Zelio Control-modular measurement


and control relays

Level control relays RM35 L

Presentation
105685

Level control relays RM35 LM33MW and RM35 LV14MW control one or two levels,
with fill or empty function:
2 RM35 LM33MW: control by resistive level probe,
2 RM35 LV14MW: control by discrete sensor.
Settings are protected by a sealable cover.
Control status is indicated by a LED.
The relays are designed for clip-on mounting on 4 rail
Applications
These devices monitor the levels of conductive liquid or non-conductive material.
They control the actuation of pumps or valves to regulate levels. They are also
suitable for protecting submersible pumps against dry running, or protecting tanks
from "overflow". They can also be used to control dosing of liquids in mixing
processes and to protect heating elements in the event of non immersion.
They have a transparent, hinged cover on their front panel to avoid any accidental
alteration of the settings. This cover can be directly sealed.

RM35 L111MW

2
5
5
5
5
5

Application examples for RM35 LM33MW:


spring, town, industrial and sea water,
metallic salt, acid or base solutions,
liquid fertilizers,
non concentrated alcohol (< 40 %),
liquids in the food-processing industry: milk, beer, coffee, etc.

2
5
5
5
5

Application examples for RM35 LV14MW:


chemically pure water,
fuels, liquid gasses (inflammable),
oil, concentrated alcohol (> 40 %),
ethylene, glycol, paraffin, varnish and paints.

Description
RM35 LM33MW
A1 A2

Min Max C

Tt
Un

1
2
3
4

1 Configuration: selection of operating


mode:
/
and of sensitivity
range. LS, St, HS.
2 Sensitivity adjustment potentiometer. %
3 Switch for selecting the number of levels.
4 Time delay adjustment potentiometer. Tt
5 Spring for clip-on mounting on 35 mm
4 rail.

12 11 14 22 21 24

5
RM35 LV14MW
12V12V Min Max 0V

Tt

1
2
3

Un

1 Configuration: selection of operating


mode:
/
and of sensor type
PNP, NPN.
2 Time delay adjustment potentiometer. Tt
3 Switch for selecting the number of levels.
4 Spring for clip-on mounting on 35 mm
4 rail.

A1 A2

12 11 14

4
Tt Yellow LED: indicates timing status.
Un Green LED: indicates that supply to the relay is on.
R Yellow LED: indicates relay output state.

Operation:
pages 53 to 55

52

Characteristics:
pages 56 and 57

References, dimensions :
page 57

Operation

Zelio Control-modular measurement


and control relays
Level control relays RM35 L

Operating principle
Control relays RM35 LM and RM35 LV are designed to control levels of:
2 Conductive liquid for RM35 LM,
2 Any other material for RM35 LV.
Relay RM35 LM measures the levels by means of resistive probes.
Relay RM35 LM controls the levels of conductive liquids.
The operating principle is based on measurement of the apparent resistance of the
liquid between two submerged probes. When this value is less than the threshold
setting on the front panel of the device, the relay changes state. To avoid electrolytic
phenomena, an a.c. current runs across the probes. A selector switch on the front
panel allows selection of the required function and sensitivity range. Control of one
single level can be achieved by using the 2nd selector switch.
In this case, the Max level probe stays up in the air and an adjustable time delay
avoids any wave effect.
Relay RM35 LV measures the levels by means of discrete sensors.
These two products activate their output relay when a tank is either emptying or
filling.
A green LED indicates that the supply is ON.
A yellow LED indicates the state of the output relay.
A yellow LED indicates that timing is in progress.
The green and yellow LEDs flash to indicate an unacceptable setting position.
Level control relay: RM35 LM33MW
Configuration
A selector switch on the front panel allows selection of the required sensitivity range
and of the empty or fill function.
A second switch allows selection of the number of levels (1 or 2) and the type of time
delay in the case of 1 level mode.
The configuration of these switches is taken into account on energisation.
If the switch is set to an unacceptable position, the product detects a fault, the output
relay stays open and the LEDs flash to signal the position error.
If the switch position is changed while the device is operating, all the LEDs flash, but
the product continues to operate normally with the function selected at the time of
energisation preceding the change of position.
The LED's return to their normal state if the switch is returned to the original position
selected prior to the last energisation.

2 Control of two levels


5 empty function

Function diagram

2 Fill/Empty function

level: 2, function:
LS (Low Sensitivity: 250 5 k),
St (Standard Sensitivity: 5 k100 k),
HS (High Sensitivity: 50 k1 M).
The output relay stays open until the liquid reaches the Max. level probe. As soon
as the Max. level is reached, the contact closes and then allows emptying of the tank
(valve opens, pump starts, ...). When the level drops below the Min. level, the
contact opens to stop the emptying process.

Supply Un
Max. level
Min. level
Relays

11-12/11-14
21-22/21-24

Relays

11-12/11-14
21-22/21-24

Note: When two levels are controlled, the anti-wave time delay function is not active.

5 fill function
level: 2, function:
LS (Low Sensitivity: 250 5 k),
St (Standard Sensitivity: 5 k100 k),
HS (High Sensitivity: 50 k1 M).
The output relay stays energised until the liquid reaches the Max. level probe. As
soon as the Max. level is reached, the contact opens and the pump stops. When the
level drops below the Min. level, the contact closes again and pumping re-starts to
raise the level.
Note: When two levels are controlled, the anti-wave time delay function is not active.

Presentation, description :
page 52

Characteristics:
pages 56 and 57

References, dimensions :
page 57

53

Operation (continued)

Zelio Control-modular measurement


and control relays
Level control relays RM35 L

Level control relay: RM35 LM33MW (continued)


Configuration (continued)
2 Control of one level, empty function
5 level: 1 - on delay functions:
LS (Low Sensitivity: 250 5 k),
St (Standard Sensitivity: 5 k100 k),
HS (High Sensitivity: 50 k1 M).

Function diagrams

2 Empty function T on
Supply Un
Level

Relays

When the liquid level rises above the probe for a time greater than the time delay
value Tt set on the front panel, the relay is energised and stays energised until the
liquid level drops back down to the probe.
If the liquid drops back down to below the set level before the end of the time delay,
the relay does not energise.

11-12/11-14
21-22/21-24

Tt

Tt

Tt

2 Empty function T off

5 level: 1 - off delay functions:


-

Supply Un
Level

Relays

11-12/11-14
21-22/21-24

Tt

Tt

Tt

Tt

Supply Un
Level

Tt

Tt

2 Fill function T off

5 level: 1 - off delay functions:


-

Supply Un
Level
11-12/11-14
21-22/21-24

Tt

Presentation, description :
page 52

54

LS (Low Sensitivity: 250 5 k),


St (Standard Sensitivity: 5 k100 k),
HS (High Sensitivity: 50 k1 M).

When the liquid level drops below the probe for a time greater than the time delay
value Tt set on the front panel, the relay is energised and stays energised until the
liquid level rises back up to the probe.
If the liquid rises back up to above the set level before the end of the time delay
period, the relay does not energise.

11-12/11-14
21-22/21-24

Tt

Relays

When the liquid level rises above the probe, the relay instantly energises and stays
energised until the liquid again reaches the probe level for a time Tt set on the front
panel.
If the liquid drops back down to below the set level before the end of the time delay
period, the relay stays energised.

2 Control of one level, fill function


5 level: 1 - on delay functions:

2 Fill function T on

Relays

LS (Low Sensitivity: 250 5 k),


St (Standard Sensitivity: 5 k100 k),
HS (High Sensitivity: 50 k1 M).

Tt

Characteristics:
pages 56 and 57

Tt

LS (Low Sensitivity: 250 5 k),


St (Standard Sensitivity: 5 k100 k),
HS (High Sensitivity: 50 k1 M).

When the liquid level drops below the probe, the relay instantly energises and stays
energised until the liquid level again reaches the probe level and stays above it for
a time greater than the time delay period Tt set on the front panel.
If the liquid drops back down to below the set level before the end of the time delay
period, the relay stays energised.

References, dimensions :
page 57

Operation (continued)

Zelio Control-modular measurement


and control relays
Level control relays RM35 L

Level control relay: RM35 LV14MW


Configuration
A selector switch on the front panel allows selection of the function (empty or fill) and
the type of sensor.
A second switch allows selection of the number of levels (1 or 2) and the type of time
delay in the case of 1 level mode.
The configuration of these switches is taken into account on energisation.
If the switch is set to an unacceptable position, the product detects a fault, the output
relay stays open and the LEDs flash to signal the position error.
If the switch position is changed while the device is operating, all the LEDs flash, but
the product continues to operate normally with the function selected at the time of
energisation preceding the change of position.
The LED's return to their normal state if the switch is returned to the original position
selected prior to the last energisation.

2 Control of two levels

Function diagram

56Fill/Empty function

5 empty function. Level: 2


The output relay stays open until the material level reaches the Max. probe. As soon
as the Max. level is reached, the contact closes and then allows emptying of the tank
(valve opens, pump starts, ...). When the level drops below the Min. probe, the
contact opens to stop the emptying process.

Supply Un
Max. level
Min. level
Relays

11-12/11-14

Relays

11-12/11-14

5 fill function. Level: 2


The output relay stays energised until the material level reaches the Max. probe. As
soon as the Max. level is reached, the contact opens and the pump stops. When the
level drops below the Min. probe, the contact closes again and pumping re-starts to
raise the level.
Note: When two levels are controlled, the anti-wave time delay function is not active.

2 Control of one level, empty function

Function diagrams

56Empty function T on

5 level: 1 - on delay
When the material level rises above the probe for a time greater than the time delay
value Tt set on the front panel, the relay is energised and stays energised until the
material level drops back down to the probe.
If the level rises above the probe before the end of the time delay period, the relay
does not energise.

Supply Un
Level
Relays

11-12/11-14

Tt

Tt

Tt

56Empty function T off

5 level: 1 - off delay


When the material level rises above the probe, the relay instantly energises and
stays energised until the material level again reaches the probe and stays below it
for a time greater than the time delay value Tt set on the front panel.
If the level drops back down to below the probe before the end of the time delay
period, the relay stays energised.

Supply Un
Level

Relays

11-12/11-14

Tt

Tt

Tt

Tt

2 Control of one level, fill function

56Fill function T on

5 level: 1 - on delay
When the material level drops below the probe for a time greater than the time delay
value Tt set on the front panel, the relay is energised and stays energised until the
material level again reaches the probe.
If the level rises above the probe before the end of the time delay period, the relay
does not energise.

Supply Un
Level

Relays

11-12/11-14

Tt

Tt

Tt

5 Fill function T off

5 level: 1 - off delay


When the material level drops below the probe, the relay instantly energises and
stays energised until the material level again reaches the probe and stays above it
for a time greater than the time delay period Tt set on the front panel.
If the level drops back down to below the probe before the end of the time delay
period, the relay stays energised.

Supply Un
Level

Relays

11-12/11-14

Tt

Presentation, description :
page 52

Tt

Characteristics:
pages 56 and 57

Tt

References, dimensions :
page 57

55

Characteristics

Zelio Control-modular measurement


and control relays
Level control relays RM35 L

Environment characteristics
Conforming to standards
Product certifications
Marking
Ambient air temperature
around the device

Storage
Operation

Permissible relative humidity


Vibration resistance
Shock resistance
Degree of protection
Conforming to IEC 60529

Conforming to IEC 60068-2-30


Conforming to IEC 60068-2-6
Conforming to IEC 60068-2-6
Casing
Terminals

2 x 24 hours+ 95 % RH at + 55 C (without condensation)


0.035 mm from 10150 Hz
5 gn
IP 30
IP 20

Degree of pollution
Overvoltage category
Insulation resistance
Rated insulation voltage
Insulation test voltage
Conforming to
IEC 60664-1/60255-5

Conforming to IEC 60664-1


Conforming to IEC 60664-1
Conforming to 60664-1/60255-5
V
Conforming to IEC 60664-1
kV
Dielectric test
kV
Shock wave

3
III
> 500 M,
500 V
250
2,
50 Hz, 1 min.
4 (1.2/50 s)

Connection
Maximum c.s.a.
Conforming to IEC 60947-1

Solid cable without cable end

mm2

Flexible cable with cable end

mm2

Tightening torque
Housing material
Power ON indicator
Relay state indicator
Timing indicator
Mounting position
without derating
Mounting

Pending
C
C

Conforming to IEC 60947-1

In relation to normal
vertical mounting plane
Conforming to IEC/EN 60715

Immunity to microbreaks

1 conductor: 0.54 (AWG 20AWG 11)


2 conductors: 0.52.5 (AWG 20AWG 14)
1 conductor: 0.22.5 (AWG 24AWG 12)
2 conductors: 0.21.5 (AWG 24AWG 16)
0.61N.m / 5.38.8 Lbf.In
Self-extinguishing plastic
Green LED
Yellow LED
Yellow LED
Any position
On

Supply characteristics
Supply voltage Un
Operating range
Voltage limits
Of the power supply circuit
Frequency
Of the power supply circuit
Galvanic isolation, supply/measurement
Maximum power consumption at Un

NF EN 60255-6 and IEC 60255-6


UL, CSA, GL, C-Tick, GOST
: 73/23/EEC and EMC 89/336/EEC
- 40+ 70
- 20+ 50

V
V

VA
W
ms

4 rail

1/2 24240
1/2 20.4264

- 15 %, + 10 %
50/60 Hz 10 %
Yes
5
1.5
90,
100

13
2
1 2

Immunity to electromagnetic interference


Electromagnetic compatibility

Immunity NF EN 61000-6-2 2002 / IEC 61000-6-2


Emission NF EN 61000-6-4
NF EN 61000-6-3
IEC 61000-6-4
IEC 61000-6-3

Measurement circuit and input characteristics


Relay type
Measurement range
Sub-measurement range

Sensitivity adjustment
Setting accuracy
Measurement error with temperature variation
Maximum voltage at the probe terminals
Maximum current across the probes
Maximum probe cable length
Maximum capacity of probe cable

V
mA
m
nF

RM35 LM33MW
RM35 LV14MW
250 1 M

250 5 k

5 k100 k

50 k1 M

5100 % of the range

10 % of the full scale / 20 % for the HS range


0.5 % / C
12
<1
40
100
100
1 for LS, 2.2 for St and 4.7 pour HS
10

Delay on pick-up

ms

600

Presentation, description :
page 52

56

LS
St
HS

Operation:
pages 53 to 55

References, dimensions :
page 57

500

Characteristics (continued)
references,
dimensions,
schemes

Zelio Control-modular measurement


and control relays

Level control relays RM35 L


1

Time delay characteristics


Relay type
Time delay on crossing the threshold
Repeat accuracy (with constant parameters)
Reset time

RM35 LM33MW
0.15, 0 + 10 %
2%
1.75

s
s

RM35 LV14MW

4 if 1 line broken /
1 if 2 lines broken

Output characteristics
Type of output
Contact type
Nominal current
Maximum switching voltage
Rated breaking capacity
Minimum breaking current
Maximum breaking current
Electrical durability
Mechanical durability
Maximum operating rate
Utilisation categories

2 C/O contacts
1 C/O contact
Cadmium-free
5
/ 250
1250
10/
5V
/ 5
1 x 105 operating cycles
30 x 106 operating cycles
360 operations/hour under full load
AC-12, AC-13, AC-14, AC-15, DC-12, DC-13

A
V
VA
mA
A

12
2
12

Conforming to IEC 60947-5-1

References

105686

12

Detection by
resistive probes
(see page 58)

1/2 24240

Detection by
discrete sensors
(see page 60)

RM35 LV14MW

Dimensions

Schemes

RM35 LM33MW, RM35 LV14MW

RM35 LM33MW

Output

Reference

Weight

2 C/O
5A

RM35 LM33MW

kg
0.130

1 C/O
5A

RM35 LV14MW

0.130

RM35 LV14MW

35/1.38

14

22

NC 12V 12V Min Max

21

24

A2

12

11

14

12
A1

0V

11

A2

A1

11

11

A2

12

Min Max

12

A1

A2

14

2,8
0.11

90/3.54

A1

14
22

72/2.83

21

RM35 LM33MW

Supply
voltage
V
/ 24240

24

105685

Function

76/2.99
72,5/2.85

mm/In.

Presentation, description :
page 52

Operation:
pages 53 to 55

Characteristics:
pages 56 and 57

57

References

Zelio Control-modular measurement


and control relays

Electrode holders and probes

Probes
Application

No.
Length
of
probes

Recommended
3
for drinks vending
machines and
where installation
space is limited
(Stainless steel)

1
Suitable for
boilers, pressure
vessels and under
high temperature
conditions (1)
(304 stainless
steel)

mm
1000

Operating
temperature
C
80

kg/cm2
2

RM 79 696 044

kg
0.800

1000

200

25

RM 79 696 014

0.360

561034

Description
Protected probe
for mounting by suspension

RM 79 696 043

Description

Type of
installation

Liquid level
control probe

Suspended
by cable

Maximum
pressure

Reference

Weight

Material

Reference

Protective shell
PUC (S7)
Electrode : stainless
steel

RM 79 696 043

Weight
kg
0.150

Maximum operating
temperature
C
100

Reference

Weight

Material

Reference

Stainless steel
isolated by ceramic

RM 79 696 006

kg
0.100

LA9 RM201

LA9 RM201

Electrode holders
561036

561035

Description
Electrode for use up to 350 C
and 15 kg/cm2 (2)

Weight
kg
0.150

(1) 3/8" BSP mounting thread with hexagonal head. Use a 24 mm spanner for tightening.
(2) 3/8" BSP mounting thread.
RM 79 696 006

Dimensions :
page 59

58

Dimensions

Zelio Control-modular measurement


and control relays
Electrode holders and probes

Probes
RM 79 696 044
38,5
32

11

7 12

14

11

PF 1/2

26

100

27,5

RM 79 696 014

G 3/8A

1000

60

60

RM 79 696 043

25

80

16

LA9 RM201

150

Electrode holder

29
13

5/32 whit

6,5

20,7

1/4 whit

84
46

9,5

Across flats

RM 79 696 006

3/8 tapered NPT

49

References :
page 58

59

References

Ultrasonic sensors
Osisonic,

Optimum and Universal

564546

Cylindrical plastic case, M12 x 1, M18 x 1, M30 x 1.5


d.c. supply, solid-state output

Optimum sensors
Sensors

12
XX5212A1KAM8

5664547

532713

18

532243

Function

Output

Reference

NO
NO

0.15

NO

PNP/NPN
NPN
PNP
PNP/NPN

XX5 12A1KAM8
XX5 12A2NAM8
XX5 12A2PAM8
XX5 18A1KAM12

kg
0.011
0.011
0.011
0.033

18

0.50 (adjustable) NO

NPN
PNP

XX5 18A3NAM12
XX5 18A3PAM12

0.033
0.033

30

1 (adjustable)

NO
NO + NC

8 (adjustable)

NO + NC

PNP/NPN
NPN
PNP
NPN
PNP

XX6 30A1KAM12
XX6 30A1NCM12 (1)
XX6 30A1PCM12 (1)
XX6 30A3NCM12
XX6 30A3PCM12

0.091
0.091
0.091
0.110
0.110

XX5218A31AM12

Accessories
Teach mode pushbutton
Teach mode pushbutton

XX6230A1KAM12

Selection of detection window


Input: M12 female connector
Output: M12 male connector
XX6230A31CM12

564530

564533

For use with


sensors
XX5 18A3 7AM12
and XX7 V1A1 7AM12

M8

For use with


sensor
12

Type
Connection by
in-line IDC
Connection to
solder terminals

XZ2CC12FD140B

XXZ PB100

M12

18, 30

Metal
clamping ring
Plastic
clamping ring

564534

Pre-wired
connectors
M8

For use with


sensor
12

Type
Straight

Elbowed

564535

XZ2CP1041L1
M12

18, 30

XSZ B111

Straight

Elbowed

564532

Reference
XXZ PB100

Weight
kg
0.035

Cabling accessories (4-wire output) (3)


Connectors

Reference
Straight
Elbowed
Straight
Elbowed
Straight
Elbowed
Straight
Elbowed
Length
m
2
5
10
2
5
10
2
5
10
2
5
10

XZ CC8FDM40V
XZ CC8FCM40V
XZ CC8FDM40S
XZ CC8FCM40S
XZ CC12FDM40B
XZ CC12FCM40B
XZ CC12FDP40B
XZ CC12FCP40B
Reference
XZ CP0166L2
XZ CP0166L5
XZ CP0166L10
XZ CP0266L2
XZ CP0266L5
XZ CP0266L10
XZ CP1141L2
XZ CP1141L5
XZ CP1141L10
XZ CP1241L2
XZ CP1241L5
XZ CP1241L10

Weight
kg
0.010
0.010
0.010
0.010
0.020
0.020
0.020
0.020
Weight
kg
0.080
0.180
0.360
0.080
0.180
0.360
0.090
0.190
0.370
0.090
0.190
0.370

Fixing accessories
Description
Fixing clamps

XUZ A118
532517

Weight

Universal sensors

564531

XX5218A1KAM12

Sensing
distance (Sn)
m
0.05
0.10

XUZ 2001

90 fixing bracket

XUZ B20

3D fixing kit (2) M12 rod


Support for
M12 rod
Ball-joint
mounted
fixing bracket

3D fixing kit example

60

Reference
XSZ B112
XSZ B118
XXZ 12
XUZ A118
XXZ 30
XUZ 2001
XUZ 2003

Weight
kg
0.006
0.010
0.025
0.038
0.115
0.050
0.160

12
XUZ B2012
0.175
18
XUZ B2003
0.175
30
XUZ B2030
0.160
(1) Sensor available with stainless steel 303 case. To order, replace the 1st letter A by the letter S.
(2) To obtain a 3D fixing kit, order:
rod support XUZ 2003, M12 rod XUZ 2001 and ball-joint mounted fixing bracket XUZ B2011.
(3) For 3-wire cabling accessories, refer to the Global Detection catalogue.

XUZ 2003

Characteristics:
page 61

For use with


sensor
12
18
12
18
30
12, 18 and 30
12, 18 and 30

Dimensions:
page 62

Schemes:
page 63

Characteristics,
setting-up

Ultrasonic sensors
Osisonic,
1

Optimum and Universal

Cylindrical plastic case, M12 x 1, M18 x 1, M30 x 1.5


d.c. supply, solid-state output

Sensor type

XX5
12A12222

Characteristics

XX5
12A22222

XX5
18A1 2222

XX5
18A32222

XX6
30A12222

XX6
30A32222

Product certifications
Conformity to standards
Connection
Sensing range
Nominal sensing distance (Sn)
Operating distance

IEC 60947-5-2, UL508 pending and CSA C22-2 n 14 pending


M8 - 4-pin
M8 - 3-pin
M12 - 4-pin
6.451
6.4102
19152
51508
51991
2038000
0.05
0.1
0.15
0.50
1
8
6.451
6.4102
25152
Adjustable using teach mode
Fixed
Fixed
Fixed
< 0.7
< 0.7
< 0.35
< 2.5
< 2.5
< 12.7
06.4
06.4
019
051
051
0203

Connector
mm
m
mm

Differential travel
Blind zone (no object must pass through this zone whilst the
sensor is operating)
Transmission frequency
Repeat accuracy
Overall beam angle (see detection lobe)
Minimum size of object to be detected

Degree of protection

mm
mm
kHz
mm

500
0.7
11
10
8
Cylinder 2.5 mm or flat bar Cylinder
1 mm wide
1.6 mm

C
C

Case
Sensing face
Vibration resistance
To IEC 60068-2-6
Mechanical shock resistance
To IEC 60068-2-27
Resistance to electromagnetic interference
Electrostatic discharges
To IEC 61000-4-2
Radiated electromagnetic fields
To IEC 61000-4-3
Fast transients
To IEC 61000-4-4
LED indicators
Output state

- 40+ 80
- 20+ 65
0+ 50
ULTEM
Epoxy
Silicone
Amplitude 1 mm (f = 1055 Hz)
30 gn, duration 11 ms, in all 3 axes

kV
V/m
kV

Setting-up assistance

First-up
Response
Recovery

75
2.54
16
Cylinder
50.8 mm
up to a
sensing
distance of
4732 mm

- 20+ 65
Valox
Epoxy

0+ 60
ULTEM
Silicone

- 20+ 60
Epoxy

8, level 4
10, level 3
1, level 3
Yellow LED, Yellow LED
Yellow LED Yellow LED, Yellow LED,
rear
rear
rear
Green LED, Green LED
Green LED

rear

Dual colour Multicolour LED, rear


1224 V with protection against reverse polarity
1028 V
25
60
40
50
< 100 (PNP and NPN) with overload and short-circuit protection
< 1 (PNP and NPN)
125
125
80
40
10
2
20
20
350
100
720
800
2
3
3
10
20
200
2
3
3
10
20
200
10
10
10
7
7
5

Power on

Rated supply voltage


Voltage limits (including ripple)
Current consumption, no-load
Switching capacity
Voltage drop
Maximum switching frequency
Delays

200
0.9
10
Cylinder
1.6 mm
up to a
sensing
distance of
635 mm
IP 65

IP 67

Conforming to IEC 60529


and IEC 60947-5-2

Storage temperature
Operating temperature
Materials

300
1.27
6
Cylinder
2.5 mm
up to a
sensing
distance of
150 mm

2
2

V
V
mA
mA
V
Hz
ms
ms
ms

Deviation angle from 90 of the


object to be detected

Setting-up precautions
Minimum mounting distances
Side by side

e: respect the distances indicated on the


detection curves shown on page 63.

References:
page 60

Dimensions:
page 62

Face to face

e = 4 x Sn max.

Schemes:
page 63

61

Dimensions

Ultrasonic sensors
Osisonic,

Optimum and Universal

Cylindrical plastic case, M12 x 1, M18 x 1, M30 x 1.5


d.c. supply, solid-state output

Dimensions
XX5 12A22AM8

XX5 18A37AM12

XX5 18A1KAM12

M18x1

M12x1

38

M18x1

43

51

50
XXZ PB100

XX6 30A32CM12

XX6 30A1KAM12

63

M12x1

M30x1,5

43,2

M30x1,5

20

(1)

4,7

77,7

65

14,5

16
45

64,3

20

85

(1) Cable, length: 152.4 mm.

42,1

117,35

Accessories
XUZ A118
90 fixing bracket ( 18)
2,5

XXZ 12, XXZ 30


90 fixing bracket ( 12 and 30)
G

18,2

50

c1

10
5

35

28

15

16,5

XXZ
12
30

20

a
35
67

b
40
65

c
33
52

c1
18
25

e
2
3

H
31
51

G
18
35

G1
18
33

25
50

40
12

19

126

132

55

a1
a

1,9

3,5
(1)

1
13
31

XUZ 2003
Support for M12 rod

b1

XUZ 2001
M12 rod

b2

XSZ B112, XSZ B118


Fixing clamps ( 12 and 18)
38,3

6,5

=
10
6,5

G1

e
1

53

23

81,7

46,3

13
67

M4

M4

M3
76,5

62

40

67

40

33

12,4

XUZ 2030
Ball-joint mounted fixing bracket ( 30)
6
42,2
30,5

24,1

XUZ B2003
Ball-joint mounted fixing bracket ( 18)
5,7
36
18,5

5,7

36

12
18

M12
19

b2
8.5
11.5

40

XSZ
a
a1
b
b1
B112
21.9
14.5
16
15.5
B118
26
15.7
22.3
20.1
(1) 2 elongated holes 4 x 8.
XUZ B2012
Ball-joint mounted fixing bracket ( 12)

50

19

22,9

76,5

36

33

22,3

22,9
90,5

22,9

Curves,
schemes

Ultrasonic sensors
1

Osisonic,

Optimum and Universal

Cylindrical plastic case, M12 x 1, M18 x 1, M30 x 1.5


d.c. supply, solid-state output

Detection curves
XX5 12A22NAM8

XX5 12A1KAM8

XX5 18A32AM12

XX5 18A1KAM12

mm
30

mm
30

mm

120

mm
300

20

20

80

200

10

40

100

-10

-40

-100

-80

-200

10

-10
-20

-20

-30

10

20

30

40 50 60
mm

-120

-30

10
cm

-300
0

50

100

150

200
mm

0 65 190 320 445 570


mm

XX6 30A12CM12

XX6 30A32CM12

mm
400

cm
400

300

300

200

200

100

100

-100

-100

-200

-200

-300

-300
-400

-400

Blind zone

20

40

60

80 100
cm

8m

Wiring schemes
M8 connector
XX5 12A1KAM8
4-wire type

NO outputs, PNP and NPN

NPN
PNP

NO outputs, PNP

1/BN

1/BN
NPN

4/BK
2/WH

4/BK
PNP

3/BU

2 PNP output
4 NPN output

NO outputs, NPN

1/BN

1 (+)
3 (-)

XX5 12A22
3-wire type

3/BU

4/BK

3/BU

(-) BU (Blue) (+) BN (Brown)


WH (White) BK (Black)

1 (+)
3 (-)
4 NPN or PNP output

(-) BU (Blue) (+) BN (Brown)


BK (Black)

NO outputs, PNP and NPN

XX5 18A32
3-wire type

NO outputs, NPN

M12 connector
XX5 18A1KAM12
4-wire type

1/BN
NPN
PNP

(-) BU (Blue) (+) BN (Brown)


WH (White) BK (Black)
NO outputs, PNP and NPN

3/BU

M12 male
connector

Sensor side

NC
NO

4/BK

3/BU

(-) BU (Blue) (+) BN (Brown)


BK (Black)
NO + NC outputs, PNP
1/BN
NPN

2/WH 4/BK

2/WH

NC
NO

4/BK

3/BU

(-) BU (Blue) (+) BN (Brown)


WH (White) BK (Black)

XX5 18A3

XXZ PB100

2
2

3/BU

3/BU

1 (+)
2 PNP output
(-) BU (Blue) (+) BN (Brown)
3 (-)
4 NPN output
WH (White) BK (Black)
XXZ PB100 (teach mode pushbutton for XX5 18A37AM12)

1 (+)
3 (-)
4 NPN or PNP output
XX6 30A22CM12
NO + NC outputs, NPN
1/BN
NPN

4/BK
2/WH

M12 female
connector

4/BK
PNP

1/BN

1/BN
NPN

NPN
PNP

NO outputs, PNP

1/BN

4/BK
2/WH

3/BU

1 (+)
2 PNP output
3 (-)
4 NPN output
XX6 30A1KAM12
4-wire type

1/BN

1/BN

4/BK

4/BK

NO

2/WH

3/BU

3/BU

Output
XXZ PB100

1 (+) BN (Brown) 2 WH (White)


3 (-) BU (Blue)
4 BK (Black)

63