You are on page 1of 2

List of Protective Relays

List of Protective Relays proposed


A. 11 kV Switch gear - 1 no
A.1 Incomer from Grid (2 nos)
A.1.1 IDMT over current and earth fault relay - CDG 31
A.1.2 Directional over current and earth fault relay - CDD 21 - 3 nos
A.2 Incomer from Turbo Alternator (1 no)
A.2.1 Inverse time voltage restraint over current relay - CDV 62
A.2.2 Under voltage relay - VAGM 22 + VTT 11
A.2.3 Low forward power interlock - WCD 13 + VTT 11
A.2.4 Rotor earth fault relay (alarm/trip) - VAEM 21 + VTT 11 and CAEM 33
A.2.5 Differential relay - CAG 34
A.2.6 Field failure relay - YCGF 11 + VAG 21 + VTT 11
A.2.7 Reverse power relay - WCD 11 + VTT 11
A.2.8 Negative phase sequence relay (alarm/trip) - CTN 31
A.2.9 Standby earth fault relay (with 1200/1 A CT in neutral earth lead) - CDG 12
A.2.10 Over voltage relay (alarm/trip) - VAGM 22 + VTT 11 - 2 sets
A.2.11 Over current relay (alarm) - CTU 12
A.2.12 Under frequency relay (alarm/trip) - FTG 11 + VTT 11 - 2 sets
A.2.13 Supervision of protection and AVR PTs - VAGM 61 + VAA
A.2.14 Stator temperature protection (alarm) - 2 nos temperature scanner
A.2.15 Supervision of synchronisation - SKE and Synchroscope
A.3 Bus coupler between turbo alternator bus and grid bus
A.3.1 Reverse power relay - CCUM 31
A.4 6.3 MVA transformer feeders (5 nos)
A.4.1
A.4.2
A.4.3
A.4.4
A.4.5
A.4.6
A.4.7

Combined instantaneous short circuit, IDMT over current and instantaneous earth fault relay - CDAG 51
Differential relay - DDT 32
Transformer oil level protection (alarm)
Buchholz relay (alarm/trip)
Oil temperature protection (alarm/trip)
Winding temperature protection (alarm/trip)
HV/LV inter-trip relay - VAA

A.5 1.6 MVA transformer feeders (14 nos)


A.5.1
A.5.2
A.5.3
A.5.4
A.5.5

Combined instantaneous short circuit, IDMT over current and instantaneous earth fault relay - CDAG 51
Transformer oil level protection (alarm)
Buchholz relay (alarm/trip)
Oil temperature protection (alarm/trip)
HV/LV inter trip relay

A.6 Other bus couplers (2 nos)


A.6.1 Synchronisation check relay - SKE
A.7 Capacitor feeders (4 nos)
A.7.1 Combined instantaneous short circuit, IDMT over current and instantaneous earth fault relay - CDAG 51
A.7.2 Neutral displacement relay - VDG 14
A.7.3 Under voltage relay - VDG 13

A.7.4 Over voltage relay - VDG 11


B. 3.3 kV Switch gear (2 nos)
B.1 Incomer (2 nos)
B.1.1 IDMT over current and earth fault relay - CDG 31
B.1.2 Standby earth fault relay - CDG 12
B.1.3 HV/LV inter trip relay - VAA
B.2 Bus coupler (1 no)
B.2.1 Synchronisation check relay - SKE
B.3 Motor Feeders (3.3 kV)
B.3.1 Comprehensive motor protection relay with instantaneous over current, earth fault etc - CTMM 501-510
B.3.2 Under voltage relay - VDG 13
C. MV power control centres
C.1 Incomers (2 nos)
C.1.1
C.1.2
C.1.3
C.1.4
C.1.5
C.1.6

Instantaneous short circuit release - English Electric make


Thermal overload release
Earth fault relay - CDG 14
Restricted earth fault relay - CAG 14
Standby earth fault relay - CDG 12 (with 500/1 A CT in neutral earthing lead)
HV/LV inter trip relay - VAA

C.2 Motor Feeders (MV, 55 kW and above)


C.2.1 HRC fuses for short circuit protection
C.2.2 Comprehensive motor protection relay - CTMFM 401-410 and VAA 12
C.3 Feeders to MCCs/Switch boards
C.3.1 HRC fuses for short circuit protection
C.3.2 Single phasing protection (alarm)
D. Motor feeders (MV, 45 kW and below)
D.1 HRC fuses for short circuit protection
D.2 Bimetal overload relay with built in single phasing preventor
E. Emergency Diesel Generator Set (625 kVA, 415 V)
E.1
E.2
E.3
E.4
E.5
E.6
E.7

Voltage restraint over current IDMT relay - CDV 62


Differential relay - CAG 34
Standby earth fault relay - CDG 12 (with 200/1 A CT in neutral earthing lead)
Under voltage relay (alarm) - VDG 13
Over voltage relay (alarm) - VDG 11
Under/over frequency relay (alarm) - Static type
Bus fault protection in bus coupler panel - CAG