Professional Documents
Culture Documents
In the early days of the electricity supply industry, protective equipment for plants
connected to a busbar installation was relied upon to clear busbar faults. This resulted in
time delayed fault clearance by time graded protections such as distance relays or
overcurrent time relays. With present day widely meshed power system networks with
line sections varying in length and numerous intermediate infeeds, fault clearance by
Zone 2 or Zone 3 of distance relay can be difficult plus the impossibility of selective
tripping of different bus sections. In order to maintain system stability and minimise
damage due to high fault levels time delayed tripping for busbar faults is no longer
acceptable. It is therefore necessary to detect busbar faults selectively with a unit form of
protection system.
Page 1
Principle of Operation
The principle of operation of a frame leakage scheme is based on the fact that any
breakdown of the switchgear insulation will raise the potential of the frame to earth and
cause a current to flow in the connection between the frame bonding bar and earth. A
current transformer connected between the bonding bar and earth will therefore measure
this earth fault current and operate a protective relay. An instantaneous current relay is
sufficient for this application.
The current transformer ratio used is not critical provided the necessary fault setting can
be obtained.
IF
Outgoing
feeder
= I1 + I2
Frame-leakage
current
Switchgear
transformer
frame
Switchgear
frame
Generator
System
earthing
Earth
I1 + I2
I1
I1
Frame
insulation
I2
Earthing
electrode
Page 2
DIFFERENTIAL PROTECTION
Two forms of differential protection are adopted for busbar protection, namely, `High
Impedance` and `Low Impedance`.
High Impedance Differential Protection
This is a unit type protective scheme in which currents entering and leaving the busbar
installation are compared continuously. The object is to provide fast operation at a low
fault setting on internal faults and yet retain stability up to the highest possible value of
short circuit current on through faults. Current transformers on each of the busbar circuits
are connected in parallel which will produce a resultant current to operate a relay for
internal busbar faults only. Theoretically such a system is unaffected by through faults,
but in practice the associated current transformer may not behave ideally when the
current exceeds a certain value. Errors in transformation due to saturation of the current
transformer cores may be sufficient to cause maloperation if special precautions are not
taken. In order to ensure stability for external faults the current through the relay is limited
by the insertion of an external resistor in series with the relay. This resistor is often
refered to as a stabilising resistor.
The stability limit of a busbar protection scheme is based on the maximum through fault
current. In general this takes the value of the associated switchgear rating irrespective of
the existing or anticipated fault levels.
Fault Setting Resistors
These are used to increase the effective primary fault setting by creating a shunt
resistance across the relay circuit. They are useful where a standard relay with a given
setting is used for all the busbar installations to achieve a given primary fault setting
throughout.
Page 3
Check Feature
A second line of defence is considered good practice in most schemes of busbar
protection, not to give security against maloperation of the primary protection due to
inherent defects but to prevent incorrect tripping as a result of damage to wiring and
equipment from extraneous sources. A check feature is provided by duplication of the
primary protection using a second set of current transformers on all circuits other than
bus section and coupler units. The check system is arranged in a similar manner to the
primary protection but forms one zone only covering the whole of the busbars and does
not discriminate between faults in the various sections of the busbars.
Use of Non-Linear Resistors (Metrosils) to Limit Voltage
Across Relay and Current Transformer Secondary Wiring
Under in-zone fault conditions, the high impedance relay circuit constitutes an excessive
burden to the current transformers, leading to the development of a high voltage the
waveform of which will be highly distorted with a peak value many times the nominal
saturation voltage. Non-linear resistors are used in parallel with the relay circuit to reduce
this voltage.
CT WIRING SUPERVISION
When a current transformer secondary winding or connections between current
transformers and the relay circuit become open circuited, the resultant out-of-balance
current will flow through the parallel combination of relay, metrosil, fault setting resistor
and current transformer magnetising impedance. This may cause the protection to
operate for load or through fault conditions depending on the effective primary setting.
The condition of an open circuit can be detected by measuring the voltage across the
relay circuit by a sensitive voltage operated relay as shown in the following figure. This
relay is set to operate when the out-of-balance current equals about 10% of the least
loaded feeder connected to the busbars or 25 amperes whichever is the greater.
If accurate details of current transformer magnetising characteristics are available, the
required setting can be calculated. Checks should be done on site to ensure that the
relay will not operate due to normal unbalance with the system and protection healthy.
CT1
I2
R
ZM2
ZM3
ZM4
R
I1
Super
vision
relay
Page 4
I3
I4
Operation of the supervision relay is arranged to give an alarm that the busbar protection
is faulty and to short circuit the buswires if this is necessary to prevent damage to the
protective relay and stability resistors.
When the busbar protection has a fault setting below full load of the connected feeders it
is very likely to operate due to an open circuit current transformer. In this case a check
feature is required to prevent tripping. At the same time it is important that the buswires
are short circuited via the supervision relay to prevent thermal damage to the protective
relay and stabilising resistors which would otherwise remain continuously picked up under
load conditions.
The supervision relay must have a time delay to prevent its operation due to genuine
busbar faults. A time delay of about 3 seconds is used.
CURRENT TRANSFORMERS
Current Transformer Design
An important advantage of using high impedance relay in a circulating current system is
the ability to predict the protective scheme performance in terms of primary fault setting
and through fault stability by calculation without heavy-current conjunctive tests. The
validity of the calculation is based on the assumption that all the current transformers are
of low reactance type. A low reactance current transformer is defined as one of which a
knowledge of the secondary exciting current, secondary winding resistance and turns
ratio is sufficient for an assessment of its performance. This covers current transformers
with uniformly distributed windings or whose core leakage flux is negligible.
Current Transformer Wiring
With high impedance circulating current schemes, it is of the utmost importance that the
lead burdens between the various sets of current transformer be kept as low as possible
in order to obtain the required stability and sensitivity. It is therefore advisable to run the
buswires in the form of a closed ring between all the circuit breaker control cabinets. This
avoids the need for numerous radial loops between the current transformers and the bus
zone panel which would be required if the buswires were formed in the bus zone panel.
A closed ring consisting of cores in multicore cables affords increased security against
maloperation which may result from unbalancing of the protection due to inadvertent
disconnection of bus wires. It also provides easy extension of the protection when new
circuits are to be connected into the protection zone.
An example of running a multicore cable ring in the case of a double busbar arrangement
is as follows :
i)
ii)
iii)
The size of conductor normally used for the interconnecting pilots is 2.5 mm. However, it
is occasionally necessary to use parallel cores to reduce the burden.
Page 5
R
M
A
a b
c d
R
M
Current Transformer Location
The three alternative arrangements as shown in the following diagram :
F1
F1
F1
Interlocked
overcurrent
relay
Circuit
protection
F3
Circuit
Protection
F3
Circuit
protection
F4
Busbar
F3
Busbar
Protection
protection
Busbar
protection
F2
Overlapping C.T.s
Interlocked
overcurrent
relay
F4
F2
i)
current transformers for feeder and busbar protection overlapping the circuit
breaker
ii)
iii)
i)
In this arrangement faults at F1 and F2 are cleared correctly by the busbar and
feeder protection respectively. Faults at F3 between the circuit breaker and
feeder protection current transformers will be cleared by the busbar protection
and possibly also by the remote end of the feeder protection. No unnecessary
disruption to loads will result from this.
Faults at F4 will be seen by the feeder protection but also by the busbar
protection resulting in unnecessary tripping of the busbars for what is
essentially a feeder fault. This is the main disadvantage of this arrangement.
ii)
This is the most common arrangement where all the current transformers are
on the feeder side of the circuit breaker. However, there is a blind spot at
point F3 where faults are seen by busbar protection but not seen by the feeder
protection. With this arrangement it is therefore required to intertrip the
remote circuit breaker when busbar protection operates.
Intertripping can be achieved by unstabilising the feeder protection and can be
instantaneous or time delayed to allow clearance of faults on the busbar side
of the circuit breaker before intertripping.
Alternatively an interlocked overcurrent relay can be used to intertrip the
remote circuit breaker. This relay is interlocked with the busbar protection.
iii)
When all the current transformers are located on the busbar side of the circuit
breaker a fault at F3 between the current transformers and circuit breaker will
continue to be fed from the busbars after the circuit breaker has been tripped
by the feeder protection. An interlocked overcurrent relay which is interlocked
with the feeder protection is required to ensure that the busbars are only
tripped for this condition and not for faults on the feeder.
BUSBAR CONFIGURATIONS
Several switching schemes are available and there are many variants of each scheme.
When selecting a suitable scheme consideration should be given to the ability to take out
any circuit breaker or other equipment for maintenance without removing the
corresponding circuit from service, also the ability to isolate the busbar for maintenance,
some schemes being more flexible than others in this respect.
In addition to plain single and double busbar schemes, the following are some of the other
more popular arrangements:
1)
With this double busbar variation, each feeder has isolators to enable switching to main or
reverse/transfer bars, and also an additional isolator to enable the feeder breaker to be
bypassed. The reverse bar may then function also as a transfer bar and the bus coupler
breaker takes over the function of the feeder breaker to free it for maintenance.
Page 7
To apply discriminative busbar protective, suitable auxiliary switches are required on each
isolator to select the CTs for the correct zone, and the trip circuits to the appropriate
relays.
Main
Reserve / Transfer
By-pass
By-pass
Isolator
Isolator
2)
Triple Busbar
Main
Reserve
Transfer CB
Transfer CB
Transfer
Page 8
3)
The mesh busbar scheme is a frequently used EHV busbar configuration. A transformer
and a feeder are linked at each corner of the mesh and four circuit breakers used to
complete the mesh interconnection the arrangement being justified on the grounds of
economy.
F1
F3
T1
T3
T4
T2
F4
F2
The protection shown consists of a fully discriminative scheme with a relay at each
corner. A fault at any corner trips the two breakers associated with that corner and also
initiates any intertripping necessary to open circuit breakers at remove ends.
F1
F3
87
87
R1
R3
T1
T3
T2
T4
87
R4
Page 9
87
R2
4)
This is a very popular and economical scheme, three breakers and two feeders being
arranged between the two busbars. Under normal conditions all breakers are closed.
During maintenance of a feeder breaker only that breaker would be kept open.
During maintenance of a busbar, all the breakers connected to that busbar would remain
open to isolate that busbar.
When busbar protection is required, then each busbar is considered individually and a
single busbar scheme applied to each as shown, as with the protection for the mesh
busbar previously, the protection scheme does not require isolator auxiliaries for CT zone
selection or in the tripping circuits, the scheme being very simple, and this together with
the operational flexibility of this busbar configuration accounts for its popularity.
Page 10
87
87
Fast
Modular scheme design allows relays to relate to each circuit and function of the
protection
High sensitivity for phase and earthfaults. Protection for each phase can be relatively
independent
Extremely stable for external faults. This is achieved by using saturation detectors
Current transformers can be of different ratio, relatively smaller output and shared
with other protective devices
Incomer
Block
BLOCK t
O/C
Backt
IF2
O/C
O/C
O/C
O/C
By using directional relays it is possible to provide zones of protection, thus only removing
the faulty section of a busbar.
Page 12