Basics of 3-phase Induction Motor (part 1)


Asif Eqbal

Basics of 3-phase Induction Motor

Introduction
This article will deal with those concepts of 3 phase induction motor which are essential prerequisite for proper
selection, procurement, installation and maintenance of the same. Before any actual discussion on motor is
started It will better to have a comparison of starting behavior of induction motor and transformer because as per
the equivalent circuit representation a 3 phase induction motor is generalized transformer.
It is assumed that readers are already familiar with the elementary concept of principle of operation and
construction of three phase induction motor.
What is the fundamental difference in working principle of induction motor and transformer? That is even
though the equivalent circuit of motor and transformer is same rotor of motor rotates where as secondary of
transformer do not.
Induction motor is a generalized transformer. Difference is that transformer is an alternating flux machine while
induction motor is rotating flux machine. Rotating flux is only possible when 3 phase voltage (or poly phase)
which is 120 degree apart in time is applied to a three phase winding (or poly phase winding) 120 degree apart in
space then a three phase rotating magnetic flux is produced whose magnitude is constant but direction keeps
changing. In transformer the flux produced is time alternating and not rotating.
There is no air gap between primary and secondary of transformer where as there is a distinct air gap between
stator and rotor of motor which gives mechanical movability to motor. Because of higher reluctance ( or low

permeability) of air gap the magnetizing current required in motor is 25-40% of rated current of motor where as in
transformer it is only 2 -5 % of rated primary current.
In an alternating flux machine frequency of induced EMF in primary and secondary side is same where as
frequency of rotor EMF depends on slip. During starting when S = 1 the frequency of induced EMF in rotor and
stator is same but after loading it is not.
Other difference is that the secondary winding and core is mounted on a shaft set in bearings free to rotate and
hence the name rotor.
If at all secondary of a transformer is mounted on shaft set at bearings the rate of cutting of mutual magnetic flux
with secondary circuit would be different from primary and their frequency would be different. The induced EMF
would not be in proportion to number of turns ratio but product of turn ratio and frequency. The ratio of primary
frequency to the secondary frequency is called slip.
Any current carrying conductor if placed in magnetic field experience a force so rotor conductor experience a
torque and as per Lenzs Law the direction of motion is such that it tries to oppose the change which has caused
so it starts chasing the field.
Top

Power flow diagram of induction motor


Stator input electrical power = A
Stator losses = B
Rotor losses = C
Mechanical output = P
A ( B + C ) = P
Roughly B= 0.03A, C= 0.04A
A 0.07A = P
0.93A = P, Hence efficiency = (P/A) x 100 = 93%

Power flow diagram of induction motor

Top

Why LT motors are delta connected and HT motors are star connected?
Reason is techno commercial.

1. In star, phase current is same as line current. But phase voltage is 1/1.732 times line voltage. So
insulation required in case of HT motor is less.
2. The starting current for motors is 6 to 7 times full load current. So start-up power will be large if HT motors
are delta connected. It may cause instability (voltage dip) in case small Power system. In starred HT motor
starting current will be less compared to delta connected motor. So starting power is reduced. Starting
torque will also be reduced. (It will not be a problem as motors are of high capacity.)
3. Also as current is less copper (Cu) required for winding will be less.
4. LT motors are delta connected.
1. Insulation will not be problem as voltage level is less.
2. Starting current will not be problem as starting power in all will be less. So no problem of voltage
dips.
3. Starting torque should be large, as motors are of small capacity.

Comparison of star and delta motor starting

LT motors have winding delta connected.


1. In case it is having star delta starter than they are started as Star connected motor.
2. After it attains 80% of synch speed the changeover takes place from star to original configuration delta.
3. In star the voltages across the windings are lesser that is 1/1.732 times that available in delta so current is
limited.
4. When it goes to delta again voltage is full line voltage so current increase even though it is lesser than the line
current it remains higher than the line current drawn in star connection at reduced voltage. So cables for motor
are sized for this current that is what it draws in delta connection.

References:
1. NEMA MG-1.
2. Industrial Power Engineering and Application Hand Book by K C Agarwaal.
3. Industrial Power System Hand Book by Shoaib Khan.
4. Theory and Calculation of Alternating Current Phenomena by Charles Proteus Steinmetz
5. Motor protection relay (MM30) manual from L&T

Asif Eqbal - Bachelor of Engineering in Electrical & Electronics engineering, from Manipal
University, (Karnataka), India in 2006. Presently involved in the design of EHV outdoor
substation and coal fired thermal power plants for more than seven years. Motto of joining EEP
as a contributor is to share my little engineering experience and help the budding engineers in
bridging the conspicuous gap between academics and Industrial practice. If you have
knowledge, let others light their candles with it, so that people who are genuinely interested in
helping one another develop new capacities for action; it is about creating timeless learning processes".