Air-Cooled Chiller, Scroll Compressors

Job Information
Job01

Tag

CGAM-1

Model Number

CGAM 60

Quantity

Product Version

170

Unit nominal tonnage

60 tons

Unit type

High efficiency

General Information
Sound attenuator package

Super quiet

IPLV

4.20 COP

Refrigerant

R410A

NPLV

5.39 COP

Capacity

83.10 tons

Sound power level

90 dBA

Full load efficiency

4.22 COP

Sound pressure level *

63 dBA

Evaporator application

Std cooling

Fouling factor

0.017610 m2-deg C/kW

Entering temperature

24.0 C

Saturated temperature-ckt 1

13.5 C

Leaving temperature

18.0 C

Saturated temperature-ckt 2

13.4 C

Fluid flow rate

11.68 L/s

Minimum flow rate

5.29 L/s

Pressure drop

64.6 kPa

Pressure drop at min flow rate

20.3 kPa

Total PD evap+strainer

91.5 kPa

Maximum flow rate

12.70 L/s

Evap fluid type

Water

Pressure drop at max flow rate

107.6 kPa

Evap fluid freeze point

0.0 C

Freeze protection (factory inst)

Ext. t-stat control

Unit application

High ambient

Total fan FLA

22.20 A

Ambient air temperature

30.0 C

Total airflow

26.10 m3/s

Elevation

0.0 m

Fin material

Lanced aluminum

Number of fans

Saturated temperature-ckt 1

49.9 C

Fan motor power

7.40 kW

Saturated temperature-ckt 2

50.0 C

Note:

* At 30 feet in free field.

Evaporator Information

Condenser Information

Compressor Information
Number of compressors

RLA

LRA

Number of circuits

Compressor A

29.30 A

208.00 A

Capacity steps

Compressor B

29.30 A

208.00 A

Total compressor power

61.50 kW

Compressor D

29.30 A

208.00 A

Compressor E

29.30 A

208.00 A

Electrical Information
Unit voltage

380 volt 3 phases

Unit hertz

60 hertz

Short circuit

Default

Short circuit rating

5000.00 A

Unit power

69.30 kW

Note:

MCA

MOP

Single point power

148.90 A

175.00 A

Incoming power line connection

Single point

Starter type

Across the line

Unit power includes: compressors, condenser fans, and control kW

Unit is outside of the scope of AHRI Air-Cooled Water Chilling Packages Using Vapor Compression Cycle
Certification Program, but is rated in accordance with AHRI Standard 550/590 (I-P).

27/01/2015

Product Version

170
Page 1 of 2

Air-Cooled Chiller, Scroll Compressors


Job Information
Job01

Tag

CGAM-1

Model Number

CGAM 60

Quantity

Product Version

170

Unit nominal tonnage

60 tons

Unit type

High efficiency

Physical Information
Length

3810 mm

Water connections

76 mm

Width

2250 mm

Refrigerant charge circuit 1

20 kg

Height

2154 mm

Refrigerant charge circuit 2

20 kg

Operating weight

2283 kg

Oil charge circuit 1

7.20 L

Shipping weight

2258 kg

Oil charge circuit 2

7.20 L

ASHRAE 90.1/CSA compliance

All versions

IPLV

4.20 COP

Refrigerant charge circuit 1

20 kg

Rated capacity (AHRI)

202.17 kW

Refrigerant charge circuit 2

20 kg

Information for LEED Projects

Note:

This product meets the minimum efficiency requirements of ASHRAE Standard 90.1 and CANS/CSA C743 for all versions (which
are based on AHRI standard rating conditions) and, therefore, also meets the LEED "Minimum Energy Performance" prerequisite in
the Energy and Atmosphere section.

The LEED Green Building Rating System, developed by the U.S. Green Building Council, provides independent, third-party verification that a building project
meets green building and performance measures.

27/01/2015

Product Version

170
Page 2 of 2