Process Industry Practices


Electrical

PIP ELSMT01D
Data Sheet for
AC Squirrel Cage Induction Motors
(600 Volts and Below) Specification

PURPOSE AND USE OF PROCESS INDUSTRY PRACTICES


In an effort to minimize the cost of process industry facilities, this Practice has
been prepared from the technical requirements in the existing standards of major
industrial users, contractors, or standards organizations. By harmonizing these technical
requirements into a single set of Practices, administrative, application, and engineering
costs to both the purchaser and the manufacturer should be reduced. While this Practice
is expected to incorporate the majority of requirements of most users, individual
applications may involve requirements that will be appended to and take precedence
over this Practice. Determinations concerning fitness for purpose and particular matters
or application of the Practice to particular project or engineering situations should not
be made solely on information contained in these materials. The use of trade names
from time to time should not be viewed as an expression of preference but rather
recognized as normal usage in the trade. Other brands having the same specifications
are equally correct and may be substituted for those named. All Practices or guidelines
are intended to be consistent with applicable laws and regulations including OSHA
requirements. To the extent these Practices or guidelines should conflict with OSHA or
other applicable laws or regulations, such laws or regulations must be followed.
Consult an appropriate professional before applying or acting on any material
contained in or suggested by the Practice.
This Practice is subject to revision at any time by the responsible Function Team and will
be reviewed every 5 years. This Practice will be revised, reaffirmed, or withdrawn.
Information on whether this Practice has been revised may be found at www.pip.org.

Process Industry Practices (PIP), Construction Industry Institute, The


University of Texas at Austin, 3925 West Braker Lane (R4500), Austin,
Texas 78759. PIP member companies and subscribers may copy this Practice
for their internal use. Changes, overlays, addenda, or modifications of any
kind are not permitted within any PIP Practice without the express written
authorization of PIP.

PIP will not consider requests for interpretations (inquiries) for this Practice.
PRINTING HISTORY
September 1997
Issued
June 2004
Complete Revision
Not printed with State funds

ASSOC. PIP

DATA SHEET

ELSMT01

ELSMT01D-D
PAGE 1 OF 1

AC SQUIRREL CAGE INDUCTION MOTORS


(600 VOLTS AND BELOW)
ISSUED FOR:

PROPOSAL

PURCHASE

JUNE 2004

AS BUILT

FACILITY NAME/LOCATION:
ITEM NAME:

PURCHASER/LOCATION:

ITEM TAG NO.:

JOB NO:

SERVICE:

PURCHASER ORDER NO.:

UNIT:

SUPPLIER/LOCATION:

P&ID NO.:

SUPPLIER ORDER/SERIAL NOS.:

DATA PROVIDED BY:

PURCHASER

SUPPLIER IF NOT BY PURCHASER

SUPPLIER

REFER TO PIP ELSMT01 FOR GENERAL REQUIREMENTS


APPLICABLE STATE AND LOCAL CODES:
SITE CONDITIONS (4.1):

OTHER DATA: (SUCH AS BEARING TYPE [4.4.1], LUBRICATION

ALTITUDE:

AMBIENT TEMP.:

METHOD [4.4.4], UNUSUAL SERVICE CONDITIONS, ETC.)

MAX.:

MIN.:

NONCLASSIFIED
CLASSIFIED (4.2.6)
AREA CLASS:

DIV/ZONE:

AUTO IGNITION TEMP.:

GROUP:

OTHER:
DATA BY PURCHASER:

DATA BY SUPPLIER:

IEEE 841 DESIGN (4.2.1)

FRAME SIZE:

SEVERE DUTY, HIGH EFFICIENCY MEETING IEEE 841

FULL LOAD SPEED:

WITH EXCEPTION OF (4.2.1):

HP:
RPM

FULL LOAD CURRENT:

IP55 BEARING PROTECTION NOT REQUIRED

LOCKED ROTOR CURRENT @ FULL VOLTAGE:

VIBRATION LEVELS PER MG-1, 2003, PART 7.8.2

ALLOWABLE STALL TIME @ FULL VOLT.:

SEC.

FOOT-FLATNESS PER MG-1, 2003, PART 4.15

ALLOWABLE STALL TIME @ 90% VOLT.:

SEC.

TESTING PER MG-1, 2003, PART 12

NOISE SOUND POWER LEVEL:

INVERTER DUTY:

INSULATION SYSTEM:

CONSTANT TORQUE

VARIABLE TORQUE

CLASS:

TURN DOWN RATIO:

RANDOM

HORSEPOWER:

TEMPERATURE RISE AT RATED LOAD:

SYNCHRONOUS SPEED:

SERVICE FACTOR:

VOLTAGE:

BEARING INFORMATION:

PHASE: 3

FORM WOUND
C MAX.

TYPE:

FREQUENCY: 60 HZ

LUBRICATION METHOD:

COUPLED DRIVE:

DIRECT

BELT

RECOMMENDED LUBRICANT:

SERVICE FACTOR:

1.15

1.0

TEMP. RISE @ FULL LOAD:

MOTOR THRUST LOADS:

MANUFACTURER & NUMBER:

SPECIAL LOAD CONDITIONS:

ODE:

STARTING METHOD:

DE:

SHOP INSPECTION & TESTS:

MOUNTING POSITION (4.3.1):

HORIZONTAL

VERTICAL

SHOP INSPECTION REQUIRED

SHAFT (VERTICAL MTG. ONLY):

UP

DOWN

FINAL TESTS WITNESSED BY PURCHASER

MAIN TERMINAL BOX LOCATION (4.3.2.2):

ADDITIONAL SPECIAL TESTS (5.2):

OVERSIZED TERMINAL BOX (4.3.2.3)


UNIDIRECTIONAL FAN REQUIRED (4.5.1)
ROTATION DIRECTION:
SPACE HEATERS REQUIRED (4.6.1):
SPACE HEATER VOLTAGE (4.6.4):
SPACE HEATER MAXIMUM SURFACE TEMP. (4.6.6):

NO.

DATE

REVISION DESCRIPTION

BY

APVD.