Professional Documents
Culture Documents
By Vinay Rai
Technology Conclave at STC Vadodara
11th & 12th July 2014
Earthing Fundamentals
What is Earthing ?
Earthing : Fundamentals
Vinay Rai
Slide 3
Safety of Property/Installation
Safety of Power System
Earthing : Fundamentals
Vinay Rai
Slide 4
Types of Earthing
System Earthing
Equipment Earthing
Lightning Protection Earthing
Static Earthing
Earthing : Fundamentals
Vinay Rai
Slide 5
As per IS : 3043
Definition
L1
L2
L3
N
Rn
Earthing : Fundamentals
Vinay Rai
Slide 6
As per IS : 3043
Definition
L1
L2
L3
N
Rn
Earthing : Fundamentals
Vinay Rai
PE
RA
Slide 7
Earthing : Fundamentals
Vinay Rai
Slide 8
Resistance Earthing
Inductance Earthing
Earthing : Fundamentals
Vinay Rai
Slide 10
Vinay Rai
Slide 11
Earthing : Fundamentals
Vinay Rai
Slide 12
Earthing : Fundamentals
Vinay Rai
Slide 13
Equipotential Bonding
No bonding - Unsafe
Earthing : Fundamentals
Vinay Rai
Slide 14
IS : 3043
Earthing of all the exposed conductive parts of electrical
equipment and all accessible conductive parts
Simultaneously accessible exposed and extraneous
conductive parts must be connected to the same earth
electrode/earth grid.
Earthing : Fundamentals
Vinay Rai
Slide 15
No Equipotential Bonding
L1 L2 L3
Earthing : Fundamentals
L1 L2 L3
Vinay Rai
Slide 16
Earthing : Fundamentals
Vinay Rai
Slide 17
Network Classification
TT System
IT System
Earthing : Fundamentals
Vinay Rai
Slide 19
TN-S System
Earthing : Fundamentals
Vinay Rai
Slide 20
TN-C System
Earthing : Fundamentals
Vinay Rai
Slide 21
TN-C-S System
Earthing : Fundamentals
Vinay Rai
Slide 22
TT System
Earthing : Fundamentals
Vinay Rai
Slide 23
IT System
Earthing : Fundamentals
Vinay Rai
Slide 24
SCPD
100 A
415V / 240V
L1
L2
L3
N
Exposed conductive
metallic part
Rc
1000
Id = 34.3A
Ud
Load
Rn =Rn
2
2
Earthing : Fundamentals
RA
5
RA = 5
Vinay Rai
Uc = 171 V
Uc = 171 V
Slide 25
415V / 240V
L1
L2
L3
N
PE
SCPD 100 A
Id = 3850A
ZS= 50m
Exposed
conductive
metallic part
Uc
Fault
Load
Uc = Uc
120=V120 V
Rn = 2
Rn
Earthing : Fundamentals
Vinay Rai
Slide 26
Vinay Rai
Slide 28
Earthing : Fundamentals
Vinay Rai
Slide 29
Earthing : Fundamentals
Vinay Rai
Slide 30
Equipment Earthing
not exceeding 5 Ohms (as per NEC)
Static Earthing
even 20 Ohms can achieve objective (as per IS 7689)
Earthing : Fundamentals
Vinay Rai
Slide 31
Earthing Of Electronic
Equipments
Vinay Rai
Slide 33
Basic Issues
1) Susceptible to random voltages far below the
levels that are perceptible to humans & that
have no effect on electrical power equipment
(even the static voltage charges generated by
lightning strokes within several thousand feet
can cause damage).
Vinay Rai
Slide 34
Basic Issues
2) Problem of noise coupling (capacitive &
inductive) between signal circuits & power
circuits.
Vinay Rai
Slide 35
Basic Issues
3) Impedance considerations related to the
power frequency safety aspects of an earthing
system may not necessarily provide the desirable
low impedance at the high frequency signals.
Vinay Rai
Slide 36
Basic Issues
4) Several elements at different locations, but
linked by a data cable that carries its own zero
reference - a conductor linking the earthing
connections at different locations. Under certain
conditions substantial differences can exist
between distant elements of the system leading to component failures.
Vinay Rai
Slide 37
Earthing Methods
1) Multiple Earthing Connections
# In a commercial/non-industrial building it is
not unusual to find neutral connected to
earth/panel enclosures at more than one
location.
Vinay Rai
Slide 38
Vinay Rai
Slide 39
Earthing Methods
Vinay Rai
Slide 40
Earthing Methods
2) Separate/Isolated Earthing Connection
# To earth computers to isolated earthing
electrodes separate from the power system
earthing electrode system.
Vinay Rai
Slide 41
Isolated Earthing
Building Steel/Power
System Earthing
10 KA Stroke to
building
Building to Computer
Capacitance
1 Ohm
10 KV
Earthing of Sensitive Electronic Equipment
Vinay Rai
Slide 42
Isolated Earthing
Computer Modules
32A CB
Earth Fault
415V/240V
5 Ohm
5 Ohm
Isolated Earthing
IF
IF = 240/10 = 24A
Earthing of Sensitive Electronic Equipment
Vinay Rai
Slide 43
Isolated Earthing
Large voltages impressed on computer
components under thunderstorm conditions
(direct strike or charge induced because of
clouds overhead).
With isolated earthing, a fault in a computer
requires fault current to pass thru the
resistance of both the isolated & power system
ground in series. In this case the current would
be insufficient to operate the protective device.
Earthing of Sensitive Electronic Equipment
Vinay Rai
Slide 44
As per IS 3043
Vide Cl. 39.4.1 :
Whatever measures are taken to provide a lownoise earthing connection, it is required that
exposed conductive parts of data processing shall
be connected to the main earthing terminal.
Vinay Rai
Slide 45
Vinay Rai
Slide 46
Earthing Methods
2) Separate/Isolated Earthing Connection
While continuous low-level noise are eliminated,
other catastrophic incidents are encountered.
Since unsafe, therefore Isolated Earthing for
Sensitive
Electronic
Equipment is
not
recommended (and in fact not permitted).
Vinay Rai
Slide 47
Earthing Methods
3) Single Point Earthing Connection
# To prevent stray/circulating currents from
affecting the computer signals & operations, it is
necessary to keep the computer ground system
separate
from
the
equipment
ground
components & connect together at only one
point.
Vinay Rai
Slide 48
Vinay Rai
Slide 49
Earthing Methods
3) Single Point Earthing Connection
Recommended method, as it eliminates problems
of earlier two methods.
Vinay Rai
Slide 50
Vinay Rai
Slide 51
This approach has been found satisfactory & is suitable for safety (at power
frequencies); it is generally not suitable for high-frequency EMC concerns.
Vinay Rai
Slide 52
Vinay Rai
Slide 53
Vinay Rai
Slide 54
Vinay Rai
Slide 55
Earthing Methods
4) Single Point Earthing Connection
Connection with Grid in the Floor
plus
Vinay Rai
Slide 56
Vinay Rai
Slide 57
It is the recommended approach in the general case, for safety as well as for EMC.
Vinay Rai
Slide 58
Vinay Rai
Slide 59
Case Histories
Case 1 :
Vinay Rai
Slide 61
Case 1 :
The earthing conductors of all the computers in
the building were connected to isolated earthing
electrode system (consisted of 6 rods driven into
the earth away from building).
The computer manufacturer was persuaded to
permit earthing of the computer system to the
building earthing system, which had concrete
encased earthing electrodes. Immediately the
erratic operations ceased.
Earthing of Sensitive Electronic Equipment
Vinay Rai
Slide 62
Case 2 :
Vinay Rai
Slide 63
Case 2 :
In the installation of a multistory office building,
several floors of modular workstations were
powered from a common, 3 phase step down
transformer with a shared neutral. Mainframe
terminals in these workstations experienced
intermittent data memory errors & data
transmission errors, & occasionally hardware
failures.
It was found that considerable (& variable) neutral
current existed. RMS values of N to earth didnt
exceed 3.7V, but the peak voltage ranged up to
10V.
Earthing of Sensitive Electronic Equipment
Vinay Rai
Slide 64
Case 2 :
Each floor of the building was isolated into 2
sections via shielded isolation transformers.
Individual N conductors were installed for all
workstation branch circuits.
Re-establishment of the N-E bond at the new
isolation transformers, combined with the
reduced neutral current in the dedicated
neutrals, reduced N-E voltage to less than 2V.
The problem was solved.
Earthing of Sensitive Electronic Equipment
Vinay Rai
Slide 65
Case 2 :
Vinay Rai
Slide 66
Thank You
Contact
Vinay Rai
Sr. Deputy General Manager
Electrical Standard Products
Larsen & Toubro Limited
32 Shivaji Marg
Near Moti Nagar
New Delhi 110015
Tel: +91-11-41419590
Mob: +91-8860476555
Email: vinay.rai@LNTEBG.com
References
IS 3043 1987: CODE OF PRACTICE FOR EARTHING