Professional Documents
Culture Documents
Chapter 4
4.1 Introduction
Purpose of an air-conditioning system is to control indoor air parameters within required thermal
comfort and indoor air quality. To achieve required indoor air parameters, the system: heat, cool,
humidify, dehumidify and filter outdoor air.
HVAC Subsystems
See Figure on the next page:
End Use
Consumes capacity to condition space air or air stream supplying space.
Air-conditioning systems = air handling systems + ducts + air distribution devices
How to select an air-conditioning system?
Operating costs
Reliability
Flexibility
Maintainability
Chapter 4
-Q,-W
Q W
All-air
-Q,-W
Q W
Chapter 4
-Q,-W
Q W
Air-water
All-water
-Q,-W
Q W
Refrigerant
Production
Convert primary energy for heating/cooling. Energy sources:
Coal
Natural gas
Fuel oil
Biomass
Produce steam and electricity.
Heating production equipment:
Vapor compressor:
Refrigerant
Compressor
Drive (usually electric motor)
Chapter 4
Heat rejection:
Disposes of heat from cooling process
Cooling tower, evaporative condenser, air-cooled condenser
Sink for waste heat: ambient dry bulb, ambient wet bulb, ground, surface water
Trades offs between cost and COP
Chapter 4
Chapter 4
Distribution
Moves capacity from production to use.
Water and steam distribution:
Air distribution:
A
centrifugal fan (Courtesy of the Train
Company, LaCrosse, WI)
Packed equipment
Air-handling unit:
Chapter 4
Chapter 4
Chapter 4
Two-position control systems are always at full capacity or off. Best for systems with slow rate
of change for controlled variable. This control is common in low cost systems, and it is relatively
imprecise.
Example: Two-position control for steam valve in the steam heating coil.
Chapter 4
Modulating control systems produce continuously variable output over a range. This is finer
control system than two-position system, and it is typical in large HVAC systems.
Throttling range (TR) is a range of input variable over which output varies through its full range.
Gain is output per input, and it is usually adjustable.
Proportional control is the simplest modulating action for which the controller output is a linear
function of input:
where OP is the proportional controller output, A is the controller output at zero offset, e is the
error (offset), and KP is the proportional gain constant.
10
Chapter 4
Smaller TR (larger gain) =>smaller offset. Smaller TR may cause stability problems.
Stability is tendency of a system to find a steady control point after an upset.
Instability is tendency for oscillations to grow.
where OPI is the PI controller output, and Ki is the integral gain constant.
Integral term drives offset to zero.
Examples of PI control in buildings include mixed-air control, duct static pressure control, and
coil controls.
11
Chapter 4
Proportional plus integral plus derivative (PID) control further speeds up action of PI control
May not be suitable for HVAC that usually do not require rapid control response.
Additional control rate of change of error
where OPID is the PID controller output, and Kd is the derivative gain constant.
Example of PID application in buildings is duct static pressure control.
Example: Comparison of P, PI, and PID controller response to input step change
12
Chapter 4
13
Chapter 4
HVAC Systems
Air-handling unit (AHU) usually consists of: coil(s), fan(s), filter(s), air-mixing controls,
humidifier, and heat recovery. The following figure represents AHU for a single zone all-air
system.
14
Chapter 4
+Q
O
H1
-Q
+Q
+W
M1
R
15
H2
M2
Chapter 4
O
M1
M
C
C'
I(M2)
H2
R
O
H1
Summer cooling
Winter heating
Summer:
Single mixing with room air:
O + R => M (cooling + dehumidification) => C (re-heat) => I (Q + W ) => R
Double mixing with room air:
O + R => M1 (cooling + dehumidification) => C + R => M2 or I (Q + W ) => R
Winter:
O (pre-heat) => H1 + R => M (humidification) => H2 (re-heat) => I (Q + W) => R
4.3.2 Variable-air-volume systems
Example:
You turn the fan speed up or down in your car.
D =m
D (iR - iI)
Q
I
AHU fan varies power to match loads.
Pressure in supply ducts is maintained to a fixed value.
Design cooling:
box is 100% open
no reheat
Off-design cooling:
zone temperature drops since cooling load decreases
box throttles until minimum flow is reached
16
Dead band:
no control action
start reheat at lower limit
Off-design heating:
minimum primary air
thermostat increases reheat as space temperature falls
Design heating:
fully energized
VAV terminals:
Single-blade dumper (pressure dependent or independent)
Air valve
Induction
Primary flow induces secondary flow from plenum.
17
Chapter 4
18
Chapter 4
19
Chapter 4
Chapter 4
Fan powered series: Fan is always on and space flow is constant. Damper controls supply of
primary air. Perimeter zones may need baseboard or fan-coil units.
Fan-powered parallel: Fan injects plenum air to reheat. Supply pressure drives primary flow that
is controlled by dumpers. Variable space flow => less fan energy.
Advantages of VAV:
Disadvantages and problems of VAV for off design (low flow rate):
Fixed supply airflow rate as well as heating and cooling coil temperatures. Capacity controlled by
terminal reheat coil.
Summer:
Cooling coil lowers TSA to set point. Reheat coil adds heat to satisfy thermostat. Typical
temperatures for cooling coil are 13oC (55oF). Reheat temperature for full load is 13oC (55oF),
when reheat turns off. For this process energy is wasted by overcool & reheat.
Winter:
Preheat coil raises TSA to set point. Reheat coil adds heat to satisfy thermostat. Typical
temperatures for preheat coil are 13oC (55oF), and reheat under full load are 38oC (100oF). No
wasted energy.
20
Chapter 4
+P
+Q
H
O
H1
M
C
-Q, -W (summer)
+W (winter)
I
R
O
R
I
O
Summer cooling
H1
Winter heating
Example:
Design a dual-duct system for the classroom at PSU (Use the data from previous example).
Assume cooling coil could reach a relative humidity of 90%.
Summer cooling processes:
O + R => M
C + H => I
21
Chapter 4
Given:
O:
iO =68.15 kJ/kg, Wo =14.4 g/kg
R:
iR =50.72 kJ/kg, WR =10 g/kg
I:
iI = 37.91 kJ/kg, WI = 9 g/kg
M:
iM = 54.95 kJ/kg
Total cooling load = 5000 W
ma =0.396 kg/s
Fresh air: 80 L/s
Find: Fan, cooling and heating coil capacities.
Total air supplied:
D a = 0.396 kg/s
m
Fan capacity:
Fresh outdoor air:
3
D o = 80 L/s = 0.080 m /s x 1.2 kg/s = 0.096 kg/s
m
WI = 9 g/kga, WR = 10g/kga, Wo = 14.4 g/kga
WH = WM = ( m
D R WR + m
D o Wo )/ m
D a = [ (m
D a- m
D o) WR + mo Wo ]/ m
Da
= [(0.396 - 0.096) x 10 + 0.096 x 14.4)]/0.396 = 11 g/kga
From the analysis in the psychrometric chart, no heating in the hot duct is needed. Then,
iH = iM = 54.95 kJ/kg
Heating coil capacity:
From psychrometric chart:
iC = 36.5 kJ/kg
m H + mC = ma
m H i H + mC i C = ma i I
mH = 0.03 kg/s
mC = 0.366 kg/s
mH + mC = 0.396
mH 54.95 + mC 36.5 =0.396 x 37.91
22
Chapter 4
Control action:
TOA<TRA
TOA=TRA
=> 100% OA
TOA>TRA
Chapter 4
Primary air has constant volume minimum OA required for ventilation. In winter, primary air
is heated space temperature and humidifies. In summer, primary air is cooled to dehumidify.
Secondary air is passing through water coil (heat exchanger) before mixing with primary air.
Central plant makes hot or cold water that is distributed via piping system to the water coil. The
water coil heats/ cools to control space temperature, and does not control humidity.
24
Chapter 4
25
Four-pipe: Two for supply and the other two for return.
26
Chapter 4
Chapter 4
Fan-coil
Unit ventilator
Radiant panels
27
28
Chapter 4
Chapter 4
29
30
Chapter 4
31
Chapter 4
Chapter 4
Heat source/sink:
Air source - low cost, and it is least efficient. Water (ground) source high cost, and it is more
efficient than air.
33
Chapter 4
Chapter 4
Advantages
Disadvantages
All Air
Duct clearance
Large ducts - space
Air balancing difficulties
Air
Water
Less space
Locally shutoff (individual
control)
Quick pull down
Good for existing buildings
Limited performance
No humidity control (general)
More energy (low efficiency)
Control of air distribution
Filter
Overall appearance
All
Water
Unitary
34