You are on page 1of 19

Preventive Maintenance Inspection

at
Cromptons Paper - Heywood
06/08/2003
General Information
Ambient Conditions
Wednesday, 6 Aug
18:00 Mostly Sunny

Temp C Dew Point Precip. Humid. Wind


28
17
Nil
50%
From the West at 7 mph

Contact information:
Diagnostic Solutions Ltd
Murlain Business Centre
Union Street
Chester CH1 1QP
T: 01244 357263 (Mon-Fri, 8.30-5.00) or 07768 582321/517206 (Outside office hours)
F: 01244 357264
E: office@diagnosticsolutions.co.uk

Ron Frend
IR Survey 6Aug03.REP

Page 1

06/08/2003

Table of Contents
Section

Equipment

PM2

Oven contactor panel

PM2

Oven contactor panel

PM2

Main panel 214

PM2

Main panel 216

PM2

Main panel 223

PM2

Main panel 229

PM2

Main panel 235

PM2

Main panel 241

10

PM2

Main panel 244

11

Boiler room

Main cabinet

12

Boiler room

Main cabinet

13

Refiners

Manilla refiner #2

14

Refiners

HiLo Pulper HiSpeed Rotor

15

Refiners

HiLo Pulper LoSpeed Rotor

16

IR Survey 6Aug03.REP

Page

Page 2

06/08/2003

Inspected Equipment:

Operator:

Oven contactor panel

Ron Frend

Identification
Section

PM2

Equipment

Oven contactor panel

Additional information

Fuses R2 & Y5

Date

06/08/2003

Time

09:12:53

Fault description
AR02: 108.8C

131.4C
120
100

AR01: 135.6C
80
60
51.2C

Fault

Poor termination

Object parameter Value


Emissivity

0.93

Object distance

1.0 m

Label

Value

AR01 : max

135.6C

AR02 : max

108.8C

Recommendation
Repair terminations
Clean and tighten the cable teminations on Red 2 and Yellow 5.

IR Survey 6Aug03.REP

Page 3

06/08/2003

Inspected Equipment:

Operator:

Oven contactor panel

Ron Frend

Identification
Section

PM2

Equipment

Oven contactor panel

Additional information

Contactor #3

Date

06/08/2003

Time

09:15:43

Fault description
112.1C
100
AR01: 119.0C
80
60

Fault

Bottom right termination

Object parameter Value


Emissivity

0.93

Object distance

1.0 m

Label

Value

AR01 : max

119.0C

40
39.3C

Recommendation
Repair termination
The overheated termination is caused by a poor electrical connection. The termination should be
cleaned and tightened.

IR Survey 6Aug03.REP

Page 4

06/08/2003

Inspected Equipment:

Operator:

Ron Frend

Main panel 214


Identification
Section

PM2

Equipment

Main panel 214

Additional information

Rear fuses

Date

06/08/2003

Time

10:26:07

Fault description
91.1C

Mid fuse top: 90.9C

80

Right fuse bottom: 93.0C


60

Fault

Poor terminations

Object parameter Value


Emissivity

0.93

Object distance

1.0 m

Label

Value

Mid fuse top : max 90.9C


47.3C

Right fuse bottom : m93.0C

Recommendation
Repair terminations
The middle top and right bottom cable terminations are overheating due to poor electrical
connection.
The terminations should be cleaned and retightened.

IR Survey 6Aug03.REP

Page 5

06/08/2003

Inspected Equipment:

Operator:

Ron Frend

Main panel 216


Identification
Section

PM2

Equipment

Main panel 216

Additional information

Contactor

Date

06/08/2003

Time

10:29:47

Fault description
93.5C

80
Bottom, mid, rear: 90.8C
60

Fault

Poor connection L2

Object parameter

Value

Emissivity

0.93

Object distance

1.0 m

Label

Value

Bottom, mid, rear : max 90.8C


46.8C

Recommendation
Repair termination
The bottom, middle, rear termination has a poor electrical connection.
Clean and tighten the termination.

IR Survey 6Aug03.REP

Page 6

06/08/2003

Inspected Equipment:

Operator:

Ron Frend

Main panel 223


Identification
Section

PM2

Equipment

Main panel 223

Additional information

Middle fuse

Date

06/08/2003

Time

10:34:51

Fault description
95.0C
AR01: 100.5C

Fault

Poor connection

Object parameter Value


80

60

Emissivity

0.93

Object distance

1.0 m

Label

Value

AR01 : max

100.5C

43.6C

Recommendation
Repair connection
The middle fuse top connection has a poor electrical connection.
Clean and tighten the fuse top connections.

IR Survey 6Aug03.REP

Page 7

06/08/2003

Inspected Equipment:

Operator:

Ron Frend

Main panel 229


Identification
Section

PM2

Equipment

Main panel 229

Additional information

Middle fuse

Date

06/08/2003

Time

10:38:11

Fault description
67.4C

60

Mid fuse bottom: 69.3C

50

Fault

Poor termination

Object parameter

Value

Emissivity

0.93

Object distance

1.0 m

Label

Value

Mid fuse bottom : max

69.3C

42.5C

Recommendation
Repair termination
The middle fuse has a bad electrical connection at the bottom of the fuse.
Clean and tighten the connnection.

IR Survey 6Aug03.REP

Page 8

06/08/2003

Inspected Equipment:

Operator:

Ron Frend

Main panel 235


Identification
Section

PM2

Equipment

Main panel 235

Additional information

Middle fuse

Date

06/08/2003

Time

10:46:29

Fault description
64.2C
60
Mid fuse top: 64.1C
50

Fault

Poor termination

Object parameter Value


Emissivity

0.93

Object distance

1.0 m

Label

Value

Mid fuse top : max 64.1C


40.6C

Recommendation
Repair termination
The middle fuse has a bad electrical connection at the top cable termination.
Clean and tighten the termination.

IR Survey 6Aug03.REP

Page 9

06/08/2003

Inspected Equipment:

Operator:

Ron Frend

Main panel 241


Identification
Section

PM2

Equipment

Main panel 241

Additional information

Righthand contactor

Date

06/08/2003

Time

10:50:34

Fault description
104.2C

Fault

Overheating coil

100

Object parameter Value

Coil: 104.8C
80

60

Emissivity

0.93

Object distance

1.0 m

Label

Value

Coil : max

104.8C

46.7C

Recommendation
Change coil
The coil is overheating and should be changed.

IR Survey 6Aug03.REP

Page 10

06/08/2003

Inspected Equipment:

Operator:

Ron Frend

Main panel 244


Identification
Section

PM2

Equipment

Main panel 244

Additional information

Main contactor

Date

06/08/2003

Time

10:56:37

Fault description
82.7C

Fault

Hot internal contacts

80

Object parameter Value

AR01: 83.4C
70
SP01
60
50
46.8C

Emissivity

0.93

Object distance

1.0 m

Label

Value

SP01

72.0C

AR01 : max

83.4C

Recommendation
Repair contactor
The coil internals are showing signs of overheating when compared to similar units.
Most probable cause is poor electrical contact at the internal contacts.
Overhaul the contactor.

IR Survey 6Aug03.REP

Page 11

06/08/2003

Inspected Equipment:

Operator:

Ron Frend

Main cabinet
Identification
Section

Boiler room

Equipment

Main cabinet

Additional information

#2 feed pump isolator

Date

06/08/2003

Time

13:08:24

Fault description
Top cables: 79.8C

81.1C
80

Fault

Hot cables

Object parameter Value


70
60
50

Bottom cables: 74.2C

43.3C

Emissivity

0.93

Object distance

1.0 m

Label

Value

Top cables : max

79.8C

Bottom cables : max 74.2C

Recommendation
Resize cables
The cables to the isolator are overheating without a point heat source. This indicates that
the cables are undersized for the application.
The cables should be replaced with a larger diameter cable.

IR Survey 6Aug03.REP

Page 12

06/08/2003

Inspected Equipment:

Operator:

Ron Frend

Main cabinet
Identification
Section

Boiler room

Equipment

Main cabinet

Additional information

Relay middle of block

Date

06/08/2003

Time

13:09:59

Fault description
89.8C
80
Middle relay: 90.5C
60

Fault

Relay overheating

Object parameter Value


Emissivity

0.93

Object distance

1.0 m

Label

Value

Middle relay : max 90.5C


40
38.2C

Recommendation
Change relay
The indicated relay is overheating and should be replaced.

IR Survey 6Aug03.REP

Page 13

06/08/2003

Inspected Equipment:

Operator:

Ron Frend

Manilla refiner #2
Identification
Section

Refiners

Equipment

Manilla refiner #2

Additional information

Overload

Date

06/08/2003

Time

13:33:27

Fault description
79.2C

Fault

Overheating

Object parameter Value


AR01: 79.8C

60

40

Emissivity

0.93

Object distance

1.0 m

Label

Value

AR01 : max

79.8C

34.4C

Recommendation
Clean and tighten
The overload top, middle connection is overheating due to a poor electrical connection.
Clean and tighten the termination.

IR Survey 6Aug03.REP

Page 14

06/08/2003

Operator:

Inspected Equipment:

HiLo Pulper HiSpeed Rotor

Ron Frend

Identification
Section

Refiners

Equipment

HiLo Pulper HiSpeed Rotor

Additional information Left hand Fuse


Date

06/08/2003

Time

13:39:23

Fault description
Left fuse top: 90.6C

90.5C
80

60

40

Fault

Overheating

Object parameter Value


Emissivity

0.93

Object distance

1.0 m

Label

Value

Left fuse top : max 90.6C

30.0C

Recommendation
Clean & tighten
The left hand fuse top connection is hot due to a poor electrical connection.
Clean and tighten the termination.

IR Survey 6Aug03.REP

Page 15

06/08/2003

Inspected Equipment:

Operator:

HiLo Pulper LoSpeed Rotor

Ron Frend

Identification
Section

Refiners

Equipment

HiLo Pulper LoSpeed Rotor

Additional information Left hand fuse


Date

06/08/2003

Time

13:41:32

Fault description
140.9C

100

LH fuse bottom: 141.7C

50

Fault

Overheating

Object parameter

Value

Emissivity

0.93

Object distance

1.0 m

Label

Value

LH fuse bottom : max

141.7C

29.6C

Recommendation
Clean & tighten
The connection at the left fuse bottom connection is very hot due to a poor electrical connection.
Clean and tighten the connection.

IR Survey 6Aug03.REP

Page 16

06/08/2003

Summary of Inspection
at
Cromptons Paper - Heywood
List of Inspected Items
Section

Equipment

Fault

Recommendation

PM2

Oven contactor panel

Poor termination

Repair terminations

PM2

Oven contactor panel

Bottom right terminatioRepair termination

PM2

Main panel 214

Poor terminations

Repair terminations

PM2

Main panel 216

Poor connection L2

Repair termination

PM2

Main panel 223

Poor connection

Repair connection

PM2

Main panel 229

Poor termination

Repair termination

PM2

Main panel 235

Poor termination

Repair termination

PM2

Main panel 241

Overheating coil

Change coil

PM2

Main panel 244

Hot internal contacts

Repair contactor

Boiler room

Main cabinet

Hot cables

Resize cables

Boiler room

Main cabinet

Relay overheating

Change relay

Refiners

Manilla refiner #2

Overheating

Clean and tighten

Refiners

HiLo Pulper HiSpeed Rotor Overheating

Clean & tighten

Refiners

HiLo Pulper LoSpeed Rotor Overheating

Clean & tighten

IR Survey 6Aug03.REP

Page 17

06/08/2003

Inspection
Order
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
20
21
22
23
24
25
26
27
28
29
30
31
32
33

Location

Description

PM2
PM1
PM1
PM1
PM1
PM1
PM1
PM1
PM1
PM1
PM2 Main Panel
PM2 Main Panel
PM2 Main Panel
PM2 Main Panel
PM2 Main Panel
PM2 Main Panel
PM2 Main Panel
PM2 Main Panel
PM2 Main Panel
PM2 Main Panel
PM2 Main Panel
PM2 Main Panel
PM2 Main Panel
PM2 Main Panel
PM2 Main Panel
PM2 Main Panel
PM2 Main Panel
PM2 Main Panel
PM2 Main Panel
PM2 Main Panel
PM2 Main Panel
PM2 Main Panel
PM2 Main Panel

Oven contactor panel


Reel drum drive
Float dryer entry roll
Calender bottom ( swimming) drive
Calender top drive
Cylinder 9 drive
Spooner control panel
Through dryer panel
High vac pump panel
Remote panel for through dryer
214
215
216
217
218
222
223
226
227
228
229
230
231
232
233
234
235
237
240
241
242
244
245

Fault
Fuses R2 & Y52:
Contactor #3

rear fuses
Contactor - L2

mid fuse top

mid fuse bottom

RH contactor - coil
Main contactor - internal

34
35
36
37
38
39
40
41
42
43
44
45
46
47
48
49
50
51
52

Agitators - Raw materials


Agitators - Raw materials
Agitators - Raw materials
Agitators - Raw materials
Agitators - Raw materials
Agitators - Raw materials
Beaters
Beaters MCC
Beaters MCC
Beaters MCC
Beaters MCC
Beaters MCC
Beaters MCC
Beaters MCC
Beaters MCC
Beaters MCC
Beaters MCC
Beaters MCC
Cutting floor

FR1 - 1st stage FLOC Refiner #1


FR2 - 1st stage FLOC Refiner #2
DEF - Deflaker
SBP - Supaseal broke pulper
BPP - Supaseal broke pulper pump
TR3 - Manilla refiner #1
#5 Beater
B2
B4
B5
C1
C3
D5
D6
E1
E2
E3
E4
Chemical panel (melamine) CP17-01

53
54
55
56
57
58
59
60
61

Boiler House
Agitators - Raw materials
Agitators - Raw materials
Agitators - Raw materials
Agitators - Raw materials
Agitators - Raw materials
Agitators - Raw materials
Agitators - Raw materials
Agitators - Raw materials

Main Panel
Poly Pulper HiSpeed Rotor
Poly Pulper LoSpeed Rotor
Manilla refiner #2
Hi-Lo Pulper HiSpeed Rotor
Hi-Lo Pulper LoSpeed Rotor
TR2 - Top wood refiner #2
TR1 - Top wood refiner #1
TRF - Top wood refiner feed pump

#2 Feed pump
Relay overheating

Overload
Fuse
Fuse

You might also like