Professional Documents
Culture Documents
Analogue/Digital
Teleprotection Equipment
TPS-NU, the new SELTA teleprotection equipment, is a flexible, reliable and costeffective solution for power line protection.
Main features
Complete configurability of the commands
employment and commands priority (i.e.
operating mode 3+1 or 2+2)
Management of indipendent and/or simultaneous commands
Different protection schemes (intertripping,
permissive underreach, permissive overreach
and blocking) with dependability, security
and transmission time compliant with IEC
608341
High hardware modularity
2 different types of subrack (back or front
side connectors)
Different digital/analogue line interfaces
(optical fiber, E1 2 Mbit/s G.703, codirectional/
contradirectional 64 kbit/s G.703, 32/64
kbit/s V.11/X.21, analogue/ digital PLC, 2/4
copper wires)
Up to 4 commands
Commands redundancy
Power Line
Power Line
Power
Line
Carrier
Power
Line
Carrier
Distance
Protection
TPS-NU
Distance
Protection
TPS-NU
Distance
Protection
TPS-NU
High Voltage
Transformer
Power Line
Power Line
ADM
SOH
ADM
SOH
Distance
Protection
Distance
Protection
TPS-NU
TPS-NU
Distance
Protection
TPS-NU
TPS-NU
TPS-NU
High Voltage
Transformer
Power Line
Power Line
Voice
and
Data
Distance
Protection
MUX
TPS-NU
MUX
TPS-NU
Voice
and
Data
Distance
Protection
Leased line
TPS-NU
TPS-NU
Applications
The TPS-NU equipment transmits and receives
the commands via:
Operating principle
Digital Line Interfaces
The Operating principle is based on encoding a
guard signal and sending a certain number of
command events encoded using specific bit
sequences.
When TPS-NU is at rest, the guard signal is transmitted continuously in order to monitor the
connection, controlling the link quality and
detecting if the connection is interrupted.
Technical data
Performances
Nominal transmission time:
Optical fiber
2.5 / 3 ms
3.5 / 5.5 ms
64 kbit/s G.703
4.5 / 7.5 ms
64 kbit/s V.11/X.21
4.5 / 7.5 ms
32 kbit/s V.11/X.21
6.5 ms
Analogue PLC
12 ms
Digital PLC
12 ms
Low-frequency channels
12 ms
Command interfaces
Security and dependability: IEC 60834-1 compliant
Number of commands
up to 4
2 (command transmission
and start criteria)
Command input:
opto-coupler
Voltage range
8 200 Vdc
Current range
3 20 mA
Command output:
solid-state relay
Contact type
normally open
Max. current
1A
250 VA
Alarms interface
electromechanical relays
and solid state relays
Electromechanical relays
Power supply
Contact type
250 Vdc
Max. current
2A
500 VAac
Solid-state relays
Contact type
normally closed
Power consumption
< 25 W
250 Vdc
Max. current
0.5 A
125 VA
Line interfaces
-10 dBm
0 dBm
25 dB
Transmission support
mono-mode optical
fiber (10/125 m)
Wavelength
1310 nm
Guaranteed attenuation
15 dB
PLC channels
Optical connectors
FC/PC
Type
4 wires
Transmission band
0 4 kHz
Reception band
12 16 kHz
Transmission support
Impedance
600 unbalanced
Wavelength
mono-mode optical
fiber (10/125 m)
1310 nm
-33 dBm
Guaranteed attenuation
22 dB
-15 dBm
Optical connectors
FC/PC
-15 dBm
Standard
Enel CC5002
mono-mode optical
fiber (10/125 m)
Wavelength
1550 nm
Guaranteed attenuation
28 dB
Optical connectors
LC
Wavelength
650 nm
Guaranteed attenuation
12 dB
Optical connectors
Latching duplex
Environmental conditions
Operating
temperature range
-10 +55 C
-40 +70 C
Relative humidity
93% at 40 C
Standards
EMC Directive 89/336/EC
E1 2 Mbit/s G.703
Bit rate
2 Mbit/s
Line code
HDB3/AMI
Impedance
120 balanced or
75 unbalanced
Bit rate
64 kbit/s
Mechanical characteristics
Line code
G.703 compliant
Installation
ETSI cabinets
Impedance
120 balanced
Dimensions
Bit rate
64/32 kbit/s
Weight
< 7.0 kg
Impedance
100 balanced or
high impedance
Low-frequency channels
Type
2/4 wires
Band
0 4 kHz
Impedance
600 bal./unbal.
or high impedance
SELTA SpA
29010 Cadeo (PC) Italy - Via Emilia, 231
Tel. +39.0523.5016.1 - Fax +39.0523.5016.333
info@selta.it - www.selta.com
SELTA reserves the right to apply modifications without any further notice