OBJETIVO
Presentar las diferencias ms sobresalientes en el Diseo,
Construccin y Aplicacin de Productos de Media Tensin
de las Normas IEC y las Normas IEEE /ANSI.

2014 General Electric


Company. All Rights Reserved

IEC International
Electrotechnical Commission
La misin de la IEC es promover entre sus miembros la
cooperacin internacional en todas las reas de la normalizacin
Electrotcnica. Para lograr lo anterior, han sido formulados los
siguientes objetivos:

Conocer las necesidades del mercado mundial eficientemente

Promover el uso de sus normas y esquemas de aseguramiento


de la conformidad a nivel mundial.

Asegurar e implementar la calidad de producto y servicios


mediante sus normas.

Establecer las condiciones de intemperabilidad de sistemas


complejos.

Incrementar la eficiencia de los procesos industriales.

Contribuir a la implementacin del concepto de salud y


seguridad humana..

Contribuir a la proteccin del ambiente.

Dar a conocer los nuevos campos electrnicos

IEC Central Office


3, rue de Varemb
P.O. Box 131
1211 Geneva 20
Switzerland

2014 General Electric


Company. All Rights Reserved

IEEE Instituto de Ingeniera


Elctrica y Electrnica
Es una asociacin mundial de tcnicos e
ingenieros dedicada a la y el desarrollo en
reas tcnicas.
Su trabajo es promover la creatividad, el
desarrollo y la integracin, compartir y aplicar
los avances en las tecnologas de la
informacin, electrnica y ciencias en general
para beneficio de la humanidad y de los
mismos profesionales.

3 Park Avenue, 17th Floor


Nueva York,
EEUU

2014 General Electric


Company. All Rights Reserved

ZONAS DE INFLUENCIA DE LAS NORMAS

MXICO: IEEE /ANSI, IEC, NOM, NMX, NRF

2014 General Electric


Company. All Rights Reserved

ESTNDARES

IEEE Std C37.20.1

IEEE Standard for Metal-Enclosed Low Voltage Power

Circuit Breaker Switchgear

IEEE Std C37.20.2

IEEE Standard for Metal-Clad Switchgear (4.76kV to

38kV)

IEEE Std C37.20.3 IEEE Standard for Metal-Enclosed Interrupter Switchgear


IEEE Std C37.20.7 IEEE Guide for Testing Metal-Enclosed Switchgear
Rated Up to 38 kV for Internal Arcing Faults

IEC 62271-200

AC Metal-Enclosed Switchgear and Controlgear for Rated


Voltages above 1kV and up to 52kV

2014 General Electric


Company. All Rights Reserved

DEFINICIONES
De acuerdo al Std ANSI/IEEE C37.20.2 se tienen las siguientes definiciones:
3.1.5 metal-clad (MC) switchgear: Metal-enclosed power switchgear characterized by the following necessary features:
a) The main switching and interrupting device is of the removable (drawout) type arranged with a mechanism for moving it physically
between connected and disconnected positions and equipped with self-aligning and self-coupling primary disconnecting devices and
disconnectable control wiring connections.
b) Major parts of the primary circuit, that is, the circuit switching or interrupting devices, buses, voltage transformers, and control power
transformers, are completely enclosed by grounded metal barriers that have no intentional openings between compartments.
Specifically included is a metal barrier in front of, or a part of, the circuit interrupting device to ensure that, when in the connected
position, no primary circuit components are exposed by the opening of a door.
c) All live parts are enclosed within grounded metal compartments.
d) Automatic shutters that cover primary circuit elements when the removable element is in the disconnected, test, or removed position.
e) Primary bus conductors and connections are covered with insulating material throughout.
f)

Mechanical interlocks are provided for proper operating sequence under normal operating conditions.

g) Instruments, meters, relays, secondary control devices, and their wiring are isolated by grounded metal barriers from all primary circuit
elements with the exception of short lengths of wire such as at instrument transformer terminals.
h) The door through which the circuit-interrupting device is inserted into the housing may serve as an instrument or relay panel and also
may provide access to a secondary or control compartment within the housing.
NOTES
1Auxiliary vertical sections may be required for mounting devices or for use as a bus transition.
2The term metal-clad (as applied to switchgear assemblies) is correctly used only in connection with switchgear conforming
fully to the definition for metal-clad switchgear given in 3.1.5. Metal-clad switchgear is metal-enclosed, but not
all metal-enclosed switchgear can be correctly designated as metal-clad.

2014 General Electric


Company. All Rights Reserved

DEFINICIONES
De acuerdo al Std ANSI/IEEE C37.20.2 se tienen las siguientes definiciones:
3.1.6 metal-enclosed (ME) power switchgear: A switchgear assembly completely enclosed on all sides and the top with sheet metal
(except for ventilating openings and inspection windows) containing primary power circuit switching or interrupting devices, or both,
with buses and connections. The assembly may include control and auxiliary devices. Access to the interior of the enclosure is provided
by doors or removable covers or both.

2014 General Electric


Company. All Rights Reserved

DIFERENCIAS FSICAS (ANSI)

Metal Clad

Metal Enclosed

2014 General Electric


Company. All Rights Reserved

IEC ES METAL-CLAD NO?!?


IEC 62.271-200 - Clasificacin
Clasificacin atendiendo a la proteccin contra contactos elctricos durante el acceso a los
compartimentos (Accesibilidad)

Prdida de
continuidad de
servicio

Cuando un compartimento
accesible del sistema se abre

Diseo constructivo

LSC1

..La barra y entonces todo la celda


debe aislarse

Sin particiones en la celda y


sin muros de particin con
las celdas adyacentes

LSC2A

El cable de acometida debe


aislarse. Las barras y las celdas
adyacentes pueden permanecer en
operacin.

Muros de particin con las


celdas adyacentes.
Compartimentacin de las
barras.

LSC2B

.El cable de acometida y las celdas


adyacentes pueden permanecer en
operacin

Muros de particin con las


celdas adyacentes.
Compartimentacin de las
barras y del cable.

2014 General Electric


Company. All Rights Reserved

CLASIFICACIN DE LAS UNIDADES SEGN


IEC 60298 e IEC 62271-200

60298

Cubicle

Compartimentado

MetalClad

62271

LSC1

LSC2A & PI

LSC2B & PM

2014 General Electric


Company. All Rights Reserved

CLASIFICACIN DE LAS UNIDADES SEGN


IEC 60298 e IEEE C37.20.2

62271-200 IEC:2003

2014 General Electric


Company. All Rights Reserved

CARACTERSTICAS DEL TABLERO IEC PARA CUMPLIR


CON IEEE C37.20.2
C.2 ANSI defined metal-clad
Metal-clad switchgear as defined in ANSI is, according to this standard, class LSC2B-PM metal-enclosed switchgear and controlgear
characterized by the following main additional requirements.
The main switching devices are withdrawable parts equipped with self-aligning and self-coupling primary disconnection devices and
disconnectable control and auxiliary circuits.
Separate compartments are provided for voltage transformers and control power transformers. Busbar compartments are
additionally divided between horizontally adjacent functional units.
Specifically included is a metal barrier in front of, or a part of, the withdrawable part to ensure that, when in the connected position,
no high-voltage parts are exposed by the opening of a door.
Main-circuit conductors and connections are shrouded with flame-resistant insulating material throughout.
Mechanical interlocks are provided for protecting operators form the accidental discharge of stored energy from withdrawable parts
by any of the following means.
a) Interlocks in the compartment to prevent the complete withdrawal of the switching device from the compartment when
the stored energy mechanism is charged.
b) A suitable device provided to prevent the complete withdrawal of the switching device until the closing function is
blocked.
c) A mechanism provided to automatically discharge the stored energy before or during the process of withdrawing the
switching device from the compartment. If the stored energy is discharged before the switching device is moved from the
connected position, an adjunct electrical interlock is required to prevent stored energy recharge.
Locking means is provided to prevent moving the withdrawable switching device into the connected position.
Segregation of auxiliary circuits is by earthed metal barriers from all high-voltage parts with the exception of short lengths of wire,
such as at instrument transformer terminals.
Main circuits of all voltage transformers include current-limiting fuses. Main circuit fuses provided for protecting transformers are
mounted in such a way that they must be disconnected from the high-voltage circuit before access can be obtained. Provisions are
made for disconnecting or automatically earthing the low-voltage circuit of voltage transformers when the high-voltage circuit is
disconnected. Provisions are made for earthing of the high-voltage winding and/or fuses during the disconnection operation to
dissipate static charges.

2014 General Electric


Company. All Rights Reserved

NIVELES DE TENSIN NOMINAL Y DE PRUEBA


Rangos Mximos de Voltaje para aplicacin de
equipos

IEC Series I Voltajes Tradicionales IEC


IEC Series II Agrega otros voltajes de NA y otras regiones
IEEE Lista de Voltajes preferidos
IEC Series I (kV)
3.6
7.2
12
17.5 24
36
52
IEC Series II (kV)
8.25
15 15.5
25.8 27
38 48.3
IEEE (kV)
4.76
8.25
15
27
38
From IEEE 62271-1, IEEE C37.20.2 & C37.20.3, IEC 62271-200 refers to -1 for these ratings

2014 General Electric


Company. All Rights Reserved

15

ANLISIS DE NORMATIVIDAD
ANSI

IEC

Tableros para Interior y Exterior con tensin de 1kV a 38kV,


60Hz

Tableros para Interior y Exterior con tensin de 1kV a 52kV,


60Hz

Compartimentado Metlicamente:
Bus
Interruptor
TPs
Cables

Compartimentos Metlicos:
Bus corrido en todo el tablero
Interruptor
Cables de Carga
Control

Barras Enfundadas

Barras desnudas

Interruptor Removible

Interruptor puede ser fijo

Calibre de Lmina:
11MSG entre partes principales y secciones
14MSG puertas, tapas, etc.

Sin especificar espesor de lmina

Arreglo de Fases 1, 2, 3:
Arriba hacia Abajo
Derecha a Izquierda
Frente hacia Atrs

Arreglo de barras de acuerdo al fabricante

2014 General Electric


Company. All Rights Reserved

16

ANLISIS DE NORMATIVIDAD
REQUISITO

ANSI

IEC

Aguante Mecnico

Resistencia Mecnica entre 1,500


y 10,000 ciclos de transferencia
con base en la tensin y la
capacidad de apertura

Resistencia Mecnica para 2,000


ciclos de transferencia

Capacidad de Apertura
Asimtrica sobre fallas a travs
de terminales

50% con alteracin de corriente*

30% sin alteracin*

Valor de corriente pico de


aguante a corto tiempo

2.7 Icc

2.5 Icc @ 50Hz


2.6 Icc @ 60Hz
2.7 Icc para casos especiales

Esfuerzo Elctrico

4 KSIsc
La corriente de apertura
simtrica a tensin mxima por
el factor asimtrico (S) por factor
de tensin (K)

3 Isc
La corriente de apertura
simtrica a tensin mxima

Duracin de Corto Circuito

Igual a 3s

Igual a 1 3s

* Modificacin de Corriente

2014 General Electric


Company. All Rights Reserved

17

PRUEBAS
ANSI /IEEE

IEC
PRUEBAS TIPO O DE DISEO

Pruebas Dielctricas

Pruebas del Dielctrico

Pruebas de aguante a Frecuencia del Sistema

Pruebas de tensin de radio interferencia

Pruebas de aguante al impulso por rayo

Medicin de la resistencia de circuitos

Prueba para el aislamiento de la barra

Pruebas de incremento de temperatura

Prueba de humedad a la entrada de boquillas

Pruebas de aguante de la corriente de corto tiempo y de cresta

Pruebas de corriente continua

Verificacin de la proteccin

Pruebas de aguante de corriente corto tiempo

Pruebas de hermeticidad

Prueba de aguante de corriente momentnea del dispositivo de


desconexin primaria del equipo auxiliar

Pruebas de compatibilidad electromagntica

Pruebas de aguante mecnico

Pruebas adicionales en circuitos auxiliares y de control

Materiales aislantes en pelcula y moldeados


Pruebas de resistencia a la flama para aislamiento aplicado
Prueba de calificacin de recubrimiento (pintura)
Prueba de lluvia para Tableros MC para uso exterior

PRUEBAS DE RUTINA O DE PRODUCCIN


Pruebas dielctricas

Pruebas del dielctrico en el circuito principal

Pruebas de Operacin Mecnica

Pruebas en circuitos auxiliares

Pruebas de puesta a tierra de transformadores de medicin

Medicin de la resistencia del circuito principal

Pruebas de operacin elctrica y alambrado de control

Prueba de hermeticidad
Diseo e inspecciones especiales
2014 General Electric
Company. All Rights Reserved

18

Medium Voltage Solutions

2014 General Electric


Company. All Rights Reserved

19

SecoGear /PowerVac

2014 General Electric


Company. All Rights Reserved

20

SecoGear
3.3kV 27kV
Air Insulated Switchgear

PowerVac
4.76kV, 8.25kV & 15kV
Air Insulated Switchgear

2014 General Electric


Company. All Rights Reserved

21

SecoGear
1. Compartimento de Control
2. Compartimento de Bus
3. Compartimento de
Interruptor
4. Shutters Automticos
5. Switch de Puesta a tierra
6. Transformadores de
Corriente
7. Transformadores de Voltaje
8. Compartimento de Cable
9. Barra de tierra
10. Apartarrayos
2014 General Electric
Company. All Rights Reserved

22

PowerVac

2014 General Electric


Company. All Rights Reserved

23

PowerVac

2014 General Electric


Company. All Rights Reserved

24

SecoGear
Tiene Certificado de ArcResistant
@17.5kV 40kA /1s
@27kV 31.5kA /1s

2014 General Electric


Company. All Rights Reserved

25

CLASIFICACIN DE ARCO INTERNO


IEC 62271-200

IEEE C37.20

IAC Internal Arc Class

Type 1 Diseos AR que tienen acceso solo al frente del equipo

Tipo A: Solo Personal Autorizado

Type 2 Diseos AR que tienen libre acceso al frente, atrs y los

Tipo B: Acceso No Restringido


F-Frente, L-Lateral, R-Rear
Ejemplo1: Classification IAC BFLR
Ejemplo2: Classification IAC BF-AR

laterales
Designacin de clasificacin IAC:
Type 1A o type 2A Pruebas bsicas
Type 1B o type 2B Pruebas adicionales, habilitando al usuario a abrir
la puerta del compartimento de control o instrumentacin
Type 1C o type 2C Cada compartimento es resistente al arco y el

efecto de la falla de arco se confina al compartimento donde ocurri


Type 1D El tablero se prueba para IAC solo en los lados requeridos

2014 General Electric


Company. All Rights Reserved

26

SecoGear - Dimensiones y Pesos


DIMENSIONES Y PESOS CLASE 17.5kV
630A / 1250A

1600A / 2000A / 2500A / 3150A


/ 4000A

Altura (mm)

2200

2200

Ancho (mm)

650/800

1000

Fondo (mm)

1400

1400

Peso (kg)

615

615

Descripcin

DIMENSIONES Y PESOS CLASE 27kV


630A / 1250A

1600A / 2000A / 2500A / 3150A


/ 4000A

Altura (mm)

2400

2400

Ancho (mm)

800

1000

Fondo (mm)

1800

1800

1100

1100

Descripcin

Peso (kg)

2014 General Electric


Company. All Rights Reserved

27

PowerVac - Dimensiones y Pesos

2014 General Electric


Company. All Rights Reserved

28

Polo Cerrado Segunda Generacin


La manga aislante protege la BV slo del
impacto mecnico, no as del medio
ambiente
Sujetadores metlicos son requeridos para
la fijacin de las mangas epxicas lo que
podra generar posibles puntos de
conduccin y falla
El aire dentro de la manga podra reducir
la confiabilidad en la operacin de la BV
15 Operaciones en condiciones de falla
De 5 a 10 mil operaciones mecnicas
Apertura en 3 o 5 ciclos

2014 General Electric


Company. All Rights Reserved

29

Polo Embebido ltima Tecnologa


La BV se encuentra encapsulada en una resina epxica,
previene daos mecnicos externos
El Circuito primario del Interruptor est completamente
embebido dentro de la resina epxica, el riesgo por falla
en el aislamiento es prcticamente nulo
Una capa de silicn flexible entre la BV y el encapsulado
asegura que el efecto cracking no se presente en la
resina epxica
Se simplifica el ensamble del polo y la calidad es
monitoreada de una manera ms sencilla
50 Operaciones en condiciones de falla
10 mil Operaciones mecnicas sin mantenimiento

Apertura en 3 ciclos

2014 General Electric


Company. All Rights Reserved

30

NIVELES DE AISLAMIENTO
SecoGear

PowerVac

Niveles de Aislamiento

Niveles de Aislamiento

Standard IEC 62271-1 2007

IEEE C37.06.1-2000

Voltajes
[Kv]

kV rms

kVp (BIL)

Voltajes
[kV]

kV rms

kVp (BIL)

3.6

10

40

4.76

19

60

7.2

20

60

8.25

36

95

17.5

38

95

15

36

95

27

60

125

27

60

125

2014 General Electric


Company. All Rights Reserved

31