You are on page 1of 6

SIMULTANEOUS

AC-DC POWER TRANSMISSION


Abstract

The advantage of parallel ac-dc power oscillations as well as to control the voltage
transmission for the improvement of transient profile of the line by controlling the total
and dynamic stability and damp out reactive power flow. Only the basic idea is
oscillations have been established. Present proposed along with the feasibility study using
paper proposes a simultaneous ac-dc power elementary laboratory model. The main object
flow scheme through the same transmission is to emphasize the possibility of simultaneous
line to get the advantages of parallel ac-dc ac-dc transmission with its inherent advantage
transmission to improve stability and damping of power flow control.

Introduction . improves stability and damps out oscillations


in power system.
HVDC transmission lines in parallel with EHV EHV ac line may be loaded to a very high
ac lines are recommended to improve transient value if the conductors are allowed to carry
and dynamic stability as well as to damp out superimposed dc current along with ac current.
oscillations in power system. Long EHV ac The added de power flow does not cause any
lines can not be loaded to its thermal limit to transient instability.
keep sufficient margin against transient This paper presents a simple scheme of
instability. But for optimum use of simultaneous EHV ac-dc power flow through
transmission lines here is a need to load EHV the same transmission line with an object to
ac lines close to their thermal limits by using achieve the advantages of parallel ac-dc
flexible ac transmission system (FACTS) transmission. Simultaneous ac-dc
components .Very fast control of SCRs in transmission may also claim advantages in
FACTS devices like state VAR system (SVS), some specific applications LV (low voltage)
controlled series capacitor (CSC), static phase and MV (Medium voltage) system.
shiftier (SPS) and controlled braking resistors
SIMULTANEOUS AC-DC TRANSMISSION:

The circuit diagram in Figure1 shows the basic carries one third of the total de current along
scheme for simultaneous ac-dc transmission. with ac current Ia .The return path of the dc
The dc power is obtained through the rectifier current is through the ground. Zigzag
bridge and injected to the neutral point of the connected winding is used at both ends to
zigzag connected secondary of sending end avoid saturation of transformer due to dc
transformer, and again it is reconverted to ac current flow. A high value of reactor. X d is
by the inverter bridge at the receiving end. used to reduce harmonics in dc current.
The inverter bridge is again connected to the In the absence of zero sequence and third
neutral of zigzag connected winding of the harmonics or its multiple harmonic voltages,
receiving end transformer. Star connected under normal operating conditions, the ac
primary windings in place of delta-connected current flow will be restricted between the
windings for the transformers may also be used zigzag connected windings and the three
for higher supply voltage. The single circuit conductors of the transmission line. Even the
transmission line carriers both 3 –phase ac and presence of these components of voltages may
dc power. It is to be noted that a part of the only be able to produce negligible current
total ac power at the sending end is converted through the ground due to high of Xd.
into dc by the tertiary winding of the Assuming the usual constant current control of
transformer connected to rectified bridge. The rectifier and constant extinction angle control
same dc power is reconverted to ac at the of inverter, the equivalent circuit of the scheme
received end by the tertiary winding of the under normal steady state operating condition
receiving end transformer connected to the is shown in Fig.2.
inverter bridge. Each conductor of the line
.

The dotted line in the figure shows the path of current, expressions for ac voltage and current,
ac return current only. The ground carries the and for active and reactive powers may be
full dc current Id only and each conductor of written in terms of A,B,C,D parameters of the
the line carries Id/3 along with the ac current lines as: :
per phase.
Neglecting the resistive drops in the line
conductors and transformer winding due to dc
Es = AER + BIR inverter respectively and Vdr and Vdi are the
(1) maximum dc voltages of rectifier and inverter
Is = CER + DIR side respectively. Values of Vdr and Vdi are
(2) 1.35 times line to line tertiary winding ac
Ps+ jQS = (- ES E*R)/B* + (D*/B*) Es2 voltages of respective sides.
(3) Reactive powers required by the converters
PR+ jQR = (ES* ER)/B* - (A*/B*)ER2 are:
(4)
Qdi = Pdi tanI (5)
Neglecting ac resistive drop in the line and Qdr = Pdr tanr (6)
transformer, the dc current and dc power may CosI = (cos + cos ( + i) )/2
be expressed as : (7)
Id = (Vdrcos - Vdicos)/(Rer+(R/3) – Rci) Cosr = (cos + cos ( + r) )/2
Pdi = Vdi x Id ; Pdr = Vdr x Id (8)
Where R is the line resistance per conductor, Where I and r are commutation angles of
Rcr and Rci commutating resistances,  and, inverter and rectifier respectively and total
firing and extinction angles of rectifier and active and reactive powers at the two ends are
Pst = Ps + Pdr and Prt = PR + Pdi (9) connected at the two ends of transmission line
Qst = Qs + Qdr and Qrt = QR + Qdi interrupt current at natural current zeroes and
(10) no special dc CB is required. To ensure proper
Total transmission line loss is: operation of transmission line CBs tripping
PL = (Ps + Pdr) – (PR + Pdi) signals to these CBs may only be given after
(11) sensing the zero crossing of current by zero
Ia being the rms ac current per conductor at crossing detectors. Else CB’s connected to the
any point of the line, the total rms current per delta side of transformers (not shown in
conductor becomes: figure1) may be used to isolate the fault.
I = sqrt (Ia2 + (Id/3)2) and PL  3I2R Saturation of transformer core, if any, due to
(12) asymmetric fault current reduces line side
If the rated conductor current corresponding to current but increases primary current of
its allowable temperature rise is Ith and transformer. Delta side CBs, designed to clear
Ia = X * Ith; X being less than unity, the dc transformers terminals faults and winding
current becomes: faults, clear these faults easily.
Id = 3 x (sqrt (1-x2) ) Ith Proper values of ac and de filters as used in
(13) HVDC system may be connected to the delta
The total current I in any conductor is side and zigzag neutral respectively to filter
asymmetrical but two natural zero-crossings in our higher harmonics from de and ac supplies.
each cycle in current wave are obtained for However, filters may be omitted for low values
(Id/3Ia) <1.414. of Vd and Id.
The instantaneous value of each conductor At neutral terminals of zigzag winding de
voltage with respect to ground become s the dc current and voltages may be measured by
voltage Vd with a superimposed sinusoid ally adopting common methods used in HVDC
varying ac voltages having rms value Eph and system. Conventional cvts as used in EHV ac
the peak value being : lines are used to measure ac component of
Emax = V + 1.414 Eph transmission line voltage. Superimposed dc
Electric field produced by any conductor voltage in the transmission line does not affect
voltage possesses a dc component the working of evts. Linear couplers with high
superimposed with sinusoid ally varying ac air-gap core may be employed for
component. But the instantaneous electric field measurement of ac component of line current
polarity changes its sign twice in cycle if as dc component of line current is not able to
(Vd/Eph) < 1.414.Therefore, higher creep age saturate high air-gap cores.
distance requirement for insulator discs used Electric signal processing circuits may be used
for HVDC lines are not required. to generate composite line voltage and current
Each conductor is to be insulated for E maz but waveforms from the signals obtained for dc
the line to line voltage has no dc component and ac components of voltage and current.
and ELL(maz) = 2.45 Eph, Therefore, conductor to Those signals are used for protections and
conductor separation distance is determined control purposes.
only by rated ac voltage of the line.
Assuming Vd/Eph = k Experimental verification .
Pdc/’Pac  (Vd * Id)/(3 * Eph * Ia * cos) = (k *
sqrt(1-x2))/(x * cos ) (15) The feasibility of the basic scheme of
Total power simultaneous ac-dc transmission was verified
Pt = Pdc + Pac = (1 + [k * sqrt (1-x2)]/(x * cos)) in the laboratory. Transformer having a rating
* Pac (16) of 2 kVA, 400/230/110V was used at each end.
Detailed analysis of short current ad design of A supply of 3-phase, 400V, 50Hz was given at
protective scheme, filter and instrumentation the sending end and a 3-phase, 400 V, 50 Hz,1
network required for the proposed scheme is HP induction motor in addition to a 3-phgase,
beyond the scope of present work, but 400V, 0.7 KW resistive load was connected at
preliminary qualitative analysis presented the receiving end. A 10 A, 110 Vdc reactor
below suggests that commonly used techniques (Xd) was used at each end with the 230V
in HVDC/ac system may be adopted for this zigzag connected neutral. Two identical SCR
purposes. bridges were used for rectifier and inverter.
In case of fault in the transmission system, gate The dc voltages of rectifier and inverter
signals to all the SCRs are blocked that to the bridges were adjusted between 145 V to135 V
bypass SCR s are released to protect rectifier to vary dc current between 0 to 3A.
and inverter bridges. CBs are then tripped at The same experiment was repeated by
both ends to isolate the complete system. As replacing the rectifier at the sending and and
mentioned earlier, if (Id3Ia) <1.414, CBs the inverter at receiving end by 24V battery
and a 5A, 25 rheostat respectively, between Xd and ground.
The power transmission with and without de 1.2 times the rated current for a short time with
component was found to be satisfactory in all the input transformer kept energized from
the cases. 400V ac. But no changes in exciting current
To check the saturation of zigzag connected and terminal voltage of transformer were
transformer for high value of Id, ac loads were noticed verifying no saturation even with high
disconnected and dc current was increased to value of I d.

For a value of x=0.7 and V d =0.05 E ph or 0.10


Proposed applications. E ph, 5.1% or 10.2% more power may be
transmitted.
1.Long EHV ac lines can not be loaded to 4.By adding a few more discs in insulator
their thermal limit to keep sufficient margin strings of each phase conductor d with
against transient instability and to keep voltage appropriate modifications in cross-arms of
regulation within allowable limit, the towers insulation level between phase to
simultaneous power flow does not imposed ground may be increased to a high value,
any extra burden on stability of the system, which permits proportional increase in E max,
rather it improves the stability. The resistive Therefore higher value of Vd may be used to
drop due to dc current being very small in increase dc and total power flow through the
comparison to impedance drop due to ac line. This modification in the exiting ac lines
current, thee is also no appreciable change in is justified due to high cost of a separate
voltage regulation due to superimposed dc HVDC line.
current. 5. With the very fast electronic control of
2. Therefore one possible application of firing angle (α ) and extinction angle (γ ) of the
simultaneous ac-dc transmission is to load the converters, the fast control of dc power may
line close to its thermal limit by transmitting also be used to improve dynamic stability and
additional dc power. Figure3 shows the damping out oscillations in the system similar
variation of Pt/Pac for changing values of k to that of the ac-dc parallel transmission lines.
and x at unity power factor. However, it is to 6. Control of  and  also controls the rectifier
be noted that additional conductor insulation is and inverter VAR requirement and therefore,
to be provided due to insertion of dc. may be used to control the voltage profile of
3. Necessity of additional dc power the transmission line during low load condition
transmission will be experienced maximum and works as inductive shunt compensation. It
during peak load period which is characterized may also be considered that the capacitive
with lower than rate voltage. If dc power is VAR of the transmission line is supplying the
injected during the peak loading period only whole or part of the inductive VAR
with V d being in the range of 5% to 10% of E requirement of the converter system. In pure
pb, the same transmission line without having HVDC system capacitance of transmission line
any enhanced insulation level may be allowed cannot be utilized to compensate inductive
to be used. VAR.
7. The independent and fast control of active
and reactive power associated with dc,
superimposed with the normal ac active and
reactive power may be considered to be
working as another component of FACTS.
8. Simultaneous ac-dc power transmission may
find its application in some special cases of Conclusions.
LV and MV distribution system.
When 3-phase power in addition to dc power A simple scheme of simultaneous EHV ac-dc
is supplied to a location very near to a furnace power transmission through the same
or to a work place having very high ambient transmission line has been presented.
temperature, rectification of 3-phase supply is Expressions of active and reactive powers
not possible at that location using associated with ac and dc, conductor voltage
semiconductor rectifier. In such place level and total power have been obtained for
simultaneous ac-dc transmission is steady state normal operating condition. The
advantageous. possible applications of the proposed scheme
In air craft 3-phase loads are generally fed may be listed as: loading a line close to its
with higher frequency supply of about 400Hz thermal limit, improvement of transient and
and separate line is used for dc loads. Skin dynamic stability and damping of oscillations.
effect restricts the optimum use of distribution In LV and MV distribution system the
wires at high frequency. Simultaneous ac-dc proposed scheme may be applied in a
power transmission reduces both volume and workplace having high ambient temperature or
weight of distributors. fed with high frequency supply or with PV
9. Another possible application is the solar cells. Only the basic scheme has been
transmission of dc power generated by PV presented with qualitative assessment for its
solar cells directly to remote dc loads through implementation. Details of practical adaptation
3-phase ac line. In all cases of separate dc are beyond the scope of the present work.
supply filter networks are not required.

References:

1. Padiyar.’HVDC Power Transmission System.’ Wiley Eastern, New Delhi, 1993.

2. I W Kimbark.’Direct Current Transmission Vol-I.’Wiley, New York, 1971.


3. Comtrol Of Active And Reactive Power Flow In IEEE Magazin.

You might also like