ENERGY STAR Qualified Homes

HVAC SYSTEM QUALITY


INSTALLATION RATER CHECKLIST

ENERGY STAR QUALIFIED HOMES

HVAC SYSTEM QUALITY INSTALLATION RATER


CHECKLIST
TABLE OF CONTENTS
Section 1

Review of HVAC System Quality Installation


Contractor Checklist

Section 2

Duct quality installation

Section 3

Duct insulation

Section 4

Duct leakage

Section 5

Whole-building delivered ventilation


HVAC System Quality Installation Rater Checklist

ENERGY STAR QUALIFIED HOMES

HVAC SYSTEM QUALITY INSTALLATION RATER


CHECKLIST
TABLE OF CONTENTS
Section 6

Ventilation controls

Section 7

Air inlets & ventilation source

Section 8

Local mechanical exhaust

Section 9

Ventilation & exhaust fan ratings (exemptions


for HVAC and remote-mounted fans)

Section 10

Combustion appliances
HVAC System Quality Installation Rater Checklist

ENERGY STAR QUALIFIED HOMES

HVAC SYSTEM QUALITY INSTALLATION RATER


CHECKLIST
TABLE OF CONTENTS
Section 11

Filtration

HVAC System Quality Installation Rater Checklist

ENERGY STAR QUALIFIED HOMES

HVAC SYSTEM QUALITY INSTALLATION RATER


CHECKLIST
SECTION 1. REVIEW OF HVAC SYSTEM QUALITY
INSTALLATION CONTRACTOR CHECKLIST
1.1

HVAC system quality installation contractor checklist


completed in its entirety

HVAC System Quality Installation Rater Checklist

ENERGY STAR QUALIFIED HOMES

HVAC SYSTEM QUALITY INSTALLATION RATER


CHECKLIST
SECTION 1. REVIEW OF HVAC SYSTEM QUALITY
INSTALLATION CONTRACTOR CHECKLIST
1.2

Review the following parameters related to system cooling


design, selection, and installation from the HVAC
Contractor checklist.

HVAC System Quality Installation Rater Checklist

ENERGY STAR QUALIFIED HOMES

HVAC SYSTEM QUALITY INSTALLATION RATER


CHECKLIST
SECTION 1. REVIEW OF HVAC SYSTEM QUALITY
INSTALLATION CONTRACTOR CHECKLIST
1.3

Rater-verified supply & return duct static pressure <110%


of contractor values (9.3, 9.4)

HVAC System Quality Installation Rater Checklist

ENERGY STAR QUALIFIED HOMES

HVAC SYSTEM QUALITY INSTALLATION RATER


CHECKLIST
SECTION 2. DUCT QUALITY INSTALLATION

2.1

Connections and routing of ductwork


completed without kinks or sharp bends

DUCT KINKS Verify ducts are installed without kinks.

HVAC System Quality Installation Rater Checklist

2.1

Connections and routing of ductwork


completed without kinks or sharp bends

DUCT SHARP BENDS Verify ducts are installed without sharp


bends.

HVAC System Quality Installation Rater Checklist

2.1

Connections and routing of ductwork


completed without kinks or sharp bends

VENTILATION DUCTS For ease of duct installation, recommend


coordination between the framer, plumber, electrician and HVAC
contractor.

HVAC System Quality Installation Rater Checklist

2.2

No excessive coiled or looped flexible


ductwork

EXCESSIVE COILED OR LOOPED DUCTS Verify ducts are


installed without excessive coiled or looped flexible duct work unless
needed for acoustical control.

HVAC System Quality Installation Rater Checklist

2.2

No excessive coiled or looped flexible


ductwork

BALANCING DAMPERS Verify balancing dampers are installed to


limit flow to diffusers instead of excess duct work.

HVAC System Quality Installation Rater Checklist

2.3

Flexible ducts in unconditioned space not be


installed in cavities smaller than outer duct
diameter in conditioned space not installed in
cavities smaller than inner duct diameter

DUCT INSTALLATION Verify ducts are installed in locations where


there is no compression of the duct or duct insulation.

HVAC System Quality Installation Rater Checklist

2.3

Flexible ducts in unconditioned space not be


installed in cavities smaller than outer duct
diameter in conditioned space not installed in
cavities smaller than inner duct diameter

DUCT INSTALLATION Verify ducts are installed in locations where


there is no compression of the duct or duct insulation.

HVAC System Quality Installation Rater Checklist

2.3

Flexible ducts in unconditioned space not be


installed in cavities smaller than outer duct
diameter in conditioned space not installed in
cavities smaller than inner duct diameter

DUCT INSTALLATION Verify ducts are installed in locations where


there is no compression of the duct or duct insulation.

HVAC System Quality Installation Rater Checklist

2.4

Flexible ducts supported at intervals as


recommended by manufacturer but at a
distance 5 ft

DUCT SUPPORT LOCATION Verify duct supports are installed at a


minimum of every 5 ft. to prevent sagging.
CODE=4 ft.???
HVAC System Quality Installation Rater Checklist

2.4

Flexible ducts supported at intervals as


recommended by manufacturer but at a
distance 5 ft

DUCT SUPPORT INSTALLATION Verify supports are installed


without compressing the duct insulation.

HVAC System Quality Installation Rater Checklist

2.5

Building cavities shall not be used as


supply or return ducts unless they meet
items 3.2, 3.3, 4.1 and 4.2 of this checklist

BUILDING CAVITY DUCT INSULATION Verify insulation is


installed in all band joist cavities and without misalignments,
compressions, gaps or voids and in full contact with the exterior.

HVAC System Quality Installation Rater Checklist

2.5

Building cavities shall not be used as supply


or return ducts unless they meet items 3.2,
3.3, 4.1 and 4.2 of this checklist

BUILDING CAVITY DUCT AIR SEALING Verify all holes, gaps and
seams of the air barrier are properly air sealed.

HVAC System Quality Installation Rater Checklist

2.6

HVAC ducts, cavities used as ducts, and combustion inlets and outlets
may pass perpendicularly through exterior walls but shall not be run
within exterior walls unless at least R-6 continuous insulation is
provided on exterior side of the cavity, along with an interior and
exterior air barrier where required by the Thermal Enclosure Checklist

BUILDING CAVITY DUCT INSULATION Verify insulation is


installed in all band joist cavities and without misalignments,
compressions, gaps or voids and in full contact with the exterior.
HVAC System Quality Installation Rater Checklist

ENERGY STAR QUALIFIED HOMES

HVAC SYSTEM QUALITY INSTALLATION RATER


CHECKLIST
SECTION 2. DUCT QUALITY INSTALLATION
2.7

Quantity and location of supply and return duct terminals


match contractor-provided balancing report

Sections 10.1 + 10.2 on the


Contractor Checklist

ENERGY STAR QUALIFIED HOMES

HVAC SYSTEM QUALITY INSTALLATION RATER


CHECKLIST
SECTION 2. DUCT QUALITY INSTALLATION
2.8

Bedrooms pressure-balanced by one of the following


methods:
A. Providing 1 sq. in. of free area opening per 1 CFM of
measured supply air using transfer grills and/or jump ducts

2.8a

Bedrooms pressure-balanced by providing 1 sq. in.


of free area opening per 1 CFM of measured supply
air using transfer grills and/or jump ducts

AIR FLOW AND SIZING Verify the transfer grilles and/or jumper
ducts are properly sized according to the measured bedroom air flows
in each room.

HVAC System Quality Installation Rater Checklist

2.8a

Bedrooms pressure-balanced by providing 1 sq. in.


of free area opening per 1 CFM of measured supply
air using transfer grills and/or jump ducts

TRANSFER GRILLES Verify transfer grilles are installed in all


bedrooms and all seams, gaps and holes are sealed with mastic, caulk
or foam.

2.8a

Bedrooms pressure-balanced by providing 1 sq. in.


of free area opening per 1 CFM of measured supply
air using transfer grills and/or jump ducts

JUMPER DUCTS Verify jumper ducts are installed in all bedrooms


and all seams, gaps and holes of the jumper duct system are sealed
with mastic.

HVAC System Quality Installation Rater Checklist

2.8a

Bedrooms pressure-balanced by providing 1 sq. in.


of free area opening per 1 CFM of measured supply
air using transfer grills and/or jump ducts

DOOR UNDERCUT EPA recommends undercutting the door by 3/4


in. above the finished floor (e.g., carpet).

HVAC System Quality Installation Rater Checklist

2.8b/c

Bedrooms pressure-balanced by
using dedicated return ducts

RETURN BOX SEALING Verify the return box is sealed to the floor,
wall or ceiling with mastic, caulk and/or foam.

HVAC System Quality Installation Rater Checklist

3.1

All connections to trunk ducts in


unconditioned space insulated

DUCT INSULATION Verify insulation is installed without


misalignment, compression, gaps and voids around all connections
and exposed duct work.

HVAC System Quality Installation Rater Checklist

3.1

All connections to trunk ducts in


unconditioned space insulated

DUCT INSULATION Verify all duct insulation is sealed in place,


preferably with Mastic.

HVAC System Quality Installation Rater Checklist

3.2-3

Prescriptive Path: Supply ducts in unconditioned attic


have insulation R-8
Performance Path: Supply ducts in unconditioned attic
have insulation R-6

DUCT INSULATION Verify all supply and return ducts, boxes, boots
and connections in unconditioned spaces have at least R-6 insulation.
Code 2009 IECC is R-8 for attic

HVAC System Quality Installation Rater Checklist

ENERGY STAR QUALIFIED HOMES

HVAC SYSTEM QUALITY INSTALLATION RATER


CHECKLIST
SECTION 4. DUCT LEAKAGE
4.1

Total measured duct leakage < 8 CFM 25 per 100 sq.


ft. of conditioned floor area

4.2

Measured duct leakage to outdoors < 4 cfm25 per 100 sq.


ft. of conditioned floor area

4.1-2

Total measured duct leakage 8 CFM25


per 100 sq. ft. of conditioned floor area

DUCT CONNECTIONS Verify all seams, gaps and holes of all


ducts are sealed with mastic prior to installing duct insulation.

HVAC System Quality Installation Rater Checklist

4.1-2

Duct boots sealed to floor, wall, or ceiling


using caulk, foam, mastic tape, or mastic
paste

DUCT BOOT SEALING Verify all seams, gaps and holes of all duct
boots are sealed to the floor, wall or ceiling, preferably with mastic.

HVAC System Quality Installation Rater Checklist

4.1-2

Duct boots sealed to floor, wall, or ceiling


using caulk, foam, mastic tape, or mastic
paste

DUCT BOOT SEALING Verify all seams, gaps and holes of all duct
boots are sealed to the floor, wall or ceiling, preferably with mastic.

ENERGY STAR QUALIFIED HOMES

HVAC SYSTEM QUALITY INSTALLATION RATER


CHECKLIST
SECTION 5. WHOLE-BUILDING DELIVERED
VENTILATION
5.1

Measured ventilation rate is within 100-120% of HVAC


contractor design values

This is where ASHRAE comes in 7.5 CFM per Occupant + 1% of the


floor area.

(Section 1 Of Contractor Checklist)

6.4

Continuously-operating ventilation &


exhaust fans include override controls

PROPER CONTROL LOCATION Verify override controls for all


fans are installed in an easily accessible location. (i.e. close to the
thermostat)

6.5

Ventilation controls labeled, unless function is


obvious (e.g. bathroom exhaust fan)

MANUFACTURER LABELED CONTROLS Verify controls that are


differentiated or labeled by the manufacturer are installed.

6.5

Ventilation controls labeled, unless function is


obvious (e.g. bathroom exhaust fan)

PERMANENTLY LABELED CONTROLS If manufacturer labeled


controls do not exist, verify permanent labels are installed to indicate
the function of the control.

7.2

Air inlets 2 ft. above grade or roof deck in climate


zones 1-3 or 4 ft. above grade or roof deck in
climate zones 4-8 and not obstructed by snow,
plantings, or other material at time of inspection

AIR INLET HEIGHT Verify any ducts located in the wall cavity are
sealed and that there is sealing around any holes or gaps created in
bottom or top plates from installation.

HVAC System Quality Installation Rater Checklist

7.3

Air inlets provided with mesh rodent /


insect screen with mesh 0.5 in.

RODENT/INSECT SCREEN Verify rodent/insect screen with mesh


is installed on all air inlets.

HVAC System Quality Installation Rater Checklist

ENERGY STAR QUALIFIED HOMES

HVAC SYSTEM QUALITY INSTALLATION RATER


CHECKLIST
SECTION 7. AIR INLETS & VENTILATION SOURCE
7.4

Ventilation air comes directly from outdoors and not from


adjacent dwelling units, garages, unconditioned
crawlspaces, or attics.

7.4

Ventilation air comes directly from outdoors


and not from adjacent dwelling units, garages,
unconditioned crawl spaces, or attics

VENTILATION DUCT TERMINATION Verify all ventilation ducts


terminate at the exterior.

HVAC System Quality Installation Rater Checklist

ENERGY STAR QUALIFIED HOMES

HVAC SYSTEM QUALITY INSTALLATION RATER


CHECKLIST
SECTION 8. LOCAL MECHANICAL EXHAUST

8.3

8.1

Kitchen continuous rate: > 5 ACH, based on kitchen


volume
Kitchen intermittent rate: > 100 CFM

8.2

Bathroom continuous rate: > 20 CFM


Bathroom intermittent rate: > 50 CFM
If fans share common exhaust duct, back-draft dampers
installed.

ENERGY STAR QUALIFIED HOMES

HVAC SYSTEM QUALITY INSTALLATION RATER


CHECKLIST
SECTION 8. LOCAL MECHANICAL EXHAUST
8.4

Common exhaust duct not shared by fans in separate


dwelling.

8.5

Clothes dryers, except electric condensing dryers equipped


with condensate drain, vented directly to outdoors.

ENERGY STAR QUALIFIED HOMES

HVAC SYSTEM QUALITY INSTALLATION RATER


CHECKLIST
SECTION 9. VENTILATION & EXHAUST FAN RATINGS
(EXEMPTIONS FOR HVAC AND REMOTE-MOUNTED FANS)
9.1

Intermittent supply & exhaust fans rated at < 3 sones


by manufacturer, unless rated flow > 400 CFM.

9.2

Continuous supply & exhaust fans rated at < 1 sone by


manufacturer.

9.3

Bathroom fans used as part of a whole-house


mechanical ventilation system shall be energy star
qualified; unless rated flow rate > 500 CFM.

ENERGY STAR QUALIFIED HOMES

HVAC SYSTEM QUALITY INSTALLATION RATER


CHECKLIST
SECTION 10. COMBUSTION APPLIANCES
10.1

Furnaces, boilers, and water heaters located within the


homes pressure boundary are mechanically drafted or
direct-vented to outdoors. As an exception,
atmospherically vented equipment is allowed in
Climate Zone 1-3. For atmospherically vented
furnaces, boilers, and water heaters, the rater has
conducted BPIs combustion safety test procedure and
determined that the CO test results are less than 25
ppm and the combustion appliance zone
depressurization limit is not exceeded.

10.1

Furnaces, boilers, and water heaters located within


the homes pressure boundary are mechanically
drafted or direct-vented to outdoors

APPROPRIATE APPLIANCES Verify mechanically drafted or directvented appliances to outdoors are installed.

HVAC System Quality Installation Rater Checklist

10.1

Furnaces, boilers, and water heaters located within


the homes pressure boundary are mechanically
drafted or direct-vented to outdoors

APPROPRIATE APPLIANCES Verify mechanically drafted or directvented appliances to outdoors are installed.

HVAC System Quality Installation Rater Checklist

What does this mean for oil?


Footnote: 31

Packaged Natural Draft


Oil Fired Boilers-Water
Only. 129,,000 BTU

ENERGY STAR QUALIFIED HOMES

HVAC SYSTEM QUALITY INSTALLATION RATER


CHECKLIST
SECTION 10. COMBUSTION APPLIANCES
10.2

If atmospherically vented fireplaces are located inside


the homes pressure boundary, total net rated exhaust
flow of the two largest exhaust fans (excluding summer
cooling fans) is 15 CFM per 100 sq. ft. of occupiable
space when at full capacity.

ENERGY STAR QUALIFIED HOMES

HVAC SYSTEM QUALITY INSTALLATION RATER


CHECKLIST
SECTION 10.3 COMBUSTION APPLIANCES
10.3
If Unvented Combustion Appliances other than cooking ranges are located
inside the homes Pressure Boundary, the Rater has operated the appliance for
at least 10 minutes and verified that the ambient CO level does not exceed 35
ppm.

ENERGY STAR QUALIFIED HOMES

HVAC SYSTEM QUALITY INSTALLATION RATER


CHECKLIST
SECTION 11. FILTRATION
11.1

MERV 6 or better filter installed in ducted


mechanical systems.

11.2

All return air and mechanically supplied outdoor air


pass through Filter.

11.3

Filter located and installed so as to facilitate


access and regular service by the owner.

11.4

Filter access panel includes gasket or comparable


sealing mechanism.

11.1-4

MERV 6 or better filter installed in


ducted mechanical systems

PROPER FILTER SPECIFICATIONS Verify all filters installed have


at least a MERV 6 rating.

HVAC System Quality Installation Rater Checklist

11.1-4

Filter located and installed so as to facilitate


access and regular service by the owner

PROPER FILTER LOCATION If the HVAC equipment is located in


an inaccessible location, such as a crawlspace, verify filters are
installed in an accessible location, such as a return box.

HVAC System Quality Installation Rater Checklist

11.1-4

Filter access panel includes gasket or comparable


sealing mechanism and fits snugly against the
exposed edge of filter when closed to prevent
bypass

PROPER FILTER INSTALLATION Verify all filters are properly


installed and do not allow air bypass.

HVAC System Quality Installation Rater Checklist

ENERGY STAR QUALIFIED HOMES

HVAC SYSTEM QUALITY INSTALLATION RATER


CHECKLIST
Any mention of trade names, commercial products and
organizations in this document does not imply endorsement
by the U.S. Environmental Protection Agency ("EPA") or the
U.S. Government. The EPA and its collaborators make no
warranties, whether expressed or implied, nor assume any
legal liability or responsibility for the accuracy,
completeness or usefulness of the contents of this
publication, or any portion thereof, nor represent that its
use would not infringe privately owned rights. Further, the
EPA cannot be held liable for construction defects or
deficiencies resulting from the proper or improper
application of the content of this guidebook.

You might also like