CHILIS ESP Calculation (FCU-PA-02) - GF PLAY AREA

Formula Based on ASHRAE Fundamentals Handbook & SMACNA Manuals for Fitting Coefficient

SUPPLY AIR DUCT


Duct
Section

Fitting
number

Airflow

Velocity

L
m

l/s

m/s

Friction
Loss
per m
Pa/m

1.55

1000.529

4.17

0.46

333.668

3.03

333.668
333.668

3.03
3.03

667.33
333.668
333.668
333.668
333.668

1000.529

Duct Dimension

Fitting type
W
mm

H
mm

Friction
Loss on
Straight
Duct
Pa
0.71

C
Fitting
Coeff.
Factor

Velocity
Pressure

1
1

0.00
0.42
0.41

10.46
10.46
5.54

0.50

1.03

1.03

1
1

0.50
0.52

5.54
5.54
5.54
9.85
5.54
5.54
5.54
5.54
5.54

1
1

0.00
0.42
3.10

10.46
10.46
5.54

0.50

0.96

0.51

0.50

5.54
5.54
5.54
9.85
5.54
5.54
5.54
5.54

Fitting
Qty.
Pc

Pa

IU-GF-07
DS01
1
2

Trans. SR4-1
Tee 45 SR5-13

VCD CR9-3

DS02
4

Trans. SR4-1

DS03
DS03
5

Tee 45 SR5-13

DS03
6
7

VCD CR9-3
Elbow, CR3-1

800
300
500*300/800*300
550
200
550
200
550
200
800*300/550*300
550
300
550
200
550
200
550
200
550
200

1.43
2.35
1.62
2.95

0.42

0.60

4.04
3.03
3.03
3.03
3.03

0.50
0.42

1.18
0.68

0.42

1.24

4.17

0.46

IU-GF-08
DS01
1
2

Trans. SR4-1
Tee 45 SR5-13

VCD CR9-3

DS02
4

Trans. SR4-1

DS03
DS03
5

Tee 45 SR5-13

DS03
6

VCD CR9-3

800
300
500*300/800*300
550
200
550
200
550
200
800*300/550*300
550
300
550
200
550
200
550
200
550
200

1.55

1.43
2.35
1.62
2.95

333.668

3.03

333.668
333.668

3.03
3.03

667.33
333.668
333.668
333.668
333.668

4.04
3.03
3.03
3.03
3.03

0.71

0.42

0.60

0.50
0.42

1.18
0.68

0.42

1.24

Elbow, CR3-1

IU-GF-01
1
Trans. SR4-1
DS01
2
1

Tee 45 SR5-13
Trans. SR4-1

Tee 45 SR5-13

DS02

900*300/800*300
800
300
550
200
800*300/550*300
550
200
550
200

1.88

1.59

1000.529
333.668

4.17
3.03

0.46

667.33
333.668

6.07
3.03

1.51

0.52

5.54

1
1
1

3.74
0.00
3.10
3.74

3.10

0.00
10.46
5.54
5.54
22.16
5.54

Fitting
Qty.

C
Fitting
Coeff.
Factor

0.86

2.40

FRESH AIR INLET DUCT


Duct Dimension

Duct
Section

W
mm
1000

DS05
14
15
16

Alum flat filter


Var Inlet ER3-2
Bell M CR3-10

H
mm
300

L
m
2.50

Airflow

Velocity

l/s
677

m/s
2.26

Friction
Loss
per m
Pa/m
0.14

Friction
Loss on
Straight
Duct
Pa
0.35

Pc

1
1

0.00
0.81
1.15

Velocity
Pressure
Pa
3.07
3.07
3.07
3.07
Safety Factor 15%
Use
TOTAL ESP

Friction
Loss on
Fittings
Pa

Total
Loss
Pa

0.00
4.39
2.27

0.71
4.39
2.27

2.77
0.00
5.71
0.00
0.00
5.71
0.00
2.77
2.88

2.77
0.60
6.88
1.18
0.68
5.71
1.24
2.77
2.88

0.00
4.39
17.17

0.71
4.39
17.17

2.77
0.00
5.32
0.00
0.00
2.82
0.00
2.77

2.77
0.60
6.49
1.18
0.68
2.82
1.24
2.77

2.88

2.88

0.00
0.00
17.17
20.72
0.00
17.17

0.86
0.86
17.17
23.11
2.40
17.17

Friction
Loss on
Fittings
Pa
0.00
15.00
2.48
3.53
Safety Factor 15%

TOTAL ESP

Total
Loss
Pa
0.35
15.00
2.48
3.53
21.36
3.20
24.56
25
25

CHILIS ESP Calculation (FCU-OF-04) - MZ OFFICE ROOM


Formula Based on ASHRAE Fundamentals Handbook & SMACNA Manuals for Fitting Coefficient

SUPPLY AIR DUCT


Duct
DUCT
Section SECTION
DS01

1
2
3
4
5
6

DS02

7
8
9
-

DS03

10
11
12

Friction
Loss on
Straight
Duct
Pa
2.08

ELBOW 90, CR3-1


ELBOW CR3-3
TEE, SR5-13
VCD, CR9-3
TEE, SR5-13
VCD, CR9-3

W
mm
1000
1000
400
400
450
450

H
mm
400
4000
150
150
250
250

L
m
5.25

l/s
1850

m/s
4.63

Friction
Loss
per m
Pa/m
0.40

0.40

136.9

2.28

0.36

0.14

0.40

344.66

3.06

0.38

0.15

Trans. SR5-13
(1000*400/800*400)
Tee 45. SR5-13
VCD CR9-1

800
450
450

400
250
250

0.8
0.3

1558.07
344.52

4.87
3.06

0.47
0.38

0.38
0.11

Trans. SR4-1
(800*400/700*400)
Tee 45. SR5-13
VCD CR9-1

700
400
400

400
150
150

0.80
0.30

1212
137

4.33
2.28

0.40
0.36

0.32
0.11

Duct Dimension

Fitting type

10

Airflow

Velocity

Farthest Supply GRILLE (375 x 375 )

Fitting
Qty.
Pc
1
1
1
1
1
1

C
Fitting
Coeff.
Factor

Velocity
Pressure

0.57
0.40
3.10
0.52
1.65
2.65

Pa
12.88
12.88
3.13
3.13
5.65
5.65

1
1
1

0.00
3.10
0.52

14.27
5.65
5.65

1
1
1

0.00
3.10
0.52

11.28
3.14
3.14

1
Safety Factor 10%
Use

FRESH AIR INLET DUCT


Duct
Section

Duct Dimension

Airflow

Velocity

Friction
Loss
per m

Friction
Loss on
Straight
Duct

Fitting
Qty.

C
Fitting
Coeff.
Factor

Velocity
Pressure

Duct Dimension

Duct
Section

W
mm
1000

DS05
11
12
13

Alum flat filter


Var Inlet ER3-2
Bell M CR3-10

H
mm
300

L
m
2.50

Airflow

Velocity

l/s
570.82

m/s
1.90

Friction
Loss
per m
Pa/m
0.10

Friction
Loss on
Straight
Duct
Pa
0.26

Fitting
Qty.
Pc
1
1
1

C
Fitting
Coeff.
Factor
0.00
0.81
1.15

Velocity
Pressure
Pa
2.18
2.18
2.18
2.18
Safety Factor 15%
Use
TOTAL ESP

Friction
Loss on
Fittings
Pa
7.34
5.15
9.72
1.63
9.32
14.97

Pa
9.42
5.30
9.72
1.63
9.32
14.97

0.00
17.50
2.94

0.38
17.50
2.94

0.00
9.73
1.63

0.32
9.84
1.63

1.50

1.50
84.47
8.45
92.91
95

Safety Factor 10%

Friction
Loss on
Fittings

Total
Loss

Total
Loss

Friction
Loss on
Fittings
Pa
0.00
15.00
1.77
2.51
Safety Factor 15%

TOTAL ESP

Total
Loss
Pa
0.26
15.00
1.77
2.51
19.53
2.93
22.46
23
118

CHILIS ESP Calculation HOTEL - STAIR PRESSURIZATION


Formula Based on ASHRAE Fundamentals Handbook & SMACNA Manuals for Fitting Coefficient

SUPPLY AIR DUCT


Duct
Section

Fitting
number

Fitting type

DS01

DS02

Duct Dimension

1
2
3
4

Trans. SR4-1
VCD, CR9-3
Tee SR5-13
Elbow, CR3-1

Trans. SR4-1

3
4 to 7
9

VCD CR9-3
Tee SR5-13

W
H
mm
mm
1250
600
600*600/1250*600
600
250
1250*600/600*250
1250*600 @ 90
1200

600

L
m
6.54

Airflow

Velocity

l/s
5001
5001

m/s
6.67

Friction
Loss
per m
Pa/m
0.51

Friction
Loss on
Straight
Duct
Pa
3.30

5001
5001
4.00

4586

6.37

0.47

1.89

600
250
1200*600/600*250
Farthest Supply Side Griile ( 800 x 200 )

Fitting
Qty.
Pc

C
Fitting
Coeff.
Factor

Velocity
Pressure

1
1
1
1

0.00
1.40
0.52
3.10
0.52

Pa
26.77
26.77
26.77
26.77
26.77

0.04

24.42

1
4
1

0.52
3.10

24.42
24.42

Safety Factor 15%

Use

FRESH AIR INLET DUCT


Duct Dimension

Duct
Section
DS05
10
11
12
13

Trans.ER4-1
Alum flat filter
Var Inlet ER3-2
PLENUM SR2-1
LOUVER ( 3 N0S)

W
mm
1250

933

H
mm
300

933

L
m
1.50

Airflow

Velocity

l/s
1038.72

m/s
2.77

Friction
Loss
per m
Pa/m
0.19

Friction
Loss on
Straight
Duct
Pa
0.29

Fitting
Qty.
Pc
1
1
1
3

C
Fitting
Coeff.
Factor
0.37
0.00
0.81
0.92

Velocity
Pressure
Pa
4.62
4.62
4.62
4.62
4.62

Safety Factor 10%


Use
TOTAL ESP

Friction
Loss on
Fittings
Pa
0.00
37.47
13.92
82.98
13.92

Pa
3.30
37.47
15.80
82.98
15.80

0.98

2.86

12.70
302.85
8.50

12.70
302.85
8.50
482.27
48.23

Safety Factor 15%

Total
Loss

530.50
126

Friction
Loss on
Fittings
Pa
1.71
15.00
3.74
4.25
8.00

Total
Loss
Pa
1.99
15.00
3.74
4.25
24.00
48.98

Safety Factor 10%

TOTAL ESP

4.90
53.88
54 Pa
180 Pa

CHILIS ESP Calculation (AHU-TR-01) - TREATED FRESH AIR SERVING KITCHEN AREA
Formula Based on ASHRAE Fundamentals Handbook & SMACNA Manuals for Fitting Coefficient

SUPPLY AIR DUCT


Duct
Section

Fitting
number

Fitting type

DS01

DS02

Trans. SR4-1

Wye, Symmetrical
Dovetail, SR5-13

3
4 to 7
8
9

Duct Dimension

VCD CR9-3
Elbow, CR3-1
Elbow, CR3-2

Airflow

Velocity

l/s
1038.72
1038.72

m/s
4.15

476.86

3.97

600
200
476.86
600
200
477.86
600
200
Farthest Supply Side Griile ( 800 x 200 )

3.97
3.98

W
H
mm
mm
1000
250
332*332/1000*250
600

200

L
m
11.00

48.36

Friction
Loss
per m
Pa/m
0.51

0.67

Friction
Loss on
Straight
Duct
Pa
5.58

32.37

Fitting
Qty.
Pc

C
Fitting
Coeff.
Factor

Velocity
Pressure

0.00
1.48

Pa
10.39
10.39

0.30

9.51

1
4
2
1

0.52
0.13
0.40

9.51
9.51
9.51

Safety Factor 15%

Use

FRESH AIR INLET DUCT


Duct Dimension

Duct
Section
DS05
10
11
12
13

Trans.ER4-1
Alum flat filter
Var Inlet ER3-2
PLENUM SR2-1
LOUVER ( 3 N0S)

W
mm
1250

933

H
mm
300

933

L
m
1.50

Airflow

Velocity

l/s
1038.72

m/s
2.77

Friction
Loss
per m
Pa/m
0.19

Friction
Loss on
Straight
Duct
Pa
0.29

Fitting
Qty.
Pc
1
1
1
3

C
Fitting
Coeff.
Factor
0.37
0.00
0.81
0.92

Velocity
Pressure
Pa
4.62
4.62
4.62
4.62
4.62
Safety Factor 15%

Use
TOTAL ESP, (Pa.)

Friction
Loss on
Fittings
Pa
0.00
15.38

Pa
5.58
47.75

2.85

35.22

4.94
4.94
7.61
8.50

4.94
4.94
7.61
8.50
114.53
17.18

Safety Factor 15%

Total
Loss

131.71
132

Friction
Loss on
Fittings
Pa
1.71
15.00
3.74
4.25
8.00
Safety Factor 15%

Total
Loss
Pa
1.99
15.00
3.74
4.25
24.00
48.98
7.35

TOTAL ESP, (Pa.)

56.33
56
188

CHILIS ESP Calculation (FCU-PRE-05) - MEZZ PREPARATION AREA


Formula Based on ASHRAE Fundamentals Handbook & SMACNA Manuals for Fitting Coefficient

SUPPLY AIR DUCT


Duct
Section

Fitting
number

Duct Dimension

Fitting type

DS01

W
H
mm
mm
800
250
1443*377/800*250
350
200

L
m
1.71

1
2

Trans. SR4-1
Tee 45 SR5-13

VCD CR9-3

Trans. SR5-13
Tee 45 SR5-13
VCD CR9-3

650
250
800*250/650*250
350
200
350
200

1.73

4
5
6

Trans. SR5-13

450
250
650*250/450*250

4.19

DS02

DS03

DS04
8
9
10

Symmetrical
Dovetail SR5-14
VCD CR9-3

350

200

350

200

350

200

7.78

Airflow

Velocity

l/s
676.11
676.11
169.03

m/s
3.38
2.41

169.03

2.41

507.08

3.12

177.52
177.52

2.54
2.54

338.05

3.00

169.03

2.41

Friction
Loss
per m
Pa/m
0.37

0.34

0.37

0.33

Friction
Loss on
Straight
Duct
Pa
0.63

Fitting
Qty.
Pc

C
Fitting
Coeff.
Factor

1
1

0.00
0.07
1.28

Pa
6.88
6.88
3.51

0.52

3.51

1
1
1

0.08
1.28
0.52

5.86
5.86
3.87
3.87

0.60

5.44
5.44

0.59

1.54

2.57

1
1
1
1

Farthest Supply diffuser ( 373 x 375 )

Velocity
Pressure

3.51
0.30
0.52

3.51
3.51

Safety Factor 15%


Use

FRESH AIR INLET DUCT


Duct
Section

Duct Dimension

Airflow

Velocity

Friction
Loss
per m

Friction
Loss on
Straight
Duct

Fitting
Qty.

C
Fitting
Coeff.
Factor

Velocity
Pressure

Duct
Section

W
mm
1000

DS05
11
12
13

Alum flat filter


Var Inlet ER3-2
Bell M CR3-10

H
mm
300

L
m
2.50

Airflow

Velocity

l/s
677

m/s
2.26

Friction
Loss
per m
Pa/m
0.14

Friction
Loss on
Straight
Duct
Pa
0.35

Fitting
Qty.
Pc

1
1

C
Fitting
Coeff.
Factor
0.00
0.81
1.15

Velocity
Pressure
Pa
3.07
3.07
3.07
3.07
Safety Factor 15%
Use
TOTAL ESP, (Pa)

Friction
Loss on
Fittings
Pa
0.00
0.48
4.49

Total
Loss
Pa
0.63
0.48
4.49

1.83

1.83

0.00
0.47
4.96
2.01

0.59
0.47
4.96
2.01

0.00
3.26

1.54
3.26
2.57

1.05
1.83
8.00
Safety Factor 15%

Friction
Loss on
Fittings

1.05
1.83
8.00
33.71
5.06
38.76
39

Total
Loss

Friction
Loss on
Fittings
Pa
0.00
15.00
2.48
3.53
Safety Factor 15%
TOTAL ESP, (Pa)

Total
Loss
Pa
0.35
15.00
2.48
3.53
21.36
3.20
24.56
65 Pa

CHILIS ESP Calculation (FCU-OF-04) - MZ OFFICE ROOM


Formula Based on ASHRAE Fundamentals Handbook & SMACNA Manuals for Fitting Coefficient

SUPPLY AIR DUCT


Duct
Section

Fitting
number

DS01

1
2
3

DS02

4
5
6

Trans. SR4-1
(650*250/500*250)
Tee 45. SR5-13
VCD CR9-1

DS03

7
8
9
10

Trans. SR4-1
(500*250/350*200)
Elbow, CR3-1
VCD CR9-3

C
Fitting
Coeff.
Factor

Velocity
Pressure

W
mm

H
mm

L
m

l/s

m/s

650
650
650

250
250
250

1.13

570.82

3.51

0.42

0.48

1
1
1

0.04
1.28
0.08

7.43
7.43
7.43

500
450
450

250
200
200

0.7

380.55

3.04

0.36

0.25

1
1
1

0.08
0.54
0.52

5.58
5.58
5.58

350
200
3.25
177.52
350
200
350
200
Farthest Supply diffuser (375 x 375 )

2.54

0.36

1.17

1
1
1
1

0.05
0.52
0.52

3.87
3.87
3.87

Fitting type

Trans. SR4-1
(1433*377/650*200)
Tee 45. SR5-13
D. Butterfly CR9-1

Friction
Loss on
Straight
Duct
Pa

Friction
Loss
per m
Pa/m

Duct Dimension

Airflow

Velocity

Fitting
Qty.
Pc

Pa

Safety Factor 15%


Use

FRESH AIR INLET DUCT


Duct Dimension

Duct
Section

W
mm
1000

DS05
11

Alum flat filter

H
mm
300

L
m
2.50

Airflow

Velocity

l/s
570.82

m/s
1.90

Friction
Loss
per m
Pa/m
0.10

Friction
Loss on
Straight
Duct
Pa
0.26

Fitting
Qty.
Pc
1

C
Fitting
Coeff.
Factor
0.00

Velocity
Pressure
Pa
2.18
2.18

12
13

Var Inlet ER3-2


Bell M CR3-10

1
1

0.81
1.15

2.18
2.18
Safety Factor 15%
Use
TOTAL ESP

Friction
Loss on
Fittings
Pa

Total
Loss
Pa

0.30
9.51
0.59

0.78
9.51
0.59

0.45
3.01
2.90

0.70
3.01
2.90

0.19
2.01
2.01
16.00

1.37
2.01
2.01
16.00
38.88
5.83
44.72
45

Safety Factor 15%

Friction
Loss on
Fittings
Pa
0.00
15.00

Total
Loss
Pa
0.26
15.00

1.77
2.51
Safety Factor 15%

TOTAL ESP

1.77
2.51
19.53
2.93
22.46
23
68

CHILIS ESP Calculation (FCU-KA-03A) - GF KITCHEN AREA


Formula Based on ASHRAE Fundamentals Handbook & SMACNA Manuals for Fitting Coefficient

SUPPLY AIR DUCT


Duct
Section

DS01

DS02

W
mm

H
mm

L
m

l/s

m/s

Friction
Loss
per m
Pa/m

800
850
850

200
200
200

4.30

501.42

3.13

0.40

Elbow. CR3-3
Elbow. CR3-1

Elbow. CR3-2

850

200

Tee 45 SR5-13

350

150

VCD CR9-3

350

150

8
7

WYE, SR5-14
Trans. SR5-13

450
450

200
200

10
9
11

Elbow, CR3-1
VCD CR9-3

Fitting
number

1
2
3

Duct Dimension

Fitting type

Trans. SR4-1
(1433*377/800*200)

DS03

Airflow

Velocity

167.14

1.624

Friction
Loss on
Straight
Duct
Pa

1.72

3.18

334.28

3.71

350
150
3.25
177.52
350
150
350
150
Farthest Supply diffuser (300 x 300 )

3.38

0.78

C
Fitting
Coeff.
Factor

Velocity
Pressure

1
1
1

0.05
0.57
0.27

5.91
5.91
5.91

0.27

5.91

0.73

6.10

0.52

6.10

1
1

0.30
0.04

8.30
8.30

1
2
1

0.52
0.52

6.88
6.88
6.88

Fitting
Qty.
Pc

2.53

Pa

Safety Factor 15%

Use

FRESH AIR INLET DUCT


Duct
Section

Duct Dimension
W

Airflow
L

Velocity

Friction
Loss
per m

Friction
Loss on
Straight
Duct

Fitting
Qty.

C
Fitting
Coeff.
Factor

Velocity
Pressure

mm
14

Alum flat filter

mm

l/s

m/s

Pa/m

Pa

Pc
1

0.00

Pa
#REF!
Safety Factor 15%
Use
TOTAL ESP, ( Pa)

Friction
Loss on
Fittings
Pa

Total
Loss
Pa

0.30
3.37
1.60

2.01
3.37
1.60

1.60

1.60

4.45

4.45

3.17

3.17

2.49
0.33

2.49
0.33

0.00
3.58
7.16
16.00

2.53
3.58
7.16
16.00
48.29
7.24

Safety Factor 15%

55.53
56

Friction
Loss on
Fittings

Total
Loss

Pa
15.00
Safety Factor 15%

TOTAL ESP, ( Pa)

Pa
15.00
15.00
2.25
17.25
17
73

CHILIS ESP Calculation (FCU-KA-03A) - GF KITCHEN AREA


Formula Based on ASHRAE Fundamentals Handbook & SMACNA Manuals for Fitting Coefficient

SUPPLY AIR DUCT


Duct
Section

Fitting
number

Fitting type

DS01

DS02

Duct Dimension
W
H
mm
mm
850
200
1443*377/850*200

Velocity

l/s
501.42
501.42

m/s
2.95

167.14

Friction
Loss on
Straight
Duct
Pa
0.98

Fitting
Qty.

Velocity
Pressure

0.05

3.18

0.52

6.10

334.28
177.52
177.52

3.71
3.38
3.38

1
1
1

0.30
1.03
0.52

8.30
6.88
6.88

350
150
3.25
177.52
450*200/350*150
177.52
350
150
350
150
350
150
Farthest Supply diffuser (300 x 300 )

3.38

1
2
1
1
1

1.03
0.08
0.52
0.52

6.88
3.84
3.84
3.84
3.84

Trans. SR4-1

VCD CR9-3

350

150

2
4
5

WYE SR5-14
Tee 45 SR5-13
VCD CR9-3

450
350
350

200
150
150

6
7
8
9
10

Trans. SR5-13
Mitered E.CR3-6
VCD CR9-3
Elbow, CR3-1

0.76

0.78

Pc

C
Fitting
Coeff.
Factor

Pa
5.24
5.24

DS03

L
m
2.77

Airflow

Friction
Loss
per m
Pa/m
0.35

2.53

Safety Factor 15%

Use

FRESH AIR INLET DUCT


Duct
Section
DS04

Duct Dimension
W
mm
1000

H
mm
300

L
m
2.50

Airflow

Velocity

l/s
677

m/s
2.26

Friction
Loss
per m
Pa/m
0.14

Friction
Loss on
Straight
Duct
Pa
0.35

Fitting
Qty.
Pc

C
Fitting
Coeff.
Factor

Velocity
Pressure
Pa
3.07

14
15

16

Alum flat filter


Var Inlet ER3-2
Return Ceiling
Grille(600 x 250)

1
1

0.00
0.81

3.07
3.07

0.00

3.07
Safety Factor 15%
Use
TOTAL ESP, ( Pa)

Friction
Loss on
Fittings
Pa
0.00
0.26

Total
Loss
Pa
0.98
0.26

3.17

3.17

2.49
7.09
3.58

2.49
7.09
3.58

0.00
3.95
0.61
2.00
2.00
21.00

2.53
3.95
0.61
2.00
2.00
21.00
49.65
7.45

Safety Factor 15%

57.10
57

Friction
Loss on
Fittings
Pa
0.00

Total
Loss
Pa
0.35

15.00
2.48

15.00
2.48

10.00

10.00
27.83
4.17
32.01
32
89

Safety Factor 15%

TOTAL ESP, ( Pa)

CHILIS ESP Calculation FAF-01 ( Serving Fresh Air for FCU's)


Formula Based on ASHRAE Fundamentals Handbook & SMACNA Manuals for Fitting Coefficient

SUPPLY AIR DUCT

DS-01

W
mm
900

H
mm
300

L
m
12.11

l/s
954.2

m/s
3.53

Friction
Loss
per m
Pa/m
0.32

DS-02

750

300

2.79

686.5

3.05

0.26

DS-03

450

250

1.45

418.8

3.72

DS-04

200

200

4.20

151.08

3.78

Duct
Section

Duct Dimension

Airflow

Velocity

Friction
Loss on
Straight
Duct
Pa
3.94

Fitting Type

Fitting
Qty.

1
2
3
4
5

Trans. SR4-1
ELBOW CR 3-3
TEE SR5-13
V. DAMPER CR9-4
TRANs. SR5-13

Pc
1
1
1
1
1

0.74

6
7
8

TEE SR5-13
V. DAMPER CR9-4
TRANs. SR5-13

0.54

0.79

9
10
11

1.01

4.25

FARTHEST SUPPLY OUTLET

C
Fitting
Coeff.
Factor

Velocity
Pressure

Friction
Loss on Total Loss
Fittings
Pa
Pa
0.30
4.24
0.98
0.98
5.49
5.49
3.91
3.91
0.60
0.60

0.04
0.13
0.73
0.52
0.08

Pa
7.52
7.52
7.52
7.52
7.52

1
1
1

0.73
0.52
0.04

5.60
5.60
5.60

4.09
2.91
0.22

4.09
2.91
0.22

TEE SR5-13
V. DAMPER CR9-4
TRANs. SR5-13

1
1
1

0.73
0.52
0.04

8.34
8.34
8.34

6.09
4.34
0.33

6.09
4.34
0.33

12
13
14
15

ELBOW 90, CR3-1


TEE SR5-13
V. DAMPER CR9-4
TRANs. SR5-13

1
1
1
1

0.17
0.18
0.52
0.94

8.59
8.59
8.59
8.59

1.46
1.55
4.47
8.07

1.46
1.55
4.47
8.07

16

R. PLENUM SR1-1

1.94

8.59

16.66

16.66
65.41
9.81
75.22
75

Safety Factor 15%

FRESH AIR INLET DUCT


Duct
Section
DS-05

Use

Duct Dimension
W
mm
900

H
mm
350

L
m
2.94

Airflow

Velocity

l/s
954.2

m/s
3.03

Friction
Loss
per m
Pa/m
0.21

Friction
Loss on
Straight
Duct
Pa
0.63

Fitting Type

17
18
19
20

MVD(fully open)
Transition
Plenum box
ALUM. FILTER

Fitting
Qty.
Pc
1
1
1
1

C
Fitting
Coeff.
Factor
0.52
0.34
0.55

Friction
Loss on Total Loss
Fittings
Pa
Pa
Pa
5.52
2.87
3.50
5.52
1.88
1.88
5.52
3.04
3.04
15.00 15.00
19.92
Safety Factor 15%
2.99
22.90
Use
23
TOTAL ESP
98
Velocity
Pressure

CHILIS ESP Calculation (EXF-01)


Formula Based on ASHRAE Fundamentals Handbook & SMACNA Manuals for Fitting Coefficient

SUPPLY AIR DUCT


Friction
Loss on
Fitting Type
Straight
Duct
Pa
0.77
Sym.Fan outlet
Flex. Conn.
Tee 45
Transition

C
Fitting
Coeff.
Factor

DS-01

W
mm
800

H
mm
300

L
m
2.40

l/s
826.25

m/s
3.44

Friction
Loss
per m
Pa/m
0.32

DS-02

650

250

4.60

684.61

4.21

0.59

2.72

Tee 45
Transition

1
1

0.74
0.04

10.94
10.94

8.10
0.44

10.82
0.44

DS-03

500

250

5.60

542.97

4.34

0.69

3.87

Wye fittings

0.41

11.12

4.56

8.43

DS-04

450

250

8.30

424.93

3.78

0.56

4.64

Tee 45
Transition
Elbow 90

1
1
2

0.74
0.08
0.54

8.59
8.59
8.59

6.36
0.69
9.28

11.00
0.69
9.28

DS-05

350

250

1.05

318.7

3.64

0.59

0.62

Tee 45
Transition

1
1

0.51
0.04

7.53
7.53

3.84
0.30

4.46
0.30

DS-06

250

250

2.40

165.25

2.64

0.40

0.96

Elbow
Drop plenum

1
1

0.52
0.05

3.94
3.94

2.05
0.20

3.01
0.20

15.00

15.00
81.20
12.18
93.38
94

Duct
Section

DS-07

Duct Dimension

Airflow

Velocity

Farthest Exhaust Grille (200 x 150)

Fitting
Qty.
Pc
1
1
1
1

0.55
0.00
0.90
0.56

Friction
Velocity
Loss on
Pressure
Fittings
Pa
Pa
7.60
4.18
7.60
0.00
7.60
6.84
7.60
4.26

Safety Factor 15%


Use

Total
Loss
Pa
4.95
0.00
7.61
5.03

FRESH AIR INLET DUCT


Duct
Section
DS-08

Duct Dimension
W
mm
800

H
mm
450

L
m
1.00

Airflow

Velocity

l/s
826.25

m/s
2.30

Friction
Loss
per m
Pa/m
0.11

Friction
Loss on
Fitting
Fitting Type
Straight
Qty.
Duct
Pa
Pc
0.11
MVD(fully open)
1
Transition
1
Plenum box
1

C
Fitting
Coeff.
Factor
0.52
0.34
0.25

Friction
Velocity
Loss on
Pressure
Fittings
Pa
Pa
3.17
1.65
3.17
1.08
3.17
0.79
Safety Factor 15%
Use
TOTAL ESP, ( Pa)

Total
Loss
Pa
1.76
1.08
0.79
3.63
0.54
4.17
4
98

CHILIS ESP Calculation (KHFAF-02)


Formula Based on ASHRAE Fundamentals Handbook & SMACNA Manuals for Fitting Coefficient

SUPPLY AIR DUCT


Friction
Loss on
Fitting Type
Straight
Duct
Pa
1.19
HOOD FILTER
M. ELBOW CR 3-9
S ELBOW CR3-1

DS-01

W
mm
400

H
mm
400

L
m
2.79

l/s
604.34

m/s
3.78

Friction
Loss
per m
Pa/m
0.43

DS-02

1200

250

3.86

2115.2

7.05

1.30

5.02

PLENUM
S. ELBOW CR3-1
TAPPINGS ER2-1

DS-03

550

550

10.34

2115.2

6.99

0.90

9.28

DS-04

600

600

12.53

2292.46

6.37

0.68

8.46

Duct
Section

Duct Dimension

Airflow

Velocity

Fitting
Qty.
Pc
1
1
1

C
Fitting
Coeff.
Factor

Velocity
Pressure

Friction
Loss on Total Loss
Fittings
Pa
Pa
20.00
21.19
0.94
0.94
1.80
1.80

0.00
0.11
0.21

Pa
0.00
8.59
8.59

1
1
1

0.13
1.53
0.22

29.93
29.93
29.93

3.89
45.79
6.58

8.91
45.79
6.58

S ELBOW CR3-1

0.44

29.43

25.90

35.18

Tee 45, SR 5-13


Transition, SR 5-13
Elbow 90
OFFSET, SR5-13
Transition
FAN O. SR7-15

1
1
1
1
1
1

0.00
0.73
0.44
0.22
0.04
0.23

24.41
24.41
24.41
24.41
24.41
24.41

0.00
17.82
10.74
5.37
0.98
5.61

8.46
17.82
10.74
5.37
0.98
5.61
169.38
25.41
194.78
195

Safety Factor 15%


Use

FRESH AIR INLET DUCT


Duct
Section
DS-05

Duct Dimension
W
mm
1200

H
mm
300

L
m
3.11

Airflow

Velocity

l/s
2292.46

m/s
6.37

Friction
Loss
per m
Pa/m
0.89

Friction
Loss on
Fitting Type
Straight
Duct
Pa
2.78
MVD(fully open)
Transition
Plenum box

Fitting
Qty.
Pc
1
1
1

C
Fitting
Coeff.
Factor
0.52
0.34
0.25

Friction
Loss on Total Loss
Fittings
Pa
Pa
Pa
24.41
12.69
15.47
24.41
8.30
8.30
24.41
6.10
6.10
29.87
Safety Factor 15%
4.48
34.35
Use
35
TOTAL ESP
230
Velocity
Pressure

CHILIS ESP Calculation (KHEXF-03)


Formula Based on ASHRAE Fundamentals Handbook & SMACNA Manuals for Fitting Coefficient

EXHAUST AIR DUCT


Duct
Section
DS-01

Duct Dimension
W
mm
300

H
mm
250

L
m
133.58

Airflow

Velocity

l/s
247.88

m/s
3.31

Friction
Loss
per m
Pa/m
0.54

Friction
Loss on
Fitting Type
Straight
Duct
Pa
71.79 Sym.Fan outlet
Flex. Conn.
ELB. CR3-1

Fitting
Qty.
Pc
1
2
6

C
Fitting
Coeff.
Factor
0.11
0.00
0.15

Friction
Velocity
Loss on
Pressure
Fittings
Pa
Pa
6.58
0.72
6.58
0.00
6.58
5.92
Safety Factor 15%

Use

Total
Loss
Pa
72.52
0.00
5.92
78.44
11.77
90.20
90 Pa

SEQUENCE OF OPERATION
AHU-TR-06
( BY PASS AIR FROM
PCU-O1 @ 4300 CFM,
SERVING MAKE-UP
AIRTO KITCHEN AND
MEZZ. PREP. )

SCENARIO

MODES OF
OPEARATION

PEAK HOUR
OPERATIONAL
MODE

NORMAL
COOLING MODE

OFF

FIRE MODE

OFF

ON

AHU-TR-07
SERVING MAKE-UP
TREATED FRESH AIR
FOR ALL FCU'S

FCU'S

ON

ON

ON

ON

OFF

PCU-01
KHFAF-01
(7159 -4300)
GROUND
FLOOR)
CFM)
ON

ON

OFF

OFF

OFF

OFF

OFF

KHFAF-05
MEZZANINE
FLOOR)

ON

TEXF-01
( GROUND
FLOOR)

See attached Systems


Integration and
Balancing
Configuration Sheet

ON

OFF

OFF

REMARKS

See attached Normal


Cooling Air balancing
Configuration sheet

ON

OFF

Refer to Electrical
Integration @ Fire
Alarm Automation
Wiring Diagram

AC & KITCHEN HOODS - SYSTEMS INTEGRATION AND BALANCING


Kitchen Area
KH # 1
KH # 2
KH # 3
KH # 4

KITCHEN
KTCHEN
HOOD
HOOD
Exhaust Air,
Fresh Air, FA
EA
1920
2400
1600
1600
525

AHU-TR-06
Treated Make
-up Air, FA

Positive Air
Pressure,
CFM

Negative Air
Pressure,
CFM

-444
-444

480
1600
1600
525

NORMAL COOLING
Kitchen Sub-Total Difference
PLAY Area
( Normal Cooling )

35

DINING Area
( Normal Cooling )

425

GF - Negative Air Pressure,CFM

Mezzanine Preparation Area


KH # 5
NORMAL COOLING
Mezzanine

KITCHEN
KTCHEN
HOOD
HOOD
Exhaust Air,
Fresh Air, FA
EA
376
471

OFFICE / MANAGER
( Normal Cooling )
Mezz. Floor - Negative Air Pressure, CFM

460

-444

Positive Air
Pressure,
CFM

Negative Air
Pressure,
CFM

95
-21

5
5

BUILDING SYSTEM GRAND TOTAL DIFFERENCE, (BALANCE AIR PRESSURE)

-21

ON AND BALANCING
Remarks
K. hood combined Exhaust & Fresh Air
Canopy Hood Exhaust air & make up air fron AHU
Canopy Hood Exhaust air & make up air fron AHU
Canopy Hood Exhaust air & make up air fron AHU
Refer to Normal Cooling Air Balance sheets

16

Remarks
K. hood combined Exhaust & Fresh Air
Refer to Normal Cooling Air Balance sheets

-16
0

AC SYSTEM - NORMAL COOLING AIR BALANCE TABULATION


Space Identification Supply Air. SA Return Air. RA Fresh Air, FA
Dining Area
Play Area
Kitchen Area
Office/Manager (Mezz)
Preparation Mezz.

4716
1392
2160
1194
942

4041
1207
2004
1169
841

675
185
156
25
101
1,142

Exhaust Air,
EA

Positive Air
Pressure,
CFM
425
35

Negative Air
Pressure,
CFM

250
150
600
444
20
5
122
21
1,142
465
465
Balance Air Pressure, CFM

Remarks

CHILIS ESP Calculation (FCU-PA-02) - PLAY AREA


Formula Based on ASHRAE Fundamentals Handbook & SMACNA Manuals for Fitting Coefficient

SUPPLY AIR DUCT


Friction
Loss on
Fitting Type
Straight
Duct
Pa
0.80
Filter Dirt Allow
Flex. Conn.
Sym.Fan outlet
Trans.(SR5-13)

C
Fitting
Coeff.
Factor

W
mm
850

H
mm
250

L
m
2.50

l/s
670.44

m/s
3.16

Friction
Loss
per m
Pa/m
0.32

700

250

1.60

502.83

2.87

0.29

0.46

Trans.(SR5-13)

0.04

4.97

0.20

500

250

2.25

335.22

2.68

0.29

0.64

Tee 45(SR5-13)

0.51

4.33

2.21

350

250

2.25

167.61

1.92

0.18

0.41

Tee 45(SR5-13)
B. Dam.(CR9-1)

1
1

0.51
0.52

2.21
2.21

1.13
1.15

Duct
Section

Duct Dimension

Airflow

Velocity

Farthest Supply diffuser

Fitting
Qty.
Pc
1
1
1
1

0.00
0.00
0.52
0.04

Friction
Velocity
Loss on
Pressure
Fittings
Pa
Pa
5.99
15.00
5.99
0.00
5.99
3.12
5.99
0.24

20.00
Safety Factor 10%

Use

FRESH AIR INLET DUCT


Duct
Section
1

Duct Dimension
W
mm
1000

H
mm
300

L
m
2.50

Airflow

Velocity

l/s
677

m/s
2.26

Friction
Loss
per m
Pa/m
0.14

Friction
Loss on
Fitting Type
Straight
Duct
Pa
0.35
MVD(fully open)
Transition
Plenum box

Fitting
Qty.
Pc
1
1
1

C
Fitting
Coeff.
Factor
0.52
0.54
0.45

Friction
Velocity
Loss on
Pressure
Fittings
Pa
Pa
3.07
1.59
3.07
1.66
3.07
1.38

Safety Factor 10%

Use
TOTAL ESP

Total
Loss
Pa
15.80
0.00
3.91
1.04
0.66
2.85
1.54
1.56
20.00
47.36
4.74
52.09
55

Total
Loss
Pa
1.94
1.66
1.38

4.98
0.50
5.47
6 Pa
61 Pa

CHILIS ESP Calculation (AHU-TR-01) - TREATED FRESH AIR SUPPLY (MAKE UP) @ KITCHEN AREA
Formula Based on ASHRAE Fundamentals Handbook & SMACNA Manuals for Fitting Coefficient

SUPPLY AIR DUCT

W
mm
1000

H
mm
250

L
m
11.20

l/s
953.73

m/s
3.81

Friction
Loss
per m
Pa/m
0.43

600

200

15.72

476.86

3.97

0.67

Duct
Section

Duct Dimension

Airflow

Velocity

Farthest Supply diffuser

Friction
Loss on
Fitting
Fitting Type
Straight
Qty.
Duct
Pa
Pc
4.85
Filter Dirt Allow
1
Flex. Conn.
1
Fan O.(SR7-17)
1
Sound Atten.
1
WYE(SR5-1)
1
10.52

Elbow (CR3-3)
Fire D.(CD9-6)
Elbow (CR3-3)

4
1
2

C
Fitting
Coeff.
Factor
0.00
0.00
0.53
0.00
0.34
0.52
0.19
1.38

Friction
Velocity
Loss on
Pressure
Fittings
Pa
Pa
8.76
20.00
8.76
0.00
8.76
4.64
8.76
25.00
8.76
2.98
9.51
9.51
9.51

Total Loss
Pa
24.85
0.00
4.85
25.00
7.83

19.77
1.81
26.24

30.30
10.52
10.52

20.00

20.00
133.88
13.39

Safety Factor 10%

Use

147.27
150 Pa

FRESH AIR INLET DUCT


Duct
Section
4

Duct Dimension
W
mm
1250

H
mm
300

L
m
9.50

Airflow

Velocity

l/s
2020

m/s
5.39

Friction
Loss
per m
Pa/m
0.65

Friction
Fitting
Loss on
Fitting Type
Qty.
Straight
Duct
Pa
Pc
6.14
MVD(fully open)
1
Plenum box
1

C
Fitting
Coeff.
Factor
0.52
0.20

Friction
Velocity
Loss on
Pressure
Fittings
Pa
Pa
17.47
9.08
17.47
3.49
Safety Factor 10%

Total Loss
Pa
15.23
3.49
18.72
2.81

Use

21.53
25 Pa

TOTAL ESP

175

CHILIS ESP Calculation (FCU-DN - 01A,01B,01C)


Formula Based on ASHRAE Fundamentals Handbook & SMACNA Manuals for Fitting Coefficient

SUPPLY AIR DUCT


Friction
Loss on
Fitting Type
Straight
Duct
Pa
0.24
Filter Dirt Allow
Sym.Fan outlet
SD5-9 Tran.
SD5-9 Tee Div.

C
Fitting
Coeff.
Factor

W
mm
600

H
mm
400

L
m
1.50

l/s
608

m/s
2.53

Friction
Loss
per m
Pa/m
0.16

500

350

3.50

626.06

3.58

0.37

1.30

SD5-9 Tran.
SD5-9 Tee Div.

1
1

0.14
0.41

7.70
7.70

1.08
3.16

2.38
3.16

450

450

300

3.40

417.37

3.09

0.34

1.14

SD5-9 Tran.
SD5-9 Tee Div.

1
1

0.13
2.70

5.75
5.75

0.75
15.54

1.89
15.54

380

300

300

3.40

208.68

2.32

0.25

0.85

SD5-9 Tran.
SD5-9 Tee Div.

1
1

0.13
0.13

3.24
3.24

0.42
0.42

1.27
0.42

380

15.00

15.00
69.08
6.91

Duct
Section

Duct Dimension

Airflow

Velocity

Farthest Supply Air Grille (300)

Fitting
Qty.
Pc
1
1
1
1

0.00
0.52
0.13
3.02

Friction
Velocity
Loss on
Pressure
Fittings
Pa
Pa
3.86
15.00
3.86
2.01
3.86
0.50
3.86
11.67

Safety Factor 10%

Use

Total
Loss

Equivalent
diameter

Pa
15.24
2.01
0.50
11.67

533

75.99
75 Pa

RETURN AIR DUCT


Duct
Section
1

Duct Dimension
W
mm
1200

H
mm
400

L
m
0.25

Airflow

Velocity

l/s
834.75

m/s
1.74

Friction
Loss
per m
Pa/m
0.06

Friction
Fitting
Loss on
Fitting Type
Straight
Qty.
Duct
Pa
Pc
0.02
MVD(fully open)
1
Plenum box
1
Wiremesh
1

C
Fitting
Coeff.
Factor
0.52
0.08
0.10

Friction
Velocity
Loss on
Pressure
Fittings
Pa
Pa
1.82
0.95
1.82
0.15
1.82
0.18

Use
TOTAL ESP

Total
Loss
Pa
0.96
0.15
1.11

2.22
5 Pa
80 Pa

CHILIS ESP Calculation (AHU-TR-07) TREATED SUPPLY AIR FOR ALL FCU'S
Formula Based on ASHRAE Fundamentals Handbook & SMACNA Manuals for Fitting Coefficient

SUPPLY AIR DUCT


Friction
Loss on
Fitting Type
Straight
Duct
Pa
4.37
Filter Dirt Allow
Flex. Conn.
Sym.Fan outlet
Sound Atten.
Transition

W
mm
500

H
mm
300

L
m
9.70

l/s
559.5

m/s
3.73

Friction
Loss
per m
Pa/m
0.45

300

200

1.00

153.24

2.55

0.39

0.39

Fire D.(curtain )
Wye fittings

200

200

8.25

82.63

2.07

0.34

2.78

Elbow 90
Transition
Tee 45
Elbow 90

Duct
Section

Duct Dimension

Airflow

Velocity

Farthest Supply FCU plenum

FRESH AIR INLET DUCT


Duct
Section
1

Duct Dimension
W
mm
750

H
mm
300

L
m
3.50

Airflow

Velocity

l/s
559.5

m/s
2.49

Friction
Loss
per m
Pa/m
0.18

Friction
Loss on
Fitting Type
Straight
Duct
Pa
0.64
MVD(fully open)
Transition
Plenum box

CU'S

Fitting
Qty.
Pc
1
1
1
1
1

C
Fitting
Coeff.
Factor
0.00
0.00
0.55
0.00
0.56

Friction
Velocity
Loss on
Pressure
Fittings
Pa
Pa
9.82
20.00
9.82
0.00
9.82
5.40
9.82
30.00
9.82
5.50

Total
Loss
Pa
24.37
0.00
0.00
30.00
9.87

1
1

0.19
0.17

4.54
4.54

0.86
0.77

1.26
0.77

2
1
1
1

0.19
0.04
0.16
0.15

2.30
2.30
2.30
2.30

0.88
0.09
0.37
0.35

3.65
0.09
0.37
0.35

0.55

0.55
71.28
7.13

Safety Factor 10%

Use

Fitting
Qty.
Pc
1
1
1

C
Fitting
Coeff.
Factor
0.52
0.34
0.20

Friction
Velocity
Loss on
Pressure
Fittings
Pa
Pa
3.72
1.94
3.72
1.27
3.72
0.74
Safety Factor 10%

Use
TOTAL ESP

78.41
80 Pa

Total
Loss
Pa
2.57
1.27
0.74
4.58
0.46
5.04
5 Pa
85 Pa

H/W

R/W

L/R

CHILIS ESP Calculation FAF -01


Formula Based on ASHRAE Fundamentals Handbook & SMACNA Manuals for Fitting Coefficient

SUPPLY AIR DUCT


Duct
Section

Duct Dimension

Airflow

Velocity

Friction
Loss
per m

W
mm
500

H
mm
400

L
m
2.80

l/s
907

m/s
4.54

Pa/m
0.52

450

400

29.10

907

5.04

0.67

12

Friction
Loss on
Fitting Type
Straight
Duct
Pa
1.46
VD(fully open)
Flex. Conn.
Transition
19.63

Transition
Elbow 45
Elbow90

Kitchen Hood ( aluminun catridge filter)

CHILIS ESP Calculation (KHFAF -05)


Formula Based on ASHRAE Fundamentals Handbook & SMACNA Manuals for Fitting Coefficient

SUPPLY AIR DUCT

Airflow

Velocity

W
mm
250

H
mm
200

L
m
3.00

Friction
Loss
per m

l/s
178

m/s
3.56

Pa/m
0.80

250

200

16.60

178

3.56

0.80

Duct
Section

12

Duct Dimension

Kitchen Hood ( aluminun catridge filter)

Friction
Loss on
Fitting Type
Straight
Duct
Pa
2.39
VD(fully open)
Flex. Conn.
Transition
13.21

Transition
Elbow90

Fitting
Qty.
Pc
1
1
1
1
2
5
1

Fitting
Qty.
Pc
1
1
1
1
5
1

C
Fitting
Coeff.
Factor

Friction
Velocity
Loss on
Pressure
Fittings

Total
Loss

0.52
0.00
0.32

Pa
14.09
14.09
14.09

Pa
7.33
0.00
4.51

Pa
8.79
0.00
5.97

0.32
0.26
0.52

15.29
15.29
15.29

4.89
7.95
39.74
25.00

Safety Factor 10%

24.52
7.95
39.74
25.00
111.97
11.20

Use

123.17
125 Pa

C
Fitting
Coeff.
Factor

Friction
Velocity
Loss on
Pressure
Fittings

H/W

R/W

H/W

R/W

Total
Loss

0.52
0.00
0.22

Pa
7.62
7.62
7.62

Pa
3.96
0.00
1.68

Pa
6.35
0.00
4.06

0.32
0.52

7.63
7.63

2.44
19.84
25.00

Safety Factor 10%

15.65
19.84
25.00
70.89
7.09

Use

77.98
80

L/R

L/R

VENTILATION (FRESH AIR) RATE PROCEDURE


Space Type

Space total
area (ft)

Occupant
Density

Play Area

Playing ground

615

Dining Area
Kitchen Area
Office Mezzanine
Manager Office Mezz.
Preparation Mezz.

Serving food
Cooking food
office
office
Serving food

675
867
227
110
562

90
9
3
2
6

Space Identification

Rate
(cfm/person)

7.5
5
5

0.3

Zone air
Distribution
Effectiveness
1

0.18
0.18
0.06
0.06
0.18

1
1
1
1
1

Rate
(cfm/ft)

Class of Air
1
2
3
1
1
3
TOTAL

VENTILATION (EXHAUST AIR) RATE PROCEDURE


Space Identification
Play Area
Dining Area
Kitchen Area
Office Mezzanine
Manager Office Mezz.
Preparation Mezz.

Space Type
Playing ground
Serving food
Cooking food
office
office
Serving food

Computed
Space total
Fresh Air Flow
area (ft)
Rate, CFM
615
675
867
227
110
562

184.5
675
156.06
15
10
101.16

Basis of
Calculation

0.80 * 184.5
(70 * 3) + (40)
867 * 0.70
0.80 * 15
0.80 * 10
101.16 * 1.20
TOTAL

Exhaust Flow Exhaust Rate


Rate, CFM
(cfm/ft)
150
250
600
10
10
122
1142

0.70

Remarks
80% of computed fresh air
Table 6-4 - public toilet
Table 6-4 - kitchen-commercial
80% of computed fresh air
80% of computed fresh air
120% of computed fresh air

URE
Air Flow Rate,
CFM
184.5
675
156.06
15
10
101.16
1,142

REMARKS, Reference
ANSI/ASHRAE STD 62.1-2007
615 ft/1 * 0.3 cfm/ft
Actual occupant density,
person * 7.5 cfm /person
867 ft/1 * 0.18 cfm/ft
3 person * 5 cfm /person
2 person * 5 cfm /person
562 ft/1 * 0.18 cfm/ft

DURE
Remarks

80% of computed fresh air


Table 6-4 - public toilet
ANSI/ASHRAE STD 62.1-2007
ble 6-4 - kitchen-commercial ANSI/ASHRAE STD 62.1-2007