Power Analytics Corporation
2
Restricted to Power Analytics Partners | Do Not Distribute
B.
H.
I.
Increased the limit of Variable shown in the results for generalmodels/AVR/Governor/PV models
Enhanced simulation window to show information about events occurring
Showed more decimal numbers for PU values in order to generate smoother
curves
On/Off status of General Models based on device status in different scenarios
Added Signal monitoring tab feature to General Models
The evolution towards Paladin DesignBase 5.0 Service pack 2 represents millions of dollars
and many years of development effort, not only by our on-staff development team, but
by users like you who provide us with valuable guidance on new features and functions.
We thank you for your continued business, and for making Paladin DesignBase the most
effective and productive modeling platform in the mission-critical arena.
5
Restricted to Power Analytics Partners | Do Not Distribute
2)
3)
4)
Add new DC Source for calculations and build the estimation method based on IEC61660. ............... 14
5)
B.
2)
3)
4)
Enhancement for the PDC "Restore View" icon in PDC toolbar ............................................................ 20
5)
6)
On/Off for Designed Load Amp part of Bus Curve in PDC TCC .............................................................. 21
7)
8)
Show coordinates when moving each PDC curve's arrow in PDC program .......................................... 24
9)
Add "delete" option for elements in PDC study to prevent Appending to wrong Study ...................... 24
10)
11)
12)
Add a searching feature for equipment name in multiple PDC studies ............................................ 27
13)
14)
15)
C.
Increase the Arc flash limitation limit on looking for upstream protection devices ............................. 32
2)
Enhancing the Arc flash calculation wizard based on selected bus ....................................................... 33
3) Arc flash labels should always present System Voltage rather than Load Flow voltage when the SC
Calculated by LF pre-fault voltage ................................................................................................................. 33
D.
E.
2)
2)
F.
2)
3)
G.
H.
2)
3)
I.
2)
Add two new Text Report browser for Adobe Reader and XPS Viewer ................................................ 52
3)
Add Backup/Restore options for project folder/library files and both together................................... 53
4)
5)
Create a Upgrade all the PA sample files icon after installing DB5 SP2 ............................................. 55
6)
7)
8)
Add Case Study list box, Add icon and Delete icon in Short Circuit toolbar .......................................... 58
9)
7
Restricted to Power Analytics Partners | Do Not Distribute
Select number of buses from the drawings (In this example BUS 1, PPC3, G1)
Open SC Option dialog box and see which buses were selected (In this example
BUS 1, PPC3, G1) from the drawings in the list, since the default option From
Current Page is selected.
8
Restricted to Power Analytics Partners | Do Not Distribute
Switch to option From Saved to ensure saved buses are showing in the list (In this
example BUS 1, PPC3, G1).
Switch back to From current Page and the buses selected from the drawings will
be displayed (In this example buses A4P, A7P, A8P, BUS 1, ).
Add buses from All Filtered Buses list (In this example A3CP, A4P, BUS 1, PPC3, G1)
and click Save button.
Switch to option From Saved and notice the buses in the list stay the same.
9
Switch back to From current Page and the buses selected from the drawings
are back on the list (In this example BUS 1, PPC3, G1).
Switch to option From Saved again, click OK to go back to the drawing and you
will see the nodes A3CP, A4P are selected besides BUS 1, PPC3, G1.
10
Restricted to Power Analytics Partners | Do Not Distribute
Select Selected Buses option and select some buses (In this example BUS 1, Bus
2, G1, G2)
Select the Export button and export the list to the text file (SCBusList.txt)
This file will keep the selected bus list which you may import anytime to do SC
study.
11
13
Restricted to Power Analytics Partners | Do Not Distribute
4) Add new DC Source for calculations and build the estimation method based on
IEC61660.
This new feature includes a new model for DC sources according to IEC61660:
14
Restricted to Power Analytics Partners | Do Not Distribute
6 1000
(. 13 660 1)
Iscmax can be entered directly or calculated from Rated Amps and SC factor Ksc.
----------------------Rectifier(s) Data
----------------------AC Circuit Side
DC Circuit
System Actual
Rated -------------------- ------------Bus Name
V
V
Cd
A
Z-mOhm R-mOhm L-mH R-mOhm L-mH
------------------------ ------ ------ -- ------ ------ ------ ------ ------ -----DCS
250
250 DS
2000 4.0760 2.3541 0.0106 98.68 0.0300
The contribution of dc Source DCS Ik= 3000 A ,which will match the value in the editor as
expected.
5) New DC Source for Classical Methodology
A new DC source which has discussed before is also verified to cover DC Classical Short
Circuit method.
The editor of this new DC source model includes the same data as the rectifier.
16
Restricted to Power Analytics Partners | Do Not Distribute
17
Restricted to Power Analytics Partners | Do Not Distribute
Right Click
The coordinate
symbol will be
shown
The new multiple coordinate symbols can be created by right-clicking the Insert
Coordinate menu item on TCC window and then selecting Yes in the following dialog
box.
Right Click
Multiple
coordinate
symbols
19
Restricted to Power Analytics Partners | Do Not Distribute
20
Restricted to Power Analytics Partners | Do Not Distribute
Show/Hide
Symbols
Catalogs
After clicking the Show/Hide Symbol Catalogs icon again, the catalog window will
disappear.
6) On/Off for Designed Load Amp part of Bus Curve in PDC TCC
When unchecking the Hide Design Load Amps check box in the following Bus Curve
dialog box, the Bus design load amps will be shown in TCC view below. This option is
designed to show or hide the Bus design load amps in TCC view.
21
Restricted to Power Analytics Partners | Do Not Distribute
Design
Load Amp
Curve
22
Restricted to Power Analytics Partners | Do Not Distribute
23
Restricted to Power Analytics Partners | Do Not Distribute
Watch
coordinate
values
9) Add "delete" option for elements in PDC study to prevent Appending to wrong Study
In a PDC single line page, after selecting the elements in a PDC study then pressing
Delete button, the following dialog box will be shown to ask whether or not to delete the
study.
24
Restricted to Power Analytics Partners | Do Not Distribute
25
Restricted to Power Analytics Partners | Do Not Distribute
Note: If selecting a branch symbol to append, two buses related to the branch will
automatically be selected to append to a PDC study.
11) Add options for deleting one or more PDC studies
After clicking the Delete the Current Study icon in the PDC toolbar, the following dialog
box will be shown from which the user can select one or more PDC studies to delete.
26
Restricted to Power Analytics Partners | Do Not Distribute
12) Add a searching feature for equipment name in multiple PDC studies
After clicking Edit/Search Equipment in PDC Studies menu item in PDC toolbar, the
following dialog box will be shown. All the selected equipment on the left side is
included in the selected PDC study on the right side.
When searching for one or more equipment name in multiple PDC studies in the above
27
Restricted to Power Analytics Partners | Do Not Distribute
13) Creating Crosshair for PDC curves (including value representation on axis)
By holding down the arrow handle of the coordinate symbol and moving it, the following
crosshair will automatically be shown. By releasing the arrow handle of the coordinate
symbol, the crosshair will automatically disappear.
28
Restricted to Power Analytics Partners | Do Not Distribute
The coordinate values will be shown in Toolbar and TCC view below.
29
Restricted to Power Analytics Partners | Do Not Distribute
30
Restricted to Power Analytics Partners | Do Not Distribute
31
Restricted to Power Analytics Partners | Do Not Distribute
1) Increase the Arc flash limitation limit on looking for upstream protection devices
The maximum fault contribution levels will be available for users to set. Its default value is 10
and can be increased up to 20 branches in upstream circuit. The user can set this value
based on his protection strategy and size of the network and the calculation speed on the
computer. This will update short circuit and PDC studies for contribution levels
automatically. This setting means every bus/equipment should be protected by a device in
at most 20 levels up branches.
32
Restricted to Power Analytics Partners | Do Not Distribute
3) Arc flash labels should always present System Voltage rather than Load Flow voltage
when the SC Calculated by LF pre-fault voltage
When the Short Circuit Calculation uses Power Flow Voltage as pre-fault voltage, then
all calculations will be based on Load flow voltage as a pre-fault and the Arc-Flash
Engine would also use this voltage which might be different from system voltage. To keep
the system data consistent, Arc-Flash labels should present System Voltage rather than
what the user considered in SC calculations. Labels are always present in System Voltage
but Arc-Flash report still will show LF voltage as a pre-fault voltage.
33
Restricted to Power Analytics Partners | Do Not Distribute
34
Restricted to Power Analytics Partners | Do Not Distribute
35
Restricted to Power Analytics Partners | Do Not Distribute
36
Restricted to Power Analytics Partners | Do Not Distribute
Modelling in DesignBase:
37
Restricted to Power Analytics Partners | Do Not Distribute
As shown in the drawing OCC-4WI is an inverter with two components connected to the
DC and AC networks separately. The inverters DC Component which is connected to
the DC side should be dragged and dropped from the DC catalog.
38
Restricted to Power Analytics Partners | Do Not Distribute
The bi-directional model includes two different modes: a rectifier mode and an inverter
mode. Each mode is modeled by different components for AC and DC sides separately
and should be activated individually by defining the two different scenarios.
The inverter mode includes the same components which are described above by using
the same name for both components. (in this example the AC Source and it is
deactivated in the current scenario were used)
In the rectifier mode the DC side is modeled with a DC Source (rectifier) and the AC side
is modeled with an AC load which can be dragged from AC catalog by looking for
Rectifier Symbol. Both components should have the same name. ( This example used DC
Source).
The AC component is a Bus for Short Circuit Studies. For load flow study its kvar should be
39
Restricted to Power Analytics Partners | Do Not Distribute
The DC component is also set as a DC Source on the DC Side and can be dragged from
the DC catalog by looking for the DC source.
For Short Circuit Studies, its SC Current can be limited and is estimated by AC impedance
from the Rated Parameters per IEC61660 standard. For load flow standards the DC
Control should be set either to Current Control or Voltage Control and by using the
same name as the AC side Rectifier Load it can pass the control parameters to the AC
side.
40
Restricted to Power Analytics Partners | Do Not Distribute
- DC-DC Converter
As shown in the drawing OCC-DCDC is a DC converter with two components connected
with LV=120 V and HV=240V sides.
A DC-DC converter can be dragged from the DC catalog. There is no meaningful data
for the branch since the two voltage networks are isolated from each other in the real
world.
41
Restricted to Power Analytics Partners | Do Not Distribute
The HV Source can be dragged just by selecting a DC Source from the DC catalog. Its
Short Circuit Current can be limited by using an estimation of AC impedance from the
Rated Parameters per IEC61660 standard. For the load flow it should be set to DC
Current Control with zero Amps in order to pass the control from LV to HV
Select Current Control and set Order =0 to transfer the power from LV side.
42
Restricted to Power Analytics Partners | Do Not Distribute
AC Source is switched off and DC Source is activated to pass the power from AC to DC.
Inverter Mode
DC Source is switched off and AC Source is activated to pass the power from DC to AC.
43
Restricted to Power Analytics Partners | Do Not Distribute
44
Restricted to Power Analytics Partners | Do Not Distribute
45
Restricted to Power Analytics Partners | Do Not Distribute
46
Restricted to Power Analytics Partners | Do Not Distribute
User can select View Graphical Results and under the UDM tab (new feature to show user
defined model variables) he/she will be able to select desired number of signals to be
plotted.
47
Restricted to Power Analytics Partners | Do Not Distribute
48
Restricted to Power Analytics Partners | Do Not Distribute
49
Restricted to Power Analytics Partners | Do Not Distribute
Miscellaneous Features
The port number can be changed and can be changed back after clicking the Default
button in the following dialog box. The default port number is 27002 when using the license
server.
50
Restricted to Power Analytics Partners | Do Not Distribute
By clicking the Show License Information button in the client license manager dialog box,
the complete descriptions for the installed DB license features and package name will be
shown as follows:
51
Restricted to Power Analytics Partners | Do Not Distribute
Two new formats including Adobe Reader and XPS Viewer have been added. The current
settings such as font size, font color, watermark, and so on for Adobe Reader and XPS
Viewer can be changed when clicking the Change Current Settings button.
For example, when changing the font color to blue and watermark to DRAFT, saving the
settings and then selecting Adobe Reader as a browser, the PF report will be created as
follows:
52
Restricted to Power Analytics Partners | Do Not Distribute
3) Add Backup/Restore options for project folder/library files and both together
When selecting File/Backup Library Files in DB5 SP2, the following dialog box will be
shown. All the selected library files can be zipped to a backup file. The default path to the
backup files is C:\DesignBase5\BackUp. All the selected options from the Data folder and
can also be browsed from different locations.
53
Restricted to Power Analytics Partners | Do Not Distribute
When selecting File/ Restore Library Files in DB5 SP2, the following dialog box will appear.
All the files in the selected zip file will be unzipped to the selected folder when clicking
Restore button in the following dialog box.
54
Restricted to Power Analytics Partners | Do Not Distribute
5) Create a Upgrade all the PA sample files icon after installing DB5 SP2
After installing DB5 SP2, a Upgrade all the PA sample files icon is created. By clicking this
icon, all the sample files under c:\designbase5\samples folder will be upgraded:
55
Restricted to Power Analytics Partners | Do Not Distribute
The user can select and copy/paste in the Text Editor Spreadsheet:
56
Restricted to Power Analytics Partners | Do Not Distribute
57
Restricted to Power Analytics Partners | Do Not Distribute
8) Add Case Study list box, Add icon and Delete icon in Short Circuit toolbar
If the Case Study for the Options with @ in the SC option dialog box checked, the Case
Study list box, Add icon, and Delete icon will be created in the Short Circuit toolbar as
follows:
58
Restricted to Power Analytics Partners | Do Not Distribute
The case study name is listed in Case Study list box. Different case study names can be
selected. When clicking Add icon (or +), a case study can be added. When clicking
Delete icon (or X), a case study can be deleted.
By unchecking Case Study for the Options with @ in the SC option dialog box, the Case
Study list box, Add icon, and Delete icon will disappear in Short Circuit toolbar as follows:
59
Restricted to Power Analytics Partners | Do Not Distribute