EPG7 User Manual

User Manual
Dear Clients,

Thank you very much for choosing an ELVAC branded product.


The product, which also includes this User Manual, is produced by ELVAC a.s., whose processes of
development, production and services for industrial electronic systems are certified according to international
Quality Control Standard ISO 9001. During production our aim was to ensure the maximum possible quality in
order for you to be fully satisfied with our product. Therefore, the product has passed functional and loading tests,
with a burn-in period of a minimum of 48 hours and was carefully packed after a thorough inspection.
Despite the minimising of any potential problems, it can sometimes occur that some computer systems do not
fully comply with your expectations. In this case, please contact our company where we will try to remove any
defects as soon as possible. Any ideas, advice and recommendations are welcome as an opportunity for us to
improve our work and to increase your satisfaction.
This manual is designed with respect to the fact that you, as users are obviously fully aware of industrial system
servicing and, therefore, it is not necessary to explain the fundamentals. Therefore, the main objective of this
manual is to inform you of the product features and to advise you of some of the risks that can occur during
incorrect use. We recommend you to read it in detail. Finally, and also importantly, we would like to assure you of
the top quality properties and high reliability of the product. Therefore, we have included test reports from the
production process and copies of certificates which were issued for our company as an expression of the quality of
the process for the development, production and service of our products.
We trust that our product will reliably serve you for a long time.

Copyright
Modification or provision of the content to a third party in any form and without the expressive consent of ELVAC
a.s. is forbidden.
COPYRIGHT ELVAC a.s. 2007-2013

-1-

Rev 4; 4/13

User Manual

CONTENTS
1

UNPACKING ........................................................................................................................ 4

SAFETY INSTRUCTIONS .................................................................................................... 4

BRIEF DESCRIPTION.......................................................................................................... 4

3.1

Supply of EPG7 .............................................................................................................................................. 5

3.2

Charger for accumulators ............................................................................................................................. 5

3.3

Drawing of dimensions ................................................................................................................................. 7

3.4

Current outputs .............................................................................................................................................. 8

3.5

Voltage outputs .............................................................................................................................................. 9

3.6

Digital inputs ................................................................................................................................................10

3.7

Digital outputs ..............................................................................................................................................12

3.8

Communication interface ............................................................................................................................12

3.9

Galvanic separation in the EPG7 ...............................................................................................................13

3.10

STATUS LED indication ..............................................................................................................................14

FIRMWARE ........................................................................................................................ 15

4.1

Firmware version .........................................................................................................................................15

4.2

Upgrade ........................................................................................................................................................15

CONTROL OF DEVICE ...................................................................................................... 16

5.1

Switching ON and OFF ................................................................................................................................16

5.2

Control ..........................................................................................................................................................16

MENU ................................................................................................................................. 17

6.1
Analogue outputs ........................................................................................................................................17
6.1.1 Current source ...........................................................................................................................................18
6.1.2 Voltage source...........................................................................................................................................18
-2-

Rev 4; 4/13

User Manual
6.1.3
6.1.4
6.1.5

Power source.............................................................................................................................................19
Hand step ..................................................................................................................................................20
Reports ......................................................................................................................................................20

6.2
Digital outputs/inputs ..................................................................................................................................20
6.2.1 Digital outputs ............................................................................................................................................21
6.2.2 Digital inputs ..............................................................................................................................................21
6.3
Tests..............................................................................................................................................................21
6.3.1 Records .....................................................................................................................................................21
6.3.2 IFC tester ...................................................................................................................................................21
6.3.2.1
Ramp ................................................................................................................................................21
6.3.2.2
Step...................................................................................................................................................22
6.3.3 Protection tester ........................................................................................................................................23
6.3.3.1
Reclosing ..........................................................................................................................................23
6.3.3.2
Frequency step .................................................................................................................................24
6.3.3.3
Voltage step ......................................................................................................................................24
6.3.3.4
Current step ......................................................................................................................................25
6.3.3.5
Frequency ramp................................................................................................................................26
6.3.3.6
Potential-free pause ..........................................................................................................................26
6.3.3.7
DI/DO simulator ................................................................................................................................27
6.3.4 Setting DI/DO ............................................................................................................................................27
6.4
Setting ...........................................................................................................................................................28
6.4.1 Transformer ...............................................................................................................................................28
6.4.2 Calibration .................................................................................................................................................29
6.5
Information ...................................................................................................................................................30
6.5.1 Battery .......................................................................................................................................................30
6.5.2 Firmware....................................................................................................................................................30
6.6

Shutdown......................................................................................................................................................30

HOW TO PROCEED IN THE CASE OF PROBLEMS........................................................ 31

-3-

Rev 4; 4/13

User Manual

1 Unpacking
If you are reading this manual then you have evidently begun to unpack the transport container. Continue with
care to prevent any damage to the treated surface or damage to parts which are sensitive to shocks and vibrations.
After unpacking, check that the delivery is complete. The transport container is produced in such a manner that
it ideally protects the product during transport from production to yourself. Therefore, we recommend using it during
future transport of the device. The producer of EPG7 also supplies a practical transport box, into which the
separate generator and accessories (supply adapter, cables, connectors, ) can be placed.

2 Safety instructions
Before first connecting the EPG7, please pay close attention to the following notifications:
The multifunctional generator is equipment supplied by DC voltage from internal NiMH accumulators or from the
external 9V DC source of voltage. Although we pay close attention to safety and each product is tested in this area,
you should comply with similar principles as in the case of other electrical appliances.
The device can be connected to an electrical circuit where the voltage corresponds to the label type. Only use
recommended NiMH accumulators in the system.
Ensure that all power cables are placed in a manner that prevents any damage. Do not place any items on it
and do not locate it in an area where it can be trod on.
Do not remove the protection covers if you are not authorized to do so. Do not intervene into the construction of
the device. During such activities there is a risk of injury from the electric current.
Do not insert any items into the unit and ensure that no liquids get into it. If this happens, immediately
disconnect the unit and call a service technician.

3 Brief description
The EPG7 is a multi-functional, multi-channel, battery supplied generator for AC or DC current or voltage (if the
voltage output card is inserted). The device is primarily designed for testing the protection functions of units in the
RTU7.4, RTU7M and IZP M3Z series. In addition, it can be used as a multi-channel generator of DC currents
during testing and revival in industry.
Digital inputs and outputs are available (part of the voltage output card). Using these, it is possible to simulate
during the protective functions, the status of the power element and to monitor the response of the protection on
the failure record.
The device has a USB2.0 communication interface; the respective SW application for OS Windows is available.

-4-

Rev 4; 4/13

User Manual
Basic technical specification for the EPG7 generator:
Display
Control
Supply voltage
Input protection
Backup accumulator
Charging current for the accumulator
Accumulator protection
Dimensions
Weight
Temperature range
Storage temperature
Ambient relative moisture
Coverage

LCD 16x4
Rotary knob with integrated button
9VDC
2,5A polyswitch
4xNiMH AA, capacity 2100mAh max.
1.5A
2,5A polyswitch
196 (207) x 100 x 40 mm
1kg
0C to +50C
-20C to +75C
30% - 95%RH non-condensing
IP20

Further technical specifications are mentioned in the following chapters.

3.1

Supply of EPG7

For the supply of EPG7, 4 NiMH accumulators are used, size AA with a capacity of up to 2100mAh. The
recommended model is Sanyo Eneloop (capacity 2000mAh). Using these accumulators, then it is possible to work
for approximately two hours. This applies for the generation of 45mA AC current on three analogue outputs up to a
load of 20 .
In addition, the device can be supplied with an external supply adapter with a stabilized output voltage of 9V
DC. The supplied output must be at least 20W. The external adapter is connected to the EPG7 by the round
supply connector with a diameter of 5.5/2.1mm. The polarity is shown in the following diagram:

The recommended type of external adapter is GS40A09-P1J (9V / 4,45A DC). The supply adapter is not
included in the delivery; the EPG7 is delivered separately. The supply part of the delivery is galvanically separated
from the remaining part. The insulation between the pins of the connecting connector and the pins of analogue
inputs for currents and voltage is 1500V DC over one minute.

3.2

Charger for accumulators

The EPG7 is fitted with an integrated charger for accumulators. The function of the charger is indicated by 4
LED diodes on the front panel (CHARGER section). The signalling of individual statuses are shown in the following
table:
RDY

CHG

TOC

FLT

Does not
shine

Does not
shine
Does not
shine

Does not
shine
Does not
shine
Does not
shine

Does not
shine
Does not
shine
Does not
shine
Does not
shine

Shines
Shines

Shines

Shines

Shines

Shines

Shines

Shines or
does not
shine

Shines or
does not
shine

Shines

Status of the charger


Disconnected
Ready for charging or automatic re-charging
Pre-charging or quick charging
Charging of 1/10 of the current at the end of the charging cycle
The exceeding of thermal limits (pause in the charging as long as
the return to normal limits)

-5-

Rev 4; 4/13

User Manual
Does not
shine

Does not
shine

Does not
shine

Shines

Fault

Description of internal charger statuses:


Disconnected:
The external supply adapter is not connected to the EPG7. The device is only supplied from the accumulators.
Ready for charging or automatic re-charging:
The charger is in this status after successful termination of the previous charging cycle
Pre-charging or quick charging:
If the voltage for one cell in the accumulator is less than 900mV, the charger is switched into the pre-charging
status. During the stated period, the accumulator is charged to 1/5 of the nominal charging current. Then, if the
temperature of the accumulator is within the range 5C to 45C, the charger is transferred to the quick charging
status. The accumulator is then charged at the full value of the charging current. The quick charging is terminated
on the basis of the fulfilment of the criterion V/t or T/t.
Charging of 1/10 of the current at the end of the charging cycle:
If the quick charging is terminated on the basis of the fulfilment of the criterion T/t (the accumulator is charged
to approximately 95% of the capacity) the charger starts to charge the accumulator by 1/10 of the nominal charging
current during the stated period. After expiration of this period, there is termination of the charging cycle. If the fast
charging is terminated on the basis of the criterion V/t the charging of the accumulator is immediately terminated.
Exceeding the thermal limits:
If the charger for generator EPG7 starts to indicate this status, then during the charging the permitted
temperature of the accumulator was exceeded. The charger indicates the most recent status although the charging
is interrupted. As soon as the temperature of the accumulator decreases below the stated limit (45C), the charging
is restored.
Fault:
If the charger is in this status, it means that the accumulator was not charged within the stated time. Another
reason can be if the charging is started when the temperature of the accumulator is outside the stated limits of 5C
to 45C. If the generator is switched into the status where the FILT LED shines and the other LED on the charger
(RDY, CHG, TOC) are OFF and the temperature of the accumulators does not exceed the above mentioned limit,
this is not a fault with the device. In this case, the function of the device charger can be restored by disconnecting
and connecting the supply adapter.
The average time for charging an internal accumulator with a capacity of 2000mAh is approximately 2 hours.

-6-

Rev 4; 4/13

User Manual

Drawing of dimensions
I G

I G

I G

> I1 Enable
I1 RMS
I1 Freq
I1 Phase

1 2 3 4 C 0 12 24

Off
20.0 mA
50.0 Hz
0

BAT AO FLT

F1

DO
2

196

READY CHRG

TOC

TX

FAULT

207

DI
PWR

RX

ETEST - THREE PHASE SOURCE AND TESTER

9V DC

ON

USB

40

3.3

100

-7-

Rev 4; 4/13

User Manual

3.4

Current outputs

The EPG7 current outputs can generate AC or DC current waveforms in three phases. As the proposed SW
modules, the currents for the device can be generated as follows:
AC or DC. For AC waveforms, it is possible to set only the identical amplitude for all 3 phases from 0 to 45mA
with the step 0.1mA. Between phases, constant phase shifts of 120 are set and the constant frequency of the
generated current of 50Hz is set. For DC waveforms, the generated current amplitude can be set within the range
+/-60mA DC with the step 0.1mA.
AC or DC function generator. For individual outputs, the amplitude, the frequency and phase shift of the
generated current can be set separately. The frequency can be set within the range 40-350Hz with the step 1Hz.
The phase shift within the range 0-360 with step 1.
Generation of the waveform of records from various data formats.
Generation of the waveform according to the default programs for testing the protection. In this case, the
generator cooperates with the setting DO and reading DI.
Current outputs are fitted with protection against damage during the disconnection of the loading loop and also
use the loading impedance measurement. In the case of exceeding the value of the loading impedance for the
stated amplitude of the generated current, the device will start to indicate this status by means of LED AOF on the
front side of the device (STATUS section). The current and voltage outputs (if the voltage card is inserted) are not
galvanically separated (they work towards a common ground). Analogue outputs are galvanically separated from
the digital inputs and outputs on generator EPG7, from the USB communication interface and from the supply
connector for connection of the external adapter.
The technical parameters of current outputs are summarized in the following table:
Number of outputs
Ranges of generated current
Precision of current generation
Loading impedance
Range of frequency of generated current
Setting of the phase shift for individual
outputs
Protection against disconnecting the
current loop
Signal processing
Connectors
Cross section of the conductor

3
45mA AC
60mA DC
0,1% of the range
Max. 100 @ 45mA AC
40-350Hz
0-360
Yes
Indication of exceeding the maximum
loading impedance LED AOF
16-bit D/A converter
3 x WAGO 734-102; span 3.5mm;
included in delivery
0,08-1,5mm2

Connection of connectors to EPG7 current outputs:


G

I
Pin
I
G

Description
Current output 1, 2 or 3
GND (these pins are internally
interconnected for all analogue
outputs)

-8-

Rev 4; 4/13

User Manual

3.5

Voltage outputs

The technical parameters of the voltage outputs are summarized in the following table:
Number of outputs
Ranges of generated voltage
Precision of voltage generation
Output current
Frequency range of generated voltage
Setting of the phase shift for individual
outputs
Protection against overloading
Signal processing
Connectors
Cross section of the conductor

3
7V AC
10V DC
0,1% of the range
Max. 30mA AC
40-350Hz
0-360
Yes
Indication of the connection, lower loading
impedance than permitted LED AOF
16-bit D/A converter
3 x WAGO 734-102; span 3.5mm;
included in delivery
0,08-1,5mm2

Connection of connectors for EPG7 voltage outputs:


G U
Pin
U
G

Description
Voltage output 1, 2 or 3
GND (these pins are internally
interconnected for all analogue
outputs)

-9-

Rev 4; 4/13

User Manual

3.6

Digital inputs

The EPG7 generator has four digital inputs. These inputs are used when testing protection when, for example,
the signal is supplied from the TRIP protection relay.
Inputs can be connected as active (excitation of the input by outside contact) or passive (excitation of input by
outside voltage). There are pins with galvanically separated signal voltage of 12V and 24V for the use of digital
inputs in the configuration as active inputs. The internal source of the signalling voltage must be connected from
the menu for the device before use. It is disconnected as default (energy saving when battery operated).
For indicating the excitation of individual inputs, a series of LED DI indication is used which is located on the
front side of the generator (DI/DO section).
The technical parameters of the digital inputs are stated in the following table:
Number of inputs
Signalling voltage
Configuration of
inputs
H level
L level
Input current
Insulating voltage
Connectors
Cross section of
the conductor

4 digital inputs
12V / 24V
Active (switching by
Passive (switching by external
dry contact)
voltage, both polarities)
ON
11-40V
OFF
0-8V
6,6mA max.
2-6,6mA; 3,3mA@12V
1,5kV DC during 1 minute
1 x WAGO 734-108; span 3.5mm; included in delivery
0,08-1,5mm2

The connection of the connector is shown in the following table:


24 12 0

Pin
1
2
3
4
C
0
12
24

Description
DI1
DI2
DI3
DI4
common pin for inputs DI1-DI4
source of signalling voltage (GND)
source of signalling voltage 12V
source of signalling voltage 24V

For the active connection of the digital inputs, the external connection of pins C and 0 is required:
24 12 0

If necessary, the 12 or 24V pin for the internal DC-DC converter for the device is used.
-10-

Rev 4; 4/13

User Manual
Connection of digital inputs as passive inputs:
24 12 0

2 1

If the digital inputs are operated as passive, the internal voltage source for the supply of external equipment can
be used. The maximum consumption from the converter on pins 12 or 24V is 125mA.

-11-

Rev 4; 4/13

User Manual

3.7

Digital outputs

If the EPG7 generator contains a digital output voltage card, the generator will have four DO1-DO4 digital
outputs for controlling external equipment. The digital outputs can be used when testing the protection. One option
is to use for simulating the status of the output element.
Switching on the individual outputs is indicated by four LED DO, which are visible on the front of the EPG7
(section DI/DO). The outputs are fitted with semiconductor switches (SSR only switching function) and the
parameters are shown in the following table:

Output
Insulating voltage
Loading of switches
Resistance in the switched on status
Connectors
Cross section of the conductor

DO1-DO4
3750 Vrms over 1 minute
1,75A@35V AC, 2,5A@50V DC
0,1 max.
1 x WAGO 734-108; span 3.5mm; included in delivery
0,08-1,5mm2

The connection of the connector is shown in the following table:

G4 S4 G3 S3 G2 S2 G1 S1
Pin
GX
SX

3.8

Description
First pin of the switch X
Second pin of the switch X

Communication interface

The EPG7 generator is fitted with the galvanically separated communication interface USB 2.0. Communication
interface serves for:
- upgrading the device FW
- the active SW module
- saving the testing course into the device (if this function is supported within the FW licence purchased)
- control by the special SW application (if this function is supported within the FW licence purchased)
Operation on the communication line is indicated by 2 yellow LED RX and TX on the front side of the device
(section USB). The connecting USB cable is included with the device. The technical parameters of the
communication interface are shown in the following table:

Connector
Communication standard
Insulation

Mini USB B, 5 pins


USB 2.0
4 kV during 1 minute

-12-

Rev 4; 4/13

User Manual

3.9

Galvanic separation in the EPG7

The individual function blocks in the EPG7 generator are galvanically separated. The analogue current and
voltage output channels are insulated from the remaining equipment. The output analogue channels are not
insulated between them; all G pins are mutually interconnected.
The size of the insulation between individual functional blocks is shown in the technical specification tables in
previous chapters. Galvanic separations are indicated in the following diagram:

I G

I G

I G

3 x Iout
3 x Uout

1 2 3 4 C 0 12 24

4 x DI
4 x DO

Napjec
zdroj

Nabje

-13-

USB

Rev 4; 4/13

User Manual

3.10 STATUS LED indication


In the following table is a description of the function of the LED indication in the STATUS section on the front of
the device:

LED
RUN
BAT

AOF

F1

Status
Shines
Does not shine
Flashes at the
frequency 2 Hz
Does not shine
Shines
Does not shine
Flashes at the
frequency 2 Hz
Does not shine

Description
Activated generation of currents or voltage on analogue outputs
Disconnected generation of currents or voltage on analogue outputs
The voltage of the battery is < 4.6V, at the voltage < 4.55V disconnects
the device
Supplied from the adapter or the value of the voltage of batteries > 4.6V
Error in the current or the analogue output voltage, overloading of the
voltage output, high impedance on the pins of the current output,
disconnection of the current output.
Analogue outputs without the failure
Activated internal converter for the supply of digital inputs
Disconnected internal converter for the digital input supply

-14-

Rev 4; 4/13

User Manual

4 Firmware
The EPG7 software consists of two parts loader and firmware. The loader is the basic equipment for the
device and serves for loading and updating FW.
Depending on the type of licence, the firmware for the generator provides the user with further functions which
are not part of the basic version.

4.1

Firmware version

Basic
Generation of currents AC or DC. For AC courses, the fixed frequency 50Hz, phase shift 120 are set. The
user only changes the amplitude of the generated signal the same in all three phases. Option of DI/DO
control and reading.
Voltage generator
Generation of AC or DC currents and voltage. The functionality is the same as for the basic version.
Function generator
This enables to set separate amplitudes, frequencies and phase shifts on individual outputs.
Record player
Option of recording error records from protection (RTU, Comtrade).
IFC Tester
Automatic testing of failure current indicators.
Protection tester
Automatic testing of protection in RTU units.
DI datalogger
Record of changes to DI with time mark.
Individual modules can be combined according to the requirements of the specific user and to deactivate, it is
necessary to load into the device the respective licence applicable to the serial number of the device.

4.2

Upgrade

Similarly as in all RTU units from ELVAC a.s., the FW can be remotely upgraded. This requires special
software, such as EPGap or User Center. In the firmware upgrade regime, the generation of analogue inputs and
other functions for the device do not work. After upgrading the firmware, normal activity of EPG7 is restored.

-15-

Rev 4; 4/13

User Manual

5 Control of device
5.1

Switching ON and OFF

Before using, it is necessary to insert into the device the NiMH accumulators or to connect him to the external
voltage source using the connector which is on the side of the box (marked 9V DC). The device is activated by the
button on the side of the box (button ON). This button is built-in into the box to prevent the accidental activation of
the device and the consequent discharging of the accumulator. After activation, it is necessary to hold the button
(use suitable item) down until the text Loading .. or Nahravam .. is displayed.
For disconnecting the device, it is possible to use long pressing of the button on the control knob for the
respective items in the menu of the device. After selection and acknowledgement, the device is disconnected. If it is
supplied from an external adapter and accumulators are inserted, the function of the charger of the accumulators
remains permanently active.
When working with the generator, due to the energy saving in the accumulators, there is automatic
disconnection of the supply to the analogue part of the device. When the device is generating on at least one
output, the signal status is indicated by the lighting of the RUN LED (STATUS section). At the same time, in this
status, the analogue part of the device is supplied.

5.2

Control

All functions and settings for the EPG7 generator are displayed in the multi-level menu which is displayed on the
4-line LCD display. To move in this menu item, use the rotary control knob with the integrated button.
By turning the control knob it is possible to move through the menu or to set a specific item. By turning in the
clockwise direction, then you can move in the menu by one item down; in the opposite direction, by one position up.
When pressing the rotary control knob, there is the selection of the item in the menu (acknowledgement). If setting
the value, the fast-speed wheel function is activated and the value is changed depending on the speed of turning
(change by 1, 2, 4, 8, 16, 32, 64). For calibration, this change is significantly greater (1, 5, 20, 50, 250, 1000, 2500).
The approximate symbols in the menu are displayed in the table:
Symbol

Description of symbols
The actual positions in the menu (first column from the left)
Selected item for editing (first column from the left)
Indication of the channel for quick editing (second column
from the left)
Overloading of the channel (fifth column from the left)

The actual positions in the menu are marked by a simple arrow always located on the left on the display. If the
specific item is selected and it does not concern the sub-menu item, the symbol is changed to a double arrow. This
symbol informs users that that item can be changed by turning of the control knob. By re-pressing the control knob
button the set value is confirmed (saved) and the symbol is changed to a single arrow.
Further pressing of the control knob button (for 2s) is used for special purposes, such as the fast setting of
several items at once, e.g. setting the frequency of further channels for analogue outputs (if enabled by the
licence). With longer pressing, more channels can be selected and then group changed. In this case the line is
marked with a cross.

-16-

Rev 4; 4/13

User Manual

6 Menu
In the diagram, is the structure of the main menu. The respective item is selected by the rotary control knob.
Depending on the licence, not all items need to be visible. Return to the previous menu item is by selecting the item
Back.

6.1

Analogue outputs

The option is for manually setting the value on the analogue outputs The visible content again depends on the
licence. The first diagram shows the menu for the basic version of the generator with the licence for the voltage
card.

In the second diagram there is the expanded menu with the licence for the functional generator with the voltage
card.

-17-

Rev 4; 4/13

User Manual

6.1.1 Current source


Option for setting the current outputs on the EPG7 generator.
a) Basic version
The generator without the licence provides only the basic option for setting the current outputs. The selected
values are applied to all three current channels at the same time.
The channel is activated by the item Enable. The value on the right side of the line shows the actual status
set (connected - On, disconnected - Off).
The second line describes the type of generated signal and the value. AC AC harmonic signal with the
adjustable effective value with the range 0-45mA and the step 0.1mA, DC DC signal with the adjustable
amplitude with the range 60mA and the step 0,1mA. In the case of overloading the channel (too high loading),
an exclamation mark is displayed on the same line.
The type of signal generated is switched depending on the value of the frequency (Freq). For the basic
versions, the frequency is only restricted for the values 0 or 50Hz. At the time of switching the frequency, the
amplitude (effective value) of the signal is set to 0mA.
The Phase item is only informative and cannot be changed in the basic version. Phases between individual
channels are firmly set for 120 (I1 0, I2 120, I3 240).
b) Function generator
Compared with the basic version, this enables each current channel to be separately set. The display
always shows all three current channels and the common channel. The common channel serves for the uniform
setting of all current channels. If it is necessary to change only some channels, the line is marked by long
pressing of the control knob. For marked lines, a cross is displayed and during selection, only channels marked
with the cross are changed.
The channel is activated by the Enable item. The value on the right side of the line shows the actual status
set (connected - On, disconnected - Off).
The second line describes the type of generated signal and the set value. AC AC harmonic signal with the
adjustable effective value with the range 0-45mA and the step 0.1mA, DC DC signal with the adjustable
amplitude with the range 60mA and the step 0,1mA.
The type of signal generated is switched depending on the value of the frequency (Freq). The range of the
frequency is 0-350Hz. The usable frequency is only 0Hz a 40-350Hz with the step 1Hz. The frequency between
45Hz and 55Hz is adjustable with the step 0.1Hz. Upon switching the frequency (between 0 and 40Hz) the
amplitude (effective value) of the signal is set to 0mA.
The Phase is adjustable within the range 0-359 with the step 1 under the condition that all channels have
the same frequency. In the case of various frequencies, it is not possible to set the phase (the value of the
phase is filled for all channels by three dashes).
The Shift function enables to change the value on the output for the common channel. If in any channel this
function is disconnected, then any changes made to the common channel are not applied to it.
In the case of overloading the channel (too high loading), an exclamation mark is displayed on the line for
the overloaded channel.

6.1.2 Voltage source


This is the option for setting voltage outputs. The option is visible when the generator contains the licence for
the voltage card and the voltage card is inserted.
a) Basic version

-18-

Rev 4; 4/13

User Manual
The generator with the basic version with voltage card provides only the basic option for setting the voltage
outputs. Selected values are applied to all three voltage channels at the same time.
The channel is activated by the item Enable. The value on the right side of the line shows the actual status
set (connected - On, disconnected - Off).
The second line describes the type of generated signal and the value. AC AC harmonic signal with the
adjustable effective value with the range 0-7V and the step 0.01V; DC DC signal with the adjustable amplitude
with the range 10V and the step 0.01V. In the case of overloading the channel (too high loading), an
exclamation mark is displayed on the same line.
The type of signal generated is switched depending on the value of the frequency (Freq). For the basic
versions, the frequency is only restricted for values 0 or 50Hz. At the time of switching the frequency, the
amplitude (effective value) of the signal is set to 0V.
The Phase item is only informative and cannot be changed in the basic version. Phases between individual
channels are firmly set for 120 (U1 0, U2 120, U3 240).
b) Function generator
Compared to the basic version with the voltage card, it enables a separate setting for each voltage channel.
The display always shows all three voltage channels and the common channel. The common channel serves for
the uniform setting of all voltage channels. If it is necessary to change only some channels, the line is marked
by long pressing of the control knob. For marked lines, the cross is displayed and during the selection, only
channels marked with the cross are changed.
The channel is activated by the Enable item. The value on the right side of the line shows the actual status
set (connected - On, disconnected - Off).
The second line describes the type of generated signal and the set value. AC AC harmonic signal with the
adjustable effective value with the range 0-7V and the step 0.01V, DC DC signal with the adjustable amplitude
with the range 10V and the step 0.01V.
The type of signal generated is switched depending on the value of the frequency (Freq). The range of the
frequency is 0-350Hz. The usable frequency is only 0Hz a 40-350Hz with the step 1Hz. The frequency between
45Hz and 55Hz is adjustable with the step 0.1Hz. Upon switching the frequency (between 0 and 40Hz) the
amplitude (effective value) of the signal is set to 0V.
The Phase is adjustable within the range 0-359 with the step 1 under the condition that all channels have
the same frequency. In the case of various frequencies, it is not possible to set the phase (the value of the
phase is filled for all channels by three dashes).
The Shift function enables to change the value on the output for the common channel. If in any channel this
function is disconnected, then any changes made to the common channel are not applied to it.
In the case of overloading the channel (too small loading), an exclamation mark is displayed on the line for
the overloaded channel.

6.1.3 Power source


For the generation of the output through the current and voltage channels. It is necessary to have the licence for
the voltage board and the functional generator.

The values of active (P) and reactive (Q) output are automatically evaluated on the basis of the effective voltage
and current values on individual channels. The outputs are measured by a minimum step or slightly after long
pressing of the control knob button. In the case that the electrical power network is not symmetric, then before the
-19-

Rev 4; 4/13

User Manual
change of the value a warning message is displayed which, after the acknowledgement, sets the network into the
default status (frequency 50Hz, phase between channels 120). The value of current I and voltage U is calculated
as the average value on all channels. If the values are not the same on all channels, a question mark is displayed
on the stated line. The type of voltage generated (Type) can be switched between the line-to-earth (L-E) and the
line-to-line (L-L). The angle expresses the phase shift between the current and the voltage.

6.1.4 Hand step


Hand step is the alternative to steps for tests for protection or IFC.

The hand step enables to generate on any channel (Ix, I1, I2, I3, Ux, U1, U2, U3) the step for the effective
value, frequency or phase. To select these values, the item Value is used. In the menu, the original value (Origin),
is displayed, as well as the new value (New). The original value is set in the analogues output menu (Analog
outputs) and serves only for reading. The new value (New) can be set manually.
The range of values is the same as in the option for analogue outputs. The effective value for the current
channels is within the range 0-45mA with the step 0.1mA. The effective value for the voltage channels is within the
range 0-7V with the step 0.01V. The frequencies of all channels is within the range 40-350Hz with the step 1Hz and
within the range 45-55Hz with the step 0.1Hz. The phases for all channels can be set within the range 0-359 with
the step 1.
The hand step only switches between the original and the new value. It does not influence the activation of the
channel. The step is switched by pressing the control knob on the item State. This line shows the actual status and
the channel with which it works (for example I2).

6.1.5 Reports
The error statuses in the voltage and current channels are displayed here. If the generation on the current
channel is activated and the channel is not loaded or the loading resistance is too high, a warning text is displayed
in the menu (e.g. overloading Overload I1). If during the generation of the signal on the voltage channel, too low
loading resistance is connected (the value of the output signal differs compared with the stated value) a warning
text is displayed in the menu (e.g. overloading Overload U2).
Another reason for the display of the warning message can be the incorrect calibration of the channel.

6.2

Digital outputs/inputs

The menu for digital inputs and outputs is displayed in the diagram. Uaux for DI activates the converter for the
excitation of digital inputs. The activation of Uaux is indicated by the flashing yellow LED.

-20-

Rev 4; 4/13

User Manual

6.2.1 Digital outputs


Available in the licence voltage card. On the display are four digital outputs and their actual set value
(connected - On, disconnected - Off). The value is changed by pressing the control knob button on the respective
line with the digital output.

6.2.2 Digital inputs


This option serves for testing the reading of digital inputs DI1 to DI4 (connected - On, disconnected - Off).

6.3

Tests

The content of this option relates to the licence Records, IFC tester and Protection tester. The diagram under
the text displays the tests menu and setting.

6.3.1 Records
The menu for working with records stored in external flash memory of the EPG7 generator.

For recording records, EPGap user software is required. Items are sorted alphabetically. The records can be
played, deleted or view their details. The memory capacity is 2MB with a maximum of 100 files.

6.3.2 IFC tester


Availably in the licence IFC tester. The option of indictor of fault currents (IFC) contains testing signals
designated only for current channels - Ramp and Step.

6.3.2.1 Ramp

-21-

Rev 4; 4/13

User Manual

The ramp serves for testing the protection of RTU units. EPG7 generates on a selected current channel (I1, I2,
I3) or all channels (Ix) a harmonic signal with the variable value with the fixed frequency of 50Hz. If the affection of
the protection is selected (menu Settings DI/DO) the time of connection and disconnection of the protection and
values of currents is measured at which the protection responded.
The channel is selected though the item Channel. DI Start determines the manner of running the test
activation by digital input (DI1, DI2, DI3, DI4) or immediately (None).
The ramp is defined by its minimum (I min) and maximum (I max) value. The range of these values is the same
as the range of current channels (0-45mA) The value I max cannot have smaller values than I min + 0,1mA. The
value of one step is stated by the increase of the effective value by Step per each Length seconds.
The maximum length of the generation of the ramp is restricted to 90s. In the case of incorrectly selected
constants when the total time exceeds 90s, then after pressing Run test a warning screen is displayed with
Long time, change values and it is necessary to correct the ramp constants.
The range of the step is 0.1mA to (I max I min) mA and the step 0.1mA. The length is within the range 0.0110s with the step 0.01s.
Click on the item Run test to initiate the test in the first step, and then there is the start of the generation
(depending on DI Start). The ramp is generated on a selected current channel; the other channels remain without
change. After termination of the test, the measured values and results are displayed. During the test, individual
steps are displayed on the display.
The test can be terminated by pressing the control knob.

6.3.2.2 Step
The step change of the effective value of the current. It is also applicable without the licence for the voltage
card.

The channel is selected through the Channel (I1, I2, I3, Ix), similarly as for testing signal Ramp. DI Start
determines the manner of running the test activation by digital input (DI1, DI2, DI3, DI4) or immediately (None).
The EPG7 generates a harmonic signal with the frequency 50Hz and will change the effective value of the
current on the selected current channel. The level of the effective value step can be set through the item Fault with
the range of the current channel (0.1-45mA). The starting effective value of the channel is stated by the value set
in the menu for analogue outputs current source.
The step change of the effective value takes place after expiration of the time Start and lasts during the Length
time. After expiration of the total time (Start + Length) there is again a step change for the effective value and the
return to the original value. The values Start and Length are adjustable form 0.01 to 45s.
Press the button on the item Run test to initiate the test, then there is running of the generation (depending on
DI Start). The step is generated on the selected channel; the other channels remain without change. After
termination of the test, the result is displayed. During the test, individual steps are displayed on the display.
The test can be terminated by pressing the control knob.

-22-

Rev 4; 4/13

User Manual

6.3.3 Protection tester


The function is accessible in the protection tester licence.

6.3.3.1 Reclosing
Test reclosing is designated for the verification of protection times of RTU units during reclosing. In the diagram
under the text, the menu for setting the Reclosing is shown.

The channel is selected through the item Channel (I1, I2, I3, Ix). DI Start determines the manner of running the
test activation by digital input (DI1, DI2, DI3, DI4) or immediately (None). This option enables to select between
successful and unsuccessful, setting the number of cycles and the size of failure on the current channel. The
remaining items set time constants. (Operating) defines the length of the duration of the generation of operating
values 0-99s with the step 0.1s. Detection states the maximum time for the implementation of protection 0-99s with
the step 0.1s. Reclosing states the maximum time for re-activation of 0-99s with the step 0.1s. Intermediate sets
the time between the status DO OFF and DO ON.
Setting the digital inputs and outputs for the definition of statuses DO OFF and DO ON is accessible through the
menu Settings DI/DO.
Press the button on the Run test item to initiate the test and set the status DO OFF, and then to start the
generation (depending on DI Start). In the case of the setting DI Start it is waiting for the expiration of the time
Intermediate. DO ON status is set. In the first phase the values of currents and voltages are generated during the
Operating time. Then, there is the error status (only on the selected channel), which lasts during the Detection
time and it is waiting for the protection response signal DI OFF (if the protection does not respond, there is
termination of the test). After the response from the protection, there is disconnection of the generation on
analogue outputs. Then there is expiration of the Intermediate time and setting the status DO OFF. The further
step is waiting during the Reclosing time for the signal DI ON (if the signal does not come, the test is terminated).
Then, there is expiration of the Intermediate time and setting of the status DO ON. On the analogue outputs, the
operating values and the error status on the selected channel are generated. Then, there is again the waiting for
detection of the failure by the signal DI OFF. The whole process is repeated according to the number of set cycles.
After termination of the test, the result with the measured times is displayed.
If the test passed OK, then the operating values will be generated on analogue outputs. Otherwise, the
generation will be disconnected.
The test can be terminated by pressing the control knob.

-23-

Rev 4; 4/13

User Manual

6.3.3.2 Frequency step


The step change of the frequency on the voltage channel with the evaluation of the response time of the
protection.

The channel is selected through the item Channel (U1, U2, U3, Ux). DI Start determines the manner of running
the test activation by digital input (DI1, DI2, DI3, DI4) or immediately (None). The value of the step change in the
frequency is represented by the item Fault. The optional range of the frequency is 40-350Hz with the step 1Hz. The
frequency between 45Hz and 55Hz is adjustable with the step 0.1Hz.
Operating defines the length of the duration of the generation of operating values 0-99s with the step 0.1s.
Detection states the maximum time for the implementation of protection 0-99s with the step 0.1s. Intermediate
sets the time between the status DO OFF and DO ON. The input DI OFF indicates the affection of the protection.
Setting the digital inputs and outputs for definition of statuses DI OFF, DO OFF a DO ON is accessible in the
Settings DI/DO menu.
Press the button on the Run test item to initiate the test and set the status DO OFF, and then to start the
generation (depending on DI Start). In the case of setting DI Start, it is waiting for the expiration of the
Intermediate time. DO ON status is set. The operating values of the currents and voltage are generated during the
Operating time. Then, there is the error status (step change of the frequency on the selected channel), which lasts
during the Detection time and it is waiting for a response from the protection signal DI OFF (if the protection does
not respond, the test is terminated). After the response from the protection, there is disconnection of the generation
on analogue outputs. Then there is expiration of the Intermediate time and setting the status DO OFF. After
termination of the test, the result with the measured times is displayed. In the case that the protection does not
respond, there is a step change in the frequency and the operating values are generated and the test is terminated.
The channels are automatically fazed.
The test can be terminated by pressing the control knob.

6.3.3.3 Voltage step


The voltage step of the effective value of the voltage with the evaluation of the response time of the protection.

The channel is selected through the item Channel (U1, U2, U3, Ux). DI Start determines the manner of running
the test activation by digital input (DI1, DI2, DI3, DI4) or immediately (None). The value of the step change of
-24-

Rev 4; 4/13

User Manual
voltage is set by the item Fault. The optional range is the same as the range of the voltage channels 0-7V with the
step 0.01V. However, on the display there will be the line-to-line voltage value. Operating defines the length of the
duration of the generation of operating values 0-99s with the step 0.1s. Detection states the maximum time for the
implementation of protection 0-99s with the step 0.1s. Intermediate sets the time between the status DO OFF and
DO ON. The input DI OFF indicates the affection of the protection.
Setting the digital inputs and outputs for definition of statuses DI OFF, DO OFF a DO ON is accessible in the
Settings DI/DO menu.
Press the button on the Run test item to initiate the test and set the status DO OFF, and then to start the
generation (depending on DI Start). In the case of setting DI Start, it is waiting for the expiration of the
Intermediate time. DO ON status is set. The operating values of the currents and voltage are generated during the
Operating time. then, there is the error status (step change in the effective value of the voltage on the selected
channel), which lasts during the Detection time and is waiting for the response from the protection signal DI OFF
(if the protection does not respond, the test is terminated). After the response from the protection, there is
disconnection of the generation on analogue outputs. Then there is expiration of the Intermediate time and setting
the status DO OFF. After termination of the test, the result with the measured times is displayed. If the protection
does not respond there is a step change in the effective value of the voltage and the operating values are
generated and the test is terminated.
The test can be terminated by pressing the control knob.

6.3.3.4 Current step


The step of the effective value of the current with the evaluation of the response time of the protection.

The channel is selected through the Channel (I1, I2, I3, Ix), similarly as for testing signal Ramp. DI Start
determines the manner of running the generation of the step activation by digital input (DI1, DI2, DI3, DI4) or
immediately (None). The value of the step change of the current is set by the item Fault. The optional range is the
same as the range of the current channels 0-45mA with the step 0.1mA. Operating defines the length of the
duration of the generation of operating values 0-99s with the step 0.1s. Detection states the maximum time for the
response from protection 0-99s with the step 0.1s. Intermediate sets the time between the status DO OFF and DO
ON. The input DI OFF indicates the affection of the protection.
Setting the digital inputs and outputs for definition of statuses DI OFF, DO OFF a DO ON is accessible in the
Settings DI/DO menu.
Press the button on the Run test item to initiate the test and set the status DO OFF, and then to start the
generation (depending on DI Start). In the case of setting DI Start, it is waiting for the expiration of the
Intermediate time. DO ON status is set. The operating values of the currents and voltage are generated during the
Operating time. then, there is the error status (step change in the effective value of the current on the selected
channel), which lasts during the Detection time and is waiting for the response from the protection signal DI OFF
-25-

Rev 4; 4/13

User Manual
(if the protection does not respond, the test is terminated). After the response from the protection, there is
disconnection of the generation on analogue outputs. Then there is expiration of the Intermediate time and setting
the status DO OFF. After termination of the test, the result with the measured times is displayed. In the case that
the protection does not respond there is a step change in the effective value of the current and the operating values
are generate and the test is terminated.
The test can be terminated by pressing the control knob.

6.3.3.5 Frequency ramp


Generation of the frequency ramp on the voltage channel.

The channel is selected though the item Channel. DI Start determines the manner of running the test
activation by digital input (DI1, DI2, DI3, DI4) or immediately (None).
The ramp is defined by its minimum (Freq. min) and maximum (Freq. max) value. The range of these values is
the same as the range of the frequency (40-350Hz). The value Freq. max cannot have smaller values than Freq.
min + 1Hz. The value of one step is stated by the increase of the frequency by Step per each Length seconds.
The maximum length of the generation of the ramp is restricted to 90s. In the case of incorrectly selected
constants when the total time exceeds 90s, then after pressing Run test a warning screen is displayed with
Long time, change values and it is necessary to correct the ramp constants.
The range of the step is 1Hz to (Freq. max Freq. min) Hz and the step 1Hz. The length is within the range
0.01-10s with the step 0.01s.
Click on the item Run test to initiate the test in the first step, and then there is the start of the generation
(depending on DI Start). The ramp is generated on a selected voltage channel; the other channels remain without
change. After termination of the test, the measured values and results are displayed. During the test, individual
steps are displayed on the display.
The test can be terminated by pressing the control knob.

6.3.3.6 Potential-free pause


Verification of the protection of RTU units during the potential-free pause test.

-26-

Rev 4; 4/13

User Manual

The channel is selected through the item Channel (I1, I2, I3, Ix). DI Start determines the manner of running the
test activation by digital input (DI1, DI2, DI3, DI4) or immediately (None). The value of the step change of the
current is set by the item Fault. The optional range is the same as the range of the current channels 0-45mA with
the step 0.1mA. Operating defines the length of the duration of the generation of operating values Fault 1 and
Fault 2 intervals in failure statuses and the Pause length of the disconnection of the generation. Detection states
the maximum time for response from the protection. All time constants are adjustable within the interval 0-99s with
the step 0.1s. The input DI OFF indicates the affection of the protection.
Setting the digital inputs and outputs for definition of statuses DI OFF, DO OFF a DO ON is accessible in the
Settings DI/DO menu.
Press the button on the Run test item to initiate the test and set the status DO ON, and then to start the
generation (depending on DI Start). The operating values of the currents and voltage are generated during the
Operating time. Then, there is the error status (step change in the effective value of the current on the selected
channel), which lasts during Fault 1. After termination of the error status, the generation is disconnected on all
channels during Pause and DO OFF is set. After the expiration of the pause, there is re-generation of the fault
during Fault 2 on the selected channel;, on the other channels the operating values are generated. DO OFF is set.
After the expiration of the time, DO OFF is set and is waiting for the response from the protection DI OFF. If the
protection responds earlier, there is termination of the test at this moment. After termination of the test, the result
with the measured times is displayed.
The test can be terminated by pressing the control knob.

6.3.3.7 DI/DO simulator


Simulator of the status of the power element.

Signals DI OFF and DI ON, are evaluated which are sent to DO Aux OFF and DO Aux ON. Intermediate sets
the time between the status DO Aux OFF and DO Aux ON.
Setting the digital inputs and outputs for the definition of statuses DI OFF, DI ON is accessible through the menu
Settings DI/DO.

6.3.4 Setting DI/DO


This option serves for the global definition of the statuses: connected - ON and disconnected - OFF for digital
inputs and outputs. The applied changes are reflected in all tests. The adjustable values for digital inputs are DI1,
DI2, DI3, DI4 and None, for digital outputs DO1, DO2, DO3, DO4 and None.

-27-

Rev 4; 4/13

User Manual

6.4

Setting

The setting menu for the generator is shown in the following diagram. The range of contrasts (Contrast) in the
display is 0-100% with the step 5%. In the generator, it is possible to select between two languages, English AN
and Czech CZ. The sound signalling for pressing the control knob button is hidden under the name Sound
(connected - On, disconnected - Off).
The item Sleep mode switches the converters on the output channels on or off, if the generation is not activated
on any channel. This will decrease the consumption of the generator. A further energy saving option is the
automatic disconnection of the generator during inactivity (Shutdown). Inactivity means the time of the last change
made by the user. The time can be set from 0 minutes to 1 day with the step 5 minutes.
The rotation of the menu (Rotate) is useful for passing quickly through the items within a wide menu.

Setting the menu and setting the channels can be saved in the memory of the generator by means of the Save
settings option. The setting of the channels can be saved into the memory analogue inputs (information on the
activation of the channel is not saved), setting tests and setting menu. The saving of the setting must be confirmed.
Setting the channels is started either from the memory of the generator (selected by the user) or the default
values are set. This function is located under the item Load memory (On loading of user values, Off loading
of default values).

6.4.1 Transformer
Menu for switching the generator units for current and voltage channels. The function enables the switching of
calculations between the primary and secondary units of the transformer. If the function is disconnected, secondary
units are used in the generator. Otherwise, the calculation according to the selected Primary and Secondary
constants is used. The resulting coefficient is stated by the ratio of the primary and secondary. If the coefficient is
too high, a warning message is displayed when enabling the recalculation.

-28-

Rev 4; 4/13

User Manual

6.4.2 Calibration
The calibration menu serves for the calibration of the voltage and current channels and calibration of the battery.
Before entering the advanced calibration menu, it is necessary to insert the Password and enter the combination
of five characters. The choice of characters is made by turning the control knob The list of available characters is
displayed on the last line of the display and the actual selected character flashes. By briefly pressing the control
knob, there is the acknowledgement of the character and passing to the other. Long pressing of the control knob
will cause the return to the previous menu.
If the correct password is inserted, the option for using or manufacturing calibration is added to the first line of
the menu. The user calibration does not support the calibration of back measurement and calibration of the battery.
By entering into this option, the advanced calibration menu is opened. The password for the user calibration is
11111.
The date of calibration displays the date when the calibration was performed. The switching between
manufacturing and user calibration constants is possible by clicking on the item Values (figure in the Chapter 6.4).
The advanced calibration menu and steps in the calibration process are shown in the following diagram. The
channel is selected by pressing the control knob on the item Channel (value I1, I2, I3, U1, U2, U3, Ubat). On the
third line is the menu for setting the calibration data.

Before running the calibration, it is necessary to connect the measuring device to the respective channel (on the
Ammeter current channel in series with the load to the Voltmeter voltage channel in parallel to the load).
The calibration process is divided into calibration for the generation of the signal and the calibration of back
measurement (not accessible for user calibration). The first step is calibration of the offset (DC calibration). On the
selected DC channel a signal is generated with the amplitude 0mA (0V). By the movement of the rotary control
knob it is necessary to set the value so that it approaches the value 0mA (0V) as much as possible. By pressing the
control knob, the value is acknowledged and passed to the next step.
The second and the third step is the calibration of the amplification for the first and the second range (30mA and
60mA, or 4.5V and 10V). The calibration procedure is the same as in the previous step, by moving the control knob
the adjusted value is modified to best match the required value and is acknowledged by pressing the control knob.
In the fourth step is the calibration of the value of the AC signal depending on the frequency (it is necessary to
switch the measuring device to the AC range). The harmonic signal is generated on the output with the frequency
50Hz and the effective value 20mA (3V). With the rotary control knob, the value on the output is generated,
although the value measured by the measuring device is entered into the generator. The acknowledgement is by
pressing the control knob button.
The same principle is in the 5th and the 6th step, the harmonic signal is generated with the frequency 200Hz
and then 350Hz. After termination of the calibration, the constants are saved in the memory of the device and it is
necessary to set the date of calibration in the date menu.
-29-

Rev 4; 4/13

User Manual
The battery is calibrated in just one step. The value of the voltage is entered on the display by the rotary control
knob. The value is acknowledged by pressing the control knob.
The calibration process can be paused by long presses of the control knob button.
Important for correct calibration:
During the calibration of current channels, it is important to connect the small loading resistor,
otherwise the generated value is restricted
During the calibration of voltage protection, it is necessary to connect the high loading resistor,
otherwise the generated value is restricted
The battery is calibrated without the connected supply adapter.

6.5

Information

The menu with information about the status of the batteries, ID number of the Firmware unit, is shown in the
diagram below.

6.5.1 Battery
If the EPG7 generator is supplied with batteries, the value of the voltage on the batteries is shown on the
display. Otherwise, a message is displayed that the device is supplied by the adapter.

6.5.2 Firmware
On the display a is the number of the Firmware version. By turning the control knob, the screen shows the list
of functions available in the licence. The available functions are marked with a cross.

6.6

Shutdown

Menu for disconnecting the generator. On the display the message is shown acknowledging the request. By
turning the control knob, you can select and acknowledge the request.

-30-

Rev 4; 4/13

User Manual

7 How to proceed in the case of problems


Anytime when the device works in a non-standard manner or when error messages are displayed, pay attention
to these statuses. This can concern minor problems which you can resolve yourself, but can also concern
symptoms of a more serious nature. If you exclude basic operator errors (for example, unconnected cable, failure in
some of the peripherals, etc.) and problems continue, order the unit to be repaired by specialists. You can contact
us on the service line; we will be pleased to help or we can agree a service action with you.
We believe that such problems will be at a minimum due to the care taken in production.
On behalf of the whole team at ELVAC a.s. we would like to thank you for your attention and we trust that you
will be satisfied with our product.

Warranty and post-warranty service is provided in the following centres:


CZ
ELVAC a.s, Hasisk 53, 700 30 Ostrava Hrabvka, Tel.: +420 597 407 336 a 337
ELVAC PRAHA s.r.o., Naskov 1100/3, 150 00 Praha 5, Tel.: +420 224 914 608
SK
ELVAC SK s.r.o., Zlatovsk 27, 911 01 Trenn, Tel.: +421 32 640 1766

-31-