Professional Documents
Culture Documents
...
/' *v
r^"\^'
V *&.-
^t
Andrew Burbelo
John M. Tobias
CECOM Safety Office
May 1996
DISTRIBUTION STATEMENT
Approved for public release;
distribution is unlimited.
CECOM
U.S. Army Communications-Electronics Command
CECOM Safety Office ATTN: AMSEL-SF-SEP
Fort Monmouth, New Jersey 07703-5024
NOTICES
Disclaimers
The findings in this report are not to be construed as an official Department of
the Army position, unless so designated by other authorized documents.
The citation of trade names and names of manufacturers in this report is not to
be construed as official Government endorsement or approval of commercial
products or services referenced herein.
ftvm Approved
_ ,jn!^TIT^ii#<tron oi .MorTnjtion^ewm!it*aT^verQe i f>oor per rwpome. including the time tor reviewing instructions, arching existing o*"**^"'
^n?i'2SSSwSSZfl
.2SSS2j7n?SSSnq !coH*ci.on ot ,ntormK,n. Ser^eommerm reg.rt.ng m burteneWf or .mother *
9*tnenna
and m,frL,n'_'>tl_^."^^;^_
. twuana
Z..^ om
,* OurOnt.
*..,,*. to
n wawtinc.
wMmnM Moiarm
MMdiiutmn StrvKt.
Servicei. Oirtnoro
Directorate for
for Inform*
Information Opwioom
Operations nd
and JMoro.
Reoom. 121S
1215 Jrftmon
Jettenon
V2Z^~?SZ^^^J^vjaoi
om to.
tlZX I w!?,Sg5i!!^MMTiS a OH Of M,^Sm .no Bodo. P.Pefwo MUM. PTOK (OTWnre). WMtngum. DC 20.
1. AGENCY USE ONLY (Xeaw *r>W
2. REPORT DATE
May 1996
Technical Report
5. FUNDING NUMBERS
8. PERFORMING ORGANIZATION
REPORT NUMBER
CECOM-TR-96-2
10. SPONSORING/MONITORING
AGENCY REPORT NUMBER
This pamphlet is a guide to proper earth grounding methods and procedures for use
with tactical systems. It describes different earth grounding systems and provides
guidance on the proper methods for their installation. Earth grounding helps to
protect personnel and equipment from electrical faults, power surges, and other
surges and transients. Earth grounding also helps reduce circuit noise and other
transmission interference that can degrade communications-electronics system
performance. The instructions contained in this pamphlet, not often found in
technical manuals, will help in setting up effective and safe earth grounding
systems for tactical equipment and shelters.
Unclassified
NSN 7S4O-01-280-S500
Unclassified
Unclassified
46
16. PRICE CODE
20. LIMITATION OF ABSTRACT
UL
Standard Form 298 (Rev. 2-89)
fmcnDW Or AN Std. Z3-l
298-102
CONTENTS
10
11
12
12
13
16
17
18
21
Appendixes:
A. Grounding Systems and the Confusion about
Grounding
29
B. Additional Documentation
32
C. The Threat
33
34
35
37
G. Definitions
38
H. Checklist
39
It is important to note that earth grounding is only a part of the total ground
system. Equally important to the earth grounding system is the need to interbond all equipment and power supply enclosures through the equipment
grounding conductor (green wire), as well as the need to bond the power supply
connection point
fl
factors that affect path impedance include wire size, length, shape and surface
area.
It's important to consider the following when choosing and installing the earth
grounding wire:
1) The Earth Grounding Conductor must be as large as possible: at least 6
AWG. This gives it the mechanical strength necessary to withstand the severe
mechanical forces subjected during lightning strikes, as well as the everyday
wear and tear (being kicked or stepped on, setup and teardown, etc.). Since high
frequency currents tend to pass over the surface of wires as opposed to through
them, wires such as flat straps that have larger surface areas than round wires
can lessen path impedance.
2) The wire should be copper or copper clad aluminum. Coatings on the
wire (such as nickel) or insulation are acceptable and help to reduce corrosion.
Steel or stainless steel cables can be used only temporarily (systems frequently
on the move) and where frequently inspected for corrosion.
3) The wire should be continuous between the equipment and earth
grounding electrode; do not splice. Ensure that the grounding wire is not
damaged or heavily corroded. If crimped or brazed connectors are provided at
the wire ends, check for damage or looseness.
4) Run the conductor as straight and short as possible. Earth Grounding
Conductors should always run in a downward direction; do not run the
conductor up and over obstacles.
5) Minimize any twists, loops, or sharp bends. Any kinks should be
straightened out. Uncorrected, such conditions will increase the conductor's
impedance and cause failures under certain conditions.
2.2 Connections:
Frequently, connection points can be the source of problems. Though
grounding connections can "look" okay, they may fail if loose or corroded. It's
important to consider the following when connecting the earth grounding wire
to the equipment or earth grounding electrode:
1) Clamp or bolt the connections tightly to prevent loosening over time. Use
a lockwasher where nuts or bolts are used. Do not overtighten the connection to
the point where the conductor strands are damaged.
3ROUH0 ftOO CU
2) When attaching, ensure that the bonding surfaces are free of paint,
corrosion, grease, or dirt.
3) Protect the connection points from corrosion and inspect regularly.
4) Connecting dissimilar metals, especially copper & aluminum or copper &
galvanized parts (zinc plated surfaces or washers) can cause corrosion at the
bonding point due to galvanic action. Avoid connecting such dissimilar metals
together. Otherwise, frequently inspect and clean as necessary.
5) Never twist or tie a ground wire around a ground rod. If a bolt is not
provided and a clamp is not available, the ground strap should be bound to the
ground rod with at least 24 tightly wound turns of stripped telephone wire or
other bare wire. This connection should then be taped to block out moisture.
See figure below.
GROUND STRAP
IMUMBSCHEW
grounding plate
WITH
73 AMP COPPER CLIPS
Quality of Ground
Very good
Good
Poor
Very Poor
Suggested Earth
Grounding Electrode
Ground rod, SWGK
Ground rod, SWGK or
plate
Buried pipes, building
frame, or other metal
object or a ground plate
or several ground rods
electrically connected
together
Same as above *
* Under poor or very poor conditions, you'll have to take special steps to
establish and maintain electrical conductivity explained in section 9.
3.2 General recommendations and precautions:
1) Never use metal natural gas lines for earth grounding. Never use buried
tanks containing flammable liquids for earth grounding.
2) When choosing a location for the earth grounding electrode, keep it away
from locations having normal pedestrian traffic. During an electrical storm or a
fault condition, dangerous voltages induced at and near the earth grounding
terminal could be hazardous to personnel (see Appendix D).
3) Aluminum should not be used as an earth grounding electrode.
4) Prior to connecting the earth grounding system, ensure that power to the
system is off. This is not necessary if the system is initially self-powered, such
as with an onboard generator.
5) Never lay system power cables or signal cables over the location of the
earth grounding electrode, grounding conductors, or SWGK cable. During a
fault condition, step potentials at and near these components may be induced on
collocated signal and power cables.
6) Install the earth grounding electrode at locations where ground will
receive rain water (i.e., outside the drip line of shelters, etc.).
7) Where air conditioning units are operated near grounding electrodes, earth
grounding resistance can be further improved by routing the air conditioner's
condensation water to the grounding electrode location via a tube or hose.
8) Wear gloves to protect hands when handling or inspecting grounding
electrodes, cables, and connections. Wear safety goggles when driving ground
rods to protect from flying metal chips.
4. GROUND ROD INSTALLATION
Take the following steps when installing a ground rod:
a. Clean the rod to remove all grease, oil or paint. Wear a safety glove to
protect your hand from sharp metal fragments.
b. Dig a hole at least 12 inches deep and 36 inches across.
c. Drive the rod through to the moist subsoil. The ground rod should be
installed straight if possible, but can be installed up to an angle of 45 degrees.
Allow about 3 inches of the rod to protrude above the bottom of the hole. When
installing a multiple section ground rod, ensure that top section is tight against
the lower rod to prevent damage to the coupling sleeve threads. Similarly, the
driving bolt should be tight against the lower rod. Be careful not to hit the
threaded end of the rod section with the hammer, or damage the threads in any
other way. When possible, use a driving hammer when installing a multiple
section ground rod.
f
OAMNOKM
IUT
VOm A0A1HST
TWOBOUNO
00
TOT SECTION
MUOTK
TOHTMAMST
IWlOWEft
wcnoN
fl)
@
GROUND ROD
DRIVING ROD
COUPLING SLEEVE
GROUND RODCLAMP
components and make sure that they are clean and not damaged. Sharp bends
and kinks must be avoided in the cable. An important step here is to maximize
the spacing between the individual stakes. Wear gloves when handling the steel
cable as loose strands can cause cuts. Attach the connector end of the cable to
the equipment grounding lug.
b. Begin with the stake closest to the grounding stud. Pull the cable taught.
Twist stake 30 to 45 degrees. Drive stake until top is flush with the ground.
Continue until all stakes are driven into the ground. Driving the stakes fully into
ground and slightly twisting them helps to ensure a tight connection between the
stakes and cable.
c. Attach the two jumper cables. Connect one from the front bumper of the
vehicle to the center of the cable, and the other from the rear bumper to the end
of the grounding cable. These cables are provided to improve SWGK
survivability and performance during high current events associated with
lightning. It is not necessary to scrape paint to improve clip contact in this case
since, under high current conditions, the paint will vaporize. However, the
grounding lug end must still be attached to a stud or other location free of paint.
6. GROUND PLATE INSTALLATION
Where soil conditions are poor or very dry, a ground plate may work better than
a ground rod.
a. Select any clean, bare metal plate or sheet that's at least 2 square feet of
surface contact with ground as described in section 2.3(2). Note that the larger
the plate is, the lower the resistance will be to ground; this is important to
consider where grounding in poor soil (some standards recommend a 3-foot by
3-foot plate). Select a metal bolt, nut and lock washer and drill a hole in the
center of the plate just large enough for the bolt. Fasten an appropriate earth
grounding conductor to the plate. Make sure the connection is clean and tight.
b. Dig a hole so that the plate can be buried vertically at 5 feet below the
surface. Though some procedures recommend installing the plate horizontally,
vertical installation ensures good soil contact on both sides of the plates. Pour a
mixture of water and salt into the soil around the plate to further increase soil
conductivity if necessary. See section 9 for information on improving soil
conductivity.
c. Connect the other end of the grounding conductor to the equipment, keeping
the path as straight as possible.
10
SALT
WATER
GROUND
STRAP
11
4) Sodium Chloride
5) Potassium Nitrate
treatment ofsoil
Prior to using any such chemicals in the soil, you should verify that there are no
environmental restrictions against using salt for such applications for the region
or area.
10. TIPS FOR GROUNDING IN POOR SOIL CONDITIONS AND
ENVIRONMENTS
One of the most important factors that must be stressed is that for any of the
areas listed below, advanced thought must be given to the placement of
equipment from an earth grounding perspective. Although mission
requirements may predetermine areas for setup, locating equipment on one side
of a camp as opposed to the other, or even moving the equipment a dozen feet
can sometimes drastically improve earth grounding installation and
effectiveness. Where grounding resistance is poor, additional emphasis must be
placed on interbonding equipment enclosures to limit hazardous voltages
developed between such equipment enclosures which can be contacted by
personnel (see section 11).
When your site does not have fine top soil, clay, loam, or shale, you must
13
TOOLAPART
t FT GROUND BOO
13 FT. GRODNO STRAPS
HMMOM
K5iE
15
10.5 Tropics
Install the ground rod or SWGK as described in sections 4 and 5. Because of
the constant high humidity, extra measures need to be taken to ensure that the
strap connection at the equipment is clean and dry to prevent corrosion. Cover
the connection of the ground with waterproof tape and check it every day.
10.6 Arctic
Cold substantially increases soil resistance and also, earth grounding impedance.
Hence, it is important to drive ground rods or install ground plates below the
area's frost line, if possible. Try to ground to an extension of a buried metal
object such as an underground pipe or a building frame. If no buried object is
available, drive in several ground rods as deeply as possible. Space them at
least two rod lengths from each other. Alternatively, a trench can be dug to
insert a horizontal rod or conductor, as discussed in section 8. The trench
should be filled with salt water which will improve conductivity when frozen.
11. COLLOCATING SHELTERS AND STAND-ALONE EQUIPMENT
During thunderstorms, lightning flashover or arcing can occur between two or
more unconnected or poorly connected metal structures that are located close to
each other. Flashover between objects can cause damage to the objects and
cause lethal voltage on the ground in the vicinity of these objects. To avoid
lightning flashover, separate equipment shelters, antenna masts, and other metal
structures at least 6 feet from each other. Otherwise, the objects must be bonded
together using a heavy copper cable, at least 6 AWG. The best way to achieve
this is by interconnecting each shelter's ground rod (electrode) with the heavy
copper cable along the ground. The cable lengths should be as short and as
straight as practical.
Equipment and shelters located within armslength of each other (6-8 feet) must
be interbonded to eliminate any hazardous voltages that may develop between
such enclosures should a fault occur in one equipment. Personnel can sustain
much worse injuries when contacting two metal surfaces at different potentials
with bare hands (a low resistance path provided across the chest) than by
contacting a surface energized to ground while wearing boots (a high resistance
path to earth).
Furthermore, where electronic equipment shelters are located within 25 feet of
each other, it is recommended that the individual earth grounding electrodes be
interconnected using a heavy copper conductor (6 AWG minimum) run along
the ground. This helps to create an earth grounding electrode system having an
overall lower grounding resistance, and results in other benefits as well.
16
It's important to note that the Equipment Grounding Conductor (the green wire
you usually see running with your power lines) is sized to handle primarily
power related faults. Although the Equipment Grounding Conductor will help
to discharge some of the current from lightning related events, its small relative
size and the way it's run (twists, turns, kinks, etc.) can create a higher
impedance path that will fail during a lightning event. For this reason,
collocated shelters should be interconnected using an independent bonding
conductor as described above. The Equipment Grounding Conductor should
never be relied upon for such purposes.
12. HOW GOOD IS A GOOD EARTH GROUND REFERENCE?
When it comes to earth grounding installation, the greater the effort that is
applied - the greater the level of safety that is obtained. It is this greater level of
safety that can make the difference between a soldier receiving a shock or being
electrocuted. The Army Safety Management Information System lists a number
of accidents where improper grounding contributed to fatalities. On the other
hand, reports also exist where soldiers walked away unharmed because proper
and effective grounding limited the hazardous voltages contacted by the soldier
during the fault condition.
It is difficult to assign a specific resistance value that must always be achieved.
Various codes and handbooks recommend anywhere from 10 to 25 ohms
resistance. MIL-HDBK-419, Handbook of Grounding, Bonding, and Shielding
recommends an earth grounding resistance of 10 ohms for tactical, mobile
systems. However, experience has shown that this requirement is often difficult
to achieve in a high-mobility, tactical environment with only one or two ground
rods installed. When making the decision as to how extensive the earth
grounding electrode system should be, consideration needs to be given to the
specific mission scenario, location, and environment. As a goal, one should
strive to achieve the 10 ohm grounding resistance when possible. The following
table lists tradeoffs that should be considered when making a decision.
17
I.IOI1TN INT.
s I H (I K K
19
Contrary to some beliefs, the lightning protection system does not prevent
lightning. Rather, it works by collecting the lightning stroke and diverting the
electrical energy, in a controlled fashion, to earth. The air terminal is
designed to intercept the lightning leader propagating from the cloud by
providing an upward propagating leader. A preferred path is then established
with the downconductor and earth electrode system. The lightning current is
then dissipated into the earth.
The concept of a "protected zone" is often attached to lightning protection
systems. In our context, we can define this as the area in which the lightning
event has a high probability of being intercepted by the lightning protection
system. For the purposes of tactical systems, the zone protected forms a cone
from the tip of the air terminal down to a distance on the ground equal to the
height of the air terminal. This approximation is not valid for structures
exceeding 50 feet in height.
The lightning protection system in its simplest form consists of a single air
terminal, downconductor and ground electrode (ground rod). This is often
seen in tactical antenna mast applications. Another common field installation
is use of an overhead wire connected to ground rods. In this case the air
terminal and the downconductor are really the same. Other configurations are
possible.
13.2 When Do I Install Lightning Protection?
Obviously if the structure or system has been hit by lightning more than once,
it is probably a strong candidate for lightning protection. As you can see from
the explanation above, it is entirely possible (and probable) that lightning may
strike twice in the same place. Otherwise examine the risk associated with
operating the system in your particular location. Use the table on the next
page to determine the risk and what to do. Assign higher scores to the
statements that apply.
20
FACTOR
SCORE
(disagree - agree)
21
GROUND ROD
INSTALL IAW
INSTRUCTIONS
SUGGESTED MATERIALS:
MAST: OE-254 (AB-1244) MAST OR WOODEN TELEPHONE POLE.
WARNING: DO NOT USE MASTS UNTESTED FOR WINDLOADING.
GUY WIRES SHOULD MAKE MINIMUM 45 DEGREE ANGLE WITH
MAST - INSTALL IAW TM INSTRUCTIONS.
AIR TERMINAL: 1 OR 2 SECTIONS OF GROUND ROD, NSN 597500-596-2324
GROUND ROD: NSN 5975-00-596-2324 OR 5820-01-263-1760 OR
EQUIVALENT.
22
DETAIL
AIR TERMINAL
SAFETY CORD
(USE 550 CORD)
CONNECTS AIR
TERMINAL AND
MAST IN CASE
OF
INADVERTENT
SEPARATION.
HOSE-TYPE
CLAMPS
HOSE-TYPE
CLAMPS
EXCESSIVE MAST
WIDTH MAY REQUIRE
ALTERNATE
CLAMPING METHOD.
IF THICK WOODEN
POLES ARE USED,
DRILL HOLES INTO
THE AIR TERMINALS
AND ATTACH WITH
BOLTS.
DOWN CONDUCTOR
23
GUY WIRES
GROUND ROD
DETAIL # 2
TOP OF MAST
MAXIMIZE ANGLE OF DOWN
CONDUCTOR WITH MAST.
AT LEAST 45 DEGREES - NO
SHARP BENDS!
DOWN CONDUCTOR
24
NAIL OR
SCREW HOSE
CLAMP TO
MAST
OVERHEAD WIRE
DOWN CONDUCTOR
25
STRUCTURAL PROTECTION:
BENDS MUST BE
GRADUAL; MINIMUM
8 INCH BEND
RADIUS
DOWN CONDUCTOR MUST NOT BEND BACK UNDER EAVES:
INCORRECT: >^r C
r-I
CORRECT
26
SHELTER SIGNAL
ENTRY PANEL
MAKE "LOOP" IN
SIGNAL COAX
STRIP OUTER
INSULATION FROM
COAX
GROUND
ROD
HOSE-TYPE CLAMP
COPPER WIRE TO GROUND, #6 AWG MINIMUM
27
28
APPENDIX A
Grounding Systems And The Confusion About Grounding.
From a safety standpoint, the functions of the grounding system can be placed in
two functional categories. One function is to provide a low impedance path
between all equipment and power supply noncurrent-carrying metal parts
(enclosures, etc.), as well as provide a bond between these parts and the power
supply neutral conductor back at the power supply. Bonding of enclosures is
carried out through the use of an Equipment Grounding Conductor (the green
wire provided with power cables), and bonding between the grounding and
neutral conductor is provided through the Main Bonding Jumper. As you can
see in the figure below, the low impedance path provided by these conductors
would permit sufficient current to flow back to the power supply to open any
circuit breaker protection in the event of a ground fault. The equipment
grounding conductor also helps to keep the voltage developed between
collocated equipment enclosures down during a fault. In these cases, the
Equipment Grounding Conductor acts more like a "bonding" conductor, in that
its main function is to bond noncurrent-carrying parts back to the power supply
rather than bond them to earth.
ground feilt-
sr
s:
discharge path to earth for surges, and provide a ground reference plane for
communication? signals. As seen in the previous figure, this is provided by the
Earth Grounding Conductor and the Earth Grounding Electrode. The Earth
Grounding system protects against hazardous voltages between enclosures and
earth ground developed as a result of power surges, lightning, and other faults.
Confusion stems from the fact that in many cases, the Equipment Grounding
Conductor not only bonds the equipment back to the power supply, but also
earth-grounds the equipment through the earth grounding conductor provided
back at the power supply. Both functions can be suitably carried out by the
Equipment Grounding Conductor for "simpler" equipment such as appliances,
tools, and individual equipment. However, as systems become larger, more
complicated, more sensitive to EMP, have more power sources or are
interconnected via numerous control and signal cables, faults can occur just
about anywhere which could follow unpredictable paths over which there is no
control (see figure below). For complex systems, such as shelters, additional
equipment grounding electrodes and conductors should be installed to ensure
that under fault conditions, hazardous voltages cannot be developed on
enclosures relative to earth ground.
lightning
discharge
electronic warfare
agatfai|
discharge
reawted eqalpmeat
complex systems can have multiple sources and paths for faults
It is important to stress that earth grounding is only part of the overall grounding
system, and is not a substitute for the Equipment Grounding Conductor or the
Main Bonding Jumper. Since power faults always follow a path back to the
30
power source, and since the earth is a poor conductor of electricity, sufficient
current will not flow back to the power supply to clear any circuit breaker
protection (see figure below). A low impedance path must be provided back to
the power source via the Equipment Grounding Conductor.
rqatpMn
Krovnd faali.*IS i *
nh*4 voll i t
4vt to firth
trth rubtmrt
L
Mrth ira*()lmf rkrtrndf
AAAAEirlfc RtsHfntt
Soil provides a poor impedance path; this energizes the equipment 's surfe'ace
During the development of equipment, the system designer is heavily involved
in ensuring that equipment grounding conductors are incorporated and suitably
sized; the designer does not get involved with the particulars of Earth
Grounding. However, the tables turn in the field in that the soldier's
involvement with Equipment Grounding Conductors is very limited (making
sure the "green" wire is connected at the generator, etc.), and much work is
placed on installing earth grounding conductors and electrodes, and
interbonding equipment. As a result, this pamphlet concentrates on proper earth
grounding procedures which are of primary concern, to the soldier. Additional
information on equipment grounding conductors and system/neutral grounding
is available in documents listed in Appendix B.
31
APPENDIX B
Additional Domrmentation and References
CECOM TR-93-1 Lightning Protection System Design
CECOM TR-94-8 Engineering Application Notes: Grounding Kit, MK-2551
A/U (Surface Wire Grounding Kit).
FM 11-487-4 Installation Practices: Communications Systems Grounding,
Bonding, and Shielding.
M1L-HDBK-419 Grounding, Bonding, and Shielding for Electronic
Equipments and Facilities.
NFPA 70 National Electrical Code
- Article 250 Grounding
- Article 550 Mobile Homes, Manufactured Homes, and Mobile
Home Parks
- Article 525
NFPA 780 Installation of Lightning Protection Systems
TB 43-0125 Installation of CE equipment: Hookup of Electrical Cables to
Mobile Generator Sets on Fielded Equipment to meet Electrical Safety
Standards.
TM 11-5820-1118-12&P Operator's and Unit Maintenance Manual Including
Repair Parts and Special Tools List for Grounding Kit, MK-2551 A/U
32
APPENDIX C
The Threat
The worst event that an earth grounding system can sustain is a direct lightning
strike. More often, equipment is subjected to and damaged by the strong
electromagnetic fields created by a nearby lightning strike, or the brief electrical
surge that can pass through signal. By installing the system with the
anticipation of the "worst case event," it can be assured that the earth grounding
system will function suitably for the other cases as well. Additionally, n>:<ny of
the factors that can lead to grounding system failure during a lightning strike can
also be the source of problems for minor events such as system noise and
communications effectiveness.
In order to get a true appreciation for what lightning is and what it can do, let us
take a brief look. Lightning is an atmospheric event by which an electrical
discharge occurs between the earth and sky. A single strike can be divided into
four components. The first is characterized by an extremely short pulse that
averages around 15,000 amps, but can go as high as 200,000 amps. This first
pulse has an extremely fast rise time, from zero to peak current in microseconds,
making it a very high frequency event. The next component is a very short
transitional period of a few thousand amps that leads to the third component
that's characterized by a steady current of a few hundred amps for up to 0.75
seconds. The last component is similar to the first component with about half
the current peak. For the average lightning strike, these components are
repeated 3 or 4 times, and have been measured up to 26 times in one event!
Now let's translate these components and events into what they do to the
grounding system. During the first "pulse component," extremely high
electromagnetic fields are developed. These fields can create strong mechanical
effects on the conductors and bonding connections causing twisting, pulling,
squeezing, and snapping. Any loose connections can be pulled apart quite
easily at this point. The following two components are primarily responsible
for heating. During these two components, enough current can be passed to
raise the temperature of a wire a few hundred degrees. Any loose, corroded, or
other connections having some resistance would melt at this point. Note how
the first component can cause connections to loosen, which would then melt
during the next "heating component." When considering the sheer magnitude of
the event that occurs and that it's repeated a number of times, it becomes very
clear that any single weak link in the grounding system could cause it to fail.
33
APPENDIX D
Haz?rrfs Due To Step Potentials
During a lightning strike, a large amount of current rapidly discharges through
the earth grounding electrode. The current density is highest near the electrode,
and rapidly decreases with distance from the electrode. In soil having uniform
resistivity, this current gradient can cause significantly high voltages, in the
thousands of volts, between any two points that are different distances from the
ground rod. The figure below illustrates this voltage gradient effect. If a person
were in this potential gradient area, straddling two of the equipotential lines,
current could travel across the body through the legs (hence the name "step
potential"). The step potential accounts for many of the injuries attributed to
lightning. Note that as one moves further away from the grounding electrode,
step potentials are greatly reduced.
STEP VOLTAGE
DISTANCE
step voltages
There are a number of things that can be done to minimize the effect of step
potentials. One is to minimize the resistance of the earth electrode, which can be
done through proper installation, use of a few interconnected electrodes, soil
treatment, etc. In addition, burying the electrode (plates or deep rods) helps to
reduce step potentials at the ground surface. One of the surest methods,
however, is to keep personnel away from the grounding elements. Ground rods
should be installed away from walk areas: at least 6 feet. It should be noted that
a person lying on the ground near a grounding electrode can also experience
severe shock; keep sleeping quarters away.
34
APPENDIX E
Earth Grounding Test
It is possible to conduct a quick test to make a rough measurement of the earth
grounding electrode's resistance. You will need the following equipment:
- multimeter (two can be used)
- four lengths of wire, 12 AWG or larger, up to 70 feet long.
- 2 short grounding electrodes (copper or steel with 1/2- to 3/4-inch diameter
and 2 feet long; a single section of a sectional ground rod works fine).
- at least four wire clamps (these can be the clip type or other type). Four
terminals may also be needed to connect the wire to the multimeter if the
multimeter doesn't have test clips.
- a hammer to drive the ground electrodes.
- an automobile or truck type battery, charged.
- a tape measure.
Setup: see figures below
Place all of the probes in a straight line with respect to the grounding electrode
being tested. Place the current probe about 60 feet away and the potential probe
at 0.62 times this distance from the ground rod under test (about 36 feet). Drive
in the current and potential probes about 1V2 feet. Connect the wire as in the
figure.
Procedure:
I) Place current probe, the multimeter and the battery in series
with the ground under test. It is important to place the probes
in a straight line with respect to the ground rod under test. Record the current
reading. Disconnect the battery.
STEP1
SET MULTIMETER FOR CURRENT READING
SET UP CIRCUIT AS SHOWN
TAKE CURRENT READING
DISCONNECT BATTERY
CURRENT
PROBE
EARTH
60 FEET
35
2) Place the multimeter in series with the potential probe and the ground rod.
Set the multimeter for a voltage reading.
3) Connect the current probe and battery in series with the ground under test.
Take the voltage reading with the multimeter. Disconnect the battery.
STEP 2
SET MULTIMETER FOR VOLTAGE READING
SETUP CIRCUIT IN DIAGRAM - CONNECT BATTERY LAST
TAKE VOLTAGE READING
DISCONNECT BATTERY
*
CURRENT
PROBE
PROBE
GROUND
I
UNDER TEST
4) Divide the voltage [volts] by the current [amperes] yielding resistance. This
is the resistance of the ground under test. (Make sure the units are correct; the
multimeter most likely will read in milliamperes, which is one thousandth of an
ampere).
SPECIAL CIRCUMSTANCES
A SINGLE BATTERY MAY NOT BE SUFFICIENT WHEN MEASURING HIGH
RESISTANCE TYPE SOILS (DRY, SANDY, ROCKY, ETC). IF THE
MULTIMETER READINGS ARE NOT STABLE, USE TWO BAKERIES IN
SERIES AS SHOWN BELOW (NOTE PROPER POLARITY):
Jumper A
CURRENT
- +
- +
batl
bat2
PROBE
EARTH
$1.5 FEET
GROUND
60 FEET
UNDER TESlB
<
CAUTION
DO NOT EXCEED 30 VOLTS TOTAL (Vtolal = Vbatl + Vbat2)
TO FURTHER REDUCE THE POTENTIAL FOR SHOCK, CONNECT JUMPER A
LAST BEFORE THE TEST, AND DISCONNECT JUMPER A FIRST AFTER THE
TEST. THIS WILL UMIT THE VOLTAGE BETWEEN ANY ACCESSIBLE PARTS
AND GROUND TO THE VOLTAGE RATING OF A SINGLE BATTERY.
36
APPENDIX F
Personnel Protection From Lightning.
The following is an extract of guidance developed at Fort Gordon on Personal
Safety During Thunderstorms.
1. Do not go outdoors or remain out during thunderstorms unless it is
necessary. Seek shelter as follows:
a.
b.
c.
d.
e.
f.
g.
h.
i.
APPENDIX G
Definitions: the National Electrical Code (NEC) creates some confusion by
using the word "grounding " to address equipment bonding, supply neutral
grounding, and earth grounding. In order to clarify this, the following terms and
definitions have been used in this pamphlet.
Bonding - the permanent joining of metallic parts to form an electrically
conductive path that will ensure electrical continuity and the capacity to conduct
safely any current likely to be imposed.
Equipment Grounding Conductor - this conductor is used to tie all noncurrentcarrying parts or an equipment (enclosure, etc.) together and back to the power
source. Unlike the grounded (neutral) conductor, it is intended to carry current
only during a fault condition.
Earth Grounding - A conductive connection between an electrical circuit or
equipment and the earth (the NEC calls this Grounding).
Earth Grounding Conductor - this conductor is used to tie the equipment/system
noncurrent-carrying metal parts to the earth grounding electrode (the NEC calls
this the grounding electrode conductor).
Earth Grounding Electrode - this is the actual element that contacts and makes a
good reference to earth, and usually consists of a ground rod, buried plates,
wires, pipes, etc. (the NEC calls this the grounding electrode).
Ground Fault - a fault condition where an ungrounded conductor (a "hot" wire,
such as the black power line) shorts to a noncurrent-carrying metal part, such as
the equipment enclosure. In contrast, a short circuit covers a fault between two
current carrying conductors, such as the hot (black) and neutral (white) wires.
Grounded Conductor - this is a current carrying conductor which is referenced
to ground by bonding it to earth ground at the power source or main service
panel (also known as the neutral, or white wire).
Impedance - a combination of resistance and reactance. Whereas the resistance
does not change with the current frequency, reactance increases with increasing
frequency.
Main Bonding Jumper - this is a conductor that is used to tie the power supply
grounded conductor (neutral) to the supply enclosure, equipment grounding
conductors, and earth grounding conductor.
Neutral Conductor - This conductor often is also the grounded conductor (with
some exceptions) and is colored white or natural grey.
38
APPENDIX H
This checklist details the principal factors required for a durable and effective
grounding/lightning protective system. Not all of the items require compliance,
depending on the particular situation. Rather, the grounding/lightning
protection system should be reviewed in light of this checklist to ensure that no
particular area has been left unaddressed.
Preparation:
G Has consideration been given to the placement of equipment or shelters from
an earth grounding perspective (local soil quality, etc.; see section 10)?
Has consideration been given to how extensive the earth grounding electrode
system should be (refer to section 12)?
D Has the soil condition been considered in selecting the type and quantity of
earth grounding electrodes (refer to section 3.1)?
Earth Grounding Conductor:
G Is the grounding wire suitably sized and of a corrosion-resistant material?
D Are loops, kinks, and sharp bends avoided?
D Are grounding conductors routed horizontally or down toward the ground
rod? (avoid going up and over objects)
D Are splices in the conductor avoided?
D Are the grounding wires free of heavy corrosion and damage, especially at
the ends?
Bonding Points:
G Are
0 Are
G Are
time?
G Are
G Are
LI Are electrodes installed where the ground will receive rain water or other
source of moisture?
D Are grounding electrodes installed away from locations with normal
pedest; ian traffic or personnel tents?
D Are power and signal cables not laid across or near earth grounding
conductors or cables?
D Where the earth grounding resistance is questionable (poor soil, buried
plumbing that may be coated, etc.), has a test been conducted (Appendix E).
Where soil quality is poor, are multiple grounding electrodes installed and
interconnected?
I'l Where soil quality is poor, is conductivity enhanced through the use of salt?
Grounding/Bonding Dead Metal Objects/Structures:
D Are all electronics equipment shelters, generators, etc. properly earth
grounded?
G Where used, are all CONEXes or other metal shelters normally occupied by
personnel grounded (including observation towers, bathrooms, and kitchens)?
D Are all electronics equipment shelters, CONEXes, and other metal shelters
located within 6 feet of each other bonded together?
D Are metal roofs which are provided to protect electronic equipment,
generator, etc. properly grounded as well as bonded to nearby equipment?
G Are generators, water tanks, POL tanks, and other metal objects grounded
as well as bonded to any other metal objects/structures within 6 feet?
Lightning Protective Masts (LPM):
G Is all equipment requiring protection located within the LPM cone of
protection? (as much as is reasonably possible)
[] Is the air terminal at top of the LPM durable?
I'.l Is a suitable grounding conductor provided from the air terminal to ground?
U Is the LPM suitably grounded via a dedicated ground rod, or otherwise
grounded to an existing ground rod system?
[] If any separate grounding electrodes are located near the LPM grounding
electrode, are they interconnected to the LPM grounding electrode?
[] Are all bonding connections secure? (clamped, not taped or twisted)
Other:
G Are personnel informed to remain within appropriate shelters when possible
during electrical storms (see Appendix F)?
G Are lightning protection masts and related grounding inspected following
electrical storms to ensure that damage was not sustained?
G If tents are used to house personnel, are they located away from ground rods
and antenna masts (tents provide poor protection; especially where personnel
lie across the ground)?
40
'J
PUBLICATION NUMBER
BE EXACT
PAP.AGPAPM
f ROM:
DATE SENT
PUBLICATION OATE
PUBLICATION TITLE
DA ,^2028-2
PREVIOUS EDITIONS
ARE OBSOLETE
Fill IN YOUR
UNIT S ADDRESS
-T7
FOID BACK
Commander
US Army Communications-Electronics Command
and Fort Monmouth
ATTN: AMSEL- SF
Fort Monmouth, New Jersey 07703-502V
I...I...II...III
FOLD BACK
II,I,LI,I.,I,.1.1.,I,I,ll