You are on page 1of 100

EIT: E-Cert SS: Unit 7

Instrument Selection

EIT Safety Instrumentation E-Learning

SAFETY INSTRUMENTED SYSTEMS &


EMERGENCY SHUTDOWN SYSTEMS
for Process Industries
using IEC 61511 and IEC 61508
Unit 7: SIL Instrument Selection
Version for EQO26: 7 November 2012

Presented by Dave Macdonald,


EIT Cape Town South Africa
Contact E-mail: macdond@telkomsa.net
Slide 1

www.eit.edu.au

EIT: E-Cert SS: Unit 7

Instrument Selection

Introduction to Chapter 7: Practical selection of

sensors and actuators for safety duties

Impact on SIS Reliability,


Types of Sensors and Actuators
Failure modes and causes
Separation, redundancy, diversity, diagnostics
Device Selection Issues: What IEC 61511 requires + Common sense
Technologies: Safety certified instruments and fieldbus
www.eit.edu.au

Slide 2

EIT: E-Cert SS: Unit 7

Instrument Selection

Sensors and Actuators remain the most critical reliability items in an SIS
Separation, diversity and redundancy are critical issues.
Safety related instruments must have a proven record of performance.
IEC 61508 / 61511 have specific requirements
Logic solver intelligence and communications power will help to provide
diagnostic capabilities to assist field device reliability
Failure modes and common cause issues are potential problems for
intelligent instruments
www.eit.edu.au

Slide 3

EIT: E-Cert SS: Unit 7

Instrument Selection

Instrument practice for safety systems : well established


ISA S 84.01 Appendix B.obsolete standard but still relevant.
IEC 61511 specifics defined in clause 11.5 and 11.6 of part 1.
Gruhn & Cheddie ISA Textbook; chapter 9
IEC 61511-1 Paragraph 11.5:
Requirements for selection of components and subsystems
11.5.2.1 Components and subsystems selected for use as part of a safety
instrumented system for SIL 1 to SIL 3 applications shall either be in
accordance with IEC 61508-2 and IEC 61508-3, as appropriate, or else they
shall be in accordance with 11.4 and 11.5.3 to 11.5.6, as appropriate
Certified
compliant to
IEC 61508
www.eit.edu.au

Fault
tolerance

Prior use
justification

Slide 4

EIT: E-Cert SS: Unit 7

Instrument Selection

Table 7.1

Typical Reliability Table


Item

Input sensor loop

(3 month proof test)

PFD avg
% of total

0.05

0.006

32

0.0005

0.0125

65

0.019 (SIL 1)

100

SIL 3 Logic Solver PLC


Output Actuator loop
(Solenoid + valve)
Totals

PFD avg

Fail to
Danger Rate
/ yr.

0.1

The field devices taken together contribute 97% of the PFD for this example.
The PFD figures for the field devices are affected by environmental conditions
and maintenance factors.
Slide 5
PES logic solvers benefit from auto-diagnostics.
www.eit.edu.au

EIT: E-Cert SS: Unit 7

Instrument Selection
Bus connected safety certified instruments
Foundation Field Bus
Profi-safe
ASI-Safety Bus
See Session 5

Slide 6

www.eit.edu.au

EIT: E-Cert SS: Unit 7

Instrument Selection

"

Good reliability and accuracy


Signal present at all timesimproved SFF
Potential for diagnostics, easier to detect faults
Possible to compare signal with other parameters
Trending and alarming available
Multiple set points
Competitive pricing
Rationalized spares
Slide 7

www.eit.edu.au

EIT: E-Cert SS: Unit 7

Instrument Selection

$
Components of the instrument
Process connection
Fouling /corrosion/process fluids/clogging
Wiring
Environmental: Process/Climate/Electrical
Specification/range/resolution.
Response time
Power supplies
Intrinsic safety barriers
Calibration/testing/ left on test/isolated.
Slide 8

www.eit.edu.au

EIT: E-Cert SS: Unit 7

Instrument Selection

Figure 7.4
Electrical Drive Trip

SIS
Logic

Process Valve Trip

380 v ac
power

SIS
Logic

Interlocks

M
Slide 9

www.eit.edu.au

EIT: E-Cert SS: Unit 7

Instrument Selection

& &

'

(
Stop Category 1
Safety Control Category 2

Safety
Relay

Power
Reset

K1 Time
Delayed

K1
Relay
E-Stop
command

www.eit.edu.au

Drive
controller

Slide 10

EIT: E-Cert SS: Unit 7

Instrument Selection

Potential Causes of Failures in Final Elements

Components of the actuator, positioner, mechanical


failures of springs

Process connection/leaks. Mechanical distortion of


pipes causing stress in valve

Valve internal faults due to : Fouling or corrosion by


process fluids/jamming/sticking/leaking

Wiring to solenoids

Pneumatics/ venting failures

Environmental. Physical impacts/fire/freezing or


icing up.
Solenoid valves sticking or blocking

www.eit.edu.au

Slide 11

EIT: E-Cert SS: Unit 7

Instrument Selection

" &

Sensor contacts closed during normal operation


Tx signals go to trip state upon failure (Normally < 4mA)
Broken wire = trip
Output contacts closed and energized for normal operation
Final trip valves go to trip (safe) position on air failure
Drives go to stop on trip or SIS signal failure
Slide 12

www.eit.edu.au

EIT: E-Cert SS: Unit 7

Instrument Selection

For an instrument to qualify for SIL target

or
Prior Use
Smart tx

Analog or switch

Build to IEC 61508 HW & SW

Certify to IEC 61508

SIL 1 or 2
SIL 3 requires
assessement and a safety
manual
Apply IEC 61511
limitations
And PFD must satisfy SIL target
www.eit.edu.au

Slide 13

EIT: E-Cert SS: Unit 7

Instrument Selection

Do not share sensors because it:


Violates the principles of independence
Creates a high level of common cause failure
Does not create a separate layer of protection
Does not provide secure maintenance
Slide 14

www.eit.edu.au

EIT: E-Cert SS: Unit 7

Instrument Selection

Snap question: What is wrong with this safety trip


design?

SIS Logic Solver

Boiler Steam
Drum

LSL

LT
1

Figure 7.5

Boiler
Trip

Logic

LIC
1

Feed water
supply

Snap question: Draw a better arrangement


www.eit.edu.au

Slide 15

EIT: E-Cert SS: Unit 7

Instrument Selection

Separate Sensors for Control and Trip: Acceptable

Figure 7.5 cont.

SIS Logic Solver


LSL

LT

Boiler Steam
Drum

LT
1

Boiler
Trip

Logic

LIC
1

Feed water
supply

Slide 16

www.eit.edu.au

EIT: E-Cert SS: Unit 7

Instrument Selection

Figure 7.6

Fault Tree Analysis for Boiler Low Level Trip


Shared Sensor

Separate Sensor

Boiler Damage

Boiler Damage

0.105 / yr.
Low level and NO TRIP

0.0075 / yr.
Low level and NO TRIP

OR
FW Fails and
No Trip
0.005 / yr.

AND
Low level
0.3 / yr.

LT-1 Fails
high-No Trip
LIC causes
low level
0.1 / yr.

AND

PFD = 0.1/2 X 0.5


= 0.025

FW Fails
FW Fails
0.2 / yr.

LT-2 Fails high


Trip fails on
demand

OR

Trip fails on demand from


FW failure

www.eit.edu.au

PFD = 0.1/2 X 0.5


= 0.025

0.2 / yr.

LT-1 Fails
high, LIC-1
causes low
level
0.1 / yr.

Slide 17

EIT: E-Cert SS: Unit 7

Instrument Selection

&

&

,$

- ,

.- ./

Sharing of sensor between SIS and BPCS only allowed


if safety integrity targets can be met. This would require
sensor diagnostics and is only likely to be possible for
SIL 1
Separate sensor is allowed to be copied to BPCS via
isolator
SIL 2, 3 and 4 normally require separate sensors with
redundancy
SIL 3 and 4 normally require separation and diverse
redundancy
www.eit.edu.au

Slide 18

EIT: E-Cert SS: Unit 7

Instrument Selection

&

&

,$

- ,

.- ./

A single valve may be used for both BPCS and SIS but
is not recommended if valve failure places a demand on
the SIS.
Normally shared valve can only be used if: Diagnostic
coverage and reaction time are sufficient to meet
safety integrity requirements
Recommendations for a single valve application
SIL 2 and SIL 3 normally require identical or diverse
separation. Diversity not always desireble
Slide 19

www.eit.edu.au

EIT: E-Cert SS: Unit 7

Instrument Selection

! &&

'

Figure 7.7

SIS
BPCS
Solenoid valve
direct acting,
direct mounted.
De-energise to
vent actuator.

FY

FV

Positioner

A/S

Check hazard demands due to valve


www.eit.edu.au

Slide 20

EIT: E-Cert SS: Unit 7

0 -

&

Instrument Selection

Figure 7.8

0 1

'
BPCS

SIS
A/S

FY

Check hazard demands due to valve


www.eit.edu.au

Slide 21

EIT: E-Cert SS: Unit 7

Instrument Selection

Do not confuse with proof testing


Compare trip transmitter value with related
variables. Not often practicable
Use safety transmitters if available
Use Smart transmitters with diagnostic alarm
but see next
Slide 22

www.eit.edu.au

EIT: E-Cert SS: Unit 7

Instrument Selection

Valve Diagnostics
Assurance that a trip valve will respond correctly when needed
Freedom of movement, full travel
Correct venting of actuator
Correct rate of response
Absence of sticking
Trip signals and solenoid all working
Slide 23

www.eit.edu.au

EIT: E-Cert SS: Unit 7

Instrument Selection

Methods for Valve Diagnostics


Online trip testing
Discrepancy alarm
Position feedback response testing
Partial closure testing manual or automatic
Smart positioners certified safety positioner
Slide 24

www.eit.edu.au

EIT: E-Cert SS: Unit 7

Instrument Selection

&

23

IEC 61508 places an upper limit on the SIL that can be


claimed for any safety function on the basis of the fault
tolerance of the subsystems that it uses.
Limit is a function of
the hw fault tolerance
the safe failure fraction
the degree of confidence in the behaviour under fault
conditions
Details in IEC 61508 part 2
www.eit.edu.au

Slide 25

EIT: E-Cert SS: Unit 7

23

Instrument Selection

&

IEC Defines two types of equipment for use in Safety


Systems:
Type A: Simple Devices: Non PES. E.g Limit switch, level
float switch, analogue circuits.
Type B: Complex Devices: Including PES. E.G Smart
transmitters. Digital communications, processor based systems.
Fault tolerance rating of B is less than A except under certain
conditions
Slide 26

www.eit.edu.au

EIT: E-Cert SS: Unit 7

Instrument Selection

IEC 61511-1 Table 6: Minimum hardware fault tolerance of


sensors, final elements and non PES logic
SIL

Minimum HW Fault Tolerance

Special requirements: See IEC 61508

The following summarized conditions apply for SIL 1,2 and 3 :


Increase FT by 1 if instrument does not have fail safe characteristics
Decrease FT by 1 if instrument meets 4 conditions.
Predominately fail safe
Prior Use ( Proven in use)
Limited device adjustment (process parameters only)
Password protected
Alternatively tables 2 and 3 of IEC 61508 may be applied with an assessment
www.eit.edu.au

Slide 27

EIT: E-Cert SS: Unit 7

&

Instrument Selection

, 4

Slide 28

www.eit.edu.au

EIT: E-Cert SS: Unit 7

&

Instrument Selection

, 4

Slide 29

www.eit.edu.au

EIT: E-Cert SS: Unit 7

4
#
4

Instrument Selection

&
,

Slide 30

www.eit.edu.au

EIT: E-Cert SS: Unit 7

Instrument Selection

Redundancy Options
Sensor or Actuator
Configuration.

Table 7.4

Selection

1oo1

Use if both PFD and FT and nuisance trip


targets are met.

1oo2

2 Sensors installed, 1 required to trip. PFD


value improved, nuisance trip rate doubled.

2oo3

3 Sensors installed, 2 required to trip. PFD


improved over 1oo1, nuisance trip rate
dramatically reduced.

Slide 31

www.eit.edu.au

EIT: E-Cert SS: Unit 7

Instrument Selection

Common Cause Failures in Sensors


Wrong specification
Hardware or circuit design errors
Environmental stress
Shared process connections
Wrong maintenance procedures
Incorrect calibrators
Slide 32

www.eit.edu.au

EIT: E-Cert SS: Unit 7

Instrument Selection

Figure 7.10

SIS

PT
1A

Be careful to analyze
for common cause
faults
e.g Try to avoid this
www.eit.edu.au

PT
1B

Slide 33

EIT: E-Cert SS: Unit 7

Instrument Selection

Figure 7.11
Where measurement is
the problem use diverse
redundancy.
e.g. Steam or Ammonia
overpressure protection

SIS

PT
01

TT
01
Slide 34

www.eit.edu.au

EIT: E-Cert SS: Unit 7

Instrument Selection

Requirements for Device to be Provenin-use

Evidence that the instrument is suitable for SIS

Consider manufacturers QA systems

PES devices need extra validation

Performance record in a similar profile

Adequate documentation
Volume of experience, > 1 yr exposure per case.
www.eit.edu.au

Slide 35

EIT: E-Cert SS: Unit 7

Instrument Selection

The approved safety instrument list

Each instrument that is suitable for SIS

Update and monitor the list regularly

Add instruments only when the data is adequate

Remove instruments from the list when they let you down

Adequate details: Include the process application


www.eit.edu.au

Slide 36

EIT: E-Cert SS: Unit 7

Instrument Selection

Additional requirements for smart transmitters


and actuators:
Details in IEC 61511 11.5.4 for devices with
Fixed Programming Languages (FPLs)
Extra for SIL 3
Formal assessmentlow probability of failure in planned
application.

Appropriate standards used in build

Consider manufacturers QA systems

Must have a safety manual

www.eit.edu.au

Slide 37

EIT: E-Cert SS: Unit 7

Instrument Selection

Figure 7.12

&
Hart
Interface

Status Alarm

SIS Logic Solver


DI

4-20 mA + FSK Data


AI
Smart
Transmitter

FSK = Frequency Shift Keyed


www.eit.edu.au

Hand Held
Programmer
Slide 38

EIT: E-Cert SS: Unit 7

&

Instrument Selection

Figure 7.14

Slide 39

www.eit.edu.au

EIT: E-Cert SS: Unit 7

Instrument Selection

Internal diagnostics with high coverage factor


Very low PFDavg values. Saves on proof testing etc.
Certified for single use in SIL 2 (instead of dual channel)
Certified for dual redundant use in SIL 3 (instead of 1oo3)
End user verification is simplified
Slide 40

www.eit.edu.au

EIT: E-Cert SS: Unit 7

Instrument Selection

&

The safety manual presents all the essential information and set
up conditions that must be followed to allow the instrument to
be validated for any given application.
The manual also supplies the failure rates summary and
expected PFDavg
Compliance to safety manual requirements must be
demonstrated in the validation phase.
See examples of safety manuals and FMEDA reports
Slide 41

www.eit.edu.au

EIT: E-Cert SS: Unit 7

Instrument Selection

&
The safety certificate is issued by the testing body to clearly define what
products have been tested and what standards and limitations have been
applied in the evaluation.
The safety certificate is an essential document for the validation phase.
See examples of Safety Certificates: 3051C and Rex Radar
Testing Authorities include :
TUV Rheinland
Exida.com
Any recognized testing body that can show competency in the SIS field.
Note : Exida specializes in certifying instruments claiming prior use
qualification. Reports supply SFF and failure rate data with declaration of fault
tolerance requirements relevant to IEC 61511. See examples.
Slide 42

www.eit.edu.au

EIT: E-Cert SS: Unit 7

Instrument Selection

$
Instruments must be well proven for safety with an assessment
report or Certified SIL capable to IEC 61508.
Intelligent instruments treated as PES
Separation, Redundancy, Diversity, Diagnostics
Diagnostic Coverage via Smarts or Logic Solver
Bus technology established and growing.
Slide 43

www.eit.edu.au

EIT EQO26: Unit 8

Reliability Analysis
EIT Safety Instrumentation E-Learning

SAFETY INSTRUMENTED SYSTEMS &


EMERGENCY SHUTDOWN SYSTEMS
for Process Industries
using IEC 61511 and IEC 61508
Unit 8: Reliability Analysis
Version for EQO26: 7 November 2012

Presented by Dave Macdonald,


EIT Cape Town South Africa
Contact E-mail: macdond@telkomsa.net
Slide 44

www.eit.edu.au

Slide 44

EIT EQO26: Unit 8

Reliability Analysis

Introduction to Chapter 8:
Reliability Analysis of the SIS
The task of measuring or evaluating the SIS design
for its overall safety integrity

Reasons and objectives

Resolving the SIS into reliability block diagrams

Identification of formulae

Trial calculation examples

Calculation software tools

www.eit.edu.au

Slide 45

EIT EQO26: Unit 8

Reliability Analysis

IEC 61511 requires reliability analysis be done for each SIF to


show that SIL target and RRF can be achieved. Why?

Because it tells everyone what RRF can be expected from each


individual safety function.
It confirms the basis of the design and the chosen proof test
interval
Compares the calculated RRF for your design with the target to
show you can achieve the target.
To predict the accident rate: H events/yr = Demand Rate (D) x
PFDavg or H = D/ RRF

www.eit.edu.au

Slide 46

EIT EQO26: Unit 8

Reliability Analysis

Terminology
RRF
SIL

Risk Reduction Factor ( e.g. 200)


Safety Integrity Level ( depends on RRF)
(SIL Tables)

Demand rate on Safety Function. ( How often the SIF is


demanded to respond to a hazard condition)

Hazardous event rate ( also called accident rate )


( e.g. 0.1/yr = 1 in 10 years)

PFDavg

www.eit.edu.au

Average probability of failure on demand of the SIF

Slide 47

EIT EQO26: Unit 8

Reliability Analysis

Terminology
MTTFd
MTTFs
MTTRd
Ti
dd
du
sd

www.eit.edu.au

Mean time to fail dangerously ( = 1/ d)


Mean time to fail safe (or spurious) ( = 1/ s)
Mean time to detect and repair a dangerous fault
Time interval between proof tests
Failure rate for dangerous detectable faults
Failure rate for dangerous undetectable faults (requires
proof testing)
Safe revealed failure rate ( causes spurious trip or loss of
affected safety channel)

Slide 48

EIT EQO26: Unit 8

Reliability Analysis

Risk Reduction Factor and PFDavg


RRF =

1
PFDavg

(PFDavg = average probability of failure on demand,)


PFDavg is a function of:
1.
Failure rate per hour for undetected faults :
2.
Test interval: Ti
3.
Redundancy (1oo1, 1oo2, 2oo3, etc)

du

Compare PFDavg with the target PFDavg for the SIL range we need.

www.eit.edu.au

Slide 49

EIT EQO26: Unit 8

Reliability Analysis

Snap Question: Why is PFD so useful to know?

1 Because it can tell you the accident event rate


H = Demand Rate x PFDavg
2 Because it helps you decide the SIL of your design
PFDavg defines the SIL range for the design
(in terms of resistance to random hardware failures

www.eit.edu.au

Slide 50

EIT EQO26: Unit 8

Reliability Analysis

Failure scenario for an Untested SIF

Unrevealed Dangerous fault


occurs
Hazardous condition
occurs (Demand)

State of Process

Operating
safely

Reportable
accident
occurs

Operating but
not protected

2 yr

1 yr
www.eit.edu.au

Slide 51

Mission time

EIT EQO26: Unit 8

Reliability Analysis

Low Demand Mode: Proof Tested SIF repaired before demand


Unrevealed Dangerous
fault occurs

State of Process

Proof test

Hazardous condition
Occurs (Demand)

Proof test reveals


fault

Operating
safely

Accident
prevented
Fault
repaired

Operating but not


protected

0.5 yr
www.eit.edu.au

Mission time

1 yr
Slide 52

EIT EQO26: Unit 8

Reliability Analysis

Low Demand Mode: Proof tested SIF but failure on demand


Unrevealed Dangerous
fault occurs

Reportable
accident
occurs
Demand occurs
before next proof
test

State of Process

Proof test

Operating
safely

Failure (to respond)


on Demand
Operating but not
protected

0.5 yr
www.eit.edu.au

Mission time

1 yr
Slide 53

EIT EQO26: Unit 8

Reliability Analysis

Diagnostic + Proof Tested SIF

Detectable Dangerous
fault occurs

PFDavg = MTTD&R x Fail danger rate

State of Process
Operating safely

Diagnostic test
reveals fault

Accident
prevented

Proof test for


undetected
faults

Fault
detected &
repaired

Diagnostic test
typically100
times/day
www.eit.edu.au

2 yr

1 yr
Slide 54

Mission time

EIT EQO26: Unit 8

0 #

Reliability Analysis

Low demand mode applies when the demand on the SIS is equal to
or less than once per year. ( IEC 61511) . Alternatively no more than
two demands per proof test interval.
Low demand calculations use PFDavg.
Hazard event rate H = D x PFDavg
High demand mode applies when the demand on the SIS is more
than once per year. ( IEC 61511) . Alternatively more than two
demands per proof test interval.
High demand mode calculations use PFH probability of dangerous
failure per hour.
Hazard event rate H = PFH

96
www.eit.edu.au

#
Slide 55

EIT EQO26: Unit 8

Reliability Analysis

Low Demand Mode Application


Pressure surge
once per year
(D)

Pressure relief
trip (SIS)

Accident occurs if
dangerous fault
undetected before the
surge occurs

Accident rate H = D x PFDavg


Provided Test interval is shorter than 1 year or
diagnostics detect faults quickly
Example: If PFDavg = 0.05 and D= 1 : H = 0.05/yr
www.eit.edu.au

Slide 56

EIT EQO26: Unit 8

Reliability Analysis

High demand Mode Application


Brake applied
100 times per
day

Electronic
Braking Controls
(SIS)

Accident occurs as
soon as brake circuit
fails

Accident rate = Probability of failure/hr of the EBC


= Failure rate per hour of the SIS
Example: If PFH = 0.0001/hr H = 0.0001/hr of service
If machine used for 5000 hrs /yr accident rate = 0.5/yr.
www.eit.edu.au

Slide 57

EIT EQO26: Unit 8

Reliability Analysis

Design Iteration for Target PFD in Low Demand Mode


SRS defines the Risk Reduction Factor
PFD = 1/RRF

Set Target PFD


Evaluate Solution PFD

Revise Design

No

Acceptable

Calculated PFD < Target PFD?

Yes
Proceed to Detail Design
www.eit.edu.au

Slide 58

EIT EQO26: Unit 8

Reliability Analysis

Elements and terms in the SIS model


Protective System
Hazard
Demand Rate

(SIS)

Hazard
Event Rate

PFD avg. = H/D = 1/(Risk Reduction Factor)


SIL3
SIL2
SIL1

Sensor

Logic

Actuator

PFD1

PFD2

PFD3

Overall PFD = PFD1 + PFD2 + PFD3


www.eit.edu.au

Slide 59

EIT EQO26: Unit 8

Reliability Analysis

Single Channel Basic calculation of PFD


du

If the fail to danger rate is d and proof test interval is Ti


PFDavg = du x Ti/2

(failure rate/yr x mean time to detect )

Example Fail to danger rate = 0.05 per year, Ti = 1 year


PFDavg = 0.05 x = 0.025.

( SIL 1)

How is this formula obtained ?


www.eit.edu.au

Slide 60

EIT EQO26: Unit 8

Reliability Analysis

6 <

Hazard
Event
Rate H

#
Accident Rate
H = Fail rate d

H=
H=

D x T<< 1

D x T> 1

Accident Rate H = PFH of SIS

Demand mode

Continuous mode
Demand rate D

Accident Rate H = Demand


Rate (D) x PFD avg of SIS
www.eit.edu.au

Slide 61

EIT EQO26: Unit 8

Reliability Analysis

= .

&
,

p(t)
1
Probability of
being failed when
demand occurs.
Proof test action

=
Average
value

0
www.eit.edu.au

Ti
Slide 62

2Ti

Time t

EIT EQO26: Unit 8

Reliability Analysis

Overt Failures

Covert Failures

Spurious Trip Rate

Dangerous Failure Rate

S = 1/MTBFsp

D = 1/MTTFD

D
DD

Loss of Production

S + DD
Trips plant unless
2oo3 or 2oo2 voting

C= Coverage
www.eit.edu.au

DU

Detectable
by Self
Diagnostics
DD

Slide 63

= C

Undetectable
except by manual
proof testing
DU

= (1 C)

EIT EQO26: Unit 8

Reliability Analysis
Example: Find the Safe and Dangerous Failure Modes
SIS High Level Trip

Logic Solver
PSV
AS

LC
1
I/P

Fluid
Feed

FC

FC
LT
1

LT
2

Assume out of range detection provided (forcing a trip)


Fail Modes/yr

Device

Bottom Blocked : 0.1 . Top leaks 0.2

LE connection

Runs low: 0.05. Runs high : 0.02

LT electronics

Breaks: 0.01 Shorts across LT: 0.1

Cable

Lost power: 0.02

Power

Totals for sensor sub system:

www.eit.edu.au

Slide 64

sp

du

dd

EIT EQO26: Unit 8

Reliability Analysis

1oo1 SIS Formulae

Single Channel SIS Fail Rates


Overt Failures

Covert Failures

Spurious Trip Rate

Dangerous Failure Rate

S = 1/MTBFsp

D = 1/MTTFD
C= Coverage
DD = C D

Loss of Production

S + DD
Trips plant unless
2oo3 or 2oo2 voting

SP Trip Rate = s + DD
www.eit.edu.au

Detectable by
Self
Diagnostics

PFD1 = DD x (MTTR)
Slide 65

D
DU

= (1 C)

Detectable by
manual proof
testing

PFD2 = DU x (Ti/2)

EIT EQO26: Unit 8

Reliability Analysis

1oo2 SIS Formulae


Single Channel SIS Fail Rates
Overt Failures

Covert Failures

Spurious Trip Rate

Dangerous Failure Rate

S = 1/MTBFsp

D = 1/MTTFD
C= Coverage
DD = C D

Loss of Production
Trips plant unless
2oo3 or 2oo2 voting

SP Trip Rate = 2 ( s + DD)


www.eit.edu.au

Detectable by
Self
Diagnostics

PFD1 =2(
DD)2( MTTR)2
Slide 66

D
DU

= (1 C)

Detectable by
manual proof
testing

PFD2 =((
D U .Ti)2)/3

EIT EQO26: Unit 8

Reliability Analysis

Formula sets
Single Channel SIS Fail Rates
Overt Failures

Covert Failures

Spurious Trip Rate

Dangerous Failure Rate

S = 1/MTBFsp

D = 1/MTTFD
C= Coverage

Loss of Production

S + DD
Trips plant unless
2oo3 or 2oo2 voting

Formula set 1
in Fig 8.6
www.eit.edu.au

DD = C D

DU

= (1 C)

Detectable by
Self
Diagnostics

Detectable by
manual proof
testing

Formula set 2
in Fig 8.6

Formula set 3
in Fig 8.6

Slide 67

EIT EQO26: Unit 8


Reliability Analysis
Multi-channel Formula Sets for PFD and s (excluding
Figure 8.6
common mode failures )
Covert Failures

Overt Failures

Dangerous Failure Rate

Spurious Trip Rate

d = 1/MTTF

s = 1/MTBFsp

Detectable
By Self
Diagnostics

D D = DC. D
Voting

Formula set 1

Formula set 2

D D (MTTR)

1oo1

1oo2

2
s

2oo2

2(
s)2(MTTR)

2 D D (MTTR)

2oo3

6(
s)2(MTTR)

6(
D D)2 (MTTR)2

Spurious trip rate

www.eit.edu.au

2(
DD)2( MTTR)2

PFD due to diagnostics


(if detected but not tripped)
Slide 68

Detectable
By Manual
Proof testing

D U = (1-DC) D
Formula set 3

D U (Ti/2)
((
D U .Ti)2)/3
D U .Ti
((
D U .Ti)2)
PFD due to proof test

EIT EQO26: Unit 8

Reliability Analysis
Sources of Reliability Data

http://www.sintef.no/Projectweb/PDS-Main-Page/PDS-Handbooks/
Sintef: http://www.sintefbok.no/Product.aspx?sectionId=65&productId=559&categoryId=10

1.
2.
3.
4.

www.eit.edu.au

Also see:
exida.com Reliability Handbook
Manufacturers Safety manuals for
specific SIL certified instruments
Faradip 3 Database
exida.com: Safety Automation
Equipment List ..Functional Safety
Assessment Reports
http://www.exida.com/index.php/resour
ces/sael/

Slide 69

EIT EQO26: Unit 8

Reliability Analysis

Dual Channel Basic calculation of PFD

Note: dd omitted for clarity

du
du

If the fail to danger rate is du and proof test interval is Ti.

PFDavg = ( du xTi)2 /3
Example: If fail to danger rate = 0.05 per year, Ti = 1 year
PFDavg = (0.05 x 1)2 / 3 = 0.00083

( SIL 3)

But this ignores common cause and is unrealistic


www.eit.edu.au

Slide 70

EIT EQO26: Unit 8

Reliability Analysis

Beta Factor: Common Cause Failures in redundant SIS


channels
Unit Failures

Common Cause
Failures

(1-
) d

(1-
) d

Example:
2oo3 sensor with
common cause
failures

(1-
) d
www.eit.edu.au

Slide 71

EIT EQO26: Unit 8

Reliability Analysis

Formulae Sets with Common Cause Factor included

www.eit.edu.au

Slide 72

EIT EQO26: Unit 8

Reliability Analysis

Dual Channel Basic calculation of PFD inc Common Cause 5%


Note: dd omitted for clarity
(1-
) du

du

(1-
) du

If the fail to danger rate is d and proof test interval is Ti.


PFDavg = ((1-
) du xTi)2 /3

+ du xTi/2

Example Fail to danger rate = 0.05 per year, Ti = 1 year Beta = 5%


PFDavg = (0.95 x 0.05 x 1)2 / 3 + (0.05 x 0.05 x ) = 0.002 ( SIL 2)

www.eit.edu.au

Slide 73

EIT EQO26: Unit 8

Reliability Analysis

2oo3 Channel Basic calculation of PFD inc Common Cause 5%


(1-
) d

(1-
) d
(1-
) d

If the fail to danger rate is d and proof test interval is Ti.


PFDavg = ((1-
) du xTi)2 + du xTi/2
Example Fail to danger rate = 0.05 per year, Ti = 1 year Beta = 5%
PFDavg = (0.95 x 0.05 x 1)2 + (0.05 x 0.05 x ) = 0.0035 ( SIL 2)

www.eit.edu.au

Slide 74

EIT EQO26: Unit 8

Reliability Analysis

Formulae Sets with Common Cause Factor included

www.eit.edu.au

Slide 75

EIT EQO26: Unit 8

!
7

Reliability Analysis

$
&

Formula for calculating PFDavg for 1oo1


PFDavg = ( DU xTi/2) + ( DD x MTTR)

Failures per year


Parameter

Value

Notes

DU

0.0500

Dangerous undetected failure rate for one channel

DD

0.1000

Dangerous detected failure rate for one channel

Ti in yrs

1.0000

Proof test interval

MTTR in yrs

0.0027

Mean time to detect and repair a detectable fault

( DU xTi/2)

2.50E-02

Undetected portion

( DD x MTTR)

2.74E-04

Detected portion

PFD for 1oo1 subsystem

2.53E-02

SIL Table: SIL 1

www.eit.edu.au

Slide 76

EIT EQO26: Unit 8

!
7

Reliability Analysis

$
&

Formula for calculating PFDavg for 1oo1


PFDavg = ( DU xTi/2) + ( DD x MTTR)

Failures per hour


Parameter

Value

Notes

DU

5.71E-06

Dangerous undetected failure rate for one channel

DD

1.14 E-05

Dangerous detected failure rate for one channel

Ti in hrs

8760

Proof test interval

MTTR in hrs

24

( DU xTi/2)

2.50E-02

Undetected portion

( DD x MTTR)

2.74E-04

Detected portion

PFD for 1oo1 subsystem

2.53E-02

SIL Table: SIL 1

www.eit.edu.au

Mean time to detect and repair a detectable fault

Slide 77

EIT EQO26: Unit 8

$
7

Reliability Analysis

!
:

&

$
(1(1-) d

(1(1-) d

Formula for calculating PFDavg for 1oo2


PFDavg = (1/3)*((1- ) DU xTi)2 + 2((1- ) DD x MTTR)2 + ( DU xTi/2)+ ( DD)x MTTR

Failures per year


Parameter

Safecalc: D = 1.71
% safe =0 C=66%

Value

Notes

DU

5.71E-06

Dangerous undetected failure rate for one channel

DD

1.14 E-05

Dangerous detected failure rate for one channel

0.1000
Ti in hrs
MTTR in hrs

Common cause factor for dangerous and safe failures

8760
24

Proof test interval


Mean time to detect and repair a detectable fault

(1/3)*((1- ) DU xTi)2

6.75E-04

Undetected Voting portion

2((1- ) DD2 x MTTR2)

1.18E-07

Detected voting portion

( DU xTi/2)

2.50E-03

Undetected Common portion

( DD)x MTTR

2.70E-05

Detected common portion

PFD for 1oo2 subsystem

3.20E-03

www.eit.edu.au

Slide 78

EIT EQO26: Unit 8

Reliability Analysis

$
7

!
:

&

$
(1(1-) d

(1(1-) d
(1(1-) d

Formula for calculating PFDavg for 2oo3

PFDavg = ((1- ) DU xTi)2 + 6((1- ) DD x MTTR)2 + ( DU xTi/2)+ ( DD)x MTTR

Failures per year


Parameter

Value

Notes

DU

5.71E-06

Dangerous undetected failure rate for one channel

DD

1.14 E-05

Dangerous detected failure rate for one channel

0.1000
Ti in hrs
MTTR in hrs

Common cause factor for dangerous and safe failures

8760
24

Proof test interval


Mean time to detect and repair a detectable fault

(1- ) DU xTi)2

2.03E-03

Undetected Voting portion

6((1- ) DD x MTTR)2

3.54E-07

Detected voting portion

( DU xTi/2)

2.50E-03

Undetected Common portion

( DD)x MTTR

2.70E-05

Detected common portion

PFD for 2oo3 subsystem

4.55E-03

www.eit.edu.au

Slide 79

EIT EQO26: Unit 8

Reliability Analysis

SIS Analysis Model Example


Sensor

Logic

d1=0.2

d2=0.02

or MTTF

5yrs

50yrs

10yrs

Apply
calculation

Proof
Testing

Auto
Diagnostics

Proof
Testing

D
Failure Rates:

PFD averages:

0.01

0.005

Actuator
d3=0.1

Overall PFD avg. = 0.025


= 2.5 E-2
Qualifies for SIL 1 (E-1 to E-2)
www.eit.edu.au

Slide 80

0.01

Apply
Testing or
Diagnostics

EIT EQO26: Unit 8

Reliability Analysis

SIS Analysis: Step 1


Protective System
Hazard
Demand Rate

(SIS)

Hazard
Event Rate

Sensor

Logic

Actuator

SIL 2

SIL 1

SIL 1

SIL 1
www.eit.edu.au

Slide 81

EIT EQO26: Unit 8

Reliability Analysis

SIS Analysis: Step 2, identify channels in each stage


Example:Dual channel sensors and actuators, single channel logic

Sensor

Sensor

Logic

Actuator

Actuator

Actuator

Logic
D

Sensor

1oo1D

1oo2D
www.eit.edu.au

1oo2
Slide 82

EIT EQO26: Unit 8

Reliability Analysis

SIS Analysis: Step 3, expand details for each single channel


Sensor
1oo2D

Logic

Sensor

1oo1D

Process
Connection

Transmitter

Cable and
Power

Expand detail of sensor sub system and apply fail rates for each item
www.eit.edu.au

Slide 83

EIT EQO26: Unit 8

Reliability Analysis

SIS Analysis:
Step 4: Decide du, dd and s for the elements
Step 5: Enter the values to table and totalize
Process
Connection

DU2
DD2
SD2

DU1
DD1
SD1
Subsystem
Element

Cable and
Power

Transmitter

Device

DU3
DD3
SD3
SD/hr

SU/hr

DD/hr

DU/hr

Process connection

1.14E-05

0.00E+00

5.71E-06

3.42E-06

Transmitter

1.14E-05

0.00E+00

5.71E-06

5.71E-07

Cable and Power

1.14E-05

0.00E+00

5.71E-06

3.42E-06

3.42E-05

0.00E+00

1.71E-05

7.42E-06

4
5

Subsystem totals

www.eit.edu.au

Slide 84

EIT EQO26: Unit 8

Reliability Analysis

SIS Analysis: Step 6, find the PFDavg for the 1oo2 subsystem
Break out the common cause failure fraction for the redundant channels and calculate
PFD for each portion and add them together

(1-
) d

1oo2

= common cause failure fraction


Failures common to
Ch1 and Ch2 sensors

(1-
) d

PFDavg

Redundant section:
PFDavg =
2((1-
).dd)2 . (MTTR)2
+ ((1-
) .du .Ti)2)/3

www.eit.edu.au

+
Slide 85

Logic
1oo1

Common cause section


PFDavg =
.dd (MTTR)
+ .
du . Ti/2)

EIT EQO26: Unit 8

Reliability Analysis

SIS Analysis: Step 7, repeat steps 3 to 6 for each stage


Example: Dual channel sensors and actuators, single channel logic

Sensor

Actuator
Logic
1oo1

Sensor

Actuator

1oo2
PFDavg
for sensors

www.eit.edu.au

1oo2
+

PFDavg for
logic solver

Slide 86

PFDavg
for actuators

EIT EQO26: Unit 8

Reliability Analysis

SIS Analysis: Example


Example: Dual channel sensors and actuators, single channel logic. 1yr test

DU = 0.05
.045

DU = 0.0025
= 5%
.0025

.045

1oo2
Dual Sensors PFD
= .00075 +.00125
= .002

C = 95%
0.05

1oo1D

DD = 0.0475
Logic solver PFD
= .00013 +.00125
= .00138

SIS PFD = .002 + .0014 +.0077


= . 0111 or 1.11 E-2 = SIL 1

www.eit.edu.au

Slide 87

DU = 0.1
= 10%

.09

.01
.09

1oo2
Dual Actuators PFD
= .005 + .0027
= .0077

EIT EQO26: Unit 8

Reliability Analysis

SIS Analysis: Example using the EIT Calculator


File name: EIT GP SIL Calculator .xls

Data Input Table for Sensor Subsystem


Proof Test Interval in Hrs (Ti)

8760

Common cause factor (B)%

5%

Mean Time To Test & Repair (Hrs) (MTTR)

24

Subsystem
Element
1

Device
Sensor all components

SD/hr

SU/hr

DD/hr

DU/hr

1.14E-05 0.00E+00 0.00E+00 5.71E-06

2
3
4
5
Subsystem totals

1.14E-05 0.00E+00 0.00E+00 5.71E-06

Calculation results for Sensing


Safe Failure Fraction

66.7%

Diagnostic coverage

0.0%

PFDavg for 1001

2.50E-02

PFDavg for 1002

2.00E-03

PFDavg for 2003

www.eit.edu.au

3.51E-03

Slide 88

EIT EQO26: Unit 8

Reliability Analysis

IEC Table of PFDs relevant to Figure 8.16

www.eit.edu.au

Slide 89

EIT EQO26: Unit 8


6

www.eit.edu.au

&

Reliability Analysis
3.

Slide 90

EIT EQO26: Unit 8

Reliability Analysis

SIS Analysis: Example Calculation for Spurious Trip


Example:Dual channel sensors and actuators, single channel logic
Sensor MTTF = 5 years, 75% safe failure fraction. C=0%, = 10%, Ti = 0.5 yrs, MTTR = 8hrs
Logic MTTF = 10 years, 50% safe failure fraction. C= 95%, = 10%, Ti = 1 yr
auto diagnostics test interval = 2 secs,
MTTR = 24hrs
Actuator MTTF = 2 years, 80 % safe failure fraction. C= 0%, = 10%, Ti = 0.25 yrs, MTTR =
24hrs

Sensor: single channel s = 1/5 x .75 = .15/yr


Logic: single channel s = 1/10 x .5 = .05
dd = (C x d ) =95% x 0.05 = .0475/yr
Actuator: single channel s = 1/2 x .8 = .4/yr

www.eit.edu.au

Slide 91

EIT EQO26: Unit 8

Reliability Analysis

SIS Analysis: Example Calculation for Spurious Trip

Example :Dual channel sensors and actuators, single channel logic


Spurious Trip for 1oo1
ST = S + DD
Parameter

Logic solver 1oo1


Sensor

Logic

Actuator Notes

0.05

DD
Total for 1oo1 subsystem

Fail safe rate

0.0475

DD rate added due to 95 coverage

0.0975

Spurious trip rate per yr

Spurious Trip for 1oo2


ST = 2x(1-B) ( S + DD) +B( S + DD)
Parameter

Actuators: 1oo2

Sensor

Logic

Actuator Notes

0.15

DD

Beta

0.1

0.1

0.27

0.72

0.015

0.04 Common portion

0.285

0.76 Spurious trip rate per yr

2x(1-B) ( S + DD)
B( S + DD)
Total for 1oo2 subsystem
Overall Spurious Trip Rate
1.1425 per yr

www.eit.edu.au

Slide 92

0.4 Fail safe rate


0 DD rate added due to S

EIT EQO26: Unit 8

Reliability Analysis

SIS Analysis: Example, Spurious Trip Rate


Example: Dual channel sensors and actuators, single channel logic
.36
..0135
.015
.0135

.04

.05

1oo1

1oo2

1oo2

Dual Sensors Spurious


= .28 trips per yr

Logic solver
.097 trips per
yr

Spurious trip rate = ..28 + .097 +.76


= 1.14 trips per year

www.eit.edu.au

.36

Slide 93

Dual Actuators PFD


= (2x .36) + (1x.04)
= .76 trips per yr

EIT EQO26: Unit 8

Reliability Analysis

Reducing Spurious Trip Rate

Design Version B

Design Version A
.15

.135

2oo3
.015

.15
.135

1oo2
Dual Sensors Spurious
= 2 x .15
= .30 trips per yr

.135

From 0.3 per year to 0.015/yr


If 1 trip costs AUD 50 000 the annual saving is
What? .
www.eit.edu.au

Slide 94

2oo3 Sensors Spurious


= 6x s2 (MTTR)+ s
= (6 x .1352x 8/8760) + .015
= .0001 + .015
. 015 trips per yr

EIT EQO26: Unit 8

Reliability Analysis

Outcomes of a Reliability Study


Show whether or not the SIS will satisfy the SIL target

Overall SIS Probability of Failure on Demand (PFDavg)

PFDavgs for each section of the SIS


Show benefits of redundancy or voting schemes
Decide the proof testing intervals
Predict the accident rate

www.eit.edu.au

Slide 95

EIT EQO26: Unit 8

Reliability Analysis

Conclusions on Analysis Models


Models help to visualise SIS performance
Software speeds up analysis
IEC 61508 part 6 - methods and tables
Fault tree analysis for detailed systems

www.eit.edu.au

Slide 96

EIT EQO26: Unit 8

Reliability Analysis

&&

0 #
9

6
;

Low demand mode applies when the demand on the SIS is equal to
or less than once per year. ( IEC 61511) . Alternatively no more than
two demands per proof test interval.
Low demand calculations use PFDavg.
Hazard event rate H = D x PFDavg
High demand mode applies when the demand on the SIS is more
than once per year. ( IEC 61511) . Alternatively more than two
demands per proof test interval.
High demand mode calculations use PFH ( same as failure to danger
rate)
Hazard event rate H = PFH

www.eit.edu.au

Slide 97

EIT EQO26: Unit 8

Pump

Power

Reliability Analysis
PSH
d = 0.05 and Ti = 1/yr:
SIS

6
Hp safety Trip

PFDavg = 0.05 x = 0.025. and


PFH = 0.05 /8760 = 5.7E-06/hr
Suppose the demand rate D is once per year and the overpressure event rate
= H/yr
In low demand mode calculation H = D x PFDavg so H = 1 x 0.025 = 0.025/yr
In high demand mode calculation H = PFH
www.eit.edu.au

Slide 98

so H = 5.7E-06/hr = 0.05/yr

0 #

EIT EQO26: Unit 8

Pump

Reliability Analysis
PSH
d = 0.05 and Ti = 1/yr:
SIS

Power

PFDavg = 0.05 x = 0.025. and


PFH = 0.05 /8760 = 5.7E-06/hr
Suppose the demand rate D is once per day ( 365/yr)
And the overpressure event rate = H/yr
In low demand mode: H = D x PFDavg so H = 365 x 0.025 = 9.1/yr
In high demand mode :H = PFH
www.eit.edu.au

so H = 5.7E-06/hr = 0.05/yr
Slide 99

0 #

EIT EQO26: Unit 8

Reliability Analysis

Demand on SIS

SIS has failures at


PFD = 0.01
PFH = 0.02/yr (2.28 E-06/hr)

H = hazardous event

D = 0.1/yr ..H =

/yr ?

D = 1.0/yr ..H =

/yr ?

D = 10.0/yr ..H =

/yr ?

D = 100 /yr ..H =

/yr ?

www.eit.edu.au

Slide 100

You might also like