnical firm that was hired by the
lead civil firm to conduct an investigation in support of
the design. For privacy reasons, names of specific
Corresponding author: Robert L. Mokwa, associate
research field: civil engineering. E-mail:
Rmokwa@ce.montana.edu.
professor,
A Case Study on Construction Dewatering-Induced Settlement Damage: Could This Have Been Avoided? 671
672 A Case Study on Construction Dewatering-Induced Settlement Damage: Could This Have Been Avoided?
house
50 '
.
pre-construction groundwater level
SPT N-Value
10
20
30
Undrained Shear
Strength (psf)
10
20
30
40
10
10
10
15
15
15
20
20
20
25
25
25
30
30
30
35
35
35
40
40
40
45
45
45
50
50
50
55
55
55
60
60
0
10
20
30
40
2000
4000
2000
4000
60
0
10
ST-1A
ST-2
ST-3
ST-4
ST-5
20
30
ST-1A
ST-2
ST-3
ST-4
ST-5
40
Pocket Penetrometer
ST-1A
ST-2
ST-3
ST-4
ST-5
A Case Study on Construction Dewatering-Induced Settlement Damage: Could This Have Been Avoided? 673
0.0 ft
6.5 ft
15
(3) Lean Clay (CL)
16.0 ft
18.5 ft
20
25
10
15
20
25
30
30
32.5 ft
35
35
(5) Silt with Sand to Silty Sand (ML, SM)
40
40
42.5 ft
45
45
47.5 ft
50
50
(7) Poorly Graded Gravel (GP)
55
55
60
60
674 A Case Study on Construction Dewatering-Induced Settlement Damage: Could This Have Been Avoided?
cv (in2/min x 100)
10
20
30
40
Su/'vo
50
10
10
15
15
20
20
25
25
30
30
35
35
40
40
45
45
50
50
lab oedometer data
assumed distribution
55
55
60
60
0
10
20
30
40
50
A Case Study on Construction Dewatering-Induced Settlement Damage: Could This Have Been Avoided? 675
4.0
Settlement (inches)
3.5
3.0
2.5
2.0
1.5
1.0
Constant groundwater drop of 12 ft (steady state condition)
Groundwater drop accounting for drawdown and recovery
0.5
0.0
0
100
200
300
400
500
Time (days)
Fig. 5 Calculated settlement assuming soil is normally consolidated.
600
700
800
676 A Case Study on Construction Dewatering-Induced Settlement Damage: Could This Have Been Avoided?
4. Summary
As with any analysis that involves approximations
and assumptions, there is seldom a single absolute
A Case Study on Construction Dewatering-Induced Settlement Damage: Could This Have Been Avoided? 677
5. Conclusions
Based on analyses of soil data from the site, it can
reasonably be concluded that anywhere from one to
three inches of settlement could have occurred during
the construction dewatering operation. Based on
conventionally accepted engineering methods, the
margin of error in the settlement estimates provided by
the defendants could easily exceed one inch.
678 A Case Study on Construction Dewatering-Induced Settlement Damage: Could This Have Been Avoided?
References