You are on page 1of 36

STEEL STRUCTURES FOR TALL BUILDINGS

TALL BUILDINGS

Depending on the place where the building is located and also on its height, the
action of the wind can be more or less severe than the seismic action. As a result,
one of the three requirements:

resistance;

rigidity;

ductility;

becomes more important to satisfy.


In situations where the action of the wind is more severe, the rigidity requirement is
more important, because the response of the structure must remain in the elastic
range. On the other hand, in situations where the seismic action is more severe, the
ductility requirement is more important, to be able to dissipate the energy.
Specific requirements are:

structural requirements;

technological and functional requirements.

1.1.1. Steel structural systems

The structure of a building usually consists of a set of plane frames, to ensure


spatial behaviour. Basically, there are three types of plane frames (Fig. 1.1). In all
these three cases, the beam-column connection must be rigid.

MRF

EBF

CBF

STEEL STRUCTURES FOR TALL BUILDINGS

MRF

CBF

EBF

MRF moment resisting frame


CBF concentrically braced frame
EBF eccentrically braced frame
Fig. 1.1. Types of plane frames

The eccentrically braced frames (EBF) were created by Egor Paul Popov
(1977) at the University of California, Berkeley (died April 19, 2001). A comparison of
the main features of these three systems is presented in table 1.1.
Table 1.1. Characteristics of structural systems plans
MRF

CBF

EBF

good

good

good

Rigidity

low

very good

good

Ductility

very good

low

good

Resistance

Commentaries on the loading state and on the energy dissipation.


The most recent structural solutions try to better control the response of the
structure. They can be classified as:

passive
o base isolation
o dampers
o tuned mass dampers
o buckling-restrained braced frames
o the use of low yield steel
2

STEEL STRUCTURES FOR TALL BUILDINGS

active

Commentaries separation of functions:

resistance moment frames;

rigidity braces;

ductility dampers.
Depending on the height of the building and mainly on the ratio between the

height H and the dimension in plan B, the most commonly used structural solutions
for resisting horizontal forces are the following ones:

moment frames (Fig. 1.2a);

frames with vertical bracings (Fig. 1.2b);

frames with vertical bracings and outriggers (Fig. 1.2c);

structures with beam-walls (Fig. 1.2d);

tubular structures (Fig. 1.2e);

multi-tube and mega-frame structures (Fig. 1.2f);

tube in tube

bundled tubes.
H
8
B
H
6
B
H
6
B

H
4
B
H
4
B
H
2
B

(a)

(b)

(c)

(d)

Fig. 1.2. Types of structural systems

(e)

(f)

STEEL STRUCTURES FOR TALL BUILDINGS

The location of seismic systems in a building depends on structural,


architectural, technological and functional requirements. Generally, codes (EN 19981, P100-1:2013) classify seismic structural systems in:

moment frames (Fig. 6.1 EN 1998-1);

Fig. 1.3. Moment resisting frames

frames with concentric bracings (Fig. 6.2 EN 1998-1) (Fig. 6.3 EN 1998-1);

Fig. 1.4. Frames with concentric bracings

frames with eccentric bracings (Fig. 6.4 EN 1998-1);

STEEL STRUCTURES FOR TALL BUILDINGS

Fig. 1.5. Frames with eccentric bracings

inverted pendulum structures (Fig. 6.5 EN 1998-1);

Fig. 1.6. Inverted pendulum structures

structures with concrete cores and concrete walls (Fig. 6.6 EN 1998-1);

Fig. 1.7. Structures with concrete cores and concrete walls

moment frames combined with concentric braces (Fig. 6.7 EN 1998-1);

STEEL STRUCTURES FOR TALL BUILDINGS

Fig. 1.8. Moment resisting frame combined with concentric bracing

moment frames combined with infills (Fig. 6.8 EN 1998-1);

Fig. 1.9. Moment resisting frame combined with infills

1.2. SEISMIC DESIGN PRINCIPLES OF METAL STRUCTURES

1.2.1. The capacity design concept

The modern seismic design approach is based on the idea that much of the
energy induced by the earthquake in the structure is dissipated by means of plastic
mechanisms; generally, it is not efficient to resist this action only in the elastic range,
unless under very special circumstances, such as the case of nuclear power plants
etc. Current trends are to better control energy dissipation, meaning the behaviour of
the structure in the post-elastic range. The basic idea is to use a plastic mechanism
which is chosen, directed and controlled by the engineer, and to ensure conditions
so that all other elements remain essentially in the elastic range until the moment
when the mechanism has exhausted its capacity of dissipation. Subsequently to this
principle, plastic deformations are accepted only in selected areas generally located
6

STEEL STRUCTURES FOR TALL BUILDINGS


in beams in a neighbouring area to the joint and, in the end, at the base of the
columns or at their top end.
The designer choses the potentially plastic zones on the structure (their type
and location) and the rest of the structure must remain basically in the elastic range
while the chosen plastic zones keep on plastifying. This means that the rest of the
structure must be able to resist, basically in the elastic range, the loads (efforts)
generated by the action that fully plastifyies all the chosen potentially plastic zones.
Following this, all the parts of the structure that are outside of the potentially plastic
zones must resist efforts associated to the capacity of the chosen plastic
mechanism, considering not the minimum values of the plastic resistance of these
zones but probable (expected) ones. This is basically the meaning of the capacity
design concept.
Remark: A higher resistance of the potentially plastic zones can either put in danger
the non-dissipative zones of the structures (as failures may occur there) or lead to
oversize of the entire structure.

1.2.2. Basic concepts

Ductility
Generally, ductility is the ability of energy dissipation in the plastic range. It is
expressed as ratio between ultimate displacement and the value of the same
displacement corresponding to the yielding limit.
Plastic hinge
It is a concept that defines a cross-section of the structural member in which
the ability to resist an increasing bending moment has been exhausted. Plastic
hinges do not exist in reality; plastic deformations develop over a certain length of
the element, so they are not located in one section, as the model presumes.
Class of the cross-section
Depending on the occurrence of local buckling of the components of a crosssection that is subjected to bending moment, four classes of cross-sections are
defined in EN 1993-1-1. Depending on the class of the cross-section, the loading
state of the structural member can be determined using elastic or plastic analysis

STEEL STRUCTURES FOR TALL BUILDINGS


and the resistance of the cross-section can be expressed in the plastic, elastic or
critical range (Fig. 1.10).
max < fy

max = fy

max = fy

max = fy

class 4
class 3
class 2
class 1

Fig. 1.10. Evolution of the stress state in a cross-section subject to bending moment

1.2.3. The main steps of seismic design of the structure

The capacity design concept tries to better manage the behaviour of the
structure in the elastic and in the plastic range till failure. The following steps are
recommended to be followed to achieve a good behaviour of the structure:
1. Chose the structural system and the model of the structure.
2. Estimate the loads in each loading case.
3. Estimate the masses. The masses are calculated corresponding to the loading
situation that contains the seismic action. They are therefore associated to the
gravitational loads that are defined by long-term factors applied to the nominal
values of the loads.
4. Pre-size structure by choosing the position of the plastic zones, implicitly the
plastic mechanism of energy dissipation. Cross-sections are proposed for all
structural members.
5. Performing a modal analysis of the structure, for determining the eigenperiods
and the distribution of equivalent static forces corresponding to each eigenmode.
6. Performing a static analysis of the structure. In this step, a number of
eigenmodes are taken into account to estimate the resulting seismic forces.

STEEL STRUCTURES FOR TALL BUILDINGS


7. Chose the cross-sections of the members in plastic zones to resist the efforts
generated by the action of the seismic base shear (Fb).
8. Estimate the plastic reserve () of the chosen plastic mechanism.
9. This reserve is taken into account by amplifying the seismic force by the factor
(while the gravitational loads remain unchanged). Do another static analysis
for this amplified seismic force (
Fb). The rest of the structure (except the
selected plastic areas) must remain essentially in the elastic range while the
chosen plastic mechanism dissipates energy, so all the other members will be
sized to resist the efforts generated by this amplified seismic force. This
amplified seismic force (
Fb) can also be determined using a virtual work
equation:
Lext = Lint

(1.1)

where:
Lext is produced by seismic force;
Lint is produced by efforts in the dissipative elements.
In the absence of a more rigorous analysis, some codes recommend penalising
values. For instance, the American code ANSI/AISC 341-10 and the Romanian
code P100-1:2013 recommend the following values for the global overstrength
factor of the structure (Tab. 1.2).
Table 1.2. Values for the global overstrength factor of the structure ([3] Tab. F.1)
Structural system

a) Moment frames

3,0

b) Concentrically braced frames

2,0

c) Eccentrically braced frames

2,5

d) Inverted pendulum structures

2,0

e) Dual frames
- moment frames + concentrically braced frames

2,0

- moment frames + eccentrically braced frames

2,5

f) Frames with buckling-restrained braces

3,0

STEEL STRUCTURES FOR TALL BUILDINGS


These recommendations apply in the situation where the structure complies with
the rules of conformations given in the codes ANSI/AISC 341-10 or P100-1:2013
for a good post-elastic behaviour of the structure.
10. Chose the cross-sections of the members outside the plastic zones to resist
the efforts generated by the action of the amplified seismic force (
Fb).
11. Return to step 5 and perform a new static analysis for the new cross-sections
of the structural members, taking into account the seismic base shear (Fb) and,
respectively, the amplified seismic force (
Fb) and follow steps 5-10 to tune up
the structure.
12. Perform a push-over analysis (post-elastic analysis) to verify that the chosen
plastic mechanism is developed and the required ductility can be obtained.
13. Improve the structure based on the results of the push-over analysis (by
changing the cross-sections of some members) and follow steps 5-12 to tune up
the structure for as many times as it is necessary.
14. Perform a time-history analysis (dynamic analysis) using accelerograms,
which can be either real or fabricated. It can be done in the elastic or in the
plastic range.
15. Improve the structure based on the results of the time-history analysis (by
changing the cross-sections of some members) and follow steps 5-14 to tune up
the structure for as many times as it is necessary.

1.3. ESSENTIAL SEISMIC REQUIREMENTS FOR THE METAL STRUCTURES


FOR TALL BUILDINGS

1.3.1. Classifications

Present day codes distinguish between the types of structures, depending on


their plastic behaviour. Basically, there are two types of structural concepts:

low dissipative structural behaviour;

dissipative structural behaviour.

These two types of behaviour are well distinguished in the European standard EN
1998-1 [10], in the Romanian code P100-1:2013 [11] and in the American code

10

STEEL STRUCTURES FOR TALL BUILDINGS


ANSI/AISC 341-10 [12]. Subsequently, three types of structures, depending on their
post-elastic behaviour, can be distinguished in the three standards [10], [11]:

DCL (limited ductility class) [10], [11] capable to undergo minimum plastic
deformations under the effects of the seismic action; EN 1998-1 [10] accepts
them in the case of buildings without isolation of the base, only in regions with
low seismicity; in ANSI/AISC 341-10, they are called ordinary structures (OMF,
OCBF, OEBF etc.);

DCM (medium ductility class) [10], [11] capable to undergo limited plastic
deformations under the effects of the seismic action; in ANSI/AISC 341-10, they
are called intermediate structures (IMF, ICBF, IEBF etc.);

DCH (high ductility class) [10], [11] capable to undergo significant plastic
deformations under the effects of the seismic action; in ANSI/AISC 341-10, they
are called special structures (SMF, SCBF, SEBF etc.).

Table 1.3. Design concepts, structural ductility classes and upper limit reference
values of the behaviour factors ([3] Tab. 6.1)
Design concept

Structural ductility

Range of the reference

class

values of the behaviour


factor q

Concept a)
Low dissipative structural
behaviour

1,5 - 2

DCL (Low)

Concept b)
Dissipative structural behaviour

DCM (Medium)

DCH (High)

also limited by the


values of Table 1.4
only limited by the
values of Table 1.4

Table 1.4. Upper limit of reference values of behaviour factors for systems regular in
elevation ([3] Tab. 6.2)
Structural type

Ductility Class

a) Moment resisting frames

11

DCM

DCH

4,0

5u/1

STEEL STRUCTURES FOR TALL BUILDINGS


b) Frame with concentric bracings
- Diagonal bracings

4,0

4,0

- V-bracings

2,0

2,5

c) Frame with eccentric bracings

4,0

5u/1

d) Inverted pendulum

2,0

2u/1

e) Structures with concrete cores or concrete walls


f) Moment resisting frame with concentric bracing

See R.C. section


4,0

4u/1

2,0

2,0

g) Moment resisting frames with infills


- Unconnected concrete or masonry infills, in contact
with the frame
- Connected reinforced concrete infills

See composite section

- Infills isolated from moment frame (see moment


frames)

4,0

5u/1

1.3.2. Some structural requirements for seismic resistant steel structures

1. The structure will follow the principle strong column weak beam to avoid
the appearance of floor mechanisms.
2. K bracings where the intersection of the diagonals is located on the column are
not accepted in seismic resistant structures (Fig. 1.11) because of the
unbalanced horizontal force that acts on the column after buckling of the
compressed diagonal. In the case of V (or inverted V) bracings, the beam
containing the intersection point of the diagonals must be continuous in that point
and sized to resist gravitational loads neglecting the presence of the braces.

Fig. 1.11. Recommendations for the bracing system

3. All structural members and their connections must remain essentially in the
elastic range under the action of the seismic base shear force (Fb).

12

STEEL STRUCTURES FOR TALL BUILDINGS


4. For earthquakes that can generate forces superior to the seismic base shear
(Fb), the structure must be able to dissipate energy using a plastic mechanism.
The mechanism must be chosen, managed and controlled by the designer and
plastic deformations must develop only in chosen zones. The beginning of plastic
behaviour of the structure must be done under the action of the force Fb.
5. The state of efforts and deformations induced on the structure by the maximum
ground acceleration (peak ground acceleration on the location) must be
estimated. A non-linear dynamic analysis is recommended for this purpose. In
this state the structure shall comply with the following requirements:

all structural members and their connections must be essentially in the


elastic range except the chosen plastic zones;

all lateral displacements (Fig. 1.12) must meet the "drift" requirements
given in codes;
v

Fig. 1.12. Limitation of lateral displacement ("drift")

all plastic deformations in the plastic zones must not exceed the ultimate
plastic deformation allowed for these zones (material and cross-section
limitations).

6. No other ultimate limit state (general instability, brittle fracture etc.) should be
reached before the formation of the plastic mechanism.
7. The acceptable plastic deformations are as follows:

plastic hinges in the members in bending:

at the ends of the beams, preferably not in the beam-column


connection (Fig. 1.13a), even though EN 1998-1 accepts it;
different research programs try to investigate the plastic behaviour
of these connections;
13

STEEL STRUCTURES FOR TALL BUILDINGS

at the ends of long links in eccentrically braced frames (EBF);

at the ends of intermediate links in eccentrically braced frames


(EBF); in this case the influence of the shear force on the plastic
moment resistance cannot be neglected.

at the base of the frame or at the top of the columns (Fig. 1.13b,
c) in the upper storey of multi-storey buildings after the formation of
at least 50% of the plastic hinges in the beams;

at the top and bottom of columns in single storey buildings in


which NEd in columns conform to the inequality: NEd/Npl,Rd < 0,3
(Fig. 1.13b, c); the same approach can be used for inverted
pendulum structures, provided that the earthquake resistant
structure possess more than one column in each plane;
rather not

recommended

recommended

recommended

(a)
(b)
Fig. 1.13. Recommended locations for plastic hinges

(c)

yielding of the tension diagonal in frames with concentric bracings;

shear yielding in the webs of short beams and short links.

8. The following are forbidden in potentially plastic zones:

change the cross-section of the element;

to have holes;

to support other secondary (or main) structural members.

9. Plastic deformations are not allowed in the following locations:

all along the columns (except for the locations at point 7);

in the joints (panel zones) of the structure (see the notes below);

in the anchor bolts of the columns;

in the connections of members (see the notes below).

Note 1:

More recent codes do not explicitly forbid plastic deformations in the

panel zone. EN 1998-1 and P100-1:2013 do not say anything about the panel

14

STEEL STRUCTURES FOR TALL BUILDINGS


zones. ANSI/AISC 341-10 has specific provisions concerning the (column) panel
zone (Fig. 1.14).
Note 2:

ANSI/AISC 341-10 limits the slenderness of the panel zone. Many

tests demonstrated that significant ductility can be obtained by shear yielding of


the panel zone (ANSI/AISC 341-10, page 9.1-201) but excessive panel zone
distortions can unfavourably affect the beam-to column connection. The
Japanese code also accepts yielding in the panel zone, based on the results of
tests.
Note 3:

EN 1998-1 accepts to dissipate energy in semi-rigid connections

(connections where a moment-rotation relation is given) if their behaviour is very


well controlled.

Fig. 1.14. The column panel zone in the joint of a structure

10. The cross-sections of the potentially plastic zones (class 1 cross-sections) must
allow the development of plastic deformations without local buckling or other
forms of instability. Plastic deformations shall be directed to the chose potentially
plastic zones.
Generally, codes make a connection between the chosen behaviour (ductility)
factor q and the slenderness of the cross-sections of structural members. For
instance, EN 1998-1 and P100-1:2013 require the following:

Table 1.5. Requirements on cross-sectional class of dissipative elements depending


on Ductility Class and reference behaviour factor ([3] Tab. 6.3)
Ductility class

Reference value of
behaviour factor q

15

Required crosssectional class

STEEL STRUCTURES FOR TALL BUILDINGS

DCM
DCH

1,5 < q 2

class 1, 2 or 3

2<q4

class 1 or 2

q>4

class 1

11. The joints and the connections of seismic-resistant structures should remain
essentially in the elastic range for a good plastic behaviour of the entire structure
(see notes at point 9). Local buckling of the joint is not acceptable.
12. Floor mechanisms or other partial (local) mechanisms are not accepted in multistorey buildings subjected to seismic actions.
13. The steel grades that are used must fulfil special requirements in order to provide
a good plastic behaviour of the entire structure.

1.3.3. Requirements for steel grades used for seismic-resistant structures

Because of the required good plastic properties, codes provide special


requirements for steel grades used for seismic-resistant structures. P100-1:2013, as
well as previous versions of EN 1998-1 and ANSI/AISC 341-10, contain precise
values for the most important mechanical characteristics of steel. Newer versions of
EN 1998-1 and ANSI/AISC 341-10 tend to be more relaxed, as they make reference
to other design codes. The most important requirements are the following ones:
1. Generally, codes limit the superior value of the yielding limit of steel. As a result,
the commonly used steel grades for seismic-resistant structures are: S235, S275
and S355. One of the reasons for limiting the yielding limit of steel was that one
of the causes of many brittle fractures during the Northridge earthquake (1994)
was that the bigger yielding limit resulted in increased requirements for
connection.
2. The steel grade and the welding material must have an adequate tenacity to
avoid brittle fracture. P100-1:2013 requires 27J on a Charpy specimen at the
minimum design temperature. EN 1998-1 no longer contain explicit values and it
makes reference to other codes. ANSI/AISC 341-10 is more precise in defining
the zones where special requirements apply.

16

STEEL STRUCTURES FOR TALL BUILDINGS


3. In potentially plastic zones, the actual maximum yielding strength, fymax shall not
exceed a value that must be written on plans. This limitation is expressed as
follows:
f y max 1,1 ov f y

(EN 1998-1)

(1.2)

f y max ov f y

(P100-1:2013)

(1.3)

Fye R y Fy

(ANSI/AISC 341-10)

(1.4)

Fye R t Fu

(ANSI/AISC 341-10)

(1.5)

where:
fy nominal value of the yielding limit (ex. 235N/mm2 for S235);
ov overstrength factor;

the recommended value in EN 1998-1 is 1,25;

P100-1:2013 recommends different values: 1,40 for S235; 1,30 for


S275 and 1,25 for S355. However, these values must be correlated
with the locally adopted value M0 =1,1;

RyFy

expected yield stress;

RtFu

expected tensile strength.

The values of Ry and Rt in ANSI/AISC 341-10 [4] are given in table 1.6.

Table 1.6. Ry and Rt for steel and steel reinforcement materials ([4] Tab. A3.1)
Application

Ry

Rt

- ASTM A36/A36M

1,5

1,2

- ASTM A1043/1043M Gr. 36 (250)

1,3

1,1

- ASTM A572/572M Gr. 50 (345) or 55 (380),

1,1

1,1

- ASTM A1043/A1043M Gr. 50 (345)

1,2

1,1

- ASTM A529 Gr. 50 (345)

1,2

1,2

- ASTM A529 Gr. 55 (380)

1,1

1,2

1,4

1,3

1,6

1,2

Hot-rolled structural shapes and bars:

ASTM A913/A913M Gr. 50 (345), 60 (415), or 65 (450),


ASTM A588/A588M, ASTM A992/A992M

Hollow structural sections:


- ASTM A500/A500M (Gr. B or C), ASTM A501
Pipe:
- ASTM A53/A53M

17

STEEL STRUCTURES FOR TALL BUILDINGS


Plates, Strips and Sheets:
- ASTM A36/A36M

1,3

1,2

- ASTM A1043/1043M Gr. 36 (250)

1,3

1,1

- A1011/A1011M HSLAS Gr. 55 (380)

1,1

1,1

- ASTM A572/A572M Gr. 42 (290)

1,3

1,0

- ASTM A572/A572M Gr. 50 (345), Gr. 55 (380),

1,1

1,2

1,2

1,1

1,25

1,25

ASTM A588/A588M
- ASTM A1043/1043M Gr. 50 (345)
Steel Reinforcement:
- ASTM A615, ASTM A706
4. P100-1:2013 requires:

f u f y 1,20 ;

u 20% ;

the elongation at the end of the yielding plateau must be superior to 1,5%;

EN 1998-1 and ANSI/AISC 341-10 no longer contain such explicit limits.


5. Steel must have a good weldability.
6. Bolts to be used are 8.8 and 10.9. 12.9 bolts generally have a brittle failure. For
in-plane loaded connections, the shear resistance must be superior to the
bearing resistance in order to have a ductile failure. For end-plate connections,
failure mode 1 (complete yielding of the flange) is the most ductile one.

1.3.4. Requirements for the connections of seismic resistant steel structures

Generally, codes require as basic principle the idea that joints must be able to
transfer the resistances of the elements, taking into account the possibility that the
resistance of the element is greater than its nominal value. To meet this
requirement, codes contain recommendations about conformation, calculation and
technological requirements for joints. Below are presented some of the most
important requirements:
1. The conformation of the joint detail must limit the zones where notch effects
could arise, important residual stresses could develop or where plastic
deformations could occur in the joints (Fig. 1.15).

18

STEEL STRUCTURES FOR TALL BUILDINGS


1:5

No

1:5

Yes

Fig. 1.15. Example of joint that avoids notch effects

2. In a connection with weld seams and bolts, loads shall not be shared between
these two different connecting means.
3. It is generally considered that full penetration butt welds are able to transfer the
required resistance.
4. EN 1998-1 [10] and P100-1:2013 [10] require for the resistance of joints realised
with fillet welds and bolts that:
R d 1,1 ov R fy

((6.1) EN 1998-1; (6.1) P100-1:2013)

(1.6)

where:
Rfy the plastic resistance of the connected member, calculated based on the
nominal value of the yielding limit;
ov overstrength factor;
Rd resistance required to the joint.
5. Given that welding requires more advanced technology and more skilled workers
(the quality of welding depends primarily on these requirements), the American
and European practice is to realize the shop connections by welding and the site
connections by bolts, thus avoiding welding on site. On the contrary, in Japan,
most of the joints on the site are made by welding.
6. Given that the weld introduces residual stresses and it can be a weak point in the
structure, in the joints of a structure it is generally recommended for the column
to be continuous (Fig. 1.16a). Yet there situations where, for technical reasons, it
is accepted that the beam is continuous (Fig. 1.16b). This type of detail is not
accepted in Romania.

19

STEEL STRUCTURES FOR TALL BUILDINGS

(a)

(b)

Fig. 1.16. Types of beamcolumn joints

7. It is recommended for the shear resistance of bolts to be superior to the bearing


resistance, in order to have a ductile failure of the connection. To fulfil this
requirement, EN 1998-1 [10] and P100-1:2013 [10] require for the shear
resistance to be 1,2 times superior to the bearing one.

1.4. THE BEAMS OF SEISMIC RESISTANT STEEL STRUCTURES

1.4.1. Conformation principles

The majority of codes recommend realising the beams with three zones (Fig.
1.17):

a rigid zone (r) at each end of the beam, near the beam to column joint;

a plastic zone (p), neighbour to the rigid one;

a central elastic zone (e).

20

STEEL STRUCTURES FOR TALL BUILDINGS

rp

pr

MG

ME

Fig. 1.17. Zones on a beam sized by the seismic action

Considering the notations (Fig. 1.17):


r
r
M rEd the maximum bending moment in the rigid zone ( M rEd = M Ed
,G + M Ed ,E );

M rpEd the bending moment in the cross-section between the rigid zone and the
rp
rp
plastic one ( M rpEd = M Ed
,G + M Ed ,E );

M pe
Ed the bending moment in the cross-section between the plastic zone and the
pe
pe
elastic one ( M pe
Ed = M Ed ,G + M Ed ,E );

during an earthquake, the gravitational loads remain unchanged, while the effects of
the seismic action can increase.
Following this, we consider a monotonic increase of the bending moments
caused by the seismic action. Failure of the beam-column connection (cross-section
r) must be avoided ( M rEd < M rRd ). Consequently, the first cross-section fully plastic is
(rp) (on the right hand side in figure 1.17) ( Mrp = Mplrp ). If the bending moment caused

by the seismic action increases, the plastic deformations develop towards crosssection (pe). In the state when the bending moment in cross-section (pe) is equal to
the plastic resistance of the cross-section ( Mpe = Mplpe ) we have plastic stress
distribution on the entire cross-section all along zone (p), where we accepted the
development of a plastic hinge. In this loading state, cross-section (r) must still

21

STEEL STRUCTURES FOR TALL BUILDINGS


remain basically in the elastic range ( M rEd < M rRd ). If the bending moment caused by
the seismic action continues to increase, rotations occur in the already formed
plastic hinge and, at a certain moment, a second plastic hinge will begin to form.
This second plastic hinge must not be located in zone (r) (on the left hand side in
figure 1.17) but in zone (p). Following a similar scenario, the entire cross-section
goes plastic all along zone (p) (on the left hand side in figure 1.17). If the beam is
properly sized, at this stage, zones (r) must be still basically in the elastic range and
zone (e) must be in the elastic range.
To get this behaviour, the cross-section in the plastic zone (p) must be class
1, the cross-section in the rigid zone (r) may be class 1 or 2 (preferably class 1) and
the cross-section in the elastic zone (e) may be class 1, 2 or 3 (preferably class 1 or
2). The length of the rigid zone (r) (Fig. 1.17) is also very important. Basically, it must
not be too long, to reduce the increase of the bending moment between the plastic
hinge and the beam to column connection. If the plastic hinge is too much away
from the column face, in order to avoid the weak column, the requirements for the
column cross-section increase. On the other hand, the rigid zone must be sufficiently
long to allow a good stress distribution in the flange between the plastic hinge crosssection and the beam to column connection.
Basically, plastic deformations in the structure must begin to develop under
the action of the base shear force (Fb) (when the equivalent seismic force reaches
this value), so, the first plastic hinge must form in a structure in a beam once that the
value of the seismic force overcomes the base shear force (Fb).

1.4.2. Types of practical solutions for beams

There are basically two types of practical solutions to direct the formation of
the plastic hinge in the beam at a certain distance from the beam to column
connection:

strengthening the rigid zone (Fig. 1.18) relative to the rest of the beam; the

solution in figure 1.18a shows an additional risk of lamellar tearing of the material
in the flange of the column, because of the welding seams;

22

STEEL STRUCTURES FOR TALL BUILDINGS

(a)

(b)

Fig. 1.18. Examples of solutions for strengthening the rigid zone (FEMA 351 [4] Fig.

2.3, FEMA 350 [4] Fig. 3.23)

reducing the beam cross-section (Fig. 1.19) in zone (p); this solution is also

known as RBS (reduced beam section) or dog bone.


RBS solution was patented in the United States by the manufacturer ARBED of
Luxembourg in 1992. After the Northridge earthquake (1994) they gave up their
intellectual property rights, which facilitated the evolution of this solution. The detail
in figure 1.19a reduces the stress concentrations. Tests showed that plastic
deformations develop all along the plastic zone. The detail in figure 1.19c tries to
follow the bending moment diagram and to generate a uniform yielding state along
the plastic zone. Tests showed that, after some plastic deformations, brittle fractures
may occur in the reduced sections in figures 1.19b and 1.19c because of the corner
areas, which are load concentrators.

(b)

(c)
(a)
Fig. 1.19. Examples of solutions for the reduced beam section

23

STEEL STRUCTURES FOR TALL BUILDINGS

1.4.3. Example of RBS design

Generally, there are two types of requirements of major importance in the


choice of the cross-sections of beams (and other structural members). They do not
refer to the reduced beam section zone (RBS) but to the beam cross-section:

the cross-section of the beam must be able to resist the bending moment
generated by the load combination containing amplified seismic forces;
r
r
M rEd = M Ed
,G + T M Ed ,E

((6.6) P100-1:2013)

(1.7)

r
r
M rEd = M Ed
,G + 1,1 ov M Ed ,E

((6.6) EN 1998-1)

(1.8)

where:
M rEd the total bending moment in the beam to column connection;
r
M Ed
,G the bending moment generated by gravitational loads;
r
M Ed
,E the bending moment generated by seismic loads;

T the value of the overstrength of the structural system (see Tab. 1.2);

the minimum value of the plastic reserve of all plastic hinge cross-sections;

ov the overstrength factor (of the material in the plastic hinge zones);

the structure must fulfil the drift requirement (Fig. 1.12);


v
lim
h

(1.9)

the displacement v in relation (1.9) is calculated without reducing the forces by


the behaviour factor q.
Generally, the drift requirement (1.9) is more difficult to be fulfilled for moment
frames. The reduction of the cross-section in the plastic hinge zone reduces the
rigidity of the frame. Researches carried out by Grubbs at the University of Texas
[16] showed that a 50% reduction of the flanges in the RBS zone reduces the rigidity
of the frame by 6 7%, while a 40% reduction of the flanges in the RBS zone
reduces it by 4 5%.
In a first iteration, the cross-sections of members (beams, columns, braces
etc.) are chosen, based on the drift requirements. Class 1 and 2 cross-sections can
be sized either in the elastic or in the plastic range.

24

STEEL STRUCTURES FOR TALL BUILDINGS


The main steps of design are the following ones:

1.4.3.1. Estimation of the position of the plastic hinge

If the loads generated by gravitational loads are less than 30% of the
resistance of the cross-section of the beam, the American code FEMA 350 [17]
recommends the following relations.
initial
form

deformed frame

plastic
hinges

L1
L
Fig. 1.20. Moment frame with plastic hinges on the beams (FEMA 350 [4] Fig. 3.23)

If gravitational loads generate more than 30% of the loads in the beam crosssection, a plastic analysis of the structure is necessary to determine the position of
the plastic hinges. FEMA 350 [17] recommends values for the distance sh (Fig. 1.21)
for different types of details of beam to column connection. Generally, this value is
around:
sh =

hc hb
+
2
2

(1.10)

where:
hc the height of the cross-section of the column ;
hb the height of the cross-section of the beam.

25

STEEL STRUCTURES FOR TALL BUILDINGS


sh
plastic hinge

hb

hc

L1
L
Fig. 1.21. Location of the plastic hinges

Depending on the type of detail, the distance sh may increase up to:


sh =

hc
+ hb
2

(1.11)

Generally, the length of the plastic hinge in steel structures beams is about half of
the beam height (hb/2) [17]. FEMA 350 [17] recommends the following values for the
dimensions in figure 1.22:

R=

4 c 2 + b2
8c

bf
c

Fig. 1.22. Geometry of RBS (reduced beam section)

a = (0,50...0,75) b f

(1.12)

b = (0,65...0,85) h b

(1.13)

1.4.3.2. Estimation of the probable value of the bending moment in the plastic hinge

26

STEEL STRUCTURES FOR TALL BUILDINGS


The aim of this sizing procedure is to limit the maximum bending moment that
may occur in the cross-section of the beam to column connection at a value inferior
to 85100% of the plastic moment resistance of the cross-section (Fig. 1.23). The
following steps need to be followed to fulfil this requirement:
1. the value of c is proposed (Fig. 1.23);

c 0,25 b f

(1.14)

2. the plastic strength modulus Wpl,RBS of the reduced section (RBS) is determined;
3. the probable value of the plastic bending moment Mplpr,RBS of the reduced crosssection (RBS) is determined (Fig. 1.23); this estimation intends to manage the
possibility for the plastic bending moment in the plastic hinge cross-section to be
bigger than the nominal value;

in the spirit of EN 1998-1 and P100-1 :2013:


Mplpr,RBS = 1,1 ov fy Wpl,RBS

(1.15)

where:
fy the nominal value of the yielding limit;
ov overstrength factor; the recommended value in EN 1998-1 is 1,25;
1,1 a safety variation of 10%;

in the American code FEMA 350 [17]:

M plpr,RBS = C pr R y Z e Fy

((3.1) FEMA 350 [17])

(1.16)

where:
Fy the nominal value of the yielding limit;
Ze the plastic strength modulus W pl,RBS;
Ry factor given in ANSI/AISC 341-10 [4] (see Tab. 1.6);
Cpr factor taking into account strain hardening and other phenomena
that can lead to overstrength; FEMA 350 [17] recommends the relation
Cpr =

Fy + Fu

((3.2) FEMA 350 [17])

2 Fy

Fu the nominal value of the ultimate strength;


Cpr = 1,2 may be used in the absence of other information;

27

(1.17)

STEEL STRUCTURES FOR TALL BUILDINGS

Bending moment resistance of the beam (MRd)


Mpr
pl,RBS
Probable moment
Mpl,RBS
Necessary ending moment resistance

Fig. 1.23. Bending moment diagrams

1.4.3.3. Estimation of the shear force in the plastic hinge

The maximum shear force is calculated writing (Fig. 1.24):


VRBS =

M prpl,RBS + M prpl,RBS

=
VRBS

L1

M prpl,RBS + M prpl,RBS
L1

q L1
2
+

(1.18)

q L1
2

(1.18)

sh

L1
L
q
VRBS

VRBS
Mplpr,RBS

Mpr
pl,RBS
L1

28

STEEL STRUCTURES FOR TALL BUILDINGS


Fig. 1.24. Equilibrium of the beam segment between the plastic hinges

1.4.3.4. Estimation of the requirements for the critical cross-section

The bending moment in the critical cross-sections M rEd at the face of the
column (Fig. 1.25a) and M cEd in the axis of the column (Fig. 1.25b) is estimated,
based on the following relations:
b

M rEd = M plpr,RBS + VRBS a +


2

(1.19)

M cEd = M plpr,RBS + VRBS s h

(1.20)

The (plastic) resistance of the beam cross-section is:

M plr ,Rd = Wpl f y M 0

(1.21)

The following requirement is checked:

M rEd = (0,85...1,00) M rpl,Rd

(1.22)

If M rEd is bigger than M plr ,Rd , c must be increased (Fig. 1.22) and return to 1.4.3.2.

a +
2

sh

M cEd

M rEd
Mplpr,RBS

Mpr
pl,RBS

VRBS

VRBS
(a)

(b)

Fig. 1.25. Estimation of the requirements for the critical cross-sections

1.4.4. Checks

29

STEEL STRUCTURES FOR TALL BUILDINGS

1.4.4.1. Resistance checks

The three zones of the beam (rigid zone, plastic zone, elastic zone) must be
checked with the following relations:
M Ed
1,00
M pl,Rd

((6.2) EN 1998-1; (6.2) P100-1:2013)

(1.23)

N Ed
0,15
N pl,Rd

((6.3) EN 1998-1; (6.3) P100-1:2013)

(1.24)

VEd
0,50
Vpl,Rd

((6.4) EN 1998-1; (6.4) P100-1:2013)

(1.25)

For class 3 cross-sections, the plastic values of the resistance must be replaced by
the elastic ones. The axial force limitation (1.24) is necessary only in the plastic
zone. The values of the resistance in relations (1.23), (1.24) and (1.25) are
calculated as follows:
M pl,Rd = Wpl f y M 0 for class 1 and 2 cross-sections

(1.26a)

M el,Rd = Wel f y M 0 for class 3 cross-sections

(1.26b)

N pl,Rd = A f y M 0

(1.27)

Vpl,Rd =

Av fy

(1.28)

M0

where:
A

the area of the cross-section of the beam;

Av the shear area of the cross-section of the beam;


M0 partial (safety) factor for resistance of the cross-section; M0 = 1,0
(EN 1998-1; EN 1993-1-1) ; M0 = 1,1 (P100-1:2013);
W pl the plastic strength modulus of the cross-section of the beam;
W el the elastic strength modulus of the cross-section of the beam;
For seismic structures, the use of class 1 and 2 cross-sections is recommended.
The efforts in relations (1.23), (1.24) and (1.25) are as follows:

for the plastic zone (p);


p
p
M pEd = M Ed
,G + M Ed ,E

(1.29)

p
N pEd = N pEd ,G + N Ed
,E

(1.30)

30

STEEL STRUCTURES FOR TALL BUILDINGS


p
p
p
VEd
= VEd
,G + VEd ,M
p
\ VEd
,M

((6.5) EN 1998-1; (6.5) P100-1:2013)

(1.31)

the design shear force associated to the application of the plastic

bending moments with opposite signs in both plastic hinge zones;


p
Ed ,M

M plp ,Rd ,A + M plp ,Rd ,B

(1.32)

L the span of the beam; it should be the distance between the two plastic
hinges design shear force associated to the application of the plastic bending
moments with opposite signs in both plastic hinge zones (L1 in figure 1.24);

for the rigid zone (r) and for the elastic zone (e);
M Ed = M Ed ,G + T M Ed ,E

(1.33)

N Ed = N Ed ,G + T N Ed ,E

(1.34)

VEd = VEd ,G + T VEd ,E

(1.35)

where:
E Ed ,G effort (M, N, V) caused by gravitational loads;
E Ed ,E effort (M, N, V) caused by seismic loads;
T = 1,1 ov M

(1.36)

T the global overstrength factor;


M pl,Rd ,i

M = min

M
Ed ,i

(1.37)

1.4.4.2. Lateral torsional buckling check

The lateral stability of the beam shall be checked presuming that a plastic
hinge occurred near the most loaded end of the beam. Both flanges of the beam
must be blocked against lateral displacements in the plastic hinge zone. Codes
generally require for these lateral supports to be able to resist a certain force; for
instance, P100-1:2013 recommends a force equal to 0,06ovfytfbf. Lateral torsional
buckling of the beam must be prevented on the entire length of the beam.
Recommendations for the maximum distance between lateral supports can be found
in EN 1993-1-1.

31

STEEL STRUCTURES FOR TALL BUILDINGS

1.4.5. Constructional recommendations for beams

1. None of the following is not permitted in the plastic zone (p):

to support secondary beams;

to change the cross-section of the beam;

to drill holes.

2. The connection between the beam flange and the column flange (beam web in
the same plane with the column web) shall be realised by fully penetrated but
weld (Fig. 1.26).
In figure 1.26, tbf is the thickness of the flange and (FEMA 350 [4]):
1

bevel as required for selected groove weld procedure;

max (tbf ;13mm) (+ 0,5tbf ; 0,25tbf );

0,75tbf tbf 19mm ( 6mm);

minimum radius 10mm (plus not limited, minus 0);

3tbf ( 13mm);

FEMA 353 [XX] covers the requirements for fabrication details, including cutting
methods and smoothness.

Fig. 1.26. Recommended welding detail for beam flange (FEMA 350 [4] Fig. 3.5)

3. The connection between the web of the beam and the column can be realised
either by fillet weld or by butt weld. The bolted connection should be avoided (in

32

STEEL STRUCTURES FOR TALL BUILDINGS


combination with flanges welded connection). If, for technological (erection)
reasons, a bolted connection is used on site, eventually, welding seam must be
realised (Fig. 1.27).

Fig. 1.27. Connection detail (ANSI/AISC 358-10 [4] Fig. 8.1)

4. It is desirable for the beam-column connections to be realised in the shop (by


welding), so that a very good behaviour can be obtained even for very severe
earthquakes. Under these circumstances, it is recommended for the site
connection to be placed in the elastic zone of the beam and, consequently, the
columns arrive on site with the rigid and plastic zones of the beams already
attached. The site connections are made by high strength bolts in slip
connections. The drawback is related to transport, as it is not always easy for
such column parts. However, it is to note that many builders prefer an end-plate
beam-column connection and this cannot be neglected.
5. The beam-column connection must be able to transfer loads corresponding to
the resistance of the connected part (beam), taking into account the overstrength
of the material in the beams.
6. Lateral torsional buckling of the beam must be prevented. Lateral stability of the
top flange is ensured by the reinforced concrete slab by means of the studs that
connect them to avoid relative slip. Special attention must be given to the bottom
flange, as lateral supports must be offered (for instance, by means of a
connection to the slab). It is recommended to avoid any connection between

33

STEEL STRUCTURES FOR TALL BUILDINGS


the slab and the top flange in the plastic zone (and in the rigid zone) [17]

(tests showed that the important increase of the cross-section because of this
connection, as concrete is in compression and steel in tension, can lead to brittle
fracture in the bottom flange when the beam is subject to cyclic loading [17]). An
increased bending moment resistance of the cross-section of the beam also
increases the risk of forming a plastic hinge on the column, instead of having it
on the beam, as desired.
7. It is recommended to have stiffeners at both ends of the plastic hinge (Fig. 1.28).
The thickness of the stiffener, tst, must be at least 75% of the thickness of the
web and bigger than 10mm. It is also recommended to be bigger than bst/15,
where bst is the width of the stiffener. The stiffener width must obey the following
relation:
2 b st + t w = b st

(1.38)

where tw is the thickness of the web.

tw
tr

br

bf
Fig. 1.28. Stiffeners on the plastic hinge zone

1.5. THE COLUMNS OF SEISMIC RESISTANT STEEL STRUCTURES

1.5.1. General recommendations

The cross-sections of columns can be one of the following ones:

open cross-sections (Fig. 1.29a);

hollow cross-sections (Fig. 1.29b).

They can be either hot-rolled or built-up by welding.

34

STEEL STRUCTURES FOR TALL BUILDINGS

(a)
Fig. 1.29. Common cross-section solutions for columns

(b)

Some of the most important advantages of hollow sections are the following ones:

the geometrical characteristics of the cross-section and the stiffness about the
two main axes are comparable;

they have a much better behaviour to accidental torsion, compared to the open
ones;

an improved resistance against fire and against corrosion.

In many cases, hollow sections are filled with concrete, which leads to a better
rigidity and an increased fire resistance.
The main drawback of hollow sections is related to more complicate joint details
when connecting the column to the beams, to braces or to the foundation.
The cross-sections of columns should be class 1 or class 2. In zones where
plastic deformations are accepted (near the connection to the foundation and at the
top end) the cross-section should be class 1.
The connections of columns should be placed neither in strongly loaded
zones (neighbour to joints), nor in potentially plastic ones. Generally, this
recommendation is obeyed if the connection of the column is placed in a zone
between H/5 and H/3 above the floor (where H is the storey height), which
corresponds to a distance of 0,8 1,2m.
The column connections may be either welded or bolted; bolted connections
use high strength bolts in slip connections and the transfer of loads can be realised
either through the splices or by contact between parts.
Columns should be connected at each floor in the plane normal to the frame
plane.
The cross-section of the part of column where plastic deformations are
accepted should have a shape that allows reducing the amount of stresses caused
by the axial force and the shear force, compared to stresses caused by the bending
moment. The length of the plastic zone should be limited at 1,5hc, where hc is the
35

STEEL STRUCTURES FOR TALL BUILDINGS


height of the column cross-section. Stiffeners should be placed all along the plastic
zone at a gap less than 0,5hc among them.

1.5.2. Recommendations for column checks

1.5.2.1. General checks

36

You might also like