PowerWAVE 3000/T

Single-phase UPS for mid-size server rooms, networks,


telecommunications systems and industrial processes

PowerWAVE 3000/T
Compact, singlephase critical
power protection
up to 20 kVA.

PowerWAVE 3000/T
Capacities from 7.5 kVA to 20 kVA
single phase
On-line double conversion, transformerless
technology for high reliability
94% efficiency across a wide load range
Integral batteries
Near unity input power factor
Low input harmonic distortion (THDi)
Small footprint and low weight
Ergonomic design for easy serviceability
Energy saving and low carbon footprint

For more information call 01256 386700


or visit www.upspower.co.uk
PowerWAVE 3000/T is a true
on-line, double-conversion, VFI
(voltage frequency independent)
UPS that provides enhanced
power protection in a compact
format. Its outstanding price/
performance delivers the best
value for money in its category
with uncompromised system
reliability and power availability.
RS232 Smart Port
CS121 SNMP
Card Slot
Dry Port Volt - Free
contacts
Maintenance
Bypass Switch
Bypass Line Fuse
Battery Fuse
Output Switch
Rectifier Line Fuse
Input/Output
terminal block

Highest load availability

Low cost of ownership

Space saving

Key benefits

Key benefits

Key benefits

Productivity maximised

High efficiency at partial and rated loads

Reduced footprint

Downtime minimised

Low carbon footprint

Up to three hours back-up with integral


batteries

PowerWAVE 3000/T offers class leading


reliability by incorporating redundant critical
circuits (RCC) which duplicate all of the
critical components and circuitry within the
UPS. Some UPS have single points of failure.
PowerWAVE 3000/T overcomes this
problem and offers exceptional reliability and
availability under all circumstances.

With a transformerless design and Energy


Saving Inverter Switching (ESIS) technology,
PowerWAVE 3000/T delivers very high
efficiency at partial and rated loads (up to
94%). This level of efficiency dramatically
reduces the Total Cost of Ownership of the
UPS during its lifecycle.

With a footprint of only 0.37m2 at 20kVA,


the PowerWAVE 3000/T has a power
density of up to 38kW/m2. As a result,
substantial and valuable space savings are
achieved even at the highest power ratings.

Flexible battery configuration


Key benefits
Optimal sizing of the battery capacity
Advanced battery monitoring
The PowerWAVE 3000/T is available in three
cabinet sizes, allowing you to choose the
required autonomy for your critical load,
avoiding the use of additional battery
cabinets. Ripple-free battery chargers
protect batteries and extend the lifetime
performance, further reducing running costs.

The advanced Battery Monitoring and


Management algorithm continuously
monitors the battery and will trigger a
warning signal in the unlikely event
of a failure.

Cabinet A

Cabinet B

Cabinet C

UPS Rating (kVA)

7.5

10

12

15

7.5

10

12

15

20

7.5

10

12

15

20

Max back-up (mins) with 100% load


(PF = 0.7) internal batteries

33

23

18

14

110

90

69

53

39

225

170

140

110

75

Max battery configuration


Dimensions (WxHxD) in mm

1 x 50 x 9Ah

3 x 48 x 9Ah

2 x 40 x 28Ah

340 x 820 x 800

450 x 1250 x 860

550 x 1650 x 890

Block diagram
SINGLE INPUT FEED (standard)

DUAL INPUT FEED


Mains (3x380/220V,
3x400/230V, 3x415/240V)

Fuse A
Cable A

FA1

Fuse B

FA2

FA4

Int. Batts.

Static Switch
Output
Switch

IA2

Inverter

F1
Maint.
Bypass

IA1

EXTERNAL
BATTERY
CABINET
(option)

Int. Batts.

Static Switch
Output
Switch

IA2

Maint.
Bypass

Cable D

IA1

Cable D

Load

Load

Uninterruptible Power
Supplies Ltd,
Woodgate,
Bartley Wood Business Park,
Hook, Hampshire RG27 9XA
Tel: 01256 386700
UVDB Verify
empowered by Achilles

Fax: 01256 386701


Email: sales@upspower.co.uk

UPS 369-01-01 UK PowerWAVE 3000/T 22/06/12

EXTERNAL
BATTERY
CABINET
(option)

FA2

Rectifier

Inverter

F1

Cable C

FA1

Rectifier
FA4

Fuse C

Cable B

You might also like