Professional Documents
Culture Documents
OpenAirTM
626
GBB...1
GIB...1
This data sheet provides a brief overview of these actuators. Please refer to the Technical Basics in document Z4626en for a detailed description as well as information on
safety, engineering notes, mounting and commissioning.
Use
CM2N4626E
31.01.2005
Building Technologies
HVAC Products
For dampers having two actuators on the same damper shaft (tandem-mounted
actuators or powerpack).
Type summary
GBB.../GIB...
131.1E
135.1E
Control type
Operating voltage
AC 24 V
136.1E
331.1E
335.1E
336.1E
161.1E
Three-position control
X
X
X
AC 230 V
164.1E
166.1E
Modulating control
Operating voltage
163.1E
Positioning signal Y
DC 0...10 V
U = DC 0...10 V
Feedback potentiometer 1 k
tandem-mounted)
X
X
Functions
Type
Control type
GBB.3..1 / GIB.3..1
Three-position control
Auxiliary switch
Powerpack
Rotary angle limitation
Modulating control
DC 0...35 V at
Offset
Uo = 0...5 V and
Span
U = 2...30 V
Rotary direction
GBB/GIB16..1
The rotary angle of the shaft adapter can be limited mechanically at increments of 5.
Ordering
Note
Potentiometer cannot be added in the field. For this reason, order the type that includes the required options.
Delivery
Individual parts such as position indicator and other mounting materials for the actuator
are not mounted on delivery.
2/4
Building Technologies
HVAC Products
CM2N4626E
31.01.2005
Accessories, spare
parts
Accessories to functionally extend the actuators are available, e.g., rotary/linear sets,
auxiliary switches (1 or 2 switches) and weather protection cover; see data sheet
N4699.
Technical data
AC 24 V supply
(SELV/PELV)
Running
Running
Holding
AC 24 V 20 % / 50/60 Hz
7 VA, 7 W
8 VA, 8 W
1.1 W
AC 230 V 10 % / 50/60 Hz
5 VA, 5 W
Nominal torque
25 Nm GBB
35 Nm GIB
50 Nm GBB
75 Nm GIB
90 / max. 95 2
150 s (50 Hz) / 125 s (60 Hz)
DC 0...10 V
DC 35 V
Characteristic functions
for GBB/GIB161.1, 166.1
for GBB/GIB163.1, 164.1
DC 0...35 V
DC 0...10 V
DC 0...5 V
DC 2...30 V
Position indicator
for GBB/GIB16...1
DC 0...10 V
DC 1 mA
Feedback potentiometer
for GBB/GIB135.1, 335.1
0...1000
<1W
Contact rating
Voltage (no mixed operation AC 24 V / AC 230 V)
Switching range for auxiliary switches
Setting increments
6 A resistive, 2 A inductive
AC 24...230 V
5...90
5
Connection cables
Cross-section
Standard length
0.75 mm
0.9 m
Protection class
Insulation class
AC 24 V, feedback potentiometer
AC 230 V, auxiliary switch
EN 60 730
lll
ll
Environmental conditions
Operation / Transport
Temperature
Humidity (non-condensing)
EN 60 730-2-14
(Type 1)
AC 230 V supply
Function data
Auxiliary switches
for GBB/GIB..4.1/..5.1/..6.1
Offset Uo
Span U
Conformity:
Australian EMC Framework
Radio Interference Emission Standard
IEC/EN 61 000-6-2
IEC/EN 61 000-6-1
IEC/EN 61 000-6-3
89/336/EEC
73/23/EEC
Radio Communication Act 1992
AS / NZS 3548
Dimensions
Weight
Without packaging
2 kg
Disposal
The document on technical basics and the environmental declaration provide information on environmental compatibility and disposal of this device.
3/4
Building Technologies
HVAC Products
CM2N4626E
31.01.2005
Internal diagrams
GBB/GIB13..1 / GBB/GIB33..1
GBB/GIB16..1
Three-position control
Modulating control
AC 0 V
SELV/PELV
0...1000
DC 0...10 V / 0...35 V
AC 24 V...230 V / 6 (2) A
100%
(Q11)
S4
(Q21)
S1
(c)
(Y2)
P1 P2 P3
(b)
(a)
6
(Y1)
GBB/GIB13...
GBB16...
GIB16...
(Y)
S1
100%
100%
S2 S3
(Q24)
(Q21)
(Q22)
0%
(Q14)
S4
(G0)
S1
(Q11)
(c)
(Y2)
(a)
(Y1)
P1 P2 P3
(b)
4626G03
AC 24 V...230 V / 6 (2) A
GBB/GIB33...
S4
M
(Q12)
SELV/PELV
0...1000
(U)
AC 230 V
AC 24 V...230 V / 6 (2) A
(G)
AC 24 V
SELV/PELV
DC 0..10 V
(Q21)
S5 S6
AC 24 V
(Q11)
4626G01
S2 S3
(Q24)
(Q12)
(Q22)
(G)
0%
(Q14)
S5 S6
DC 0..10 V
Cable labeling
Pin
Actuators
AC 24 V
Actuators
AC 230V
Auxiliary switch
Feedback
potentiometer
Code
No.
G
G0
Y1
Y2
Y
U
N
Y1
Y2
Q11
Q12
Q14
Q21
Q22
Q24
a
b
c
1
2
6
7
8
9
4
6
7
S1
S2
S3
S4
S5
S6
P1
P2
P3
4626G02
S2 S3
(Q24)
(Q12)
(Q22)
(N)
0%
(Q14)
S5 S6
Cable
Color
Abbreviation
red
black
purple
orange
grey
pink
blue
black
white
grey/red
grey/blue
grey/pink
black/red
black /blue
black /pink
white/red
white/blue
white/pink
RD
BK
VT
OG
GY
PK
BU
BK
WH
GY RD
GY BU
GY PK
BK RD
BK BU
BK PK
WH RD
WH BU
WH PK
Meaning
System potential AC 24 V
System neutral
Position signal AC 0 V, clockwise
Position signal AC 0 V, counter-clockwise
Position signal DC 0...10 V, 0...35 V
Position indication DC 0...10 V
Neutral conductor
Control signal AC 230 V, clockwise
Control signal AC 230 V, counter-clockwise
Switch A Input
Switch A Normally closed contact
Switch A Normally open contact
Switch B Input
Switch B Normally closed contact
Switch B Normally open contact
Potentiometer 0...100 % (P1-P2)
Potentiometer pick-off
Potentiometer 100...0 % (P3-P2)
Dimensions
Dimensions in mm
4/4
Building Technologies
HVAC Products
Subject to alteration
CM2N4626E