You are on page 1of 21

BOQ OF ELECTRICAL WORKS FOR KOTAK BRANCH @

JAIPUR
SR
DESCRIPTION
A MCB DB / PANEL / SWITCH GEAR

11/6/2014
UNIT QTY

SITC of 14/16 SWG CRCA fabricated & powder coated after 7 tank
process compartmentalised panel with air ventilation & dust/vermin
proof , free standing floor mounted on100 mm rigid 'C' MS base
supported on concrete base with anchor fasteners Panels to be top /
bottom entry & accessible from front & rear side or as required by
consultant & site conditions Design to be made by contractor &
approved by consultant before fabrication with respect to SLD &
specks. Bus bar to be of electrolytic Aluminium with current density of
1.0 amp per SQMM or 1.25 amp per sqmm for copper as mentioned.
Panel shall confirm to all applicable IS standards. All MCCB shall be
with microprocessor release with RHOM .All internal wiring to be done
in PVC insulated copper wires. Outgoing from MCCB to be terminated
in bus bars in cable alley & all terminations to have BI-Metallic strip
as required All MCCB to have spreader links. All DB's to be IP43 .
SITC of DB'S readymade or fabricated as per design & site
conditions or consultants requirements .TPN DB shall have 4 nos
separate neutral links with internal wiring done as required with
copper wire & cable sockets Internal terminations & wiring to be neatly
dressed up in a systematic manner. All MCB to be 'C' & 'D' curve as
mentioned & all indicators to be LED. All MCB & DB to be approved
by consultant before procurement . DB to be fixed surface or recessed
as per requirement. APFC panel to have capacitor duty MCB &
Contactors

1 SITC of MAIN MCCB DB


100 A 4P 16 KA MCCB -- 1 nos
C 6 A 3P MCB 10 KA 1 Nos
C 32 A 3P MCB 10 KA 1 Nos
C 40 A 3P MCB 10 KA 2 Nos
C 63 A 3P MCB 10 KA 3 Nos
8 Way VTPN MCCB DB IP 43 -- 1 nos
2 SITC of LIGHTING MCB DB
C 40 A 4P MCB 10 KA 1 Nos
40A, 2P, RCCB, 100MA -- 3 nos
C 6-32 A SP MCB 10 KA 12 Nos
6 Way TPN MCB DB IP 43 -- 1 nos
3 SITC of RAW POWER MCB DB
C 40 A 4P MCB 10 KA 1 Nos
40A, 2P, RCCB, 100MA -- 3 nos
C 6-32 A SP MCB 10 KA 12 Nos
6 Way TPN MCB DB IP 43 -- 1 nos
4 SITC of AC MCB DB
C 63 A 4P MCB 10 KA 1 Nos
63 A, 2P, RCCB, 100MA -- 3 nos
C 6-32 A SP MCB 10 KA 12 Nos
6 Way TPN MCB DB IP 43 -- 1 nos
5 SITC of AC MCB DB

Nos

Nos

Nos

Nos

RATE

8
9
10
11
12
13
14
15
16
17
18
19
20
21
22
23
24
25
26
27

C 63A, 4P, 10KA MCB -- 1nos


C 25 A 3P MCB 10 KA 2 Nos
C 32 A 3P MCB 10 KA 1 Nos
C 25A SP MCB 10KA -- 5 nos
8 Way VTPN MCB DB IP 43 -- 1 nos
SITC of UPS LTG/PWR MCB DB
C 25 A 4P 10 KA MCB -- 1 nos
25 A, 2P, RCCB, 30MA , ( HPI - A )-- 3 nos
C 6-32 A SP MCB, 10KA -- 18 nos
8 Way TPN MCB DB IP 43 -- 1 nos
APFC PANEL (14 KVAR)
APFC 4 step meter ---- 1nos
Gas filled 440 v capasitor 7.5 kvar X 1 step
Gas filled 440 v capasitor 2.5 kvar X 1 step
Gas filled 440 v capasitor 2.5 kvar X 1 step
Gas filled 440 v capasitor 2.5 kvar X 1 step
A/M switch , phase indication lamps with mcb tp for protection
4P alumnium bus bar with colour coded HSS as per capacity
30 sec delay timming for manual operation,power contactors
,auxilary contactors , illumniated start stop push buttons with
elements , tpmcb for power contactors , phase indication lamps ,
Digital amp meter , with CT , digital voltmeter with selector switch ,
on / off indication lamps for capasitors.
All capacitor duty contactors to be used.
Capacitors to be placed in separate compartments with small
continous rating ventilation fans
All MCCB to have spreader links with RHOM
sensing CT to be included . APFC shall be contactor switched with 7
% detuned harmonic filters.
SITC of 63 a 4p Aluminium busbar in enclosure
SITC of 100A 4P 16KA MCCB in enclosure
SITC of 100A 4P 100 MA RCCB in enclosure
SITC of 160A 4P 25KA MCCB in enclosure
SITC of C 16/25/32/, 2P, 10 KA MCB in enclosure
SITC of C 40 /63 , 2P, 10 KA MCB in enclosure
SITC of C 16/25/32/, 4P, 10 KA MCB in enclosure
SITC of C 40 / 63 ,4P, 10 KA MCB in enclosure
SITC of 63A, 4P, 30MA ELCB in enclosure
SITC of 25A, 2P, 100MA ELCB in enclosure
SITC of 25A, 4P, 100MA ELCB in enclosure
SITC of 16A, 4P, 30MA ELCB in IP55 enclosure
SITC of 80A, 4P, 10KA MCB in IP55 enclosure
SITC of 25 a 2P RCBO 100 ma in enclosure
SITC of RYB INDICATOR with 6a, 4P, 10KA MCB in enclosure
SITC of 100 A TPN HRC SFU with cable entry box & surface
enclosure
SITC of 160 A TPN SDF with cable entry box & surface enclosure
SITC of 100 A , 4P, Manual Online Change over Switch with cable
entry box and surface enclosure
SITC of 125 A , 4P, Manual Online Change over Switch with cable
entry box and surface enclosure
SITC of 160 A , 4P, Manual Online Change over Switch with cable
entry box and surface enclosure

Nos

Nos

Nos

Nos
Nos
Nos
Nos
Nos
Nos
Nos
Nos
Nos
Nos
Nos
Nos
Nos
Nos
Nos

1
0
0
0
0
0
0
0
0
14
4
0
0
0
0

Nos

Nos

Nos

Nos

Nos

B EARTHING
Chemical / maintenance free earthing pits to be provided to attain
minimum resistivity of the soil .Mentioned are some of the makes
,other equivalent makes can be acceptable in case of non avilability
with prior intimation.[extra earth pits to be added if required to form a
grid to reduce resistivity ]makes - universal , jef techno, rapid, fast
electrode, JK, ashlok, cuprous.etc ( DG earth pits 4 nos included in
this section )
SITC of Universal Earthing systems make maintenance free
1 earthing electrode , 3 mts length , UES 60/CP, 60MM OD , Dual
copper flats in copper pipe filled with special conductive material
SITC of Universal Earthing systems make maintenance free
2 earthing electrode , 3 mts length , UES 90/12 , 88 MM OD , Dual G.I.
flats in G.I. pipe filled with special conductive material
3 S/F of 25 x 3 mm flat GI tape with spacer , saddle & insulators
4 S/F of 8 SWG GI bare wire
5 S/F of 8 SWG COPPER bare wire
6 S/F of 25 x 3 mm flat copper tape with spacer , saddle & insulators
7 S/F of 6 sqmm x 1 c copper flex cable in conduits
8 S/F of 10 sqmm x 1 c copper flex cable in conduits
9 S/F of earth bus bar 25 x 3 copper with ms enclosure
10 S/F of earth bus bar 25 x 3 mm G.I. with ms enclosure
C RACEWAY / TRUNKING /CABLE TRAY / CONDUITING / J BOX
a Supply, Installation heavy duty LHSFT PVC MMS conduits in
ceiling, flooring, recessed in walls, chasing & re-cementing the same.
1 20 mm PVC. conduits
2 25 mmPVC. conduits
3 32 mm PVC conduits
4 40 mm PVC. conduits
5 S/Fof 100 X 100 X 50 MM 16 swg GI fabricated junction box & cover
6 S/Fof 150 X 150 X 50 MM 16 swg GI fabricated junction box & cover
7 S/Fof 200 X 200 X 50 MM 16 swg GI fabricated junction box & cover
8 S/Fof 250 X 250 X 50 MM 16 swg GI fabricated junction box & cover
9 S/Fof 300 X 300 X 50 MM 16 swg GI fabricated junction box & cover
S/F of pre galvanised ladder type cable tray with hanger support, all
b
accessories etc.
1 300mm wide
2 200mm wide
3 150mm wide
S/F of pregalvanised Perforated cable tray on floor , all accessories
c
etc.
1 100mm wide
2 150mm wide
3 200mm wide
4 300mm wide
S/F of 16 SWG GI fabricated trunking trays with covers with all fixing
d
accessories & complete in all respects .40 mm deep
1 300mm wide
2 200mm wide
3 150mm wide
4 100 mm wide

Nos

Nos

Mts 65
Mts 150
Mts 25
Mts 45
Mts 100
Mts
0
Nos
1
Nos
1

Mts
0
Mts 140
Mts
5
Mts
5
Nos
0
Nos
0
Nos
0
Nos
0
Nos
0

Mts
Mts
Mts

0
0
0

Mts
Mts
Mts
Mts

0
0
0
0

Mts
Mts
Mts
Mts

5
5
10
10

1
2
3
4
5
6
7
F
1
2
3
D

S/F of 16 swg Aluminium box section to be laid on floor with all


excavation, re-cementing & refinishing civil works to make good in line
with the existing floor level Respective junction box to be fabricated in
16 SWG GI sheet with cut out as required for terminating the box
sections. Shall include pvc conduits from JB to work station Power
points
65 x 40 mm 16 swg aluminium box section
100 x 40 mm 16 swg aluminium box section
150 x 50 mm 16 swg aluminium box section
150 x 150 x 50 mm GI Junction box with cover & cut outs
200 x 200 x 50 mm GI Junction box with cover & cut outs
250 x 250 x 50 mm GI Junction box with cover & cut outs
300 x 300 x 50 mm GI Junction box with cover & cut outs
PVC TRUNKING
75 x 50 MM
75 x 75 MM
100 x 50 MM
CABLING

1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
20
E

SITC of copper / aluminium / XLPE cabling & multi stranded copper


cable pvc insulated to be laid in trenches, walls, floor, ceiling as
required with saddle, spacers, pvc conduits in a well-dressed manner
excavation for cables to be included
1.5 sqmm x 4 c copper armoured cable
2.5 sqmm x 4 c copper armoured cable
2.5 sqmm x 3 c copper armoured cable
4 sqmm x 4 c copper armoured cable
4 sqmm x 2 c copper armoured cable
6 sqmm x 3 c copper armoured cable
6 sqmm x 4 c copper armoured cable
10 sqmm x 2 c copper armoured cable
10 sqmm x 4 c copper armoured cable
16 sqmm x 4 c alumium armoured cable
25 sqmm x 3.5 c aluminium armoured cable
35 sqmm x 3.5 c aluminium armoured cable
50 sqmm x 3.5 c aluminium armoured cable
70 sqmm x 3.5 c aluminium armoured cable
95 sqmm x 3.5 c aluminium armoured cable
6 SQMM X 1 C copper multistranded in PVC conduits
10 SQMM X 1 C copper multistranded in PVC conduits
16 SQMM X 1 C copper multistranded in PVC conduits
25 SQMM X 1 C copper multistranded in PVC conduits
35 SQMM X 1 C copper multistranded in PVC conduits
TERMINATIONS

1
2
3
4
5
6

SITC of terminations to cables with single compressions seamens


type brass glands, copper / alum cable sockets & complete
terminations in all respects. Multistranded cable in PVC conduits shall
be terminated with PVC glands
1.5 sqmm x 4 c copper armoured cable
2.5 sqmm x 4 c copper armoured cable
2.5 sqmm x 3 c copper armoured cable
4 sqmm x 4 c copper armoured cable
4 sqmm x 2 c copper armoured cable
6 sqmm x 3 c copper armoured cable

Mts
Mts
Mts
Nos
Nos
Nos
Nos

50
55
RO
30
5
5
0

Mts
Mts
Mts

3
3
3

Mts
Mts
Mts
Mts
Mts
Mts
Mts
Mts
Mts
Mts
Mts
Mts
Mts
Mts
Mts
Mts
Mts
Mts
Mts
Mts

5
0
0
50
265
0
20
0
0
45
0
180
RO
RO
0
40
RO
0
0
0

Nos
Nos
Nos
Nos
Nos
Nos

2
0
0
6
30
0

7
8
9
10
11
12
13
14
15
16
17
18
19
20

6 sqmm x 4 c copper armoured cable


10 sqmm x 2 c copper armoured cable
10 sqmm x 4 c copper armoured cable
16 sqmm x 4 c alumium armoured cable
25 sqmm x 3.5 c aluminium armoured cable
35 sqmm x 3.5 c aluminium armoured cable
50 sqmm x 3.5 c aluminium armoured cable
70 sqmm x 3.5 c aluminium armoured cable
95 sqmm x 3.5 c aluminium armoured cable
6 SQMM X 1 C copper multistranded
10 SQMM X 1 C copper multistranded
16 SQMM X 1 C copper multistranded
25 SQMM X 1 C copper multistranded
35 SQMM X 1 C copper multistranded

Nos
Nos
Nos
Nos
Nos
Nos
Nos
Nos
Nos
Nos
Nos
Nos
Nos
Nos

10
0
0
14
0
4
RO
RO
0
20
RO
0
0
0

F LIGHT FIXTURES (with L.E.D lamps )

1
2
3
4
5
G

Supply & Fixing of lights, fans, exhaust , spot , tube , bracket light
with all accessories, connectors , wires , including assembly of light
fixtures , suspension arrangement etc.( makes -wipro, philips, GE ,
bajaj )All fixtures to have electroinc ballast with atleast .95 pf and
lamps
2' x 2' LED Light Fixture(wipro - LM14 032-XXX WH XX 32)
LED 18W Down Light Round LED Fixture(wipro-LD49 161 XXX 60
XX 18 W )
LED 10W Down Light Round LED Fixture(wipro-LD49 900 XXX 60
XX 10 W )
Fixing of 9'' exhaust fan with loovers
Wall mounted Fan 3leaf , 14'', tiliting and siewel .( crompton,
almonard, usha, bajaj, rally)
LIGHTING WIRING [ PVC LHSFT MMS CONDUITS ]

Nos

35

Nos

35

Nos

20

Nos

Nos

Pts

Pts

Pts

Pts

Pts

25

Pts

40

Pts

23

Pts

12

Pts

SITC of light point / circuit wiring direct to MCB DB or switch board as


mentioned in respective drawings including circuits from switch board
& lights to MCB DB with 1.5 / 2.5 / 4 SQMM or as mentioned with
FRLS copper wires in PVC conduits with all terminations in copper
cable sockets/ lugs, using switch accessories including chasing & recementing for recess boxes & conduiting as required MK, Crab tree
switches to be considered

1
2
3
4

Switch board to switch board looping & sub circuit from DB shall be
2.5 SQMM x 3 wires
Switch board to primary & secondary point wiring shall be 1.5 SQMM
x 3 wires
DB to direct primary & secondary point wiring shall be 2.5 SQMM x 3
wires
Primary light point wiring directly controlled from LDB with 2.5 SQMM
x 3 wires in pvc conduits for lights on raw power
Secondary light point wiring looped to primary point controlled from
LDB with 2.5 SQMM x 3 w for lights on raw power
Primary light point wiring controlled from LDB with 2.5 SQMM x 3
wires for emergency lights
Secondary light point wiring looped to primary point controlled from
LDBwith 2.5 SQMM x 3 w for emergency lights

Primary light point wiring using 1.5SQMM X 3 W controlled from local


5 switch board including sub circuitof 2.5SQMM X 3 W to DB for lights
on raw power
Secondary light point wiring using 1.5SQMM X 3 W looped to primary
6
point controlled from SB for lights on raw power
Primary light point wiring using 1.5SQMM X 3 W controlled from local
7 switch board including sub circuitof 2.5SQMM X 3 W to DB for lights
on emergency power
Secondary light point wiring using 1.5SQMM X 3 W looped to primary
8
point controlled from SB for lights on emergency power
9 Looping to very short point for tube light in cove with 1.5 x 3 wire

H POWER WIRING [ PVC LHSFT MMS CONDUITS ]


SITC of power point / circuit wiring direct to MCB DB or switch board
as mentioned in respective drawings including circuits from switch
board & S/S to MCB DB with 2.5 / 4 SQMM or as mentioned in
respective drawings with FRLS copper wires in already laid Trunking &
Conduits where trunking is not available, with all terminations in
copper cable sockets/ lugs, using switch accessories including
chasing & re-cementing for recess boxes & conduiting as required,
this item shall also include the laying of conduits on floor & some extra
conduits for future use .MK, Crabtree switches for quote to be
considered . Wiring to be done in already laid floor race ways &
conduits, however flexible conduits with partitions etc. to be
considered. Primary power points shall include circuits from
respective MCB DB 'S . All emergency switch boards to have a
different colour for segrecation of labelled prominently
1
2
3
4
5
6
7
8
9
10
11
12
13
14
I
1
2
3
4
5
6
7

2.5 SQMM x 3 wire Primary power point wiring from work station
MCB DB to Switched Socket for IT Devices UPS power
2.5 SQMM x 3 wire secondary power point wiring looped from above
primary point wiring for IT devices UPS power
4 SQMM x 3 wire Primary power point wiring from work station MCB
DB to work station / IT Devices for UPS power
4 SQMM x 3 wire secondary power point wiring looped from above
primary point wiring for work station / IT Utility UPS power
2.5 SQMM x 3 wire Primary power point wiring from work station
MCB DB to work station for RAW power
2.5 SQMM x 3 wire secondary power point wiring looped from above
primary point wiring for work sation RAW power
4 SQMM x 3 wire Primary power point wiring from work station MCB
DB to work station for RAW power
4 SQMM x 3 wire secondary power point wiring looped from above
primary point wiring for work sation RAW power
S/F of 16a switch & 3 nos. 6 a socket with face plate & conceal box
and internal wiring with terminations
S/F of 6a switch & 6 a universal socket with face plate & conceal box
and internal wiring with terminations
S/F of 16a switch & 2 nos. 6 a socket with face plate & conceal box
and internal wiring with terminations
4 SQMM x 3 wire Primary power point wiring from MCB DB to Utility
Switched Socket for Utility Raw power
4 SQMM x 3 wire secondary power point wiring looped from above
primary point wiring for Utility Raw power
S/F of 6 / 16a switch socket with face plate, enclosure , internal wiring
& all terminations for utility points.
MISC ITEMS [ IN PVC CONDUITS ]
This item shall be used for other than mentioned in the BOQ
SITC of 1.5 sqmmx 3 c circuit in conduits
SITC of 2.5 sqmmx 3 c circuit in conduits
SITC of 4 sqmmx 3 c circuit in conduits
SITC of 6 sqmmx 3 c circuit in conduits
SITC of 1.5 sqmmx 5 c circuit in conduits
SITC of 2.5 sqmmx 5 c circuit in conduits
SITC of 4 sqmmx 5 c circuit in conduits

Pts

10

Pts

26

Pts

Pts

12

Pts

10

Pts

35

Pts

Pts

Nos

30

Nos

50

Nos

Pts

Pts

10

Nos

15

mts
mts
mts
mts
mts
mts
mts

0
0
0
0
0
0
0

8 SITC of 6 sqmmx 5 c circuit in conduits


J POWER LIASONING
Liasoning to enhance or procure new KWH energy meter for the
1 premises for demand load. Official charges shall be paid directly by
cheque to the power company as per request & receipt
K TEMPORARY POWER ARRANGEMENT FOR CONSTRUCTION

mts

job

mts
nos
nos

40
2
5

This shall be an one time installation & shall be maintained by the


contractor till the end of the project without any extra payment . This
shall also include electrician to be provided till the end of the project to
provide power supply for construction. After completeion the
contarctor can take back the DB , lights , switch socket s etc
1 S/F of 16 sqmm x 4 c alumnium armoured cable
2 S/F of 20 a metal clad plug socket with sp mcb in enclosure
3 S/F of 16/6 a switch socket with box
MCB DB consisting of the following [ on returnable basis to contractor
4
]
40 a 4 p elmcb -- 1nos
40 a 2 p 100ma rccb --- 3 nos
25 a spmcb ---------- 12 nos
25 a 4 p mcb ---- 1nos
6 way tpn db --- 1nos
5 S/F of 1x 36 w tube light fixture with tube
6 S/F of 200 W lamp with holder
7 S/F of extra 200 w lamps
8 S/F of 36 w extra tube only
9 S/F of 40/36 x 3 c double pvc coated wire
10 S/F of 12 swg x 2 nos bare G.I earthing with cable
11 S/F of 23/36 twin twisted wire for temporary lighting

NOTES
1 Contractor to approve all GA dwgs before fabrication
2 Contractor to provide all shop dwgs prior to installation

nos
1
nos 10
nos
5
nos
5
nos
5
mts 100
mts 40
coils 2

SUB TOTAL
TAXES
TAXES

Contractor to provide all as built dwgs( 3 sets ) after completion


Contractor to execute in coordination with all vendors ,
4
consultants & Architect

TOTAL

RUPEES [ in words ]______________________________________________________


STAMP OF CONTRACTOR _________________________________
SIGN OF CONTRACTOR ________________________________
PLACE ______________________________

DATE __________________

11/6/2014
AMOUNT
.

0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0

0
0
0
0
0
0
0
0
0

0
0
0
0
0
0
0
0
0

0
0
0

0
0
0
0

0
0
0
0

0
0
0
0
0
0
0
0
0
0

0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0

0
0
0
0
0
0

0
0
0
0
0
0
0
0
0
0
0
0
0
0

0
0
0
0
0

0
0
0
0
0
0
0
0
0

0
0
0
0
0
0
0
0
0
0
0
0
0
0

0
0
0
0
0
0
0

0
0
0

0
0
0
0
0
0
0
0

BOQ OF LV WORKS FOR KOTAK BRANCH @ JAIPUR


A CONVENTIONAL FIRE DETECTION SYSTEM
SITC of Conventional Type Fire Alarm Control Panel devices like SMOKE
DETECTOR, HEAT DETECTOR, MULTI DETECTOR, MCP, flasher cum
hooter , control modules, response indicators etc. and shall field
Programmable and with multiple characters LCD display as per the
detailed specification complete with battery backup of 48 hours operation
1
and 4 hrs in alarm operation with battery charger and annunciator window
etc. System shall have provision to integrate with life safety facilities i.e.
HVAC, PA Lift or elevator by providing NO/NC contacts and BMS
compatibility shall be through MODBUS/ Bacnet/ TCP-IP protocol. FACP
FM APPROVED.

11/6/2014
UNIT QTY RATE

nos

nos

RO

nos

18

nos

18

nos

SITC of Conventional Type Multisensor smoke detectors with required


accessories along with Junction box & Glands & Terminations.

nos

SITC of Conventional Type Manual call points, ABS plastic, square 4 "x 4"
6 , with Break glass message embedded on the glass, enclosed along with
the break glass in junction box & Terminations.

nos

SITC of Conventional Type white strobe light cum sounder with control
module. The strobe light cum sounder shall be made of ABS plastic and
7
have the Db level of 110dbs and a multi tone facility. The Conventional
Type control Module shall be fitted in a junction box.

nos

nos

nos

RO

nos

nos

nos

nos

nos

nos

2 SITC of Repeater Panel with all Accessories


SITC of Conventional Type Photo electric smoke detectors for above
2 Ceiling with required accessories along with Junction box & Glands &
Terminations.
SITC of Conventional Type Photo electric smoke detectors for below
3 Ceiling with required accessories along with Junction box & Glands &
Terminations.
SITC of Conventional Type Rate of rise thermal detectors with required
4
accessories along with Junction box & Glands & Terminations.
5

8 SITC of response indicator with required accessories.


SITC of Conventional Type Fault isolator modules with required
9
accessories including JB & glands
SITC of Conventional Type monitor modules for sprinkler flow switches
10
with required accessories including JB & Glands.
SITC of Conventional Type Control modules for AC trip off with required
11
accessories including JB & glands
SITC of Conventional Type Control modules for Access trip off with
12
required accessories including JB & glands
SITC of Conventional Type Control modules for Public Address system
13
with required accessories including JB & glands
SITC of Conventional Type Control modules for Lift interface with required
14
accessories including JB & glands
15 SITC of Panic Bar On Fire Exit Door

SITC of 2c x 1.5 Sq.mm FRLS Armoured cable. ATC conductor stranded,


PVC insulated to form a core, Cores laid up, Overall shielded with Alumylar tape with tinned copper drain wire of size 0.5 Sq. mm, PVC
innersheathed G.I. Wire armoured, PVC sheathed cable (Colour: RED )
16 SITC of 2c x 1.5 Sq.mm FRLS Armoured cable. ATC conductor
stranded, PVC insulated to form a core, Cores laid up, Overall
shielded with Alu-mylar tape with tinned copper drain wire of size 0.5
Sq. mm, PVC innersheathed G.I. Wire armoured, PVC sheathed cable
(Colour: RED )

mts

120

SITC of 150 x 50 x 2 mm Perforated Open type cable tray with suspended


support at 0.6 Mtr interval

mts

RO

16

NOTES
1 Contractor to approve all GA dwgs before fabrication
2 Contractor to provide all shop dwgs prior to installation

SUB TOTAL
TAXES
TAXES

Contractor to provide all as built dwgs( 3 sets ) after completion


Contractor to execute in coordination with all vendors , consultants
4
& Architect

TOTAL

RUPEES [ in words ]______________________________________________________


STAMP OF CONTRACTOR _________________________________
SIGN OF CONTRACTOR ________________________________
PLACE ______________________________

DATE __________________

11/6/2014
AMOUNT

0
0

0
0
0

0
0
0
0
0
0
0
0
0

0
0

BOQ OF LV WORKS FOR KOTAK BRANCH @ JAIPUR


E VOICE / DATA / SIGNAL

11/6/2014

UNIT QTY

RATE

AMOUNT

Supply, installation, testing & commissioning [S.I.T.C] of


signal cabling wiring in already laid & considered floor
raceway & / or floor conduits .As per drawings it shall include
conduits where ever necessary other than laid raceway,
conduits & with all terminations. This item shall include
conduits in partition or where ever required from Junction Box
SITC of 2 pair phone wire for voice from hub / server /

1 electrical room to voice outlets

SITC of RJ-11 phone socket outlet plate & enclosure along

2 with all terminations for voice outlets

SITC of CAT 6 wire from hub / server / electrical room to data

3 outlets

SITC of CAT 6 I/O, face plate & enclosure along with all

4 terminations for data outlets

SITC of CAT 6 wire from server room to data outlets for WIFI

5 with terminations
6 SITC of 5 pair jelly filled 0.5 mm armoured phone cable
7 S/F of 50 pair TTB
8 SITC of RG 6 antena wire from electrical room to TV outlets
SITC of RG 6 TV antena socket outlet with Conceal box &

9 face plate
10 SITC of RG11 antena wire with pvc conduit
11 SITC of 4 way splitter in 12" x 12'' x 2'' pvc box
12 SITC of multi mode fibre optic cable
13 SITC of multi mode fibre optic cable converter
14 SITC of multi mode fibre optic cable patch cord
NOTES
1 Contractor to approve all GA dwgs before fabrication
2 Contractor to provide all shop dwgs prior to installation

Pts

60

Nos

60

Pts

70

Nos

70

Pts

RO

Mtr
Nos
Pts

50
1
0

0
0
0

Nos

Mtr
0
Nos 0
Mtr
0
Nos 0
Nos 0
SUB TOTAL
TAXES
TAXES

0
0
0
0
0

Contractor to provide all as built dwgs( 3 sets ) after


completion
Contractor to execute in coordination with all vendors ,
4
consultants & Architect
3

TOTAL

RUPEES [ in words ]______________________________________________________


STAMP OF CONTRACTOR _________________________________
SIGN OF CONTRACTOR ________________________________
PLACE ______________________________

DATE __________________

You might also like