Series 1950 Explosion-Proof Differential Pressure Switches


Specifications - Installation and Operating Instructions
Set Point Adjustment
Screw

UL and CSA Listed, FM Approved For


CL. I GR. C, D - CL. II GR. E, F, G - CL. III
Series 1950 Switches
Operating ranges and deadbands

1/2 (12.7)
female NPT
Electrical
Conduit
Connection

Series 1950 Explosion-Proof Differential Pressure Switches combine the best features of the Series 1900 Pressure Switch with an integral explosion-proof and weather-proof housing. Each unit is UL &
CSA listed; FM approved for use in Class I, Groups C & D; Class II,
Groups E, F, & G; and Class III atmospheres (NEMA 7 & 9). They are
totally rain-tight for outdoor installations. Twelve models allow setpoints from .03 to 20 inches w.c. and from .5 to 50 psi (3.4 to 345 kPa).
Easy access to the SPDT switch for electrical hook-up is provided by
removing the top plate of the three-part aluminum housing. Adjustment
to the set point of the switch can be made without disassembling the
housing. The unit is very compact, about half the weight and bulk of
equivalent conventional explosion-proof switches.
CAUTION
For use only with air or compatible gases. Use of the Model 1950
switch with explosive media connected to the Low pressure port
(including differential pressure applications in such media) is not recommended. Switch contact arcing can cause an explosion inside the
switch housing which, while contained, may render the switch inoperative. If switch is being used to sense a single positive pressure relative to atmosphere, run a line from the low pressure port to a non-hazardous area free of combustible gases. This may increase response
time on -0 and -00 models.
Note: The last number-letter combination in the model number identifies the switchs electrical rating (number) and diaphragm material (letter). The 2F combination is standard as described in the physical data
above. In case of special models, a number 1 rating is the same as 2;
a number 3 or 4 rating is 10A 125, 250, 480 VAC; 1/8 H.P. 125 VAC; 1/4
H.P. 250 VAC; a number 5 or 6 rating is 1A 125 VAC. Letter B indicates
a Buna-N diaphragm; N = Neoprene; S = Silicone; and V = Viton.

DWYER INSTRUMENTS, INC.


P.O. BOX 373 MICHIGAN CITY, INDIANA 46361, U.S.A.

To order
specify
Model Number
1950-02-2S
1950-00-2F
1950-0-2F
1950-1-2F
1950-5-2F
1950-10-2F
1950-20-2F

Operating
Range:
Inches, W.C.
0.03 to 0.10
0.07 to 0.15
0.15 to 0.5
0.4 to 1.6
1.4 to 5.5
3.0 to 11.0
4.0 to 20.0
Operating
Model Number Range: PSI
1950P-2-2F
0.5 to 2.0
1950P-8-2F
1.5 to 8.0
1950P-15-2F
3.0 to 15.0
1950P-25-2F
4.0 to 25.0
1950P-50-2F
15.0 to 50

Approximate
Dead Band
At Min. Set Point At Max. Set Point
0.025
0.05
0.04
0.05
0.10
0.15
0.15
0.20
0.3
0.4
0.4
0.5
0.4
0.6
Approximate Dead Band
Min. Set Point
Max. Set Point
0.3 psi
0.3 psi
1.0 psi
1.0 psi
0.9 psi
0.9 psi
0.7 psi
0.7 psi
1.0 psi
1.5 psi

SPECIFICATIONS
Service: Air and non-combustible, compatible gases.
Wetted Materials: Consult factory.
Temperature Limits: -40 to 140F (-40 to 60C); 0 to 140F
(-17.8 to 60C) for 1950P-8, 15, 25, and 50. -30 to 130F (-34.4 to
54.4C) for 1950-02.
Pressure Limits:
Continuous: 1950s - 45 w.c. (0.11 bar);
1950Ps - 35 psi (2.41 bar); 1950P-50 only - 70 psi (4.83 bar).
Surge: 1950s - 10 psi (0.69 bar), 1950Ps - 50 psi (3.45 bar), 1950P-50
only - 90 psi (6.21 bar).
Enclosure Rating: IP54, NEMA 3, 7 and 9.
Switch Type: Single-pole double-throw (SPDT).
Electrical Rating: 15 A @, 125, 250, 480 VAC, 60 Hz. Resistive 1/8
HP @ 125 VAC, 1/4 HP @ 250 VAC, 60 Hz.
Electrical Connections: 3 screw type, common, normally open and
normally closed.
Process Connections: 1/8 female NPT.
Mounting Orientation: Diaphragm in vertical position. Consult factory
for other position orientations.
Set Point Adjustment: Screw type on top of housing.
Weight: 3.25 Ib (1.5 kg); 1950-02 model, 4.4 lb (2 kg).
Agency Approvals: CE, UL, CSA, FM.

RESPONSE TIME: Because of restrictive effect of flame arrestors,


switch response time may be as much as 10-25 seconds where applied
pressures are near set point.

Phone: 219/879-8000
Fax: 219/872-9057

www.dwyer-inst.com
e-mail: info@dwyer-inst.com

17/64 [6.75] DIA MTG


HOLES (2)
RANGE ADJUSTMENT
SCREW

3-1/2
[88.9]
1950-02: 7-3/4 (196.9) dia. x 4-11/32
(110.3) depth. For complete dimensions
request drawing 28-700175-00 from our
Customer Service Department

4-7/8
[123.8]
1/2 NPT(F)
ELEC.
CONDUIT
CONNECTION

1/8 NPT(F)
HIGH PRESSURE
PORT

5-7/16
[138.1]

1-11/16
[42.9]

1/8 NPT(F)
PRESSURE
PORT

VENT DRAIN
PLUG

3/8
[9.53]
1-7/16
[36.5]

1950 Switch Outline Dimensions

INSTALLATION
1. Select a location free from excess vibration and corrosive atmospheres where temperatures will be within the limits noted under
Specifications on reverse. Switch may be installed outdoors or in areas
where the hazard of explosion exists. See reverse for specific types of
hazardous service.
2. Mount standard switches with the diaphragm in a vertical plane and
with switch lettering and nameplate in an upright position. Some switches are position sensitive and may not reset properly unless they are
mounted with the diaphragm vertical.
3. Connect switch to source of pressure, vacuum or differential pressure.
Metal tubing with 1/4 O.D. is recommended, but any tubing which will
not restrict the air flow can be used. Connect to the two 1/8 female NPT
pressure ports as noted below:
A. Differential pressures - connect pipes or tubes from source
of greater pressure to high pressure port marked HIGH
PRESS, and from source of lower pressure to low pressure
port marked LOW PRESS.
B. Pressure only (above atmospheric pressure) - connect
tube from source of pressure to high pressure port. The low
pressure port is left open to atmosphere.
C. Vacuum only (below atmospheric pressure) - connect tube
from source of vacuum to low pressure port. The high
pressure port is left open to atmosphere.
4. To make electrical connections, remove the three hex head screws
from the cover and after loosening the fourth captive screw, swing the
cover aside. Electrical connections to the standard single pole, double
throw snap switch are provided by means of terminals marked COM
(common), NO (norm open), NC (norm closed). The normally open
contacts close and the normally closed contacts open when pressure
increases beyond the set point. Switch loads for standard models should
not exceed the maximum specified current rating of 15 amps resistive.
Switch capabilities decrease with an increase in ambient temperature,
load inductance, or cycling rate. Whenever an application involves one
or more of these factors, the user may find it desirable to limit the
switched current to 10 amps or less in the interest of prolonging switch
life.

Copyright 2012Dwyer Instruments, Inc.

ADJUSTMENT: To Change the Set point


1. Remove the plastic cap and turn the slotted Adjust-ment Screw at the
top of the housing clockwise to raise the set point pressure and counterclockwise to lower the set point. After calibration, replace the plastic cap
and re-check the set point.
2. The recommended procedure for calibrating or checking calibration is
to use a T assembly with three rubber tubing leads, all as short as possible and the entire assembly offering minimum flow restriction. Run one
lead to the pressure switch, another to a manometer of known accuracy
and appropriate range, and apply pressure through the third tube. Make
final approach to the set point very slowly. Note that manometer and
pressure switch will have different response times due to different internal volumes, lengths of tubing, fluid drainage, etc. Be certain the switch
is checked in the position it will assume in use, i.e. with diaphragm in a
vertical plane and switch lettering and Dwyer nameplate in an upright
position.
3. For highly critical applications check the set point adjustment and if
necessary, reset it as noted in step A.
MAINTENANCE
The moving parts of these switches need no maintenance or lubrication.
The only adjustment is that of the set point. Care should be taken to keep
the switch reasonably clean. Periodically the vent drain plug should be
rotated, then returned to its original position. This will dislodge deposits
which could accumulate in applications where there is excessive condensation within the switch. The Series 1950 Explosion-Proof Differential
Pressure Switch is not field serviceable and should be returned if repair
is needed (field repair should not be attempted and may void warranty).
Be sure to include a brief description of the problem plus any relevant
application notes. Contact customer service to receive a return goods
authorization number before shipping.

Printed in U.S.A. 1/12