You are on page 1of 4

electrical-engineering-portal.

com

http://electrical-engineering-portal.com/transformer-protection-abstract-from-nec

Transformer Protection Abstract from NEC

Transformer protection - Aabstract from NEC (National Electric Code)

NEC, Code 450.4


Calculate overcurrent Protection on the Primary
According to NEC 450.4, each transformer 600 volts, nominal, or less shall be protected by an individual
overcurrent device installed in series with each ungrounded input conductor.
Such overcurrent device shall be rated or set at not more than 125% of the rated full-load input current of the auto
transformer.
Further, according to NEC Table 450.3 (B), if the primary current of the transformer is less than 9 amps, an
overcurrent device rated or set at not more than 167% of the primary current shall be permitted. Where the primary
current is less than 2 amps, an overcurrent device rated or set at not more than 300% shall be permitted.

Example

Decide Size of circuit breaker (overcurrent protection device) is required on the primary side to protect a 75kva
440v-230v 3 transformer.
75kva x 1,000 = 75,000VA
75,000VA / (440V x 3) = 98.41 amps.
The current (amps) is more than 9 amps so use 125% rating.
123 amps x 1.25 = 112.76 amps
Use 125 amp 3-pole circuit breaker (the next highest fuse/fixed-trip circuit breaker size per NEC 240.6). The
overcurrent device on the primary side must be sized based on the transformer KVA rating and not sized based on the
secondary load to the transformer.
Top

NEC, Code 450.3B


Calculate overcurrent Protection on the Secondary
According to NEC Table 450.3 (B), where the secondary current of a transformer is 9 amps or more and 125% of this
current does not correspond to a standard rating of a fuse or circuit breaker, the next higher standard rating shall be
required. Where the secondary current is less than 9 amps, an overcurrent device rated or set at not more than 167%
of the secondary current shall be permitted.

Example
Decide size of circuit breaker (overcurrent protection device) is required on the secondary side to protect a 75kva
440v-230v 3 transformer. We have Calculate the secondary overcurrent protection based on the size of the
transformer, not the total connected load.
75kva x 1,000 = 75,000va
75,000va / (230V x 3) = 188.27 amps. (Note: 230V 3 is calculated)
The current (amps) is more than 9 amps so use 125% rating.
188.27 amps x 1.25 = 235.34 amps
Therefore: Use 300amp 3-pole circuit breaker (per NEC 240.6).
Top

NEC, Section 450-3 (a)


Transformers over 600 volts, Nominal
For primary and secondary protection with a transformer impedance of 6% or less, the primary fuse must not be
larger than 300% of primary Full Load Amps (F.L.A.) and the secondary fuse must not be larger than 250% of
secondary F.L.A.
Top

NEC, Section 450-3 (b)

Transformers over 600 volts, Nominal


For primary protection only, the primary fuse must not be larger than 125% of primary F.L.A.
For primary and secondary protection the primary feeder fuse must not be larger than 250% of primary F.L.A. if the
secondary fuse is sized at 125% of secondary F.L.A.
Top

NEC, Section 450-3 (b)


Potential (Voltage) Transformer
These shall be protected with primary fuses when installed indoors or enclosed.
Top

NEC, Section 230-95


Ground-Fault Protection of Equipment
This section show that 277/480 volt wye only connected services, 1000 amperes and larger, must have ground
fault protection in addition to conventional overcurrent protection.
The ground fault relay (or sensor) must be set to pick up ground faults which are 1200 amperes or more and actuate
the main switch or circuit breaker to disconnect all ungrounded conductors of the faulted circuit.
Top

NEC, Section 110-9


Interrupting Capacity
Any device used to protect a low voltage system should be capable of opening all fault currents up to the maximum
current available at the terminal of the device.
Many overcurrent devices, today, are used in circuits that are above their interrupting rating.
By using properly sized Current Limiting Fuses ahead of these devices, the current can usually be limited to a value
lower than the interrupting capacity of the overcurrent devices.
Top

NEC, Section 110-10


Circuit Impedance and Other Characteristics
The overcurrent protective devices, along with the total impedance, the component short-circuit withstand ratings,
and other characteristics of the circuit to be protected shall be so selected and coordinated so that the circuit
protective devices used to clear a fault will do so without the occurrence of extensive damage to the electrical
components of the circuit.
In order to do this we must select the overcurrent protective devices so that they will open fast enough to prevent

damage to the electrical components on their load side.


Originally published at Electrical Notes & Articles

You might also like