Professional Documents
Culture Documents
BASICS
MACHINES
POWER SYSTEM
ELECTRONICS
QUESTIONS
VIDEOS
ONLINE EXAM
Search for:
Search
or
Error
Angle
Instrument
Transformer
Current
Transformer(CT)
Current
Transformer
Class
Transformer
or
CT
Transformer
or
CT
in
Current
Transformer
or
CT
Error
in
Current
Transformer
in
Current
Transformer
transformer
class or CT
class.
But in the case of protection, the CT may not have the accuracy level as good as metering CT
although it is desired not to be saturated during high fault current passes through primary. So core of
protection CT is so designed that it would not be saturated for long range of currents. If saturation of
the core comes at lower level of primary current the proper reflection of primary current will not come
to secondary, hence relays connected to the secondary may not function properly and protection
system losses its reliability.
Suppose you have one CT with current ratio 400/1 A and its protection core is situated at 500 A. If
the primary current of the CT becomes 1000 A the secondary current will still be 1.25 A as because
the secondary current will not increase after 1.25 A because of saturation. If actuating current of the
relay connected the secondary circuit of the CT is 1.5 A, it will not be operated at all even fault level
of the power circuit is 1000 A.
The degree of accuracy of a protection CT may not be as fine as metering CT but it is also
expressed by CT accuracy class or simply current transformer class or CT class as in the case
of
metering
current
transformer
but
in
little
bit
different
manner.
A CT functions with the same basic working principle of electrical power transformer, as we
discussed earlier, but here is some difference. If a electrical power transformer or other general
purpose transformer, primary current varies with load or secondary current. In case of CT, primary
current is the system current and this primary current or system current transforms to the CT
secondary, hence secondary current or burden current depends upon primary current of the current
transformer.
Are you confused? OK let us clear you.
In a power transformer, if load is disconnected, there will be only magnetizing current flows in the
primary. The primary of the power transformer takes current from the source proportional to the load
connected with secondary . But in case of CT, the primary is connected in series with power line. So
current through its primary is nothing but the current flows through that power line. The primary
current of the CT, hence does not depend upon whether the load or burden is connected to the
secondary or not or what is the impedance value of burden. Generally CT has very few turns in
primary where as secondary turns is large in number. Say Np is number of turns in CT primary and
Ip is the current through primary. Hence the primary AT is equal to NpIp AT.
If number of turns in secondary and secondary current in that current transformer are N s and
Isrespectively then Secondary AT is equal to NsIs AT.
In an ideal CT the primary AT is exactly is equal in magnitude to secondary AT.
So from the above statement it is clear that if a CT has one turn in primary and 400 turns in
secondary winding, if it has 400 A current in primary then it will have 1 A in secondary burden.
Thus the turn ratio of the CT is 400/1 A
Is -
Secondary
current.
Es Secondary
induced
Ip Primary
Ep Primary
induced
KT Turns
ratio
=
Numbers
of
secondary
turns/number
I0 Excitation
Im Magnetizing
component
Iw Core
loss
component
m - Main flux.
emf.
current.
emf.
of
primary
turns.
current.
of
I0 .
of
I0.
Let us take flux as reference. EMF Es and Ep lags behind the flux by 90. The magnitude of the
passers Es and Ep are proportional to secondary and primary turns. The excitation current Io which is
made up of two components Im and Iw.
The secondary current I0 lags behind the secondary induced emf Es by an angle s. The secondary
current is now transferred to the primary side by reversing Is and multiplied by the turns ratio KT. The
total current flows through the primary Ip is then vector sum of KT Is and I0.
For a ideal CT the angle between the primary and reversed secondary current vector is zero. But for
an actual CT there is always a difference in phase between two due to the fact that primary current
has to supply the component of the exiting current. The angle between the above two phases in
termed
asphase
angle
error
in
current
transformeror
CT.
Here
in
the
pharos
the phase angle error is usually expressed in minutes.
1.
2.
3.
4.
diagram
it
is
http://www.electrical4u.com/current-transformer-ct-class-ratio-error-phase-angle-error-in-currenttransformer/
http://www.ece.uidaho.edu/ee/classes/ECE526S05/
http://www.ece.uidaho.edu/ee/classes/ECE526S05/text/
http://www.ece.uidaho.edu/ee/classes/
http://www.ece.uidaho.edu/ee/classes/ECE211/
Procedures to follow:
1. Visual and Mechanical Inspection
2. Electrical Tests:
1. Electrical Tests Current Transformers
2. Electrical Tests Voltage Transformers
3. Electrical Tests Coupling-Capacitor Voltage Transformers
4. Electrical Tests High-Accuracy Instrument Transformers (Reserved)
3. Test Values:
1. Test Values: Visual and Mechanical
2. Test Values: Current Transformers Electrical
3. Test Values:Voltage Transformers Electrical
4. Test Values: Coupling Capacitor Voltage Transformers
5. Test Values: High-Accuracy Instrument Transformers (Reserved)
4. Tables (100.5, 100.9 and 100.12)
2. Electrical Tests
2.1 Electrical Tests Current Transformers
1. Perform resistance measurements through bolted connections with a low-resistance
ohmmeter, if applicable, in accordance with Section 1.
2. Perform insulation-resistance test of each current transformer and its secondary wiring
with respect to ground at 1000 volts dc for one minute.For units with solid-state
components that cannot tolerate the applied voltage, follow manufacturers
recommendations.
3. Perform a polarity test of each current transformer in accordance with ANSI/IEEE C57.13.1.
4. Perform a ratio-verification test using the voltage or current method in accordance
with ANSI/IEEE C57.13.1.
5. Perform an excitation test on transformers used for relaying applications in accordance
with ANSI/IEEE C57.13.1.
6. Measure current circuit burdens at transformer terminals in accordance with
ANSI/IEEE C57.13.1.
7. When applicable, perform insulation-resistance tests on the primary winding with the
secondary grounded. Test voltages shall be inaccordance with Table 100.5.
8. When applicable, perform dielectric withstand tests on the primary winding with the
secondary grounded. Test voltages shall be inaccordance with Table 100.9.
9. Perform power-factor or dissipation-factortests in accordance with test
equipment manufacturers published data.
10. Verify that current transformer secondary circuits are grounded and have only one
grounding point in accordance with ANSI/IEEE C57.13.3. That grounding point should be
located as specified by the engineer in the project drawings.
Go to Index of Procedures
3. Test Values
3.1 Test Values Visual and Mechanical
1. Compare bolted connection resistance values to values of similar connections.
Investigate values which deviate from those of similar bolted connections by more than 50
percent of the lowest value. (1.6.1)
2. Bolt-torque levels shall be in accordance with manufacturers published data. In the
absence of manufacturers published data, use Table 100.12.
3. Results of the thermographic survey.
4. Perform power-factor or dissipation-factortests in accordance with test
equipment manufacturers published data.
5. Verify that the coupling-capacitor voltage transformer circuits are grounded and have only
one grounding point in accordance with ANSI/IEEE C57.13.3. That grounding point should
be located as specified by the engineer in the project drawings.
Go to Index of Procedures
TABLE 100.5
Transformer Insulation Resistance Acceptance Testing
In the absence of consensus standards, the NETA Standards Review Council suggests the above representative values.
NOTE: Since insulation resistance depends on insulation rating (kV) and winding capacity (kVA), values obtained should
be compared to manufacturers published data.
Go to Index of Procedures
TABLE 100.9
Instrument Transformer Dielectric Tests Field Acceptance
Table 100.9 is derived from Paragraph 8.8.2 and Tables 2 of ANSI/IEEE C57.13-1993, Standard Requirements for
Instrument Transformers.
+ Periodic dc potential tests are not recommended for transformers rated higher than 34.5 kV.
* DC potential tests are not recommended for transformers rated higher than 200 kV BIL. DC tests may prove beneficial
as a reference for future testing. In such cases the test direct voltage shall not exceed the original factory test rms
alternating voltages.
Go to Index of Procedures
TABLE 100.12
US Standard Fasteners Bolt-Torque Values for Electrical
Connections
http://electrical-engineering-portal.com/testing-and-commissioning-procedure-for-motors
http://electrical-engineering-portal.com/testing-of-power-transformer-measurement-of-impedancevoltage-and-load-loss
http://electrical-engineering-portal.com/inspection-and-test-procedures-for-rotating-machinerysynchronous-motors-and-generators
http://electrical-engineering-portal.com/location-of-current-transformers-in-hv-substation