You are on page 1of 43

Air Conditioning

Technical Data
VRV IV heat pump, with continuous heating

EEDEN14-200_1

RYYQ-T

Outdoor Unit RYYQ-T

TABLE OF CONTENTS
RYYQ-T

Features . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2

Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3
Technical Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Electrical Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Technical Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Technical Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Electrical Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Electrical Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Technical Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Electrical Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

3
4
5
6
7
7
8
8

Options . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10

Combination table . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11

Capacity tables . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Capacity Table Legend

14

. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14

Dimensional drawings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15

Centre of gravity . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16

Piping diagrams . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17

Wiring diagrams . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 21
Wiring Diagrams - Three Phase

. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 21

10

External connection diagrams . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 25

11

Sound data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 27
Sound Power Spectrum . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Sound Pressure Spectrum . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

12

29

Installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 31
Installation Method . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Fixation and Foundation of Units . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Refrigerant Pipe Selection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

13

27

31
32
33

Operation range . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 40

VRV Systems RYYQ-T

Outdoor Unit RYYQ-T

1
t is a mn e Ue h t rs V oy T I oS - d Q Vt Y RuY OVR

Features
Customize your VRV for best seasonal efficiency & comfort with the
weather dependant Variable Refrigerant Temperature function

Fits any building as also indoor installation is possible as a result of


high external static pressure of up to 78.4 Pa. Indoor installation
leads to less piping length, lower installation costs, increased
efficiency and better visual aesthetics

Simplified installation & guaranteed optimal efficiency with automatic


charging & testing

Up to 28% higher seasonal efficiency with Variable Refrigerant


Temperature when compared to previous series

Best comfort, no cold draft by supply of a high outblow air


temperature thanks to Variable Refrigerant Temperature and all
inverter technology

Continuous comfort: Unique continuous heating technology makes


VRV IV the best alternative to traditional heating systems

Easy compliance with F-gas regulation thanks to automated


refrigerant containment check

VRV configurator software for the fastest and most accurate


commissioning, configuration and customisation

Wide piping flexibility: 30m indoor height difference, maximum piping


length: 190m, total piping length: 1,000m

Accurate temperature control, fresh air provision, air handling units,


Biddle air curtains and hot water production, all integrated in a single
system requiring only one single point of contact

The ability to control each conditioned zone individually keeps VRV


system running costs to an absolute minimum

Spread your installation cost by phased installation

Wide range of indoor units: possibility to combine VRV with stylish


indoor units (Daikin Emura, Nexura, ...)

Keep your system in top condition via our ACNSS service: 24/7
monitoring for maximum efficiency, extended lifetime, immediate
service support thanks to failure prediction and a clear understanding
of operability and usage

Available as heating only by irreversible field setting

Outdoor unit display for quick on-site settings and easy read out of
errors together with the indication of service parameters for checking
basic functions.
Free combination of outdoor units to meet installation space or
efficiency requirements

Inverter

VRV Systems RYYQ-T

Outdoor Unit RYYQ-T

Specifications

2-1 Technical Specifications


Capacity range

RYYQ8T

RYYQ10T

RYYQ12T

RYYQ14T

RYYQ16T

RYYQ18T

RYYQ20T

HP

10

12

14

16

18

20

Cooling capacity

Nom.

kW

22.4

28.0

33.5

40.0

45.0

50.0

56.0

Heating capacity

Nom.

kW

22.4

28.0

33.5

40.0

45.0

50.0

56.0

kW

25.0

31.5

37.5

45.0

50.0

56.0

63.0

Power input - 50Hz

Cooling

Nom.

kW

5.21

7.29

8.98

11.0

13.0

14.7

18.5

Heating

Nom.

kW

4.75

6.29

7.77

9.52

11.1

12.4

14.5

Max.

kW

5.51

7.38

9.10

11.2

12.8

14.4

17.0

Max.

Capacity control

Method
4.30

3.84

3.73

3.64

3.46

3.40

3.03

ESEER

6.37 / 7.53

5.67 / 7.20

5.50 / 6.96

5.31 / 6.83

5.05 / 6.50

4.97 / 6.38

4.42 / 5.67

COP

4.72 / 4.54

4.45 / 4.27

4.31 / 4.12

4.20 / 4.02

4.05 / 3.91

4.03 / 3.89

3.86 / 3.71

Maximum number of connectable indoor units

64

Min.

100

125

150

175

200

225

250

Nom.

200

250

300

350

400

450

500

Max.

260

325

390

455

520

585

650

Casing

Colour

Dimensions

Unit

Daikin White

Material

Painted galvanized steel plate

Packed unit

Weight
Packing

Height

mm

Width

mm

Depth

mm

Height

mm

Width

mm

Depth

mm

1,310
835

261

268

364

398

kg

279

287

384

418

Material

Carton
kg

2.00

3.00

Material

Wood
kg

17.00

18.50

Material

Plastic
kg

0.50

Type

Cross fin coil

Fin
Compressor

1,820
1,000

kg

Weight
Heat exchanger

1,240
765

Packed unit

Weight
Packing 3

1,685
930

Unit

Weight
Packing 2

Treatment

Anti-corrosion treatment

Quantity

Model

Inverter

Type

Hermetically sealed scroll compressor

Crankcase heater
Fan

33

Type

Propeller fan

Quantity

Air flow rate

Cooling Nom.

m/min

External static
pressure

Max.

Pa

162

175

2
185

223

Output

65

66

10.4

11.7

11.8

1.7

1.9

750

Nom.

dBA

Sound pressure level

Cooling

Nom.

dBA

Operation range

Cooling

Min.~Max.

CDB

-5~43

Heating

Min.~Max.

CWB

-20~15.5

78

79

81

58

86

61

Type

88

R-410A
kg

5.9

6.3

Type
Charged volume

64

2
Brushless DC motor

Cooling

Refrigerant oil

261

Sound power level

Charge

251

Vertical

Quantity
Model

Refrigerant

260

78

Discharge direction
Fan motor

Inverter controlled

EER

Indoor index
connection

10.3
Synthetic (ether) oil

VRV Systems RYYQ-T

0.8

0.5

0.7

1.8

Outdoor Unit RYYQ-T

Specifications

2-1 Technical Specifications


Piping connections

RYYQ8T

Liquid

RYYQ10T

RYYQ12T

Type
OD

Gas

mm

9.52

RYYQ20T

15.9

mm

19.1

22.2

28.6
Both liquid and gas pipes

Piping length

OU - IU Max.

165

After
branch

90

1,000

Max.

Total piping length

System Actual

Level difference

OU - IU Outdoo m
r unit in
highest
position

90

Indoor m
unit in
highest
position

90

IU - IU

Max.

30

Defrost method

PED

RYYQ18T

Braze connection

OD

Safety devices

RYYQ16T

12.7

Type

Heat insulation

RYYQ14T

Braze connection

Reversed cycle
Item

01

High pressure switch

02

Fan driver overload protector

03

Inverter overload protector

04

PC board fuse

Category

Category II

Standard Accessories : Installation and operation manual;


Standard Accessories : Connection pipes;

2-2 Electrical Specifications


Power supply

RYYQ8T

RYYQ10T

RYYQ12T

RYYQ14T

Name

RYYQ16T

RYYQ18T

RYYQ20T

18.0

20.8

26.9

Y1

Phase

3N~

Frequency

Hz

50

Voltage

380-415

Min.

-10

Max.

Current

Nominal running
Cooling
current (RLA) - 50Hz

Current - 50Hz

Minimum Ssc value

kVa

1,216

564

615

917

924

873

970

Minimum circuit amps (MCA)

16.1

22.0

24.0

27.0

31.0

35.0

39.0

Maximum fuse amps (MFA)

20

25

Total overcurrent amps (TOCA)

17.3

Full load amps


(FLA)

Total

1.2

For power supply

Quantity

For connection with


indoor

Quantity

Remark

F1,F2

Voltage range

Wiring connections 50Hz

10
7.2

10.2

Power supply intake

12.7

15.4

32

40

24.6
1.3

50

35.4
1.5

1.8

42.7
2.6

5G

Both indoor and outdoor unit

Notes
(1) Cooling: indoor temp. 27CDB, 19CWB; outdoor temp. 35CDB; equivalent piping length: 5m; level difference: 0m
(2) heating: indoor temp. 20CDB; outdoor temp. 7CDB, 6CWB; equivalent refrigerant piping: 5m; level difference: 0m (nominal)
(3) Actual number of connectable indoor units depends on the indoor unit type (VRV indoor, Hydrobox, RA indoor, etc.) and the connection ratio restriction for the system (50% \<=
CR \<= 130%)
(4) For more details on operation range see TW drawing
(5) Voltage range: units are suitable for use on electrical systems where voltage supplied to unit terminal is not below or above listed range limits.
(6) Maximum allowable voltage range variation between phases is 2%.
(7) Refer to refrigerant pipe selection or installation manual
(8) For more details on standard accessories refer to Installation/operation manual
(9) RLA is based on following conditions: indoor temp. 27CDB, 19CWB; outdoor temp. 35CDB
(10) MSC means the maximum current during start up of the compressor. VRV IV uses only inverter compressors. Starting current is always max. running current.

VRV Systems RYYQ-T

Outdoor Unit RYYQ-T

Specifications

(11) Select wire size based on the value of MCA. The MCA can be regarded as the maximum running current.

(12) MFA is used to select the circuit breaker and the ground fault circuit interrupter (earth leakage circuit breaker).
(13) TOCA means the total value of each OC set.
(14) FLA means the nominal running current of the fan
(15) In accordance with EN/IEC 61000-3-11, respectively EN/IEC 61000-3-12, it may be necessary to consult the distribution network operator to ensure that the equipment is
connected only to a supply with Zsys Zmax, respectively Ssc minimum Ssc value.
(16) European/International Technical Standard setting the limits for voltage changes, voltage fluctuations and flicker in public low-voltage supply systems for equipment with rated

current 75A.
(17) European/International Technical Standard setting the limits for harmonic currents produced by equipment connected to public low-voltage systems with input current \>16A and
\<= 75A per phase
(18) Short-circuit power
(19) system impedance
(20) Multi combination (22~54HP) data is corresponding with the standard multi combination as mentioned on 3D079534
(21) Sound power level is an absolute value that a sound source generates.
(22) Sound pressure level is a relative value, depending on the distance and acoustic environment. For more details, please refer to the sound level drawings.
(23) Sound values are measured in a semi-anechoic room.
(24) The STANDARD ESEER value corresponds with normal VRV4 Heat Pump operation, not taking into account advanced energy saving operation functionality
(25) The AUTOMATIC SEER value corresponds with normal VRV4 Heat Pump operation, taking into account advanced energy saving operation functionality ( variable refrigerant
temperature control operation)
(26) heating: indoor temp. 20CDB; outdoor temp. 7CDB, 6CWB; equivalent refrigerant piping: 5m; level difference: 0m (maximum)
(27) Cooling: indoor temp. 27CDB, 19.0CWB; outdoor temp. 35CDB; equivalent piping length: 5m; level difference: 0m
(28) Sound values are theoretical values based on sound results of individual installed units. Possible deviations due to variety of installation patterns are not taken into account.
(29) Soundpressure system [dBA] = 10*log[10^(A/10)+10^(B/10)+10^(C/10)] , with Unit A = A dBA, Unit B = B dBA, Unit C = C dBA
(30) Cooling: indoor temp. 27CDB, 19CWB; outdoor temp. 35CDB; equivalent piping length: 5m (horizontal); level difference: 0m
(31) Heating: indoor temp. 20CDB; outdoor temp. 7CDB, 6CWB; equivalent refrigerant piping: 5m; level difference: 0m

RYYQ22
T

2-3 Technical Specifications


System

RYYQ24
T

RYYQ26
T

RYYQ28
T

RYYQ30
T

RYYQ32
T

RYMQ12T

RYYQ34
T

RYYQ36
T

RYYQ40
T

Outdoor unit module 1

RYMQ1 RYMQ8
0T
T

Outdoor unit module 2

RYMQ1 RYMQ1 RYMQ1 RYMQ1 RYMQ1 RYMQ1 RXYQ1 RYMQ2 RYMQ1 RYMQ1
2T
6T
4T
6T
8T
6T
8T
0T
0T
2T

Outdoor unit module 3

RYMQ16T

RYYQ38
T

RYMQ8 RYMQ1
T
0T

Capacity range

RYMQ2 RYMQ1
0T
8T

HP

22

24

26

28

30

32

34

36

38

40

Cooling capacity

Nom.

kW

61.5

67.4

73.5

78.5

83.5

90.0

95.0

101.0

106.0

111.5

Heating capacity

Nom.

kW

61.5

67.4

73.5

78.5

83.5

90.0

95.0

101.0

106.4

111.5

Max.

kW

69.0

75.0

82.5

87.5

93.5

100.0

106.0

113.0

119.5

Power input - 50Hz

125.0

Cooling

Nom.

kW

16.27

18.2

20.0

22.0

23.7

26.0

27.7

31.5

Heating

Nom.

kW

14.06

15.85

17.29

18.87

20.17

22.2

23.5

25.6

25.54

26.46

Max.

kW

16.48

18.31

20.30

21.90

23.50

25.6

27.2

29.8

29.89

30.88

EER

3.77

3.70

3.68

3.57

3.52

3.46

3.43

3.21

3.42

3.61

ESEER

5.58 /
7.07

5.42 /
6.81

5.39 /
6.89

5.23 /
6.69

5.17 /
6.60

5.05 /
6.50

5.01 /
6.44

4.68 /
6.02

5.03 /
6.36

5.29 /
6.74

COP

4.37 /
4.19

4.25 /
4.10

4.25 /
4.06

4.16 /
4.00

4.14 /
3.98

4.05 /
3.91

4.04 /
3.90

3.95 /
3.79

4.17 /
4.00

4.21 /
4.05

Min.

275

300

325

350

375

400

425

450

475

500

Nom.

550

600

650

700

750

800

850

900

950

1,000

Max.

715

780

845

910

975

1,040

1,105

1,170

1,235

1,300

Maximum number of connectable indoor units


Indoor index
connection

VRV Systems RYYQ-T

31.0

64

Outdoor Unit RYYQ-T

Specifications
RYYQ22
T

2-3 Technical Specifications


Piping connections

RYYQ26
T

RYYQ28
T

RYYQ30
T

RYYQ32
T

Liquid

OD

mm

Gas

OD

mm

Piping length

OU - IU Max.

165

After
branch

90

1,000

Max.

15.9

RYYQ36
T

RYYQ38
T

34.9

RYYQ40
T

41.3

System Actual

Level difference

OU - IU Outdoo m
r unit in
highest
position

90

Indoor m
unit in
highest
position

90

Max.

RYYQ34
T

19.1

28.6

Total piping length

IU - IU
PED

RYYQ24
T

30

Category

Category II

Standard Accessories : Installation and operation manual;


Standard Accessories : Connection pipes;

2-4 Technical Specifications


System

Outdoor unit module 1

RYYQ42T

RYYQ44T

RYYQ46T

RYMQ10T

RYMQ12T

RYMQ14T

Outdoor unit module 2

RYYQ50T

RYYQ52T

RYMQ16T

RYMQ18T

RYMQ16T

Capacity range

RYYQ54T

RYMQ18T

RYMQ16T

Outdoor unit module 3

RYMQ18T

HP

42

44

46

48

50

52

54

Cooling capacity

Nom.

kW

118.0

123.5

130.0

135.0

140.0

145.0

150.0

Heating capacity

Nom.

kW

118.0

123.5

130.0

135.0

140.0

145.0

150.0

Max.

kW

131.5

137.5

145.0

150.0

156.0

162.0

168.0

Power input - 50Hz

Cooling

Nom.

kW

33.3

35.0

37.0

39.0

40.7

42.4

44.1

Heating

Nom.

kW

28.49

29.97

31.72

33.3

34.6

35.9

37.2

Max.

kW

32.98

EER

34.70
3.54

36.8

38.4

40.0

41.6

43.2

3.51

3.46

3.44

3.42

3.40

ESEER

5.19 / 6.65

5.17 / 6.62

5.13 / 6.60

5.05 / 6.50

5.02 / 6.46

4.99 / 6.42

4.97 / 6.38

COP

4.14 / 3.99

4.12 / 3.96

4.10 / 3.94

4.05 / 3.91

4.05 / 3.90

4.04 / 3.89

4.03 / 3.89

Maximum number of connectable indoor units

64

Indoor index
connection

Min.

525

550

575

600

625

650

675

Nom.

1,050

1,100

1,150

1,200

1,250

1,300

1,350

1,365

1,430

1,495

1,560

1,625

1,690

1,755

Piping connections

Liquid

Max.
OD

mm

19.1

Gas

OD

mm

41.3

Piping length

OU - IU Max.

165

After
branch

90

1,000

Max.

Total piping length

System Actual

Level difference

OU - IU Outdoo m
r unit in
highest
position

90

Indoor m
unit in
highest
position

90

IU - IU
PED

Max.

Category

30
Category II

Standard Accessories : Installation and operation manual;


Standard Accessories : Connection pipes;

RYYQ48T

VRV Systems RYYQ-T

Outdoor Unit RYYQ-T

Specifications

2-5 Electrical Specifications

RYYQ22
T

RYYQ24
T

RYYQ26
T

RYYQ28
T

RYYQ30
T

RYYQ32
T

RYYQ34
T

RYYQ36
T

RYYQ38
T

RYYQ40
T

25.2

28.1

30.7

33.5

36.0

38.8

44.9

44.3

43.7

2,140

1,532

1,539

1,488

1,848

1,797

1,894

2,750

2,052

51.0

55.0

59.0

62.0

66.0

70.0

76.0

Current

Nominal running
Cooling
current (RLA) - 50Hz

22.9

Current - 50Hz

Minimum Ssc value

kVa

1,179

Minimum circuit amps (MCA)

Maximum fuse amps (MFA)

Wiring connections 50Hz

46.0
63

80

For power supply

Quantity

For connection with


indoor

Quantity

Remark

F1,F2

81.0
100

5G

Power supply intake

Both indoor and outdoor unit

2-6 Electrical Specifications

RYYQ42T

RYYQ44T

RYYQ46T

RYYQ48T

RYYQ50T

RYYQ52T

RYYQ54T

Current

Nominal running
Cooling
current (RLA) - 50Hz

46.2

48.7

51.4

54.0

56.8

59.6

62.4

Current - 50Hz

Minimum Ssc value

kVa

2,412

2,463

2,765

2,772

2,721

2,670

2,619

Minimum circuit amps (MCA)

84.0

86.0

89.0

93.0

97.0

101.0

105.0

Maximum fuse amps (MFA)

Wiring connections 50Hz

100

125

For power supply

Quantity

For connection with


indoor

Quantity

Remark

F1,F2

Power supply intake

5G

Both indoor and outdoor unit

Notes
(1) Cooling: indoor temp. 27CDB, 19CWB; outdoor temp. 35CDB; equivalent piping length: 5m; level difference: 0m
(2) heating: indoor temp. 20CDB; outdoor temp. 7CDB, 6CWB; equivalent refrigerant piping: 5m; level difference: 0m (nominal)
(3) Actual number of connectable indoor units depends on the indoor unit type (VRV indoor, Hydrobox, RA indoor, etc.) and the connection ratio restriction for the system (50% \<=
CR \<= 130%)
(4) For more details on operation range see TW drawing
(5) Voltage range: units are suitable for use on electrical systems where voltage supplied to unit terminal is not below or above listed range limits.
(6) Maximum allowable voltage range variation between phases is 2%.
(7) Refer to refrigerant pipe selection or installation manual
(8) For more details on standard accessories refer to Installation/operation manual
(9) RLA is based on following conditions: indoor temp. 27CDB, 19CWB; outdoor temp. 35CDB
(10) MSC means the maximum current during start up of the compressor. VRV IV uses only inverter compressors. Starting current is always max. running current.
(11) Select wire size based on the value of MCA. The MCA can be regarded as the maximum running current.
(12) MFA is used to select the circuit breaker and the ground fault circuit interrupter (earth leakage circuit breaker).
(13) TOCA means the total value of each OC set.
(14) FLA means the nominal running current of the fan
(15) In accordance with EN/IEC 61000-3-11, respectively EN/IEC 61000-3-12, it may be necessary to consult the distribution network operator to ensure that the equipment is
connected only to a supply with Zsys Zmax, respectively Ssc minimum Ssc value.
(16) European/International Technical Standard setting the limits for voltage changes, voltage fluctuations and flicker in public low-voltage supply systems for equipment with rated
current 75A.
(17) European/International Technical Standard setting the limits for harmonic currents produced by equipment connected to public low-voltage systems with input current \>16A and
\<= 75A per phase
(18) Short-circuit power
(19) system impedance
(20) Multi combination (22~54HP) data is corresponding with the standard multi combination as mentioned on 3D079534
(21) Sound power level is an absolute value that a sound source generates.
(22) Sound pressure level is a relative value, depending on the distance and acoustic environment. For more details, please refer to the sound level drawings.
(23) Sound values are measured in a semi-anechoic room.
(24) The STANDARD ESEER value corresponds with normal VRV4 Heat Pump operation, not taking into account advanced energy saving operation functionality
(25) The AUTOMATIC SEER value corresponds with normal VRV4 Heat Pump operation, taking into account advanced energy saving operation functionality ( variable refrigerant
temperature control operation)
(26) heating: indoor temp. 20CDB; outdoor temp. 7CDB, 6CWB; equivalent refrigerant piping: 5m; level difference: 0m (maximum)
(27) Cooling: indoor temp. 27CDB, 19.0CWB; outdoor temp. 35CDB; equivalent piping length: 5m; level difference: 0m
(28) Sound values are theoretical values based on sound results of individual installed units. Possible deviations due to variety of installation patterns are not taken into account.
(29) Soundpressure system [dBA] = 10*log[10^(A/10)+10^(B/10)+10^(C/10)] , with Unit A = A dBA, Unit B = B dBA, Unit C = C dBA
(30) Cooling: indoor temp. 27CDB, 19CWB; outdoor temp. 35CDB; equivalent piping length: 5m (horizontal); level difference: 0m
(31) Heating: indoor temp. 20CDB; outdoor temp. 7CDB, 6CWB; equivalent refrigerant piping: 5m; level difference: 0m

VRV Systems RYYQ-T

Outdoor Unit RYYQ-T

Specifications

2-7 Technical Specifications


Casing
Dimensions

RYMQ8T

Packing

RYMQ14T

Daikin White
Painted galvanized steel plate

Unit

Height

mm

Width

mm

Depth

mm

Height

mm

Width

mm

Depth

mm

1,685
930

1,240
765
1,820

1,000

1,310
835

kg

188

195

309

319

kg

206

213

329

339

Material

Carton
kg

2.00

3.00

Material
Material

Heat exchanger

Type

Wood

Compressor

Quantity

kg

17.00

18.50
Plastic

Weight

kg

0.50

Treatment

Anti-corrosion treatment
1

Model

Inverter

Type

Hermetically sealed scroll compressor

Crankcase heater

33

Type

Propeller fan

Quantity

Air flow rate

Cooling Nom.

m/min

External static
pressure

Max.

Pa

162

175

2
185

223

1
Brushless DC motor

Output

Cooling

Nom.

dBA

Sound pressure level

Cooling

Nom.

dBA

Operation range

Cooling

Min.~Max.

CDB

-5~43

Heating

Min.~Max.

CWB

-20~15.5

58

86

61

88

64

65

66

5.9

6.3

10.3

10.4

11.7

11.8

Synthetic (ether) oil


l

1.0

1.2

1.4

2.4

3.3

Liquid, gas and equalizing pipe


01

High pressure switch

02

Fan driver overload protector

03

Inverter overload protector

04

PC board fuse

2-8 Electrical Specifications

Current

81

Type

Item

Voltage range

79

R-410A
kg

Charged volume

Power supply

78

Type
Charge

750

Sound power level

Safety devices

261

Model

Heat insulation

251

Vertical

Quantity

Piping connections

260

78

Discharge direction

Refrigerant oil

0.50

Cross fin coil

Fin

Refrigerant

RYMQ20T

Packed unit

Weight

Fan motor

RYMQ18T

Unit

Packing 3

Fan

RYMQ16T

Material

Weight
Packing 2

RYMQ12T

Colour

Packed unit

Weight

RYMQ10T

RYMQ8T

RYMQ10T

RYMQ12T

RYMQ14T

Name

Y1

Phase

3N~

Frequency

Hz

50

Voltage

380-415

Min.

-10

Max.

Nominal running
Cooling
current (RLA) - 50Hz

VRV Systems RYYQ-T

RYMQ16T

RYMQ18T

RYMQ20T

18.0

20.8

26.9

10
7.2

10.2

12.7

15.4

Outdoor Unit RYYQ-T

Specifications

2-8 Electrical Specifications


Current - 50Hz

Minimum circuit amps (MCA)

RYMQ8T

RYMQ10T

RYMQ12T

RYMQ14T

RYMQ16T

RYMQ18T

RYMQ20T

16.1

22.0

24.0

27.0

31.0

35.0

39.0

25

Maximum fuse amps (MFA)

20

Total overcurrent amps (TOCA)

17.3

Full load amps


(FLA)

1.2

Total

Notes

32

40

24.6
1.3

1.8

Sound values are measured in a semi-anechoic room.

VRV Systems RYYQ-T

50

35.4
1.5

42.7
2.6

Outdoor Unit RYYQ-T

Options

3-1

Options

RYYQ-T
RYMQ-T
RXYQ-T

No.

I.

Item.

RYYQ8T
RXYQ8T

RYYQ10-12T
RXYQ10-12T

-----

---

Outdoor multi connection kit (see note 2)


Outdoor multi connection kit (see note 2)

No.

Item.

1a
1b
1c
1d
2
3
4
5
6

Cool/heat selector (switch)


Cool/heat selector (PCB)
Cool/heat selector (sWB mounting plate)
&RROKHDWVHOHFWRU [LQJER[
VRVFRQJXUDWRU
Heater tape kit (see note 6)
Heater tape kit PCB
Demand PCB (see note 7)
Demand PCB (mounting plate)

KHRQ22M64H
---

KHRQ22M75H

KHRQ22M64T
-------

KHRQ22M75T
BHFQ22P1007
BHFQ22P1517

KHRQ22M20T
KHRQ22M29T9

Refnet Joint

III.
IV.

RYYQ20~54T
RXYQ20~54T

KHRQ22M29H

Refnet heater

II.

RYYQ14-18T
RXYQ14-18T

------8HP

------10HP

12HP

14HP
KRC19-26A
BRP2A81

---

16HP

18HP

20HP

KKSA26A560*
KJB111A
EKPCCAB*

EKBPH012T*

EKBPH020T*
EKBPHPCBT*
DTA104A61/62*

---

KKSB26B1l*

NOTES

1.
2.
3.
4.
5.
6.
7.

All options are kits


Only for multi units
Option 1a and 1b are both required to operate the COOL/HEAT SELECTOR function on a VRV4 Heat Pump system
Option 1d is required to mount 1a
1c is only required when combining 1b with 3 on a VRV4 Heat Pump system
To install the HEATER TAPE KIT, a HEATER TAPE KIT PCB is required
To install the DEMAND PCB on the Large casing type, the DEMAND PCB (MOUNTING PLATE) is required

Medium casing type VRV4 Heat Pump: modules 8~12HP


Large casing type VRV4 Heat Pump: modules 14~20HP

3D079531E

10

VRV Systems RYYQ-T

Outdoor Unit RYYQ-T

Combination table

4-1

Combination Table

5<<47
5<047

5<<4 
5<<4
5<<4
5<<4
5<<4
5<<4
5<<4
5<<4
5<<4
5<<4
5<<4
5<<4
5<<4
5<<4
5<<4
5<<4
5<<4
5<<4
5<<4
5<<4
5<<4
5<<4
5<<4
5<<4

+3

+3

+3

+3

+3

+3

+3
+HDW3803
0XOWLFRPELQDWLRQ
ZLWKRXWGRRUXQLWV
0XOWLFRPELQDWLRQ
ZLWKRXWGRRUXQLWV

6HH1RWHVFRQFHUQLQJEDVHPRGHOW\SH














































127(6

5<<4a  VLQJOHQRQFRQWLQXRXVKHDWLQJPRGHO
5<<4a  PXOWLQRQFRQWLQXRXVKHDWLQJPRGHO
 6LQJOHXQLWFDQEHFKRVHQ5<<4 PRGHO FRQWLQXRXVKHDWLQJ DQG5;<4 PRGHO QRQFRQWLQXRXVKHDWLQJ
 0XOWLFRPELQDWLRQVQRQFRQWLQXRXVKHDWLQJFRQVLVWRXWRI5;<4aPRGXOHV(J5;<4  5;<4 5;<4
 0XOWLFRPELQDWLRQVFRQWLQXRXVKHDWLQJFRQVLVWRXWRI5<04aPRGXOHV(J5<<4  5<04 5<04 

JPXOWLPRGHOV5<04 FDQQRWEHXVHGDVVWDQGDORQHXQLWV 5<04a+3
 0XOWLFRPELQDWLRQVFDQQHYHUFRQWDLQ5<<4aPRGHOV
 0XOWLFRQWLQXRXVKHDWLQJ5<<4 FRPELQDWLRQVFDQQHYHUFRQWDLQ5;<4 PRGHOV
 0XOWLQRQFRQWLQXRXVKHDWLQJ5;<4 FRPELQDWLRQVFDQQHYHUFRQWDLQ5<04 PRGHOV

'$

RYYQ-T
RYMQ-T
RXYQ-T
Indoor unit combination pattern

VRV* DX
indoor

RA DX
indoor

Hydrobox

AHU (3)

VRV* DX indoor

RA DX indoor

Hydrobox

01

AHU (3)

02

0: allowed
x: forbidden
NOTES

1) VRV* DX indoor
- VRV DX indoor can only be allowed with one of the other combinable indoor units.
eg
Allowed: (VRV DX indoor + Hydro) OR (VRV DX indoor + RA DX indoor) OR (VRV DX indoor + AHU)
Not allowed: [VRV DX indoor + (RA DX indoor & (Hydro or AHU))] OR [VRV DX indoor + (Hydro & (RA DX indoor or AHU))]
2) 01
- Connecting only Hydroboxes without a VRV DX indoor unit to a VRV IV Heat Pump unit is not allowed
 
6HHDOVRFRQQHFWLRQUDWLR &5 UHVWULFWLRQV '
 
2QO\+\GURER[FRQQHFWLRQFI'DLNLQ$OWKHUPDVROXWLRQV
 2QO\FRPSDWLEOH+\GURER[LV+;< VHULHV+\GURER[
 
+;+' +\GURER[LVQRWDOORZHG
3) 02:



AHU connection only (combination with VRV DX indoor units is not allowed; max. 30HP = 3 x 250 class EKEXV kit)
;FRQWUROLVSRVVLEOH XSWR[>(.(;9(.(4) ER[@DUHDOORZHGWRRQHRXWGRRUXQLW V\VWHP QR9DULDEOH5HIULJHUDQW7HPSHUDWXUHFRQWUROSRVVLEOH
<FRQWUROLVSRVVLEOH XSWR[>(.(;9(.(4) ER[@DUHDOORZHGWRRQHRXWGRRUXQLW V\VWHP QR9DULDEOH5HIULJHUDQW7HPSHUDWXUHFRQWUROSRVVLEOH

4) &RPELQDWLRQRI$+8ZLWK+\GURER[RU5$';LQGRRUXQLWVLVQRWDOORZHG
5)  )ROORZLQJDUHFRQVLGHUHGDV$+8

(.(;9(.(4 0) $+8FRLO

%LGGOHDLUFXUWDLQV

);04B0)XQLWV
Information
9.0LVFRQVLGHUHGWREHDUHJXODU959';LQGRRUXQLW

3D079543D(1/2)

VRV Systems RYYQ-T

11

Outdoor Unit RYYQ-T

Combination table

4-1

Combination Table

RYYQ-T
RYMQ-T
RXYQ-T
Indoor/Outdoor combination

RYYQ*
(single CH)

RYYQ*
(multi CH)

RXYQ*
(single n-CH)

RXYQ*
(multi n-CH)

VRV* DX indoor

RA DX indoor

Hydrobox (HXY*)

01

01

AHU (2)

0:
x:

allowed
forbidden
NOTES

1) 01
Upon request through SPN procedure
1) (2) Following are considered as AHU

(.(;9(.(4 0) $+8FRLO

%LGGOHDLUFXUWDLQV

);04B0)XQLWV

3D079543D(2/2)
RYYQ-T
RYMQ-T
RXYQ-T

VRV4 Heat Pump RA DX indoor unit compatibility list


&RQJXUDWLRQ
:DOOPRXQWHG

Emura

)ORRU&HLOLQJ

Flex

)ORRUVWDQGLQJ

FVXS

Nexura

8QLWW\SH
FTXG25J
FTXG35J
FTXG50J
FTXS20K
FTXS25K
FTXS35K
FTXS42K
FTXS50K
FTXS60G
FTXS71G
CTXS15K
CTXS35K
FLXS25B
FLXS35B
FLXS50B
FLXS60B
FVXS25F
FVXS35F
FVXS50F
FVXG25K
FVXG35K
FVXG50K

NOTES

1. Limitations on use of RA DX indoor units with VRV4 Heat Pump is subject to rules mentioned in 3D079543 and 3D079540.
2. Use VRV DX indoor equivalent in case RA/SA DX Cassette, Ceiling mounted or Duct type is needed.

3D082373

12

VRV Systems RYYQ-T

Outdoor Unit RYYQ-T

Combination table

4-1

Combination Table

5<<47

959+HDW3XPS5$';LQGRRUXQLWFRPSDWLELOLW\OLVW
&RQJXUDWLRQ
:DOOPRXQWHG

(PXUD

)ORRU&HLOLQJ

)OH[

)ORRUVWDQGLQJ

)9;6

1H[XUD

8QLWW\SH
)7;*)7;*)7;*)7;6.
)7;6.
)7;6.
)7;6.
)7;6.
)7;6*
)7;6*
&7;6.
&7;6.
)/;6%
)/;6%
)/;6%
)/;6%
)9;6)
)9;6)
)9;6)
)9;*.
)9;*.
)9;*.

127(6

 /LPLWDWLRQVRQXVHRI5$';LQGRRUXQLWVZLWK959+HDW3XPSLVVXEMHFWWRUXOHVPHQWLRQHGLQ'DQG'
 8VH959';LQGRRUHTXLYDOHQWLQFDVH5$6$';&DVVHWWH&HLOLQJPRXQWHGRU'XFWW\SHLVQHHGHG

'

VRV Systems RYYQ-T

13

Outdoor Unit RYYQ-T

Capacity tables

5-1

Capacity Table Legend

,QRUGHUWRIXOOOPRUH\RXUUHTXLUHPHQWVRQTXLFNDFFHVVRIGDWDLQWKHIRUPDW\RXUHTXLUHZHKDYHGHYHORSHGDWRROWR
FRQVXOWFDSDFLW\WDEOHV
%HORZ\RXFDQQGWKHOLQNWRWKHFDSDFLW\WDEOHGDWDEDVHDQGDQRYHUYLHZRIDOOWKHWRROVZHKDYHWRKHOS\RXVHOHFWWKH
FRUUHFWSURGXFW

 &
 DSDFLW\WDEOHGDWDEDVHOHWV\RXQGEDFNDQGH[SRUWTXLFNO\WKHFDSDFLW\LQIRUPDWLRQ\RXDUHORRNLQJIRUEDVHGXSRQXQLW
PRGHOUHIULJHUDQWWHPSHUDWXUHDQGFRQQHFWLRQUDWLR

KWWSH[WUDQHWGDLNLQHXURSHFRPFDSWDE
 (GDWDDSSJLYHVDFRPSOHWHRYHUYLHZRIWKH'DLNLQSURGXFWVDYDLODEOHLQ\RXUFRXQWU\ZLWKDOOHQJLQHHULQJGDWDDQG
FRPPHUFLDOLQIRLQ\RXURZQODQJXDJH'RZQORDGWKHDSSQRZ

KWWSVLWXQHVDSSOHFRPXVDSSGDLNLQHGDWDLG"PW 

 6HOHFWLRQVRIWZDUHDOORZV\RXWRGRORDGFDOFXODWLRQVHTXLSPHQWVHOHFWLRQVDQGHQHUJ\VLPXODWLRQVIRURXU959'DLNLQ
$OWKHUPDUHIULJHUDWLRQDQGDSSOLHGV\VWHPVSURGXFWV

KWWSH[WUDQHWGDLNLQHXURSHFRPHQVRIWZDUHGRZQORDGVGHIDXOWMVS

14

VRV Systems RYYQ-T

Outdoor Unit RYYQ-T

Dimensional drawings

6-1

Dimensional Drawings


3LWFKRIIRXQGDWLRQEROWKROHV

5<<47
5<047

'HWDLO$

[PP2EORQJKROHV
)RXQGDWLRQEROWKROH

'HWDLO%

9LHZ&

02'(/

$$

$%

5<<47



$&


5<<47



5<047







5<047







'
1R

3DUWVQDPH

5HPDUNV

/LTXLGSLSHFRQQHFWLRQSRUW

6HHQRWH

*DVSLSHFRQQHFWLRQSRUW

6HHQRWH

(TXDOL]LQJSLSHFRQQHFWLRQSRUW

6HHQRWH

3RZHUFRUGURXWLQJKROH VLGH



3RZHUFRUGURXWLQJKROH IURQW



3RZHUFRUGURXWLQJKROH IURQW



3RZHUFRUGURXWLQJKROH IURQW



3RZHUFRUGKROH ERWWRP



3LSHURXWLQJKROH IURQW



3LSHURXWLQJKROH ERWWRP



*URXQGLQJWHUPLQDO

,QVLGHRIVZLWFKER[ 0

127(6

 '
 HWDLO$DQGGHWDLO%LQGLFDWHWKHGLPHQVLRQVDIWHU[LQJWKHDWWDFKHGSLSLQJ
 OWHPVWRWNQRFNRXWKROH
 *DVSLSH
EUD]LQJFRQQHFWLRQ5<<475<047
EUD]LQJFRQQHFWLRQ5<<475<047
EUD]LQJFRQQHFWLRQ5<<475<047
/LTXLGSLSH
EUD]LQJFRQQHFWLRQ5<<475<047
EUD]LQJFRQQHFWLRQ5<<475<047
(TXDOL]LQJSLSH
EUD]LQJFRQQHFWLRQ5<047
EUD]LQJFRQQHFWLRQ5<047

3LWFKRIIRXQGDWLRQEROWKROHV

3LWFKRIIRXQGDWLRQEROWKROHV

5<<47
5<047

'HWDLO$

[PP2EORQJKROHV
)RXQGDWLRQEROWKROH

'HWDLO%

9LHZ&

02'(/

$$

$%

5<<475<047





5<<475<047





'
1R

3DUWVQDPH

5HPDUNV

/LTXLGSLSHFRQQHFWLRQSRUW

6HHQRWH

*DVSLSHFRQQHFWLRQSRUW

6HHQRWH

(TXDOL]LQJSLSHFRQQHFWLRQSRUW

6HHQRWH

3RZHUFRUGURXWLQJKROH VLGH



3RZHUFRUGURXWLQJKROH IURQW



3RZHUFRUGURXWLQJKROH IURQW



3RZHUFRUGURXWLQJKROH IURQW



3RZHUFRUGKROH ERWWRP



3LSHURXWLQJKROH IURQW



3LSHURXWLQJKROH ERWWRP



*URXQGLQJWHUPLQDO

,QVLGHRIVZLWFKER[ 0

127(6

 '
 HWDLO$DQGGHWDLO%LQGLFDWHWKHGLPHQVLRQVDIWHU[LQJWKHDWWDFKHGSLSLQJ
 OWHPVWRWNQRFNRXWKROH
 *DVSLSH
EUD]LQJFRQQHFWLRQ5<<475<047

/LTXLGSLSH
EUD]LQJFRQQHFWLRQ5<<475<047
EUD]LQJFRQQHFWLRQ5<<475<047

(TXDOL]LQJSLSH
EUD]LQJFRQQHFWLRQ5<047
EUD]LQJFRQQHFWLRQ5<047

VRV Systems RYYQ-T

15

Outdoor Unit RYYQ-T

Centre of gravity

7-1

Centre of Gravity

5<<47
5<047

&HQWHURI
IRXQGDWLRQEROW
KROH

&HQWHURIIRXQGDWLRQ
EROWKROH

&HQWHURIIRXQGDWLRQ
EROWKROH
8QLW
5<<47
5<047

$$



$%



$&



&HQWHURIIRXQGDWLRQ
EROWKROH 6/27

&HQWHURIIRXQGDWLRQ
EROWKROH 6/27

'
5<<47
5<047

&HQWHURIIRXQGDWLRQ
EROWKROH

&HQWHURI
IRXQGDWLRQEROW
KROH

&HQWHURIIRXQGDWLRQ
EROWKROH

&HQWHURIIRXQGDWLRQ
EROWKROH 6/27

&HQWHURIIRXQGDWLRQ
EROWKROH 6/27

8QLW
5<<47
5<<47
5<047
5<047

$$
7&%
7&%
7&%
7&%

$%
7&%
7&%
7&%
7&%

$&
7&%
7&%
7&%
7&%

'

16

VRV Systems RYYQ-T

Outdoor Unit RYYQ-T

Piping diagrams

8-1

Piping Diagrams

5<047

6HUYLFH
SRUW
)DQ

'RXEOHWXEH
+HDWH[FKDQJHU

)LOWHU

+HDWVLQN
3&%

(OHFWURQLF
H[SDQVLRQ
YDOYH <(
+HDWH[FKDQJHU

(OHFWURQLF
H[SDQVLRQ
YDOYH <(

&DSLOODU\
WXEH

)LOWHU

3UHVVXUH
UHJXODWLQJ
YDOYH

)RXUZD\
YDOYH <6

)LOWHU

&DSLOODU\
WXEH

)LOWHU

)RXUZD\
YDOYH <6

/RZ
SUHVVXUH
VHQVRU
613/

+LJKSUHVVXUH
VHQVRU 613+

)LOWHU

)LOWHU

+LJKSUHVVXUH
VZLWFK 63+

2,/
6(3$5$725

&DSLOODU\WXEH

)LOWHU

&KHFN
YDOYH

2QO\IRU
+3

&KDUJH
SRUW
/LTXLG
SLSH
*DV
SLSH

6ROHQRLG
YDOYH
<6

&RPSUHVVRU

)LOWHU

&DSLOODU\
WXEH

$&&808/$725

6ROHQRLG
YDOYH <6

(TXDOL]LQJ
SLSH
6WRSYDOYH
:LWKVHUYLFHSRUWRQRQVLWHSLSLQJVLGHPPDUHFRQQHFWLRQ

'

VRV Systems RYYQ-T

17

Outdoor Unit RYYQ-T

Piping diagrams

8-1

Piping Diagrams

5<047

6HUYLFH
SRUW
)DQ

)DQ

'RXEOHWXEH
+HDWH[FKDQJHU

)LOWHU
(OHFWURQLF
H[SDQVLRQ
YDOYH <(

+HDWVLQN
3&%

+HDWH[FKDQJHU

3UHVVXUH
UHJXODWLQJ
YDOYH

&DSLOODU\
WXEH

)LOWHU

(OHFWURQLF
H[SDQVLRQ
YDOYH <(

)RXUZD\
YDOYH <6

)LOWHU

&DSLOODU\
WXEH

)LOWHU

)RXUZD\
YDOYH <6

/RZ
SUHVVXUH
VHQVRU
613/

+LJKSUHVVXUH
VHQVRU 613+

&KHFN
YDOYH
)LOWHU
2,/
6(3$5$725
6ROHQRLG
YDOYH
<6

&RPSUHVVRU
&DSLOODU\
WXEH

$&&808/$725
&KDUJH
SRUW
/LTXLG
SLSH
*DV
SLSH

)LOWHU

)LOWHU

+LJKSUHVVXUH
VZLWFK 63+

6ROHQRLG
YDOYH
<6 &RPSUHVVRU
&DSLOODU\
WXEH

)LOWHU

)LOWHU

+LJKSUHVVXUH
VZLWFK 63+

2,/
6(3$5$725

&DSLOODU\WXEH

)LOWHU

&KHFN
YDOYH

2QO\IRU
+3

6ROHQRLG
YDOYH <6

(TXDOL]LQJ
SLSH
6WRSYDOYH
:LWKVHUYLFHSRUWRQRQVLWHSLSLQJVLGHPPDUHFRQQHFWLRQ

'

18

VRV Systems RYYQ-T

Outdoor Unit RYYQ-T

Piping diagrams

8-1

Piping Diagrams

5<<47

6HUYLFH
SRUW
)DQ

'RXEOHWXEH
+HDWH[FKDQJHU

)LOWHU

+HDWVLQN
3&%

(OHFWURQLF
H[SDQVLRQ
YDOYH <(
+HDWH[FKDQJHU

(OHFWURQLF
H[SDQVLRQ
YDOYH <(
+HDWVWRUDJH
YHVVHO

3UHVVXUH
UHJXODWLQJ
YDOYH

)RXUZD\
YDOYH <6
&DSLOODU\WXEH

)LOWHU

(OHFWURQLF
H[SDQVLRQ
YDOYH <(

)RXUZD\
YDOYH <6

/RZ
SUHVVXUH
VHQVRU
613/

+LJKSUHVVXUH
VHQVRU 613+

+LJKSUHVVXUH
VZLWFK 63+

2,/
6(3$5$725

&DSLOODU\WXEH

)LOWHU

&KHFN
YDOYH

)LOWHU

)LOWHU

&RPSUHVVRU
2QO\IRU
+3

&DSLOODU\
WXEH

$&&808/$725

6ROHQRLG
YDOYH
<6

&KDUJH
SRUW
)LOWHU

6ROHQRLG
YDOYH <6

/LTXLG
SLSH
*DV
SLSH
6WRSYDOYH
:LWKVHUYLFHSRUWRQRQVLWHSLSLQJVLGHPPDUHFRQQHFWLRQ

'

VRV Systems RYYQ-T

19

Outdoor Unit RYYQ-T

Piping diagrams

8-1

Piping Diagrams

5<<47

6HUYLFH
SRUW
)DQ

'RXEOHWXEH
+HDWH[FKDQJHU

)DQ

)LOWHU
(OHFWURQLF
+HDWVLQN H[SDQVLRQ
YDOYH <(
3&%
+HDWH[FKDQJHU
(OHFWURQLF
H[SDQVLRQ
YDOYH <(

(OHFWURQLF
H[SDQVLRQ
YDOYH <(

+HDWVWRUDJH
YHVVHO
)RXUZD\
YDOYH <6

&DSLOODU\
WXEH

)LOWHU

3UHVVXUH
UHJXODWLQJ
YDOYH

)LOWHU

)RXUZD\
YDOYH <6

/RZ
SUHVVXUH
VHQVRU
613/

+LJKSUHVVXUH
VHQVRU 613+

2,/
6(3$5$725

&DSLOODU\WXEH

2,/
6(3$5$725
)LOWHU

)LOWHU

+LJKSUHVVXUH
VZLWFK 63+

)LOWHU

&KHFN
YDOYH

)LOWHU

&KHFN
YDOYH

)LOWHU
6ROHQRLG
YDOYH
<6
&DSLOODU\
WXEH

&RPSUHVVRU
&DSLOODU\
WXEH

$&&808/$725

+LJKSUHVVXUH
VZLWFK 63+

6ROHQRLG
YDOYH
<6
&RPSUHVVRU
2QO\IRU
+3

&KDUJH
SRUW
/LTXLG
SLSH

)LOWHU 6ROHQRLG
YDOYH <6

*DV
SLSH
6WRSYDOYH
:LWKVHUYLFHSRUWRQRQVLWHSLSLQJVLGHPPDUHFRQQHFWLRQ

'

20

VRV Systems RYYQ-T

Outdoor Unit RYYQ-T

Wiring diagrams

9-1

Wiring Diagrams - Three Phase

RYYQ8T
RYMQ8T
RXYQ8T
Power supply

9
Seg1

Seg2

On
2II

Seg3

(Note 8)

On
2II

(Note 3)

(Note 9)

TO IN/D UNIT TO OUT/D UNIT

(Note 3)

Selector

/D\RXWRI
0&0)

(Note 4)
(Note 4)

(OFRPSRER[
(OFRPSRER[

indoor
outdoor

Outer Shell

Heat
Cool

Cool
Heat
Fan

7HUPLQDORI
M1C

Cool/heat selector
(optional accessory) (note 3)
(Front side)

A1P
A2P
A3P
A4P
BS1~3
&&
'6'6
E1HC
)8)8
F3U
F101U
F400U
F410U ~ F412U
HAP
K1M
K1R
K3R
K3R
K4R
K6R
K7R

Printed circuit board (main)


3ULQWHGFLUFXLWERDUG QRLVHOWHU
Printed circuit board (inv)
3ULQWHGFLUFXLWERDUG IDQ
3XVKEXWWRQVZLWFK $3  PRGHVHWUHWXUQ
Capacitor (A3P)
Dip switch (A1P)
Crankcase heater
)XVH 7$9  $3
)LHOGIXVH
Fuse (A4P)
Fuse (A2P)
Fuse (A2P)
Pilotlamp (service monitor-green) (A1P)
Magnetic relay (A3P)
Magnetic relay (A3P)
Magnetic relay (A2P)
Magnetic relay (Y3S) (A1P)
Magnetic relay (Y2S) (A1P)
Magnetic relay (Y5S) (A1P)
Magnetic relay (E1HC) (A1P)

K11R
L1R
M1C
M1F
PS
Q1DI
QR1P
R1T
R21T
R3T
R4T
R5T
R6T
R7T
55
R24
R77
R78
S1NPH
S1NPL
S1PH

Magnetic relay (Y1S) (A1P)


Reactor
Motor (compressor)
0RWRU IDQ
6ZLWFKLQJSRZHUVXSSO\ $3$3
Field earth leakage breaker
Phase reversal detect circuit (A1P)
Thermistor (AIR) (A1P)
Thermistor (M1C discharge)
Thermistor (accumulator)
7KHUPLVWRU KHDWH[FOLTSLSH
7KHUPLVWRU VXEFRROOLTSLSH
7KHUPLVWRU KHDWH[FJDVSLSH
7KHUPLVWRU KHDWH[FGHLFHU
Resistor (A3P)
Resistor (current sensor) (A4P)
Resistor (current sensor) (A3P)
Resistor (current limiting) (A3P)
Pressure sensor (high)
Pressure sensor (low)
Pressure switch (disch)

SEG1~SEG3
V1R
;$;$
X3A
X1M
X1M
Y1E
Y2E
Y3E
Y1S
Y2S
Y3S
Y5S
Z1C~Z6C
Z1F

X37A
X66A

(Rear side)

7-segment display (A1P)


Power module (A3P) (A4P)
Connector (M1F)
Connector (check the residual charge)
Terminal block (power supply)
Terminal block (control) (A1P)
(OHFWURQLFH[SDQVLRQYDOYH PDLQ
(OHFWURQLFH[SDQVLRQYDOYH LQMHFWLRQ
(OHFWURQLFH[SDQVLRQYDOYH VWRUDJHYHVVHO  QRWH
Solenoid valve (main)
Solenoid valve (accumulator oil return)
Solenoid valve (OIL1)
Solenoid valve (sub) (note 9)
1RLVHOWHU IHUULWHFRUH
1RLVHOWHU $3  ZLWKVXUJHDEVRUEHU

&RQQHFWRUIRURSWLRQDODFFHVVRULHV
Connector (power adapter)
Connector (remote switching cool/heat selector)

NOTES

1.
2.
3.
4.
5.
6.
7.
8.
9.

This wiring diagram applies only to the outdoor unit.


HOGZLULQJ
WHUPLQDOEORFN
FRQQHFWRU WHUPLQDO
: Protective earth (SREW)
:KHQXVLQJWKHRSWLRQDODGDSWHUUHIHUWRWKHLQVWDOODWLRQPDQXDORIWKHRSWLRQDODGDSWHU
)RUFRQQHFWLRQZLULQJWRLQGRRURXWGRRUWUDQVPLVVLRQ))RXWGRRURXWGRRUWUDQVPLVVLRQ))UHIHUWRWKHLQVWDOODWLRQPDQXDO
How to use BSaVZLWFK5HIHUWRVHUYLFHSUHFDXWLRQODEHORQHOFRPSRER[FRYHU
:KHQRSHUDWLQJGRQWVKRUWFLUFXLWWKHSURWHFWLRQGHYLFH S1PH)
&RORUVEONEODFNUHGUHGEOXEOXHZKWZKLWHJUQJUHHQ
2QO\IRURYYQ model.
2QO\IRURYYQ/RYMQ model.

VRV Systems RYYQ-T

2D083677

21

Outdoor Unit RYYQ-T

Wiring diagrams

9-1

Wiring Diagrams - Three Phase

RYYQ10-12T
RYMQ10-12T
RXYQ10-12T
Power supply

9
Seg1

Seg2

On
2II

Seg3

(Note 8)

On
2II

(Note 3)

(Note 9)

TO IN/D UNIT TO OUT/D UNIT

(Note 3)

Selector

/D\RXWRI
0&0)

(Note 4)
(Note 4)

(OFRPSRER[

indoor

(OFRPSRER[

outdoor

Outer Shell

Heat
Cool

Cool
Heat
Fan

7HUPLQDORI
M1C

Cool/heat selector
(optional accessory) (note 3)
(Front side)

A1P
A2P
A3P
A4P
BS1~3
&&
'6'6
E1HC
)8)8
F101U
F3U
F410U ~ F412U
F601U
HAP
K1M
K1R
K3R
K3R
K4R
K6R
K7R

Printed circuit board (main)


3ULQWHGFLUFXLWERDUG QRLVHOWHU
Printed circuit board (inv)
3ULQWHGFLUFXLWERDUG IDQ
3XVKEXWWRQVZLWFK $3  PRGHVHWUHWXUQ
Capacitor (A3P)
Dip switch (A1P)
Crankcase heater
)XVH 7$9  $3
Fuse (A4P)
)LHOGIXVH
Fuse (A2P)
Fuse (A3P)
Pilotlamp (service monitor-green) (A1P)
Magnetic contactor (A3P)
Magnetic relay (A3P)
Magnetic relay (A3P)
Magnetic relay (Y3S) (A1P)
Magnetic relay (Y2S) (A1P)
Magnetic relay (Y5S) (A1P)
Magnetic relay (E1HC) (A1P)

K11R
/5/5
M1C
M1F
PS
Q1DI
QR1P
R1T
R21T
R3T
R4T
R5T
R6T
R7T
R8T
R1
R24
R313
55
S1NPH
S1NPL

Magnetic relay (Y1S) (A1P)


Reactor
Motor (compressor)
0RWRU IDQ
6ZLWFKLQJSRZHUVXSSO\ $3$3
Field earth leakage breaker
Phase reversal detect circuit (A1P)
Thermistor (AIR) (A1P)
Thermistor (M1C discharge)
Thermistor (accumulator)
7KHUPLVWRU KHDWH[FOLTSLSH
7KHUPLVWRU VXEFRROOLTSLSH
7KHUPLVWRU KHDWH[FJDVSLSH
7KHUPLVWRU KHDWH[FGHLFHU
Thermistor (M1C body)
Resistor (current limiting) (A3P)
Resistor (current sensor) (A4P)
Resistor (current sensor) (A3P)
Resistor (A3P)
Pressure sensor (high)
Pressure sensor (low)

S1PH
SEG1~SEG3
V1R
V2R
;$;$
X3a
X1M
X1M
Y1E
Y2E
Y3E
Y1S
Y2S
Y3S
Y5S
Z1C~Z6C
Z1F
X37A
X66A

(Rear side)

Pressure switch (disch)


7-segment display (A1P)
Power module (A3P) (A4P)
Power module (A3P)
Connector (M1F)
Connector (check the residual charge)
Terminal block (power supply)
Terminal block (control) (A1P)
(OHFWURQLFH[SDQVLRQYDOYH PDLQ
(OHFWURQLFH[SDQVLRQYDOYH LQMHFWLRQ
(OHFWURQLFH[SDQVLRQYDOYH VWRUDJHYHVVHO  QRWH
Solenoid valve (main)
Solenoid valve (accumulator oil return)
Solenoid valve (OIL1)
Solenoid valve (sub) (note 9)
1RLVHOWHU IHUULWHFRUH
1RLVHOWHU $3  ZLWKVXUJHDEVRUEHU
&RQQHFWRUIRURSWLRQDODFFHVVRULHV
Connector (power adapter)
Connector (remote switching cool/heat selector)

NOTES

1.
2.
3.
4.
5.
6.
7.
8.
9.

22

This wiring diagram applies only to the outdoor unit.


HOGZLULQJ
WHUPLQDOEORFN
FRQQHFWRU WHUPLQDO
: Protective earth (SREW)
:KHQXVLQJWKHRSWLRQDODGDSWHUUHIHUWRWKHLQVWDOODWLRQPDQXDORIWKHRSWLRQDODGDSWHU
)RUFRQQHFWLRQZLULQJWRLQGRRURXWGRRUWUDQVPLVVLRQ))RXWGRRURXWGRRUWUDQVPLVVLRQ))UHIHUWRWKHLQVWDOODWLRQPDQXDO
How to use BSaVZLWFK5HIHUWRVHUYLFHSUHFDXWLRQODEHORQHOFRPSRER[FRYHU
:KHQRSHUDWLQJGRQWVKRUWFLUFXLWWKHSURWHFWLRQGHYLFH S1PH)
&RORUVEONEODFNUHGUHGEOXEOXHZKWZKLWHJUQJUHHQ
2QO\IRURYYQ model.
2QO\IRURYYQ/RYMQ model.

VRV Systems RYYQ-T

2D083678

Outdoor Unit RYYQ-T

Wiring diagrams

9-1

Wiring Diagrams - Three Phase

RYYQ14-16T
RYMQ14-16T
RXYQ14-16T
Power supply

Seg1

Seg2

On
2II

Seg3

(Note 7)

On
2II

(Note 8)
(Note 3)
TO IN/D UNIT TO IN/D UNIT
(Note 3)
selector

/D\RXWRI
0&0&0)0)

Heat
Cool

Cool
Heat
Fan

(Note 4)
(Note 4)

(OFRPSRER[

indoor
Cool/heat selector (optional accessory) (note 3)

outdoor
Outer Shell

7HUPLQDORI
0&0&

(OFRPSRER[

&RORUV EONEODFNUHGUHGEOXEOXH
ZKWZKLWHJUQJUHHQ

LVFRQQHFWRUFRORUIRUFRPSRQHQW

LVGLVFULPLQDWLRQFRORUIRU
component lead wire

A1P
$3$3
$3$3
$3$3
BS1~3
&&
'6'6
(+&(+&
)8)8
F101U
F3U
F400U
F410U ~ F412U
HAP
K1M
K1R
K3R
K3R
K4R
K5R
K6R
K7R

Printed circuit board (main)


3ULQWHGFLUFXLWERDUG QRLVHOWHU
Printed circuit board (inv)
3ULQWHGFLUFXLWERDUG IDQ
3XVKEXWWRQVZLWFK $3  PRGHVHWUHWXUQ
&DSDFLWRU $3  $3
Dip switch (A1P)
Crankcase heater
)XVH 7$9  $3
)XVH $3$3
)LHOGIXVH
)XVH $3$3
)XVH $3$3
Pilotlamp (service monitor-green) (A1P)
0DJQHWLFFRQWDFWRU $3$3
0DJQHWLFUHOD\ $3$3
0DJQHWLFUHOD\ $3$3
Magnetic relay (Y4S) (A1P)
Magnetic relay (Y2S) (A1P)
Magnetic relay (Y3S) (A1P)
Magnetic relay (Y5S) (A1P)
Magnetic relay (E1HC) (A1P)

K8R
K11R
/5/5
0&0&
0)0)
PS
Q1DI
QR1P
55
R24
R77
R78
R1T
5757
R3T
R4T
R5T
R6T
R7T
S1NPH
S1NPL
63+63+

Magnetic relay (E2HC) (A1P)


Magnetic relay (Y1S) (A1P)
Reactor
Motor (compressor)
0RWRU IDQ
6ZLWFKLQJSRZHUVXSSO\ $3$3$3
Field earth leakage breaker
Phase reversal detect circuit (A1P)
5HVLVWRU $3$3
5HVLVWRU FXUUHQWVHQVRU  $3$3
5HVLVWRU FXUUHQWVHQVRU  $3$3
5HVLVWRU FXUUHQWOLPLWLQJ  $3$3
Thermistor (AIR) (A1P)
7KHUPLVWRU 0&0&GLVFKDUJH 
Thermistor (accumulator)
7KHUPLVWRU KHDWH[FOLTSLSH
7KHUPLVWRU VXEFRROOLTSLSH
7KHUPLVWRU KHDWH[FJDVSLSH
7KHUPLVWRU KHDWH[FGHLFHU
Pressure sensor (high)
Pressure sensor (low)
Pressure switch (disch)

SEG1~SEG3
V1R
V1R
X1A~4A
X5A~X6A
X1M
X1M
Y1E
Y2E
Y3E
Y1S
Y2S
Y3S
Y4S
Y5S
Z1C~Z7C
Z1F

X37A
X66A

7-segment display (A1P)


3RZHUPRGXOH $3$3
3RZHUPRGXOH $3$3
&RQQHFWRU 0)0)
Connector (check the residual charge)
Terminal block (power supply)
Terminal block (control) (A1P)
(OHFWURQLFH[SDQVLRQYDOYH PDLQ
(OHFWURQLFH[SDQVLRQYDOYH LQMHFWLRQ
(OHFWURQLFH[SDQVLRQYDOYH VWRUDJHYHVVHO  QRWH
Solenoid valve (main)
Solenoid valve (accumulator oil return)
Solenoid valve (OIL1)
Solenoid valve (OIL2)
Solenoid valve (sub) (note 8)
1RLVHOWHU IHUULWHFRUH
1RLVHOWHU $3$3  ZLWKVXUJHDEVRUEHU
&RQQHFWRUIRURSWLRQDODFFHVVRULHV
Connector (power adapter)
Connector (remote switching cool/heat selector)

NOTES

1.
2.
3.
4.
5.
6.
7.
8.

This wiring diagram applies only to the outdoor unit.


HOGZLULQJ
WHUPLQDOEORFN
FRQQHFWRU WHUPLQDO
: Protective earth (SREW)
:KHQXVLQJWKHRSWLRQDODGDSWHUUHIHUWRWKHLQVWDOODWLRQPDQXDORIWKHRSWLRQDODGDSWHU
)RUFRQQHFWLRQZLULQJWRLQGRRURXWGRRUWUDQVPLVVLRQ))RXWGRRURXWGRRUWUDQVPLVVLRQ))UHIHUWRWKHLQVWDOODWLRQPDQXDO
How to use BSaVZLWFK5HIHUWRVHUYLFHSUHFDXWLRQODEHORQHOFRPSRER[FRYHU
:KHQRSHUDWLQJGRQWVKRUWFLUFXLWWKHSURWHFWLRQGHYLFH 63+63+)
2QO\IRURYYQ model.
2QO\IRURYYQ/RYMQ model.

2D083679

VRV Systems RYYQ-T

23

Outdoor Unit RYYQ-T

Wiring diagrams

9-1

Wiring Diagrams - Three Phase

RYYQ18-20T
RYMQ18-20T
RXYQ18-20T
Power supply

Seg1

Seg2

On
2II

(Note 7)

Seg3

On
2II

(Note 8)
(Note 3)
TO IN/D UNIT TO IN/D UNIT
(Note 3)
selector

/D\RXWRI
0&0&0)0)

Heat
Cool

Cool
Heat
Fan

(Note 4)
(Note 4)

(OFRPSRER[

indoor
Cool/heat selector (optional accessory) (note 3)

(OFRPSRER[

&RORUV EONEODFNUHGUHGEOXEOXH
ZKWZKLWHJUQJUHHQ

LVFRQQHFWRUFRORUIRUFRPSRQHQW

LVGLVFULPLQDWLRQFRORUIRU
component lead wire

A1P
$3$3
$3$3
$3$3
BS1~3
&&
&&
'6'6
(+&(+&
)8)8
F3U
F101U
F400U
F410U ~ F412U
F601U
HAP
K1M
K1R
K3R
K3R
K4R
K5R
K6R
K7R
K8R

Printed circuit board (main)


3ULQWHGFLUFXLWERDUG QRLVHOWHU
Printed circuit board (inv)
3ULQWHGFLUFXLWERDUG IDQ
3XVKEXWWRQVZLWFK $3  PRGHVHWUHWXUQ
Capacitor (A3P)
Capacitor (A6P)
Dip switch (A1P)
Crankcase heater
)XVH 7$9  $3
)LHOGIXVH
)XVH $3$3 
Fuse (A2P)
)XVH $3$3
Fuse (A6P)
Pilotlamp (service monitor-green) (A1P)
0DJQHWLFFRQWDFWRU $3$3
0DJQHWLFUHOD\ $3$3
0DJQHWLFUHOD\ $3$3
Magnetic relay (Y4S) (A1P)
Magnetic relay (Y2S) (A1P)
Magnetic relay (Y3S) (A1P)
Magnetic relay (Y5S) (A1P)
Magnetic relay (E1HC) (A1P)
Magnetic relay (E2HC) (A1P)

K11R
L1R ~ L3R
0&0&
0)0)
PS
Q1DI
QR1P
R1
55
R24
R77
R78
R313
55
R1T
5757
R3T
R4T
R5T
R6T
R7T
R8T
S1NPH
S1NPL
63+63+

Magnetic relay (Y1S) (A1P)


Reactor
Motor (compressor)
0RWRU IDQ
6ZLWFKLQJSRZHUVXSSO\ $3$3$3
Field earth leakage breaker
Phase reversal detect circuit (A1P)
Resistor (current limiting) (A6P)
Resistor (A3P)
5HVLVWRU FXUUHQWVHQVRU  $3$3
Resistor (current sensor) (A3P)
Resistor (current limiting) (A3P)
Resistor (current censor) (A6P)
Resistor (A6P)
Thermistor (AIR) (A1P)
7KHUPLVWRU 0&0&GLVFKDUJH 
Thermistor (accumulator)
7KHUPLVWRU KHDWH[FOLTSLSH
7KHUPLVWRU VXEFRROOLTSLSH
7KHUPLVWRU KHDWH[FJDVSLSH
7KHUPLVWRU KHDWH[FGHLFHU
7KHUPLVWRU 0&ERG\
Pressure sensor (high)
Pressure sensor (low)
Pressure switch (disch)

outdoor
Outer Shell

7HUPLQDORI
0&0&

SEG1~SEG3
V1R
V1R
V2R
X1A~4A
X5A~X6A
X1M
X1M
Y1E
Y2E
Y3E
Y1S
Y2S
Y3S
Y4S
Y5S
Z1C~Z7C
Z1F

X37A
X66A

7-segment display (A1P)


3RZHUPRGXOH $3$3
3RZHUPRGXOH $3$3
Power module (A6P)
&RQQHFWRU 0)0)
Connector (check the residual charge)
Terminal block (power supply)
Terminal block (control) (A1P)
(OHFWURQLFH[SDQVLRQYDOYH PDLQ
(OHFWURQLFH[SDQVLRQYDOYH LQMHFWLRQ
(OHFWURQLFH[SDQVLRQYDOYH VWRUDJHYHVVHO  QRWH
Solenoid valve (main)
Solenoid valve (accumulator oil return)
Solenoid valve (OIL1)
Solenoid valve (OIL2)
Solenoid valve (sub) (note 8)
1RLVHOWHU IHUULWHFRUH
1RLVHOWHU $3$3  ZLWKVXUJHDEVRUEHU

&RQQHFWRUIRURSWLRQDODFFHVVRULHV
Connector (power adapter)
Connector (remote switching cool/heat selector)

NOTES

1.
2.
3.
4.
5.
6.
7.
8.

This wiring diagram applies only to the outdoor unit.


HOGZLULQJ
WHUPLQDOEORFN
FRQQHFWRU WHUPLQDO
: Protective earth (SREW)
:KHQXVLQJWKHRSWLRQDODGDSWHUUHIHUWRWKHLQVWDOODWLRQPDQXDORIWKHRSWLRQDODGDSWHU
)RUFRQQHFWLRQZLULQJWRLQGRRURXWGRRUWUDQVPLVVLRQ))RXWGRRURXWGRRUWUDQVPLVVLRQ))UHIHUWRWKHLQVWDOODWLRQPDQXDO
How to use BSaVZLWFK5HIHUWRVHUYLFHSUHFDXWLRQODEHORQHOFRPSRER[FRYHU
:KHQRSHUDWLQJGRQWVKRUWFLUFXLWWKHSURWHFWLRQGHYLFH 63+63+)
2QO\IRURYYQ model.
2QO\IRURYYQ/RYMQ model.

2D083680

24

VRV Systems RYYQ-T

Outdoor Unit RYYQ-T

10

External connection diagrams

10 - 1 External Connection Diagrams


5<<47

3RZHU6XSSO\

0DLQ6ZLWFK

2XWGRRUXQLWV

6ZLWFK

10

)XVH

3RZHU6XSSO\

0DLQ6ZLWFK

:LUHVFDEOH
7UDQVPLVVLRQOLQH
:LUHVFDEOH

:LUHVFDEOH

:LUHVFDEOH

7UDQVPLVVLRQOLQH

7UDQVPLVVLRQOLQH

7UDQVPLVVLRQOLQH

3RZHUOLQH

6ZLWFK

6ZLWFK

)XVH
:LUHVFDEOH

6ZLWFK

)XVH
:LUHVFDEOH

3RZHUOLQH

6ZLWFK

)XVH

)XVH

:LUHVFDEOH
3RZHUOLQH

3RZHUOLQH

:LUHVFDEOH
3RZHUOLQH

,QGRRUXQLWV

'

127(6












$OOZLULQJFRPSRQHQWVDQGPDWHULDOVWREHSURFXUHGRQWKHVLWHPXVWFRPSO\ZLWKWKHDSSOLFDEOHORFDODQGQDWLRQDOFRGHV
8VHFRSSHUFRQGXFWRUVRQO\
$VIRUGHWDLOVVHHZLULQJGLDJUDP
,QVWDOOFLUFXLWEUHDNHUIRUVDIHW\
$OOHOGZLULQJDQGFRPSRQHQWVPXVWEHSURYLGHGE\OLFHQVHGHOHFWULFLDQ
8QLWVKDOOEHJURXQGHGLQFRPSOLDQFHZLWKWKHDSSOLFDEOHORFDODQGQDWLRQDOFRGHV
:LULQJVKRZQDUHJHQHUDOSRLQWVRIFRQQHFWLRQJXLGHVRQO\DQGDUHQRWLQWHQGHGIRURUWRLQFOXGHDOOGHWDLOVIRUDVSHFLFLQVWDOODWLRQ
%HVXUHWRLQVWDOOWKHVZLWFKDQGWKHIXVHWRWKHSRZHUOLQHRIHDFKHTXLSHPHQW
,QVWDOOWKHPDLQVZLWFKWKDWFDQLQWHUUXSWDOOWKHSRZHUVRXUFHVLQDQLQWHJUDWHGPDQQHUEHFDXVHWKLVV\VWHPFRQVLVWVRIWKHHTXLSPHQWXWLOL]LQJWKHPXOWLSOHSRZHUVRXUFHV
,IWKHUHH[LVWVWKHSRVVLELOLW\RIUHYHUVHGSKDVHORVHSKDVHPRPHQWDU\EODFNRXWRUWKHSRZHUJRHVRQDQGRIIZKLOHWKHSURGXFWLVRSHUDWLQJDWWDFKDUHYHUVHGSKDVHSURWHFWLRQFLUFXLWORFDOO\
5XQQLQJWKHSURGXFWLQUHYHUVHGSKDVHPD\EUHDNWKHFRPSUHVVRUDQGRWKHUSDUWV
 0XVWLQVWDOOHDUWKOHDNDJHFLUFXLWEUHDNHU

5<<47

3RZHU6XSSO\

3RZHU6XSSO\

:KHQWKHSRZHUVRXUFHLVVXSSOLHGWRHDFKRXWGRRUXQLWLQGLYLGXDOO\!

2XWGRRUXQLWV

0DLQ
6ZLWFK

:KHQWKHSRZHUVRXUFHLVFRQQHFWHGLQVHULHVEHWZHHQWKHXQLWV!

2XWGRRUXQLWV

0DLQ
6ZLWFK

:LUHVFDEOH
7UDQVPLVVLRQOLQH

:LUHVFDEOH
7UDQVPLVVLRQOLQH

3RZHU6XSSO\

3RZHU6XSSO\

0DLQ
6ZLWFK

0DLQ
6ZLWFK

:LUHVFDEOH
7UDQVPLVVLRQOLQH
:LUHVFDEOH
3RZHUOLQH

6ZLWFK
)XVH

:LUHVFDEOH
7UDQVPLVVLRQOLQH
:LUHVFDEOH
7UDQVPLVVLRQOLQH

:LUHVFDEOH
7UDQVPLVVLRQOLQH

6ZLWFK
)XVH

6ZLWFK
)XVH

:LUHVFDEOH
7UDQVPLVVLRQOLQH

6ZLWFK
)XVH

:LUHVFDEOH
3RZHUOLQH
:LUHVFDEOH
3RZHUOLQH

:LUHVFDEOH
3RZHUOLQH

:LUHVFDEOH
3RZHUOLQH

,QGRRUXQLWV

:LUHVFDEOH
3RZHUOLQH

:LUHVFDEOH
7UDQVPLVVLRQOLQH

6ZLWFK

6ZLWFK

)XVH

:LUHVFDEOH
3RZHUOLQH

)XVH

:LUHVFDEOH
3RZHUOLQH

:LUHVFDEOH
7UDQVPLVVLRQOLQH

6ZLWFK
)XVH

:LUHVFDEOH
3RZHUOLQH

,QGRRUXQLWV

:LUHVFDEOH
7UDQVPLVVLRQOLQH

6ZLWFK
)XVH

:LUHVFDEOH
3RZHUOLQH

'

127(6

 $OOZLULQJFRPSRQHQWVDQGPDWHULDOVWREHSURFXUHGRQWKHVLWHPXVWFRPSO\ZLWKWKHDSSOLFDEOHORFDODQGQDWLRQDOFRGHV
 8VHFRSSHUFRQGXFWRUVRQO\
 $VIRUGHWDLOVVHHZLULQJGLDJUDP
 ,QVWDOOFLUFXLWEUHDNHUIRUVDIHW\
 $OOHOGZLULQJDQGFRPSRQHQWVPXVWEHSURYLGHGE\OLFHQVHGHOHFWULFLDQ
 8QLWVKDOOEHJURXQGHGLQFRPSOLDQFHZLWKWKHDSSOLFDEOHORFDODQGQDWLRQDOFRGHV
 :LULQJVKRZQDUHJHQHUDOSRLQWVRIFRQQHFWLRQJXLGHVRQO\DQGDUHQRWLQWHQGHGIRURUWRLQFOXGHDOOGHWDLOVIRUDVSHFLFLQVWDOODWLRQ
 %HVXUHWRLQVWDOOWKHVZLWFKDQGWKHIXVHWRWKHSRZHUOLQHRIHDFKHTXLSHPHQW
 ,QVWDOOWKHPDLQVZLWFKWKDWFDQLQWHUUXSWDOOWKHSRZHUVRXUFHVLQDQLQWHJUDWHGPDQQHUEHFDXVHWKLVV\VWHPFRQVLVWVRIWKHHTXLSPHQWXWLOL]LQJWKHPXOWLSOHSRZHUVRXUFHV
 WKHFDSDFLW\RI81,7PXVWEHODUJHUWKDQ81,7ZKHQWKHSRZHUVRXUFHLVFRQQHFWHGLQVHULHVEHWZHHQWKHXQLWV
 ,IWKHUHH[LVWVWKHSRVVLELOLW\RIUHYHUVHGSKDVHORVHSKDVHPRPHQWDU\EODFNRXWRUWKHSRZHUJRHVRQDQGRIIZKLOHWKHSURGXFWLVRSHUDWLQJDWWDFKDUHYHUVHGSKDVHSURWHFWLRQFLUFXLWORFDOO\
5XQQLQJWKHSURGXFWLQUHYHUVHGSKDVHPD\EUHDNWKHFRPSUHVVRUDQGRWKHUSDUWV
 0XVWLQVWDOOHDUWKOHDNDJHFLUFXLWEUHDNHU

VRV Systems RYYQ-T

25

Outdoor Unit RYYQ-T

10

External connection diagrams

10 - 1 External Connection Diagrams


5<<47

:KHQWKHSRZHUVRXUFHLVVXSSOLHGWRHDFKRXWGRRUXQLWLQGLYLGDXOO\!

:KHQWKHSRZHUVRXUVHLVFRQQHFWHGLQVHULHVEHWZHHQWKHXQLWV!

287'22581,76

3RZHUVXSSO\
0DLQ
VZLWFK

287'22581,76

3RZHUVXSSO\
0DLQ
VZLWFK

10

ZLUHVFDEOH
ZLUHVFDEOH
7UDQVPLVVLRQOLQH 7UDQVPLVVLRQOLQH
81,7
81,7

81,7
6ZLWFK

6ZLWFK
)XVH

)XVH

81,7

6ZLWFK
)XVH

ZLUHVFDEOH
ZLUHVFDEOH
7UDQVPLVVLRQOLQH 7UDQVPLVVLRQOLQH
81,7
81,7

6ZLWFK
3RZHUVXSSO\

3RZHUVXSSO\
0DLQ
VZLWFK

0DLQ
VZLWFK

ZLUHVFDEOH
7UDQVPLVVLRQOLQH
ZLUHVFDEOH
3RZHUOLQH 6ZLWFK
)XVH
ZLUHVFDEOH
3RZHUOLQH

ZLUHVFDEOH
7UDQVPLVVLRQOLQH
ZLUHVFDEOH
7UDQVPLVVLRQOLQH

ZLUHVFDEOH
7UDQVPLVVLRQOLQH

ZLUHVFDEOH
7UDQVPLVVLRQOLQH

6ZLWFK
)XVH

6ZLWFK
)XVH

6ZLWFK
)XVH

ZLUHVFDEOH
3RZHUOLQH

ZLUHVFDEOH
3RZHUOLQH

ZLUHVFDEOH
3RZHUOLQH

,1'22581,76

ZLUHVFDEOH
3RZHUOLQH
6ZLWFK
)XVH
ZLUHVFDEOH
3RZHUOLQH

ZLUHVFDEOH
7UDQVPLVVLRQOLQH

ZLUHVFDEOH
7UDQVPLVVLRQOLQH

6ZLWFK
)XVH
ZLUHVFDEOH
3RZHUOLQH

6ZLWFK
)XVH
ZLUHVFDEOH
3RZHUOLQH

ZLUHVFDEOH
7UDQVPLVVLRQOLQH

6ZLWFK
)XVH
ZLUHVFDEOH
3RZHUOLQH

,1'22581,76

'
127(6

 $OOZLULQJFRPSRQHQWVDQGPDWHULDOVWREHSURGXFHGRQWKHVLWHPXVWFRPSO\ZLWKWKHDSSOLFDEOHORFDODQGQDWLRQDOFRGHV
 8VHFRSSHUFRQGXFWRUVRQO\
 $VIRUGHWDLOVVHHZLULQJGLDJUDP
 ,QVWDOOFLUFXLWEUHDNHUIRUVDIHW\
 $OOHOGZLULQJDQGFRPSRQHQWVPXVWEHSURYLGHGE\OLFHQVHGHOHFWULFLDQ
 8QLWVKDOOEHJURXQGHGLQFRPSOLDQFHZLWKWKHDSSOLFDEOHORFDODQGQDWLRQDOFRGHV
 :LULQJVKRZQDUHJHQHUDOSRLQWVRIFRQQHFWLRQJXLGHVRQO\DQGDUHQRJLQWHQGHGIRURUWRLQFOXGHDOOGHWDLOVIRUDVSHFLFLQVWDOODWLRQ
 %HVXUHWRLQVWDOOWKHVZLWFKDQGWKHIXVHWRWKHSRZHUOLQHRIHDFKHTXLSHPHQW
 ,QVWDOOWKHPDLQVZLWFKWKDWFDQLQWHUUXSWDOOWKHSRZHUVRXUFHVLQDQLQWHJUDWHGPDQQHUEHFDXVHWKLVV\VWHPFRQVLVWVRIWKHHTXLSPHQWXWLOL]LQJWKHPXOWLSOHSRZHUVRXUFHV
 7KHFDSDFLW\RI81,7PXVWEHODUJHUWKDQ81,7ZKHQWKHSRZHUVRXUFHLVFRQQHFWHGLQVHULHVEHWZHHQWKHXQLWV
 ,IWKHUHH[LVWVWKHSRVVLELOLW\RIUHYHUVHGSKDVHORVHSKDVHPRPHQWDU\EODFNRXWRUWKHSRZHUJRHVRQDQGRIIZKLOHWKHSURGXFWLVRSHUDWLQJDWWDFKDUHYHUVHGSKDVHSURWHFWLRQFLUFXLWORFDOO\
5XQQLQJWKHSURGXFWLQUHYHUVHGSKDVHPD\EUHDNWKHFRPSUHVVRUDQGRWKHUSDUWV
 0XVWLQVWDOOHDUWKOHDNDJHFLUFXLWEUHDNHU

26

VRV Systems RYYQ-T

Outdoor Unit RYYQ-T

11

Sound data

11 - 1 Sound Power Spectrum

5<<47
5<047

11

6RXQGSRZHUOHYHO>G%@

6RXQGSRZHUOHYHO>G%@

5<<47
5<047

G%$

G%$

2FWDYHEDQGFHQWHUIUHTXHQF\>+]@

2FWDYHEDQGFHQWHUIUHTXHQF\>+]@

'
127(6

'
127(6

 G%$ $ZHLJKWHGVRXQGSRZHUOHYHO $VFDOHDFFRUGLQJWR,(&


 5HIHUHQFHDFRXVWLFLQWHQVLW\G% (:P
 0HDVXUHGDFFRUGLQJWR,62

 G%$ $ZHLJKWHGVRXQGSRZHUOHYHO $VFDOHDFFRUGLQJWR,(&


 5HIHUHQFHDFRXVWLFLQWHQVLW\G% (:P
 0HDVXUHGDFFRUGLQJWR,62

6RXQGSRZHUOHYHO>G%@

5<<47
5<047

6RXQGSRZHUOHYHO>G%@

5<<47
5<047

G%$

G%$

2FWDYHEDQGFHQWHUIUHTXHQF\>+]@

2FWDYHEDQGFHQWHUIUHTXHQF\>+]@

'
127(6

'
127(6

 G%$ $ZHLJKWHGVRXQGSRZHUOHYHO $VFDOHDFFRUGLQJWR,(&


 5HIHUHQFHDFRXVWLFLQWHQVLW\G% (:P
 0HDVXUHGDFFRUGLQJWR,62

VRV Systems RYYQ-T

 G%$ $ZHLJKWHGVRXQGSRZHUOHYHO $VFDOHDFFRUGLQJWR,(&


 5HIHUHQFHDFRXVWLFLQWHQVLW\G% (:P
 0HDVXUHGDFFRUGLQJWR,62

27

Outdoor Unit RYYQ-T

11

Sound data

11 - 1 Sound Power Spectrum

6RXQGSRZHUOHYHO>G%@

11

5<<47
5<047

6RXQGSRZHUOHYHO>G%@

5<<47
5<047

G%$

G%$

2FWDYHEDQGFHQWHUIUHTXHQF\>+]@

2FWDYHEDQGFHQWHUIUHTXHQF\>+]@

'
127(6

127(6

 G%$ $ZHLJKWHGVRXQGSRZHUOHYHO $VFDOHDFFRUGLQJWR,(&


 5HIHUHQFHDFRXVWLFLQWHQVLW\G% (:P
 0HDVXUHGDFFRUGLQJWR,62

 G%$ $ZHLJKWHGVRXQGSRZHUOHYHO $VFDOHDFFRUGLQJWR,(&


 5HIHUHQFHDFRXVWLFLQWHQVLW\G% (:P
 0HDVXUHGDFFRUGLQJWR,62

6RXQGSRZHUOHYHO>G%@

5<<47
5<047

G%$
2FWDYHEDQGFHQWHUIUHTXHQF\>+]@

'
127(6

 G%$ $ZHLJKWHGVRXQGSRZHUOHYHO $VFDOHDFFRUGLQJWR,(&


 5HIHUHQFHDFRXVWLFLQWHQVLW\G% (:P
 0HDVXUHGDFFRUGLQJWR,62

28

'

VRV Systems RYYQ-T

Outdoor Unit RYYQ-T

11

Sound data

11 - 2 Sound Pressure Spectrum

5<<47
5<047

11

6RXQGSUHVVXUHOHYHO>G%@

6RXQGSUHVVXUHOHYHO>G%@

5<<47
5<047

G%$

G%$

2FWDYHEDQGFHQWHUIUHTXHQF\>+]@

2FWDYHEDQGFHQWHUIUHTXHQF\>+]@

'
127(6

'
127(6

P

P

IURQWVLGH

 'DWDLVYDOLGDWIUHHHOGFRQGLWLRQ
 'DWDLVYDOLGDWQRPLQDORSHUDWLRQFRQGLWLRQ
 G%$ $ZHLJKWHGVRXQGSUHVVXUHOHYHO $VFDOHDFFRUGLQJWR,(&
 5HIHUHQFHDFRXVWLFSHVVXUHVG% 3D
 0HDVXULQJSRVLWLRQ

P

IURQWVLGH

 'DWDLVYDOLGDWIUHHHOGFRQGLWLRQ
 'DWDLVYDOLGDWQRPLQDORSHUDWLRQFRQGLWLRQ
 G%$ $ZHLJKWHGVRXQGSUHVVXUHOHYHO $VFDOHDFFRUGLQJWR,(&
 5HIHUHQFHDFRXVWLFSHVVXUHVG% 3D
 0HDVXULQJSRVLWLRQ

P

6RXQGSUHVVXUHOHYHO>G%@

5<<47
5<047

6RXQGSUHVVXUHOHYHO>G%@

5<<47
5<047

G%$

G%$

2FWDYHEDQGFHQWHUIUHTXHQF\>+]@

2FWDYHEDQGFHQWHUIUHTXHQF\>+]@

'
127(6

'
127(6

 'DWDLVYDOLGDWIUHHHOGFRQGLWLRQ
 'DWDLVYDOLGDWQRPLQDORSHUDWLRQFRQGLWLRQ
 G%$ $ZHLJKWHGVRXQGSUHVVXUHOHYHO $VFDOHDFFRUGLQJWR,(&
 5HIHUHQFHDFRXVWLFSHVVXUHVG% 3D
 0HDVXULQJSRVLWLRQ
P

IURQWVLGH

P

IURQWVLGH

 'DWDLVYDOLGDWIUHHHOGFRQGLWLRQ
 'DWDLVYDOLGDWQRPLQDORSHUDWLRQFRQGLWLRQ
 G%$ $ZHLJKWHGVRXQGSUHVVXUHOHYHO $VFDOHDFFRUGLQJWR,(&
 5HIHUHQFHDFRXVWLFSHVVXUHVG% 3D
 0HDVXULQJSRVLWLRQ

P

P

VRV Systems RYYQ-T

29

Outdoor Unit RYYQ-T

11

Sound data

11 - 2 Sound Pressure Spectrum

6RXQGSUHVVXUHOHYHO>G%@

11

5<<47
5<047

6RXQGSUHVVXUHOHYHO>G%@

5<<47
5<047

G%$

G%$

2FWDYHEDQGFHQWHUIUHTXHQF\>+]@

2FWDYHEDQGFHQWHUIUHTXHQF\>+]@

'
127(6

127(6

P

P

6RXQGSUHVVXUHOHYHO>G%@

5<<47
5<047

G%$
2FWDYHEDQGFHQWHUIUHTXHQF\>+]@

'
127(6

 'DWDLVYDOLGDWIUHHHOGFRQGLWLRQ
 'DWDLVYDOLGDWQRPLQDORSHUDWLRQFRQGLWLRQ
 G%$ $ZHLJKWHGVRXQGSUHVVXUHOHYHO $VFDOHDFFRUGLQJWR,(&
 5HIHUHQFHDFRXVWLFSHVVXUHVG% 3D
 0HDVXULQJSRVLWLRQ
P

IURQWVLGH

P

IURQWVLGH

 'DWDLVYDOLGDWIUHHHOGFRQGLWLRQ
 'DWDLVYDOLGDWQRPLQDORSHUDWLRQFRQGLWLRQ
 G%$ $ZHLJKWHGVRXQGSUHVVXUHOHYHO $VFDOHDFFRUGLQJWR,(&
 5HIHUHQFHDFRXVWLFSHVVXUHVG% 3D
 0HDVXULQJSRVLWLRQ

P

IURQWVLGH

 'DWDLVYDOLGDWIUHHHOGFRQGLWLRQ
 'DWDLVYDOLGDWQRPLQDORSHUDWLRQFRQGLWLRQ
 G%$ $ZHLJKWHGVRXQGSUHVVXUHOHYHO $VFDOHDFFRUGLQJWR,(&
 5HIHUHQFHDFRXVWLFSHVVXUHVG% 3D
 0HDVXULQJSRVLWLRQ

P

30

'

VRV Systems RYYQ-T

Outdoor Unit RYYQ-T

12

Installation

12 - 1 Installation Method

5<<47
5<047

)RUVLQJOHXQLWLQVWDOODWLRQ
3DWWHUQ

)RULQVWDOODWLRQLQURZV
3DWWHUQ

RUPRUH

3DWWHUQ
RUPRUH

RU
PRUH

)5217 
RUPRUH

3DWWHUQ

RU
PRUH

RUPRUH

)5217 
RUPRUH

RUPRUH

RUPRUH RUPRUH

RUPRUH

)5217 
RUPRUH

RUPRUH

)5217 
RUPRUH

RUPRUH

RUPRUH
RUPRUH

)5217 
RUPRUH

RUPRUH
RUPRUH

RUPRUH

)5217

RUPRUH

RUPRUH RUPRUH

RUPRUH

RUPRUH

RUPRUH
RUPRUH

3DWWHUQ
RUPRUH

RUPRUH

RUPRUH

)5217 
RUPRUH

RUPRUH

RU
PRUH RUPRUH

3DWWHUQ
RUPRUH

RUPRUH

RUPRUH

RUPRUH

RUPRUH
)5217

RUPRUH

RUPRUH

3DWWHUQ
RUPRUH

)5217 
RUPRUH

RUPRUH

RUPRUH
RU
PRUH

3DWWHUQ

:DOOKHLJKWXQUHVWULFWHG

:DOOKHLJKW
XQUHVWULFWHG

RUPRUH

RUPRUH

RUPRUH
RUPRUH

)5217

RUPRUH

RUPRUH

)5217 
RUPRUH

)5217 
RUPRUH

RUPRUH

RUPRUH

RU
PRUH
RU
PRUH RUPRUH
RU
PRUH
RUPRUH
RUPRUH

)5217

)5217 
RUPRUH

RUPRUH

RUPRUH
RUPRUH

RUPRUH

RUPRUH

RUPRUH
RUPRUH

RUPRUH
RUPRUH

RUPRUH RUPRUH

RUPRUH

)URQW!

)5217 
RUPRUH

RUPRUH

)5217
RUPRUH

RUPRUH

6XFWLRQVLGH!

RUPRUH

12

)RUFHQWUDOL]HGJURXSOD\RXW

127(6

 +HLJKWVRIZDOOVLQFDVHRISDWWHUQVDQG
)URQWPP
6XFWLRQVLGHPP
6LGH+HLJKWXQUHVWULFWHG
,QVWDOODWLRQVSDFHDVVKRZQRQWKLVGUDZLQJLVEDVHGRQWKHFRROLQJRSHUDWLRQDWGHJUHHVRXWGRRUDLUWHPSHUDWXUH
:KHQWKHGHVLJQRXWGRRUDLUWHPSHUDWXUHH[FHHGVGHJUHHVRUWKHORDGH[FHHGVPD[LPXPDELOLW\RIPXFKJHQHUDWLRQORDGRIKHDWLQDOORXWGRRUXQLWWDNHWKHVXFWLRQVLGHVSDFHPRUH
EURDGO\WKDQWKHVSDFHDVVKRZQRQWKLVGUDZLQJ
 ,IWKHDERYHZDOOKHLJKWVDUHH[FHHGHGWKHQKDQGKVKRXOGEHDGGHGWRWKHIURQWDQGVXFWLRQVLGHVHUYLFHVSDFHVUHVSHFWLYHO\DVVKRZQLQWKHJXUHRQWKHULJKW
 :KHQLQVWDOOLQJWKHXQLWVPRVWDSSURSULDWHSDWWHUQVKRXOGEHVHOHFWHGIURPWKRVHVKRZQDERYHLQRUGHUWRREWDLQWKHEHVWWLQWKH
VSDFHDYDLODEOH$OZD\VNHHSLQPLQGWKHQHHGWROHDYHHQRXJKVSDFHIRUDSHUVRQWRSDVVEHWZHHQXQLWVDQGZDOODQGDOVRIRUWKHDLUWRFLUFXODWHIUHHO\
,IPRUHXQLWVDUHWREHLQVWDOOHGWKDQDUHFDWHUHGIRULQWKHDERYHSDWWHUQV\RXUOD\RXWVKRXOGWDNHDFFRXQWRIWKHSRVVLELOLW\RIVKRUWFLUFXLWV 
 7KHXQLWVVKRXOGEHLQVWDOOHGWROHDYHVXIFLHQWVSDFHDWWKHIURQWIRUWKHRQVLWHUHIULJHUDQWSLSLQJZRUNWREHFDUULHGRXWFRPIRUWDEO\

'

VRV Systems RYYQ-T

31

Outdoor Unit RYYQ-T

12

Installation

12 - 2 Fixation and Foundation of Units


RYYQ-T
RYMQ-T
RXYQ-T

Nut
Spring washer
Frame

Foundation bolt type: JA


Size: M12
Four bolts are required
3 thread ridges or more

12

Drain ditch

Foundation bolt executing method

(Smooth down grade of 1/50)

Y ditch
When building a
foundation on the
ground
Y
ditch

When building a
foundation on the
FRQFUHWHRRU

Drain ditch
When installing multiple units in connection

Y
ditch

Floor
X-X cross section

NOTES

1. The proportions of cement: sand: gravel for the concrete shall be 1:2:4 and the reinforcement bars with a diameter of
10mm (approx, 300mm intervals) shall be placed.
2. 7KHVXUIDFHVKDOOEHQLVKHGZLWKPRUWDU7KHFRUQHUHGJHVVKDOOEHFKDPIHUHG
3. :KHQWKHIRXQGDWLRQLVEXLOWRQDFRQFUHWHRRUUXEEOHLVQRWQHFHVVDU\KRZHYHUWKHVXUIDFHRIWKHVHFWLRQRQZLFKWKH
IRXQGDWLRQLVEXLOWVKDOOKDYHDURXJKQLVK
4. A drain ditch shall be made around the foundation to thoroughly drain water from the equipment installation area.
5. :KHQLQVWDOOLQJWKHHTXLSPHQWRQDURRIWKHRRUVWUHQJKWVKDOOEHFKHFNHGDQGZDWHUSURRQJPHDVXUHVVKDOOEHWDNHQ

32

VRV Systems RYYQ-T

Model

AA

AB

RYYQ8-12T
RYMQ8-12T
RXYQ8-12T

766

992

RYYQ14-20T
RYMQ14-20T
RXYQ14-20T

1076

1302

RXYCQ8

497

697

RXYCQ10-14

792

992

RXYCQ16-20

1102

1302

AC

AD

113

185

100

160

3D079547B

Outdoor Unit RYYQ-T

12

Installation

12 - 3 Refrigerant Pipe Selection

RYYQ-T
RXYQ-T
RYMQ-T

1.
1.1.

Refrigerant pipe size and allowable


pipe length

1.3.1.

Choose from the following table in accordance with the outdoor unit
total capacity type, connected downstream.

General information

Outdoor unit capacity


type (HP)

NOTICE
The refrigerant R410A requires strict cautions for keeping the
system clean, dry and tight.

Clean and dry: foreign materials (including mineral oils or


moisture) should be prevented from getting mixed into the
system.

Tight: R410A does not contain any chlorine, does not destroy
the ozone layer, and does not reduce earth's protection
against harmful ultraviolet radiation. R410A can contribute
slightly to the greenhouse effect if it is released. Therefore we
should take special attention to check the tightness of the
installation.

19.1

10

22.2

12~16

Piping and other pressure containing parts shall comply with the
applicable legislation and shall be suitable for refrigerant. Use
phosphoric acid deoxidised seamless copper for refrigerant.

34.9

26~34
36~54

1.3.

19.1

41.3

Piping between refrigerant branch kits: D

Indoor unit capacity


index

Piping outer diameter size (mm)


Gas pipe

150x<200

19.1

Installation shall be done by a licensed installer, the choice of


materials and installation shall conform completely with the
applicable national and international codes.

200x<290

22.2

In Europe, EN 378 is the applicable standard that shall be used.

420x<640

Foreign materials inside pipes (including oils for fabrication) must be 30


mg/10 m.
Temper grade: use piping with temper grade in function of the pipe
diameter as listed in table below.
Temper grade of piping material

15.9

O (annealed)

19.1

1/2H (half hard)

290x<420

Determine the proper size referring to following tables and reference figure
(only for indication).

9.5

12.7

28.6

15.9

640x<920

34.9

19.1

>920

41.3

19.1

Example:
Downstream capacity for E=capacity index of unit 1
Downstream capacity for D=capacity index of unit 1+capacity index
of unit 2
1.3.3.

Selection of piping size

Liquid pipe

15.9

NOTICE

Pipe (mm)

12.7
15.9

24

<150

9.5

Choose from the following table in accordance with the indoor unit
total capacity type, connected downstream. Do not let the
connection piping exceed the refrigerant piping size chosen by the
general system model name.

Selection of piping material


NOTICE

Liquid pipe

28.6

18~22

Piping between refrigerant branch kit and BP unit: F

Pipe size for direct connection on BP unit must be based on the total
capacity of the connected indoor units (only in case RA DX indoor
units are connected).
Total capacity index of connected
indoor units

Gas pipe
(mm)

Liquid pipe
(mm)

12.7

6.4

20-62

a
D

B
C y

63-149

15.9

150-208

19.1

9.5

Example:
Downstream capacity for F=capacity index of unit 4+capacity index
of unit 5

12

Piping outer diameter size (mm)


Gas pipe

1.3.2.

1.2.

Piping between outdoor unit and (first) refrigerant


branch kit: A, B, C

1.3.4.

Piping between BP unit and RA DX indoor unit: G

Only in case RA DX indoor units are connected.

E
1

Indoor unit capacity index

2
1,2
3
4,5
a,b
x,y

20, 25, 30

VRV DX indoor unit


BP box
RA DX indoor unit
Indoor branch kit
Outdoor multi connection kit

50
60
71

Gas pipe (mm)


9.5

Liquid pipe (mm)


6.4

12.7
15.9

9.5

4P329765-1C (1/5)

VRV Systems RYYQ-T

33

Outdoor Unit RYYQ-T

12

Installation

12 - 3 Refrigerant Pipe Selection


RYYQ-T
RXYQ-T
RYMQ-T
1.3.5.

12

Piping between refrigerant branch kit and indoor unit: E

1.4.

Pipe size for direct connection to indoor unit must be the same as the
connection size of the indoor unit (in case indoor unit is VRV DX indoor or
Hydrobox).
Piping outer diameter size
(mm)
Gas pipe

Liquid pipe

15, 20, 25, 32, 40, 50

Indoor unit capacity index

12.7

6.4

63, 80, 100, 125

15.9

200

19.1

250

22.2

9.5

For piping example, refer to "9.3. Selection of piping size".

When using refnet joints at the first branch counted from the outdoor unit
side, choose from the following table in accordance with the capacity of
the outdoor unit (example: refnet joint a).
Outdoor unit capacity type (HP)

1
2
3
4
5

KHRQ22M29T9

12-22

KHRQ22M64T

24-54

KHRQ22M75T

For refnets joints other than the first branch (example refnet joint b),
select the proper branch kit model based on the total capacity index of all
indoor units connected after the refrigerant branch.
Indoor unit capacity index

KHRQ22M20T

200x<290

KHRQ22M29T9

290x<640

KHRQ22M64T

640

KHRQ22M75T

Concerning refnet headers, choose from the following table in


accordance with the total capacity of all the indoor units connected below
the refnet header.
Indoor unit capacity index

<200
Size up
HP Class

Gas side (mm)

19.1 22.2

10

22.2 25.4(a)

Liquid size (mm)


9.5 12.7

28.6(b)

12+14

2 pipes

<200

Outdoor unit
Main pipes
Increase
First refrigerant branch kit
Indoor unit

2 pipes

8-10

When the equivalent pipe length between outdoor and indoor units is 90
m or more, the size of the main pipes (both gas side and liquid side) must
be increased. Depending on the length of the piping, the capacity may
drop, but even in such a case it is possible to increase the size of the
main pipes.

Selection of refrigerant branch kits

Refrigerant refnets

2 pipes
KHRQ22M29H

200x<290

KHRQ22M29H

290x<640

KHRQ22M64H(a)

640

KHRQ22M75H

(a) If the pipe size above the refnet header is 34.9 or more, KHRQ22M75H is
required.

12.7 15.9

16

28.6 31.8(a)

18~22

28.6 31.8(a)

15.9 19.1

INFORMATION

34.9(b)

15.9 19.1

Maximum 8 branches can be connected to a header.

24
26~34

34.9 38.1(a)

36~54

41.3(b)

19.1 22.2

(a) If size is NOT available, increase is NOT allowed.


(b) Increase is NOT allowed.

Number of outdoor units

Branch kit name

BHFQ22P1007

BHFQ22P1517

The pipe thickness of the refrigerant piping shall comply with the
applicable legislation. The minimal pipe thickness for R410A piping must
be in accordance with the table below.
Pipe (mm)

Minimal thickness t (mm)

6.4
9.5

0.80

12.7
15.9
19.1
22.2

The RYYQ22~54 models, consisting of two or three RYMQ modules,


require a 3-pipe system. There is an additional equalizing pipe for
such modules (in addition to the conventional gas and liquid piping).
This equalizing pipe does not exist for RYYQ8~20 or RYXQ8~54
units.

0.99
0.80

28.6

0.99

34.9

1.21

41.3

1.43

The equalizing pipe connections for the different RYMQ modules are
mentioned in below table.
RYMQ
8

In case the required pipe sizes (inch sizes) are not available, it is also
allowed to use other diameters (mm sizes), taken the following into
account:

Select the pipe size nearest to the required size.


Use the suitable adapters for the change-over from inch
to mm pipes (field supply).
In this case, the additional refrigerant calculation has to be
adjusted as mentioned in "14. Charging refrigerant".

Equalizing pipe (mm)


19.1

10
12

How to choose an outdoor multi connection piping kit (needed if the


outdoor unit capacity type is 22 HP or more). Choose from the following
table in accordance with the number of outdoor units.

14

22.2

16
18
20

28.6

4P329765-1C (2/5)

34

VRV Systems RYYQ-T

Outdoor Unit RYYQ-T

12

Installation

12 - 3 Refrigerant Pipe Selection

RYYQ-T
RXYQ-T
RYMQ-T

1.5.

Deciding the equalizing pipe diameter:

In case of 3 multi units: the connection diameter of outdoor to


T-joint has to be kept.

In case of 2 multi units: the connection pipe has to have the


largest diameter.

System piping (length) limitations

1.5.1.

Piping length restrictions

Make sure to perform the piping installation within the range of the
maximum allowable pipe length, allowable level difference and
allowable length after branching as indicated below. Three patterns
will be discussed, including VRV DX indoor units combined with
Hydrobox units or RA DX indoor units.

There is never a connection of the equalizing pipe with the indoor


units.
Example (free multi combination): RYMQ8+RYMQ12+RYMQ18.
Largest connection is 28.6 (RYMQ18); 22.2 (RYMQ12) and
19.1 (RYMQ8). In figure below only equalizing pipe is shown.

12

Definitions
Actual piping length: pipe length between outdoor(1) and indoor
units.
Equivalent piping length(2): pipe length between outdoor(1) and
indoor units.
Total piping length: total piping length from the outdoor(1) to all indoor units.
Difference in height between outdoor and indoor units: H1.

22.2 mm

28.6 mm

Difference in height between indoor and indoor units: H2.

19.1 mm

Difference in height between outdoor and outdoor units: H3.


Difference in height between outdoor and BP unit: H4.

INFORMATION

Difference in height between BP unit and BP unit: H5.

Reducers or T-joints are field supplied.

Difference in height between BP unit and RA DX indoor unit: H6.

NOTICE
Refrigerant branch kits can only be used with R410A.

INFORMATION
Equalizing pipe for RYMQ has to be connected between
the outdoor modules of multi continuous heating models:
RYYQ22~54 consisting of 2 or 3 RYMQ8~20 modules. The
equalizing pipe should never have a connection to any
indoor unit.

1.5.2.

(1)

If the system capacity is >20HP, re-read "the first outdoor branch as seen
from the indoor unit".
Assume equivalent piping length of refnet joint=0.5 m and refnet
header=1 m (for calculation purposes of equivalent piping length, not for
refrigerant charge calculations).

(2)

System only containing VRV DX indoor units

System setup
Branch with refnet joint and refnet
header

Branch with refnet joint

Branch with refnet header

Single outdoor
i

a
b

a
A

e
D

f
F

7
H2

d
1

e
2

H1 H1

f
3

k
7

H2

H1
b

c
1

e
3

Example 1.2

Example 1.1

f
4

h
7
H2

i
8

Example 1.3

Multi outdoor

Refnet joint

r
u

c
B

d
C

r
u

Refnet header

H3

H3

Indoor unit

e
D

f
E

g
F

Example 2.1

p
8

Outdoor multi
connection
piping kit

H1
G

H3

d
1

e
2

f
3

g
5

h
6

H2

r
u

H1
k
b

c
1

d
2

H1
e

f
4

g
6

7
8

4P329765-1C (3/5)

VRV Systems RYYQ-T

35

Outdoor Unit RYYQ-T

12

Installation

12 - 3 Refrigerant Pipe Selection


RYYQ-T
RXYQ-T
RYMQ-T
Example 3: with standard multi layout

12
r

u
Maximum allowable length

Between outdoor and indoor units (standard multi/free multi combinations)

Actual piping length

165 m/135 m

Example 1.1
unit 8: a+b+c+d+e+f+g+p165 m

Example 1.2
unit 6: a+b+h165 m
unit 8: a+i+k165 m

Example 1.3
unit 8: a+i165 m

Example 2.1
unit 8: a+b+c+d+e+f+g+p135 m
Equivalent length(2)

190 m/160 m

Total piping length

1000 m/500 m

Example 1.1
a+b+c+d+e+f+g+h+i+j+k+l+m+n+p1000 m

Example 2.1
a+b+c+d+e+f+g+h+i+j+k+l+m+n+p500 m

Between outdoor branch and outdoor unit (only in case >20 HP)

Actual piping length

10 m

Example 3
r, s, t10 m; u5 m

Equivalent length

13 m

Maximum allowable height difference


H1

50 m (40 m)(a) (if outdoor is located below indoor units)

H2

30 m

H3

5 m
(a) Conditional extension up till 90 m is possible without additional option kit:
In case the outdoor location is higher than indoor: extension is possible up till
90 m and following 2 conditions must be fulfilled:
Liquid piping size up (see table "Size up").
Dedicated setting on outdoor unit is required (see "[2-49]").
In case the outdoor location is lower than indoor: extension is possible up till 90 m
and following 6 conditions must be fulfilled:
40~60 m: minimum connection ratio connected: 80%.
60~65 m: minimum connection ratio connected: 90%.
65~80 m: minimum connection ratio connected: 100%.
80~90 m: minimum connection ratio connected: 110%.
Liquid piping size up (see table "Size up").
Dedicated setting on outdoor unit is required (see "[2-35]").

a.

The piping length between all indoor to the nearest branch kit is
40 m.
Example: h, I, j p40 m

b.

It is necessary to increase the pipe size of the gas and liquid


piping if the pipe length between the first and the final branch kit
is over 40 m.
If the increased pipe size is larger than the pipe size of the main
pipe, then the pipe size of the main pipe has to be increased as
well.
Increase the pipe size as follows:
9.5 12.7; 12.7 15.9; 15.9 19.1; 19.1 22.2; 22.2
25.4(1); 28.6 31.8(3); 34.9 38.1(3)
Example: unit 8: b+c+d+e+f+g+p90 m and b+c+d+e+f+g
>40 m; increase the pipe size of b, c, d, e, f, g.

Maximum allowable length after branch


The pipe length from the first refrigerant branch kit to the indoor unit
40 m.
Example 1.1: unit 8: b+c+d+e+f+g+p40 m
Example 1.2: unit 6: b+h40 m, unit 8: i+k40 m
Example 1.3: unit 8: i40 m
However, extension is possible if all below conditions are met. In this
case limitation can be extended up to 90 m.

1
b

c
B

d
C

e
D

f
E

g
F

p H1

7
H2

1 Outdoor units
2 Refnet joints (A~G)
3 Indoor unit (1~8)
(1)

If available on the site. Otherwise it cannot be increased.

4P329765-1C (4/5)

36

VRV Systems RYYQ-T

Outdoor Unit RYYQ-T

12

Installation

12 - 3 Refrigerant Pipe Selection

RYYQ-T
RXYQ-T
RYMQ-T
c.

d.

When the piping size is increased (step b), the piping length has to be
counted as double (except for the main pipe and the pipes that are not
increased in pipe size).

Example 2: unit 6: b+h40 m, unit 8: i+k40 m

The total piping length has to be within limitations (see table


above).
Example:
a+b*2+c*2+d*2+e*2+f*2+g*2+h+i+j+k+l+m+n+p1000 m
(500 m).

1.5.4.

Example 3: unit 8: i40 m, unit 2: c40 m

12

System containing VRV DX indoor units and RA DX


indoor units

System setup

The piping length difference between the nearest indoor from first branch
to the outdoor unit and farthest indoor to the outdoor unit is 40 m.

Example: The farthest indoor unit 8. The nearest indoor unit 1


(a+b+c+d+e+f+g+p)(a+h)40 m.
1.5.3.

System containing VRV DX indoor units and Hydrobox

H4
e
BP1

System setup
Example 1: Branch with refnet joint.

H5

H1

h
1

a
A

c
B

d
C

d
1

f
3

k
7

H2

Example 3: Branch with refnet header

c
2

e
3

f
4

g
6

Between outdoor unit and indoor unit.


100 m

Example:
a+b+g+l100 m

Equivalent length(a)

120 m

Total piping length

250 m

Example:
a+b+d+g+l+k+c+e+f+h+i+j250 m

(a) Assume equivalent piping length of refnet joint=0.5 m and refnet header=1 m (for
calculation purposes).

h
7
H2

i
8

Between BP unit and indoor unit.


Indoor unit capacity index

1~7 VRV DX indoor units


8 Hydrobox unit (HXY*)

Maximum allowable length


Between outdoor and indoor units.
Actual piping length

135 m

Example 1:
a+b+c+d+e+f+g+p135 m
a+b+c+d+k135 m

Remark:

Example 2:
a+i+k135 m
a+b+e135 m

Example: a>5 m

Example 3:
a+i135 m
a+d135 m
Equivalent length(a)
Total piping length

160 m
300 m

Actual piping length

H1
1

H6

Header

H2

Maximum allowable length


j

e
2

BP box
1~5 RA DX indoor units
6,7 VRV DX indoor units

b
c

7
H2

7
BP2

H1

Example 2: Branch with refnet joint and refnet header.

H1

g
6

4
G

f
E

Pipe length

<60

2~15 m

60

2~12 m

71

2~8 m

Minimum allowable length between outdoor unit and first refrigerant branch
kit>5 m (the refrigerant noise from the outdoor unit can be transmitted).

Maximum allowable height difference


H1

50 m (40 m) (if outdoor is located below indoor units)

H2

15 m

Example 3:
a+b+c+d+e+f+g+h+i300 m

H4

40 m

H5

15 m

H6

5 m

(a) Assume equivalent piping length of refnet joint=0.5 m and refnet header=1 m (for
calculation purposes).

Maximum allowable height difference (on Hydrobox indoor unit)


H1

50 m (40 m) (if outdoor is located below indoor units)

H2

15 m

Maximum allowable length after branch


The pipe length from the first refrigerant branch kit to the indoor unit 40 m.
Example 1: unit 8: b+c+d+e+f+g+p40 m

Maximum allowable length after branch


The pipe length from the first refrigerant branch kit to the indoor unit 50 m.
Example: b+g+l50 m
If the piping length between the first branch and BP unit or VRV DX indoor unit
is over 20 m, it is necessary to increase the gas and liquid piping size between
the first branch and BP unit or VRV DX indoor unit. If the piping diameter of the
sized up piping exceeds the diameter of the piping before the first branch kit,
than the latter also requires a liquid piping and gas piping size up.

4P329765-1C (5/5)

VRV Systems RYYQ-T

37

Outdoor Unit RYYQ-T

12

Installation

12 - 3 Refrigerant Pipe Selection


RYYQ-T
RYMQ-T
RXYQ-T
Maximum piping length

Maximum height difference

Longest pipe
(A+[B,G,E,J])
Actual / (Equivalent)

$IWHUUVWEUDQFK
(B,G,E,J)
Actual

Indoor to indoor (3)


(H2)

Outdoor to outdoor (3)


(H3)

Total
Piping
Length

Standard
Only VRV DX indoor connected
Standard multi combination

165/(190)m

40m(1)

10/(13)m

50/40m(3)

30m

5m

1000m

Free multi combination


(=all, except standard multi combination)

135/(160)m

40m(1)

10/(13)m

50/40m(3)

30m

5m

500m

135/(160)m
100/(120)m
50/(55)m(4)
165/(190)m
165/(190)m

40m
50m(2)
40m
40m

10/(13)m
10/13m
10/13m

50/40m
50/40m
40/40m
40/40m
40/40m

15m
15m
15m
15m

5m
5m
5m

300-500m(5)
250m
1000m
1000m

Reference drawing see page 2/3

12

Hydrobox connection
RA connection
AHU connection

Pair
Multi(6)
Mix(7)

$IWHUUVWEUDQFKIRU
Indoor to outdoor (3)
outdoor multi (D)
(H1)
Actual / (Equivalent)

NOTES

)RUVWDQGDUGPXOWLFRPELQDWLRQVVHH'
 ([WHQVLRQLVSRVVLEOHLIDOOEHORZFRQGLWLRQVDUHPHW OLPLWDWLRQFDQEHH[WHQGHGXSWRP

D7KHSLSLQJOHQJWKEHWZHHQDOOLQGRRUWRWKHQHDUHVWEUDQFKNLWLVP

E,WLVQHFHVVDU\WRLQFUHDVHWKHSLSHVL]HRIWKHJDVDQGOLTXLGSLSLQJLIWKHSLSHOHQJWKEHWZHHQWKHILUVWDQGWKHILQDOEUDQFKNLWLVRYHUP

,IWKHLQFUHDVHGSLSHVL]HLVODUJHUWKDQWKHSLSHVL]HRIWKHPDLQSLSHWKHQWKHSLSHVL]HRIWKHPDLQSLSHKDVWREHLQFUHDVHGDVZHOO

F:KHQWKHSLSLQJVL]HLVLQFUHDVHG E WKHSLSLQJOHQJWKKDVWREHFRXQWHGDVGRXEOH7KHWRWDOSLSLQJOHQJWKKDVWREHZLWKLQOLPLWDWLRQV VHHWDEOHDERYH 

G7KHSLSLQJOHQJWKGLIIHUHQFHEHWZHHQWKHQHDUHVWLQGRRUIURPILUVWEUDQFKWRWKHRXWGRRUXQLWDQGIDUWKHVWLQGRRUWRWKHRXWGRRUXQLWLVP
 ,IWKHSLSLQJOHQJWKEHWZHHQWKHILUVWEUDQFKDQG%3ER[RU959LQGRRULVRYHUPLWVQHFHVVDU\WRLQFUHDVHWKHJDVDQGOLTXLGSLSLQJVL]HEHWZHHQILUVWEUDQFKDQG
%3ER[RU959LQGRRU
 ([WHQVLRQXSWLOOPLVSRVVLEOHZLWKRXWDGGLWLRQDORSWLRQNLW
J,QFDVHWKHRXWGRRUORFDWLRQLVKLJKHUWKDQLQGRRUH[WHQVLRQLVSRVVLEOHXSWLOOPXQGHUIROORZLQJFRQGLWLRQV


/LTXLGSLSLQJVL]HXS GHWDLOVLQLQVWDOODWLRQPDQXDO 
- Dedicated setting on outdoor unit is required (details in installation manual).
J,QFDVHWKHRXWGRRUORFDWLRQLVORZHUWKDQLQGRRUH[WHQVLRQLVSRVVLEOHXSWLOOPXQGHUIROORZLQJFRQGLWLRQV


aPPLQLPXPFRQQHFWLRQUDWLRFRQQHFWHG


aPPLQLPXPFRQQHFWLRQUDWLRFRQQHFWHG


aPPLQLPXPFRQQHFWLRQUDWLRFRQQHFWHG


aPPLQLPXPFRQQHFWLRQUDWLRFRQQHFWHG
+


/LTXLGSLSLQJVL]HXS GHWDLOVLQLQVWDOODWLRQPDQXDO 
- Dedicated setting on outdoor unit is required (details in installation manual).
 7KHDOORZDEOHPLQLPXPOHQJWKLVP
(5) In case of multi connection.
 8VLQJVHYHUDO$+8 (.(;9(.(4NLWV 
 0L[RI$+8DQG959';LQGRRU

3D079540C(1/3)

38

VRV Systems RYYQ-T

Outdoor Unit RYYQ-T

12

Installation

12 - 3 Refrigerant Pipe Selection

RYYQ-T
RYMQ-T
RXYQ-T
Outdoor

12

VRV indoor
Hydrobox
Hydrobox

VRV indoor

NOTES

1. Schematic indication: illustrations may vary from real unit outlook.


2. Displayed system is only to illustrate piping length limitations! Combination of displayed indoor unit types is not allowed. See 3D079543 for allowed combinations.

Allowable piping length


EXV to AHU (K)

BP to RA (H4)

2~15m

5m

P

5m

P

5m

P

5m

RA connection
AHU connection

Pair
Multi (1)
Mix

Max. height difference

BP to RA (F)

(2)

EXV to AHU (H5)

NOTES

1. Using several AHU (EKEXV + EKEQ- kits)


2. Mix of AHU and VRV DX indoor

3D079540C(2/3)
RYYQ-T
RYMQ-T
RXYQ-T
System pattern
Allowed connection ratio (CR)

Total

Allowable capacity
capacity

* Other combinations are N.A.


Only VRV DX indoor
VRV DX indoor + RA DX indoor
Only RA DX indoor
VRV DX indoor + LT hydrobox
VRV DX indoor + AHU (mix)
Only AHU (pair AHU + multi AHU)(4)

50~130%
80~130%
80~130%
50~130%
50~110%(3)
90~110%(3)

Indoor unit quantity


(VRV, RA, AHU, Hydrobox)
(excl. BP box and EXV kits)
Max. 64
Max. 32(1)
Max. 32(1)
Max. 32
Max. 64(2)
Max. 64(2)

VRV DX indoor

RA DX indoor

Hydrobox

AHU

50~130%
0~130%
50~130%
50~110%
-

0~130%
80~130%
-

0~80%
-

0~110%
90~110%

NOTES

1.
2.
3.
4.

There is no restriction for the number of connectable BP boxes


When using AHU connection: see EKEXV kit as an indoor unit for counting the total number of indoor units
Restrictions by air handling unit capacity
Pair AHU = system with 1 AHU connected to one outdoor unit // Multi AHU = system with several AHU connected to 1 outdoor unit system

SPECIAL INFORMATION REGARDING VENTILATION APPLICATIONS

I. FXMQ_MF model is considered as an AHU, following AHU limitations and respecting additional limitations:

0D[LPXP);04B0)FRQQHFWLRQUDWLR &5 ZKHQFRPELQHGZLWK959';LQGRRUXQLWV&5

0D[LPXP);04B0)FRQQHFWLRQUDWLR &5 ZKHQRQO\$+8LVXVHG&5

RSHUDWLRQUDQJHLQIRUPDWLRQVHHVSHFLFDWLRQVRI);04B0)XQLW
II. Biddle aircurtain is considered as an AHU, following AHU limitations

RSHUDWLRQUDQJHLQIRUPDWLRQVHHVSHFLFDWLRQVRI%LGGOHXQLW 
Ill. [EKEXV + EKEQ] combined with AHU is considered as an AHU, following AHU limitations

RSHUDWLRQUDQJHLQIRUPDWLRQVHHVSHFLFDWLRQVRI(.(;9(.(4XQLW 
IV. VKM is considered to be a regular VRV DX indoor unit

RSHUDWLRQUDQJHLQIRUPDWLRQVHHVSHFLFDWLRQVRI9.0XQLW
V. VAM does not have limitations on connection as there is no refrigerant connection with the outdoor unit (only communication F1/F2; so counting in # indoor units)

3D079540C(3/3)

VRV Systems RYYQ-T

39

Outdoor Unit RYYQ-T

13

Operation range

13 - 1 Operation Range
5<<47
5<047

+HDWLQJ

&RROLQJ

,QGRRUWHPSHUDWXUH &:%

2SHUDWLRQUDQJH

5DQJHIRUSXOOGRZQRSHUDWLRQ

2XWGRRUWHPSHUDWXUH &:%

5DQJHIRUSXOOGRZQRSHUDWLRQ

2SHUDWLRQUDQJH

2XWGRRUWHPSHUDWXUH &'%

13

,QGRRUWHPSHUDWXUH &'%

127(6

 7KHVHJXUHVDVVXPHWKHIROORZLQJRSHUDWLRQFRQGLWLRQV
,QGRRUDQGRXWGRRUXQLWV
(TXLYDOHQWSLSHOHQJWKP
/HYHOGLIIHUHQFHP
 'HSHQGLQJRQRSHUDWLRQDQGLQVWDOODWLRQFRQGLWLRQVWKHLQGRRUXQLWFDQFKDQJHRYHUWRIUHH]HXSRSHUDWLRQ LQGRRUGHLFLQJ 
 7RUHGXFHWKHIUHH]HXSRSHUDWLRQ LQGRRUGHLFLQJ IUHTXHQF\LWLVUHFRPPHQGHGWRLQVWDOOWKHRXWGRRUXQLWLQDORFDWLRQQRWH[SRVHGWRZLQG
 2SHUDWLRQUDQJHLVYDOLGLQFDVHGLUHFWH[SDQVLRQLQGRRUXQLWVDUHXVHG,QFDVHVSHFLDOLQGRRUXQLWVDUHXVHG HJ+\GURER[ UHIHUWRWHFKQLFDOVSHFV
RIGHGLFDGHGXQLW

40

VRV Systems RYYQ-T

'

The present leaflet is drawn up by way of information only and does not
constitute an offer binding upon Daikin Europe N.V.. Daikin Europe N.V.
has compiled the content of this leaflet to the best of its knowledge. No
express or implied warranty is given for the completeness, accuracy, reliability or fitness for particular purpose of its content and the products
and services presented therein. Specifications are subject to change
without prior notice. Daikin Europe N.V. explicitly rejects any liability for
any direct or indirect damage, in the broadest sense, arising from or related to the use and/or interpretation of this leaflet. All content is copyrighted by Daikin Europe N.V.

BARCODE

Daikin products are distributed by:

Naamloze Vennootschap - Zandvoordestraat 300, B-8400 Oostende - Belgium - www.daikin.eu - BE 0412 120 336 - RPR Oostende

EEDEN14-200_1 05/14 Copyright Daikin


The present publication supersedes EEDEN13-200_1

These products are not within the scope of


the Eurovent certification program