ESTIMATION OF TOTAL POPULATION

Drawing Ref. No.

Units

1
3
2
4
5
6

School Building
Boy's Hostel
Girl's Hostel
Canteen
Staff Quarter
Class IV Staff Quarter
Total

Nos. of
Person
260
130
130
50
32
24
626

Reference
Manholes
MH11
MH7
MH9
MH7
MH2
MH1

ESTIMATION OF SANITARY SEWAGE


PER CAPITA SEWAGE CONTRIBUTION
>
Per Capita Water Supply
>
Gross Per Capita Water Supply
>
Per Capita Sewage Contribution

135
155
85
132

lpcd
lpcd
%
lpcd

STAGE WISE WASTE WATER QUANTITY


Unit
Persons
Mld
m/day
m/hr.

MH11
260
0.034
34.310
1.430

Node Wise Population


MH9
130
130
0.017
0.017
17.155
17.155
0.715
0.715
MH7

MH7
50
0.007
6.598
0.275

MH2
32
0.004
4.223
0.176

MH1
24
0.003
3.167
0.132

Total
626
0.083
82.609
3.442

Design Peak Flow


Since total poulation is less than 20000, therefore as per CPHEEO manual guidelines peak factor assumed as 3.

Unit
Peak factor
Mld
m/day
m/hr.
l/d

Node Wise Population


MH11
MH7
MH9
MH7
3
3
3
3
0.103
0.051
0.051
0.020
102.931
51.465
51.465
19.794
4.289
2.144
2.144
0.825
1029307.5 514653.75
514653.75 197943.75

MH2
3
0.013
12.668
0.528
126684

MH1
3
0.010
9.501
0.396
95013

Total
3
0.248
247.826
10.326
2478256

POPULATION ESTIMATION

Flormation level considered is


Pipe Material

10 m
Corrugated HDPE (Smooth Interior)

Reference Node
MH11
MH7
MH9
MH2
MH1

Total load (l/d) Total load (l/s) Averge load (l/s)


1029307.5
11.91
3.97
712597.5
8.25
2.75
514653.75
5.96
1.99
126684
1.47
0.49
95013
1.10
0.37

Screenshot of Pipe and Manholes

ABSTRACT SHEET
Sewer Collection System for School Option 1
Sr
No

Description

Quantity

Unit

Rate

261.72

Cu.M.

310.00

23.05

Cu.M.

324.00

68

RMT

513.00

12.00
12.00

No.
No.

1115.00
1167.00

1 Excavation for pipe line trenches incl. all safety

provisions using site rails and stacking excavated


stuff up to a lead of 90 mts. cleaning the site etc.
complete for lifts and strata as specified. Upto 1.50
mt depth.
Total Excavation
Upto 1.50 mt depth
In hard rock
1.50 m to 3.0 m depth
In hard rock

(GWSSB SOR SECTION-B ITEM NO.15, PAGE


NO.65&66)
2 Providing and supplying in standard length ISI mark

high density Polyethylene H.D.P.E. Pipes suitable


for potable water as per IS specification no.
4984/1995 including all local and central taxes,
transportation, freight charges, octroi, inspection
charges, loading, unloading, conveyance to the
departmental stores etc.
complete.
PE-100 Conforming to Design stress of 10.0 N/mm2
150 mm
(GWSSB SOR SEC:-A ITEM NO:13(G)
PAGE NO.33)
3 RCC precast M.H. Frame & Cover Manufacture,

supply & Delivery at store or at site of work precast


RCC M.200 Frame & cover suitable to drainage
M.H. and as per type design & Drawing including
cost of
reinforcement M.S. Angles or Flate, curring mold
work etc.
Heavy Duty
Frame
Cover
(GWSSB SOR SEC:-A ITEM NO:23(A)
PAGE NO.46)

4 Lowering, laying and jointing HDPE pipes and

specials of following class and diameter (By butt


fusion welding method) including cost of
conveyance from stores to site of works including
cost of labour, material, giving satisfactory hydraulic
testing as per IS Code
150 mm
(GWSSB SOR SEC:-B ITEM NO:12(B)
Page No.64)

68.40

RMT

84.00

216.63

Cu.M.

16.00

3.40

Cu.M.

2115.00

8.00

No.

8600.00

2.17

Rmt.

5800.00

5 Refilling

the
pipeline
trenches
incl.
ramming,watering, consolidating disposal of surplus
stuff as directed within a radius of 3 km.
(GWSSB SOR SEC:-B ITEM NO:23
Page No.69)

6 Providing and casting in situ cement concrete1:4:8

using granite quarzite trap metal of size 25mm to


40mm including consolidation curing etc. complete.
Network pipe bedding

(GWSSB SOR SEC:-D ITEM NO:1


Page No.77)
7 Sewer Manhole
Providing and constructing Sewer manholes, scraper
manholes and unit house connection chamber, as per
the type design in brick masonary in C. M. 1:3 and
outside plastering in C. M. 1:3 necessary coping in
R.C.C.M. 200 fixing C. I. steps and fixing manhole
frame and covers (But excluding supply of manhole
frame and covers) over manholes and house
connection chambers and fixing Manhole covers
(but excluding supplying of manhole covers) over
scraper manhole etc. complete, providing and fixing
safety chain wherever necessary as per the
stipulations in the type desing complete (excl.
excavation).
a) Manhole type "A" Circular type having inside

diameter of 1200 mm for depth up to 1.5 m depth


(for 150 mm to 500 mm dia sewer)
Manhole type "A" as above but up to 1.0 M depth.
Extra depth beyond 1 .0 M but up to 1 .5 M depth for
"A" type manhole above.

b) Manhole type "B" circular type having inside

diameter of minimum 1500 mm and for depth from


1.5 M to 4.0 M (for 150 mm to 600 mm dia sewers)
Manhole type "B" as above but up to 1.5 M depth.
Extra depth beyond 1 .5 M but up to 4.0 M depth for
type B manhole above.
(GWSSB SOR SEC:-C ITEM NO:2,
Page No.72&73)

4.00

No.

14050.00

0.66

Rmt.

8660.00

2.00

No.

200000.00

8 Septic tank and Soak pit

Providing Septic Tank and Soak Pit for disposal


of sewage complete.
Market Rate
Total Amount (Based on GWSSB SOR 2011-12)
Total Estimate for CHINCHALI option 1
Total Estimate for GARKHEDI option 1 (10% added extra)

Amount

81132.97
7469.75

35089.20

13380.00
14004.00

5745.60

3466.11

7191.00

68800.00
12589.83

56200.00
5696.13

400000.00

710,764.58
710,765.00
781,842.00

MEASUREMENT SHEET
Sewer Collection System for School Option 1

Sr
Description
No
1 Excavation for pipe line trenches incl. all safety

No

Quantity

Unit

Total

151.96

Cu.M.

Total

16.10

Cu.M.

Total

109.76

Cu.M.

Total

6.95

Cu.M.

A1+B1

261.72

Cu.M.

A2+B2

23.05

Cu.M.

68.40

RMT

12.00

No.

provisions using site rails and stacking excavated


stuff up to a lead of 90 mts. cleaning the site etc.
complete for lifts and strata as specified. Upto
1.50 mt depth.
A ManHole Excavation
A1 0.00 m to 1.5 m depth

In hard rock
A2 1.50 m to 3.0 m depth
In hard rock
B Excavation for Pipeline trenches
B1 0.00 m to 1.5 m depth

In hard rock
B2 1.50 m to 3.0 m depth
In hard rock
Total for Excavation
Upto 1.50 mt depth
In hard rock
1.50 m to 3.0 m depth
In hard rock
2 Providing and supplying in standard length ISI
mark high density Polyethylene H.D.P.E. Pipes
suitable for potable water as per IS specification
no. 4984/1995 including all local and central
taxes, transportation, freight charges, octroi,
inspection
charges,
loading,
unloading,
conveyance to the departmental stores etc.
complete.
PE-100 Conforming to Design stress of 10.0
N/mm2
150 mm
3

68

RCC precast M.H. Frame & Cover Manufacture,


supply & Delivery at store or at site of work precast
RCC M.200 Frame & cover suitable to drainage M.H.
and as per type design & Drawing including cost of
reinforcement M.S. Angles or Flate, curring mold
work etc.
Heavy Duty
Frame

II

Cover

12.00

No.

Lowering, laying and jointing HDPE pipes and


specials of following class and diameter (By butt
fusion welding method) including cost of
conveyance from stores to site of works including
cost of labour, material, giving satisfactory
hydraulic testing as per IS Code
150 mm

68.40

RMT

Total Excavation for Manhole =


Deduction
Manhole Volume
Manhole Bedding
Brick Work of Manhole
Total Deduction
Total Qty for Refilling = (A-B)

168.06

Cu.M.
Cu.M.
Cu.M.
A

23.19
23.87
16.16
63.21
104.85

B
Cu.M.

Total Pipe Excavation (C)


Deduction
Pipe Volume
Pipe Bedding
Total Deduction (D)
Total Pipe Qty. (C-D)

116.71

1.53
3.40
4.93
111.78

Cu.M.
Cu.M.
D
Cu.M.

216.63

Cu.M.

3.40

Cu.M.

Refilling
the
pipeline
trenches
incl.
ramming,watering, consolidating disposal of
surplus stuff as directed within a radius of 3 km.
watering, consolidating disposal of surplus stuff
as

TOTAL FOR REFILLING =


I+II
6

Providing and casting in situ cement


concrete1:4:8 using granite quarzite trap metal of
size 25mm to 40mm including consolidation
curing etc. complete.
Network pipe bedding

Providing and constructing Sewer manholes,


scraper manholes and unit house connection
chamber, as per the type design in brick masonary
in C. M. 1:3 and outside plastering in C. M. 1:3
necessary coping in R.C.C.M. 200 fixing C. I.
steps and fixing manhole frame and covers (But
excluding supply of manhole frame and covers)
over manholes and house connection chambers
and fixing Manhole covers
(but excluding supplying of manhole covers) over
scraper manhole etc. complete, providing and
fixing safety chain wherever necessary as per the
stipulations in the type desing complete (excl.
excavation).
a) Manhole type "A" Circular type having inside
diameter of 1200 mm for depth upto 1.5 m depth
(for 150 mm to 500 mm dia sewer)
Manhole type "A" as above but up to 1.0 M
depth.
Extra depth beyond 1 .0 M but up to 1 .5 M depth
for "A" type manhole above.
b) Manhole type "B" circular type having inside
diameter of minimum 1500 mm and for depth
from 1.5 M to 4.0 M (for 150 mm to 600 mm dia
sewers)
Manhole type "B" as above but up to 1.5 M
depth.
Extra depth beyond 1 .5 M but up to 4.0 M depth
for type B manhole above.
8

8.00

No.

2.17

Rmt.

4.00

No.

0.66

Rmt.

2.00

No

Providing Septic Tank and Soak Pit for disposal


of sewage complete.