You are on page 1of 62

Generator and

Power Station Protection

Synopsis
Disclaimer

GENERATOR and
POWER STATION
PROTECTION

Disclaimer
Seminar Synopsis

bmoor@powersystemprotection.com.au
bmoor9@yahoo.com.au
www.powersystemprotection.com.au
Barrie Moor, B Eng (Elec)

bmoor@powersystemprotection.com.au

Slide 2

Disclaimer
z
z

The material presented in this module is for Educational purposes


only.
This module contains a summary of information for the protection of
various types of electrical equipment. Neither the author, nor
anyone acting on his behalf, makes any warranty or representation,
express or implied, as to the accuracy or completeness of the
information contained herein, nor assumes any responsibility or
liability for the use, or consequences of the use, of any of this
information.
The practical application of any of the material contained herein
must be in accordance with legislative requirements and must give
due regard to the individual circumstances.

bmoor@powersystemprotection.com.au

Barrie Moor : 2012

Slide 3

bmoor@powersystemprotection.com.au
(07) 3298 5260

Generator and
Power Station Protection

Synopsis
Disclaimer

Seminar Synopsis
z
z

Over Current Protection


Differential Protection

z
z

High Impedance Differential Protection


Biased Differential Protection
Sequence Components

Motor Protection
Generator Protection

Generator Faults
Generator Events
Power System Events

bmoor@powersystemprotection.com.au

Barrie Moor : 2012

Slide 4

bmoor@powersystemprotection.com.au
(07) 3298 5260

Seminar costs will vary depending on attendee


numbers and your individual circumstances.
However, by organising your own in-house
seminar:

You can expect savings of between 40%


and 65%.
Plus you eliminate travel and
accommodation expenses for all of your
attendees.

We provide:

2 or 3 day seminar presentation


All seminar handout material, notes, folders,
CDs, etc
Laptop Computer and Data Projector
Note that we guarantee that all seminars will be presented personally by
our principal engineer and seminar author, Barrie Moor

Each attendee receives:

Two or three day seminar presentation


Hard copy manual with all presentations, plus supporting technical
papers
CD with all printed material, plus considerable extra material and tools,
including:
pdf of seminar colour slides 2 per page
additional technical papers
tools for sequence component analysis of single, double and three
phase faults
tools for grading of IDMT overcurrent relays
tools for distance relay calculations, apparent impedance calculations,
fault resistance, mho and offset mho characteristic load limits
Certificate of attendance

You provide:

Seminar conference room (preferably on-site, within your own facilities)


Whiteboard
Any catering for lunch and tea breaks

To discuss your requirements, or to obtain a firm price quotation,


please contact us at:
enquiries@powersystemprotection.com.au

Generator and
Power Station Protection

Over Current Protection


Fuses and Contactors

GENERATOR and
POWER STATION
PROTECTION

Over Current Protection


z

Over Load Protection

Over Current Protection

OVER CURRENT
PROTECTION

Operation to the thermal capability of plant


Primarily for clearance of faults
Some measure of over load protection may be provided

Overcurrent Relays
Fuses & Contactors
Directional Relays
Barrie Moor, B Eng (Elec)

bmoor@powersystemprotection.com.au

Slide 1

Discrimination by Time

z
z
z

Slide 2

Discrimination by Time

Setting chosen to ensure CB nearest to the fault opens


first
Often referred to as
Independent Definite Time Delay Relay
Timing intervals selected to ensure upstream relays do
not operate before CBs trip at fault location
Disadvantage
Longest fault clearing time occurs in section closest to
the power source where fault level is the highest

RELAY A

RELAY B

TIME

bmoor@powersystemprotection.com.au

RELAY C

RELAY A

0.4 secs
RELAY B

0.4 secs
RELAY C

CURRENT

bmoor@powersystemprotection.com.au

Slide 3

Discrimination by Current
z
z
z

bmoor@powersystemprotection.com.au

Discrimination by Current

Apply where fault current varies with fault location due to


intermediate impedance
Set to operate at current values so that only relay
nearest to fault trips its CB
Difficulties

RELAY A

Same fault level at the end of one zone and the start of the
next
Fault levels vary with changing source impedance
(eg. As generators come on and go off line)

bmoor@powersystemprotection.com.au

Barrie Moor : 2012

Slide 4

Relay A cannot distinguish


between a fault here, for
which it needs to operate

Slide 5

bmoor@powersystemprotection.com.au

RELAY B

And a fault here for


which it should not
operate

Slide 6

bmoor@powersystemprotection.com.au
(07) 3298 5260

Generator and
Power Station Protection

Over Current Protection


Fuses and Contactors

Discrimination by Current

Discrimination by Time & Current

FDR OC

IAmax

IBmax

RELAY A

HV OC

Significant difference between


currents seen for Faults A & B
Set HV OC to 1.3 x maximum
through current for LV Fault

Instantaneous
element

TIME

RELAY B

RELAY C

ICmax

IBmax

IAmax

FDR OC

CURRENT

Slide 7

bmoor@powersystemprotection.com.au

Slide 8

Discrimination with
Inverse Time Over Current Relays

Inverse Over Current Relays


Time of operation inversely proportional to fault current

Faster operating times at higher fault levels


Faster operating times for faults nearer to the source

IAmax

IBmax

RELAY A

Curves generally plotted in log - log or


log(current) linear(time) format

TIME

Time and current


coordination

RELAY A

FDR OC

bmoor@powersystemprotection.com.au

ICmax

RELAY C

A
FDR OC

RELAY B

RELAY B

ICmax

RELAY C

Inverse time and


current coordination

RELAY A
RELAY B

Instantaneous
element

RELAY C

ICmax

IBmax

IAmax

CURRENT

bmoor@powersystemprotection.com.au

Slide 10

bmoor@powersystemprotection.com.au

Relay Curves to IEC 60255


(BS142)
TIME S tan dard _ Inverse =

z
z

Relay Curves to IEC 60255


(BS142)

0.14 TMS
I
P

TIME Very _ Inverse =

0.02

1
z

I = Actual relay current


Relay Settings
TMS = Time Multiplier Setting
P
= Plug (Current) pickup setting
Usual curve for transmission and distribution systems

bmoor@powersystemprotection.com.au

Barrie Moor : 2012

Slide 11

Slide 12

13.5 TMS
I
P 1

I = Actual relay current


Relay Settings
TMS = Time Multiplier Setting
P
= Plug (Current) pickup setting
Systems where the fault level decreases significantly
between relaying points

bmoor@powersystemprotection.com.au

Slide 13

bmoor@powersystemprotection.com.au
(07) 3298 5260

Generator and
Power Station Protection

Over Current Protection


Fuses and Contactors

Relay Curves to IEC 60255


(BS142)
TIME Extremely _ Inverse =

z
z

Relay Curves to IEC 60255


(BS142)

80 TMS

TIME Long _ Time _ Inverse =

I
P 1

z

I = Actual relay current


Relay Settings
TMS = Time Multiplier Setting
P
= Plug (Current) pickup setting
Grading with fuses

bmoor@powersystemprotection.com.au

Slide 14

120 TMS
I
P 1

I = Actual relay current


Relay Settings
TMS = Time Multiplier Setting
P
= Plug (Current) pickup setting
Long time thermal protection
Motor & Generator Protection

bmoor@powersystemprotection.com.au

Slide 15

IDMT Relay Grading Curves

Standard Characteristics to IEC 60255

100

Relay Characteristic

Very Inverse (VI)

Extremely Inverse (EI)

Long Time (LTI)

0.14 TMS
0.02

10

Seconds

Standard Inverse (SI)

13.5 TMS
I1

80 TMS
I2 1
120 TMS
I1

0.1
100

1 .10
Fault Current

1 .10

Standard Inverse
Very Inverse
Etremely Inverse
Long Time Inverse
bmoor@powersystemprotection.com.au

Slide 16

Electro Mechanical Relays

US Characteristics to IEC 60255


Relay Characteristic
U1 Moderately Inverse

0.0104

TD 0.0226+ 0.02
M 1

U2 Inverse

5.95

TD 0.180 + 2
M 1

U3 Very Inverse

3.88

TD 0.0963 + 2
M 1

U4 Extremely Inverse *

5.64

TD 0.02434 + 2
M 1

U5 Short Time Inverse

0.00342

TD 0.00262 + 0.02
M 1

L FLUX PRODUCED BY SHADING LOOP

FLUX PRODUCED BY INPUT CURRENT

k I

(1-k) I

SHADING LOOP

TD
M

bmoor@powersystemprotection.com.au

Barrie Moor : 2012

DISC

TAPPED
COIL

DISC

- L

FLUX PRODUCED BY INPUT

= Time dial (TMS)


= Multiple of pick-up current

Slide 18

bmoor@powersystemprotection.com.au

Slide 19

bmoor@powersystemprotection.com.au
(07) 3298 5260

Generator and
Power Station Protection

Over Current Protection


Fuses and Contactors

Electro Mechanical Relays


Construction

Electro Mechanical Relays


Inverse Definite Minimum Time

Time multiplier
(TMS) Settings

Trip Contacts
and
Flag

(continuous adjustable)

Current sensitivity selected by Plugs on the magnetic circuit

Magnetic circuit saturates at extreme over current

Shaded Pole
z

Moving Contact

Higher sensitivity selected via more turns


ie. Same Ampere Turns operating quantity
more turns = less current
Limits the minimum operating time
Typically around 20x plug setting
Hence IDMT performance : DM = definite minimum

Time coordination via Time Multiplier setting

Adjusted the starting point of the induction disk wrt the fixed trip contact
Often called Lever Setting

Current (Plug)
Settings

Trip Contacts

bmoor@powersystemprotection.com.au

Slide 20

bmoor@powersystemprotection.com.au

Standard Inverse Relay Grading Curves

Slide 21

Standard Inverse Relay Grading Curves

100

Adjust TMS to
achieve time
coordination

3.5

If we have
sufficient
margin here

10

Seconds

Seconds

2.5

Then with the same


characteristic, we tend to
have greater margin at
lower currents due to
divergence of the curves

1.5

0.1
100

And since we are usually interested in


operating times of 3 seconds or less,
we may get a better perception if we
use
a linear axis for time . 4
3
1 .10
1 10

0.5

1 .10
Fault Current

IDMT Curves
OC

OC

Electromechanical relays
4

Must not pick up at < 1.00 pu current


Must pick up at > 1.30 pu current
May not have well defined characteristics between
1.3 and 2.0 pu current

3.5

Electromechanical relays tend to a definite minimum


time at high currents, say > 20 x ISET

2.5

Microprocessor based relays will have a genuine definite


minimum time.

IDMT Relay Grading Curves

Seconds

OC
OC

1 .10

100

Fault Current

Due to saturation of their magnetic circuits

1.5

0.4 Seconds
Margin

0.5

100
bmoor@powersystemprotection.com.au

Barrie Moor : 2012

1 .10
Fault Current
3

1 .10

0.4 Seconds
Margin

Slide 24

bmoor@powersystemprotection.com.au
(07) 3298 5260

Generator and
Power Station Protection

Over Current Protection


Fuses and Contactors

Instantaneous Element

OC
OC

OC

Reduces tripping time at high fault levels


Allows a the discriminating curves behind the high set
element to be lowered

Minimises fault damage in both cases

Beware
Simple E/M instantaneous elements may have a substantial
transient overreach on fault currents that include DC offset

IDMT Relay Grading Curves

3.5

Grading of upstream relay now occurs at the instantaneous


setting and not at maximum fault level

2.5
Seconds

OC

Set Tx HV inst
element and now
grade here

1.5

0.5

1 .10
Fault Current
3

100
bmoor@powersystemprotection.com.au

1 .10

Slide 26

GENERATOR and
POWER STATION
PROTECTION

Relay Coordination Procedure


Current Setting
z

Start with selection of relay characteristic

Choose current settings

OVER CURRENT
PROTECTION

Setting and
Coordination
Procedures

As far as possible, use relays of the same characteristic


Determine maximum load current limitations
Determine starting current requirements
As far as possible, select operating current of each
upstream relay greater than that of the successive
downstream relay

Barrie Moor, B Eng (Elec)

bmoor@powersystemprotection.com.au

Slide 29

Relay Current Pick-up Setting


z

z
z

Allow for emergency loading conditions


Allow safety margin
Allow for relay reset ratio

z
z
z

Set below the current pickup level of the next upstream


relay
Allow for load pickup current

bmoor@powersystemprotection.com.au

Barrie Moor : 2012

Slide 30

Load Pickup Current

Set above maximum load current

bmoor@powersystemprotection.com.au

Motor starting current


Auxiliary heaters
Transformer magnetising inrush
Capacitor charging current
Lighting loads - 10s to 100s of msec

Slide 31

Filaments and electrodes heating


Arc lamps starting

bmoor@powersystemprotection.com.au

Slide 32

bmoor@powersystemprotection.com.au
(07) 3298 5260

Generator and
Power Station Protection

Over Current Protection


Fuses and Contactors

Relay Coordination Procedure


Time Multiplier Setting

Load Pickup Current


z

Hot load pickup

Load pickup, but now with loss of diversity between cyclic


loads

Voltage recovery pickup

Pickup currents not as severe as for complete loss of


supply and subsequent hot load pickup
But more motors may still be on-line as under voltage
releases may not have disconnected them

bmoor@powersystemprotection.com.au

Slide 33

Determine, under various system configurations, the


values of short circuit current that will flow through each
protective device
Set relays to give minimum operating time at maximum
fault currents
Check performance (discrimination) at lower fault levels

Plot and coordinate relay curves on log/log or log/linear


format

Relay TMS Grading


z

Coordinate relays via time multipliers to achieve


appropriate grading margins

Cold load pickup

Short term loss of supply and subsequent load pickup


currents on return of supply

Plot to a common current base (across transformers)

bmoor@powersystemprotection.com.au

Slide 34

Relay TMS Grading

Must provide for


CB tripping time (0.1 sec ??)
Relay timing errors
Relay overshoot
CT errors (10% ??)
Safety margin (10% ??)
A typical figure of 0.3 - 0.4 seconds is usually OK
0.3 for numerical relays
0.4 for electromechanical relays
Alternatively calculate a margin
Only necessary for slow tripping times (> 1.0 sec)

bmoor@powersystemprotection.com.au

Slide 35

Relay TMS Grading

bmoor@powersystemprotection.com.au

Slide 36

Grading of Parallel Elements

OC

OC

OC

OC

OC

Relay Technology

z
z

ElectoMechanical

Static

Digital

Numerical

Timing Error %

7.5

Overshoot Time (s)

0.05

0.03

0.02

0.02

Safety Margin (s)

0.1

0.05

0.03

0.03

Typical margin (s)

0.4

0.35

0.3

0.3

Worst case for grading is with only 1 transformer in service


But this will be an unusual operating condition
E/M & Electronic Relays
Only a single relay setting is available
Hence, effectively no option but to set for the worst case, namely
1 transformer case
And accept slower performance for system normal,
namely when both transformers are in service
Microprocessor based relays
These relays have multiple setting groups
So, maybe set Group 1 for system normal : 2 transformers
And change to group 2 when one transformer is OOS
z
z

Automatically ??
Via SCADA & operator intervention ??

Hence for an E/M relay tripping in 0.5 seconds


t = (7.5 + 7.5 + 10)% x 0.5 + 0.1 + 0.05 + 0.1
t = 0.375 seconds
CT Errors

Barrie Moor : 2012

bmoor@powersystemprotection.com.au

Slide 38

bmoor@powersystemprotection.com.au
(07) 3298 5260

Generator and
Power Station Protection

Over Current Protection


Fuses and Contactors

z
z
z

20MVA

Fdr_1 OC
800A FLC

33kV

3 Fault Levels
2 Tx IN : 10000A
1 Tx IN : 7500A
300A FLC
Fdr_2 OC
SI 400A
TMS 0.2

11kV

3 Fault Levels
2 Tx IN : 16000A
1 Tx IN : 12000A

HV OC
20MVA

Feeder 1

Relay_2 := SI Fdr2_Plug , Fdr2_TMS , I2

Feeder 2

Relay_1 := SI Fdr1_Plug , Fdr1_TMS , I1

n
n

0.14 TMS

I
P

Maximum through fault level occurs when both transformers


are in service
But the maximum individual transformer current flows when
the 2nd transformer is OOS
Need to consider both conditions when grading relays

HV OC

SI( P , TMS , I) :=

Relay Characteristic

Grading of Parallel Elements

SI( Fdr2_Plug , Fdr2_TMS , Imax) = 0.421

SI( Fdr1_Plug , Fdr1_TMS , Imax) = 0.832

Imax:= 10000

Grade Fdr_1 OC over Fdr_2 OC at the maximum through fault level of 10kA
Set Fdr_1 OC above maximum feeder load of 800A
and check against maximum fault level of 10kA

Fdr2_Plug := 400

Imax

Fdr2_TMS := 0.2

Fdr2_Plug

Tripping time at maximum fault level

Fdr2_Tmin := SI( Fdr2_Plug , Fdr2_TMS , Imax)

Fdr2_Tmin = 0.421

So select settings for Feeder 1

Fdr1_Plug := 1000

Given data for Feeder 2

Imax
Fdr1_Plug

Required tripping time

Fdr1_Tmin := Fdr2_Tmin + 0.4

Assume TMS = 1.0

Fdr1_TMS_1 := SI( Fdr1_Plug , 1.0, Imax)

This would result in a tripping time of

Fdr1_TMS_1 = 2.971

= 25

= 10

Fdr1_Tmin = 0.821

Fdr1_TMS := 1

Hence we can calculate the required TMS to achieve the required tripping time

Fdr1_Tmin
Fdr1_TMS_1

Fdr1_TMS = 0.276
Fdr1_TMS := round ( Fdr1_TMS + .003, 2)

Round Up

0.02

Fdr1_TMS = 0.28

_T = 0.411

Tx OC Grading (11kV Base Currents)

Grade Transformer HV OC under the maximum current condition, namely with one transformer OOS

3
2.8

Imax:= 12000

2.6

FLC_33kV:=

20000000

2.4

3 33000

FLC_33kV= 350

130 % FLC_33kV= 455

Set
Allow for 33/11kV ratio

2.2

Tx_HV_Plug := 500
Tx_HV_Plug := 3 Tx_HV_Plug
Tx_HV_Plug = 1500

2
1.8

Fdr Tripping time at maximum fault level

Fdr1_Tmin := SI( Fdr1_Plug , Fdr1_TMS , Imax)

Fdr1_Tmin = 0.769

1.6

Transformer HV OC

Tx_HV_Tmin:= Fdr1_Tmin + 0.4

Tx_HV_Tmin = 1.169

1.4

Assume TMS = 1.0

Tx_HV_TMS_1 := SI( Tx_HV_Plug, 1.0, Imax)

1.2

This would result in a tripping time of

Tx_HV_TMS_1 = 3.297

Hence we can calculate the required TMS to achieve the required tripping time

Tx_HV_TMS := 1

0.8

Tx_HV_Tmin
Tx_HV_TMS_1

Tx_HV_TMS = 0.355

0.6

Tx_HV_TMS := round ( Tx_HV_TMS + .003, 2)

Round up

0.4

Tx_HV_TMS = 0.36

0.2
0
100

1 .10

1 .10

1 .10

Fdr 2 OC
Fdr 1 OC

Feeder 1

Relay_1 := SI Fdr1_Plug , Fdr1_TMS , I1

Tx HV

Relay_3 := SI Tx_HV_Plug, Tx_HV_TMS, I3

n
n

SI( Fdr1_Plug , Fdr1_TMS , Imax) = 0.769

SI( Tx_HV_Plug, Tx_HV_TMS, Imax) = 1.187

_T = 0.418

Tx OC Grading (11kV Base Currents)

Sequential Operation of Over Current


Relays

3
2.8

2.6

2.4
2.2

As CBs trip, fault current magnitudes and flows will change


We need to integrate how far each relay progresses towards
tripping in each stage

1.8

1.6

To determine total tripping times


To ensure relays that should not trip, remain stable

Relay 1 operating time must have a suitable margin above the


total of Relay 2 and the subsequent Relay 3 operations

1.4
1.2
1
0.8

Relay 1

0.6

Relay 2

0.4

Relay 3

0.2
0
100

1 .10

Fdr 2 OC
Fdr 1 OC
Tx HV OC

Barrie Moor : 2012

1 .10

1 .10

bmoor@powersystemprotection.com.au

Slide 45

bmoor@powersystemprotection.com.au
(07) 3298 5260

Generator and
Power Station Protection

Over Current Protection


Fuses and Contactors

GENERATOR and
POWER STATION
PROTECTION

Directional Over Current Relays


z

OVER CURRENT
PROTECTION

z
z
z

Directional Relays

Extra discrimination may be achieved by making the


response of the relay directional when current can flow in
both directions
Achieved via voltage (polarising) connections to the relay
Digital and numeric relay achieve phase displacements
via software
EM & Static relays require suitable connection of input
quantities to the relay

Barrie Moor, B Eng (Elec)

Slide 46

Directional Over Current Relays


Application to Parallel Feeders

Ring Mains Systems

Fdr 2

OC

OC

Apply directional relays at the feeder receiving ends

Typically set to 50% of FLC, TMS = 0.1


Grade below non-directional relays at the source end
Ensure DOC relay thermal rating is OK

bmoor@powersystemprotection.com.au

Slide 48

GENERATOR and
POWER STATION
PROTECTION

0.1

0.1

11..3
3

1.3
0.9

0.9

Slide 54

Earth Fault Protection

OVER CURRENT
PROTECTION

Implement more sensitive protection responding only to


residual current of the system
Low settings are permissible and beneficial

Earth Fault Relays

z
z

Slide 55

Earth faults are the most frequent


Earth faults may be limited by earth fault resistance
Earth faults may be limited by neutral earth impedance

Typical settings 20 - 40% x FLC


Time grade in the same manner as for phase OC relays
Beware of the burden that electromechanical relays may
place on CTs at low current settings

Barrie Moor, B Eng (Elec)

Barrie Moor : 2012

2.1

bmoor@powersystemprotection.com.au

bmoor@powersystemprotection.com.au

2.1

1.7

Open the ring at the


supply point
And then grade
clockwise
And then anticlockwise
Source substation relays
do not HAVE to be
directional
Intermediate substation
slower relays do not
HAVE to be directional

0.5

OC
Fdr 1

Slide 47

1.7

OC

bmoor@powersystemprotection.com.au

0.5

bmoor@powersystemprotection.com.au

Although burden does decrease at very high currents with


saturation of the relays magnetic circuits

bmoor@powersystemprotection.com.au

Slide 56

bmoor@powersystemprotection.com.au
(07) 3298 5260

Generator and
Power Station Protection

Over Current Protection


Fuses and Contactors

Earth Fault Protection

Directional Earth Fault Protection

Not suitable for


2:1:1 Current
applications
(Transformer HV
current in the case of
Star/Delta or Delta/Star
through phase/phase
faults)

z
z

Voltage Quantity required to polarise relay


Use the system residual voltage

EF Prot
z

OC
OC

This voltage will be zero for balanced system voltages

EF Prot

OC

OC

This is the vector sum of all three phase voltages


This is thus three times the zero sequence voltage

Normal Load conditions


Three phase events
2 phase events not involving earth

EF Prot
OC

bmoor@powersystemprotection.com.au

Slide 57

bmoor@powersystemprotection.com.au

GENERATOR and
POWER STATION
PROTECTION

Directional Earth Fault Protection

5 limb core type


3 x 1 phase units

Va

Vb

3.Vo

Slide 59

minimum
pre-arcing
I2t

250

maximum
total I2t

160

Discrimination between fuse


links is achieved when the
total I2t of the minor fuse link
does not exceed the prearcing I2t of the major fuse
link
But note that this applies only
for high speed operation
where there is no heat
dissipation
ie. I2t adiabatic performance
As a starting point, a current
rating ratio between fuses of
1.6 - 2 is probably OK
(but this depends on the
specific fuse design)

200

Performance effectively
follows I2t law
z Pre Arcing time
z Arc time
Fuse Fuse grading
requires that the total I2t of
the smaller fuse be less
than the pre-arcing I2t of the
larger fuse

80

Slide 61

Fuse
Bullrush Curves

Fuses
z

bmoor@powersystemprotection.com.au

125

bmoor@powersystemprotection.com.au

Barrie Moor, B Eng (Elec)

100

Vc

Fuses
and
Fuse Contactors

50

63

OVER CURRENT
PROTECTION

40

32

3 . V0 is obtained from a VT with the secondary


connected in a broken delta
Primary star point of VT must be earthed
And to provide the path for zero sequence flux
VT must be

35

Slide 58

Fuse Rating

bmoor@powersystemprotection.com.au

Barrie Moor : 2012

Slide 62

bmoor@powersystemprotection.com.au

Slide 63

bmoor@powersystemprotection.com.au
(07) 3298 5260

Generator and
Power Station Protection

Over Current Protection


Fuses and Contactors

Expulsion Fuses

Fuses & TRV Performance


Current
interrupted at
natural
current zero

z
z

z
z
z

Used where expulsion gases cause no problem such as in overhead


circuits and equipment
Special materials (fiber, melamine, boric acid, liquids such as oil or
carbon tetrachloride ) located in close proximity to fuse element and
arc rapidly create gases
These produce a high pressure turbulent medium surrounding the
arc
Expulsion process deionises gases them as well as removing them
from arc area
In inductive circuits, transient recovery voltage (TRV) will be
maximum at current zero.

Current lags
Voltage by 90
deg

1.5

System
Voltage

0.5

0.5

Fuse Voltage
1

1.5

0.002

0.004

0.006

0.008

0.01

0.012

0.014

0.016

0.018

0.02

0.022

0.024

TRV across
blown fuse
element

Circuit Voltage
Fuse Voltage
Current

bmoor@powersystemprotection.com.au

Slide 64

Slide 65

Tin for M Effect low


overload fuse performance
See later

Current Limiting Fuses (HRC Fuses)


z

bmoor@powersystemprotection.com.au

Current Limiting Fuses

Fuse is designed to insert a large resistance


Hence, prospective level of fault current is reduced
And zero crossing of the current and voltage will be reasonably
in phase TRV significantly reduced
Fuse element is completely surrounded with filler material, typically
silica sand
Arc energy melts the sand, thus inserting the required high
resistance
But this design may have difficulty interrupting low level overloads.
Overcome by
M Effect designs
Spring assisted designs

bmoor@powersystemprotection.com.au

Slide 66

bmoor@powersystemprotection.com.au

Current Limiting Fuses


M Effect for low level overloads

Current Limiting Fuses

bmoor@powersystemprotection.com.au

Barrie Moor : 2012

Slide 67

Slide 68

M Effect : A.W. Metcalf - 1939

bmoor@powersystemprotection.com.au

Slide 69

bmoor@powersystemprotection.com.au
(07) 3298 5260

Generator and
Power Station Protection

Over Current Protection


Fuses and Contactors

Current Limiting Fuses

Grading Relays with Fuses


z

bmoor@powersystemprotection.com.au

Slide 70

Grading Relays with Fuses


z
z

bmoor@powersystemprotection.com.au

Slide 71

The next relay to a VI characteristic


And subsequent further upstream relays to SI characteristics

bmoor@powersystemprotection.com.au

High fault level applications

Option 1 : Also select EI characteristics


Option 2 : Check also for the possibility of setting
z

Or T ' 0.4 t + 0.15

Fuse Contactors

First relay upstream of the fuse should be set to EI


characteristic
Now to coordinate further upstream relays

Extremely Inverse curve


80 TMS
TIMEExtremely _ Inverse =
follows a similar I2t
2
I
characteristic
P 1

Relay current setting should
be approximately 3 times the
fuse rating
Grading margin of not less
than 0.4 seconds
recommended

Slide 72

eg

40kA fault level


Contactor rated to only 10kA
Fuse operates for all faults above say 7 kA
Contactor and associated protection relay operate for
lower fault levels
Warning the fuse may also have a minimum breaking
capacity and the contactor must be set to operate above
this point

bmoor@powersystemprotection.com.au

Slide 73

Fuse Contactors
100

Fuse operation
below 2kA is not
permissible

10

10kA Contactor
operates for faults
below 7kA

0.1

Fuse operates for


faults above 7kA
0.01
100

1 .10

Fuse
Relay / Contactor
Fuse

bmoor@powersystemprotection.com.au

Barrie Moor : 2012

1 .10

1 .10

Slide 74

bmoor@powersystemprotection.com.au
(07) 3298 5260

Generator and
Power Station Protection

High Impedance Differential Protection

GENERATOR and
POWER STATION
PROTECTION

Synopsis
z

HIGH IMPEDANCE
DIFFERENTIAL
PROTECTION

z
z
z

Busbar Protection and


Galvanically Connected
Plant

z
z

HZ Differential Protection Principles


Determination of setting voltage
CT requirements
Current operated schemes and stabilising resistors
Limiting secondary system voltages to safe levels
Primary operating current and application of shunt
resistors
CT supervision requirements
Application of high impedance differential protection
schemes to other galvanically connected plant

Barrie Moor, B Eng (Elec)

bmoor@powersystemprotection.com.au

Slide 1

z
z

Dependability
Must trip for all in-zone faults
Discrimination
Must not trip for any out-of-zone faults
Security
Against all sources of mal-tripping

Dependability

M
I
S

Speed of operation
As quickly as possible

bmoor@powersystemprotection.com.au

bmoor@powersystemprotection.com.au

Barrie Moor : 2012

E
L
&

Slide 2

CT Connections & Polarity

Bus Zone Protection Requirements


z

bmoor@powersystemprotection.com.au

!!!

P1
I1

P1
I1

S1

S1
I2

I2

Security
S2
S2
P2

Slide 3

P2

bmoor@powersystemprotection.com.au

Slide 4

Internal Fault

External Fault

RELAY

RELAY

Slide 5

bmoor@powersystemprotection.com.au

Slide 7

bmoor@powersystemprotection.com.au
(07) 3298 5260

Generator and
Power Station Protection

High Impedance Differential Protection

3 Phase CT Connections

Current Mismatch
z
CT MARSHALLING

z
z

CT Manufacturing Variations
Inequality of CT Burdens
CT Saturation

Highest Fault Current on CT exposed to through fault


Worst possible mismatch is
z
z

Total saturation of the CT on the faulted plant


All other CTs transform perfectly

DIFFERENTIAL
RELAY

bmoor@powersystemprotection.com.au

Slide 8

bmoor@powersystemprotection.com.au

Slide 9

External Fault

External Fault & CT Saturation


CT Saturates :
Magnetising branch
impedance becomes zero

External Fault

Rlead
Rct

High
Impedance
RELAY
Relay

RELAY
Rlead

15000A

5000A

5000A

5000A

VRELAY = IFAULT (R CT + R LEADS )


bmoor@powersystemprotection.com.au

Slide 10

bmoor@powersystemprotection.com.au

Slide 11

CTs will saturate under internal fault conditions, but


relay operation is assured provided absolutely all CTs
meet the requirement

Setting Voltage and Margins

Internal Fault
z

Fault current comprises

AC Component
DC Component

Hence, employ a DC Stabilised Relay

And considering 0% / 100% CT saturation case

No additional margin on the setting is required


High
Impedance
RELAY
Relay

This in an unrealistically extreme case


100% safety margin is automatically built in

So, no additional safety margin on setting is required

VKNEE 2 VRELAY
bmoor@powersystemprotection.com.au

Barrie Moor : 2012

Slide 12

bmoor@powersystemprotection.com.au

Slide 13

bmoor@powersystemprotection.com.au
(07) 3298 5260

Generator and
Power Station Protection

High Impedance Differential Protection

CT Selection
z
z

All CTs to be the same ratio


All CTs to have Vk 2.Vsetting

This is an absolute MUST


Preferably Vk 5.Vsetting

CT
CTinternal
internal
resistance
resistance

0.1 PX 500 R3

200 ohms

bmoor@powersystemprotection.com.au

Barrie Moor : 2012

Assuming the CT has been


selected to match plant
rating

IRMS = 0.52 I

Slide 16

VRELAY =

VKNEE
2
Slide 15

In the case of a heavy internal fault, secondary system voltages may


become excessive
Implications include damage to equipment and safety of personnel
Empirical Formula

VK = CT RMS knee point voltage


VF = Maximum RMS voltage that would occur if the CT did not
saturate
Install metrosils if this voltage become excessive
(eg. >2.8kV peak)

bmoor@powersystemprotection.com.au

Slide 17

Metrosil Parameters
METROSIL NON-LINEAR RESISTORS

V = C . IB
4
1 10

Do not simply set

VPEAK = 2 2 VK (VF VK )
Relay
0.2A
10 ohms

V = C I

Beware of short cut methods

V = I.R
= 0.2 x (200 + 10)
= 42 volts

20% setting is usually OK

Where V & I are PEAK


values
C = Metrosil constant
B = Metrosil constant
(0.2 0.25)
And, because of the
non-linearity

Preferably
Preferably55times
timestotooptimise
optimise
relay
relayperformance,
performance,but
but22isisthe
the
absolute
absoluteminimum
minimumtotoensure
ensure
reliable
reliablerelay
relayoperation
operation

bmoor@powersystemprotection.com.au

Metrosil Parameters

Ensure Operation for genuine in-zone faults

Metrosils

bmoor@powersystemprotection.com.au

Slide 14

Voltage operated
Current operated, incl stabilising
resistor
Typical current settings
as low as possible, but
> 20% of plant rating
< 30% of fault current

VRELAY = IFAULT (RCT + RLEADS)

Not absolutely critical


But highly recommended to specify class PX CTs

Current Operated Schemes


z

Ensure Stability under through faults

VKNEE 2 VRELAY

bmoor@powersystemprotection.com.au

Knee Point voltage


CT Resistance

Class Requirements

Summary

CT
CTknee
knee
point
pointvoltage
voltage

Need to know

Magnetising
Magnetising
current
currentat
atknee
knee
point
pointvoltage
voltage

Based on the previous equations, the RMS current at the


relay setting voltage Vs(rms) is:-

VSetting RMS =

1000

C
2

I
RMS
0 . 52

100

10
0.001

C = 450
C = 600
C = 900

0.01

B = 0.25
B = 0.25
B = 0.25

0.1

10

IRMS

100

Metrosil Current - Amps

Slide 18

bmoor@powersystemprotection.com.au

= 0 . 52

2 VSetting RMS

Slide 19

bmoor@powersystemprotection.com.au
(07) 3298 5260

Generator and
Power Station Protection

High Impedance Differential Protection

Primary Operating Current

Shunt Resistors
z
z

Desensitise scheme
Prevent tripping on open CTs

I mag

I metrosil

RELAY

I relay

I shunt

R shunt

I mag

Primary operating current > maximum plant loading


Effectively becomes a medium impedance scheme

IP = CT (IRELAY+ IMETROSIL+ N IMAG)


N = Number of CTs in parallel

bmoor@powersystemprotection.com.au

Slide 20

Primary Operating Current

bmoor@powersystemprotection.com.au

CT Supervision
z

I mag

I metrosil

I relay

I shunt

R shunt

I mag

RELAY

Slide 21

IP = CT (IRELAY+ IMETROSIL+ ISHUNT+ N IMAG)

Effect of CT problems when Shunt Resistors are installed


Scheme is part way to a trip condition
Effect of CT problems when BZ Check scheme is installed
Half of the scheme is already tripped
CT Supervision Setting Principles
Set to 50% of minimum load
Operation : initially (eg. < 3 secs)
Nil : allow for correct operation of BZ protection
Operation : short time (eg. > 3 secs)
Alarm
CT Shorting

N = Number of CTs in parallel

bmoor@powersystemprotection.com.au

Slide 23

GENERATOR and
POWER STATION
PROTECTION

bmoor@powersystemprotection.com.au

Slide 24

HZ Protn Application to Plant


z
z

HIGH IMPEDANCE
DIFFERENTIAL
PROTECTION

Requires Galvanic Connection


All CT ratios the same
Can Apply To

Application to other
Plant

Busbars
Transformers
Generators & Motors
Capacitors
Reactors

Barrie Moor, B Eng (Elec)

bmoor@powersystemprotection.com.au

Barrie Moor : 2012

Slide 25

bmoor@powersystemprotection.com.au

Slide 26

bmoor@powersystemprotection.com.au
(07) 3298 5260

Generator and
Power Station Protection

High Impedance Differential Protection

Generators & Motors

Auto Transformers
All CT ratios to
be the same
This CT will carry
maximum current
and hence
dictates ALL CT
ratios

Stabilising
Resistors

But this CT is internal


and may have a single
fixed ratio.
Thus, must be specified
correctly at time of
purchase !!

DIFF

Relays

bmoor@powersystemprotection.com.au

Slide 27

Restricted Earth Fault Protection

bmoor@powersystemprotection.com.au

Slide 28

Reactors Earthed Neutral

CT terminals
near to
protected object
are connected

DIFF

bmoor@powersystemprotection.com.au

Slide 29

Reactors Floating Neutral

DIFF

bmoor@powersystemprotection.com.au

Slide 30

Capacitors Earthed Neutral

DIFF

DIFF

CT terminals
away from
protected object
are connected

REF

DIFF

DIFF

DIFF

DIFF

DIFF

Floating neutral
bus is also protected

bmoor@powersystemprotection.com.au

Barrie Moor : 2012

Slide 31

bmoor@powersystemprotection.com.au

Slide 32

bmoor@powersystemprotection.com.au
(07) 3298 5260

Generator and
Power Station Protection

High Impedance Differential Protection

Capacitors Floating Neutral

DIFF

DIFF

DIFF

Floating neutral
bus is also protected

bmoor@powersystemprotection.com.au

Barrie Moor : 2012

Slide 33

bmoor@powersystemprotection.com.au
(07) 3298 5260

Generator and
Power Station Protection

Sequence Components

GENERATOR and
POWER STATION
PROTECTION

Sequence Components
z

SEQUENCE
COMPONENTS

A Quick Review

Positive Sequence
ABC
Equal in magnitude
120 degrees apart
Negative Sequence
AC B
Equal in magnitude
120 degrees apart
Zero Sequence
ABC
Equal in magnitude
In phase

V1
I1
V2
I2
V0
I0

Barrie Moor, B Eng (Elec)

bmoor@powersystemprotection.com.au

Slide 1

Sequence Networks
V1 = 1 / 0

I0
IA

Source

I phase
IB

Z1s

Relay
Location

Z1f
I1

Fault
Location

V2 = 0

V0 = 0

Source

Negative Sequence Network

I2

Positive Sequence Network

I1

Slide 2

Z2s

Relay
Location

Source
Zero Sequence Network

Sequence Components

bmoor@powersystemprotection.com.au

Z0s

Relay
Location

Z2f
I2

Fault
Location

Z0f
I0

Fault
Location

IC
bmoor@powersystemprotection.com.au

Slide 4

Sequence Components
Three phase conditions
z

bmoor@powersystemprotection.com.au

Slide 5

3 Phase Balanced Current

Positive sequence only

Three phase load


Three phase fault
No neutral (earth fault) current

bmoor@powersystemprotection.com.au

Barrie Moor : 2012

Slide 6

Balanced currents sum to zero


Positive sequence currents
Negative sequence currents
But zero sequence current will sum to 3.Io

bmoor@powersystemprotection.com.au

In =In3.Io
=0

Slide 7

bmoor@powersystemprotection.com.au
(07) 3298 5260

Generator and
Power Station Protection

Sequence Components

Sequence Networks
3 Phase Fault

Sequence Components
Phase Phase fault
Positive and Negative sequence components only
And consider the special case where
A phase equal in magnitude but opposite in phase

I3 _ Phase _ Fault = I1 =

V
Z POS

Positive Sequence Network

Source

Z POS = Z1s + Z1f

Z1s

Relay
Location

Z1f
I1

B to C
Phase to Phase fault

Fault
Location

bmoor@powersystemprotection.com.au

Slide 8

Sequence Networks (A phase)


Phase Phase fault

bmoor@powersystemprotection.com.au

Slide 9

Sequence Networks (A phase)


Phase Phase fault
I1 = I2

Z1f
I1

Fault
Location

Z2s

z
Relay
Location

Z2f
I2

Fault
Location

A phase
IA1 & IA2 antiphase
Sum to zero
B phase
IB1 & IB2 at 60o
C phase
IC1 & IC2 at 60o
IB = - IC

bmoor@powersystemprotection.com.au

Z1s

Relay
Location

Z1f
I1

Slide 10

Sequence Components
Phase Phase fault
z

Source

Fault
Location

V
Z pos + Z neg

Source

Negative Sequence Network

Relay
Location

Negative Sequence Network

Positive Sequence Network

Z1s

Source

Positive Sequence Network

z
Source

I1 = I2 =

Z2s

Relay
Location

Z2f
I2

Fault
Location

Since Z1 ~ Z2
|I1| = |I2| = 50%
of 3 phase fault
level

bmoor@powersystemprotection.com.au

Slide 11

Sequence Components
Earth Fault

|I1| = |I2| = 50% of 3 phase fault level


Thus |IB| = |IC| = 86.6% of 3 phase fault level
(because of 60o angles)

bmoor@powersystemprotection.com.au

Barrie Moor : 2012

Slide 12

A phase

bmoor@powersystemprotection.com.au

positive sequence
negative sequence
zero sequence

Equal in magnitude
and phase

Slide 14

bmoor@powersystemprotection.com.au
(07) 3298 5260

Generator and
Power Station Protection

Sequence Components

Sequence Networks
A Phase Earth Fault

Relay
Location

Z1f
I1

bmoor@powersystemprotection.com.au

Slide 15

Sequence Networks
A Phase Earth Fault
V2 = 0

Relay
Location

Z1f = 0.15
I1

Fault
Location

V1 = 0.75

Z2s = 0.10

V2 = -0.10
Relay
Location

Relay
Location

V2 = -0.25

I0

I = 1.0

Positive Sequence
Balanced three phase load
Balanced three phase fault
No neutral (earth) current
Negative Sequence
Unbalanced load
Phase to phase fault
No neutral (earth) current
Zero Sequence
Earth fault
Neutral current = 3 . Io
Cannot flow into or out of a delta
Can circulate around (within) the delta

bmoor@powersystemprotection.com.au

Barrie Moor : 2012

Fault
Location

Slide 16

V
Z pos + Z neg + Z zero

IB = 0
ZS2

ZS1

Fault
Location

V0 = -0.50

Relay
Location

INEUT = 3 I0

I = 1.0

Slide 17

I1

Relay
Location

ZS0

I2

Relay
Location

Zl

Zl

Zl

Fault
Location

Fault
Location

Fault
Location

Positive
Sequence

Negative
Sequence

I0

Zero
Sequence

bmoor@powersystemprotection.com.au

Sequence Components
Summary

Z0f
I0

Fault
Location

IC = 0

bmoor@powersystemprotection.com.au

Z2f
I2

IA = I1 + I2 + I0

V0 = -0.15

Z0f = 0.35

Fault
Location

I = 1.0

Relay
Location

bmoor@powersystemprotection.com.au

I1 = I2 = I0 =

Z0s= 0.15

Z2f = 0.15
I2

Relay
Location

Z0s

Source
Zero Sequence Network

V1 = 0.90

V0 = 0

Source

Negative Sequence Network

Positive Sequence Network

Z1s = 0.10

Z2s

Sequence Networks
A Phase Earth Fault

V1 = 1 / 0

Source

Fault
Location

Source
Zero Sequence Network

Z1s

Source

Negative Sequence Network

Source

Positive Sequence Network

Sequence Components
Earth Fault

Slide 18

GENERATOR and
POWER STATION
PROTECTION
Io = 0

TRANSFORMERS
and
SEQUENCE
COMPONENTS

Io = 0

Io = 0

Differential
Protection
Requirements

Io
Io
Io
3Io

Barrie Moor, B Eng (Elec)

Slide 19

bmoor@powersystemprotection.com.au

Slide 20

bmoor@powersystemprotection.com.au
(07) 3298 5260

Generator and
Power Station Protection

Sequence Components

Transformer Current Flows


z

Transformer Current Flows


z

Star / Star Transformer : LV Earth Fault

Current flows in corresponding HV winding


Appears as EF on the HV system also

Star / Star Transformer : LV Earth Fault


But, suppose we dont have an upstream power system earth
However, consider the effect of adding a delta connected tertiary
winding
HV line current flows in a 2:1:1 ratio
No I0 on the HV system as there is no path for neutral current flow

I0
I0
I1,
I1, I2
I2 &
& I0
I0

I1,
I1, I2
I2 &
& I0
I0

I1,
I1, I2
I2

I1,
I1, I2
I2 &
& I0
I0

So
So where
where did
did the
the I0
I0 go
go ??
??
bmoor@powersystemprotection.com.au

Slide 21

Star / Star Transformer : LV Earth Fault


Retain the delta connected tertiary winding
But, lets reinstate the power system earth
Power system and delta winding zero sequence current flow
distributions will depend on their relative Z0 impedances

I0I0

Star/Star transformers, with a delta tertiary winding:


Will have a mismatch between zero sequence current flows on
the HV & the LV windings
It is thus necessary to exclude zero sequence current from the
differential relay protection algorithms
Star/Star transformers, without a delta tertiary winding:
May still have a mismatch between zero sequence current flows
on the HV & the LV windings

I1,
I1, I2,
I2, I0I0

I1,
I1, I2
I2 &
& I0
I0

bmoor@powersystemprotection.com.au

Slide 24

Transformer Current Flows


z

The transformer tank can act as a low quality tertiary delta winding

It is thus still necessary to exclude zero sequence current from


the differential relay protection algorithms

bmoor@powersystemprotection.com.au

Slide 25

Positive Sequence Network

Delta / Star Transformer : LV Earth Fault

Slide 23

Transformers, Sequence Components


and Differential Protection

Transformer Current Flows


z

bmoor@powersystemprotection.com.au

ZS

Current in corresponding HV winding only


Appears as phase to phase fault from the perspective of
the HV system

ZS

I1
I1 &
& I2
I2 only
only

I1,
I1, I2
I2 &
& I0
I0

LV

LV

HV

Z1HL

HV

Zfdr

Zfdr

So
So where
where did
did the
the I0
I0 go
go ??
??
bmoor@powersystemprotection.com.au

Barrie Moor : 2012

Slide 26

bmoor@powersystemprotection.com.au

Slide 27

bmoor@powersystemprotection.com.au
(07) 3298 5260

Generator and
Power Station Protection

Sequence Components

Negative Sequence Network


ZS

ZS

LV

LV

HV

Z1HL

HV

Zero Sequence Network


Zfdr

ZS

Zfdr

ZS

bmoor@powersystemprotection.com.au

Slide 28

Transformer Current Flows


z

Slide 30

I1
I1 &
& I2
I2

bmoor@powersystemprotection.com.au

Slide 31

30 deg

Sequence Components
Transformer LV ph-ph fault
HV

Consider B-C fault on the LV of either of


Star Delta transformer
Delta Star transformer
30 deg phase shift
will shift + 30 deg
Positive seq components
Negative seq components
will shift - 30 deg

Barrie Moor : 2012

Slide 29

Current in all 3 LV windings


Current in all 3 HV windings
Appears as 2:1:1 fault on the HV system

30 deg

bmoor@powersystemprotection.com.au

Zfdr

I1
I1 &
& I2
I2

I1
I1 &
& I2
I2

Sequence Components
Transformer LV ph-ph fault

HV

Star / Delta Transformer : LV phase to phase fault

bmoor@powersystemprotection.com.au

Z1HL

Zfdr

bmoor@powersystemprotection.com.au

Current in 2 LV windings
Current in 2 HV windings
Appears as 2:1:1 fault on the HV system

I1
I1 &
& I2
I2

LV

HV

Transformer Current Flows

Delta / Star Transformer : LV phase to phase fault

LV

Slide 33

LV

LV phase to phase fault


HV distribution is 1 : 2 : 1
LV distribution is 0 : 1 : 1
So be careful when grading HV & LV IDMT OC Relays
|I1| = |I2| = 50% of 3 fault level
But note that I1 & I2 are 60o apart on the LV, but are shifted 30o and
are thus, for the 2 phase, in phase on the HV
LV current is 86.6% of 3 fault level in both phases
HV current in the 2 phase is the same as for LV 3 fault !!

bmoor@powersystemprotection.com.au

Slide 34

bmoor@powersystemprotection.com.au
(07) 3298 5260

Generator and
Power Station Protection

Sequence Components

Transformers, Sequence Components


and Differential Protection
z
z

Compensate for the transformer phase shift


Exclude zero sequence current from the differential relay
protection scheme

Zero sequence current can flow into and out of earthed


star windings
Zero sequence current cannot flow into or out of delta
windings
Zero sequence current can circulate around delta windings
(said to be trapped in the delta)

bmoor@powersystemprotection.com.au

Barrie Moor : 2012

Slide 35

bmoor@powersystemprotection.com.au
(07) 3298 5260

Generator and
Power Station Protection

Transformer Protection

GENERATOR and
POWER STATION
PROTECTION

Types of Fault
z
z
z

TRANSFORMER
PROTECTION

z
z
z
z
z
z

Phase-ground faults - from winding to core or winding to tank


Phase-phase faults - between windings
Interturn faults - between single turns or adjacent layers of the same
winding (Buchholz)
Arcing contacts
Local hotspots caused by shorted laminations
Low level internal partial discharges (moisture ingress or design
problems)
Bushing faults (internal to the tank)
Tapchanger faults (often housed in a separate tank)
Terminal faults (external to the tank, but inside the transformer zone)

Barrie Moor, B Eng (Elec)

bmoor@powersystemprotection.com.au

Slide 1

bmoor@powersystemprotection.com.au

Slide 2

Gas Sample

Buchholz Protection
z

Alarm

Two floats in the relay:


Upper float
z
z
z

Detects accumulation of gas


Detects loss of oil
Incipient faults

Float
To Tank

Partial discharge
Winding & core overheating
Bad contacts and joints
z

Trip

Pressure Relief Device (Qualitrol)

Float

To Conservator

z
BUCHHOLZ RELAY

May alarm only or may be set to trip

Lower float
z
z

Spring assisted pressure relief devices


Relieves pressure impulses due to massive internal fault conditions.
Helps prevent the tank bursting or splitting
Relay contacts are also connected to trip the transformer.
Since pressure waves travel with a finite velocity, they may rupture
the tank locally before the pressure wave has reached the pressure
relief device, if it is some distance away. Several units may therefore
be required on larger transformers.

Detects surge in oil < 100ms


Although it does take a finite time for
pressure waves to initiate Buchholz
tripping

bmoor@powersystemprotection.com.au

Slide 3

bmoor@powersystemprotection.com.au

GENERATOR and
POWER STATION
PROTECTION

Basic Transformer Protection


z

Fuses
Transformers without CBs
Perhaps to a few MVA
Overcurrent & Earth Fault Protection
Transformers with CBs
Perhaps 5 - 50MVA
Differential Protection
Transformers > 10MVA
z
z
z

Slide 4

TRANSFORMER
PROTECTION
Biased Differential
Protection

Fast
Can be sensitive
May detect terminal faults also

Barrie Moor, B Eng (Elec)

bmoor@powersystemprotection.com.au

Barrie Moor : 2012

Slide 5

bmoor@powersystemprotection.com.au

Slide 6

bmoor@powersystemprotection.com.au
(07) 3298 5260

Generator and
Power Station Protection

Transformer Protection

Differential Protection

IT IS NOT THE P1/S1 OR P2/S2


ORIENTATIONS THAT ARE
IMPORTANT, BUT THE
PREFERENCE FOR THE
AWAY SIDES OF THE CTs
TO CONNECT TO THE RELAY

Differential Protection of Transformers


11/132kV

CURRENT FLOWS
INTO PLANT

CURRENT FLOWS
OUT OF PLANT

P1

P2

S1

S2

2400A

2400/1

200/1

200A

TRIPPING ELEMENT
DETECTS ONLY THE
MIS-MATCH CURRENT
CURRENT FLOWS
INTO RELAY

SIDE OF CT AWAY
FROM PROTECTED
PLANT CONNECTS
TO RELAY

CURRENT FLOWS
OUT OF RELAY

Differential
Relay

TRIP
ELEMENT

1A
TRIP
ELEMENT

SIDE OF CT AWAY
FROM PROTECTED
PLANT CONNECTS
TO RELAY

bmoor@powersystemprotection.com.au

BIAS or
RESTRAINT
ELEMENT

Slide 7

Transformer Differential Mismatch


z

bmoor@powersystemprotection.com.au

CT ratios selected to compensate for the transformer turns


ratio

z
z

Mismatched CTs

BIAS or
RESTRAINT
ELEMENT

Slide 8

Transformer Differential Mismatch

Differential CT ratio selection

1A

CTs do not exactly compensate for transformer turns ratio


Transformer turns ratio changes with tap changing
Implement a biasing restraint system

Inrush on energisation (2nd harmonic)


Over excitation (5th harmonic)
Transformer phase shifts
Earth fault (neutral zero sequence) currents

Magnetizing current in the CTs, especially as some


saturation due to DC fault current sets in.

The amount of bias is increased under heavy through fault


conditions to compensate for possible CT saturation

bmoor@powersystemprotection.com.au

Slide 9

Inrush Current on
Energisation of Transformer

bmoor@powersystemprotection.com.au

Second Harmonic on Inrush


z

Transformer inrush current on energization.

TRIP
ELEMENT

bmoor@powersystemprotection.com.au

Barrie Moor : 2012

Slide 10

Slide 11

Inrush current produces a current from the energizing side


only, appearing as an internal fault.
Inrush current magnitude can be as great as a through 3
phase fault.
This current is characterized by the appearance of second
harmonics, so additional restraint can be based on this 2nd
harmonic signature
Relay setting below the 2nd harmonic level is required
(Ratio of 2nd harmonic to fundamental)

bmoor@powersystemprotection.com.au

Slide 12

bmoor@powersystemprotection.com.au
(07) 3298 5260

Generator and
Power Station Protection

Transformer Protection

Inrush current : with 2nd Harmonic

Fifth Harmonic on over excitation

Transformer Inrush Current


z

12

10

Current
8
6

z
4
2

Overfluxing, caused by too high a voltage, or too low a frequency.


Increased magnetising current
This is characterized by third & fifth harmonics.
Fifth harmonic restraint to retrain tripping of the differential
element
Typically no user calculations or settings are required
Sustained overfluxing may damage the transformer
Time delayed V/f tripping function (long time)
Especially applicable to generator transformers
z

2
0

0.05

0.1

0.15

0.2

0.25

0.3

0.35

0.4

0.45

0.5

Frequency can be anywhere from zero to nominal during run-up and


run down

Not so necessary for transmission or distribution applications


z

Frequency will not deviate significantly from nominal

Seconds

Transformer Inrush Current

bmoor@powersystemprotection.com.au

Slide 13

bmoor@powersystemprotection.com.au

GENERATOR and
POWER STATION
PROTECTION

Bias Differential Protection


z
z
z

Slide 14

Allow for Transformer turns ratio


Allow for Transformer phase shifts
Eliminate Zero Sequence currents from the relaying system

P1
S1

SEQUENCE
COMPONENTS

P1
S1

A Quick Review

Bias Windings

Operating
Winding

Barrie Moor, B Eng (Elec)

bmoor@powersystemprotection.com.au

Slide 15

GENERATOR and
POWER STATION
PROTECTION

bmoor@powersystemprotection.com.au

Slide 16

CT Connections and Ratios


z
z

TRANSFORMER
PROTECTION

z
z

Continued

Star/Delta and Delta/Star transformers have a 30 degree phase shift


Compensate with CTs connected opposite to the transformer
connections. ie:
Star connected CTs on the delta side of the transformer
Delta connected CTs on the star side of the transformer
Phase shift compensated
Zero sequence currents flowing in the transformer star windings
prevented from entering the relaying system
But how do we get the correct delta connection for our CTs ???

Barrie Moor, B Eng (Elec)

bmoor@powersystemprotection.com.au

Barrie Moor : 2012

Slide 17

bmoor@powersystemprotection.com.au

Slide 18

bmoor@powersystemprotection.com.au
(07) 3298 5260

Generator and
Power Station Protection

Transformer Protection

Determination of CT Connection

Determination of CT Connection

Yd11

Dy11

D11
D11

D1
D1

Diff Prot

Diff Prot

CT Primary is star connected


CT secondary is D11 connected
Overall connection is thus YD11

CT Primary is star connected


CT secondary is D1 connected
Overall connection is thus YD1

bmoor@powersystemprotection.com.au

Slide 19

Star/Delta and Delta/Star Transformers


CT Connection Summary
z

Slide 20

CT Connection Summary
z

Transformer HV is STAR connected


HV CTs are delta connected (ie. phase shifting)
HV CTs EQUAL to the transformer phase shift
LV CTs in star

Compensates for the phase shift across a star-delta


transformer.

Prevents any zero sequence currents flowing in the star


winding from entering the relay

And for Star / Star transformers ??

bmoor@powersystemprotection.com.au

Slide 21

CT YD11 Connections

The correct vector group must be chosen for the CTs to


ensure that through currents balance.

Transformer LV is STAR connected


LV CTs are delta connected (ie. phase shifting)
LV CTs OPPOSITE to the transformer phase shift
HV CTs in star

Since they are not present in the line on the delta side.
It is still necessary to eliminate Io from the relaying system
Connect CTs delta / delta
Or use the D12 / D12 feature of microprocessor relays

bmoor@powersystemprotection.com.au

Slide 22

CT YD1 Connections

S2

S2

S1

D11
D11

bmoor@powersystemprotection.com.au

D1
D1

S1
C

D11

A phase output is at "11 o'clock"

A phase output is at "11 o'clock"


A phase "S1" connects to B phase "S2"
B phase "S1" connects to C phase "S2"
C phase "S1" connects to A phase "S2"

A phase "S1" connects to B phase "S2"


B phase "S1" connects to C phase "S2"
C phase "S1" connects to A phase "S2"

Barrie Moor : 2012

S2
S1

bmoor@powersystemprotection.com.au

S2

S2

S1

D11

S1

S2

S1

S2
S2

C
S1

S1

S2

S1

Slide 23

bmoor@powersystemprotection.com.au

B
C

D1

A phase output is at "1 o'clock"


A phase "S2" connects to B phase "S1"
B phase "S2" connects to C phase "S1"
C phase "S2" connects to A phase "S1"

Slide 24

bmoor@powersystemprotection.com.au
(07) 3298 5260

Generator and
Power Station Protection

Transformer Protection

Away side of CTs connected to relay.


Hence, transformer current in or out
corresponds to relay current in or out

P1

P2

S1

S2

A1

A2

a2

a1

Transformer Current Flows

P2

P1

S2

S1

There must be a path for the current to flow


There must be an Ampere Turns balance
If there is current flowing in one winding

If there is no current flowing in one winding

z
z

Bias Windings

There must be current in the coupled winding


There can be no current in the coupled winding

Operating
Windings

Notice that the


connections for
the Delta windings
are the same !!
Away side of CTs connected to relay.
Hence, transformer current in or out
corresponds to relay current in or out.
bmoor@powersystemprotection.com.au

External Phase Earth Fault


P1

P2

S1

S2

A1

A2

a2

Slide 26

External Phase Phase Fault


a1

P2

P1

P1

P2

S2

S1

S1

S2

A1

A2

Bias Windings

Operating
Windings

Protection Scheme remains balanced


HV 0:1:1 (HV looks like a phase phase fault)
LV 0:0:1 (LV is actually a single phase fault)

Barrie Moor : 2012

1 / 0 1/-240
= 1.732 /-30
-24

bmoor@powersystemprotection.com.au

1/

P2

P1

S2

S1

Operating
Windings

Protection Scheme remains balanced


HV 1:2:1 (HV has a 2:1:1 current distribution)
LV 0:1:1 (LV is actually a phase phase fault)

Delta CTs and Ratio Selection

1/

CT ratios must allow for the fact


that current flowing into the
relay from the delta connected
CTs is 3 times the CT
secondary current
Hence, a standard 1A CT will
result in relay current of 3
times the CT secondary current
Thus, CTs with ratios such as
1000/0.577 are, for this reason,
quite common.

a1

Bias Windings

Delta CTs and Ratio Selection


z

a2

1 / -120

Slide 29

CT ratios must allow for the fact


that current flowing into the
relay from the delta connected
CTs is 3 times the CT
secondary current
Hence, a standard 1A CT will
result in relay current of 3
times the CT secondary current
Thus, CTs with ratios such as
1000/0.577 are, for this reason,
quite common.

bmoor@powersystemprotection.com.au

Ia - Ic = 1.732 /-30

Slide 30

bmoor@powersystemprotection.com.au
(07) 3298 5260

Generator and
Power Station Protection

Transformer Protection

S1

Select
SelectCT
CTRatios
Ratios

132/66/11kV
132/66/11kV
80/80/10
80/80/10MVA
MVA
HV
HV800/600/400/100/0.577
800/600/400/100/0.577
LV
800/600/400/100/0.577
LV 800/600/400/100/0.577
TV
TVSingle
Singleratio
ratio--TBA
TBA

S1

z
z
P1

S1

S1

S1

S1

P1

P1

C
S1

P1

TV CT Ratio Selection

P1

Select
SelectCT
CTRatios
Ratios

zz

zz

P1

z
z

HV : 80 MVA @ 132kV = 350A


HV CT provides
800/700/600/500/400/300/200/100/0.577
Select HV CT = 400/0.577

132/66/11kV
132/66/11kV
80/80/10
80/80/10MVA
MVA
HV
HV800/600/400/100/0.577
800/600/400/100/0.577
LV
LV800/600/400/100/0.577
800/600/400/100/0.577
TV
TVSingle
Singleratio
ratio--TBA
TBA

Tertiary : 10MVA @ 11kV = 525A


Try for Tertiary CT = 600/1

A
S1

B
S1

S1

S1

C
S1

z
z

But now check for stability due to


an out-of-zone tertiary 3 ph fault
Lets check for say 4800A @ 11kV

P1

P1
S1

S1

S1

S1

S1

S1

P1

P1

P1

P1

z
z
z
z

Slide 32

Select
SelectCT
CTRatios
Ratios

zz

TV CT Ratio Check

Tertiary out-of-zone 3 phase fault


of 4800A @ 11kV
CT = 600/1 star connected
Relay current = 8A

TV CT Ratio Review
HV CT is 400/0.577

Base the tertiary ratio on this and the transformer ratio


Not on Tertiary MVA rating

z
A
S1

B
S1

8A
8A

132/66/11kV
132/66/11kV
80/80/10
80/80/10MVA
MVA
HV
HV800/600/400/100/0.577
800/600/400/100/0.577
LV
LV800/600/400/100/0.577
800/600/400/100/0.577
TV
TVSingle
Singleratio
ratio--TBA
TBA

132kV current = 4800 * 11 / 132 = 400A


132kV CT is 400 / 0.577 delta connected
Relay current = 400 / (400/0.577) * 1.7321 = 1A

Select
SelectCT
CTRatios
Ratios

zz

132/66/11kV
132/66/11kV
80/80/10
80/80/10MVA
MVA
HV
HV800/600/400/100/0.577
800/600/400/100/0.577
LV
LV800/600/400/100/0.577
800/600/400/100/0.577
TV
TVSingle
Singleratio
ratio--TBA
TBA

Tert CT = HV CT * Tx Ratio
Tert CT = 400 * 132 / 11 = 4800/1

A
S1

B
S1

S1

z
z
z

Whoops !!!
Will trip on through current
Review Tertiary CT ratio

P1

P1
S1

S1

S1

S1

S1

S1

P1

P1

P1

P1

1A
1A

Re-check Tertiary out-of-zone


3 phase fault of 4800A @ 11kV
CT is now 4800/1 star connected
Relay current = 1A

z
z

132kV current = 4800 * 11 / 132 = 400A


132kV CT is 400 / 0.577 delta connected
Relay current = 400 / (400/0.577) * 1.7321 = 1A

Yes !!!
Remains stable on through current

Barrie Moor : 2012

S1

S1

S1

P1

P1

P1

132/66/11kV
132/66/11kV
80/80/10
80/80/10MVA
MVA
HV
HV800/600/400/100/0.577
800/600/400/100/0.577
LV
LV800/600/400/100/0.577
800/600/400/100/0.577
TV
TVSingle
Singleratio
ratio--TBA
TBA

HV CT = 400/0.577

LV : 80 MVA @ 66kV = 700A


LV CT provides 800/700/600/500/400/300/200/100/0.577
Select LV CT = 700/0.577
NO !!!!!!!!!!!!!!!!

A
S1

S1

S1

1A
1A
C

S1

P1

P1
S1

S1

S1

S1

S1

S1

P1

P1

P1

P1

z
A

z
A

Select
SelectCT
CTRatios
Ratios

LV CT Ratio Selection

S1

1A
1A
bmoor@powersystemprotection.com.au

S1

S1

P1

Slide 34

zz

132/66/11kV
132/66/11kV
80/80/10
80/80/10MVA
MVA
HV
HV800/600/400/100/0.577
800/600/400/100/0.577
LV
LV800/600/400/100/0.577
800/600/400/100/0.577
TV
TVSingle
Singleratio
ratio4800/1
4800/1

P1
S1

bmoor@powersystemprotection.com.au

z
z

P1

Select
SelectCT
CTRatios
Ratios

zz

Slide 33

TV CT Ratio Re-Check

C
S1

bmoor@powersystemprotection.com.au

bmoor@powersystemprotection.com.au

Base the LV CT on HV ratio


and the transformer ratio,
not on LV MVA rating
LV CT = 400 * 132/66
= 800 / 0.577

S1

P1

P1
S1

S1

S1

S1

S1

S1

P1

P1

P1

P1

Slide 35

bmoor@powersystemprotection.com.au

Slide 36

bmoor@powersystemprotection.com.au
(07) 3298 5260

Generator and
Power Station Protection

Transformer Protection

CT Ratio Selection

Modern Microprocessor Relays


z

The CT ratios must be opposite to the transformer ratio

Choose one CT ratio


Base all other CT ratios on this selection and transformer
turns ratio
Not on winding MVA !!!

All CTs connected in Star


Relay has to process phase shifts
Relay has to remove neutral current

And, as noted before CT ratios must allow for the fact


that current flowing into the relay from the delta connected
CTs is 3 times the CT secondary current

bmoor@powersystemprotection.com.au

S1

S1

S1

S1

S1

S1

P1

P1

IBRELAY = IB IA
ICRELAY = IC IB

D11

IA RELAY
1 1 0 IA
1


IBRELAY = 3 0 1 1 IB
ICRELAY
1 0 1 IC
A

Slide 39

D12

bmoor@powersystemprotection.com.au

Barrie Moor : 2012

S1

S1
B

S2

S2

S2

S2

S1

S1
C

D11

A phase output is at "11 o'clock"


A phase "S1" connects to B phase "S2"
B phase "S1" connects to C phase "S2"
C phase "S1" connects to A phase "S2"

B
C

D1

A phase output is at "1 o'clock"


A phase "S2" connects to B phase "S1"
B phase "S2" connects to C phase "S1"
C phase "S2" connects to A phase "S1"

bmoor@powersystemprotection.com.au

Slide 40

Modern Microprocessor Relays


D12 Zero sequence current elimination

Modern Microprocessor Relays

IA RELAY
2 1 1 IA

1

IB
=

RELAY

3 1 2 1 IB
ICRELAY
1 1 2 IC

S2

IARELAY
1 0 1 IA
1
IB


RELAY = 3 1 1 0 IB
ICRELAY
0 1 1 IC

D11

P1

D1

S1

IA RELAY
1 1 0 IA
1


IBRELAY = 3 0 1 1 IB
ICRELAY
1 0 1 IC

S1

IA RELAY
1 0 1 IA
1


IBRELAY = 3 1 1 0 IB
ICRELAY
0 1 1 IC

S2

D1

S1

P1

Slide 38

S1

IA RELAY
1 0 1 IA
1


IBRELAY = 3 1 1 0 IB
ICRELAY
0 1 1 IC

S1

Modern Microprocessor Relays

IA RELAY = IA IC

bmoor@powersystemprotection.com.au

S1

bmoor@powersystemprotection.com.au

P1

P1

S1

P1

Modern Microprocessor Relays


P1

S1

P1

Slide 37

P1

P1

P1

IA RELAY
2 1 1 IA

1

IB
=

RELAY

3 1 2 1 IB
ICRELAY
1 1 2 IC

IA RELAY =

1
(2 IA IB IC)
3

1
(3 IA IA IB IC)
3

1
(3 IA (IA + IB + IC))
3

1
(3 IA 3 I0)
3

= IA I0

Slide 41

bmoor@powersystemprotection.com.au

Slide 42

bmoor@powersystemprotection.com.au
(07) 3298 5260

Generator and
Power Station Protection

Transformer Protection

Modern Microprocessor Relays

CT Phase and Ratio Adjustment


TAP POSITION

All CTs can now be connected in Star

Dyn1
20MVA 33/11kV

Relay internal processing adjusts for phase angle


Relay internal processing rejects zero sequence
components

400/1

CT ratios mismatches can also now be accommodated

Magnitudes normalised to transformer FLC


Phase angles compensated
Zero sequence current eliminated

Slide 43

00
1A

Select one ratio to meet load requirements


Base all other ratios on the first (not on load !)

Yd11

1A

Software CT
x 1.429

Use the relay equations to determined the worst


mismatch
Typically

I1 + I2
2

Bias =

the worst mismatch of transformer ratio


and CT ratios (remember 3 for delta CTs !!!)

50%
Not Average !!

Diff = I1 + I2

At the top tap position .......... & then


At the bottom tap position.
And both should be the same for a microprocessor based
relay that is correctly mid tap balanced

bmoor@powersystemprotection.com.au

00

Slide 44

To decide worst case - consider the overall scheme

Differential
Element

bmoor@powersystemprotection.com.au

Allow Margin (perhaps 10-15%) allowing

Yy0
Software CT
x 1.143

Differential Relay Bias Settings

CT ratio selection

0.7A

Transformer Microprocessor Differential Protection Relay

Differential Relay Bias Settings

-300
-300

0.875A

Software
CT Ratio
Adjustment

1500/1

1050A
00

00

Internal processing within relay then adjusts CT current to


match transformer turns ratio
CTs can be fine tuned to match middle tap position
Allows for more sensitive relay settings

bmoor@powersystemprotection.com.au

350A

Slide 45

I1 & I2 are the currents into the two sides of the


transformer

bmoor@powersystemprotection.com.au

Slide 46

Tap Changer Position

Transformer Bias Differential Protection


4

For any setting of tap changer and through current, and


given the CT ratios, the values of bias current and
differential current can easily be calculated.
Base calculation on the relay algorithm not on an
arbitrary or simple mismatch calculation

Diff := I1 + I2

OPERATE
OPERATE

1.5

RESTRAIN
RESTRAIN

Through
ThroughFault
Faultwith
with
CT
CTSaturation
Saturation

1
0.5

Probably 10 15%

And check your elbow !!

Barrie Moor : 2012

Transformer
Transformer
Internal Fault
Internal Fault
Protection Trips
Protection Trips

Note that the previous equations are not the only options
available to and used by relay manufacturers
Hence use THE ACTUAL RELAY equations !!

bmoor@powersystemprotection.com.au

3.5

2.5

Allow the recommended safety margin

Differential
Current

0.5

1.5

15% Differential Setting


25% Differential Setting
35% Differential Setting

Slide 47

bmoor@powersystemprotection.com.au

2.5

3.5

Bias Current

Through
ThroughFault
Fault
Mismatch
Mismatchdue
duetotoCT
CTRatios
Ratios&&
Transformer
TransformerTap
TapChanging
Changing
4.5
5
5.5
6

Bias :=

I1 + I2
2

Slide 48

bmoor@powersystemprotection.com.au
(07) 3298 5260

Generator and
Power Station Protection

Transformer Protection

GENERATOR and
POWER STATION
PROTECTION

CT Requirements
z

Some CT saturation is permissible for through faults

Such CT saturation occurs mainly due to the DC


component of the fault current

TRANSFORMER
PROTECTION

Most manufacturers provide simple equations to


determine CT class

No complex calculations required

Winding Neutral
End Faults
Barrie Moor, B Eng (Elec)

bmoor@powersystemprotection.com.au

Slide 49

bmoor@powersystemprotection.com.au

Slide 50

Transformer Neutral Fault Current & Primary Current

Protection for neutral end earth faults

Significant current flows in the


actual fault near to the neutral
end of the transformer winding

16

14

Differential Protection

FAULT
CURRENT

Small current
Many turns

12

10

Line current mismatch


is too small to trip the
differential relay

multiples
of
rated
current

Large current
Few turns

But very little line


current flows at the
HV terminals

We need to monitor
neutral current flow

0
0

10

20

30

40

Fault Current in Shorted Turns


Primary Current

bmoor@powersystemprotection.com.au

Slide 51

50

60

70

80

90

100

DISTANCE OF FAULT
FROM NEUTRAL
(Percentage of winding)

bmoor@powersystemprotection.com.au

Slide 52

Auto Transformer
High Imp Phase Segregated Protection

Restricted Earth Fault Protection

All CT ratios to
be the same
This CT will carry
maximum current
and hence
dictates ALL CT
ratios

CT terminals
near to
protected object
are connected

REF

bmoor@powersystemprotection.com.au

Barrie Moor : 2012

CT terminals
away from
protected object
are connected

DIFF

Slide 53

bmoor@powersystemprotection.com.au

But this CT is internal


and may only have a
single fixed ratio.
Therefore, this must be
specified correctly at
the time of purchase !!

Slide 54

bmoor@powersystemprotection.com.au
(07) 3298 5260

Generator and
Power Station Protection

Transformer Protection

HV CTs

High Impedance Protection


z
z

LV CTs

One per phase at neutral end


But above the star point

Especially sensitive in detecting earth faults in the


bottom 25% of the winding
Application to

Neutral CTs

Auto Transformers
REF earth fault schemes

Tertiary windings not specifically protected


Setting principles same as for bus zone

Select voltage setting to achieve through fault stability


CT Vk > 2.Vset to ensure scheme operation

Tertiary
High
Impedance
Relays

bmoor@powersystemprotection.com.au

Slide 55

GENERATOR and
POWER STATION
PROTECTION

Restricted Earth Fault Protection


HV scheme also remains
stable for all LV EFs

LV scheme remains
stable for external EF

HV scheme remains
stable for external EF

EARTHING
TRANSFORMERS

Restricted EF Prot

Operation
and
Protection

Restricted EF Prot
Barrie Moor, B Eng (Elec)

Transformer delta winding and star winding REF protection schemes


bmoor@powersystemprotection.com.au

Earthing Transformer Fault Currents

Slide 58

Earthing Transformer

LOAD

B
C
Earthing Transformer

bmoor@powersystemprotection.com.au

Barrie Moor : 2012

Slide 59

bmoor@powersystemprotection.com.au

Slide 60

bmoor@powersystemprotection.com.au
(07) 3298 5260

Generator and
Power Station Protection

Transformer Protection

Earthing Transformer Fault Currents

Earthing Transformers
z
z

LOAD

z
z

Provide a good earth reference for a delta winding during


earth faults
Restrict the voltage rise on the healthy phase during
earth faults inoperative during balanced voltage
conditions
Carry significant current only during earth faults
ie. 3 x I0 only
Earthing transformer and associated power transformer
considered as a single unit and tripped together

Earthing Transformer

bmoor@powersystemprotection.com.au

Slide 61

Effectively Earthed System

R0/X1 < 1
X0/X1 < 3

Limit voltage rise on unfaulted phases

Slide 63

Over Current Protection

Two types of faults we need to consider:

Internal faults - faults inside the earthing transformer, the


result of insulation breakdown.

External faults - faults on the system outside the earthing


transformer. These can cause overheating of the earthing
transformer

bmoor@powersystemprotection.com.au

Interturn, interwinding or winding-to-core faults


Fed from delta-connected current transformers, so that
earth faults on the system, which generate only zero
sequence current, are not seen
Hence, O/C setting can be very low

Earth Fault Protection

Barrie Moor : 2012

Long term low level unbalance may cause thermal


damage
Need to consider and set earth fault below
z
z

bmoor@powersystemprotection.com.au

Slide 64

Earth Fault Protection

Over Current Protection

Slide 62

Protection of Earthing Transformer

80% of rated phase - phase voltage


Otherwise healthy phases can reach 100% of rated phase
- phase voltage
May even exceed this on transients

bmoor@powersystemprotection.com.au

bmoor@powersystemprotection.com.au

Slide 65

continuous rating capability


short-time rating capability

Combination of IDMT and definite time functions used

bmoor@powersystemprotection.com.au

Slide 66

bmoor@powersystemprotection.com.au
(07) 3298 5260

Generator and
Power Station Protection

Transformer Protection

Overcurrent Setting Must be:


z
z

LOAD

O/C relay
z

Def Time E/F relay


IDMT E/F relay

Earthing Transformer

bmoor@powersystemprotection.com.au

Slide 67

bmoor@powersystemprotection.com.au

Earth Fault Protection


Affected by long term residual voltage, which may cause
thermal damage

actual thermal limit

30

1 10

adiabatic
thermal limit
4

1 10

remember - no over temperature sensor is provided

Need to consider and set earth fault below

Thermal Protection

1 10
TIME - SECONDS

Slide 68

2300

O/C relay does not operate for external


earth faults
Def Time and IDMT E/F relays operate for
external earth faults

Greater than the magnetising current


Greater than the maximum inrush current. This depends on
Earthing transformers B-H characteristics
The point-on-wave of the energisation
The remanence of the core
One common estimate of upper bound is 50x the magnetising
current
Tolerant of Earthing Transformer manufacturing variations
Impedances variations between the individual phases of the
earthing transformer may result in some spill current from the
delta CTs under through EFs

continuous rating capability


short-time rating capability

Combination of IDMT and definite time relays used to do


this

earthing transformer E/F relay - Definite Time


100

10

earthing transformer
E/F relay - IDMT
downstream E/F relay

0.1
10

bmoor@powersystemprotection.com.au

cont
rating
30A

100
1 10
EARTH FAULT CURRENT - AMPS

EARTHING TRANSF THERMAL PROTECTION

max E/F
current
2300A

1 10

Slide 69

Earthing Transformer CTs


Differential Trip due to LV I0 Currents

Biased Differential Protection


400/0.577
z
z

Earthing transformers are included inside the biased differential


zone of their power transformer
Current transformer connections important
LV CTs will be star connected
Thus Io can flow to the differential relay
And earthing transformer now supplies Io
Thus stability for external earth faults becomes an issue

1600/1
0
0

a
b
c

external
earth
fault

To eliminate Io from the relaying system

132 / 33 kV

YD12 CT connection with microprocessor differential relay


Or utilise additional Earthing Transformer CT connections

bmoor@powersystemprotection.com.au

Barrie Moor : 2012

Slide 71

bmoor@powersystemprotection.com.au
(07) 3298 5260

Generator and
Power Station Protection

Transformer Protection

Earthing Transformer CTs


Eliminate I0 from the relaying system

Zero Sequence Current Trap

400/0.577
A

1600/1
0

132 / 33 kV
0

CT includes a delta tertiary


winding to trap zero
sequence currents

b
c

C
all 1600/0.333
N

Star connected interposing


CTs with neutral connection

external
earth
fault

Interposing CT secondary
without neutral connection
3 wire connection to the relay
I1 & I2 only

bmoor@powersystemprotection.com.au

GENERATOR and
POWER STATION
PROTECTION

Modern Microprocessor Relays

D1
D11
D12

Slide 74

IARELAY
1 0 1 IA
= 1 1 1 0 IB
IB
RELAY


3
0 1 1 IC
ICRELAY

TRANSFORMER
PROTECTION

IARELAY
1 1 0 NoIA

phase change
1
IB

IB

1removes
1 But,
RELAY = 3 0
neutral current
1 0
1 IC
ICRELAY

Delta Windings with


Earthed Corner

IARELAY
2 1 1 IA
IB
1

RELAY = 3 1 2 1 IB
ICRELAY
1 1 2 IC

Barrie Moor, B Eng (Elec)

bmoor@powersystemprotection.com.au

Slide 75

Typical for transformer tertiary windings


To maintain stability on through faults

Slide 76

Earthed Delta Corners inside the


Differential Zone

Delta windings with earthed corner


z

bmoor@powersystemprotection.com.au

Need to include CT in the earthed corner


CT to be the same ratio as the main CT
Connect in parallel with the earthed phase CT

This cannot be overcome with phase shifting and Io


facilities of microprocessor based relays

CT installed on the earthed corner.


Same ratio as phase CTs
In parallel with the phase CT on
the earthed phase
This is also required for
microprocessor relay schemes
bmoor@powersystemprotection.com.au

Barrie Moor : 2012

Slide 77

bmoor@powersystemprotection.com.au
(07) 3298 5260

Generator and
Power Station Protection

Transformer Protection

GENERATOR and
POWER STATION
PROTECTION

Neutral Displacement Protection


z
z

TRANSFORMER
PROTECTION

Applicable to delta windings with no earth reference


Connected to open delta of VT secondary

z
z

Neutral Displacement
Protection

To provide a zero sequence flux path


3 x 1 phase VTs or
5 limb VT

Relay must be immune to 3rd harmonics


Tripping time can be relatively slow
Problems can occur with resonance on energisation

Barrie Moor, B Eng (Elec)

bmoor@powersystemprotection.com.au

Slide 79

Neutral Displacement Protection

bmoor@powersystemprotection.com.au

Slide 80

Neutral Displacement Protection


z

Measures 3.Vo for a solid E/F

VT with open delta


secondary winding

Healthy phases rise to full phase-phase potential


Healthy phases are now only 60 deg apart
Thus, for standard 63.5V VT, output voltage is 190.5V
Set relay to 10% say 20V

190.5
0
63.5
VV VVVV
0110
63.5
190.5
110
VA = 0

Voltage
Displacement
Relay

bmoor@powersystemprotection.com.au

Barrie Moor : 2012

Slide 81

bmoor@powersystemprotection.com.au

VC = 3

VB = 3

+150

-150

Neutral
Displacement
Protection

Slide 82

bmoor@powersystemprotection.com.au
(07) 3298 5260

Generator and
Power Station Protection

Motor Protection

GENERATOR and
POWER STATION
PROTECTION

Motor Protection
z

To detect faults within the motor and supply system

MOTOR
PROTECTION

Thermal Withstand

Faults on the supply system, cables, etc


Internal faults
Often as a result of previous thermal events
Motor overload
Starting and Stalling currents & times
Unbalanced voltage supply (NPS)

System events

Loss of load, under voltage, etc.

Barrie Moor, B Eng (Elec)

bmoor@powersystemprotection.com.au

Slide 1

bmoor@powersystemprotection.com.au

GENERATOR and
POWER STATION
PROTECTION

Motor Protection
z
z
z
z
z
z
z
z
z
z

Thermal Protection
Extended Start Protection
Stalling Protection
Number of Starts Limitation
Negative Sequence Current Detection
Short Circuit Protection
Earth Fault Protection
Under Voltage Protection
Loss of Load Protection
Winding RTD measurement and trip

Slide 2

MOTOR
PROTECTION

THERMAL
PROTECTION

Thermal Protection

Barrie Moor, B Eng (Elec)

bmoor@powersystemprotection.com.au

Slide 3

Thermal Overload Protection

bmoor@powersystemprotection.com.au

Slide 4

61

Starting Current

5
0.8

z
z

Winding failures are often due to previous heating


Because of the motors thermal mass

Infrequent short term overloads may have no affect


But sustained overloads, of even just a few percent, may
cause aging and premature insulation failure
Insulation life may be halved for operation every 10 deg C
above rated maximum.

High starting current reduces


to full load current as the motor
gains speed
Positive sequence impedance
of the motor at any slip is :-

4
0.6

IZ( (ss) )

0.4
2
0.2
1

250

500

750

2
Z POS = R S1 + R1 + (X S1 + X R 1 )
S

bmoor@powersystemprotection.com.au

Barrie Moor : 2012

1000

1250

1500

Slide 5

bmoor@powersystemprotection.com.au

Slip =

NSYNC N ACT
NSYNC

Slide 6

bmoor@powersystemprotection.com.au
(07) 3298 5260

Generator and
Power Station Protection

Motor Protection

Motor Impedances

Positive Sequence Impedance

(Rs1 + Rr1)

j(Xs1 + Xr1)

At any slip
2

2
Z POS = R S1 + R1 + (X S1 + X R1 )
S

(1 - S) Rr1
S

Positive Sequence Equivalent Circuit


of Induction Motor

(Rs2 + Rr2)

At standstill with slip = 1.0

j(Xs2 + Xr2)

Z POS =

(R S1 + R R1 )2 + (X S1 + X R1 )2

(S - 1) Rr2

(2 - S)

Negative Sequence Equivalent Circuit


of Induction Motor

bmoor@powersystemprotection.com.au

Slide 7

Negative Sequence Impedance


z

This is a small impedance, hence high starting current


eg. up to 6 pu

bmoor@powersystemprotection.com.au

Slide 8

Motor Impedances
z

At any slip

Positive Sequence : Standstill


Z POS =

2
Z NEG = R S2 + R 2 + (X S2 + X R 2 )
2S

(R S1 + R R1 )2 + (X S1 + X R1 )2

Negative Sequence : Running

At normal running with slip 0

2
Z NEG = R S2 + R 2 + (X S 2 + X R 2 )
2

2
Z NEG = R S 2 + R 2 + (X S 2 + X R 2 )
2

R is small compared with X:

These will be approximately the same !!

Z POS STANDSTILL = Z NEGRUNNING


bmoor@powersystemprotection.com.au

Slide 9

Motor Impedances
z
z

Barrie Moor : 2012

Positive sequence impedances at Start-up & Running


ZPOSSTARTING
ZPOSRUNNING

ZPOSRUNNING

Slide 11

bmoor@powersystemprotection.com.au

Full Load Current


Starting Current

eg. 1/6 th

eg. ZNEG = ZPOS / 6


So, what does this
mean for NPS current

ZPOSSTARTING = ZNEGRUNNING

And since:
ZNEGRUNNING

Or, as a typical example, when running, 1% NPS


supply voltage would result in:
6% NPS current

bmoor@powersystemprotection.com.au

Slide 10

Motor Impedances

Consider an example where ISTART/IFLC = 6


Hence, 1pu positive sequence supply voltage results in:
1 pu current when running at full load
6 pu current at start-up
But the negative sequence impedance at running is the
same as the positive sequence impedance at startup
So, when running, 1 pu NPS supply voltage would
result in:
6 pu NPS current

bmoor@powersystemprotection.com.au

Full Load Current


Starting Current

Slide 12

bmoor@powersystemprotection.com.au
(07) 3298 5260

Generator and
Power Station Protection

Motor Protection

Negative Sequence Current


z

Question

Negative sequence current will equal:

% of NPS in the supply voltage


Multiplied by the ratio of starting / full load current
Multiplied by full load current

z
z

An induction motor starting current is 6 times the full load


running current.
The supply is unbalanced so that there is 5% NPS
component in the voltage component.
What will the NPS current component be (as a percent of
positive sequence FLC)

V Starting Current
INPS = NPS
[IFLC ]
FLC

VPOS

bmoor@powersystemprotection.com.au

Slide 13

Question
z

bmoor@powersystemprotection.com.au

Rotor Currents

A motor operates at a slip on 0.05

z
z

The rotor currents due to the positive sequence supply


current will be at what frequency ?

The rotor currents due to the negative sequence supply


current will be at what frequency ?

bmoor@powersystemprotection.com.au

Slide 15

Negative Sequence Protection


z

IEQ =

(IPOS )2 + (K INPS )2

INPS =

VNPS Starting Current

IFLC
VPOS
FLC

K=1.5 to 6

bmoor@powersystemprotection.com.au

Low level setting to provide alarm


IDMT element for tripping

Slide 16

Impedance increases as the motor speeds up


2

2
ZPOS = RS1 + R1 + (XS1 + XR1)
S

Time grade/time delay, as possible

Due to Positive Sequence Supply : close to DC


Due to Negative Sequence Supply : close to double
frequency
NPS current skin effects exacerbate rotor heating

Motor Starting Current vs Speed

Two stage protection

Slide 14

To allow unassociated system NPS events (eg. system


earth faults) to be cleared by their protection systems

And hence, current reduces with speed

Also the speed does not


increase linearly with time
Acceleration tends to be slow
initially
And, especially so, with high
inertia loads

I( s)

250

500

750

1000

1250

1500

bmoor@powersystemprotection.com.au

Barrie Moor : 2012

Slide 17

bmoor@powersystemprotection.com.au

Slide 18

bmoor@powersystemprotection.com.au
(07) 3298 5260

Generator and
Power Station Protection

Motor Protection

Motor Starting Current vs Time


Speed

Starting & Stalling


z

Motor current remains practically unaltered during the


entire starting time
Current alone cannot distinguish between:

I( s)

Normal starting
Stalled condition

z
2

Low Inertia Loads

2502

3 500 4

750
5

6 10007

81250 9

Rapid Starting
Starting time is likely to be less than the safe stall time
Duration of starting current distinguishes starting/stalling

1500
10

t ( ss)

bmoor@powersystemprotection.com.au

Slide 19

Starting & Stalling


z

Older Style Relays

Electronic & Numeric Relays

Long time for a normal start up 10s of seconds

Long time starting is OK due to cooling from rotation and


windage

Safe stall withstand time may be less than normal starting


time

Speed switch interlock confirms a normal start

Slide 20

Motor Thermal Protection

High Inertia Loads

bmoor@powersystemprotection.com.au

Characteristics may be questionable


Characteristics easily adapted by the user to match the
motor characteristic

A stalled motor receives no cooling and may be damaged

bmoor@powersystemprotection.com.au

Slide 21

Motor Thermal Protection


(eg. via P&B Golds Relay)
z

C
B
Fixed Trip
Contact

Flag

z
HEATERS

Slide 22

Stalling of a Motor, Once Running

Thermal Contacts

bmoor@powersystemprotection.com.au

A, B & C phase elements


operated via
Heaters
Bi-metallic coils
Elements trip for
Overload
Unbalance
Saturating CT elements
provide for
Relay settings
De-sensitise to heavy
starting currents

Stalling of a motor once running (eg. due to a bearing


seizure)

Successful start-up and current has fallen to FLC


Massive rise in current due to stalled motor event
Rapid tripping now required
Interlock with under-voltage detection, as necessary

Perhaps to allow re-acceleration following a system voltage


dip
Perhaps to prevent re-acceleration following a system
voltage dip

SATURATING CURRENT TRANSFORMERS

bmoor@powersystemprotection.com.au

Barrie Moor : 2012

Slide 23

bmoor@powersystemprotection.com.au

Slide 24

bmoor@powersystemprotection.com.au
(07) 3298 5260

Generator and
Power Station Protection

Motor Protection

Stalling of a Motor, Once Running


z

Temperature Detection Devices


z

Bearing failure

Roller bearings tend to fail very quickly

Protection is basically limited to preventing consequential


thermal damage to the motor

Sleeve bearings temperature rise may be indicative of


prospective failure

RTDs or Thermistors
Measure temperature of:

Detect:

Also include RTD bearing temperature detection

Slide 25

Number of Starts Limitation


z
z

bmoor@powersystemprotection.com.au

Slide 27

Barrie Moor : 2012

Slide 28

Protects against failure of mechanical systems, eg:

Slide 29

Breakage of a conveyor belt


Loss of pump priming

Based on a low power element

2 heating time constants are required


In star connection, the winding current equals the line current
In delta connection, the winding current reduces to 0.577 times
the line current

bmoor@powersystemprotection.com.au

bmoor@powersystemprotection.com.au

Motor power, required to drive the load, is the same


Hence, supply line current to the motor also remains unchanged
But, via the delta connection, the motor winding voltage has now
increased by a factor of 1.732
Therefore, motor winding current reduces to 0.577

Relays require a dual slope characteristic

This line current is thus 1/3 of the delta connected DOL current

Change to delta connection, once motor approaches full


speed

Loss of Load Protection

At full speed, independent of motor connection (star or delta)

Each phase winding is only supplied at VPH-N voltage


Hence, motor winding current is reduced to 0.577 of the delta
connected DOL current
Line current is the same as the motor winding current

Star / Delta Starting Systems

Requires both ends of all 3 phase windings to be made available


to the switching circuitry

Star connection for start-up

Slide 26

Motor is initially star connected, to limit the starting current

Less number of hot starts are allowable


Relay must maintain a separate count of hot and cold
starts
Relay interlock enforces the necessary time delay required
between successive starts to provide for motor cool down

bmoor@powersystemprotection.com.au

Alarm & Trip


Fine tune the relays thermal algorithm

Star / Delta Starting Systems

Starting blocked if the permitted number of starts is


exceeded
Hot & Cold starts

Motor overloading
Prospective failure of associated plant
Prospective failure of sleeve bearings

Actions:

bmoor@powersystemprotection.com.au

Motor windings
Shaft bearings

Must be configured to not prevent motor starting


Low inertia loads (eg. compressors) may require this to be
inhibited during the entire startup period
Time delay required to prevent mal-operation during
system transient events

bmoor@powersystemprotection.com.au

Slide 30

bmoor@powersystemprotection.com.au
(07) 3298 5260

Generator and
Power Station Protection

Motor Protection

GENERATOR and
POWER STATION
PROTECTION

Under Voltage Protection


z
z

Motor may stall under sustained under voltage


For transient under voltages (due to unrelated system
events):
Time delay to allow the motor to re-accelerate, if the plant
requirements permit

MOTOR
PROTECTION

Contactors may need to be latched

Trip the motor if plant operation would be threatened by


the re-acceleration or re-start, following a system event
Under voltage protection must allow for voltage suppression
on start-up
Settings <80% are typical
Ensure any under voltage protection does not block normal
starting

Short Circuit
Protection
Barrie Moor, B Eng (Elec)

bmoor@powersystemprotection.com.au

Slide 31

Short Circuit Protection


z

Motor design makes internal phase-phase faults very


unlikely
Any internal phase to phase fault will almost certainly also
involve earth
However, phase to phase faults are significantly more
likely on the supply cable or within the motor terminal box

Slide 33

Motor Thermal & HZ EF Protection


z
z

Stabilising
Resistor
EARTHFAULT
PROTECTION

bmoor@powersystemprotection.com.au

Barrie Moor : 2012

Ideally, set for instantaneous operation


Hence, set above starting current

bmoor@powersystemprotection.com.au

Slide 34

High Impedance EF Protection

EF protection via residual


connection of CTs
Low impedance EF protection
OK for CTs with adequate
knee point voltage
High impedance EF protection
applicable for lower quality
CTs

Time delayed characteristic


IDMT characteristic

High set elements to quickly clear major faults

bmoor@powersystemprotection.com.au

Set above FLC, but below start-up current


To prevent mal-operation during start-up

Be aware of mal-operation due to CT unbalance due to


high starting currents

Motor
Thermal Protection

Sensitive elements may detect faults in their early stages


and hence minimise fault damage.

Earth Faults

Slide 32

Short Circuit Protection

Phase - Phase Faults

bmoor@powersystemprotection.com.au

Allows for CT saturation on


starting current
(No through fault condition to
consider).

Otherwise, EF protection will


require a time delay to prevent
mal-operation during start-up

Slide 35

ISTART
RSTAB =
z
z
z
z

CTRATIO
(RCT + k RL + RR )
IEFsetting

RCT = CT resistance
RR = Series connected O/C and/or thermal relay resistance
RL = Lead resistance (one way)
k = CT connection factor

k = 1 for 4 wire connection : star point at CT typical


k = 2 for 6 wire connection : star point at relay unusual

bmoor@powersystemprotection.com.au

Slide 36

bmoor@powersystemprotection.com.au
(07) 3298 5260

Generator and
Power Station Protection

Motor Protection

Sensitive EF Protection via


Core Balance CT
z

Core Balance EF Protection and Cables

Resistance earthed systems

Core balance EF protection allows for sensitive settings


Setting should be <30% of EF current
Setting must be >3 times the steady state charging current
of the feeder

To prevent mal-trip during un-associated system earth faults

Otherwise, utilise a VT supply to implement a directional core


balance SEF scheme
All three phases pass through a single CT
Also, the neutral for a 4 wire system
Beware of sheath earthing requirements for cable systems

bmoor@powersystemprotection.com.au

SEF

Slide 37

Fuse Contactors

Cable sheath earthing via


the core balance CT
ensures detection of phase
to sheath faults

bmoor@powersystemprotection.com.au

Slide 38

Fuse Contactors
100

High fault level applications

eg

40kA fault level


Contactor rated to only 10kA
Fuse operates for all faults above say 7 kA
Contactor and associated protection relay operate for
lower fault levels
Warning the fuse may also have a minimum breaking
capacity and the contactor must be set to operate above
this point

0.1

10kA Contactor
operates for faults
below 7kA 0.01
100

bmoor@powersystemprotection.com.au

Fuse operation
below 2kA is not
permissible

10

Slide 39

bmoor@powersystemprotection.com.au

Fuse operates for


faults above 7kA
1 .10

Fuse
Relay / Contactor
Fuse

1 .10

1 .10

Slide 40

Differential Protection

Stabilising
Resistors
Relays

bmoor@powersystemprotection.com.au

Barrie Moor : 2012

Slide 41

bmoor@powersystemprotection.com.au
(07) 3298 5260

Generator and
Power Station Protection

Generator Protection

GENERATOR and
POWER STATION
PROTECTION

Generator Protection
z

Generator Fault

Generator Event

External Event

GENERATOR
PROTECTION

Rapid tripping necessary


Slower tripping, with alarm to allow operator intervention
Remember that every generator in the power station will
see this event
Remote power stations may also see this event
Tripping to be as slow as possible, with alarm to allow
operator intervention
Islanding may also be an option

Barrie Moor, B Eng (Elec)

bmoor@powersystemprotection.com.au

Slide 1

GENERATOR and
POWER STATION
PROTECTION

bmoor@powersystemprotection.com.au

Slide 2

Differential Protection
z
z

GENERATOR
PROTECTION

Generator Faults

Detects multiphase faults


Earth faults typically limited by high resistance earthing
Consequences of multiphase faults
Damage due to fault current
Damage due to unbalanced mechanical forces
Generator design to minimise risk
Design to minimise risk of multiphase faults
Earth switch systems
Differential protection schemes
Bias Differential
High Impedance Differential
Overall Differential

Barrie Moor, B Eng (Elec)

bmoor@powersystemprotection.com.au

Slide 3

Bias Differential Protection

bmoor@powersystemprotection.com.au

Biased Differential Protection


z

Current Transformers

Bias

Neutral and Line CTs to be matched


Good quality : Class PX recommended

Protection

Select a relay operating quantity,


eg. Vector addition of CT currents

I1 + I2

Select a relay restraining quantity,


eg. 50% of scalar addition of CT currents

I1 + I2
2

Bias

Operate

bmoor@powersystemprotection.com.au

Barrie Moor : 2012

Slide 4

Slide 5

bmoor@powersystemprotection.com.au

Slide 6

bmoor@powersystemprotection.com.au
(07) 3298 5260

Generator and
Power Station Protection

Generator Protection

Bias Differential Protection


Under Through Fault Conditions

Bias

Bias Differential Protection


Under Internal Fault Conditions

Bias

I1

Bias

I2

Bias

I1

I2

Operate

Operate

I1+I2 0

I1+I2 = IF

bmoor@powersystemprotection.com.au

Slide 7

Biased Differential Protection


Typical Relay Characteristic

bmoor@powersystemprotection.com.au

Biased Differential Protection


Typical Relay Characteristic

I1 + I2

I1 + I2

Operating Current

Operating Current

TRIP
TRIP
RESTRAIN
RESTRAIN

TRIP
TRIP
RESTRAIN
RESTRAIN

Restraint (Bias) Current

I1 + I2
2

bmoor@powersystemprotection.com.au

Restraint (Bias) Current

Slide 10

Biased Differential Protection


z

Slide 8

I1 + I2
2

bmoor@powersystemprotection.com.au

Slide 11

High Impedance Differential Protection

Protection - Can be set reasonably sensitive

CTs are matched


No phase angle mismatch across the generator
No neutral current (zero sequence) mismatch
No over excitation (3rd & 5th harmonic) mismatch
No 2nd harmonic (transformer inrush) mismatch
z

Nevertheless, a small amount of 2nd harmonic restrain may


be warranted, especially if a hard energisation of the
generator transformer may occur

Relay bias
z
z

Allows for any CT mismatch


Bias increased at higher fault currents to accommodate any
CT saturation

bmoor@powersystemprotection.com.au

Barrie Moor : 2012

Slide 12

bmoor@powersystemprotection.com.au

Slide 13

bmoor@powersystemprotection.com.au
(07) 3298 5260

Generator and
Power Station Protection

Generator Protection

High Impedance Differential Protection


z

CTs are matched

High Impedance Differential Protection

Exactly the same ratio ie no compensating turns !!


Class PX recommended

Worst mismatch ??

CT saturation on a heavy through fault


Ensure stability for this as worst case event

Zmag = 0
Rct
Rleads

Rstab

V=

IF
(R CT + R LEADS )
CT

Rleads

bmoor@powersystemprotection.com.au

Slide 14

High Impedance Differential Protection


Setting Voltage and Margins
z

High Impedance Differential Protection

AC Component
DC Component

Hence, employ a DC Stabilised Relay

And considering 0% / 100% CT saturation case

No additional margin on the setting is required


This in an unrealistically extreme case
100% safety margin is automatically built in
Rstab

So, no additional safety margin on setting is required

bmoor@powersystemprotection.com.au

Slide 17

High Impedance Differential Protection


CT Selection
z
z

All CTs to be the same ratio


All CTs to have Vk 2.Vsetting

This is an absolute MUST


Preferably Vk 5.Vsetting

Need to know

Slide 16

Fault current comprises

bmoor@powersystemprotection.com.au

Knee Point voltage


CT Resistance

Not critical
But easiest to specify
class PX CTs

bmoor@powersystemprotection.com.au

Barrie Moor : 2012

bmoor@powersystemprotection.com.au

Slide 18

High Impedance Differential Protection


Metrosils

Magnetising
Magnetising
current
currentat
atknee
knee
point
pointvoltage
voltage

z
z
z

CT
CTknee
knee
point
pointvoltage
voltage
CT
CTinternal
internal
resistance
resistance

In the case of a heavy internal fault, secondary system voltages may


become excessive
Implications include damage to equipment and safety of personnel
Empirical Formula

VPEAK = 2 2 VK (VF VK )
z
z

Class Requirements

VK 2 VSET

VK = CT RMS knee point voltage


VF = Maximum RMS voltage that would occur if the CT did not
saturate
Install metrosils if this voltage become excessive
(eg. >2.8kV peak)

0.1 PX 200 R5
Slide 19

bmoor@powersystemprotection.com.au

Slide 20

bmoor@powersystemprotection.com.au
(07) 3298 5260

Generator and
Power Station Protection

Generator Protection

Core Balance Differential Protection


(for smaller generators)

BIAS DIFF
'X'
BIAS DIFF
'Y'

Diff

G
HIGH IMP
DIFF 'Y'
BIAS DIFF
'X'

bmoor@powersystemprotection.com.au

Slide 21

bmoor@powersystemprotection.com.au

Slide 22

Voltage Displacement Protection


OVERALL
BIAS DIFF

z
TRANSFORMER
BIAS DIFF

z
z
z

High resistance earthing


And with the GCB open un-earthed system
Voltage displacement protection measures 3.Vo
Problems

Ferro-resonance
Unbalanced Capacitance

GENERATOR
HIGH IMP
DIFF

bmoor@powersystemprotection.com.au

Slide 23

bmoor@powersystemprotection.com.au

Slide 24

Voltage Displacement Protection


z

GCB
(OPEN)

GENERATOR
TRANSFORMER

Measures 3.Vn for a solid E/F

Healthy phases rise to full phase-phase potential


Healthy phases are now 60 deg apart
Thus, for standard 63.5V VT, output voltage is 190.5V
Set relay to 10% say 20V

VT with open delta


secondary winding

190.5
63.5
110
63.5
110 VVVV
190.5

Voltage
Displacement
Relay

bmoor@powersystemprotection.com.au

Barrie Moor : 2012

Neutral
Displacement
Protection

Slide 25

bmoor@powersystemprotection.com.au

Slide 26

bmoor@powersystemprotection.com.au
(07) 3298 5260

Generator and
Power Station Protection

Generator Protection

Stator Earth Fault Protection


z

High resistance earthing limits E/F to low levels

Not less than capacitance current


Insulation breakdown
Core damage

Rapid Tripping

Stator Earth Fault Protection

To minimise EF damage
To minimise probability of subsequent EF causing a
phase-phase fault
But not to result in nuisance tripping

95% Protection Neutral Voltage Displacement


100% Protection - Signal Injection

bmoor@powersystemprotection.com.au

Slide 27

Stator Earth Fault Protection

bmoor@powersystemprotection.com.au

Slide 29

95% Stator Earth Fault Protection

95% Stator
EF Protection

bmoor@powersystemprotection.com.au

Slide 30

bmoor@powersystemprotection.com.au

Slide 31

Transient Overvoltage Conditions


and Stator Earthfault Protection

100% Stator Earth Fault Protection

A
B
C

NEUTRAL
GROUNDING

STRAY
CAPACITANCES

I CAPA

EARTH
FAULT

I CAPB

95% Stator
EF Protection

I CAPTOTAL

I CAPA I CAPB

IN
100% Stator EF Protection
via Injection Method

bmoor@powersystemprotection.com.au

Barrie Moor : 2012

Require : I N

Slide 32

bmoor@powersystemprotection.com.au

I CAPTOTAL

Slide 33

bmoor@powersystemprotection.com.au
(07) 3298 5260

Generator and
Power Station Protection

Generator Protection

Transient Overvoltage Conditions


and Stator Earthfault Protection
z
z
z

z
z

Transmission System
Faults & Stator Earthfault Protection

350 MVA Generator


20 kV phase-phase
0.4 F per phase

I1 & I2 only

Determine a suitable direct connected neutral earthing


resistor
The neutral earthing resistor is to connected via a
20kV/220V transformer determine the neutral earthing
resistor

bmoor@powersystemprotection.com.au

No generator neutral
current for HV system
earth fault.

Slide 34

bmoor@powersystemprotection.com.au

Transmission System
Faults & Stator Earthfault Protection

Transmission System
Faults & Stator Earthfault Protection

Transformer
HV to LV
Winding Capacitance

z
z
z

z
z

UGN = Generator rated voltage


C12 = HV-LV coupling capacitance
UHV = System HV voltage
6 = only 1/6 th of voltage is effective
6 = 3 phases x 2 safety factor
0.05 = 5% setting voltage

Re max
Small generator neutral
current for HV system
earth fault, due to Transformer
HV-LV capacitive coupling.

bmoor@powersystemprotection.com.au

Slide 36

Slide 37

Restricted Earth Fault Protection

0.05 U GN
U
6 C12 HV
6

Transformer
HV to LV
Winding Capacitance

Small generator neutral


current for HV system
earth fault, due to Transformer
HV-LV capacitive coupling.

bmoor@powersystemprotection.com.au

Slide 38

3rd Harmonic Earth Fault Protection


3rd harmonic voltage
exists under normal
conditions

3rd harmonic voltage


is essentially shorted
out and falls to a low value
under fault conditions

REF

bmoor@powersystemprotection.com.au

Barrie Moor : 2012

Slide 39

bmoor@powersystemprotection.com.au

Slide 40

bmoor@powersystemprotection.com.au
(07) 3298 5260

Generator and
Power Station Protection

Generator Protection

Parallel Connected Generators


& Stator Earthfault Protection

Generator Earthing via Earthing Transformer

Core Balance
Current Direction
Detection

Core Balance
Current Direction
Detection

A-E

A
Core Balance
Current Direction
Detection

z
z
z
z

bmoor@powersystemprotection.com.au

Slide 41

bmoor@powersystemprotection.com.au

Generator Earthing via Earthing Transformer

Slide 42

Transverse Differential Protection


A

N1 / N2

Earthing Resistance

RA

Earthing Transformer rated to perhaps several hundred kVA


Open Delta secondary voltage is not VSEC
A-E & B-E voltages now become full ph-ph potential
And are at 60 deg, not 120deg
Open delta output is 3 x VSEC

B-E

C
Earthed

95% Stator
EF Protection

B
RB

100% Stator
EF Injection
Signal

BIAS ELEMENTS

bmoor@powersystemprotection.com.au

Slide 43

Interturn Protection

bmoor@powersystemprotection.com.au

Rotor Earth Fault Protection


z
z
z

Unearthed system
Single Fault not a major problem - Delayed tripping
Double Fault is a major problem - Instantaneous tripping

VT Star point NOT


earthed, but connected to
generator star point,
above the earthing resistor

bmoor@powersystemprotection.com.au

Barrie Moor : 2012

Arcing and burning damage due to current flow


Mechanical damage due to unbalanced mechanical forces
This may be disastrous !!!!!

Monitor DC insulation level - Usually 2 stages

Interturn
Protection

Slide 44

Alarm when DC insulation falls a little


Trip when DC insulation becomes unacceptably low

Hence, we
measure phase
unbalance, not
3.Vo

Slide 45

bmoor@powersystemprotection.com.au

Slide 46

bmoor@powersystemprotection.com.au
(07) 3298 5260

Generator and
Power Station Protection

Generator Protection

Rotor Earth Fault Protection


Potentiometer Method

Rotor Earth Fault Protection


Injection Method
Detects all Field
Winding earth faults
even when generator is
off-line

Detects all Field


Winding earth faults
except mid-point faults

Field
Winding

Field
Winding

Exciter

Exciter

bmoor@powersystemprotection.com.au

Slide 47

bmoor@powersystemprotection.com.au

To initiate backup tripping


of remote CBs

z
z

Breaker Fail
Current Check

High fault current events


Low fault current events

Current Check
CB Contacts

&

&

0.15
sec

0.20
sec

Trip

Trip

Generator CB status
based on
Auxiliary Contact Operation

Generator and
Transmission Events
Barrie Moor, B Eng (Elec)

Slide 49

Generator Protection

z
z

bmoor@powersystemprotection.com.au

Thermal Overload Capacity

t=

Tripping of Generator
Islanding of Generator

Start Stage

Tripping Stage

bmoor@powersystemprotection.com.au

Barrie Moor : 2012

Slide 50

Stator Overload Protection

Generator Event
External Event
And, for both of these, consider the effects of ...

GENERATOR
PROTECTION

Generator CB
TRIP Signal

bmoor@powersystemprotection.com.au

Slide 48

GENERATOR and
POWER STATION
PROTECTION

Generator CB Fail Protection


z

Auxiliary
Supply

Push Button to detect


Field Winding mid-point
faults

Slide 51

Const
I2 1

Alarm
Delayed to allow time for operator action
But within the machine capability

Thermal memory

bmoor@powersystemprotection.com.au

Slide 52

bmoor@powersystemprotection.com.au
(07) 3298 5260

Generator and
Power Station Protection

Generator Protection

Stator Overload Capability

Stator Overload Capability

1 10

Seconds

Seconds

1 10

1000

100

Curve Allowing
for
Stator Cooling

1000

t=

100

Manufacturers
Adiabatic
10 Curve

t =

Manufacturers
Adiabatic
10 Curve

Const
I2 1

t =

2
I
Const
1

ln 1 rated2
2
I rated 1 I 1

Const
I2 1

1.2

1.4

1.6

1.8

1.2

Generator Current (pu)

1.4

1.6

1.8

Generator Current (pu)

bmoor@powersystemprotection.com.au

Slide 53

bmoor@powersystemprotection.com.au

Slide 54

VOLTAGE CONTROLLED OVERCURRENT

NPS Protection

TIME

Reverse rotating stator flux cuts the rotor at double


frequency
Rotor is not laminated

Long time tripping

Overload characteristic
(Voltage Normal)

Results in significant rotor eddy current heating effects


To allow time for operator intervention

I2 t = const

Fault Characteristic
(Voltage Depressed)

CURRENT

bmoor@powersystemprotection.com.au

Slide 55

bmoor@powersystemprotection.com.au

Slide 56

NEGATIVE PHASE SEQUENCE PROTECTION


Continuous NPS Rating

I 2R

8.%

Generator NPS Constant

Const

10

Manufacturers Formula

2.

Const

NPS Capability
t

Const
I 2

1 10

For NPS heating over a longer time, allow for heat


dissipated

t=

SECONDS
1000

I
K
ln 1 2R
2
I2 R
I2

100

10

0.1
0.01

0.1

10

NPS CURRENT

Standard Manufactuers NPS Formula

Barrie Moor : 2012

bmoor@powersystemprotection.com.au

Slide 58

bmoor@powersystemprotection.com.au
(07) 3298 5260

Generator and
Power Station Protection

Generator Protection

NEGATIVE PHASE SEQUENCE PROTECTION


Continuous NPS Rating

I 2R

8.%

Generator NPS Constant

Const

10

Manufacturers Formula

2.

Over Voltage Protection


t

Const

Const
I 2

GEC Formula including


allowance for heat dissipation

Const .
ln 1
2
I 2R

I 2R
I 2

Causes

1 10

AVR malfunction
Transmission system major load rejection

SECONDS

Time delay

1000

100

To allow time for transmission system causes to be


rectified (eg. By tripping of capacitor banks)

Effects

10

Over Voltage damage to insulation


Over Excitation heating effects

0.1

10

0.1

0.01

NPS CURRENT
Standard Manufactuers NPS Formula
GEC NPS Formula including heat dissipation effects

bmoor@powersystemprotection.com.au

Over Excitation Protection

Over Excitation Protection


z

V = 4.44 f N max

V
1
=
f 4.44 N

z
z
z

Slide 61

May only be active when GCB is open


May be set to trip excitation only when the GCB is open

Several Stages
Coordination with O/V Protection
Reset Ratio

bmoor@powersystemprotection.com.au

Voltage
Frequency

GCB Interlocking

V
f

max

Flux depends on

max

Slide 60

To ensure Over Excitation protection resets OK after


clearance of transmission system events.

bmoor@powersystemprotection.com.au

Slide 62

Reverse Power Protection

GeneratorOver
Allowable VoltsCapability
/ Hertz
Generator
Generator OverExcitation
Excitation Capability
1000

Generator Over Excitation


Capability

SECONDS
Trip GCB
100

Trip Switchyard CBs


Over Excitation
Stage 2

z
Over Excitation
Stage 1

(GCB Closed)

10

z
Over Excitation
Stage 1
(GCB Open during run-up)

Over Voltage
Protection

1
1

1.025

1.05

1.075

1.1

Allowable Volts / Hertz

1.125

1.15

1.175

1.2

1.225

1.25

1.275

Causes
Loss of prime mover
Out of step events
Inadvertent GCB closure
GCB closure without excitation
Consequences
Fire hazard
Shaft damage
Turbine blade damage (eg. due to loss of steam cooling)
Tripping
High speed during genuine reverse power faults
Low speed during normal machine shut down
(eg to ensure steam valves are really closed)

1.3

Volts / Hertz (pu)

bmoor@powersystemprotection.com.au

Barrie Moor : 2012

Slide 64

bmoor@powersystemprotection.com.au
(07) 3298 5260

Generator and
Power Station Protection

Generator Protection

Under Excitation Protection


z

Generator Capability Diagram

Total loss of excitation

Under excitation due to generator (eg AVR) faults

Under excitation due to system events

Prime Mover (MW)


Limit

Operation as an induction generator


Rotor slip frequency current thermal damage
High speed tripping

MW

Stator Current (MVA)


Limit

Stability
Limit

Field
Current
Limit

Delayed tripping
Multi stage tripping

MVAr

bmoor@powersystemprotection.com.au

Slide 66

Generator Capability Diagram

bmoor@powersystemprotection.com.au

Slide 67

Under Excitation Protection

MW

Results in a circle of
infinite diameter on the
MW / MVAr diagram
ie. a straight line

R
Also results in a circle
on the MW/MVAr
capability diagram
Loss
Lossof
of
Excitation
Excitation
Protection
Protection

Under
Under
Excitation
Excitation
Protection
Protection

Based on generator
impedance parameters,
but recommend to check
the capability diagram too.

MVAr

bmoor@powersystemprotection.com.au

Slide 68

bmoor@powersystemprotection.com.au

Slide 69

Under Frequency Protection

Generator
Under
Frequence Capability
Capability
Generator
Under
Frequency
100

Over Excitation Problems

z
z

LP Turbine blade stress problems


Cumulative effects

Multi-staged tripping

Continuous : 47.5 - 51 Hz

Minutes
SECONDS

Best covered by genuine Over Excitation protection

10

Allow for (say) 15 events in the machines lifetime


First stages to island the machine
Final stage to trip the machine

0.1
45 45.5 46

46.5 47

Turbine Life

bmoor@powersystemprotection.com.au

Barrie Moor : 2012

47.5 48

48.5 49

49.5 50 50.5 51 51.5 52 52.5 53 53.5 54

Frequency

Slide 70

bmoor@powersystemprotection.com.au
(07) 3298 5260

Generator and
Power Station Protection

Generator Protection

Generator
Under
Frequence Capability
Capability
Generator
Under
Frequency

Generator
Under
Frequence Capability
Capability
Generator
Under
Frequency

100

100

Continuous : 47.5 - 51 Hz

Continuous : 47.5 - 51 Hz

Minutes
SECONDS

Minutes
SECONDS

10

10

1
Complete Shutdown

1
Complete Shutdown

Island

Island

0.1

0.1
45 45.5 46

46.5 47

47.5 48

48.5 49

49.5 50 50.5 51 51.5 52 52.5 53 53.5 54

Turbine Life

45 45.5 46

Frequency

Under Frequency Protection


z

z
z

z
z

Barrie Moor : 2012

49.5 50 50.5 51 51.5 52 52.5 53 53.5 54

Frequency

Slide 75

Typically the generator is unloaded in over frequency (over


speed) scenarios

Mechanical devices also provide over speed protection

bmoor@powersystemprotection.com.au

Slide 76

Out of Step Protection


(Pole Slipping)
X

Causes
Transmission system power swings due to slow clearance of
faults
Increased transmission system reactance due to tripping of
feeders
Effects
Voltage and frequency fluctuations
Indiscriminate operation of generator and transmission system
protection relays
Other generators also fall out of step
Mechanical damage
Detection by monitoring transmission system impedance

bmoor@powersystemprotection.com.au

48.5 49

Many relays provide over frequency protection


Not a problem for the turbine blades

Out of Step Protection


(Pole Slipping)
z

47.5 48

Over Frequency Protection

Cumulative effect
Assume say 15 events over the machines lifetime
Protection set to trip when 1/15th of life is used
Set each stage tripping time based on the withstand of the next
stage
If stages 1-3 island and stage 4 trips the generator
May be prudent to set stage 4 to a slower time than stage 3
Provides for rapid fall in frequency and prevents unnecessary
tripping
Stage 3 has already de-loaded the generator, so slower stage 4
time is OK

bmoor@powersystemprotection.com.au

46.5 47

Turbine Life

Unstable swing, but not


specifically involving this
particular generator.
May trip on 2nd or subsequent
swings.

Zsystem
Stage 2

Unstable swing, specifically


involving this particular
generator. Trip on 1st swing.
May trip on 2nd or subsequent
swings if coordination with
transmission system power
swing tripping is required.

0.9 x Xtf
Stage 1

-Xd'

Slide 77

bmoor@powersystemprotection.com.au

Slide 78

bmoor@powersystemprotection.com.au
(07) 3298 5260

Generator and
Power Station Protection

Generator Protection

Out of Step Protection


(Pole Slipping)
z
z

Characteristic A
-Xd'

ra

0.9 x XTr

Requires a swing counting system

120
R

Stage 2 swing involves other generators


May raise alarm only
May trip on 2nd or subsequent swings
z

rb

Requires a swing counting system


Characteristic B

Slide 79

Out of Step Protection


(Pole Slipping)

bmoor@powersystemprotection.com.au

Slide 80

Out of Step Protection


(Pump Storage Synchronous Motor)

Stable swing, but not specifically


involving this particular generator.
Tripping not required.

Characteristic A

Characteristic A

ra

ra

0.9 x XTr
120
R

Stable swing, specifically involving


this particular generator.
Tripping not required.

0.9 x XTr
120
R

X'd

X'd
rb

rb

Characteristic B

bmoor@powersystemprotection.com.au

Characteristic B

Slide 81

Embedded Generation and


Protection Schemes at PCC

Over Voltage
Under Voltage
Over Frequency
Under Frequency
Loss of Utility Supply

Neutral Voltage Displacement


Reverse Power
Directional Over Current

bmoor@powersystemprotection.com.au

Barrie Moor : 2012

Slide 82

The embedded generation must not be permitted to


supply Utility customers in isolation

And also perhaps

bmoor@powersystemprotection.com.au

Embedded Generation and


Islanding Detection

Typical protection schemes at the Point of Common


Coupling (PCC) include

Unstable swing, specifically


involving this particular
generator. Trip on 1st swing.
May trip on 2nd or subsequent
swings if coordination with
transmission system power
swing tripping is required.

X'd

Should be employed in conjunction and coordination with


transmission system Power Swing Tripping schemes

bmoor@powersystemprotection.com.au

Unstable swing, but not


specifically involving this
particular generator.
May trip on 2nd or subsequent
swings.

Stage 1 swing requires tripping of generator


May trip on first or 2nd swing
z

0.9 x Xtf

Swing entering and leaving from the RHS


will stabilise
Swing entering the RHS but exiting via the LHS
will not stabilise

Out of Step Protection


(Pole Slipping)

Zsystem
Stage 2

Stage 1

Slide 83

The Utility supply is normally the means of regulating the


system voltage and frequency within the permitted limits.
The Utility connection may be the only means of ensuring
an effectively earthed system.
Utility reclose onto unsynchronised embedded generators
is likely
Safety for utility workers : Who may not expect the system
to remain energised by the embedded generation supply

bmoor@powersystemprotection.com.au

Slide 84

bmoor@powersystemprotection.com.au
(07) 3298 5260

Generator and
Power Station Protection

Generator Protection

Embedded Generation and


Islanding Detection
z

Embedded Generation and


Islanding Detection

On lost of Utility connection

Embedded generation may be overloaded, leading to


generator undervoltage/underfrequency.
Embedded generation may be underloaded, leading to
overvoltage/overfrequency.
Little change to the absolute levels of voltage or frequency
if there is little resulting change to the load flow.

Significant mismatch between embedded generator


capability and island system load

But when the embedded generator capability and island


system load reasonably match

bmoor@powersystemprotection.com.au

Slide 85

Voltage Vector Shift Relay

bmoor@powersystemprotection.com.au

Change in load on disconnection from the utility


Subsequent step change in generator phase angle

Easily determined by measuring zero crossing duration of


the voltage waveform

bmoor@powersystemprotection.com.au

Slide 87

Embedded Generation and


Islanding Detection
z

Barrie Moor : 2012

bmoor@powersystemprotection.com.au

Probably the most often used scheme


Rate of change of frequency (df/dt), in response to
inevitable small load changes
df/dt is greater with the generation isolated than when
the generation is in parallel with the public,
interconnected power system.
Simply determined by measurement of time between zero
crossings system of voltage.
Problem : Possible nuisance tripping in response to normal
power system events, where the system is subject to
significant frequency excursions.

bmoor@powersystemprotection.com.au

Direct intertripping simply based on SCADA system status


of Utility system CBs and Reclosers
Power Line signalling scheme
Signal is continually broadcast from the utility system
using the power lines as the signalling path
Lost of signal at the generator indicates an island
condition

Slide 88

Embedded Generation and


Islanding Detection

ROCOF (Rate of Change of Frequency) Relay

Slide 86

Transfer Tripping Schemes

V1 V2
P=
Sin()
X

Transfer Tripping schemes


ROCOF (Rate of Change of Frequency) relay
Change in Harmonic Distortion
Active Detection Techniques

Embedded Generation and


Islanding Detection

Embedded Generation and


Islanding Detection
z

May be detected by voltage and frequency protection


schemes
Vector Shift Protection

Change in Harmonic Distortion

Slide 89

Harmonic distortion when connected to the utility will be


small and stable
Especially with invertor based generators, total harmonic
distortion (THD) will increase when disconnected from the
utility supply
Easily detected by changes in 3rd harmonic.

bmoor@powersystemprotection.com.au

Slide 90

bmoor@powersystemprotection.com.au
(07) 3298 5260

Generator and
Power Station Protection

Generator Protection

Embedded Generation and


Islanding Detection
z

REF 'Y'

And putting it all together


VOLTAGE
DISPLACEMENT 'X'

PILOT WIRE 'Y'


PILOT WIRE 'X'

VOLTAGE
DISPLACEMENT 'Y'

SYNCH

GENERATOR
TRANSFORMER

Active Detection Techniques

To detect islanding even under perfect load match


Small variations are purposely applied to the AVR system
When connected to the utility supply, these variations
have negligible effect on the output from the embedded
generator
But when disconnected from the utility system,
significant turbulence results
Reactive Export Error Detector (REED) relay detects
excessive changes in reactive power flow
corresponding to the AVR changes
Detection time will be greater than for the passive
schemes

DIFF 'Y'

CB FAIL 'X'

DIFF 'X'

CB FAIL 'Y'

INST OC 'Y'

STATOR
OVERLOAD 'Y'

NEGATIVE
SEQUENCE 'Y'
OUT OF
STEP 'Y'

REVERSE
POWER 'Y'

LOSS/UNDER
EXCITATION 'Y'

DIFF 'X'

BUCH
AVR
HIGH IMP
DIFF 'Y'

BIASED
DIFF 'X'

UNIT
TRANSFORMER

NEF

AVR
IDMT OC
SYNCH
OC 'X'

DIFF 'Y'

EXCITATION
TRANSFORMER

UNDER
FREQUENCY 'X'

UNDER
FREQUENCY 'Y'

OVER
VOLTAGE 'X'

OVER
VOLTAGE 'Y'

OVER
EXCITATION 'X'

OVER
EXCITATION 'Y'

OUT OF
STEP 'X'
NEGATIVE
SEQUENCE 'X'

REF 'Y'

LOSS/UNDER
EXCITATION 'X'
STATOR
OVERLOAD 'X'

REVERSE
POWER 'X'

BUS ZONE

SHUNT

ROTOR
EF 'X'

ROTOR
EF 'Y'

STATOR EF 'X'
STATOR EF
INJECTION 'Y'

bmoor@powersystemprotection.com.au

Barrie Moor : 2012

Slide 91

bmoor@powersystemprotection.com.au
(07) 3298 5260

You might also like