Automatic transfer switches

Order code Description

Qty
per
pkg

Wt

[kg]

ATK20

Automatic transfer switch,


24VDC auxiliary supply

0.700

ATK40

Automatic transfer switch,


230VAC auxiliary supply

0.900

PACR

IP54 front protection cover

0.107

DIMENSIONS (mm)
62

31

52

ATK...

ATK

AUTOMATIC
TRANSFER
SWITCH

General characteristics
The automatic transfer switch ATK is used for the
automatic changeover of the load from the main line to
a secondary line.
It is made of a single unit in an insulated housing and
has two outgoings for the automatic and/or manual
control of contactors or circuit breakers.
MANUAL CHANGEOVER
This mode consents to the manual changeover from one
source to another and viceversa.
AUTOMATIC CHANGEOVER
This mode automatically enables the switching of two
lines within a time period, adjustable between 0.5 and
120 seconds.
The control of the two line contactors or circuit breakers
is achieved in a safe and reliable manner by means of a
safety system with internal electromechanical interlock
of the ATK unit.

POWER ON

ALARM

SECONDARY
LINE

144

PACR

MAIN
LINE

AUT ON/OFF

MAIN LINE ON

SEC LINE ON

OPEN ALL LINES

TEST

SETUP

LOAD

144

138.5

138.5

WIRING DIAGRAM

Operational characteristics
Rated supply voltage: 24VDC (ATK20) 230VAC (ATK40)
Voltage range: 0.7-1.35% Us (ATK20)
0.8-1.2% Us (ATK40)
Maximum current consumption: 250mA (ATK20) 45mA (ATK40)
Rated current: 100mA (ATK20) - 35mA (ATK40)
Connection time: 100%
Maximum voltage ripple: 10% (ATK20)
Power loss ride through (MPU circuit): 300ms
Galvanic isolation between control network and
internal circuits
True RMS control of supplt voltage
Microprocessor supervision of functions
Membrane keypad and 3 digit display
11 signalling LEDs
Adjustable tripping limits and time
AUT-MAN-TEST operating mode
1 Main L-L voltage measurement input
1 Secondary L-L voltage measurement input
100-415VAC rated voltage control
70-500VAC L-L voltage range
50 or 60Hz rated frequency
Full scale measurement accuracy: 1% 1digit
2 output relays (16A Ith changeover contact) for Main
and Secondary contactor or circuit breaker control
1 alarm output relay (8A Ith changeover contact)
IP41 on front, IP54 with sealable cover (order
separately)
IP20 at rear.
Set up
The set up contemplates the following setting parameters:
Max voltage limit for Main and Secondary lines
Min voltage limit for Main and Secondary lines
Min-Max limit tripping delay for Main and
Secondary lines
Min-Max limit delay at voltage return for Main and
Secondary lines
Changeover/interlock control time for circuit breakers
control of Main and Secondary lines.

Reference standards
Compliant with standards: IEC/EN50081-1,
IEC/EN50082-2, IEC/EN61010-1, IEC/EN60068-2-6,
IEC/EN60068-2-27, IEC/EN60529, IEC/EN61000-4-11
and EN50011.

LOVATO ELECTRIC S.P.A.


CONTROL SOLUTIONS
FOR INDUSTRY

VIA DON E. MAZZA, 12


24020 GORLE (BG) ITALY
TEL. +39 0354282111

INTERNATIONAL SALES DIPARTMENT:


TEL. +39 0354282281
FAX +39 0354282400

Web: www.LovatoElectric.com
E-mail: lovato.s@LovatoElectric.com

PD39 GB 03 02

Selling points
Microprocessor supervision
Easy and simple installation
RMS voltage measurements (full scale accuracy: 1%
1digit)