Professional Documents
Culture Documents
PAKONG
3/4
MODULATING
OPERATING
CONTROLS
PROCEDURES
CONTENTS
CONTENTS.INS 210392
UNIT MASTER
AIR FLOW
GOVERNOR POSITION
ID FAN SPEED
10
11
12
CONDENSER LEVEL
13
14
15
16
BANG
:1
CONTROLS
MASTER
MASTER.INS 030992
-------------------------------------------------------------------SYSTEM
BOILER-TURBINE COORDINATION
CON.T VARIABLE
MEGAWATTS, PRESSURE
CONTROL DEVICE
SET VALUE
GSM PB
"UNIT MSTR"
GROUP DISPLAY
001
UNIT MASTER
TX DEVN DISPLAY
089
MASTER
(A)
PERMISSIVES
(1)
Coordinated Mode: Air Flow, Fuel Flow, Governor, Main Steam Temperature,
Feedwater Flow and Condensate Flow controls selected to AUTO.
(2)
Boiler Follow Mode: Air Flow, Fuel Flow and Governor (optional) selected
to AUTO.
(3)
Base Input Mode: Air Flow, Fuel Flow and Governor (optional) selected to
AUTO.
(4)
(B)
OPERATOR
ACTION
relevant Operating
(2)
Select Group
subwindows.
(3)
Select the required mode. The subwindow displays the selected mode. If
the required permissives are not complete, "PERMISSIVE LOSS" will be
indicated. Any faulty transmitter affecting the Unit Master or Fuel/Air
Deviation condition will force the Unit Master to remain in Manual Mode.
(4)
After about 5 seconds the mode selection subwindow indicates the mode
active condition. If the system remains in the mode selected status it
means that one of the subloops is not correctly initialized [balanced].
This can be caused by excessive air flow, significant change in fuel
heating value or faulty transmitter calibration.
Operation
Display
AUTO.
[Refer to
(1)
001
["UNIT
MSTR"]
and
ENABLE
all
-2(5)
(6)
The Target Load Set Point initializes at the existing MW for CO and BF
Modes and at Fuel Flow for BI Mode.
Set the desired MW load at the
Target Load Set Point Subwindow.
(7)
Set the
facility
System
burners
(8)
Set the required load change rate in MW/MIN at the Rate subwindow.
Then select AUTO at this subwindow to permit the load change to start.
(9)
If ADS control of the Target Load is required, select AUTO on the Target
Load subwindow. ADS control is available in the CO Mode only.
(C)
(1)
COMMENTS
The maximum load is limited by the auxiliary plant capacity.
[PID:
This is calculated from the number of Fans, Feedpumps,
COAW408]
Condensate Pumps and Boiler Circulating Water Pumps in service as
follows:
Each FD Fan
Each ID Fan
Each MDBFP
Each TDBFP
Each Cond Pump
Two BCWP
Three BCWP
360
360
90
360
350
360
600
MW
MW
MW
MW
MW
MW
MW
The lowest value from the four auxiliary groups is selected; for
example, one TDBFP and one MDBFP would limit the target load to 450 MW.
The maximum value of Auxiliary Plant Capacity [APC] is 635 MW.
(2)
The Required Output [COAY400] is calculated from the Target Load, Rate
Setter, Minimum and Maximum Limits .and the Auxiliary Plant Capacity.
The Required Output [RO] is the set point for Governor, Fuel and Air
control loops.
(3)
I f an auxiliary trip causes the APC to drop below the existing RO, a
RUNBACK is initiated. This causes the RO to decrease as a fast rate to
the new value determined by the APC. The Unit Master is automatically
transferred to BI Mode before the Runback starts.
(4)
The major flow loops are checked for abnormal deviation from th~
required value.
This applies to Fuel, Air, Governor, Feedwater and
Condensate. I f the auxiliary plant is unable to follow the load demand
for any reason, a flow deviation occurs.
For example, fuel valve at
maximum causes a fuel flow low condition.
Any increase in RO is
blocked and, after a short time delay, the RO is reduced until the
deviation is within limits.
-3-
(5)
Modes:
MANUAL
The target load and required output tracks fuel flow.
The Air Flow and Oxygen controls may be placed on AUTO.
The Air
Demand follows Fuel Flow when above the minimum air flow limit. Manual
Mode is normally used at unit start up until stable firing conditions
are achieved.
BASE INPUT
The boiler energy input [fuel and air] is set by the
Target Load.
The resulting MW depends on the fuel heating value.
Pressure is controlled to a fixed set point if the Governor is on AUTO
[Turbine Follow].
If the governor is not auto, the pressure is
proportional to firing rate and inversely proportional to governor
position. Changes in governor position causes transient change to MW.
Base Input Mode is used when stable boiler operation is required.
BOILER FOLLOW
The boiler input is determined by the turbine energy
demand. This is calculated from First Stage Pressure, Throttle Pressure
and Pressure Set Point. Pressure correction is made by adjusting t
boiler inputs [fuel and air].
The governor may be on automatic c..
manual operation.
If the governor is on AUTO it controls MW at the
Target Load setting [para (2)] and sliding pressure is permitted.
The
Boiler Follow Mode allows responsive control when the governor is not
available for automatic operation.
COORDINATED
The boiler inputs [fuel and air] and the governor
respond to a common demand signal, Required Output.
Refer to
Paragraph (2).
Sliding pressure and ADS control is available in this
mode. The governor is adjusted to control MW and the boiler inputs are
regulated to maintain pressure.
The Coordinated Mode is the normal
method of operation.
BANG
CONTROLS
COMBUSTION
AIR
FLOW
AIRFLOW.INS 030992
-------------------------------------------------------------------SYSTEM
COMBUSTION AIR
CONT VARIABLE
PID :
CONTROL DEVICE
3SGB-CDR-1,2
SET VALUE
GSM PB
"COMB AIR"
GROUP DISPLAY
002
COMBUSTION AIR
TX DEVN DISPLAY
089
MASTER
(A)
PERMISSIVES:
(1)
(2)
(3}
(4)
(B)
SGBF409
OPERATOR
ACTION:
(1)
[GSM
"COMB
AIR")
and
ENABLE
the
(2)
Check that the indicated Air Demand [SV] is a reasonable value for the
existing load condition.
[e.g. for 300MW, should be approximately 50%.
The minimum is 33%]
The PV and SV indications on Fan lA subwindow
should be aligned, indicating tracking' balance.
(3)
(4)
(5)
-2-
(C)
COMMENTS:
(1)
The basic Air Demand equals the Required Output [RO] calculated by the
Boiler Master.
When the Boiler Master is in MAN mode, the RO equals
Fuel Flow.
(2)
The excess air is calculated from the .RO and the 02 set point.
The
excess air component is added to the basic [stochiometric] air demand.
Refer to 02 control notes.
(3)
(4)
(5)
After selecting Air Auto, AUTO will be indicated on the subwindow if t'
permissives are OK.
The MAN indication will remain on until boile1
master permissives and initialization check is complete [WAITING]. This
takes about 5 seconds. If MAN remains on, air flow may be excessive
for firing rate, or boiler master permissives not complete, or ID fan
damper Not Auto. If air flow is excessive, the PV and SV arrows on Fan
lA subwindow will not align and the flue gas 02 indication will be
higher than the set point. Reduce air flow until tracking balance is
achieved.
(6)
Pitch oil pressure low [<12 Bar] or excess furnace pressure deviation
blocks both AUTO and MANUAL operation of blade pitch.
BANG
3
FLUE
GAS
&
OXYGEN
CARBON
MONOXIDE
02ANDCO.INS 030992
-------------------------------------------------------------------SYSTEM
COMBUSTION AIR
CONl' VARIABLE
CONTROL DEVICE
SET VALUE
GSM PB
"COMB AIR"
GROUP DISPLAY
002
COMBUSTION AIR
TX DEVN DISPLAY
089
MASTER
PERMISSIVES
(A)
Flue Gas 02
(1)
No 02 transmitter deviation.
(2)
(3)
Flue Gas
[Monitor ON.]
co
(1)
No CO transmitter deviation.
(2)
02 control AUTO.
OPERATOR
(B)
[Monitor ON.]
ACTION
Flue Gas 02
If all
(1)
(2)
(3)
(4)
from boiler
CO control
on the OZ
+/- 2% 02.
-2Flue Gas CO
(1)
(2)
(3)
(C)
[Display 089].
If both OK,
enable
COMMENTS
(1)
(2)
(3)
The real time trend for air flow, fuel flow, 02 and CO should be checked
frequently for normal combustion conditions.
BANG
GAS
FUEL
CONTROLS
FLOW
GASFUEL.INS 030992
SYSTEM
GAS FUEL
CONT VARIABLE
FGAF408
CONTROL DEVICE
CONTROL VALVES
3FGA-ACV-l,
SET VALUE
GSM PB
"FUEL"
GROUP DISPLAY
004
FUEL
TX DEVN DISPLAY
090
(A)
PERMISSIVES:
(1)
(2)
(3)
(4)
(5)
(6)
M.F.T. reset.
(7)
(8)
>
0.11 Bar.
-2( B1)
OPERATOR
ACTION
[GAS
ONLY
FIRING]
(1)
Select Group Operation Display 004 (FUEL) and ENABLE subwindow of the
fuel gas control valve required for auto operation.
The capacity of
each gas control valve is about 60% ECR. At higher loads with gas fuel
only, two valves are required on Auto ..
(2)
(3)
(4)
(5)
(6)
(7)
value
for
the
existing
also
load
on
( B2)
COMBINED
FIRING
(1)
Refer to Fuel Oil Operating Procedure for permissives for Oil firing.
(2)
(3)
(C)
(1)
COMMENTS:
Gas fuel flow control functions between burner header pressure limits
0.15 to 1.50 Bar.
If a limit is reached, the fuel gas flow control
transfers to header pressure control. An alarm is initiated to advise
"Gas Limited" condition exists.
If oil is on auto, the gas error is
transferred to the oil control.
/
! '
BANG
OIL
FUEL
CONTROLS
FLOW
OILFUEL.INS 030992
SYSTEM
OIL FUEL
CONT VARIABLE
FOBF407
CONTROL DEVICE
CONTROL VALVES
3FOB-ACV-7,8
SET VALUE
GSM PB
11
GROUP DISPLAY
004
FUEL
TX DEVN DISPLAY
090
(A)
I I
FUEL 11
PERMISSIVES:
(1)
(2)
(3)
(4)
(5)
(6)
M.F.T. reset.
(7)
(8)
>
6.5 Bar.
-2( B::l)
ACTION
[OIL
ONLY
FIRING]
(1)
Select Group Operation Display 004 (FUEL) and ENABLE subwindow of the
fuel oil control valve required for auto operation. [Only ONE valve of
pair ACV-7/ACV-8 permitted on auto at same time; each valve is >100%
capacity].
(2)
Check fuel flow PV is reasonable value for the existing load condition.
Note that SV tracks fuel.
(3)
(4)
(5)
(6)
(7)
( B2)
COMBINED
also
on.
FIRING
(1)
Refer to Fuel Gas Operating Procedure for permissives for Gas firing.
(2)
(3)
(C)
I l..
OPERATOR
COMMENTS:
(1)
Oil fuel flow control functions between burner header pressure limits
7.5 to 21.0 Bar.
If a limit is reached, the fuel oil flow control
transfers to pressure control.
An . alarm is initiated to advise "Oil
Limited" condition exists.
If gas is on auto, the oil error is
transferred to the gas control.
(2)
Each oil fuel control valve is >100% capacity and only one can be on
AUTO at one time. If operating conditions require the second valve to
be opened it must be under manual control.
BANG
GOVERNOR
POSITION
GOVERNOR.INS 030992
-------------------------------------------------------------------SYSTEM
TURBINE GOVER'NOR
CONT VARIABLE
CONTROL DEVICE
SET VALUE
GSM PB
"UNIT MSTR"
001
UNIT MASTER
TX DEVN DISPLAY
089
MASTER
(A)
.'
AIR XMTRS
PERMISSIVES:
(1)
(2)
(3)
No transmitter deviation:
First Stage Pressure [P1]
Throttle Pressure [Pt]
Megawatt
(4)
{5)
(B)
&
OPERATOR
[MHI]
[MHI]
ACTION
(1)
(2)
Select Group Operation Display 001 (UNIT MSTR) and ENABLE Subwindow 7,
"Governor Position Demand".
(3)
(5)
(6)
is
also
ON.
-2(7)
(8)
(C)
COMMENTS
(1)
(2)
(3)
} <L
MANUAL control of governor valves is NOT available from the Unit Master
Governor subwindow.
MANUAL CONTROL OF THE GOVERNOR IS ONLY AVAILABLE FROM THE MHI DEH
GOVERNOR PANEL.
BANG
7-FURNACE
ID
PRESSURE
FAN
CONTROLS
DAMPERS
IDFDAMP.INS 030992
-------------------------------------------------------------------SYSTEM
INDUCED DRAFT.
CONT VARIABLE:
FURNACE PRESSURE
PID:
CONT DEVICE:
CDR-127, CDR-128
SET VALUE
(-)
GSM PB
"FURN GAS"
GROUP DISPLAY
003
FURNACE GAS
TX DEVN DISPLAY
089
(A)
; j-
20 mm
PERMISSIVES:
(1)
(2)
(B)
SGAP401
OPERATOR
ACTION
(1)
(2)
(3)
(4)
(5)
-2-
(c)
COMMENTS:
(1)
AUTO mode
(2)
(3)
(4)
If the actual pressure is more than +/- 25mm from the set point, damper
movement which increases the error magnitude is blocked. This applies
in MANUAL and AUTO modes.
(5)
(6)
Display a real time trend of furnace pressure at all times and check
frequently for abnormal patterns. [PID: SGAP401].
BANG
ID
FAN
CONTROLS
SPEED
IDSPEED.INS 030992
SYSTEM
INDUCED DRAFT
CONT VARIABLE
ID FAN SPEED
CCES009,CCES010
CONTROL DEVICE
3CCE-FAN-1A,
SET VALUE
GSM PB
"FURN GAS"
GROUP DISPLAY
003
TX DEVN DISPLAY
N/A
(A)
FURNACE GAS
PERMISSIVES:
(1)
(2)
(3)
(B)
lB
OPERATOR
ACTION
(1)
Select Group Operation Display 003 ["FURN GAS"] and ENABLE subwindows
for ID Fan hydaulic couplings.
(2)
(3)
(4)
-2-
(C)
COMMENTS:
(1)
Control may
(2)
If furnace pressure is more than +/- 25 mm from the set point, any
speed change command in the direction which increases the error
magnitude is blocked. This applies in MANUAL and AUTO modes.
(3)
The Process Variable is the average speed demand with time constant to
simulate actual speed response. Transfer to AUTO is bumpless, the
speed will slowly go to the calculated set point.
(4)
BANG
MOTOR
BOILER
FEED
CONTROLS
PUMPS
MDBFP.INS 030992
-------------------------------------------------------------------SYSTEM
FEEDWATER
CON.T VARIABLE
DRUM LEVEL
CONTROL DEVICE
MDBFP 3A,
SET VALUE
0 mm
GSM PB
"FEED WTR"
GROUP DISPLAY
010
FEEDWATER
TX DEVN DISPLAY
092
CNDS
(A)
PERMISSIVES:
(1)
(2)
No transmitter deviation:
feedwater flow [hi range]
first stage pressure
drum level [east, west]
(B)
,c
OPERATOR
[Running).
ACTION
(1)
Select group operation display 010 [FEED WTR] and ENABLE subwindow of
pumps required on AUTO.
(2)
(3)
(4)
Select AUTO for Motor Pumps in service. [Note: The pump speed demand
will go to the minimum value required for pumping at the prevailing
drum pressure.)
(5)
-2-
(C)
COMMENTS:
(1)
The drum level is normally the average of the medians of the east and
west sides The level indication is density compensated over the range
0 - 220 Bar. A separate subwindow is provided for the drum level set
point.
(2}
The feedwater demand FWAF431 is the steam flow (first stage pressure}
plus drum level correction.
When steam flow increases or decreases,
the feedwater flow first goes in the opposite direction to the steam
flow to compensate for drum level swell/shrink effect.
The feedwater
demand is the set value (SV} displayed on pump 3A subwindow. The flow
range is 0-125%ECR.
(3}
The feedwater flow (PV) is indicated on both pump subwindows. The pump
controller adjusts pump speed so that feedwater flow always equals
feedwater demand (SV). The 3B pump subwindow SV is BIAS, range +/- 20%
speed.
(4)
The pump speed range is 2100-7000 r.p.m. for 0-100% control output W
A minimum pump speed bias is calculated from boiler drum pressure.
This factor is added to the speed demand in auto mode.
When a pump is
selected to auto, the speed demand immediately goes to the calculated
minimum value. At this minimum speed the pump pressure is almost equal
to the drum pressure and the pump can immediately contribute flow. The
second pump may be selected to auto at any speed; balancing is
automatic and bumpless.
(5)
When turbine driven pumps are also selected to AUTO, the motor driven
pumps follow the turbine pump controller output. Because of differing
pump characteristics, the percentage flow may not be the same for
turbine and motor pumps.
(6)
trend display showing drum level (SGFL407}, feedwater flow (FWAF419} and
steam flow (TGFP400). When level is decreasing, INCREASE the flow; when
level is increasing, DECREASE the flow. DO NOT wait for level to reach
the set point before reversing the flow.
Try to estimate the average
flow for the existing load and work around that point.
BANG
TURBINE
BOILER
FEED
CONTROLS
PUMPS
TDBFP.INS 030992
-------------------------------------------------------------------SYSTEM
FEEDWATER
CONT VARIABLE
DRUM LEVEL
CONTROL DEVICE
TDBFP 2A,
SET VALUE
0 mm
GSM PB
"FEED WTR"
GROUP DISPLAY
010
FEEDWATER
TX DEVN DISPLAY
092
(A)
2B
PERMISSIVES:
(1)
(2)
No transmitter deviation:
Feedwater flow [hi range]
First stage pressure
Drum level [east/west]
(3)
(B)
OPERATOR
[running].
ACTION
(1)
Select group operation display 010 [FEED WTR] and ENABLE subwindow of
pumps required on AUTO.
(2)
(3)
(4)
(5)
-2-
(C)
COMMENTS:
(1)
The drum level is normally the average of the medians of the east and
west sides The level indication is density compensated over the range
0 - 220 Bar. A separate subwindow is provided for the drum level set
point.
(2)
The feedwater demand FWAF431 is the steam flow (first stage pressure)
plus drum level correction.
When steam flow increases or decreases,
the feedwater flow first goes in the opposite direction to the steam
flow to compensate for drum level swell/shrink effect.
The feedwater
demand is the set value (SV) displayed on pump 2A subwindow. The flow
range is 0-125%ECR.
(3)
(4)
The pump speed range is 2700-5600 r.p.m. for 0-100% control output (MV).
A minimum pump speed bias is calculated from boiler drum pressure.
This factor is added to the speed demand in auto mode.
When a pump is
selected to auto, the speed demand goes to the calculated minimum value.
At this minimum speed the pump pressure is almost equal to the drum
pressure and the pump can immediately contribute flow.
The second
pump may be selected to auto at any speed; balancing is automatic and
bumpless.
(5)
(6)
(7)
12
BANG
DEAERATOR
CONTROLS
LEVEL
DEALVL.INS 030992
-------------------------------------------------------------------SYSTEM
CONDENSATE
CONT VARIABLE
DEAERATOR LEVEL
CONTROL DEVICE
SET VALUE
LEVEL:
GSM PB
GROUP DISPLAY
014
TX DEVN DISPLAY
092
CNDS
(A)
70%
PERMISSIVES:
(1)
(2)
(3)
(B)
3FWC-P-1A, lB, lC
OPERATOR
ACTION
(1)
(2)
(3)
(4)
(5)
( C)
display
014
and
ENABLE
subwindow
of
pumps
COMMENTS:
(1}
(2)
(3)
If deaerator level is greater than 90% [2525 mm], the deaerator high
level controller opens overflow valves ACV-170, 173 and dumps the
excess condensate to the condenser. The high level control is always
in auto mode. [GSM: "DEA MISC"]
BANG
CONTROLS
CONDENSER
LEVEL
CONDLVL.INS 030992
-------------------------------------------------------------------SYSTEM
CONDENSATE
CON.T VARIABLE
CONDENSER LEVEL
CONTROL DEVICE
70%
90%
GSM PB
"DEA
014
DEA
TX DEVN DISPLAY
098
(A)
(1)
(B)
CNDS"
&
CONDENSATE
PERMISSIVES
No condenser level transmitter deviation.
OPERATOR
[Monitor ON].
ACTION
(1)
If both
(2)
ENABL ....
(3)
(4)
(C)
) I..J.
&
ACV-54
ACV-57
ACV-63
014
[DEA
&
CONDENSATE]
and
COMMENTS
(1)
(2)
BANG
13
SECONDARY SUPERHEATER
TEMPERATURE
OUTLET
SECSHO.INS 030992
-------------------------------------------------------------------SYSTEM
MAIN STEAM
CONT VARIABLE
CONTROL DEVICE
SET VALUE
GSM PB
GROUP DISPLAY
006
007
SEC SH TO 2A LINE
SEC SH TO 2B LINE
TX DEVN DISPLAY
094
(A)
PERMISSIVES
(1)
(2)
(3)
(4)
(B)
[Refer B(3)]
OPERATOR
ACTION
(1)
Check thermocouples
agreement.
[Display
094]
for
reasonable
(2)
(3)
Select AUTO on set point subwindow [1]. If manual set point required,
select MAN and adjust set value to the required temperature.
(4)
(5)
(6)
SSHB
values
SPRAY].
and
pair
ENABLE
ENABLE
-2-
(C)
}_ I
COMMENTS
(1)
(2) .
The steam lines from each side of the secondary superheater outlet
header CROSS OVER before going to the second stage desuperheaters 2A
and 2B. [DESH 1C,1D -> 2A; 1A,1B -> 2B]
(3)
(4)
(5)
The set point subwindow appears on group operation displays 006 ana
007. Either may be used.
(6)
BANG
TERTIARY
14
(FINAL)
SUPERHEATER
TEMPERATURE
OUTLET
TERSHO.INS 030992
-------------------------------------------------------------------SYSTEM
MAIN STEAM
CONT VARIABLE
CONTROL DEVICE
SET VALUE
GSM PB
"TSH SPRAY"
GROUP DISPLAY
008
TX DEVN DISPLAY
094,095
(A)
') 7
[Refer B(3)]
TERTIARY SH
STEAM TEMP XMTRS #1,#2
PERMISSIVES
(1)
(2}
(3}
(4}
(B)
(WEST,EAST)
OPERATOR
ACTION
(1)
Check thermocouples
agreement.
[Display
094,095]
for
reasonable
values
and pair
(2)
Select group
operation display
008
[GSM:
"TSH SPRAY"].
subwindows for set value and for valves required for operation.
(3)
(4)
ENABLE
-2-
(C)
COMMENTS
(1)
(2)
The steam lines from each side of the secondary superheater outlet
header CROSS OVER before going to the second stage desuperheaters 2A
and 2B.
[DESH lC,lD -> 2A; lA,lB -> 2B]
The second stage
desuperheaters
2A,
2B
control
the
tertiary superheater outlet
temperatures [West, East].
(3)
(4)
(5)
BANG
CONTROLS
--------------------------------- ~ ----------------------------------
SYSTEM
REHEAT STEAM
CONT VARIABLE
CONTROL DEVICE
SET VALUE
540 DEG
GSM PB
"RE HTR"
GROUP DISPLAY
009
REHEATER TEMP
TX DEVN DISPLAY
095
(A)
2.
CDR-125,
CDR-126
PERMISSIVES
{1)
(2)
{3)
No Boiler Trip.
(4)
(B)
2B
OPERATOR
ACTION
{1)
Check thermocouples
agreement.
[Display
095}
for
reasonable
value
and
pair
{2)
Select Group Operation Display 009 ["RE HTR"] and ENABLE subwindows for
Burner Tilt and Gas Recirculation Fans.
{3)
{4)
(5)
(6)
(7)
-2-
(C)
COMMENTS
(1)
The maximum reheat steam set point reduces as boiler load decreases.
This maximum value overrides the operator set point.
Refer function
generator FG-78.
(2)
The GR Fan inlet vanes have a minimum position when in AUTO mode.
minimum varies with load.
(3) .
(4)
The
BANG
16
STEAM
TEMPERATURE
CONTROLS
[SPRAYS]
RHSPRAYS.INS 030992
-------------------------------------------------------------------REHEAT STEAM
CONT VARIABLE
CONTROL DEVICE
SET VALUE
GSM PB
"RE HTR"
GROUP DISPLAY
009
REHEATER TEMP
TX DEVN DISPLAY
095
(A)
[ACV-241,246,257,262]
PERMISSIVES
(1)
(2)
(3)
(B)
}I
\.
SYSTEM
OPERATOR
ACTION
(1)
(2)
Select Group Operation Display 009. [Press GSM "RE HTR"] and ENABLE
subwindows for required control valves.
(3)
(4)
(5)
(6)
-2-
(C)
COMMENTS
(1)
(2)
Only ONE