Professional Documents
Culture Documents
SIMATIC S7 Ethernet
Driver
System Configuration....................................................................................................... 3
Error Messages.............................................................................................................. 46
Introduction
This manual describes how to connect the Display and the External Device (target PLC).
In this manual, the connection procedure will be described by following the below sections:
System Configuration
This section shows the types of External
Devices which can be connected and SIO
type.
Setup Items
This section describes communication
setup items on the Display.
Set communication settings of the Display
with GP-Pro Ex or in offline mode.
Operation
System Configuration
The system configuration in the case when the External Device and the Display are connected is shown.
Series
SIMATIC S7-200
Series
SIMATIC S7-300
Series
CPU
CPU222
CPU224
CPU224 XP
CPU226
Link I/F
CP 243-1 IT*2
CP 243-1
CPU312IFM
CPU313
CPU314
CPU314IFM
CPU315
CPU315-2 DP
CPU316
CPU316-2 DP
CPU318-2
CPU315-2 PN/DP
CPU317-2 PN/DP
CPU319-3 PN/DP
CP 343-1 IT
CP 343-1
CPU315-2 PN/DP
CPU317-2 PN/DP
CPU319-3 PN/DP
Ethernet interface
on CPU*3
SIO Type*1
Setting
Example
Ethernet
(TCP)
(OP Communication)
Setting
Example 3
(page 13)
Ethernet
(TCP)
(FETCH/WRITE)
Setting
Example 1
(page 7)
Ethernet
(TCP)
(OP Communication)
Setting
Example 2
(page 10)
Ethernet
(TCP)
(OP Communication)
Setting
Example 2
(page 10)
Ethernet
(TCP)
(FETCH/WRITE)
Setting
Example 1
(page 7)
Ethernet
(TCP)
(OP Communication)
Setting
Example 2
(page 10)
CPU412-1
CPU412-2 DP
CPU413-1
CPU413-2 DP
CPU414-1
CPU414-2 DP
CPU414-3 DP
CPU416-1
CPU416-2 DP
CPU416-3 DP
CPU417-4
CPU414-3PN/DP
CPU416-3PN/DP
CP 443-1 IT
CP 443-1
CPU414-3PN/DP
CPU416-3PN/DP
Ethernet interface
on CPU*3
Ethernet
(TCP)
(OP Communication)
Setting
Example 2
(page 10)
SIMATIC S7-1200
Series
CPU1211C
CPU1212C
CPU1214C
PROFINET
interface on CPU*4
Ethernet
(TCP)
(OP Communication)
Setting
Example 4
(page 16)
LOGO! Series
OBA7
Ethernet interface
on CPU*3
Ethernet
(TCP)
(OP Communication)
Setting
Example 5
(page 19)
SIMATIC S7-400
Series
Series
CPU
SIMATIC S7-1500
Series
CPU1511-1 PN
CPU1513-1 PN
CPU1515-2 PN
CPU1516-3 PN/DP
CPU1518-4 PN/DP
CPU1516F-3 PN/DP
CPU1518F-4 PN/DP
*1
SIO Type*1
Link I/F
PROFINET
interface on CPU
Ethernet
(TCP)
(OP Communication)
Setting
Example
Setting
Example 6
(page 22)
*2
CP 243-1 IT and CP 243-1 can use the version of CPU above Rel.1.20.
*3
The Ethernet interface in the CPU only supports OP Communication. FETCH/WRITE cannot be used.
*4
The PROFINET interface in the CPU only supports OP Communication. FETCH/WRITE cannot be used.
Connection Configuration
1:1 Connection
Display
External Device
HUB
1:n Connection
Max 16 units
Display
External Device
External Device
HUB
n:1 Connection
Max 32 units
Display
Display
External Device
HUB
The number of connectable Displays depends on the External Device.
The number of connectable Display depends on the External Device.
Please refer to the External Device manual for more details.
The following limitations apply when using the LOGO! series:
1:n connections require a network switch.
n:1 connection is not supported.
You cannot use the Display if the ladder software is online.
Setup Items
Setup Description
Number of Devices/
PLCs
Manufacturer
Select the manufacturer of the External Device to be connected. Select "Siemens AG".
Series
Select a model (series) of the External Device to be connected and connection method.
Select "SIMATIC S7 Ethernet".
Check the External Device which can be connected in "SIMATIC S7 Ethernet" in system
configuration.
"1 System Configuration" (page 3)
Port
Check this option when you synchronize the system data area of Display and the device
(memory) of External Device. When synchronized, you can use the ladder program of
External Device to switch the display or display the window on the display.
Cf. GP-Pro EX Reference Manual "LS Area (Direct Access Method Area)"
This can also be set in GP-Pro EX or in the Display's offline mode.
Cf. GP-Pro EX Reference Manual "Display Unit (System Area) Settings Guide"
Cf. Maintenance/Troubleshooting Manual "Main Unit - System Area Settings"
Communication Settings
Examples of communication settings of the Display and the External Device, recommended by Pro-face, are
shown.
3.1
Setting Example 1
GP-Pro EX Settings
Communication Settings
To display the setup screen, from the [Project] menu, point to [System Settings] and select [Device/PLC].
Specific Settings] in the [Device/PLC] window, click [Add Device] to add another External Device.
GP3000, GP-4100 Series, GP-4*01TM,
GP-Rear Module and LT3000 Series
Notes
Check with a network administrator about IP address. Do not set the duplicate IP address.
You need to set IP address on the Display in the offline mode of the Display.
Notes
The FETCH ports Partner that is set in the ladder software communication setting dialog box must be the
same as the [Port No. (FETCH)] set in the GP-Pro EX communication settings. Likewise, the WRITE ports
Partner must be the same as the [Port No. (WRITE)].
If each Partner of the FETCH port and the WRITE port is blank, the [Port No.] can be also set to [Auto].
Check with a network administrator about IP address. Do not set the duplicate IP address.
The "Keep Alive" feature of Siemens CP Module is not supported. Please set the "Keep Alive" to 0.
When the Display is turned off and on again during communication with the External Device or is switched to
offline mode and then back to online mode, it may take several tens of seconds before the communication is
resumed.
3.2
Setting Example 2
GP-Pro EX Settings
Communication Settings
To display the setup screen, from the [Project] menu, point to [System Settings] and select [Device/PLC].
Port No. that is set to [Port No. (FETCH)] performs communication in OP Communication. Port
No. that is set to [Port No. (WRITE)] is not used.
10
Specific Settings] in the [Device/PLC] window, click [Add Device] to add another External Device.
GP3000, GP-4100 Series, GP-4*01TM,
GP-Rear Module and LT3000 Series
Notes
Check with a network administrator about IP address. Do not set the duplicate IP address.
You need to set IP address on the Display in the offline mode of the Display.
11
Notes
Check that the CPU rack number and CPU slot number to be used for communication are the same as the GPPro EX setting. If the setting is not the same, communication cannot be conducted.
Check with a network administrator about IP address. Do not set the duplicate IP address.
When the Display is turned off and on again during communication with the External Device or is switched to
offline mode and then back to online mode, it may take several tens of seconds before the communication is
resumed.
12
3.3
Setting Example 3
GP-Pro EX Settings
Communication Settings
To display the setup screen, from the [Project] menu, point to [System Settings] and select [Device/PLC].
Port No. that is set to [Port No. (FETCH)] performs communication in OP Communication. Port
No. that is set to [Port No. (WRITE)] is not used.
Set the "Timeout" value to "3" (sec) or more.
13
Specific Settings] in the [Device/PLC] window, click [Add Device] to add another External Device.
GP3000, GP-4100 Series, GP-4*01TM,
GP-Rear Module and LT3000 Series
Notes
Check with a network administrator about IP address. Do not set the duplicate IP address.
You need to set IP address on the Display in the offline mode of the Display.
14
Select "This is a Server Connection" to connect the External Device to the Display.
In the "Local Properties (Server)" area, select "Accept all connection requests." to allow connections from
all IP addresses.
Clear the "Enable the Keep Alive function for this connection." check box because the Display does not
support KeepAlive.
The connection number is displayed in this dialog box. If the connection number is "1", for
example, [Connection 1] is displayed.
Notes
Check with your network administrator about the IP address. Do not duplicate IP addresses.
The subroutine "ETH0_CTRL" must be called by the ladder program every scan.
When the Display is turned off and on again during communication with the External Device or is switched to
offline mode and then back to online mode, it may take several tens of seconds before the communication is
resumed.
15
3.4
Setting Example 4
GP-Pro EX Settings
Communication Settings
To display the setup screen, from the [Project] menu, point to [System Settings] and select [Device/PLC].
Port No. that is set to [Port No. (FETCH)] performs communication in OP Communication. Port
No. that is set to [Port No. (WRITE)] is not used.
Set the "Timeout" value to "3" (sec) or more.
16
Specific Settings] in the [Device/PLC] window, click [Add Device] to add another External Device.
GP3000, GP-4100 Series, GP-4*01TM,
GP-Rear Module and LT3000 Series
Notes
Check with a network administrator about IP address. Do not set the duplicate IP address.
You need to set IP address on the Display in the offline mode of the Display.
17
Setting Value
IP address
192.168.0.1
Subnet mask
255.255.255.0
18
3.5
Setting Example 5
GP-Pro EX Settings
Communication Settings
To display the setup screen, from the [Project] menu, point to [System Settings] and select [Device/PLC].
Port No. that is set to [Port No. (FETCH)] performs communication in OP Communication. Port
No. that is set to [Port No. (WRITE)] is not used.
Set the "Timeout" value to "3" (sec) or more.
19
Specific Settings] in the [Device/PLC] window, click [Add Device] to add another External Device.
GP3000, GP-4100 Series, GP-4*01TM,
GP-Rear Module and LT3000 Series
Notes
Check with a network administrator about IP address. Do not set the duplicate IP address.
You need to set IP address on the Display in the offline mode of the Display.
20
Setting Value
IP address
192.168.0.1
Subnet mask
255.255.255.0
Gateway
192.168.0.10
(4) From [Peer-to-Peer Connections], right-click [Ethernet Connections] and from the shortcut menu select [Add
Connection].
(5) Double-click the added connection and select [Server Connection].
(6) In [Local Properties (Server)], select the [Connect with an Operator Panel (OP)] and [Accept all connection
requests] check boxes. In [Remote Properties (Client)], set [TSAP] to "02.00".
(7) Click [OK] to close the dialog box.
(8) Update the Parameter VM Mapping and then download the communication setting to the External Device.
21
3.6
Setting Example 6
GP-Pro EX Settings
Communication Settings
To display the setup screen, from the [Project] menu, point to [System Settings] and select [Device/PLC].
Port No. that is set to [Port No. (FETCH)] performs communication in OP Communication. Port
No. that is set to [Port No. (WRITE)] is not used.
Set the "Timeout" value to "3" (sec) or more.
22
Specific Settings] in the [Device/PLC] window, click [Add Device] to add another External Device.
GP3000, GP-4100 Series, GP-4*01TM,
GP-Rear Module and LT3000 Series
Notes
To use a S7-1500 Series device, from the [PLC Type] list select [S7-1200 Series].
Check with a network administrator about IP address. Do not set the duplicate IP address.
You need to set IP address on the Display in the offline mode of the Display.
23
Setting Value
IP address
192.168.0.1
Subnet mask
255.255.255.0
(5) In the project tree, right-click the data block and select [Properties].
(6) In the [General] tab, select [Attributes]. Clear the [Optimized block access] check box, and click [OK]. Clear
the check boxes of all data blocks.
(7) In the project tree, select [Device configuration].
(8) In the [General] tab, select [Protection]. Select the [Permit access with PUT/GET communication from
remote partner] check box, and click [OK].
(9) Set the data block, and then compile the project.
(10)Save and transfer the project to the External Device.
When you compile the project, an offset is mapped to each element in the data block.
Specify the addresses as follows.
Example: When the following offsets are applied to elements of data block [DB2].
Name
Data type
Address notation of
GP-Pro EX
Offset
Data1
Bool
0.0
DB00002.DBX00000.0
Data2
Word
2.0
DB00002.DBW00002
Data3
DWord
4.0
DB00002.DBW00004
24
Setup Items
Set communication settings of the Display with GP-Pro EX or in offline mode of the Display.
The setting of each parameter must be identical to that of External Device.
4.1
Setup Items
Setup Description
Port No.
Use an integer from 1024 to 65535 to enter FETCH port number and WRITE number of
display. If a check is put in [Auto], port number is set automatically.
When the connection type is OP Communication, the port number set to [Port No.
(FETCH)] implements communication.
Timeout
Use an integer from 1 to 127 to enter the time (s) for which the Display waits for the
response from the External Device.
Retry
In case of no response from the External Device, use an integer from 0 to 255 to enter how
many times the Display retransmits the command.
Wait To Send
Use an integer from 0 to 255 to enter standby time (ms) for the Display from receiving
packets to transmitting next commands.
25
Device Setting
To display the [Individual Device Settings] dialog box, from [Device-Specific Settings] in the [Device/PLC]
window, select the external device and click [Settings]
Specific Settings] in the [Device/PLC] window, click [Add Device] to add another External Device.
Setting contents of device setting differs depending on the connection type (SIMATIC S7-300/400 Series only).
<S7-300/400 Series Connection type: FETCH/WRITE>
GP3000, GP-4100 Series, GP-4*01TM,
GP-Rear Module and LT3000 Series
Setup Items
Setup Description
PLC Type
Device Names
Destination IP Address
Check with a network administrator about IP address. Do not set the duplicate IP
address.
Connection Type
FETCH Port
Use an integer from 1024 to 65535 to enter the FETCH port No. of the External Device.
WRITE Port
Use an integer from 1024 to 65535 to enter the WRITE port No. of the External Device.
26
Setup Items
Setup Description
PLC Type
Device Names
Destination IP Address
Check with a network administrator about IP address. Do not set the duplicate IP
address.
Connection Type
Use an integer from 0 to 7 to enter the CPU rack number of the External Device.
Use an integer from 0 to 31 to enter the CPU slot number of the External Device.
Select the check box when using tag data (symbol addresses). This will enable you to select
the tags you want to use.
"5.6 When Using a Tag" (page 39)
27
Setup Items
Setup Description
PLC Type
Device Names
Destination IP Address
Check with a network administrator about IP address. Do not set the duplicate IP
address.
Connection Number
Use an integer from 0 to 7 to enter the connection number of the External Device.
Module Position
Use an integer from 0 to 6 to enter the module position of the External Device.
Select the check box when using tag data (symbol addresses). This will enable you to select
the tags you want to use.
"5.6 When Using a Tag" (page 39)
28
Setup Items
Setup Description
PLC Type
Device Names
Destination IP Address
Check with a network administrator about IP address. Do not set the duplicate IP
address.
Use Tag Data
Select the check box when using tag data (symbol addresses). This will enable you to select
the tags you want to use.
"5.6 When Using a Tag" (page 39)
29
Setup Items
Setup Description
PLC Type
Device Names
Destination IP Address
Check with a network administrator about IP address. Do not set the duplicate IP
address.
Use Tag Data
Select the check box when using tag data (symbol addresses). This will enable you to select
the tags you want to use.
"5.6 When Using a Tag" (page 39)
30
4.2
Communication Settings
To display the setting screen, touch [Device/PLC Settings] from [Peripheral Settings] in offline mode. Touch the
External Device you want to set from the displayed list.
Setup Items
Setup Description
Port No.
Set the FETCH port No. and WRITE port No. of the Display. Select either [Fixed] or
[Auto]. When you select [Fixed], use an integer from 1024 to 65535 to enter the port No. of
the Display. When you select [Auto], the port No. will be automatically assigned regardless
of the entered value. When the connection type is OP Communication, the port number set
to [Port No. (FETCH)] implements communication.
Timeout (s)
Use an integer from 1 to 127 to enter the time (s) for which the Display waits for the
response from the External Device.
Retry
In case of no response from the External Device, use an integer from 0 to 255 to enter how
many times the Display retransmits the command.
Use an integer from 0 to 255 to enter standby time (ms) for the Display from receiving
packets to transmitting next commands.
31
Device Setting
To display the setting screen, touch [Device/PLC Settings] from [Peripheral Settings]. Touch the External Device
you want to set from the displayed list, and touch [Device].
Setup Items
Device/PLC Name
Setup Description
Select the External Device for device setting. Device name is a title of External Device set
with GP-Pro EX.(Initial value [PLC1])
Display the PLC type.
PLC TYPE
Please make a change of the PLC type by [Device Setting] of GP-Pro EX.
Set IP address of the External Device.
DEST IP ADDR
Check with a network administrator about IP address. Do not set the duplicate IP
address.
Display the connection type.
CONNECTION TYPE
Please make a change of the connection type by [Device Setting] of GP-Pro EX.
FETCH PORT NO.
Use an integer from 1024 to 65535 to enter the FETCH port No. of the External Device.
Available only if the PLC type is "S7-300/400 Series". Valid only when the connection
type is [FETH/WRITE].
Use an integer from 1024 to 65535 to enter the WRITE port No. of the External Device.
Available only if the PLC type is "S7-300/400 Series". Valid only when the connection
type is [FETH/WRITE].
Use an integer from 0 to 7 to enter the rack number that External Device is mounted to.
Available only if the PLC type is "S7-300/400 Series". Valid only when the connection
type is [OP Communication].
32
Setup Items
Setup Description
Use an integer from 0 to 31 to enter the slot number that External Device is mounted to.
Available only if the PLC type is "S7-300/400 Series". Valid only when the connection
type is [OP Communication].
CONNECTION NO.
Use an integer from 0 to 7 to enter the connection number of the External Device.
Available only if the PLC type is "S7-200 Series".
MODULE POSITION
Use an integer from 0 to 6 to enter the module position of the External Device. Available
only if the PLC type is "S7-200 Series".
33
5.1
S7-300/400 Series
This address can be specified as system data area.
Bit Address
Device
English
Word Address
German
English
German
32
bits
Remarks
Data Block
(OP Communication)
DB00001.DBX00000.0 DB65535.DBX65535.7
DB00001.DBW00000 DB65535.DBW65534
Data Block
(FETCH/WRITE)
DB00001.DBX00000.0 DB00255.DBX16383.7
DB00001.DBW00000 DB00255.DBW16382
Input
I00000.0 I00127.7
E00000.0 E00127.7
IW00000 IW00126
EW00000 EW00126
*1
Output
Q00000.0 Q00127.7
A00000.0 A00127.7
QW00000 QW00126
AW00000 AW00126
*1
Marker
M00000.0 - M00255.7
MW00000 - MW00254
Timer
-----
T00000 - T00255
Counter
-----
*1
C00000 C00255
Z00000 Z00255
*1
*1
*2 *3
*2 *3
When the connection type is FETCH / WRITE, to write the bit address, the Display first reads the word
address on the External Device. Next, the Display changes only the target bit from the word data, and
writes the entire word back to the External Device.
If you change the word address value from the ladder program while the Display reads and writes the
External Device data, the result may be incorrect.
*2
Write disable.
*3
Data Type varies depending on the connection type. When the connection type is OP Communication,
Data Type is BCD. When it is FETCH/WRITE, Data Type is binary.
Please refer to the GP-Pro EX Reference Manual for system data area.
Cf. GP-Pro EX Reference Manual "LS Area (Direct Access Method Area)"
Please refer to the precautions on manual notation for icons in the table.
34
5.2
S7-200 Series
This address can be specified as system data area.
Bit Address
Device
English
Variable
Word Address
German
English
V00000.0 - V10239.7
German
32
bits
Remarks
VW00000 - VW10238
Input
I00000.0 I00015.7
E00000.0 E00015.7
IW00000 IW00014
EW00000 EW00014
*1
Output
Q00000.0 Q00015.7
A00000.0 A00015.7
QW00000 QW00014
AW00000 AW00014
*2
Marker
M00000.0 - M00031.7
MW00000 - MW00030
Timer
-----
T00000 - T00255
Counter
-----
C00000 C00255
Z00000 Z00255
*3
*3
*1
Writing to the addresses IW0 to IW2 is disabled, depending on the CPU type. These addresses are
reserved for onboard I/O.
*2
Only when the External Device is in the EXECUTION mode, writing to the output device is enabled.
When the External Device switches to the STOP mode, the output device is reset.
*3
Write disable.
Please refer to the GP-Pro EX Reference Manual for system data area.
Cf. GP-Pro EX Reference Manual "LS Area (Direct Access Method Area)"
Please refer to the precautions on manual notation for icons in the table.
35
5.3
S7-1200 Series
This address can be specified as system data area.
Device
Bit Address
English
Word Address
German
English
German
Data Block
DB00001.DBX00000.0 DB65535.DBX65535.7
Input
I00000.0 I01023.7
E00000.0 E01023.7
IW00000 IW01022
EW00000 EW01022
Output
Q00000.0 Q01023.7
A00000.0 A01023.7
QW00000 QW01022
AW00000 AW01022
Marker
32
bits
DB00001.DBW00000 DB65535.DBW65534
M00000.0 - M08191.7
MW00000 - MW08190
Please refer to the GP-Pro EX Reference Manual for system data area.
Cf. GP-Pro EX Reference Manual "LS Area (Direct Access Method Area)"
Please refer to the precautions on manual notation for icons in the table.
36
Remarks
5.4
LOGO! Series
This address can be specified as system data area.
Bit Address
Device
English
Variable
Marker
German
English
V00000.0 - V00849.7
German
32
bits
VW00000 - VW00848
Read
I00000.0 I00003.7
E00000.0 E00003.7
Write
I00000.0 I00002.7
E00000.0 E00002.7
Q00000.0 Q00001.7
A00000.0 A00001.7
Input
Output
Word Address
IW00000 IW00002
EW00000 EW00002
QW00000
AW00000
M00000.0 - M00003.7
MW00000 - MW00002
Please refer to the GP-Pro EX Reference Manual for system data area.
Cf. GP-Pro EX Reference Manual "LS Area (Direct Access Method Area)"
Please refer to the precautions on manual notation for icons in the table.
37
Remarks
5.5
S7-1500 Series
This address can be specified as system data area.
Bit Address
Device
English
Word Address
German
English
German
Data Block
(OP Communication)
DB00001.DBX00000.0 DB59999.DBX65533.7
Input
I00000.0 I32767.7
E00000.0 E32767.7
IW00000 IW32766
EW00000 EW32766
Output
Q00000.0 Q32767.7
A00000.0 A32767.7
QW00000 QW32766
AW00000 AW32766
Marker
32
bits
DB00001.DBW00000 DB59999.DBW65532
M00000.0 - M16383.7
MW00000 - MW16382
Please refer to the GP-Pro EX Reference Manual for system data area.
Cf. GP-Pro EX Reference Manual "LS Area (Direct Access Method Area)"
Please refer to the precautions on manual notation for icons in the table.
38
Remarks
5.6
Device
BOOL
BYTE
SINT
USINT
Bit Address
Word Address
32
bits
Single
Tag
<TAGNAME>
1D
Array
<TAGNAME>[xl] <TAGNAME>[xh]
2D
Array
<TAGNAME>[xl,yl] <TAGNAME>[xh,yh]
3D
Array
<TAGNAME>[xl,yl,zl] <TAGNAME>[xh,yh,zh]
4D
Array
<TAGNAME>[xl,yl,zl,wl] <TAGNAME>[xh,yh,zh,wh]
5D
Array
<TAGNAME>[xl,yl,zl,vl,wl] <TAGNAME>[xh,yh,zh,vh,wh]
6D
Array
<TAGNAME>[xl,yl,zl,ul,vl,wl]
<TAGNAME>[xh,yh,zh,uh,vh,
wh]
Single
Tag
<TAGNAME>.00 <TAGNAME>.07
<TAGNAME>
1D
Array
<TAGNAME>[xl].00 <TAGNAME>[xh].07
<TAGNAME>[xl] <TAGNAME>[xh]
2D
Array
<TAGNAME>[xl,yl].00 <TAGNAME>[xh,yh].07
<TAGNAME>[xl,yl] <TAGNAME>[xh,yh]
3D
Array
<TAGNAME>[xl,yl,zl].00 <TAGNAME>[xh,yh,zh].07
<TAGNAME>[xl,yl,zl] <TAGNAME>[xh,yh,zh]
4D
Array
5D
Array
<TAGNAME>[xl,yl,zl,vl,wl].0
0<TAGNAME>[xl,yl,zl,vl,wl] <TAGNAME>[xh,yh,zh,vh,wh] <TAGNAME>[xh,yh,zh,vh,wh]
.07
6D
Array
<TAGNAME>[xl,yl,zl,ul,vl,wl]
.00 <TAGNAME>[xh,yh,zh,uh,vh,
wh].07
<TAGNAME>[xl,yl,zl,ul,vl,wl]
<TAGNAME>[xh,yh,zh,uh,vh,
wh]
Single
Tag
<TAGNAME>.00 <TAGNAME>.07
<TAGNAME>
39
Remarks
*1 *2
*1 *2
*1
Device
INT
WORD
UINT
DINT
DWORD
UDINT
Bit Address
Word Address
Single
Tag
<TAGNAME>.00 <TAGNAME>.15
<TAGNAME>
1D
Array
<TAGNAME>[xl].00 <TAGNAME>[xh].15
<TAGNAME>[xl] <TAGNAME>[xh]
2D
Array
<TAGNAME>[xl,yl].00 <TAGNAME>[xh,yh].15
<TAGNAME>[xl,yl] <TAGNAME>[xh,yh]
3D
Array
<TAGNAME>[xl,yl,zl].00 <TAGNAME>[xh,yh,zh].15
<TAGNAME>[xl,yl,zl] <TAGNAME>[xh,yh,zh]
4D
Array
5D
Array
<TAGNAME>[xl,yl,zl,vl,wl].0
0<TAGNAME>[xl,yl,zl,vl,wl] <TAGNAME>[xh,yh,zh,vh,wh] <TAGNAME>[xh,yh,zh,vh,wh]
.15
6D
Array
<TAGNAME>[xl,yl,zl,ul,vl,wl]
.00 <TAGNAME>[xh,yh,zh,uh,vh,
wh].15
<TAGNAME>[xl,yl,zl,ul,vl,wl]
<TAGNAME>[xh,yh,zh,uh,vh,
wh]
Single
Tag
<TAGNAME>.00 <TAGNAME>.15
<TAGNAME>
Single
Tag
<TAGNAME>.00 <TAGNAME>.31
<TAGNAME>
1D
Array
<TAGNAME>[xl].00 <TAGNAME>[xh].31
<TAGNAME>[xl] <TAGNAME>[xh]
2D
Array
<TAGNAME>[xl,yl].00 <TAGNAME>[xh,yh].31
<TAGNAME>[xl,yl] <TAGNAME>[xh,yh]
3D
Array
<TAGNAME>[xl,yl,zl].00 <TAGNAME>[xh,yh,zh].31
<TAGNAME>[xl,yl,zl] <TAGNAME>[xh,yh,zh]
4D
Array
5D
Array
<TAGNAME>[xl,yl,zl,vl,wl].0
0<TAGNAME>[xl,yl,zl,vl,wl] <TAGNAME>[xh,yh,zh,vh,wh] <TAGNAME>[xh,yh,zh,vh,wh]
.31
6D
Array
<TAGNAME>[xl,yl,zl,ul,vl,wl]
.00 <TAGNAME>[xh,yh,zh,uh,vh,
wh].31
<TAGNAME>[xl,yl,zl,ul,vl,wl]
<TAGNAME>[xh,yh,zh,uh,vh,
wh]
Single
Tag
<TAGNAME>.00 <TAGNAME>.31
<TAGNAME>
40
32
bits
Remarks
*1 *2 *3
*1
*1 *2
*1
Device
DATE*4
REAL
TIME
TIME_OF_DA
Y
DATE_AND_
TIME
Bit Address
Word Address
Single
Tag
<TAGNAME>
1D
Array
<TAGNAME>[xl] <TAGNAME>[xh]
2D
Array
<TAGNAME>[xl,yl] <TAGNAME>[xh,yh]
3D
Array
<TAGNAME>[xl,yl,zl] <TAGNAME>[xh,yh,zh]
4D
Array
<TAGNAME>[xl,yl,zl,wl] <TAGNAME>[xh,yh,zh,wh]
5D
Array
<TAGNAME>[xl,yl,zl,vl,wl] <TAGNAME>[xh,yh,zh,vh,wh]
6D
Array
<TAGNAME>[xl,yl,zl,ul,vl,wl]
<TAGNAME>[xh,yh,zh,uh,vh,
wh]
Single
Tag
<TAGNAME>
1D
Array
<TAGNAME>[xl] <TAGNAME>[xh]
2D
Array
<TAGNAME>[xl,yl] <TAGNAME>[xh,yh]
3D
Array
<TAGNAME>[xl,yl,zl] <TAGNAME>[xh,yh,zh]
4D
Array
<TAGNAME>[xl,yl,zl,wl] <TAGNAME>[xh,yh,zh,wh]
5D
Array
<TAGNAME>[xl,yl,zl,vl,wl] <TAGNAME>[xh,yh,zh,vh,wh]
6D
Array
<TAGNAME>[xl,yl,zl,ul,vl,wl]
<TAGNAME>[xh,yh,zh,uh,vh,
wh]
41
32
bits
Remarks
*1 *2
*1 *2 *5
Device
STRING
*1
Bit Address
Word Address
Single
Tag
<TAGNAME>
1D
Array
<TAGNAME>[xl] <TAGNAME>[xh]
2D
Array
<TAGNAME>[xl,yl] <TAGNAME>[xh,yh]
3D
Array
<TAGNAME>[xl,yl,zl] <TAGNAME>[xh,yh,zh]
4D
Array
<TAGNAME>[xl,yl,zl,wl] <TAGNAME>[xh,yh,zh,wh]
5D
Array
<TAGNAME>[xl,yl,zl,vl,wl] <TAGNAME>[xh,yh,zh,vh,wh]
6D
Array
<TAGNAME>[xl,yl,zl,ul,vl,wl]
<TAGNAME>[xh,yh,zh,uh,vh,
wh]
32
bits
Remarks
*1 *2
<TAGNAME>: For structures, Tag Name includes the structure name. The maximum length of the Tag Name
is 255 characters, which includes delimiters and the element number.
Example
BOOL type single tag:
"BOOLSYMBOL"
BOOL type 1D array:
"BOOL1D[10]"
WORD type 2D array:
"WORD2D[10,10]"
UDINT type 3D array:
"UDINT[0,1,2]"
User-defined structure:
"STRUCT001.STRINGSYM"
You cannot start names with any of the following text:
LS, USER, SCR, PRT
*2
The number of elements for each dimension is shown from "l" (Number of minimum element) to "h" (Number
of maximum element).
*3
By default, the system data area is set up with 16 words. Even if you want to use less than 16 words for the
system data area, you have to map a 16 word (or larger) array tag and then select the items for the system data
area.
*4
Handled as 16-bit devices in the External Device, but as 32-bit devices in GP-Pro EX.
*5
64-bit device
42
Please refer to the GP-Pro EX Reference Manual for system data area.
Cf. GP-Pro EX Reference Manual "LS Area (Direct Access Method Area)"
Please refer to the precautions on manual notation for icons in the table.
43
S7-200/1200/1500/LOGO! Series
This address can be specified as system data area.
Device
Bit Address
Word Address
32
bits
*1
*1
Remarks
BOOL
Single Tag
<TAGNAME>
BYTE
SINT
USINT
Single Tag
<TAGNAME>.00 <TAGNAME>.07
<TAGNAME>
INT
WORD
UINT
Single Tag
<TAGNAME>.00 <TAGNAME>.15
<TAGNAME>
*1 *2
DINT
DWORD
UDINT
Single Tag
<TAGNAME>.00 <TAGNAME>.31
<TAGNAME>
*1
DATE*3
REAL
TIME
TIME_OF_DA
Y
Single Tag
<TAGNAME>
*1
DATE_AND_
TIME
Single Tag
<TAGNAME>
*1 *4
STRING
Single Tag
<TAGNAME>
*1
*1
<TAGNAME>: For structures, Tag Name includes the structure name. The maximum length of the Tag Name
is 255 characters, which includes delimiters and the element number.
Example:
BOOL type single tag:
"BOOLSYMBOL"
User-defined structure:
"STRUCT001.STRINGSYM"
You cannot start names with any of the following text:
LS, USER, SCR, PRT
*2
*3
Handled as 16-bit devices in the External Device, but as 32-bit devices in GP-Pro EX.
*4
64-bit device
44
German
Device Code
(HEX)
DB
DB
0000
Input
0080
Output
0081
Marker
0082
Timer
0060
Word Address
Counter
0061
Word Address
Variable
0001
Device
Data Block
45
Address Code
Error Messages
Error messages are displayed on the Display screen as follows: "No.: Device Name: Error Message (Error
Occurrence Area)". Each description is shown below.
Item
Description
No.
Error No.
Device Name
Name of the External Device where error occurs. Device name is a title of the External
Device set with GP-Pro EX. (Initial value [PLC1])
Error Message
Refer to your External Device manual for details on received error codes.
Refer to "Display-related errors" in "Maintenance/Troubleshooting Guide" for details on the error
messages common to the driver.
Description
Comment
Description
Comment
0x05
0x0A
46