You are on page 1of 46

Siemens AG

SIMATIC S7 Ethernet
Driver

System Configuration....................................................................................................... 3

External Device Selection ................................................................................................ 6

Communication Settings .................................................................................................. 7

Setup Items .................................................................................................................... 25

Supported Device Addresses......................................................................................... 34

Device Code and Address Code.................................................................................... 45

Error Messages.............................................................................................................. 46

SIMATIC S7 Ethernet Driver

Introduction
This manual describes how to connect the Display and the External Device (target PLC).
In this manual, the connection procedure will be described by following the below sections:

System Configuration
This section shows the types of External
Devices which can be connected and SIO
type.

"1 System Configuration" (page 3)

Selection of External Device


Select a model (series) of the External
Device to be connected and connection
method.

"2 External Device Selection" (page 6)

Example of Communication Settings


This section shows setting examples for
communicating between the Display and
the External Device.

"3 Communication Settings" (page 7)

Setup Items
This section describes communication
setup items on the Display.
Set communication settings of the Display
with GP-Pro Ex or in offline mode.

"4 Setup Items" (page 25)

Operation

GP-Pro EX Device/PLC Connection Manual

SIMATIC S7 Ethernet Driver

System Configuration
The system configuration in the case when the External Device and the Display are connected is shown.

Series

SIMATIC S7-200
Series

SIMATIC S7-300
Series

CPU
CPU222
CPU224
CPU224 XP
CPU226

Link I/F

CP 243-1 IT*2
CP 243-1

CPU312IFM
CPU313
CPU314
CPU314IFM
CPU315
CPU315-2 DP
CPU316
CPU316-2 DP
CPU318-2
CPU315-2 PN/DP
CPU317-2 PN/DP
CPU319-3 PN/DP

CP 343-1 IT
CP 343-1

CPU315-2 PN/DP
CPU317-2 PN/DP
CPU319-3 PN/DP

Ethernet interface
on CPU*3

SIO Type*1

Setting
Example

Ethernet
(TCP)
(OP Communication)

Setting
Example 3
(page 13)

Ethernet
(TCP)
(FETCH/WRITE)

Setting
Example 1
(page 7)

Ethernet
(TCP)
(OP Communication)

Setting
Example 2
(page 10)

Ethernet
(TCP)
(OP Communication)

Setting
Example 2
(page 10)

Ethernet
(TCP)
(FETCH/WRITE)

Setting
Example 1
(page 7)

Ethernet
(TCP)
(OP Communication)

Setting
Example 2
(page 10)

CPU412-1
CPU412-2 DP
CPU413-1
CPU413-2 DP
CPU414-1
CPU414-2 DP
CPU414-3 DP
CPU416-1
CPU416-2 DP
CPU416-3 DP
CPU417-4
CPU414-3PN/DP
CPU416-3PN/DP

CP 443-1 IT
CP 443-1

CPU414-3PN/DP
CPU416-3PN/DP

Ethernet interface
on CPU*3

Ethernet
(TCP)
(OP Communication)

Setting
Example 2
(page 10)

SIMATIC S7-1200
Series

CPU1211C
CPU1212C
CPU1214C

PROFINET
interface on CPU*4

Ethernet
(TCP)
(OP Communication)

Setting
Example 4
(page 16)

LOGO! Series

OBA7

Ethernet interface
on CPU*3

Ethernet
(TCP)
(OP Communication)

Setting
Example 5
(page 19)

SIMATIC S7-400
Series

GP-Pro EX Device/PLC Connection Manual

SIMATIC S7 Ethernet Driver

Series

CPU

SIMATIC S7-1500
Series

CPU1511-1 PN
CPU1513-1 PN
CPU1515-2 PN
CPU1516-3 PN/DP
CPU1518-4 PN/DP
CPU1516F-3 PN/DP
CPU1518F-4 PN/DP

*1

SIO Type*1

Link I/F

PROFINET
interface on CPU

Ethernet
(TCP)
(OP Communication)

Setting
Example

Setting
Example 6
(page 22)

OP Communication has a larger address range of usable devices as that of FETCH/WRITE, so we


recommend use of OP Communication.
"5 Supported Device Addresses" (page 34)

*2

CP 243-1 IT and CP 243-1 can use the version of CPU above Rel.1.20.

*3

The Ethernet interface in the CPU only supports OP Communication. FETCH/WRITE cannot be used.

*4

The PROFINET interface in the CPU only supports OP Communication. FETCH/WRITE cannot be used.

GP-Pro EX Device/PLC Connection Manual

SIMATIC S7 Ethernet Driver

Connection Configuration

1:1 Connection

Display

External Device

HUB

1:n Connection

Max 16 units

Display

External Device

External Device

HUB

n:1 Connection

Max 32 units

Display

Display

External Device

HUB
The number of connectable Displays depends on the External Device.
The number of connectable Display depends on the External Device.
Please refer to the External Device manual for more details.
The following limitations apply when using the LOGO! series:
1:n connections require a network switch.
n:1 connection is not supported.
You cannot use the Display if the ladder software is online.

GP-Pro EX Device/PLC Connection Manual

SIMATIC S7 Ethernet Driver

External Device Selection


Select the External Device to be connected to the Display.

Setup Items

Setup Description

Number of Devices/
PLCs

Enter an integer from 1 to 4 for the number of series to set.

Manufacturer

Select the manufacturer of the External Device to be connected. Select "Siemens AG".

Series

Select a model (series) of the External Device to be connected and connection method.
Select "SIMATIC S7 Ethernet".
Check the External Device which can be connected in "SIMATIC S7 Ethernet" in system
configuration.
"1 System Configuration" (page 3)

Port

Select the Display port to be connected to the External Device.

Use System Area

Check this option when you synchronize the system data area of Display and the device
(memory) of External Device. When synchronized, you can use the ladder program of
External Device to switch the display or display the window on the display.
Cf. GP-Pro EX Reference Manual "LS Area (Direct Access Method Area)"
This can also be set in GP-Pro EX or in the Display's offline mode.
Cf. GP-Pro EX Reference Manual "Display Unit (System Area) Settings Guide"
Cf. Maintenance/Troubleshooting Manual "Main Unit - System Area Settings"

GP-Pro EX Device/PLC Connection Manual

SIMATIC S7 Ethernet Driver

Communication Settings
Examples of communication settings of the Display and the External Device, recommended by Pro-face, are
shown.

3.1

Setting Example 1
GP-Pro EX Settings
Communication Settings
To display the setup screen, from the [Project] menu, point to [System Settings] and select [Device/PLC].

GP-Pro EX Device/PLC Connection Manual

SIMATIC S7 Ethernet Driver


Device Settings
To display the [Individual Device Settings] dialog box, from [Device-Specific Settings] in the [Device/PLC]
window, select the external device and click [Settings]

. To connect multiple External Devices, from [Device-

Specific Settings] in the [Device/PLC] window, click [Add Device] to add another External Device.
GP3000, GP-4100 Series, GP-4*01TM,
GP-Rear Module and LT3000 Series

GP4000 (excluding GP-4100 Series, GP-4*01TM and


GP-Rear Module) Series and IPC Series(PC/AT)

Notes

Check with a network administrator about IP address. Do not set the duplicate IP address.

Set IP address on the External Device for IP address in Device-specific settings.

You need to set IP address on the Display in the offline mode of the Display.

GP-Pro EX Device/PLC Connection Manual

SIMATIC S7 Ethernet Driver

External Device Settings


Use the FETCH TCP protocol and WRITE TCP protocol so that the Ethernet driver can read and write data for
the External Device. Setting example is shown below. Please refer to the manual of the External Device for more
details.
(1) Select CP343-1/443-1 from hardware configuration menu in the ladder software "STEP 7" by Siemens AG.
When the dialog box is displayed, set [IP address] and [Subnet mask] in the [Parameters] tab.
(2) Start up "NetPro" from "STEP7", and select the CPU to which CP343-1/443-1 is connected. Right-click to
select [Insert New Connection].
(3) Select [TCP connection] for [Type] in the displayed dialog box, and leaving [Unspecified] selected for
[Station], click [OK].
(4) Click the [Options] tab in the displayed dialog box, and select [Fetch passive] in [Mode].
(5) Click the [Address] tab, and enter the port No. (FETCH PORT No. Default 2000) Do not set the duplicate port
No.
(6) Click [OK].
(7) Select the CPU again to which CP343-1/443-1 is connected. Right-click to select [Insert New Connection].
(8) Select [TCP connection] for [Type] in the displayed dialog box, and leaving [Unspecified] selected for
[Station], click [OK].
(9) Click the [Options] tab in the displayed dialog box, and select [Write passive] in [Mode].
(10)Select the [Address] tab and enter the port No. (WRITE PORT No. Default 2001) Do not set the duplicate
port No.
(11)Click [OK].
(12)Save the above setting contents and download to the External Device.

Notes

The FETCH ports Partner that is set in the ladder software communication setting dialog box must be the
same as the [Port No. (FETCH)] set in the GP-Pro EX communication settings. Likewise, the WRITE ports
Partner must be the same as the [Port No. (WRITE)].
If each Partner of the FETCH port and the WRITE port is blank, the [Port No.] can be also set to [Auto].

Check with a network administrator about IP address. Do not set the duplicate IP address.

The "Keep Alive" feature of Siemens CP Module is not supported. Please set the "Keep Alive" to 0.

When the Display is turned off and on again during communication with the External Device or is switched to
offline mode and then back to online mode, it may take several tens of seconds before the communication is
resumed.

GP-Pro EX Device/PLC Connection Manual

SIMATIC S7 Ethernet Driver

3.2

Setting Example 2
GP-Pro EX Settings
Communication Settings
To display the setup screen, from the [Project] menu, point to [System Settings] and select [Device/PLC].

Port No. that is set to [Port No. (FETCH)] performs communication in OP Communication. Port
No. that is set to [Port No. (WRITE)] is not used.

GP-Pro EX Device/PLC Connection Manual

10

SIMATIC S7 Ethernet Driver


Device Settings
To display the [Individual Device Settings] dialog box, from [Device-Specific Settings] in the [Device/PLC]
window, select the external device and click [Settings]

. To connect multiple External Devices, from [Device-

Specific Settings] in the [Device/PLC] window, click [Add Device] to add another External Device.
GP3000, GP-4100 Series, GP-4*01TM,
GP-Rear Module and LT3000 Series

GP4000 (excluding GP-4100 Series, GP-4*01TM and


GP-Rear Module) Series and IPC Series(PC/AT)

Notes

Check with a network administrator about IP address. Do not set the duplicate IP address.

Set IP address on the External Device for IP address in Device-specific settings.

You need to set IP address on the Display in the offline mode of the Display.

GP-Pro EX Device/PLC Connection Manual

11

SIMATIC S7 Ethernet Driver

External Device Settings


The Communication setting for the External Device is executed using ladder software (STEP 7).
Please refer to the manual of the External Device for more details.
(1) Start up ladder software.
(2) Select [New Project Wizard] of [File] menu and make a project. Set the CPU, Organization Block, and project
name to be used following the instruction provided by the wizard.
(3) Start up Hardware setting.
(4) Select the module to be used from the catalog view and allocate it to the slot of the mounted module number.
(5) After allocating the module, [Property] dialog box is displayed. Set IP address and subnet mask to [Property]
dialog box of the module to be used for communication.
(6) Select [New] from [Subnet] of [Property] dialog box.
(7) Confirm displayed Subnet property and click [OK].
(8) Select Subnet property displayed in [Subnet] of [Property] dialog box. Click [OK] to close [Property] dialog
box.
(9) Select [Save and Compile] from [Station] menu and save the contents of the settings. After saving, end
Hardware setting.
(10)Start up NetPro and download the contents for setting to the External Device. After the download is
completed, reboot the power of the External Device.

Notes

Check that the CPU rack number and CPU slot number to be used for communication are the same as the GPPro EX setting. If the setting is not the same, communication cannot be conducted.

Check with a network administrator about IP address. Do not set the duplicate IP address.

When the Display is turned off and on again during communication with the External Device or is switched to
offline mode and then back to online mode, it may take several tens of seconds before the communication is
resumed.

GP-Pro EX Device/PLC Connection Manual

12

SIMATIC S7 Ethernet Driver

3.3

Setting Example 3
GP-Pro EX Settings
Communication Settings
To display the setup screen, from the [Project] menu, point to [System Settings] and select [Device/PLC].

Port No. that is set to [Port No. (FETCH)] performs communication in OP Communication. Port
No. that is set to [Port No. (WRITE)] is not used.
Set the "Timeout" value to "3" (sec) or more.

GP-Pro EX Device/PLC Connection Manual

13

SIMATIC S7 Ethernet Driver


Device Settings
To display the [Individual Device Settings] dialog box, from [Device-Specific Settings] in the [Device/PLC]
window, select the external device and click [Settings]

. To connect multiple External Devices, from [Device-

Specific Settings] in the [Device/PLC] window, click [Add Device] to add another External Device.
GP3000, GP-4100 Series, GP-4*01TM,
GP-Rear Module and LT3000 Series

GP4000 (excluding GP-4100 Series, GP-4*01TM and


GP-Rear Module) Series and IPC Series(PC/AT)

Notes

Check with a network administrator about IP address. Do not set the duplicate IP address.

Set IP address on the External Device for IP address in Device-specific settings.

You need to set IP address on the Display in the offline mode of the Display.

GP-Pro EX Device/PLC Connection Manual

14

SIMATIC S7 Ethernet Driver

External Device Settings


Use the ladder software (STEP 7 Micro/Win32) for communication settings of the External Device. Please refer to
the manual of the External Device for details.
(1) Start up the ladder software.
(2) From the [Tool] menu, select [Ethernet Wizard].
(3) Click [Next].
(4) Click [Read Module] to detect the installed Ethernet module.
(5) Enter the [Position] value of the detected module in [Module Position], and then click [Next].
(6) Set [IP Address] and [Subnet Mask], and then click [Next].
(7) Enter "1" (the number of the Display to be connected) in "Number of connections to configure for this
module.", and then click [Next].
(8) Follow the steps below to set the Display, and then click [OK].

Select "This is a Server Connection" to connect the External Device to the Display.

In the "Local Properties (Server)" area, select "Accept all connection requests." to allow connections from
all IP addresses.

In the "Remote Properties (Client)" area, enter "10.00" in "TSAP".

Clear the "Enable the Keep Alive function for this connection." check box because the Display does not
support KeepAlive.
The connection number is displayed in this dialog box. If the connection number is "1", for
example, [Connection 1] is displayed.

(9) Click [Next].


(10)To save the module configuration, set the memory address of the External Device, and then click [Next].
(11)Click [Finish].
(12)Click [Yes] for the confirmation message.
(13)Select [Save] from [File], and download the configuration to the External Device.

Notes

Check with your network administrator about the IP address. Do not duplicate IP addresses.

The subroutine "ETH0_CTRL" must be called by the ladder program every scan.

When the Display is turned off and on again during communication with the External Device or is switched to
offline mode and then back to online mode, it may take several tens of seconds before the communication is
resumed.

GP-Pro EX Device/PLC Connection Manual

15

SIMATIC S7 Ethernet Driver

3.4

Setting Example 4
GP-Pro EX Settings
Communication Settings
To display the setup screen, from the [Project] menu, point to [System Settings] and select [Device/PLC].

Port No. that is set to [Port No. (FETCH)] performs communication in OP Communication. Port
No. that is set to [Port No. (WRITE)] is not used.
Set the "Timeout" value to "3" (sec) or more.

GP-Pro EX Device/PLC Connection Manual

16

SIMATIC S7 Ethernet Driver


Device Settings
To display the [Individual Device Settings] dialog box, from [Device-Specific Settings] in the [Device/PLC]
window, select the external device and click [Settings]

. To connect multiple External Devices, from [Device-

Specific Settings] in the [Device/PLC] window, click [Add Device] to add another External Device.
GP3000, GP-4100 Series, GP-4*01TM,
GP-Rear Module and LT3000 Series

GP4000 (excluding GP-4100 Series, GP-4*01TM and


GP-Rear Module) Series and IPC Series(PC/AT)

Notes

Check with a network administrator about IP address. Do not set the duplicate IP address.

Set IP address on the External Device for IP address in Device-specific settings.

You need to set IP address on the Display in the offline mode of the Display.

GP-Pro EX Device/PLC Connection Manual

17

SIMATIC S7 Ethernet Driver

External Device Settings


Use the ladder software (STEP 7 BASIC) to configure the External Device communication settings. Please refer
to the External Device manual for details.
(1) Start up the ladder software.
(2) Create a project and select the External Device.
(3) Select the PROFINET interface on the CPU and display the setup screen.
(4) Select [Ethernet address] and set up as follows.
Setup Items

Setting Value

IP address

192.168.0.1

Subnet mask

255.255.255.0

(5) Save and transfer the project to the External Device.

GP-Pro EX Device/PLC Connection Manual

18

SIMATIC S7 Ethernet Driver

3.5

Setting Example 5
GP-Pro EX Settings
Communication Settings
To display the setup screen, from the [Project] menu, point to [System Settings] and select [Device/PLC].

Port No. that is set to [Port No. (FETCH)] performs communication in OP Communication. Port
No. that is set to [Port No. (WRITE)] is not used.
Set the "Timeout" value to "3" (sec) or more.

GP-Pro EX Device/PLC Connection Manual

19

SIMATIC S7 Ethernet Driver


Device Settings
To display the [Individual Device Settings] dialog box, from [Device-Specific Settings] in the [Device/PLC]
window, select the external device and click [Settings]

. To connect multiple External Devices, from [Device-

Specific Settings] in the [Device/PLC] window, click [Add Device] to add another External Device.
GP3000, GP-4100 Series, GP-4*01TM,
GP-Rear Module and LT3000 Series

GP4000 (excluding GP-4100 Series, GP-4*01TM and


GP-Rear Module) Series and IPC Series(PC/AT)

Notes

Check with a network administrator about IP address. Do not set the duplicate IP address.

Set IP address on the External Device for IP address in Device-specific settings.

You need to set IP address on the Display in the offline mode of the Display.

GP-Pro EX Device/PLC Connection Manual

20

SIMATIC S7 Ethernet Driver

External Device Settings


Use the ladder software (LOGO!Soft Comfort V7.0) to configure the External Device communication settings.
Please refer to the External Device manual for details.
(1) Start up the ladder software.
(2) Create the ladder diagram.
(3) From the [Tools] menu select [Ethernet connections], and define the setup items as follows:
Setup Items

Setting Value

IP address

192.168.0.1

Subnet mask

255.255.255.0

Gateway

192.168.0.10

(4) From [Peer-to-Peer Connections], right-click [Ethernet Connections] and from the shortcut menu select [Add
Connection].
(5) Double-click the added connection and select [Server Connection].
(6) In [Local Properties (Server)], select the [Connect with an Operator Panel (OP)] and [Accept all connection
requests] check boxes. In [Remote Properties (Client)], set [TSAP] to "02.00".
(7) Click [OK] to close the dialog box.
(8) Update the Parameter VM Mapping and then download the communication setting to the External Device.

GP-Pro EX Device/PLC Connection Manual

21

SIMATIC S7 Ethernet Driver

3.6

Setting Example 6
GP-Pro EX Settings
Communication Settings
To display the setup screen, from the [Project] menu, point to [System Settings] and select [Device/PLC].

Port No. that is set to [Port No. (FETCH)] performs communication in OP Communication. Port
No. that is set to [Port No. (WRITE)] is not used.
Set the "Timeout" value to "3" (sec) or more.

GP-Pro EX Device/PLC Connection Manual

22

SIMATIC S7 Ethernet Driver


Device Settings
To display the [Individual Device Settings] dialog box, from [Device-Specific Settings] in the [Device/PLC]
window, select the external device and click [Settings]

. To connect multiple External Devices, from [Device-

Specific Settings] in the [Device/PLC] window, click [Add Device] to add another External Device.
GP3000, GP-4100 Series, GP-4*01TM,
GP-Rear Module and LT3000 Series

GP4000 (excluding GP-4100 Series, GP-4*01TM and


GP-Rear Module) Series and IPC Series(PC/AT)

Notes

To use a S7-1500 Series device, from the [PLC Type] list select [S7-1200 Series].

Check with a network administrator about IP address. Do not set the duplicate IP address.

Set IP address on the External Device for IP address in Device-specific settings.

You need to set IP address on the Display in the offline mode of the Display.

GP-Pro EX Device/PLC Connection Manual

23

SIMATIC S7 Ethernet Driver

External Device Settings


Use ladder software (STEP 7 Professional) to define External Device communication settings. Please refer to the
External Device manual for details.
(1) Start the ladder software.
(2) Create a project and select the External Device.
(3) For CPU select the PROFINET interface and display the setup screen.
(4) Select [Ethernet address] and define the settings as follows.
Setup Items

Setting Value

IP address

192.168.0.1

Subnet mask

255.255.255.0

(5) In the project tree, right-click the data block and select [Properties].
(6) In the [General] tab, select [Attributes]. Clear the [Optimized block access] check box, and click [OK]. Clear
the check boxes of all data blocks.
(7) In the project tree, select [Device configuration].
(8) In the [General] tab, select [Protection]. Select the [Permit access with PUT/GET communication from
remote partner] check box, and click [OK].
(9) Set the data block, and then compile the project.
(10)Save and transfer the project to the External Device.

When you compile the project, an offset is mapped to each element in the data block.
Specify the addresses as follows.
Example: When the following offsets are applied to elements of data block [DB2].
Name

Data type

Address notation of
GP-Pro EX

Offset

Data1

Bool

0.0

DB00002.DBX00000.0

Data2

Word

2.0

DB00002.DBW00002

Data3

DWord

4.0

DB00002.DBW00004

GP-Pro EX Device/PLC Connection Manual

24

SIMATIC S7 Ethernet Driver

Setup Items
Set communication settings of the Display with GP-Pro EX or in offline mode of the Display.
The setting of each parameter must be identical to that of External Device.

"3 Communication Settings" (page 7)


Set the Displays IP address in offline mode.
Cf.

4.1

Maintenance/Troubleshooting Guide "Ethernet Settings"

Setup Items in GP-Pro EX


Communication Settings
To display the setup screen, from the [Project] menu, point to [System Settings] and select [Device/PLC].

Setup Items

Setup Description

Port No.

Use an integer from 1024 to 65535 to enter FETCH port number and WRITE number of
display. If a check is put in [Auto], port number is set automatically.
When the connection type is OP Communication, the port number set to [Port No.
(FETCH)] implements communication.

Timeout

Use an integer from 1 to 127 to enter the time (s) for which the Display waits for the
response from the External Device.

Retry

In case of no response from the External Device, use an integer from 0 to 255 to enter how
many times the Display retransmits the command.

Wait To Send

Use an integer from 0 to 255 to enter standby time (ms) for the Display from receiving
packets to transmitting next commands.

Refer to the GP-Pro EX Reference Manual for Indirect Device.

GP-Pro EX Device/PLC Connection Manual

25

SIMATIC S7 Ethernet Driver

Device Setting
To display the [Individual Device Settings] dialog box, from [Device-Specific Settings] in the [Device/PLC]
window, select the external device and click [Settings]

. To connect multiple External Devices, from [Device-

Specific Settings] in the [Device/PLC] window, click [Add Device] to add another External Device.
Setting contents of device setting differs depending on the connection type (SIMATIC S7-300/400 Series only).
<S7-300/400 Series Connection type: FETCH/WRITE>
GP3000, GP-4100 Series, GP-4*01TM,
GP-Rear Module and LT3000 Series

GP4000 (excluding GP-4100 Series, GP-4*01TM and


GP-Rear Module) Series and IPC Series(PC/AT)

Setup Items

Setup Description

PLC Type

Select the External Device series.

Device Names

Select the display language of device names, either English or German.


Set IP address of the External Device.

Destination IP Address
Check with a network administrator about IP address. Do not set the duplicate IP
address.
Connection Type

Select the connection type.

FETCH Port

Use an integer from 1024 to 65535 to enter the FETCH port No. of the External Device.

WRITE Port

Use an integer from 1024 to 65535 to enter the WRITE port No. of the External Device.

GP-Pro EX Device/PLC Connection Manual

26

SIMATIC S7 Ethernet Driver


<S7-300/400 Series Connection type: OP Communication>
GP3000, GP-4100 Series, GP-4*01TM,
GP-Rear Module and LT3000 Series

GP4000 (excluding GP-4100 Series, GP-4*01TM and


GP-Rear Module) Series and IPC Series(PC/AT)

Setup Items

Setup Description

PLC Type

Select the External Device series.

Device Names

Select the display language of device names, either English or German.


Set IP address of the External Device.

Destination IP Address
Check with a network administrator about IP address. Do not set the duplicate IP
address.
Connection Type

Select the connection type.

CPU Rack Number

Use an integer from 0 to 7 to enter the CPU rack number of the External Device.

CPU Slot Number

Use an integer from 0 to 31 to enter the CPU slot number of the External Device.

Use Tag Data

Select the check box when using tag data (symbol addresses). This will enable you to select
the tags you want to use.
"5.6 When Using a Tag" (page 39)

GP-Pro EX Device/PLC Connection Manual

27

SIMATIC S7 Ethernet Driver


<S7-200 Series>
GP3000, GP-4100 Series, GP-4*01TM,
GP-Rear Module and LT3000 Series

GP4000 (excluding GP-4100 Series, GP-4*01TM and


GP-Rear Module) Series and IPC Series(PC/AT)

Setup Items

Setup Description

PLC Type

Select the External Device series.

Device Names

Select the display language of device names, either English or German.


Set IP address of the External Device.

Destination IP Address
Check with a network administrator about IP address. Do not set the duplicate IP
address.
Connection Number

Use an integer from 0 to 7 to enter the connection number of the External Device.

Module Position

Use an integer from 0 to 6 to enter the module position of the External Device.

Use Tag Data

Select the check box when using tag data (symbol addresses). This will enable you to select
the tags you want to use.
"5.6 When Using a Tag" (page 39)

GP-Pro EX Device/PLC Connection Manual

28

SIMATIC S7 Ethernet Driver


<S7-1200/1500 Series>
GP3000, GP-4100 Series, GP-4*01TM,
GP-Rear Module and LT3000 Series

GP4000 (excluding GP-4100 Series, GP-4*01TM and


GP-Rear Module) Series and IPC Series(PC/AT)

Setup Items

Setup Description

PLC Type

Select the External Device series.

Device Names

Select the display language of device names, either English or German.


Set IP address of the External Device.

Destination IP Address
Check with a network administrator about IP address. Do not set the duplicate IP
address.
Use Tag Data

Select the check box when using tag data (symbol addresses). This will enable you to select
the tags you want to use.
"5.6 When Using a Tag" (page 39)

GP-Pro EX Device/PLC Connection Manual

29

SIMATIC S7 Ethernet Driver


<LOGO! Series>
GP3000, GP-4100 Series, GP-4*01TM,
GP-Rear Module and LT3000 Series

GP4000 (excluding GP-4100 Series, GP-4*01TM and


GP-Rear Module) Series and IPC Series(PC/AT)

Setup Items

Setup Description

PLC Type

Select the External Device series.

Device Names

Select the display language of device names, either English or German.


Set IP address of the External Device.

Destination IP Address
Check with a network administrator about IP address. Do not set the duplicate IP
address.
Use Tag Data

Select the check box when using tag data (symbol addresses). This will enable you to select
the tags you want to use.
"5.6 When Using a Tag" (page 39)

GP-Pro EX Device/PLC Connection Manual

30

SIMATIC S7 Ethernet Driver

4.2

Setup Items in Offline Mode


Refer to the Maintenance/Troubleshooting guide for information on how to enter offline mode or
about the operation.
Cf. Maintenance/Troubleshooting Guide "Offline Mode"

Communication Settings
To display the setting screen, touch [Device/PLC Settings] from [Peripheral Settings] in offline mode. Touch the
External Device you want to set from the displayed list.

Setup Items

Setup Description

Port No.

Set the FETCH port No. and WRITE port No. of the Display. Select either [Fixed] or
[Auto]. When you select [Fixed], use an integer from 1024 to 65535 to enter the port No. of
the Display. When you select [Auto], the port No. will be automatically assigned regardless
of the entered value. When the connection type is OP Communication, the port number set
to [Port No. (FETCH)] implements communication.

Timeout (s)

Use an integer from 1 to 127 to enter the time (s) for which the Display waits for the
response from the External Device.

Retry

In case of no response from the External Device, use an integer from 0 to 255 to enter how
many times the Display retransmits the command.

Wait To Send (ms)

Use an integer from 0 to 255 to enter standby time (ms) for the Display from receiving
packets to transmitting next commands.

GP-Pro EX Device/PLC Connection Manual

31

SIMATIC S7 Ethernet Driver

Device Setting
To display the setting screen, touch [Device/PLC Settings] from [Peripheral Settings]. Touch the External Device
you want to set from the displayed list, and touch [Device].

Setup Items
Device/PLC Name

Setup Description
Select the External Device for device setting. Device name is a title of External Device set
with GP-Pro EX.(Initial value [PLC1])
Display the PLC type.

PLC TYPE
Please make a change of the PLC type by [Device Setting] of GP-Pro EX.
Set IP address of the External Device.
DEST IP ADDR
Check with a network administrator about IP address. Do not set the duplicate IP
address.
Display the connection type.
CONNECTION TYPE
Please make a change of the connection type by [Device Setting] of GP-Pro EX.
FETCH PORT NO.

Use an integer from 1024 to 65535 to enter the FETCH port No. of the External Device.
Available only if the PLC type is "S7-300/400 Series". Valid only when the connection
type is [FETH/WRITE].

WRITE PORT NO.

Use an integer from 1024 to 65535 to enter the WRITE port No. of the External Device.
Available only if the PLC type is "S7-300/400 Series". Valid only when the connection
type is [FETH/WRITE].

CPU RACK NO.

Use an integer from 0 to 7 to enter the rack number that External Device is mounted to.
Available only if the PLC type is "S7-300/400 Series". Valid only when the connection
type is [OP Communication].

GP-Pro EX Device/PLC Connection Manual

32

SIMATIC S7 Ethernet Driver

Setup Items

Setup Description

CPU SLOT NO.

Use an integer from 0 to 31 to enter the slot number that External Device is mounted to.
Available only if the PLC type is "S7-300/400 Series". Valid only when the connection
type is [OP Communication].

CONNECTION NO.

Use an integer from 0 to 7 to enter the connection number of the External Device.
Available only if the PLC type is "S7-200 Series".

MODULE POSITION

Use an integer from 0 to 6 to enter the module position of the External Device. Available
only if the PLC type is "S7-200 Series".

GP-Pro EX Device/PLC Connection Manual

33

SIMATIC S7 Ethernet Driver

Supported Device Addresses


Range of supported device address is shown in the table below. Please note that the actually supported range of
the devices varies depending on the External Device to be used. Please check the actual range in the manual of
your External Device.

5.1

S7-300/400 Series
This address can be specified as system data area.
Bit Address

Device

English

Word Address

German

English

German

32
bits

Remarks

Data Block
(OP Communication)

DB00001.DBX00000.0 DB65535.DBX65535.7

DB00001.DBW00000 DB65535.DBW65534

Data Block
(FETCH/WRITE)

DB00001.DBX00000.0 DB00255.DBX16383.7

DB00001.DBW00000 DB00255.DBW16382

Input

I00000.0 I00127.7

E00000.0 E00127.7

IW00000 IW00126

EW00000 EW00126

*1

Output

Q00000.0 Q00127.7

A00000.0 A00127.7

QW00000 QW00126

AW00000 AW00126

*1

Marker

M00000.0 - M00255.7

MW00000 - MW00254

Timer

-----

T00000 - T00255

Counter

-----

*1

C00000 C00255

Z00000 Z00255

*1

*1
*2 *3
*2 *3

When the connection type is FETCH / WRITE, to write the bit address, the Display first reads the word
address on the External Device. Next, the Display changes only the target bit from the word data, and
writes the entire word back to the External Device.
If you change the word address value from the ladder program while the Display reads and writes the
External Device data, the result may be incorrect.

*2

Write disable.

*3

Data Type varies depending on the connection type. When the connection type is OP Communication,
Data Type is BCD. When it is FETCH/WRITE, Data Type is binary.

Please refer to the GP-Pro EX Reference Manual for system data area.
Cf. GP-Pro EX Reference Manual "LS Area (Direct Access Method Area)"
Please refer to the precautions on manual notation for icons in the table.

"Manual Symbols and Terminology"

GP-Pro EX Device/PLC Connection Manual

34

SIMATIC S7 Ethernet Driver

5.2

S7-200 Series
This address can be specified as system data area.
Bit Address

Device

English

Variable

Word Address

German

English

V00000.0 - V10239.7

German

32
bits

Remarks

VW00000 - VW10238

Input

I00000.0 I00015.7

E00000.0 E00015.7

IW00000 IW00014

EW00000 EW00014

*1

Output

Q00000.0 Q00015.7

A00000.0 A00015.7

QW00000 QW00014

AW00000 AW00014

*2

Marker

M00000.0 - M00031.7

MW00000 - MW00030

Timer

-----

T00000 - T00255

Counter

-----

C00000 C00255

Z00000 Z00255

*3
*3

*1

Writing to the addresses IW0 to IW2 is disabled, depending on the CPU type. These addresses are
reserved for onboard I/O.

*2

Only when the External Device is in the EXECUTION mode, writing to the output device is enabled.
When the External Device switches to the STOP mode, the output device is reset.

*3

Write disable.

Please refer to the GP-Pro EX Reference Manual for system data area.
Cf. GP-Pro EX Reference Manual "LS Area (Direct Access Method Area)"
Please refer to the precautions on manual notation for icons in the table.

"Manual Symbols and Terminology"

GP-Pro EX Device/PLC Connection Manual

35

SIMATIC S7 Ethernet Driver

5.3

S7-1200 Series
This address can be specified as system data area.

Device

Bit Address
English

Word Address

German

English

German

Data Block

DB00001.DBX00000.0 DB65535.DBX65535.7

Input

I00000.0 I01023.7

E00000.0 E01023.7

IW00000 IW01022

EW00000 EW01022

Output

Q00000.0 Q01023.7

A00000.0 A01023.7

QW00000 QW01022

AW00000 AW01022

Marker

32
bits

DB00001.DBW00000 DB65535.DBW65534

M00000.0 - M08191.7

MW00000 - MW08190

Please refer to the GP-Pro EX Reference Manual for system data area.
Cf. GP-Pro EX Reference Manual "LS Area (Direct Access Method Area)"
Please refer to the precautions on manual notation for icons in the table.

"Manual Symbols and Terminology"

GP-Pro EX Device/PLC Connection Manual

36

Remarks

SIMATIC S7 Ethernet Driver

5.4

LOGO! Series
This address can be specified as system data area.
Bit Address

Device

English

Variable

Marker

German

English

V00000.0 - V00849.7

German

32
bits

VW00000 - VW00848

Read

I00000.0 I00003.7

E00000.0 E00003.7

Write

I00000.0 I00002.7

E00000.0 E00002.7

Q00000.0 Q00001.7

A00000.0 A00001.7

Input

Output

Word Address

IW00000 IW00002

EW00000 EW00002

QW00000

AW00000

M00000.0 - M00003.7

MW00000 - MW00002

Please refer to the GP-Pro EX Reference Manual for system data area.
Cf. GP-Pro EX Reference Manual "LS Area (Direct Access Method Area)"
Please refer to the precautions on manual notation for icons in the table.

"Manual Symbols and Terminology"

GP-Pro EX Device/PLC Connection Manual

37

Remarks

SIMATIC S7 Ethernet Driver

5.5

S7-1500 Series
This address can be specified as system data area.
Bit Address

Device

English

Word Address

German

English

German

Data Block
(OP Communication)

DB00001.DBX00000.0 DB59999.DBX65533.7

Input

I00000.0 I32767.7

E00000.0 E32767.7

IW00000 IW32766

EW00000 EW32766

Output

Q00000.0 Q32767.7

A00000.0 A32767.7

QW00000 QW32766

AW00000 AW32766

Marker

32
bits

DB00001.DBW00000 DB59999.DBW65532

M00000.0 - M16383.7

MW00000 - MW16382

Please refer to the GP-Pro EX Reference Manual for system data area.
Cf. GP-Pro EX Reference Manual "LS Area (Direct Access Method Area)"
Please refer to the precautions on manual notation for icons in the table.

"Manual Symbols and Terminology"

GP-Pro EX Device/PLC Connection Manual

38

Remarks

SIMATIC S7 Ethernet Driver

5.6

When Using a Tag


S7-300/400 Series
This address can be specified as system data area.

Device

BOOL

BYTE

SINT
USINT

Bit Address

Word Address

32
bits

Single
Tag

<TAGNAME>

1D
Array

<TAGNAME>[xl] <TAGNAME>[xh]

2D
Array

<TAGNAME>[xl,yl] <TAGNAME>[xh,yh]

3D
Array

<TAGNAME>[xl,yl,zl] <TAGNAME>[xh,yh,zh]

4D
Array

<TAGNAME>[xl,yl,zl,wl] <TAGNAME>[xh,yh,zh,wh]

5D
Array

<TAGNAME>[xl,yl,zl,vl,wl] <TAGNAME>[xh,yh,zh,vh,wh]

6D
Array

<TAGNAME>[xl,yl,zl,ul,vl,wl]
<TAGNAME>[xh,yh,zh,uh,vh,
wh]

Single
Tag

<TAGNAME>.00 <TAGNAME>.07

<TAGNAME>

1D
Array

<TAGNAME>[xl].00 <TAGNAME>[xh].07

<TAGNAME>[xl] <TAGNAME>[xh]

2D
Array

<TAGNAME>[xl,yl].00 <TAGNAME>[xh,yh].07

<TAGNAME>[xl,yl] <TAGNAME>[xh,yh]

3D
Array

<TAGNAME>[xl,yl,zl].00 <TAGNAME>[xh,yh,zh].07

<TAGNAME>[xl,yl,zl] <TAGNAME>[xh,yh,zh]

4D
Array

<TAGNAME>[xl,yl,zl,wl].00 - <TAGNAME>[xl,yl,zl,wl] <TAGNAME>[xh,yh,zh,wh].07 <TAGNAME>[xh,yh,zh,wh]

5D
Array

<TAGNAME>[xl,yl,zl,vl,wl].0
0<TAGNAME>[xl,yl,zl,vl,wl] <TAGNAME>[xh,yh,zh,vh,wh] <TAGNAME>[xh,yh,zh,vh,wh]
.07

6D
Array

<TAGNAME>[xl,yl,zl,ul,vl,wl]
.00 <TAGNAME>[xh,yh,zh,uh,vh,
wh].07

<TAGNAME>[xl,yl,zl,ul,vl,wl]
<TAGNAME>[xh,yh,zh,uh,vh,
wh]

Single
Tag

<TAGNAME>.00 <TAGNAME>.07

<TAGNAME>

GP-Pro EX Device/PLC Connection Manual

39

Remarks

*1 *2

*1 *2

*1

SIMATIC S7 Ethernet Driver

Device

INT
WORD

UINT

DINT
DWORD

UDINT

Bit Address

Word Address

Single
Tag

<TAGNAME>.00 <TAGNAME>.15

<TAGNAME>

1D
Array

<TAGNAME>[xl].00 <TAGNAME>[xh].15

<TAGNAME>[xl] <TAGNAME>[xh]

2D
Array

<TAGNAME>[xl,yl].00 <TAGNAME>[xh,yh].15

<TAGNAME>[xl,yl] <TAGNAME>[xh,yh]

3D
Array

<TAGNAME>[xl,yl,zl].00 <TAGNAME>[xh,yh,zh].15

<TAGNAME>[xl,yl,zl] <TAGNAME>[xh,yh,zh]

4D
Array

<TAGNAME>[xl,yl,zl,wl].00 - <TAGNAME>[xl,yl,zl,wl] <TAGNAME>[xh,yh,zh,wh].15 <TAGNAME>[xh,yh,zh,wh]

5D
Array

<TAGNAME>[xl,yl,zl,vl,wl].0
0<TAGNAME>[xl,yl,zl,vl,wl] <TAGNAME>[xh,yh,zh,vh,wh] <TAGNAME>[xh,yh,zh,vh,wh]
.15

6D
Array

<TAGNAME>[xl,yl,zl,ul,vl,wl]
.00 <TAGNAME>[xh,yh,zh,uh,vh,
wh].15

<TAGNAME>[xl,yl,zl,ul,vl,wl]
<TAGNAME>[xh,yh,zh,uh,vh,
wh]

Single
Tag

<TAGNAME>.00 <TAGNAME>.15

<TAGNAME>

Single
Tag

<TAGNAME>.00 <TAGNAME>.31

<TAGNAME>

1D
Array

<TAGNAME>[xl].00 <TAGNAME>[xh].31

<TAGNAME>[xl] <TAGNAME>[xh]

2D
Array

<TAGNAME>[xl,yl].00 <TAGNAME>[xh,yh].31

<TAGNAME>[xl,yl] <TAGNAME>[xh,yh]

3D
Array

<TAGNAME>[xl,yl,zl].00 <TAGNAME>[xh,yh,zh].31

<TAGNAME>[xl,yl,zl] <TAGNAME>[xh,yh,zh]

4D
Array

<TAGNAME>[xl,yl,zl,wl].00 - <TAGNAME>[xl,yl,zl,wl] <TAGNAME>[xh,yh,zh,wh].31 <TAGNAME>[xh,yh,zh,wh]

5D
Array

<TAGNAME>[xl,yl,zl,vl,wl].0
0<TAGNAME>[xl,yl,zl,vl,wl] <TAGNAME>[xh,yh,zh,vh,wh] <TAGNAME>[xh,yh,zh,vh,wh]
.31

6D
Array

<TAGNAME>[xl,yl,zl,ul,vl,wl]
.00 <TAGNAME>[xh,yh,zh,uh,vh,
wh].31

<TAGNAME>[xl,yl,zl,ul,vl,wl]
<TAGNAME>[xh,yh,zh,uh,vh,
wh]

Single
Tag

<TAGNAME>.00 <TAGNAME>.31

<TAGNAME>

GP-Pro EX Device/PLC Connection Manual

40

32
bits

Remarks

*1 *2 *3

*1

*1 *2

*1

SIMATIC S7 Ethernet Driver

Device

DATE*4
REAL
TIME
TIME_OF_DA
Y

DATE_AND_
TIME

Bit Address

Word Address

Single
Tag

<TAGNAME>

1D
Array

<TAGNAME>[xl] <TAGNAME>[xh]

2D
Array

<TAGNAME>[xl,yl] <TAGNAME>[xh,yh]

3D
Array

<TAGNAME>[xl,yl,zl] <TAGNAME>[xh,yh,zh]

4D
Array

<TAGNAME>[xl,yl,zl,wl] <TAGNAME>[xh,yh,zh,wh]

5D
Array

<TAGNAME>[xl,yl,zl,vl,wl] <TAGNAME>[xh,yh,zh,vh,wh]

6D
Array

<TAGNAME>[xl,yl,zl,ul,vl,wl]
<TAGNAME>[xh,yh,zh,uh,vh,
wh]

Single
Tag

<TAGNAME>

1D
Array

<TAGNAME>[xl] <TAGNAME>[xh]

2D
Array

<TAGNAME>[xl,yl] <TAGNAME>[xh,yh]

3D
Array

<TAGNAME>[xl,yl,zl] <TAGNAME>[xh,yh,zh]

4D
Array

<TAGNAME>[xl,yl,zl,wl] <TAGNAME>[xh,yh,zh,wh]

5D
Array

<TAGNAME>[xl,yl,zl,vl,wl] <TAGNAME>[xh,yh,zh,vh,wh]

6D
Array

<TAGNAME>[xl,yl,zl,ul,vl,wl]
<TAGNAME>[xh,yh,zh,uh,vh,
wh]

GP-Pro EX Device/PLC Connection Manual

41

32
bits

Remarks

*1 *2

*1 *2 *5

SIMATIC S7 Ethernet Driver

Device

STRING

*1

Bit Address

Word Address

Single
Tag

<TAGNAME>

1D
Array

<TAGNAME>[xl] <TAGNAME>[xh]

2D
Array

<TAGNAME>[xl,yl] <TAGNAME>[xh,yh]

3D
Array

<TAGNAME>[xl,yl,zl] <TAGNAME>[xh,yh,zh]

4D
Array

<TAGNAME>[xl,yl,zl,wl] <TAGNAME>[xh,yh,zh,wh]

5D
Array

<TAGNAME>[xl,yl,zl,vl,wl] <TAGNAME>[xh,yh,zh,vh,wh]

6D
Array

<TAGNAME>[xl,yl,zl,ul,vl,wl]
<TAGNAME>[xh,yh,zh,uh,vh,
wh]

32
bits

Remarks

*1 *2

<TAGNAME>: For structures, Tag Name includes the structure name. The maximum length of the Tag Name
is 255 characters, which includes delimiters and the element number.
Example
BOOL type single tag:
"BOOLSYMBOL"
BOOL type 1D array:
"BOOL1D[10]"
WORD type 2D array:
"WORD2D[10,10]"
UDINT type 3D array:
"UDINT[0,1,2]"
User-defined structure:
"STRUCT001.STRINGSYM"
You cannot start names with any of the following text:
LS, USER, SCR, PRT

*2

The number of elements for each dimension is shown from "l" (Number of minimum element) to "h" (Number
of maximum element).

*3

By default, the system data area is set up with 16 words. Even if you want to use less than 16 words for the
system data area, you have to map a 16 word (or larger) array tag and then select the items for the system data
area.

*4

Handled as 16-bit devices in the External Device, but as 32-bit devices in GP-Pro EX.

*5

64-bit device

To use tags, you need to import Tag Data (symbol addresses).


For information about how to import, please refer to GP-Pro EX Reference Manual.
Cf. GP-Pro EX Reference Manual, "Using Device/PLC Tags"
When the tag of the "S5TIME" data type is imported, the data type is changed to
"WORD". When the tag of the "CHAR" data type is imported, the data type is
changed to "STRING (CHAR)".

GP-Pro EX Device/PLC Connection Manual

42

SIMATIC S7 Ethernet Driver

Please refer to the GP-Pro EX Reference Manual for system data area.
Cf. GP-Pro EX Reference Manual "LS Area (Direct Access Method Area)"
Please refer to the precautions on manual notation for icons in the table.

"Manual Symbols and Terminology"

GP-Pro EX Device/PLC Connection Manual

43

SIMATIC S7 Ethernet Driver

S7-200/1200/1500/LOGO! Series
This address can be specified as system data area.

Device

Bit Address

Word Address

32
bits

*1

*1

Remarks

BOOL

Single Tag

<TAGNAME>

BYTE
SINT
USINT

Single Tag

<TAGNAME>.00 <TAGNAME>.07

<TAGNAME>

INT
WORD
UINT

Single Tag

<TAGNAME>.00 <TAGNAME>.15

<TAGNAME>

*1 *2

DINT
DWORD
UDINT

Single Tag

<TAGNAME>.00 <TAGNAME>.31

<TAGNAME>

*1

DATE*3
REAL
TIME
TIME_OF_DA
Y

Single Tag

<TAGNAME>

*1

DATE_AND_
TIME

Single Tag

<TAGNAME>

*1 *4

STRING

Single Tag

<TAGNAME>

*1

*1

<TAGNAME>: For structures, Tag Name includes the structure name. The maximum length of the Tag Name
is 255 characters, which includes delimiters and the element number.
Example:
BOOL type single tag:
"BOOLSYMBOL"
User-defined structure:
"STRUCT001.STRINGSYM"
You cannot start names with any of the following text:
LS, USER, SCR, PRT

*2

Only one of the system data area items can be used.

*3

Handled as 16-bit devices in the External Device, but as 32-bit devices in GP-Pro EX.

*4

64-bit device

You cannot import S7-200/1200/1500/LOGO! series tag data (symbol addresses).


Please refer to the GP-Pro EX Reference Manual for system data area.
Cf. GP-Pro EX Reference Manual "LS Area (Direct Access Method Area)"
Please refer to the precautions on manual notation for icons in the table.

"Manual Symbols and Terminology"

GP-Pro EX Device/PLC Connection Manual

44

SIMATIC S7 Ethernet Driver

Device Code and Address Code


Use device code and address code when you select "Device Type & Address" for the address type in data displays.
Device Name
English

German

Device Code
(HEX)

DB

DB

0000

(Data Block No. x 0x10000)


+ Value of (word address
divided by 2)

Input

0080

Value of word address


divided by 2

Output

0081

Value of word address


divided by 2

Marker

0082

Value of word address


divided by 2

Timer

0060

Word Address

Counter

0061

Word Address

Variable

0001

Value of word address


divided by 2

Device

Data Block

GP-Pro EX Device/PLC Connection Manual

45

Address Code

SIMATIC S7 Ethernet Driver

Error Messages
Error messages are displayed on the Display screen as follows: "No.: Device Name: Error Message (Error
Occurrence Area)". Each description is shown below.
Item

Description

No.

Error No.

Device Name

Name of the External Device where error occurs. Device name is a title of the External
Device set with GP-Pro EX. (Initial value [PLC1])

Error Message

Displays messages related to the error which occurs.


Displays IP address or device address of the External Device where error occurs, or error
codes received from the External Device.

Error Occurrence Area


IP address is displayed such as "IP address (Decimal): MAC address (Hex)".
Device address is displayed such as "Address: Device address".
Received error codes are displayed such as "Decimal [Hex]".

Display Examples of Error Messages


"RHAA035: PLC1: Error has been responded for device write command (Error Code: 2 [02H])"

Refer to your External Device manual for details on received error codes.
Refer to "Display-related errors" in "Maintenance/Troubleshooting Guide" for details on the error
messages common to the driver.

Error Code Peculiar to External Device


<Connection type: FETCH/WRITE>
Error Code
0x09

Description

Comment

Address Error: Trying to access an address


that does not exist.

Check the address and correct it. It may be


out of the address range, or DB may not be
set to the External Device.

<Connection type: OP Communication>


Error Code

Description

Comment

0x05

Trying to access an address that does not


exist.

Check the address range.

0x0A

Trying to access a DB that does not exist.

Check that DB is set.

GP-Pro EX Device/PLC Connection Manual

46

You might also like