Professional Documents
Culture Documents
CENTRO DE TECNOLOGIA
PROGRAMA DE PS-GRADUAO EM ENGENHARIA ELTRICA
CONTROLADORES
PID
AUTO-AJUSTVEL
FORTALEZA
OUTUBRO 2007
NEBULOSO
ii
CONTROLADORES
PID
AUTO-AJUSTVEL
NEBULOSO
Fortaleza
Outubro 2007
iii
CONTROLADORES
PID
AUTO-AJUSTVEL
NEBULOSO
iv
DEDICATRIA
AGRADECIMENTOS
vi
RESUMO
vii
ABSTRACT
With the globalization and the competitiveness in all the levels of the industrial sector, the
final product quality search became higher. On the other hand, energy saving became another
important factor in modern industry. The consumption of electric energy in the industrial
sector represents 45.5% of the total consumption of the country. The motor force represents
most of this consumption, arriving to be superior of 80% in the textile, paper and cellulose
sectors. This work presents two strategies of control, auto-adjustable PID and fuzzy
controller, the objectives are a better final product quality and the energy saving. Ventilation
and compression industrials process are used in this work. An analysis of limit cycles
presence through the descriptive function of the fuzzy controller is carried through, providing
a previously validation of fuzzy controllers parameters by simulations, saving time in the
adjust phase. Set-point changes are easily made and on-line, still the process is running, in the
two considered controllers. Comparisons of energy consumption are made between the
conventional strategies and the two strategies considered in this work.
Keywords: Industrial processes, auto-adjustable PID, Fuzzy controller, limit cycle, energy
saving, PLC, fans and compressors.
viii
SUMRIO
LISTA DE TABELAS............................................................................................
LISTA DE FIGURAS............................................................................................
LISTA DE SMBOLOS........................................................................................
LISTA DE ABREVIATURAS E SIGLAS ..........................................................
x
xi
xiv
xv
CAPTULO 1.
1. INTRODUO.....................................................................................................................1
1.1 - INTRODUO ............................................................................................................1
1.2 - ORGANIZAO DO TRABALHO. ...........................................................................7
1.3 - PUBLICAES. ..........................................................................................................8
CAPTULO 2.
2. CONTROLE PID AUTO-AJUSTVEL ............................................................................10
2.1 INTRODUO.............................................................................................................10
2.2 - IDENTIFICAO EM FREQNCIA DA FUNO DE TRANSFERNCIA DO
PROCESSO .........................................................................................................................11
2.2.1 - ESTIMAO DA FUNO DE TRANSFERNCIA DO PROCESSO POR
MEIO DO REL .............................................................................................................12
2.2.1.1 AVALIAO EXPERIMENTAL DO MTODO DE IDENTIFICAO
COM O REL .................................................................................................................16
2.2.2 MODELAGEM DE BAIXA ORDEM ATRAVS DO REL ..........................18
2.3 MTODO DE AUTO-SINTONIA DE CONTROLADORES PID..............................21
2.3.1 - CONTROLADOR PID AUTO-AJUSTVEL COM ESPECIFICAES DE
FASE E GANHO PARA O SISTEMA COMPENSADO ..............................................22
2.3.1.1 - ESPECIFICAO DE FASE E GANHO PARA O SISTEMA
COMPENSADO..............................................................................................................23
2.4 - CONCLUSES...........................................................................................................28
CAPTULO 3.
3. CONTROLADOR NEBULOSO COM ANLISE DE ESTABILIDADE ........................29
3.1 INTRODUO.............................................................................................................29
3.2 CONTROLADORES NEBULOSOS.........................................................................30
3.2.1 - INTERFACE DE FUZZIFICAO" ................................................................31
3.2.2 - BASE DE CONHECIMENTO ............................................................................31
3.2.3 - PROCEDIMENTO DE INFERNCIA ...............................................................33
3.2.4 - INTERFACE DE "DEFUZZIFICAO" ............................................................35
3.3 CONTROLADOR NEBULOSO COM ANLISE DE ESTABILIDADE .................35
3.4 PREDIO DO CICLO LIMITE DO SISTEMA NEBULOSO USANDO O
MTODO DA FUNO DESCRITIVA ...........................................................................39
3.4.1 FUNO DESCRITIVA ....................................................................................40
3.4.2 CICLO LIMITE...................................................................................................42
3.4.3 - FUNO DESCRITIVA ANALTICA DO CONTROLADOR NEBULOSO..43
3.4.4 ANLISE PARA O CONTROLADOR IMPLEMENTADO. ..............................46
3.5 CONCLUSO...............................................................................................................51
ix
CAPTULO 4.
4. PLANTAS INDUSTRIAIS E RESULTADOS EXPERIMENTAIS..................................53
4.1 INTRODUO.............................................................................................................53
4.2 VENTILADORES INDUSTRIAIS............................................................................53
4.2.1 BANCADAS DOS EXPERIMENTOS....................................................................56
4.2.2 ESTRATGIAS DE CONTROLES USADAS ....................................................57
4.2.3 VENTILADOR CENTRFUGO. .............................................................................58
4.2.4 VENTILADOR AXIAL. ..........................................................................................63
4.3 COMPRESSORES .....................................................................................................67
4.3.1 CONTROLE DE CAPACIDADE............................................................................68
4.3.2 BANCADA EXPERIMETAL..................................................................................69
4.4 CONCLUSES .............................................................................................................74
CAPTULO 5.
5. CONCLUSES E PROPOSTAS DE TRABALHOS FUTUROS .....................................76
5.1 CONCLUSES .............................................................................................................76
5.2 PROPOSTAS DE TRABALHOS FUTUROS..............................................................78
REFERNCIAS BIBLIOGRFICAS..................................................................................79
APNDICE A.........................................................................................................................85
APNDICE B.........................................................................................................................94
LISTA DE TABELAS
Tabela 1.1 - Consumo de Eletricidade em Fora Motriz no Setor Industrial Brasileiro............3
Tabela 2.1. Lista de cdigos.....................................................................................................17
Tabela 3.1 - Operadores de implicao nebulosa.....................................................................33
Tabela 3.2 - Principais T-norma e T-conorma..........................................................................33
Tabela 3.3 Base de regra do controlador nebuloso................................................................38
Tabela 3.4 Situaes a) Erro negativo, derivada do erro negativa e sada de controle
negativa. b)Erro positivo, derivada do erro zero e sada de controle positiva.....................38
Tabela 4.1 Lista de cdigos...................................................................................................59
Tabela 4.2 ndices de desempenho para o ventilador centrfugo...........................................62
Tabela 4.3 Comparao de consumo de energia....................................................................63
Tabela 4.4 Lista de cdigos...................................................................................................64
Tabela 4.5 ndices de desempenho para o ventilador axial....................................................66
Tabela 4.6 Comparao de consumo de energia....................................................................67
Tabela 4.7 Dados de placa compressor..................................................................................69
Tabela 4.8 ndices de desempenho para o compressor..........................................................73
Tabela 4.9 Comparao de consumo de energia....................................................................73
Tabela A.1 - Classificao de ventiladores quanto ao nvel de presso....................................85
xi
LISTA DE FIGURAS
Figura 1.1 - Consumo de energia eltrica no pas entre os principais setores...........
3
13
Figura 2.2: (a) Rel sem histerese, (b) Rel com histerese.......................................
14
Figura 2.3: Sada do rel u(t), onda quadrada; sada do processo y(t), caracterstica
senoidal......................................................................................................................
14
15
G(j).........................................................................................................................
Figura 2.5: Bancada do ventilador centrfugo...........................................................
16
17
18
19
Figura 2.9: (a) rel com histerese no-simtrica, (b) sada do rel (onda quadrada)
e sada do processo....................................................................................................
19
21
22
23
25
27
28
31
36
37
40
N ( A, ) G ( j ) ......................................................................................................
43
43
47
48
xii
49
49
50
50
51
54
55
55
56
57
59
60
60
61
61
64
65
65
66
69
70
71
72
72
xiii
74
86
86
87
87
88
89
90
91
92
93
96
96
100
xiv
LISTA DE SMBOLOS
ISO
TEP
CLP
CO2
PID
CN
FSF
BEN
BEU
xv
Gp
p
rp
Gs
Nome
Unidade
admensional
admensional
admensional
Minutos
Minutos
Segundos
admensional
Funo do controlador
ganho do controlador
ngulo do controlador
Funo do controlador
ngulo do processo
admensional
admensional
radianos
admensional
radianos
Ganho do processo
admensional
rs
s
i,j
FNe
FZe
FPe
FNde
FZde
FPde
Abreviatura
min
min
seg
rad
rad
admensional
admensional
radianos
rad
admensional
admensional
admensional
admensional
admensional
admensional
admensional
Hertz
Hz
Variao da entrada
Hertz
Hz
e
de
Erro
derivada do erro
admensional
admensional
1
1
admensional
admensional
admensional
Crisp
N(A, )
an
bn
admensional
admensional
xvi
A
J1,J2,J3 e J4
Amplitude
ndices de desempenhos
V1
Rendimento volumtrico
Constante relativa a geometria do
compressor, da ordem de 0,5
Dimetro do rotor macho
L
Wc
wk
k
mec
T2
T1
T2S
k
Metros
cbicos por
hora
m3/h
admensional
admensional
Milimetro
Rotaes por
minuto
Milimetro
Watts
Kilograma
por segundo
admensional
Coeficiente emprico
admensional
mm
rpm
mm
W
Kg/s
J/kg
o
o
o
C
C
C
CAPTULO 1
INTRODUO
1.1 - INTRODUO
CAPTULO 1 INTRODUO
Figura 1.1 - Consumo de energia eltrica no pas entre os principais setores.(Moreira, 2006)
CAPTULO 1 INTRODUO
Figura 1.2 - Consumo de energia eltrica para o setor industrial. (Moreira, 2006)
Setor consumidor
de Eletricidade
Cimento
317,5
285,8
13,5
Ferro Gusa e Ao
1.213,5
1.092,2
51,6
19,1
17,2
0,8
Minerao e Pelotizao
738,4
664,5
31,4
Minerais No Ferrosos
884,3
795,8
37,6
Qumica
1.369,3
1.232,3
58,3
Alimentos e Bebidas
1.062,2
955,9
45,2
Txtil
384,5
346,1
16,4
Papel e Celulose
1.148,8
1.033,9
48,9
Indstria Cermica
236,1
210,1
5,2
1.772,1
1.329,1
170,8
9.145,8
7.962,9
479,7
CAPTULO 1 INTRODUO
CAPTULO 1 INTRODUO
PID. Somente 3% das malhas utilizam controladores avanados para superar deficincias do
controlador PD.
O controlador PID (Proporcional, Integral e Derivativo) a principal estrutura
de controle convencional, e a sintonia tima ou o auto-ajuste dos seus parmetros constitui,
ainda hoje, um desafio tanto a nvel acadmico quanto industrial. Entretanto, os controladores
baseados em tcnicas convencionais, por serem projetados considerando-se apenas as relaes
lineares entre as variveis do modelo do processo a ser controlado, apresentam limitaes
frente a sistemas que possuem caractersticas complexas como: no-linearidades, atrasos de
transporte e parmetros variantes no tempo.
Para superar as limitaes do controle convencional, tcnicas de controle
avanadas podem ser empregadas. A maioria dos especialistas em controle denominam
controladores avanados quando referem-se a controladores inteligentes, adaptativos, nolineares e/ou preditivos. As estratgias de controle avanadas permitem o aprimoramento do
desempenho dos sistemas de controle quando comparadas s tcnicas convencionais. Por
outro lado, para a implementao do controle avanado, h a necessidade da configurao de
um elevado nmero de parmetros, o que requer conhecimentos especializado e de tcnicas
matemticas complexas.
Entre as tcnicas de controle avanados, os controladores inteligentes vem
sendo implementados com sucesso, inclusive em CLPs do fabricante Fuji, principalmente
pela capacidade de incorporarem conhecimento especializado e pela possibilidade de
associaes com outras tcnicas convencionais e avanadas. O desenvolvimento da tecnologia
de processamento de informao, aliado s tcnicas de inteligncia computacional, tornou
possvel o desenvolvimento de sistemas de controle automticos, ditos inteligentes, como uma
soluo para suprir as deficincias dos sistemas de controle convencionais. Desde que a
inteligncia computacional apresenta aspectos relativos incorporao de caractersticas da
inteligncia humana, os sistemas de controle inteligentes tendem a imitar a maneira de tomada
de decises humana. As vantagens potenciais oferecidas em relao aos esquemas
convencionais de controle so: i) menor dependncia de modelos quantitativos; ii) algoritmos
de tomada de decises estruturados de maneira simples; iii) capacidade de aprendizado e, iv)
maior grau de autonomia (BARTOS, 1997; COELHO & COELHO, 1997a e 1997b)
CAPTULO 1 INTRODUO
CAPTULO 1 INTRODUO
1.3 - PUBLICAES
CAPTULO 1 INTRODUO
SNCA 2007
Projeto de controle nebuloso atravs do mtodo da funo descritiva com previso de
ciclos limites. F. A. Guimares, O. M. Almeida, R. T. Pontes. SBAI 2007.
Controle PID auto-ajustvel em ventiladores industriais visando a eficincia
energtica. F. A. Guimares, O. M. Almeida, A. B. Moreira, V. P. B. Aguiar, C. R. S.
CAPTULO 2
CONTROLE PID AUTO-AJUSTVEL
2.1 INTRODUO
11
12
substituio da resposta ao degrau por um segundo experimento com o rel. Neste caso foi
utilizado um rel com histerese com adicional atraso de transporte na malha de
realimentao. LI et al. (1991) investigaram os erros de modelagem quando a nolinearidade modelada pela mtodo da funo descritiva. SCHEI (1994) utilizou dois
experimentos com o rel para estimar dados nas freqncias crtica e de cruzamento do eixo
imaginrio negativo do diagrama de Nyquist e, ento, determinar os parmetros de um
modelo discreto ARX (Auto Regressive Exogenous) para a funo de transferncia do
processo. LUNDH & STRM (1994) sugeriram a utilizao dos dados gerados pelo
experimento com o rel para estimar um modelo contnuo para o processo e a utilizao
desde modelo para o ajuste inicial dos ganhos de controladores self-tuning. WANG et al.
(1997a) derivaram expresses exatas para os perodos e amplitudes dos ciclos limites
estabelecido com um processo de primeira ordem com atraso de transporte. WANG et al.
(1997b) propuseram a utilizao do mtodo para determinao da funo de transferncia do
processo em um grande intervalo de freqncia. BI et al. (1997) utilizaram a transformada
rpida de Fourier para melhorar a preciso na estimao dos dados a partir do experimento
com o rel. WANG et al. (1999a), utilizando a transformada rpida de Fourier, propuseram
uma modificao que possibilita a estimao da funo de transferncia do processo em
vrias freqncias. WANG & CLUET (1996) propuseram um novo mtodo para, a partir do
experimento com o rel, obter a resposta em freqncia e a resposta ao degrau do processo
utilizando a tcnica FSF (Frequency Sampler Filter ) e estimadores dos mnimos quadrados.
13
ento u(t)=d
ento u(t)=-d
O rel sem histerese (figura 2.2a) pode ser modelado no domnio do tempo
por
Se [(e(t)<0 ]
ento u(t)=-d
Se [(e(t)>0 ]
ento u(t)= d
14
Figura 2.2: (a) Rel sem histerese, (b) Rel com histerese.
Os sinais e(t) e u(t) so mostrados na figura 2.3. A sada do rel u(t), varivel
de controle, corresponde a uma onda quadrada. Com os sinais da figura 2.3a e 2.3b, como
entrada para o processo e, considerando-se que a resposta do processo em malha fechada seja
dominada pelas componentes de baixa freqncia, a sada oscila de forma senoidal como
mostra a figura 2.3a e 2.3b, respectivamente.
Figura 2.3: Sada do rel u(t), onda quadrada; sada do processo y(t), caracterstica senoidal.
G ( j ) =
a
4d
(2.1)
15
G ( j ) =
4d
a2 2 j
(2.2)
4d
a)
b)
Figura 2.4: Interseo dos lugares geomtricos do recproco inverso da funo descritiva do rel sem
histerese (a) e com histerese (b) com o lugar geomtrico de G(j).
a
j
4d
(2.3)
16
17
18
Hz
m3/s
19
S te p V e n til a d o r C e n trfu g o
2 .5 0 0
Vazo(m3/s)
2 .0 0 0
1 .5 0 0
1 .0 0 0
0 .5 0 0
0 .0 0 0
0
10
20
30
40
T e m p o (s e g )
50
60
70
V azo R ad ial [m /s ]
Para este caso, a fim de eliminar rudos de medida, fez-se um filtro de mdia
mvel.
Devido presena de um atraso de transporte na malha, um modelo capaz de
representar adequadamente o processo pode ser obtido a partir da equao 2.4.
G (s) =
K p e LS
Ts + 1
(2.4)
Figura 2.9: (a) rel com histerese no-simtrica, (b) sada do rel (onda quadrada) e sada do processo.
20
Tu 1 +Tu 2
Kp
0
Tu 1 +Tu 2
0
y (t )dt
u (t )dt
y y () y (0)
=
u u () u (0)
(2.5)
onde Tu1 e Tu2 esto definidos na figura 2.9b. O ganho do processo pode ser obtido tambm
pela resposta ao degrau, o ganho dado pelo valor da varivel de controle em regime
permanente dividido pelo valor do degrau.
A constante de tempo (T) pode ser obtida por
T=
Tu 2
0 + d0 K p d2 K p
Ln
d1K p d 0 K p (d 2 + d 0 ) K p e
(2.6)
Ad d 0 K p + d1 K p
(2.7)
a) Aplicao Prtica
(2.8)
21
22
Gc ( j ) = rc e jc
(2.9)
onde
rc = K p [1 + ( c Td
Kp
1 2
) ]=
cTi
cos( c )
(2.10)
c = arctan( cTd
1
)
cTi
23
(2.11)
j p
(2.12)
24
tem-se
p = arctan(
rp =
a
4d
a 2
2
1
Ku
(2.13)
(2.14)
(2.15)
(2.16)
Kc =
rs cos( s p )
rp
= K u .rs . cos( s p )
tan( s p ) = ( Td
1
)
Ti
(2.17)
(2.18)
(2.19)
25
Td =
Ti =
1
2 c
[tan(
p ) + 4 + tan 2 ( s p )
Td
(2.20)
(2.21)
(2.22)
s=-180o
(2.23)
Figura 2.13: Com a especificao da margem de ganho Am, o ponto S movido para a posio
especificada do plano_G(s).
26
27
28
2.4 - CONCLUSES
supervisionados
atravs
de
um
aplicativo
SCADA
de
propsito
geral.
CAPTULO 3
CONTROLADOR NEBULOSO
3.1 INTRODUO
CAPTULO 3 CONTROLADOR
NEBULOSO
30
CAPTULO 3 CONTROLADOR
NEBULOSO
31
CAPTULO 3 CONTROLADOR
32
NEBULOSO
....
.....
(3.1)
....
.....
Rn: Se x1 A1,n e x2 A2,n Ento y Cn
onde x1, x2 so variveis lingusticas que representam o estado do processo e y a varivel
lingustica de controle. A1,i, A2,i e Ci so valores lingusticos das variveis lingusticas nos
universos de discurso U, V e W, respectivamente, com i=1,...,n.
Um conjunto de regras tais como Se (x1 A1,i e x2 A2,i) Ento (yi Ci)
implementada por uma implicao (relao) nebulosa Ri definida como:
R (A
i
1, i
e A2 , i Ci )
( x1 , x 2 , u ) = [ A1,i ( x1 )
A ( x 2 )] C (u )]
2 ,i
(3.2)
CAPTULO 3 CONTROLADOR
33
NEBULOSO
Implicao
max(1-a,b)
min(1-a+b,1 )
1, se ab
1, se ab
min(a/b), se ab
1-a+ab
max(1-a,min(a,b))
min(a,b)
ab
Nome
Kleene-Diemes
Lukasiewicz
Rescher-Gaines
Brower-Gdel
Goguen
Reichenbach
Zadeh-Wilmott
Mandani
Larsen
t-norma
min(a,b)
ab
max(a+b-1,0)
a, se b=1
b, se a=1
0 seno
t-conorma
max(a,b)
a+b-ab
min(a+b,1 )
a, se b=0
b, se a=0
1 seno
Nome
Zadeh
probabilstica
Lukasiewicz
Weber
CAPTULO 3 CONTROLADOR
34
NEBULOSO
i , j = A ( xi* ),
1 i n,
i, j
1 j m
j = T ( 1, j , L, n , j )
1 j n
C ( y) = I ( j , C ( y)),
'
j
y Y
C ( y ) = ( C ( y ),L, C ( y )),
'
'
1
'
m
y Y
CAPTULO 3 CONTROLADOR
NEBULOSO
35
CAPTULO 3 CONTROLADOR
36
NEBULOSO
-1, -1
1, 1
e(t), e(t)
(3.3)
(3.4)
(3.5)
(3.6)
FZe = 1 +
FZe = 1
FPe =
1
e
(3.7)
(3.8)
onde FNe a funo negativo do erro, FZe a funo zero do erro, FPe a funo positivo
do erro, e o erro e o limite da funo de pertinncia do erro.
CAPTULO 3 CONTROLADOR
37
NEBULOSO
de
, se - 1 < de < 0;
FNde = 1 , se de < - 1 ;
FZde = 1 +
FZde = 1
FPde =
de
de
1
de
(3.9)
(3.10)
, se - 1 < de < 0;
(3.11)
, se 0 < de < 1 ;
(3.12)
, se 0 < de < 1 ;
FPde = 1 , se de > 1 .
(3.13)
(3.14)
onde FNde a funo negativo da derivada do erro, FZde a funo zero da derivada do
erro, FPde a funo positivo da derivada do erro e de a derivada do erro.
Com o propsito de simplificar o processo de defuzzificao e facilitar a
implementao, funes tipo crisp so utilizadas para o processo nebuloso de sada. A
figura 3.3 apresenta as funes de pertinncia para o incremento da varivel de controle.
CAPTULO 3 CONTROLADOR
38
NEBULOSO
e(t)
N
Z
P
N
N
N
Z
de(t)
Z
N
Z
P
P
Z
P
P
ii)
e(t)
e(t)
N
Z
P
N
N
N
Z
de(t)
Z
N
Z
P
P
Z
P
P
N
Z
P
N
N
N
Z
de(t)
Z
N
Z
P
P
Z
P
P
(3.15)
(3.16)
CAPTULO 3 CONTROLADOR
NEBULOSO
39
e de e de e de
u = Crisp 1 . + .1 + . ,
1 1 1 1 1 1
(3.17)
de e.de e
e.de e.de
+
+
u = Crisp
1
1
1
1
1
1
1
1
(3.18)
de e
e.de
,
u = Crisp +
1
1
1 1
(3.19)
.de + 1 .e e.de
u = Crisp 1
1 . 1
(3.20)
CAPTULO 3 CONTROLADOR
NEBULOSO
40
como o controle nebuloso. Em (KIM et al, 2000) dito que o ciclo-limite causa uma regio de
estabilidade limitada pela atrao sem afetar o comportamento local ao redor do ponto de
operao. Se uma perturbao leva o controle nebuloso para fora da regio de estabilidade, ele
se tornar instvel mesmo se o ponto de operao continua estvel e precisa de mais cuidado
(GUIMARAES et al, 2007a).
Lamentavelmente, apenas alguns projetos de pesquisa levam em considerao
esse problema reportado. Perng e Hara mostraram a existncia do ciclo-limite em um sistema
de controle nebuloso por experimentos (PERNG et al, 2005; HARA & ISHIBE, 1992) e
Kickert e Mandani tentaram demostrar teoricamente o ciclo-limite de um sistema de controle
nebuloso pela aproximao do controlador lgico nebuloso em um rel multinvel em
(KICKERT E MANDANI, 1978). Gordillo et al (1997) tentaram d um entendimento
qualitativo do comportamento dos sistemas de controle nebuloso e previram os ciclo-limites
indesejveis usando a funo descritiva experimental do controlador nebuloso.
CAPTULO 3 CONTROLADOR
41
NEBULOSO
u (t ) = u ( x = A sin t , x = A cos t )
a0
+ (a n cos(nt ) + bn sin( nt ))
2 n =1
(3.21)
(3.22)
onde:
a0 =
an =
bn =
u (t )dt
(3.23)
u (t ) cos(nt )dt
(3.24)
u (t ) sin(nt )dt
(3.25)
N ( A, ) =
(b1 + ja1 )e jt 1
= (b1 + ja1 )
A
Ae jt
(3.26)
sendo:
a1 =
b1 =
u (t ) cos(t )dt
(3.27)
u (t ) sin(t )dt
(3.28)
CAPTULO 3 CONTROLADOR
NEBULOSO
42
1 + N ( A, )G ( j ) = 0
(3.29)
Se A = A1 e = 1 satisfaz a equao (3.29), ento o sistema em malhafechada ter um ciclolimite com a amplitude A1 e a freqncia 1 / 2 . Ento, no caso em que
as duas curvas de G ( j ) e 1 / N ( A, ) so plotadas em um nico plano complexo, se as duas
curvas formam um ponto de operao comum, promovem o surgimento de ciclos limites. Pela mesma
razo, se a curva N ( A, ) G ( j ) plotada no plano complexo, se a curva passa pelo ponto (-1,0) o
ciclo-limite estabelecido. Na figura 3.5, apresenta-se duas representaes no plano complexo dos
lugares geomtricos que caracterizam ciclos limites.
CAPTULO 3 CONTROLADOR
NEBULOSO
43
CAPTULO 3 CONTROLADOR
44
NEBULOSO
as
suposies
que
mesmo
simtrico.
x(t ) = A sin t ,
Se
ento
1 sin 1
1
A
(3.30)
a1 =
a1 =
u (t ). cos tdt ,
(3.31)
(3.32)
/2
( / 2 )
u (t ). cos tdt
( / 2 )
/2
a1 =
+
u (t ). cos tdt
u (t ). cos tdt
(3.33)
1 ( / 2 )
0 u k . cos k dk
/2
u (t ). cos tdt
u (t ). cos tdt
/ 2 u k . cos k dk
/2
a1 =
u (t ). cos tdt
{
2
/2
u ( t ). cos td t +
/2
u ( t ). cos td t
(3.34)
CAPTULO 3 CONTROLADOR
45
NEBULOSO
Pelo Lema 2,
a1 =
a1 =
{ u(t).cos tdt}
2
(3.35)
h 1
i +1
i=0
(3.36)
u (t ). cos tdt
a1 =
(3.37)
.de + 1 e.de
. cos tdt .
Crisp. 1
1 . 1
a1 =
(3.38)
a1 =
1
1
1
2.Crisp
2
2
1 . A..0 cos t.dt + 1 A.0 cos t. sin t.dt + A.0 cos t. sin t.dt +
.1 . 1
a1 =
(0.5. cos 1 . sin 1 + 0.5. 1 0.5. cos 0 ) + 1 ( 0.5. cos 2 1 + 0.5 cos 0) +
2.Crisp
A
1 ..
3
.1 . 1
+ . A 0.333 cos 1 0.333
b1 =
u (t ). sin tdt
(3.42)
h 1
i +1
i =0
u (t ). sin tdt
(3.40)
(3.41)
(3.39)
(3.43)
CAPTULO 3 CONTROLADOR
.de + 1 e.de
. sin t.dt
Crisp. 1
1 . 1
b1 =
b1 =
1
1
1
2.Crisp. A
2
2
1 . 0 cos sin t.dt + 1 0 sin t.dt . A0 cos t. sin t.dt
.1 . 1
b1 =
2
2.Crisp. A 1 .. 0,5 cos 1 + 0,5 + 1 (0,5 cos 1 . sin 1 + 0,5. 1 )
46
NEBULOSO
(3.44)
(3.45)
(3.46)
CAPTULO 3 CONTROLADOR
NEBULOSO
47
CAPTULO 3 CONTROLADOR
NEBULOSO
48
CAPTULO 3 CONTROLADOR
49
NEBULOSO
Diagrama de Nyquist
0.2
0.15
Funo de transferncia
do processo
0.1
0.05
Funo descritiva do
controlador nebuloso
0
-0.16
-0.14
-0.12
-0.1
-0.08
-0.06
-0.04
-0.02
0.02
Eixo Real
Figura 3.9 Diagrama de Nyquist da planta e do controlador nebuloso sem ciclo limite.
0.4
0.3
Sada do processo
Vazao(m3/s)
0.2
0.1
0
-0.1
-0.2
-0.3
-0.4
10
20
30
40
50
Tempo(seg)
60
70
80
90
100
CAPTULO 3 CONTROLADOR
50
NEBULOSO
Diagrama de Nyquist
0.1
Funo de transferncia
do processo
0.08
Eixo Imaginrio
0.06
0.04
0.02
Funo descritiva do
controlador nebuloso
-0.02
-0.08
-0.06
-0.04
-0.02
0.02
Eixo Real
Figura 3.11 Diagrama de Nyquist da planta e do controlador nebuloso com ciclo limite.
Vazao(m3/s)
na figura 3.12.
Figura 3.12 Resposta a regulao do sistema Nebuloso com ciclo limite simulado.
CAPTULO 3 CONTROLADOR
51
NEBULOSO
Para o mesmo caso, o CLP foi reprogramado com estes parmetros causadores
de ciclos limite. Foi obtida a resposta real da planta sem estabilidade conforme mostra a
figura 3.13 na qual pode-se observar a existncia do ciclo-limite.
Figura 3.13 Resposta a regulao do sistema Nebuloso com ciclo limite no sistema real.
3.5 CONCLUSO
Neste
captulo
apresentou-se
estrutura
do
controlador
nebuloso
implementado. Para garantir a no existncia de ciclos limites, foi realizado um estudo que
resultou na modelagem por funo descritiva do controlador. A partir desta modelagem foi
possvel derivar um mtodo sistemtico de ajuste de escala do controlador que leva o sistema
estabilidade. O controlador nebuloso derivado foi aplicado a plantas industriais, e como
exemplo apresentou-se neste captulo o caso do ventilador centrfugo. Outras aplicaes sero
apresentadas no prximo captulo.
CAPTULO 3 CONTROLADOR
NEBULOSO
52
CAPTULO 4
PLANTAS INDUSTRIAIS E RESULTADOS
EXPERIMENTAIS
4.1 INTRODUO
54
Figura 4.1 - Ventilador acionado velocidade constante com damper para o controle de vazo.
55
Figura 4.2 - Ventilador acionado velocidade varivel. O controle da vazo obtido por variao da rotao do
ventilador.
56
57
58
59
Descrio
Transdutor de vazo
Transdutor de presso
Transdutor de temperatura
Damper
Transdutor de posio
Contactores
Transdutores de corrente
Motor de induo trifsico
Inversor de freqncia
Sensor de velocidade do motor
Medidor de grandezas eltricas
60
61
1.60
70
1.40
60
1.20
50
1.00
40
0.80
30
0.60
VelMotor(Hz)
Vazo(m/s)
20
0.40
0.20
10
0.00
0
0
100
200
300
Vazo Radial [m/s]
Tempo(seg)
SetPoint
Vel.M.Radial [Hz]
1.60
70
1.40
60
1.20
50
1.00
40
0.80
30
0.60
0.40
20
0.20
10
0.00
0
0
100
200
Tempo(seg)
VelMotor(HZ)
Vazo(m/s)
CN Ventilador Centrfugo
300
Vazo Radial [m/s]
SetPoint
Vel.M.Radial [HZ]
Figura 4.10 Resposta do ventilador centrfugo ao controle nebuloso usando os seguintes parmetros 1 = 0,5 ,
1 = 0,2 e Crisp = 2.
62
J1 =
k[e( k )]
(4.1)
k =1
N
J2 =
[u( k ) u ]
J3 =
1
N
(4.2)
k =1
u( k )
(4.3)
k =1
J 4 = [ y (k ) y ]2
(4.4)
k =1
ndice
CN
PID
J1
J2
J3
J4
2301
45076
33,46
49,42
1671
55863
35,53
52,89
63
Como pode ser visto na tabela 4.3, a economia de energia eltrica varia
de 43,71% 81,81% dependendo da vazo de operao. Para valores menores de vazo, a
economia maior porque o damper opera quase que totalmente fechado, impondo uma
maior carga para o ventilador.
4.2.4 VENTILADOR AXIAL.
64
Cdigo
Descrio
FT
PDT
M
ZT
K3, K4
TCs
MIT
INV
SV
MG
Transdutor de vazo
Transdutor de presso
Damper
Transdutor de posio
Contactores
Transdutores de corrente
Motor de induo trifsico
Inversor de freqncia
Sensor de velocidade do motor
Medidor de grandezas eltricas
65
4.00
80
3.50
70
3.00
60
2.50
50
2.00
40
1.50
30
1.00
20
0.50
10
0.00
0
0
100
200
Tempo(seg)
VelMotor(Hz)
Vazo(m/s)
300
Vazo Axial [m/s]
SetPoint
Vel.M.Axial [Hz]
66
4.00
80
3.50
70
3.00
60
2.50
50
2.00
40
1.50
30
1.00
20
0.50
10
0.00
0
0
100
200
VelMotor(Hz)
Vazo(m/s)
CN Ventilador Axial
300
Tempo(seg)
Vazo Axial [m/s]
SetPoint
Vel.M.Axial [Hz]
ndice
CN
PID
J1
J2
J3
J4
15629
38214
32,67
311,91
9369
26809
33,82
247,73
67
uma enorme economia de energia. A tabela 4.6 faz a comparao do consumo de energia para
vrios valores de vazo com a operao do ventilador com o uso do damper e com a variao
da velocidade.
Tabela 4.6 Comparao de consumo de energia.
68
69
O compressor acionado por um motor de 3HP, que pode ser acionado tanto
pela rede eltrica como por um inversor de freqncia de 2,5 kW do modelo Altivar31 da
Schneider-Electric.
O compressor do fabricante KAESER modelo Sigma SX3 e seus dados de
fabricao so mostrados na tabela 4.7. Segue a foto do compressor junto com o reservatrio
de ar na figura 4.15.
Tabela 4.7 Dados de placa compressor.
70
PI
TI
FIT
PT
REDE
K2
VP
K1
MG
C
M
MG
PT
FIT
PI
TI
VP
71
72
PID Compressor
50
7.00
45
40
5.00
35
4.00
30
25
3.00
20
2.00
15
VelMotor(Hz)
Presso(bar)
6.00
10
1.00
0.00
0
200
400
600
0
800
Tempo(seg)
Presso
[bar]
SetPoint [bar]
VelMotor [Hz]
Figura. 4.18 Resposta do controlador PID com os parmetros: Kp =1,85, Ti = 4,125 e Td = 1,031.
7.0
60
6.0
50
5.0
40
4.0
30
3.0
20
2.0
VelMotor(Hz)
Presso(bar)
CN Compressor
10
1.0
0.0
0
200
400
600
Tempo(seg)
800
0
1000
Presso [bar]
SetPoint [bar]
VelMotor [Hz]
73
ndice
CN
PID
J1
J2
J3
J4
3673
23984
41,35
268,75
11257
1880
32,85
379,72
No ensaio feito com o controlador PID, nota-se que ocorre um pequeno erro de
offset, ou seja, a presso ficou um pouco menor do que a presso desejada. O controlador
nebuloso apresentou um comportamento bastante oscilatrio.
Os ndices J1 e J4 do controlador nebuloso foram bem melhores que os do
controlador PID, porm os ndices J2 e J3 foram melhores para o controlador PID.
A mesma anlise de consumo de energia mostrada nos ventiladores ser feita
para o compressor. A tabela 4.9 mostra o consumo de energia da operao, em 10 minutos,
com o uso da vlvula de alvio e a operao com a variao da velocidade do compressor.
mostrada tambm a economia percentual de energia eltrica da operao com a variao da
velocidade para os ensaios com durao de 10 minutos.
Tabela 4.9 Comparao de consumo de energia.
Presso(bar)
6
Consumo(kWh)
Vlvula de Alvio
PID/Fuzzy
0.368
0.282
Economia %
23.37
74
sempre fica ajustado para um ponto de operao, o que no ocorre nas estratgias de controle
convencionais, onde o controle ajustado para uma faixa de operao. A figura 4.20 mostra a
resposta do compressor trabalhando com o controle feito pela vlvula de alvio.
Presso(bar)
7.8
7.6
7.4
7.2
7.0
6.8
0
200
400
600
Tempo(seg)
Figura 4.20 Operao do compressor com o controle feito pela vlvula de alvio.
4.4 CONCLUSES
75
CAPTULO 5
CONCLUSES E PROPOSTAS DE TRABALHOS
FUTUROS
5.1 CONCLUSES
77
78
REFERNCIAS BIBLIOGRFICAS
ABNT - NBR 10131 -1987 - Bombas hidrulicas de fluxo.
ALMEIDA, O. M., W. C. AMARAL, (1991), Mtodo Frequencial para Auto-ajuste de
Controladores PID: Implementao e Anlise, VIII CBA, pp. 45-50.
ALMEIDA O. M. e COELHO A. A.R. (2002). A Fuzzy Logic Method for Autotuning a PID
Controller: SISO And MIMO Systems, IFAC - 15th Triennial World Congress,
Barcelona, Spain.
ALMEIDA, A. T., FERREIRA, F. J. T. E. e BOTH, D.(2005). Technical and Economical
Considerations in the Application of Variable-Speed Drives With Electric Motor
Systems. IEE Proc.-Electr. Power Appl, Vol 41, No. 1 January/February 2005. pp. 188199.
ALMEIDA, O, M (2002). Controle PID Auto-ajustvel Inteligente e Preditivo, Tese de
Doutorado. 2002. Universidade Federal de Santa Catarina, UFSC, Brasil.
ALMEIDA, O. M. ; LIMA, S. E. U.; REIS, L. L. N. e BEZERRA, L. D. S (2004). A MIMO
Fuzzy Logic Autotuning PID Controller: Method and Application. In: 9th Online World
Conference
on
Soft
Computing
in
Industrial
Applications,
2004,
Beijing/Australia/Oxford/New M. Anais do 9th Online World Conference on Soft
Computing in Industrial Applications, 2004.
ALMEIDA, O. M. e COELHO, A. A. R. (1999), Controladores PID Auto-Ajustavel e
Nebulosos: Aspectos de Projeto, Sintonia e Aplicao Prtica, 4o SBAI Simpsio
Brasileiro de Automao Inteligente, pp. 675-680, So Paulo, SP.
ASHRAE HVAC (2000). Systems & Equipment Handbook, 2000.
STRM, K. J. e HGGLUND T. (1995). PID Controllers: Theory, Design E Tuning.
Instrument Society of America.
STRM, K. J. e HGGLUND T. (1988), Automatic Tuning of PID Controllers, Instrument
Society of America.
STRM, K. e HAGGLUND, T. (1984), Automatic Tuning of Simple Regulators with
Specifications on Phase and Amplitude Margins, Automatica Vol.20, N. 5, pp-645-651.
STRM, K. J. e WITENARK, B. (1995), Adaptive Control, Adison-Wesley Publishing
Company,
STRM, K. J., e WITTENMARK, B. , (1990), Computer Controlled Systems; Theory and
Design, Prentice-Hall International.
BARTOS, F. J. (1997). Artificial Intelligence: Smart Thinking for Complex Control, Control
Engineering, July, pp. 44-52
REFERNCIAS BIBLIOGRFICAS
80
REFERNCIAS BIBLIOGRFICAS
81
REFERNCIAS BIBLIOGRFICAS
82
LEE, C. C., (1995b), Fuzzy Logic in Control Systems: Fuzzy Logic Controller Part II, IEEE
Trans. Systems Man Cybernetics, 20(2): pp 404-418, March/April.
LI, W., ESKINAT, E. e LUIBEN, W. L.,(1991), An Improved Autotune Identification
Method, Ind. Eng. Chem. Process Des. Dev., 30, pp. 1530-1541.
LUNDH, M. e STRM, K. J., (1994), Automatic Initialization of a Robust Self-tuning
Controller, Automatica, 30, pp. 1649-1662.
LUYBEN, W. L., (1997), Derivation of Transfer Function for Highly Non-Linear Destillation
Columns, Ind. Eng. Chem. Process Des. Dev. 26, pp 2490-2495.
MACINTYRE, A. J. (1990), Ventilao Industrial e controle de poluio. Ed. LTC, Rio de
Janeiro,1990, 2a. ed.
MANDANI, E. H. e ASSILIAN, S., (1975), Na Experiment in Linguistic Synthesis with a
Fuzzy Logic Controller, Int. J. Man Machine Studies 7(1): pp 1-13.
MANDANI, E. H.,(1974), Applications of Fuzzy Algorithms for Control of Simple Dynamic
Plant, Proc. IEE 121(12): pp 1585-1588.
MCKERVEY, G. W. e PERRY, B (1993). Fan Applications in the Cement Industry.
Cement Industry Technical Conference, 1993. Record of Conference Papers., 35th
IEEE. 23-27 May 1993 pp.467 476.
MCMILLAN G, K.(1994).; Tuning and Control Loop Performance; Instruments Society of
American, 1994
MESQUITA, A.L.S., GUIMARAES, F. A. e NEFUSSI, N (1988). Engenharia de ventilao
industrial. CETESB, So Paulo, 1988.
MINISTRIO DAS MINAS E ENERGIA. BALANO DE ENERGIA TIL (BEU). Braslia,
2005 Disponvel: www.mme.gov.br, 2005.
MINISTRIO DAS MINAS E ENERGIA. BALANO ENERGTICO NACIONAL (BEN).
Braslia, 2005. Disponvel: www.mme.gov.br Acessado em 06 de janeiro de 2006.
MOREIRA, A. B. (2006). Anlise Da Operao De Sistemas De Ventilao Industrial
Visando Eficincia Energtica. Dissertao de Mestrado. 2006
NASCU, I.; DE KEYSER, R.; FOLEA, S. e BUZDUGAN, T. (2006). Development and
Evaluation of a PID Auto-Tuning Controller Automation, Quality and Testing,
Robotics, 2006 IEEE International Conference on Volume 1, May 2006 pp.122 127
OLIVER, J. A., MCCLUSKEY, R.K., WEISS, H. W. e SAMOTYJ M. J.
(1992)...Adjustable-speed drive retrofit for Ormond beach FD fans. IEE Proc.Electric. Power Appl. Vol 7, No. 3 September 1992. pp. 580-588.
OZDEMIR, E. (2003). Energy conservation opportunities with a variable speed controller in
aboiler house. Elsevier. November 2003 pp. 981-993.
REFERNCIAS BIBLIOGRFICAS
83
PERNG J. W ;WU B.; CHIN, H. e LEE, T.T (2005);Limit cycle analysis of uncertain fuzzy
vehicle control systems Networking, Sensing and Control, 2005. Proceedings. 2005
IEEE 19-22 March 2005 pp.626 631
RODRIGUES, P. S. B. (1991). Compressores industriais. Rio de Janeiro: Didatica e
Cientifica, 1991. 515p. ISBN 8571900299
SANTOS, V. A., PERRONE, F. P. D., FERREIRA, A. C., OLIVEIRA, L. H., SOARES, G.
A., MOTTA, R. B., MOYA, H. C. e PIFFER R.(2005) Otimizao de Sistemas
Motrizes Industriais. VI SBQEE p 727-732, 21 a 24 de agosto de 2005.
SAVOLAINEN, A. (2004). Hacia un futuro major Revista ABB, March 2004 pp.34-38.
SCHEI, T. S. (1994), Automatic Tuning of PID Controllers Based on Transfer Function
Estimation, Automatica, vol 30, N. 12, pp 1983-1989.
SCHMIDLIN, C. R. (2006). Operao Do Conjunto Bomba Centrfuga, Motor De Induo
Trifsico E Inversor De Freqncia Visando A Eficincia No Uso Da Energia Eltrica.
Dissertao de Mestrado. 2006
SHEN, J. H., WU, J. S. e YU, C. C., (1991), Use of Based-relay Feedback for System
Identification, AICHE J. 42, pp. 1174-1180.
SKOCZOWSKI, S.; DOMEK, S.; PIETRUSEWICZ, K. e BROEL-PLATER, B. (2005). A
method for improving the robustness of PID control.; Industrial Electronics, IEEE
Transactions on Volume 52, Issue 6, Dec. 2005 pp. 1669 1676.
TAO, C. W. e TAUR, J. S.(2005) Robust Fuzzy Control for a Plant with Fuzzy Linear
Model.IEEE Transactions On Fuzzy Systems, Vol. 13, No. 1, February 2005 pp 30-41.
VIANA, C. N. A.(2002), Manual do Programa de Eficientizao Industrial - Mdulo:
Ventiladores e Exaustores. ELETROBRS / PROCEL, Rio de Janeiro, 2002.
WANG, L. e CLUET, W. R., (1996), Use of PRESS residual in dynamic system
identification, Automatica, 32, pp. 181-784.
WANG, Q. G., HANG, C. C. e BI, Q., (1999a), A technique for frequency response
identification relay feedback, IEEE Transaction on Control Systems Technology, 7(1),
pp. 122 128.
WANG, Q. -G., HANG, C. C. e ZOU B., (1997a). Process Frequency Response Estimation
from Rely Feedback, Control Engineering Practice, 5, pp. 1293-1302.
WANG, Q. G., HANG, C. C. e ZOU, B., (1997b)., Low-order modeling for relay feedback,
Ind. Eng. Chem. Res., 36 pp. 375-386.
YANG, S M (1998). A Constant Air Flow Rate Control of Blower for Residential
Applications. IEEE Transactions On Industry Applications, Vol. 34, No. 2, March/April
1998.
REFERNCIAS BIBLIOGRFICAS
84
APNDICE A
CLASSIFICAO DOS VENTILADORES
At 1,97 kPa.
1,97 kPa a 7,85 kPa.
7,85 kPa 24,52 kPa
24,52 kPa a 98,07 kPa.
86
87
sobre a superfcie de revoluo cnica, cuja geratriz uma linha curva (MACINTYRE, 1990).
Na Figura A.3 ilustram-se as modalidades construtivas dos rotores dos ventiladores.
O rotor de simples suco ou unilateral tem somente uma entrada para o fluido,
enquanto que o de dupla suco ou entrada bilateral (MACINTYRE, 1990), tambm
denominado de rotor gmeo, apresenta duas entradas e opera com o dobro da vazo. As
Figuras A.5 (a) e (b) mostram os rotores de simples e dupla suco, respectivamente.
88
Figura A.5 -Rotores centrfugos de (a) simples e (b) dupla suco. (MOREIRA, 2006)
O rotor simples estgio, com um rotor apenas, o caso mais comum. De duplo
estgio, com dois rotores montados num mesmo eixo. O ar entra e passa pela caixa do
primeiro estgio, logo em seguida penetra na caixa do segundo estgio com a energia
proporcionada pelo primeiro rotor e recebe a energia do segundo rotor, que se adiciona ao
primeiro. Obtm-se assim, presses elevadas da ordem de 29.42 a 39.23 kPa com a utilizao
de 3, 4, 5 ou mais estgios (MACINTYRE, 1990).
APLICAES E CARACTERSTICAS
89
(MESQUITA et al, 1988). Possui eficincia baixa, tpica de 65% a 72% (MCKERVEY &
PERRY, 1993) e apresenta durante seu funcionamento a presena de rudo audvel. A Figura
A.6 (a) um esquema do corte radial de um ventilador centrfugo de rotor radial. A Figura
A.6 (b) mostra a sua curva caracterstica juntamente com as curvas de potncia e eficincia.
Note que a curva caracterstica bem comportada, que a potncia deste rotor
aumenta com a vazo de forma diretamente proporcional, e que sua eficincia mxima ocorre
para valores relativamente baixos, menores 50% da vazo mxima (FRANA, 1999). Assim,
para este tipo de ventilador, o motor pode ficar sobrecarregado, quando as condies de
funcionamento se aproximam da vazo mxima tambm conhecida como descarga livre.
Desenvolvem presses razoavelmente elevadas (at 4,91 kPa), e operam em altas
temperaturas.
Figura A.6 - (a) Forma construtiva e (b) curva caracterstica de ventilador centrfugo de rotor de aletas retas.
FONTE: (FRANA, 1999)
90
mximo, tambm mais compacto e pode ser usado em locais onde h limitao de espao
(MCKERVEY & PERRY, 1993). So os ventiladores mais aplicados em sistemas de
condicionamento de ar.
Uma de suas particularidades sua curva caracterstica, mostrada na Figura
A.7(b). Uma particularidade o ramo instvel na curva Presso e vazo, na faixa das baixas
vazes (FRANA, 1999). O ramo instvel quando a curva presso versus vazo apresenta
um ramo ascendente e descendente, representado pela regio a-b (ASHRAE HVAC, 2000) na
Figura A.7 (b).
A potncia cresce constantemente com o aumento da vazo, o que requer
ateno para a determinao do ponto de operao do sistema motoventilador e na seleo do
motor de acionamento, este pode danificar-se caso a vazo resultante seja muito maior que a
projetada (FRANA, 1999). Pode ser construdo com muitas ps o que permite operar vazes
de ar maiores, com baixa rotao, tendo como conseqncia baixo rudo. Por este motivo so
utilizados em instalaes de ar condicionado (VIANA, 2002).
Figura A.7 - (a) Forma construtiva e (b) curva caracterstica de ventilador centrfugo de rotor com aletas
curvadas para frente. FONTE: (FRANA, 1999)
91
92
Figura A.9 - (a) Forma construtiva e (b) curva caracterstica de ventilador centrfugo de rotor com aletas
curvadas para trs. FONTE: (FRANA, 1999)
Os ventiladores axiais por sua vez se classificam em: axial propulsor, tubo
axial e axial com aeroflios. O axial propulsor o mais barato para mover grandes volumes
de ar a baixas presses. utilizado freqentemente para ventilao ambiente, e dificilmente
para ventilao local exaustora (MESQUITA & GUIMARAES, 1988) .
O tubo-axial um propulsor com ps mais espessas e mais largas, fica
localizado dentro de um duto, permitindo assim sua direta conexo em dutos, mostrado na
Figura A.10 (a). constitudo de uma carcaa tubular que o envolve um rotor axial. O motor
pode ser diretamente acoplado ao rotor, estando exposto ao escoamento do fluido, ou
colocado sobre a carcaa, acionando o rotor atravs de polias e correia. aplicado em
sistemas com grande vazo e baixa presso. Como mostra a Figura A.10 (b), sua curva
caracterstica apresenta uma regio de instabilidade entre os pontos a e b, e a potncia
mxima quando a vazo nula (FRANA, 1999) .
93
Figura A.10 - (a) Forma construtiva e (b) curva caracterstica de ventilador tubo-axial.FONTE: (FRANA,
1999)
O axial com aeroflios possui uma calota central, que possibilita sua utilizao
a presses mais elevadas. utilizado com freqncia em ventilao de minas subterrneas e,
em algumas vezes, em indstrias. Para esse tipo de ventilador, a forma das ps importante,
no devendo ser utilizados onde haja risco de eroso e corroso (MOREIRA, 2006).
APNDICE B
COMPRESSORES
CLASSIFICAO DOS COMPRESSORES QUANTO S APLICAES
APNDICE B COMPRESSORES
95
96
APNDICE B COMPRESSORES
determinado filete, o ar nele contido fica encerrado entre o rotor e as paredes da carcaa. A
rotao faz ento com que o ponto de engrenamento v se deslocando para a frente, reduzindo
o espao disponvel para o ar e provocando a sua compresso. Finalmente, alcanada a
abertura de descarga, e o ar liberado. (RODRIGUES, 1991)
A relao de compresso interna do compressor de parafusos depende da
geometria da mquina e da natureza do fluido, podendo ser diferente da relao entre as
presses do sistema.
projeto
original,
tornando
mquina
cada
vez
mais
competitiva.
APNDICE B COMPRESSORES
97
APNDICE B COMPRESSORES
98
para as mais variadas espcies de gases, inclusive contendo lquido ou partculas slidas em
suspenso.
a) Vazo de operao
A vazo volumtrica aspirada por um compressor de parafusos pode ser
estimada atravs da relao (RODRIGUES, 1991):
V1 =v.C.D2.N.L.
(B.1)
Onde:
V1 = Vazo volumtrica aspirada,
v = Rendimento volumtrico,
C = Constante relativa a geometria do compressor, da ordem de 0,5,
D = Dimetro do rotor macho,
N = Rotao do rotor macho,
L = comprimento dos rotores.
O rendimento volumtrico visa compensar as perdas decorrentes da
recirculao por entre as folgas do rotor, e depende principalmente da magnitude dessas
folgas, da velocidade de rotao, da relao de compresso e do tipo de gs. As correlaes
analticas para o clculo desse coeficiente so muito complicadas ou no fornecem a preciso
satisfatria, e por isso devemos nos reportar ao fabricante da mquina para obter informaes
a esse respeito. Os valores tpicos para compressores industriais se encontram na faixa de 70 a
90%.
b) Potncia de compresso
O clculo da pertencia consumida por um compressor de parafusos deve ser
conduzido a partir da tradicional formula (RODRIGUES, 1991):
APNDICE B COMPRESSORES
m .wk
Wc =
k .mec
99
(B.2)
Onde:
Wc = Potncia consumida
T2 = T1 +
.(T2 S T1 )
k
(B.3)
100
APNDICE B COMPRESSORES
Onde:
T2 = Temperatura do gs descarregado
T1 = Temperatura de suco
T2S = Temperatura terica adiabtica de descarga
k = Rendimento adiabtico
= Coeficiente emprico
O coeficiente est associado remoo de calor efetuada durante o processo
de compresso do gs. Nos compressores no-lubrificados essa remoo de calor pequena,
sendo devida ao sistema de arrefecimento da mquina, de modo que se situa em torno de
0,9. Quando o compressor abundantemente lubrificado, esse coeficiente se mostra bastante
reduzido devido ao resfriamento efetuado pelo leo (RODRIGUES, 1991). Valores de em
torno de 0,1 ou 0,2 tem sido observados, mas nesse caso h forte dependncia da vazo de
circulao do lubrificante.