Professional Documents
Culture Documents
Pag. 1/13
TECHNICAL DESCRIPTION
Volume 3, Part D
Technical Description
Thermo-technological installations
CONTENT
1.
GENERAL DATA..................................................................................................................... 2
1.1.
Object of the project..........................................................................................................2
1.2.
Work location.................................................................................................................... 2
1.3.
General considerations.....................................................................................................2
2. REFERENCE DOCUMENTS...................................................................................................2
2.1.
International agreements..................................................................................................2
2.2.
Agreements and approvals CNCF CFR.........................................................................3
3. EXISTING SITUATION............................................................................................................. 3
3.1.
Cmpina station................................................................................................................ 3
3.2.
Comarnic station...............................................................................................................3
3.3.
Valea Larg operation halt................................................................................................4
3.4.
Sinaia station.................................................................................................................... 4
3.5.
Buteni station..................................................................................................................4
3.6.
Azuga station....................................................................................................................4
3.7.
Azuga Predeal section...................................................................................................5
4. GENERAL PRINCIPLES FOR REHABILITATION WORKS....................................................5
4.1.
General principles for Smax. 120 km/h...........................................................................5
4.2.
Types of designed works..................................................................................................5
5. DESCRIPTION OF THE DESIGNED WORKS.........................................................................5
5.1.
Cmpina station................................................................................................................ 5
5.2.
Comarnic station...............................................................................................................6
5.3.
Valea Larg operation halt................................................................................................7
5.4.
Sinaia station.................................................................................................................... 8
5.5.
Buteni station..................................................................................................................9
5.6.
Azuga station.................................................................................................................. 10
5.7.
Azuga Predeal section.................................................................................................11
6. TYPES OF MATERIALS PROVIDED FOR THE WORKS......................................................11
6.1.
New materials................................................................................................................. 11
6.2.
Reused materials............................................................................................................ 11
7. WORKS.................................................................................................................................. 11
8. SCHEDULES FOR CHECKING THE WORKS PERFORMANCE, QUALITY AND
ACCEPTANCE............................................................................................................................... 11
9. LABOR PROTECTION MEASURES AND FIRE PROTECTION...........................................12
10. ENVIRONMENT PROTECTION.............................................................................................12
11. ECONOMIC DOCUMENTATIONS.........................................................................................12
Pag. 2/13
TECHNICAL DESCRIPTION
Volume 3, Part D
Technical Description
Thermo-technological installations
TECHNICAL DESCRIPTION
1.
GENERAL DATA
2.
REFERENCE DOCUMENTS
Pag. 3/13
TECHNICAL DESCRIPTION
-
EXISTING SITUATION
Pag. 4/13
TECHNICAL DESCRIPTION
The thermal station is placed in a room at the ground floor, is provided with 90/70 0C heat carrier
boiler with pit gas burner and is connected to an improper smoke chimney (section smaller than
required).
The indoor heating installation is incomplete and badly dimensioned.
The heating units are steel radiators, generally mounted under the windows.
The distribution network is placed at the floor level; it is made out of steel pipes for the thermal
station and copper pipes for the rest of the building.
The heating units are provided with valves on the supply pipe and on the return pipe as well as
with hand driven air-release valve on the radiator.
The domestic hot water is not prepared in the existing thermal station.
The power unit (old and obsolete) is placed in a room independent from the passenger building.
The power unit room has no ventilation installation.
In the rooms for the railway traffic control installations and afferent staff, there is no air conditioning
to improve the working conditions.
Nowadays, the public toilet is of non heated latrine type.
3.3. Valea Larg operation halt
The IS building has no heating installation; at present, the heating is provided by solid fuel stoves.
The (old and obsolete) power unit is mounted in the IS building. This room has no ventilation
installation at present.
In the rooms for the railway traffic control installations and afferent staff, there is no air conditioning
to improve the working conditions.
3.4. Sinaia station
The heating installations of the Official Station building and the Passenger building are in very poor
condition. At present, the heat carrier source for these buildings is its own thermal station place din
the Official Station building.
The (old and obsolete) power unit is mounted in the Official Station building. This room has no
ventilation installation at present.
In the rooms for the railway traffic control installations and afferent staff, there is no air conditioning
to improve the working conditions.
3.5. Buteni station
The IS building has no heating installation; at present, the heating is provided by stoves.
The (old and obsolete) power unit is mounted in the IS building. This room has no ventilation
installation at present
In the rooms for the railway traffic control installations and afferent staff, there is no air conditioning
to improve the working conditions.
Nowadays, the public toilet is of non heated latrine type.
3.6. Azuga station
The passenger building, which also comprises IS rooms, was provided with a modern thermal
station two years ago. The thermal station is placed in a room at the ground floor and is provided
TERMO-TEHNOLOGICAL INSTALLATIONS CNCF 22.01.2015 Mtro Rev 0
Pag. 5/13
TECHNICAL DESCRIPTION
with 90/700C heat carrier boiler with pit gas burner, pumps, expansion vessel and a collector
distributor pipe.
The indoor heating installation is new (about 2 years) and is in operation.
The heating units are steel radiators, generally mounted under the windows.
The distribution network is placed at the floor level and the ground floor ceiling; it is made out of
steel pipes for the thermal station and copper pipes for the rest of the building.
The heating units are provided with valves on the supply pipe and on the return pipe as well as
hand driven air-release valve on the radiator.
The domestic hot water is not prepared in the existing thermal station.
The power unit (old and obsolete) is placed in a room independent from the passenger building.
The power unit room has no ventilation installation.
In the rooms for the railway traffic control installations and afferent staff, there is no air conditioning
to improve the working conditions.
Nowadays, the public toilet is of non heated latrine type.
3.7. Azuga Predeal section
The control block building in Predeal has no heating installation; at present, electric radiators are
used for heating.
In the rooms for the railway traffic control installations and afferent staff, there is no air conditioning
to improve the working conditions.
4.
5.
The IS building was provided with new heating installations with static units (steel radiators).
The type of each radiator is written on the relevant plan.
The thermal source consists in a new KESTON module (80/60 0C hot water) thermal station placed
at the ground floor; this module does not require the use of a chimney.
TERMO-TEHNOLOGICAL INSTALLATIONS CNCF 22.01.2015 Mtro Rev 0
Pag. 6/13
TECHNICAL DESCRIPTION
The hot water distribution (supply) network is placed at the ground floor ceiling and the return pipe
is partly laid at the ground floor level and partly under the ground floor ceiling.
After the completion of the heating installation, it has to be tested, primed and oil painted
complying with the norms in force.
The exhaust gas resulted from the hot water KESTON module is to be evacuated through PVC
pipe mounted in the existing masonry chimney.
The thermal energy required for heating is 61.128 W (52.570 kcal/h).
In the thermal station at the basement of the passenger building, a 100l boiler is to be mounted for
instant preparation of the domestic hot water, instead of the existing boiler in the IS building which
shall be demounted.
Ventilation installation
The power unit room needs a vent installation. When the power unit operates, the heat engine and
the generator unit are heated and part of the heat is released in the room. The fan of the heat
engine evacuates the hot air outside through a sheet piping. The compensation of the evacuated
air as well as the fresh air required for the combustion is introduced into the room by an axial fan
mounted to the wall.
Air-conditioning installations
SPLIT air conditioning system was provided in the rooms for the railway traffic control installations
and afferent staff rooms. The powers of these devices were settled by calculating the heat input
from the outside during the summer season as well as the heat releases of the afferent device,
from the artificial lighting, as well as from the persons working in the room.
The dispatcher room is provided with two air conditioning installations with heating /cooling modes
(one in operation and one for backup). Two air conditioning installations (one in operation and one
for backup) are provided in the room where the UPS and the computer cubicles are to be mounted.
The (indoor + outdoor) installations have to be mounted by the supplier.
District LC
The CL District building was provided with new heating installation with static units (steel radiators).
The type of each radiator is written on the relevant plan.
The thermal source consists in a KESTON module (80/60 0C hot water) thermal station placed at
the ground floor; this module does not require the use of a chimney.
The hot water distribution (supply) network is partly placed under the ground floor ceiling and partly
at the ground floor level.
After the completion of the heating installation, it has to be tested, primed and oil painted
complying with the norms in force.
The exhaust gas resulted from the hot water KESTON module is to be evacuated through PVC
pipe.
The distance between the burnt gas evacuation pipe and the air inlet pipe for combustion will be
two meters (vertically).
The thermal energy required for heating is 56.643 W (48.713 kcal/h).
5.2. Comarnic station
TERMO-TEHNOLOGICAL INSTALLATIONS CNCF 22.01.2015 Mtro Rev 0
Pag. 7/13
TECHNICAL DESCRIPTION
Within this project, modification and completion works were carried out for the existing indoor
central heating installation, depending on the new arrangements for the IS room and on the
standards in force.
A part of the demounted units and cocks were remounted to other positions as required by the
calculus of the heat losses according to SR 1907/1 and 2 1997.
It is necessary to demount ten units of which five are to be remounted. The remaining five units are
placed at the beneficiarys disposal to be further used to other indoor heating works.
Six new heating units of the same type as the existing ones will be additionally mounted.
Small modifications of the distribution network were designed in order to avoid the computers room
of the IS installation.
A new chimney is to be designed for the thermal station and two safety valves shall be mounted on
the supplu pipe of the boiler (according to STAS 7132 / 86).
The thermal energy required for heating is 72.551 W (62.394 kcal/h).
Ventilation installation
The power unit is in a separate room, independent from the station building and needs ventilation
installation. When the power unit operates, the heat engine and the generator unit are heated and
part of the heat is released in the room. The fan of the heat engine evacuates the hot air outside
through a sheet piping. The compensation of the evacuated air as well as the fresh air required for
the combustion is introduced into the room by an axial fan mounted to the wall. During the cold
season, the power unit room is heated by electric radiators.
Air-conditioning installations
SPLIT air conditioning system was provided in the rooms for the railway traffic control installations
and afferent staff. The powers of the devices were settled by calculating the heat input from the
outside during the summer season as well as the heat release of the afferent device, from the
artificial lighting, as well as from the persons working in the room.
The dispatcher room is provided with two air conditioning installations, with heating/ cooling modes
(one in operation and one for backup). Two air conditioning installations (one in operation and one
for backup) are provided in the room where the UPS and the computer cubicles are to be mounted.
One air conditioning installation was provided in the stationmasters room. The (indoor + outdoor)
installations have to be mounted by the supplier.
Indoor heating installations have been provided for the new WC using steel radiators.
The thermal energy required for heating is 17.441 W (15.000 kcal/h).
The heat carrier, 80/60 gr.C hot water is supplied by a gas operated wall boiler which will supply
the domestic hot water as well.
The boiler is of modern type without chimney; 21.500 kCal/h, mounted in a separate room or in the
tickets sellers cabin.
The WC rooms are to be aerated by the provided windows and the disabled persons cabin shall be
ventilated using special provided fan.
5.3. Valea Larg operation halt
TERMO-TEHNOLOGICAL INSTALLATIONS CNCF 22.01.2015 Mtro Rev 0
Pag. 8/13
TECHNICAL DESCRIPTION
The IS building was provided with new heating installation with static units (steel radiators).
The type of each radiator is written on the relevant plan.
The thermal source is a hot water electric boiler placed at the ground floor in the C.T room with 90 /
700 C operation temperature.
The hot water distribution (supply) network is placed at the basement ceiling and the return pipe at
the basement floor.
After the completion of the heating installation, it has to be tested, primed and oil painted
complying with the norms in force.
The thermal energy required for heating is 37.475 W (32.229 kcal/h).
Ventilation installation
The power unit room needs ventilation installation. When the power unit operates, the heat engine
and the generator unit are heated and part of the heat is released in the room. The fan of the heat
engine evacuates the hot air outside through a sheet piping. The compensation of the evacuated
air as well as the fresh air required for the combustion is introduced into the room by an axial fan
mounted to the wall.
Air-conditioning installations
SPLIT air conditioning system was provided in the rooms for the railway traffic control installations
and afferent staff. The powers of the devices were settled by calculating the heat input from the
outside during the summer season as well as the heat releases of the afferent device, from the
artificial lighting, as well as from the persons working in the room.
The dispatcher room is provided with two air conditioning installations, with heating/ cooling modes
(one in operation and one for backup). Two air conditioning installations (one in operation and one
for backup) are provided in the room where the UPS and the computers cubicles are to be
mounted. The (indoor + outdoor) installations have to be mounted by the supplier.
5.4. Sinaia station
In the Official Station building, namely: Power unit room, New IS relay room and Computer
room, and in the passenger building, namely: Office room, Station master office and
Dispatcher office, new static units (steel radiators) were provided. These radiators shall be
connected to the existing columns.
The type of each radiator is written on the relevant plan.
The thermal source consists in the existing thermal station in operation situated in the building of
Sinaia Official Station.
After the completion of the heating installation, it has to be tested, primed and oil painted
complying with the norms in force.
Ventilation installation
The power unit room needs ventilation installation. When the power unit operates, the heat engine
and the generator unit are heated and part of the heat is released in the room. The fan of the heat
engine evacuates the hot air outside through a sheet piping. The compensation of the evacuated
air as well as the fresh air required for the combustion is introduced into the room by an axial fan
mounted to the wall.
TERMO-TEHNOLOGICAL INSTALLATIONS CNCF 22.01.2015 Mtro Rev 0
Pag. 9/13
TECHNICAL DESCRIPTION
Air-conditioning installations
SPLIT air conditioning system was provided in the rooms for the railway traffic control installations
and afferent staff. The powers of the devices were settled by calculating the heat input from the
outside during the summer season as well as the heat release of the afferent device, from artificial
lighting, as well as from the persons working in the room.
The dispatcher room is provided with two air conditioning installations, with heating/ cooling modes
(one in operation and one for backup). Two air conditioning installations (one in operation and one
for backup) are provided in the room where the UPS and the computers cubicles are to be
mounted. One air conditioning installation with heating/ cooling mode was provided in the Station
master office. The (indoor + outdoor) installations have to be mounted by the supplier.
5.5. Buteni station
The IS building was provided with new heating installation with static units (steel radiators).
The type of each radiator is written on the relevant plan.
The thermal source is the KESTON 80/60 0C hot water wall-mounted gas fuel boiler placed at the
ground floor of the C.T. room.
The hot water distribution (supply) network is placed on the ground floor ceiling and the return pipe
is laid at the ground floor level.
After the completion of the heating installation, it has to be tested, primed and oil painted
complying with the norms in force.
The burnt gas resulted from the hot water boiler will be evacuated through a PVC pipe.
The distance between the burnt gas evacuation pipe and the air inlet pipe for combustion will be
two meters (vertically).
The thermal energy required for heating is 38.298 W (32.936 kcal/h).
Ventilation installation
The power unit room needs ventilation installation. When the power unit operates, the heat engine
and the generator unit are heated and part of the heat is released in the room. The fresh air is
introduced into the room through an axial fan mounted to the wall. The fan of the heat engine
evacuates the hot air to the outside by a sheet piping.
Air-conditioning installations
SPLIT air conditioning system was provided in the rooms for the railway traffic control installations
and afferent staff. The powers of the devices were settled by calculating the heat input from the
outside during the summer season as well as the heat release of the afferent device, from artificial
lighting, as well as from the persons working in the room.
The dispatcher room is provided with two air conditioning installations, with heating/ cooling modes
(one in operation and one for backup). Two air conditioning installations (one in operation and one
for backup) are provided in the room where the UPS and the computers cubicles are to be
mounted. The (indoor + outdoor) installations have to be mounted by the supplier.
Indoor heating installations have been provided for the new WC using steel radiators.
The thermal energy required for heating is 17.441 W (15.000 kcal/h).
TERMO-TEHNOLOGICAL INSTALLATIONS CNCF 22.01.2015 Mtro Rev 0
Pag. 10/13
TECHNICAL DESCRIPTION
The heat carrier, 80/60 gr.C hot water is supplied by a gas operated wall boiler which will supply
the domestic hot water as well.
The boiler is of modern type without chimney; 21.500 kCal/h, mounted in a separate room or in the
tickets sellers cabin.
The WC rooms are to be aerated by the provided windows and the disabled persons cabin shall be
ventilated using special provided fan.
5.6. Azuga station
The existing installation was modified and completed within this project depending on the new IS
room arrangements and the standards in force. The heat carrier is supplied by the thermal station
situated at the ground floor of the building.
A part of the demounted units and cocks were remounted to other positions as required by the
calculus of the heat losses according to SR 1907/1 and 2 1997.
It is necessary to demount five units of which four are to be remounted. The remaining unit is
placed at the beneficiarys disposal to be further used to other indoor heating works.
Four new heating units of the same type as the existing ones will be additionally mounted.
The thermal energy required for heating is 66.112 W (56.856 kcal/h).
Ventilation installation
The power unit is in a separate room, independent from the station building and needs ventilation
installation. When the power unit operates, the heat engine and the generator unit are heated and
part of the heat is released in the room. The fan of the heat engine evacuates the hot air to the
outside by a sheet piping. The compensation of the evacuated air as well as the fresh air required
for the combustion is introduced into the room by an axial fan mounted to the wall. During the cold
season, the room is heated by electric radiators.
Air-conditioning installations
SPLIT air conditioning system was provided in the rooms for the railway traffic control installations
and afferent staff. The powers of the devices were settled by calculating the heat input from the
outside during the summer season as well as the heat release of the afferent device, from artificial
lighting, as well as from the persons working in the room.
The dispatcher room is provided with two air conditioning installations, with heating/ cooling modes
(one in operation and one for backup). Two air conditioning installations (one in operation and one
for backup) are provided in the room where the UPS and the computers cubicles are to be
mounted. In the station master office, one air conditioning installation was mounted. The (indoor +
outdoor) installations have to be mounted by the supplier.
Indoor heating installations have been provided for the new WC using steel radiators.
The thermal energy required for heating is 17.441 W (15.000 kcal/h).
The heat carrier, 80/60 gr.C hot water is supplied by a gas operated wall boiler which will supply
the domestic hot water as well.
The boiler is of modern type without chimney; 21.500 kCal/h, mounted in a separate room or in the
tickets sellers cabin.
The WC rooms are to be aerated by the provided windows and the disabled persons cabin shall be
ventilated using special provided fan.
TERMO-TEHNOLOGICAL INSTALLATIONS CNCF 22.01.2015 Mtro Rev 0
Pag. 11/13
TECHNICAL DESCRIPTION
Air-conditioning installations
SPLIT air conditioning system was provided in the rooms for the railway traffic control installations
and afferent staff. The powers of the devices were settled by calculating the heat input from the
outside during the summer season as well as the heat release of the afferent device.
Three air conditioning installation with heating/cooling mode (two in operation and one for backup)
were provided in the control block building. One air conditioning installation was mounted in the
battery and rectifier room.
6.
7.
WORKS
The provided thermal ventilation works are performed only inside the buildings or in the close
vicinity and do not require stopping the railway traffic.
All materials resulted from demounting the existing installations will be stored in special rooms until
the contractor will transport them in the places indicated by the beneficiary.
8.
Pag. 12/13
TECHNICAL DESCRIPTION
The works quality will be supervised complying with the specific sheet Supervision Schedule for
Works Quality annexed to the project. The contractor should also observe the Law no. 10 /
18.01.1995, referring to the quality and the Performance Guide for Installations (approval
M.L.P.A.T. - C.T.S. no. 18 / 18.02.1996).
The works acceptance will be made complying with:
-
9.
H.G. 273 / 14.06.1994 Acceptance regulation for the construction works and afferent
installations
I 13 - 2002 - Norm for designing and construction of the heating installations, chap. 20
I. 5 - 1998 - Norm for designing and construction of the ventilation and air-conditioning
installations
The contractor should observe the indications in paragraph 1.8. of the Specifications
corresponding to the present project.
10. ENVIRONMENT PROTECTION
The modernization works for the thermo-technological installations are carried out using
environmentally friendly materials.
The materials resulted after taking out of use the existing constructions (installations) are to be
managed according to the specialty documentation Specific environment protection works,
component part of this project
eng. D. Caracaleanu
M.Q. EXPERT
eng. A. M. Blaga
TECHNICAL DESCRIPTION
TECHNICL EXPERT
eng. D. Caracaleanu
HEAD OF TEAM
eng. R. Minea
DRAWN UP
eng. C. Radu
SUPERVISOR
eng. R. Minea
Pag. 13/13