You are on page 1of 20

TECHNICAL DATA SHEET

NEW PRODUCT
Rev. 3 05/2014

New Cable Glands REV and REVD series


for ATEX and IECEx world
...Your Best Solution
for three methods of protection: Ex d/Ex e/Ex tb

1 - New Product Technical Data Sheet - REV, REVD series cable glands Rev. 3 - 05/2014

MARKING REV AND REVD SERIES CABLE GLANDS

1.
2.
3.
4.
5.
6.
7.
8.
9.
10.

The symbol CE means "Conformit Europenne" and it shows that the item is complying the essential
requirements of the Directives on safety, public health, consumer protection, ecc
N of the registered body (CESI) responsible for production monitoring in accordance with Directive
94/9/CE ATEX
Denotes the equipment with explosion protection
Group II (surface devices)
Category 2 (suitable for zone 1 and 2 for gas and zone 21 and 22 for dust)
Gas and Dust (this material can be installed both in presence of gas and dust)
ATEX Certification number
Protection method (Ex d: flame-proof, Ex e: increased safety, IIC: GAS group, Gb: Epl Equipment
protection level, Ex tb: dusts protection, IIIC: dusts group)
IP protection
IECEx Certification number

CERTIFICATE DATA AND CONFORMITY TO STANDARDS


ZONES

1 - 21 - 2 - 22

AMBIENT TEMPERATURE

-40C +110C

IP PROTECTION

IP66/67

ATEX CERTIFICATION

CESI 13 ATEX019X (ELFIT)


CESI 13 ATEX 032X (CORTEM)

IECEx CERTIFICATION

IECEx CES 13.0005X (ELFIT)


IECEx CES 13.0011X (CORTEM)

CONFORMITY TO STANDARDS

OTHER CERTIFICATIONS

ATEX 94/9/CE
EN 60079-0:2012; EN60079-1:2007;
EN 60079-7:2007; EN 60079-31:2009;
EN 60529:1991
IEC 60079-0:2011; IEC 60079-1:2007;
IEC 60079-7:2006; IEC 60079-31:2008;
IEC 60529:2001
RoHS standard 2002/95/CE
Russian certification GOST TR CU

PRODUCT DESCRIPTION REV AND REVD CABLE GLANDS


The new cable glands of REV and REVD series are suitable for use in hazardous areas with danger of explosion to enable direct insertion of non-armoured cables, REV series cable glands, and of armored cables, REVD series cable glands, into explosion-proof junction boxes and/or lighting fixtures, plugs and sockets,etc...

2 - New Product Technical Data Sheet - REV, REVD series cable glands Rev. 3 - 05/2014

The new cable glands series has optimally exceeded all the tests currently required for the certification of this product. The result is a cable gland of highest performance in terms of reliability and safety, able to cover a wide range of the main cables on the marked
such as plaited armoured cables, flat or wire cables with armour thickness from 0 to 2,5 mm.
REV and REVD series is more competitive and, at the same time, more powerful than the cable glands of
the previous series.
The most important innovation is the use of one sealing ring on the inner and outer sheath of the cable
and no longer a kit of sealing rings of different diameters. REV series is constituted by a single sealing ring
which tightens the incoming cable ensuring the 'Ex d' way of protection. REVD series has a second sealing
ring that tightens on the outer sheath of the cable to ensure the IP66/67 degree of protection avoiding the
ingress of water, moisture, rain and dust. The cable range available for each cable gland is described in
the following tables.
A further advantage is the lighter weight and the smaller dimensions, an important detail when theres the
need to install a large number of cable glands on explosion-proof enclosures.
The new cable glands REV and REVD series have been designed to replace FL/FG e FAL/FGA series
cable glands. They are realized in NICKEL-PLATED BRASS, STAINLESS STEEL and GALVANIZED
STEEL from 3/8" up to 2 and in NICKEL-PLATED BRASS and STAINLESS STEEL from 2 1/2 up to 4".
This new series includes also REVL, REVDL series special version which can accommodate smaller cable
diameters than the standard required for each measure. In this way, the use of reductions is avoids.
The new cable glands of REVF and REVN series are designed to replace the FGF series (female threaded
entry) and the FGN series cable glands (male threaded entry) available from 3/8" to 2" sizes and made of
NICKEL-PLATED BRASS, STAINLESS STEEL and GALVANIZED STEEL. Its also available a waterproof series: TEV series for non-armoured cables and TEVD for armoured cables.
They are provided with high-tech and high mechanical performance compression rings and gaskets
with high-temperature resistance.
Thanks to their structure, they are particularly suitable both in harsh application, such as marine one, and
places subjected to stress and mechanical shock as often happens in all those places of the heavy industry where safety is a top priority.
The new series has three types of protection 'Ex d', 'Ex e' and 'Ex tb'. It can be also used in Ex i intrinsic
safety circuits. In this case, the cable glands have a part painted light blue.
The evolution of the marking has allowed us to create a transparent polyester label which has stood very
well the various tests of salt corrosion, durability in harsh environments and high temperatures, impact resistance.
In order to ensure a greater security and reliability of its cable glands, Elfit, in addition to mandatory certification tests, submits its products to further harsher tests. It evaluates the resistance of its cable glands to a
traction test without fixing the cable armour and with much higher load values (up
to an extra 50%) than required by the standard.

3 - New Product Technical Data Sheet - REV, REVD series cable glands Rev. 3 - 05/2014

DETAILS OF REV SERIES CABLE GLANDS


FOR UNARMOURED CABLES FROM 3/8 TO 2

CABLE GLAND PARTS

1.
2.
3.
4.

Body
Sealing ring
Compression ring in plastic material
Nut

1
4

ASSEMBLING INSTRUCTIONS

Step 1

Insert on the cable the nut 4 and the compression ring 3

Step 2

Assembly the body 1 and the sealing ring 2 with the equipment

Step 3

After inserting the cable into the sealing ring 2 close by tightening the nut 4

Cable gland properly


assembled

4 - New Product Technical Data Sheet - REV, REVD series cable glands Rev. 3 - 05/2014

MODELS, FEATURES AND DIMENSIONS


REV SERIES CABLE GLANDS FOR UNARMOURED CABLES FROM 3/8 TO 2
Code
REV

Code
REV

Code
REV

Nickelplated
brass

Stainless
Steel

Galvanized
Steel

REV01B
REV1B
REV2B
REV3B
REV4B
REV5B
REV6B
REV01NB
REV1NB
REV2NB
REV3NB
REV4NB
REV5NB
REV6NB
REV01IB
REV1IB
REV2IB
REV3IB
REV4IB
REV5IB
REV6IB

REV01S
REV1S
REV2S
REV3S
REV4S
REV5S
REV6S
REV01NS
REV1NS
REV2NS
REV3NS
REV4NS
REV5NS
REV6NS
REV01IS
REV1IS
REV2IS
REV3IS
REV4IS
REV5IS
REV6IS

REV01G
REV1G
REV2G
REV3G
REV4G
REV5G
REV6G
REV01NG
REV1NG
REV2NG
REV3NG
REV4NG
REV5NG
REV6NG
REV01IG
REV1IG
REV2IG
REV3IG
REV4IG
REV5IG
REV6IG

Thread*

3/8" ISO7/1
1/2" ISO7/1
3/4" ISO7/1
1" ISO7/1
1 1/4 ISO7/1
1 1/2 ISO7/1
2" ISO7/1
3/8" NPT
1/2" NPT
3/4" NPT
1" NPT
1 1/4 NPT
1 1/2 NPT
2" NPT
*M16X1,5
*M20X1,5
*M25X1,5
*M32X1,5
*M40X1,5
*M50X1,5
*M63X1,5

Dimensions mm

Cable Range mm

AC

d min-max

24
24
32
40
48
53
63
24
24
32
40
48
53
63
24
24
32
40
48
53
63/65

28
28
37
47
56
62
73
28
28
37
47
56
62
73
28
28
37
47
56
62
73

44
47
48,5
59,5
60
64
64
45
49
50,5
63,5
64
66
67
45
45
46,5
53,5
54
56
58

5 10
7 12
12 18
18 24
24 30
30 35
35 45
5 10
7 12
12 18
18 24
24 30
30 35
35 45
5 10
7 12
12 18
18 24
24 30
30 35
35 45

* The o-ring for IP protection is provided assembled to the cable gland for parallel threads (ISO metric)

5 - New Product Technical Data Sheet - REV, REVD series cable glands Rev. 3 - 05/2014

MODELS, FEATURES AND DIMENSIONS REVL CABLE GLANDS


SPECIAL VERSION FOR UNARMOURED CABLES FROM 1/2 TO 2
Code
REVL

Code
REVL

Code
REVL

Nickelplated
brass

Stainless
Steel

Galvanized
Steel

REVL1B
REVL2B
REVL3B
REVL4B
REVL5B
REVL6B
REVL1NB
REVL2NB
REVL3NB
REVL4NB
REVL5NB
REVL6NB
REVL1IB
REVL2IB
REVL3IB
REVL4IB
REVL5IB
REVL6IB

REVL1S
REVL2S
REVL3S
REVL4S
REVL5S
REVL6S
REVL1NS
REVL2NS
REVL3NS
REVL4NS
REVL5NS
REVL6NS
REVL1IS
REVL2IS
REVL3IS
REVL4IS
REVL5IS
REVL6IS

REVL1G
REVL2G
REVL3G
REVL4G
REVL5G
REVL6G
REVL1NG
REVL2NG
REVL3NG
REVL4NG
REVL5NG
REVL6NG
REVL1IG
REVL2IG
REVL3IG
REVL4IG
REVL5IG
REVL6IG

Thread*

1/2" ISO7/1
3/4" ISO7/1
1" ISO7/1
1 1/4 ISO7/1
1 1/2 ISO7/1
2" ISO7/1
1/2 NPT
3/4 NPT
1 NPT
1 1/4 NPT
1 1/2 NPT
2 NPT
*M20X1,5
*M25X1,5
*M32X1,5
*M40X1,5
*M50X1,5
*M63X1,5

Dimensions mm

AC1
24
32
40
48
53
63
24
32
40
48
53
63
24
32
40
48
53
63/65

AC2
24
24
32
40
48
53
24
24
32
40
48
53
24
24
32
40
48
53

M1
28
37
47
56
62
73
28
37
47
56
62
73
28
37
47
56
62
73

Cable Range mm

C
47
47
52,5
59,5
62
64
49
49
56,5
63,5
64
67
45
45
46,5
53,5
54
58

d min-max
5 10
7 12
12 18
18 24
24 30
30 35
5 10
7 12
12 18
18 24
24 30
30 35
5 10
7 12
12 18
18 24
24 30
30 35

* The o-ring for IP protection is provided assembled to the cable gland for parallel threads (ISO metric)

6 - New Product Technical Data Sheet - REV, REVD series cable glands Rev. 3 - 05/2014

MODELS, FEATURES AND DIMENSIONS REVF CABLE GLANDS VERSION


FOR UNARMOURED CABLES FROM 3/8 TO 2 WITH A FEMALE THREADED ENTRY
Code
REVF
(female)

Code
REVF
(female)

Code
REVF
(female)

Nickelplated brass

Stainless
Steel

Galvanized
Steel

REVF01B
REVF1B
REVF2B
REVF3B
REVF4B
REVF5B
REVF6B
REVF01NB
REVF1NB
REVF2NB
REVF3NB
REVF4NB
REVF5NB
REVF6NB
REVF01IB
REVF1IB
REVF2IB
REVF3IB
REVF4IB
REVF5IB
REVF6IB

REVF01S
REVF1S
REVF2S
REVF3S
REVF4S
REVF5S
REVF6S
REVF01NS
REVF1NS
REVF2NS
REVF3NS
REVF4NS
REVF5NS
REVF6NS
REVF01IS
REVF1IS
REVF2IS
REVF3IS
REVF4IS
REVF5IS
REVF6IS

REVF01G
REVF1G
REVF2G
REVF3G
REVF4G
REVF5G
REVF6G
REVF01NG
REVF1NG
REVF2NG
REVF3NG
REVF4NG
REVF5NG
REVF6NG
REVF01IG
REVF1IG
REVF2IG
REVF3IG
REVF4IG
REVF5IG
REVF6IG

Thread*

3/8" ISO7/1
1/2" ISO7/1
3/4" ISO7/1
1" ISO7/1
1 1/4 ISO7/1
1 1/2 ISO7/1
2" ISO7/1
3/8" NPT
1/2" NPT
3/4" NPT
1" NPT
1 1/4 NPT
1 1/2 NPT
2" NPT
*M16X1,5
*M20X1,5
*M25X1,5
*M32X1,5
*M40X1,5
*M50X1,5
*M63X1,5

Dimensions mm

AC
M
24
28
24
28
32
37
40
47
48
56
53
62
63
73
24
28
24
28
32
37
40
47
48
56
53
62
63
73
24
28
24
28
32
37
40
47
48
56
53
62
63/65 73

C
69,5
75,5
77
92
92,5
98,5
98,5
68,5
76,5
78
94
95,5
97,5
98,5
70,5
70,5
72
79
79,5
82,5
84,5

Cable Range mm

d min-max
5 10
7 12
12 18
18 24
24 30
30 35
35 45
5 10
7 12
12 18
18 24
24 30
30 35
35 45
5 10
7 12
12 18
18 24
24 30
30 35
35 45

* The o-ring for IP protection is provided assembled to the cable gland for parallel threads (ISO metric)

7 - New Product Technical Data Sheet - REV, REVD series cable glands Rev. 3 - 05/2014

MODELS, FEATURES AND DIMENSIONS REVN CABLE GLANDS VERSION


FOR ARMOURED CABLES FROM 3/8 TO 2 WITH A MALE THREADED ENTRY
Code
REVN
(male)

Code
REVN
(male)

Code
REVN
(male)

Nickel-plated
brass

Stainless
Steel

Galvanized
Steel

REVN01B
REVN1B
REVN2B
REVN3B
REVN4B
REVN5B
REVN6B
REVN01NB
REVN1NB
REVN2NB
REVN3NB
REVN4NB
REVN5NB
REVN6NB
REVN01IB
REVN1IB
REVN2IB
REVN3IB
REVN4IB
REVN5IB
REVN6IB

REVN01S
REVN01G
REVN1S
REVN1G
REVN2S
REVN2G
REVN3S
REVN3G
REVN4S
REVN4G
REVN5S
REVN5G
REVN6S
REVN6G
REVN01NS REVN01NG
REVN1NS REVN1NG
REVN2NS REVN2NG
REVN3NS REVN3NG
REVN4NS REVN4NG
REVN5NS REVN5NG
REVN6NS REVN6NG
REVN01IS REVN01IG
REVN1IS
REVN1IG
REVN2IS
REVN2IG
REVN3IS
REVN3IG
REVN4IS
REVN4IG
REVN5IS
REVN5IG
REVN6IS
REVN6IG

Thread*

3/8" ISO7/1
1/2" ISO7/1
3/4" ISO7/1
1" ISO7/1
1 1/4 ISO7/1
1 1/2 ISO7/1
2" ISO7/1
3/8" NPT
1/2" NPT
3/4" NPT
1" NPT
1 1/4 NPT
1 1/2 NPT
2" NPT
*M16X1,5
*M20X1,5
*M25X1,5
*M32X1,5
*M40X1,5
*M50X1,5
*M63X1,5

Dimensions mm

AC
M
24
28
24
28
32
37
40
47
48
56
53
62
63
73
24
28
24
28
32
37
40
47
48
56
53
62
63
73
24
28
24
28
32
37
40
47
48
56
53
62
63/65 73

C
69,5
75,5
77
92
92,5
98,5
98,5
71,5
79,5
81
100
100,5
102,5
104,5
72,5
66,5
74
82
75,5
77,5
81,5

Cable Range mm

d min-max
5 10
7 12
12 18
18 24
24 30
30 35
35 45
5 10
7 12
12 18
18 24
24 30
30 35
35 45
5 10
7 12
12 18
18 24
24 30
30 35
35 45

* The o-ring for IP protection is provided assembled to the cable gland for parallel threads (ISO metric)

8 - New Product Technical Data Sheet - REV, REVD series cable glands Rev. 3 - 05/2014

DETAILS OF REV/REVS SERIES CABLE GLANDS


FOR UNARMOURED CABLES FROM 2 1/2 TO 4

CABLE GLAND PARTS


1.
2.
3.
4.

Body
Compression gasket
Anti-friction ring
Nut

ASSEMBLING INSTRUCTIONS

Step 1

Insert on the cable the nut 4 and the ring 3

Step 2

Assembly the body 1 and the compression gasket 2 on the electrical equipment

Step 3

After having slipped the cable into the compression gasket 2 close by tightening the nut 4

Cable gland properly assembled

9 - New Product Technical Data Sheet - REV, REVD series cable glands Rev. 3 - 05/2014

MODELS, FEATURES AND DIMENSIONS


REV/REVS SERIES CABLE GLANDS FOR UNARMOURED CABLES FROM 2 1/2 TO 4
Code

Code

REV/REVS

REV/REVS

Nickel-plated
brass

Stainless
Steel

Thread*

Dimensions mm

Cable Range mm

AC1

AC2

d min-max

REV7B
REVS7B
REV8B
REVS8B
REV9B
REVS9B
REV10B
REVS10B
REV7NB
REVS7NB
REV8NB

REV7S
REVS7S
REV8S
REVS8S
REV9S
REVS9S
REV10S
REVS10S
REV7NS
REVS7NS
REV8NS

2 1/2 ISO7/1
2 1/2 ISO7/1
3" ISO7/1
3" ISO7/1
3 1/2 ISO7/1
3 1/2 ISO7/1
4" ISO7/1
4 ISO7/1
2 1/2 NPT
2 1/2 NPT
3" NPT

84
90
100
105
115
120
115
120
84
90
100

73
84
94
98
105
112
105
112
73
84
94

100
100
100
100
101
101
101,5
101,5
110
110
112

46 55
55 62
62 70
70 78
76 84
84 92
76 84
84 92
46 55
55 62
62 70

REVS8NB

REVS8NS

REV9NB
REVS9NB
REV10NB
REVS10NB
REV7IB
REVS7IB
REV8IB
REVS8IB
REV10IB
REVS10IB

REV9NS
REVS9NS
REV10NS
REVS10NS
REV7IS
REVS7IS
REV8IS
REVS8IS
REV10IS
REVS10IS

3" NPT
3 1/2 NPT
3 1/2 NPT
4" NPT
4 NPT
*M75X1,5
*M75X1,5
*M90X1,5
*M90X1,5
*M100X1,5
*M100X1,5

105
115
120
115
120
84
90
100
105
115
120

98
105
112
105
112
73
84
94
98
105
112

112
114
114
115,5
115,5
88
88
88
88
89,5
89,5

70 78
76 84
84 92
76 84
84 92
46 55
55 62
62 70
70 78
76 84
84 92

* The o-ring for IP protection is provided assembled to the cable gland for parallel threads (ISO metric)

10 - New Product Technical Data Sheet - REV, REVD series cable glands Rev. 3 - 05/2014

DETAILS OF REVD SERIES CABLE GLANDS


FOR ARMOURED CABLES FROM 3/8 TO 2

8
1
5

CABLE GLAND PARTS


1. Body
2. Sealing ring
3. Conical metallic compression
ring
4. Metallic compression ring
5. Intermediate Body
6. IP sealing ring on the outer
sheath of the cable
7. Teflon washer
8. Nut

ASSEMBLING INSTRUCTIONS
Step 1

Assembly the body 1 complete with the sealing ring 2 on the equipment.

Step 2

Insert on the cable in sequence the details 8-7-6-5 and pre-assemble the whole
loosely.

Step 3

Insert the compression ring 4 on the cable armour.

Step 4

Open the armour to connect the compression ring 3 with the compression ring 4.

Step 5

Once connected, no sticking out filaments of the armour should remain because
they could interfere with the thread of the body 1. If you experience this problem,
the filaments must be cut to avoid to compromise the final assembly between the
body 1 and the intermediate body 5.

Step 6

Insert the internal sheath into the sealing ring 2 and the two compression rings
previously assembled into the body 1, pulling the cable towards the interior of the
equipment, so that the armour does not spill out by the two compression rings 34.

Step 7

Complete the assembly by tightening the pre-assembled parts (Step 2) on the


body 1 and close the whole system.

Cable gland properly assembled

11 - New Product Technical Data Sheet - REV, REVD series cable glands Rev. 3 - 05/2014

MODELS, FEATURES AND DIMENSIONS


REVD SERIES CABLE GLANDS FOR ARMOURED CABLES FROM 3/8 TO 2
Code

Code

Code

REVD

REVD

REVD

Nickelplated brass
REVD01B
REVD1B
REVD2B
REVD3B
REVD4B
REVD5B
REVD6B
REVD01NB
REVD1NB
REVD2NB
REVD3NB
REVD4NB
REVD5NB
REVD6NB
REVD01IB
REVD1IB
REVD2IB
REVD3IB
REVD4IB
REVD5IB
REVD6IB

Stainless
Steel
REVD01S
REVD1S
REVD2S
REVD3S
REVD4S
REVD5S
REVD6S
REVD01NS
REVD1NS
REVD2NS
REVD3NS
REVD4NS
REVD5NS
REVD6NS
REVD01IS
REVD1IS
REVD2IS
REVD3IS
REVD4IS
REVD5IS
REVD6IS

Galvanized
Steel
REVD01G
REVD1G
REVD2G
REVD3G
REVD4G
REVD5G
REVD6G
REVD01NG
REVD1NG
REVD2NG
REVD3NG
REVD4NG
REVD5NG
REVD6NG
REVD01IG
REVD1IG
REVD2IG
REVD3IG
REVD4IG
REVD5IG
REVD6IG

Thread*

Dimensions mm

Cable Range mm
d min-max
Internal
sheath

3/8" ISO7/1
1/2" ISO7/1
3/4" ISO7/1
1" ISO7/1
1 1/4 ISO7/1
1 1/2 ISO7/1
2" ISO7/1
3/8" NPT
1/2" NPT
3/4" NPT
1" NPT
1 1/4 NPT
1 1/2 NPT
2" NPT
*M16X1,5
*M20X1,5
*M25X1,5
*M32X1,5
*M40X1,5
*M50X1,5
*M63X1,5

AC
24
24
32
40
48
53
63
24
24
32
40
48
53
63
24
24
32
40
48
53
63/65

M
28
28
37
47
56
62
73
28
28
37
47
56
62
73
28
28
37
47
56
62
73

C
69
72
73,5
86,5
89
94
94
70
74
75,5
90,5
93
96
97
70
70
71,5
80,5
83
86
88

5 10
7 12
12 18
18 24
24 30
30 35
35 45
5 10
7 12
12 18
18 24
24 30
30 35
35 45
5 10
7 12
12 18
18 24
24 30
30 35
35 45

D min-max
Outer
sheath of the
cable
8 15
11 16
16 24
24 31
31 37
37 43
43 53
8 15
11 16
16 24
24 31
31 37
37 43
43 53
8 15
11 16
16 24
24 31
31 37
37 43
43 53

* The o-ring for IP protection is provided assembled to the cable gland for parallel threads (ISO metric)

12 - New Product Technical Data Sheet - REV, REVD series cable glands Rev. 3 - 05/2014

MODELS, FEATURES AND DIMENSIONS REVDL CABLE GLANDS


SPECIAL VERSION FOR ARMOURED CABLES FROM 1/2 TO 2
Code
REVDL

Code
REVDL

Code
REVDL

Nickelplated
brass

Stainless
Steel

Galvanized
Steel

REVDL1B
REVDL2B
REVDL3B
REVDL4B
REVDL5B
REVDL6B
REVDL1NB
REVDL2NB
REVDL3NB
REVDL4NB
REVDL5NB
REVDL6NB
REVDL1IB
REVDL2IB
REVDL3IB
REVDL4IB
REVDL5IB
REVDL6IB

REVDL1S
REVDL2S
REVDL3S
REVDL4S
REVDL5S
REVDL6S
REVDL1NS
REVDL2NS
REVDL3NS
REVDL4NS
REVDL5NS
REVDL6NS
REVDL1IS
REVDL2IS
REVDL3IS
REVDL4IS
REVDL5IS
REVDL6IS

REVDL1G
REVDL2G
REVDL3G
REVDL4G
REVDL5G
REVDL6G
REVDL1NG
REVDL2NG
REVDL3NG
REVDL4NG
REVDL5NG
REVDL6NG
REVDL1IG
REVDL2IG
REVDL3IG
REVDL4IG
REVDL5IG
REVDL6IG

Thread*

1/2" ISO7/1
3/4" ISO7/1
1" ISO7/1
1 1/4 ISO7/1
1 1/2 ISO7/1
2" ISO7/1
1/2" NPT
3/4" NPT
1" NPT
1 1/4 NPT
1 1/2 NPT
2" NPT
*M20X1,5
*M25X1,5
*M32X1,5
*M40X1,5
*M50X1,5
*M63X1,5

Dimensions mm

AC1
24
32
40
48
53
63
24
32
40
48
53
63
24
32
40
48
53
63/65

AC2
24
24
32
40
48
53
24
24
32
40
48
53
24
24
32
40
48
53

M1
28
37
47
56
62
73
28
37
47
56
62
73
28
37
47
56
62
73

Cable Range mm

C
72
72
77,5
86,5
91
94
74
74
81,5
90,5
93
97
70
70
71,5
80,5
83
88

d min-max D min-max
Internal
Outer
sheath
sheath of
the cable
5 10
8 15
7 12
11 16
12 18
16 24
18 24
24 31
24 30
31 37
30 35
37 43
5 10
8 15
7 12
11 16
12 18
16 24
18 24
24 31
24 30
31 37
30 35
37 43
5 10
8 15
7 12
11 16
12 18
16 24
18 24
24 31
24 30
31 37
30 35
37 43

* The o-ring for IP protection is provided assembled to the cable gland for parallel threads (ISO metric)

13 - New Product Technical Data Sheet - REV, REVD series cable glands Rev. 3 - 05/2014

DETAILS OF REVD/REVDS SERIES CABLE GLANDS


FOR ARMOURED CABLES FROM 2 1/2 TO 4

CABLE GLAND PARTS


1.
2.
3.
4.
5.
6.
7.

Body
Compression gasket
Anti-friction ring
Armour clamping body
Ring nut
Intermediate body
IP gasket on the outer sheath of
the cable
8. Nut
NOTE: REVDS series cable glands
has a special body (1) to accomodate a wider cable range

ASSEMBLING INSTRUCTIONS
Step 1 Insert on the cable in sequence the details 8-7-6-5-4 and pre-assemble the whole loosely.
Step 2 Fit the body 1 complete with the compression gasket 2 and the anti-friction ring 3 on the equipment.
Step 3 After having slipped the under armour sheath of the cable into compression gasket 2, tighten the
assembly with the armour clamping body 4. Keep the cable pushed towards the inside of the equipment, so that the armour is always in contact with the conical part of the armour tightening section.
Step 4 Push the ring nut 5 on the armour and to the cone (armour clamping body 4). The over armour sheath of the cable must have a maximum distance equal to 2mm from the ring nut 5. Once connected,
no sticking out filaments of the armour should remain because they could interfere with the thread. If
you experience this problem, the filaments must be cut to avoid to compromise the final assembly
between the armour clamping body 4 and the intermediate body 6.
Step 5 Assemble the intermediate body 6 with the armour clamping body 4 and the ring nut 5, while always
keeping the cable pusched towards the inside of the apparatus and ensuring that the armour does
not move away from the locking system.
Step 6 Complete the installation by tightening the upper gasket 7, which was previously inserted into the
intermediate body 6 and locked with nut 8.

Cable gland properly assembled

14 - New Product Technical Data Sheet - REV, REVD series cable glands Rev. 3 - 05/2014

MODELS, FEATURES AND DIMENSIONS


REVD/REVDS SERIES CABLE GLANDS FOR ARMOURED CABLES FROM 2 1/2 TO 4
Code

Code

REVD/
REVDS

REVD/
REVDS

Nickel-plated
Brass

Stainless
Steel

REVD7B
REVDS7B

REVD7S
REVDS7S

2 1/2 ISO7/1
2 1/2 ISO7/1

REVD8B

REVD8S

REVDS8B

Dimensions mm

Thread*

Cable Range mm

AC1

AC2

AC3

AC4

84

105

118

127

185

3" ISO7/1

90
100

105
113

118
130

127
140

REVDS8S

3" ISO7/1

105

113

130

REVD9B

REVD9S

3 1/2 ISO7/1

115

135

144

REVDS9B

REVDS9S

REVD10B
REVDS10B

REVD10S
REVDS10S

3 1/2 ISO7/1
4" ISO7/1
4 ISO7/1

120
115
120

135
135
135

REVD7NB
REVDS7NB

REVD7NS
REVDS7NS

2 1/2 NPT

84

2 1/2 NPT

90

REVD8NB

REVD8NS

REVDS8NB
REVD9NB

REVDS8NS
REVD9NS

3" NPT NPT


3" NPT
3 1/2 NPT

REVDS9NB
REVD10NB

REVDS9NS
REVD10NS

REVDS10NB

REVDS10NS

REVD7IB
REVDS7IB
REVD8IB

REVD7IS
REVDS7IS
REVD8IS

REVDS8IB
REVD10IB

REVDS8IS
REVD10IS

REVDS10IB

REVDS10IS

d min-max D min-max
Internal
Outer
sheath
sheath of the
cable

185
185

46 55
55 62

54 78
54 78

62 70

64 90

140

185

70 78

64 90

153

187

76 84

88 104

144
144
144

153
153
153

187
187,5
187,5

84 92
76 84
84 92

88 104
88 104
88 104

105

118

127

195

46 55

54 78

105

118

127

195

55 62

54 78

100
105
115

113
113
135

130
130
144

140
140
153

197
197
200

62 70
70 78
76 84

64 90
64 90
88 104

3 1/2 NPT
4" NPT
4 NPT

120
115
120

135
135
135

144
144
144

153
153
153

84 92
76 84
84 92

88 104
88 104
88 104

*M75X1,5
*M75X1,5
*M90X1,5
*M90X1,5
*M100X1,5
*M100X1,5

84
90
100
105
115
120

105
105
113
113
135
135

118
118
130
130
144
144

127
127
140
140
153
153

200
201,5
201,5
173
173
173
173
175,5
175,5

46 55
55 62
62 70
70 78
76 84
84 92

54 78
54 78
64 90
64 90
88 104
88 104

* The o-ring for IP protection is provided assembled to the cable gland for parallel threads (ISO metric)

15 - New Product Technical Data Sheet - REV, REVD series cable glands Rev. 3 - 05/2014

TIGHTENING TORQUES TO ENSURE THE CLAMPING OF THE CABLE


Size

Tightening (Nm)

01

20

20

45

50

60

65

65

70

80

90

10

90

STANDARD ACCESSORIES UPON REQUEST


Earthing rings
A series

Lock nuts
DL series

They are used to guarantee


the earthing of the cable
gland and the installed equipment.

They assure the fixing of


cable glands with parallel
thread (isometric).

PVC protectors
PGA... series

Reducers and adaptors


RE series

PGA series protectors are


made in PVC and are used
to offer a further protection
to the cable glands from
the entry of dusts and liquids.

They allow the connection


between different threads or
different sizes.

Plugs PLG... series

Auto-binder tape

They can be used to temporarly close not necessary entries.

Tape for the mechanical


protection adaptable to all
sizes of the cable glands.

Serrated internal washer


Serrated or shake-proof washers act as an anti-vibration device to
prevent the cable gland from loosening. It can be also used as an
earth enhancing devise on painted enclosures.

16 - New Product Technical Data Sheet - REV, REVD series cable glands Rev. 3 - 05/2014

TABLE OF ACCESSORIES UPON REQUEST


CABLE
GLANDS
SERIES
PROTECTORS
01
1
2
L2
3
L3
4
L4
5
L5
6
L6

CABLE GLAND CODE


REV REVD REVL REVDL 01
REV REVD REVL REVDL 1
REV REVD 2
REVL REVDL 2
REV REVD 3
REVL REVDL 3
REV REVD 4
REVL REVDL 4
REV REVD 5
REVL REVDL 5
REV REVD 6
REVL REVDL 6

LOCK NUTS FOR METRIC CABLE GLANDS


REV REVD REVL REVDL REVF REVN 01I
01
REV REVD REVL REVDL REVF REVN 1I
1
REV REVD REVL REVDL REVF REVN 2I
2
REV REVD REVL REVDL REVF REVN 3I
3
REV REVD REVL REVDL REVF REVN 4I
4
REV REVD REVL REVDL REVF REVN 5I
5
REV REVD REVL REVDL REVF REVN 6I
6
EARTHING RINGS Thread ISO 261
REV REVD REVL REVDL REVF REVN 01I
01
REV REVD REVL REVDL REVF REVN 1I
1
REV REVD REVL REVDL REVF REVN 2I
2
REV REVD REVL REVDL REVF REVN 3I
3
REV REVD REVL REVDL REVF REVN 4I
4
REV REVD REVL REVDL REVF REVN 5I
5
REV REVD REVL REVDL REVF REVN 6I
6
SERRATED INTERNAL WASHER Thread ISO 261
REV REVD REVL REVDL REVF REVN 01I
01
REV REVD REVL REVDL REVF REVN 1I
1
REV REVD REVL REVDL REVF REVN 2I
2
REV REVD REVL REVDL REVF REVN 3I
3
REV REVD REVL REVDL REVF REVN 4I
4
REV REVD REVL REVDL REVF REVN 5I
5
REV REVD REVL REVDL REVF REVN 6I
6

ACCESSORIES ACCESSORIES ACCESSORIES


CODE
CODE
CODE
BLACK PVC
PGA1F
PGA1F
PGA2R
PGA1F
PGA3
PGA2R
PGA4
PGA3
PGA5
PGA4
PGA6R
PGA5
Nickel-plated
brass
DL01IB
DL1IB
DL2IB
DL3IB
DL4IB
DL5IB
DL6IB
Nickel-plated
brass
A0131B
A1311IB
A2312IB
A3313IB
A4314IB
A5315IB
A6316IB
Stainless steel
RDI01IS/A4
RDI1IS/A4
RDI2IS/A4
RDI3IS/A4
RDI4IS/A4
RDI5IS/A4
RDI6IS/A4

Galvanized Steel
DL01IG
DL1IG
DL2IG
DL3IG
DL4IG
DL5IG
DL6IG
Stainless steel
A0131S
A1311IS
A2312IS
A3313IS
A4314IS
A5315IS
A6316IS

MORE ACCESSORIES UPON REQUEST

17 - New Product Technical Data Sheet - REV, REVD series cable glands Rev. 3 - 05/2014

Stainless steel
DL01IS
DL1IS
DL2IS
DL3IS
DL4IS
DL5IS
DL6IS

OTHER ACCESSORIES RECOMMENDED


Sealant for threads
The Loctite 577 (or a product of equal or
superior characteristics) must be used on
the threaded entry of NPT and ISO 7/1 cable gland to ensure a better IP seal. It
should be applied, covering at least 2 full
threads, only on the tapered thread.

APPLICATION EXAMPLES
Cortem aluminium junction box EJB-4 series complete with:

n2 REV5NB

n. 4 PLG2NB

n 1 REVD6NB

Lighting fixtures FLFE-258 complete with:

n2 REV2IB
18 - New Product Technical Data Sheet - REV, REVD series cable glands Rev. 3 - 05/2014

n 7 REVD2NB

ATEX REFERENCE STANDARDS


ATEX 94/9/CE

Equipment for explosive atmospheres

EN 60079-0:2012

Electrical apparatus for explosive gas atmospheres


Part 0: General Requiremets

EN60079-1:2007

Electrical apparatus for explosive gas atmospheres


Part 1: Flameproof enclosures d

EN 60079-7:2007

Electrical apparatus for explosive gas atmospheres


Part 7: Incresed safety e

EN 60079-31:2009

Explosive atmospheres
Part 31: Equipment dust ignition protection by enclosure "t"

EN 60529:1991

Degrees of protection provided by enclosures (IP Code)

IECEX REFERENCE STANDARDS


IEC 60079-0:2011

Electrical apparatus for explosive gas atmospheres


Part 0: General Requiremets

IEC 60079-1:2007

Electrical apparatus for explosive gas atmospheres


Part 1: Flameproof enclosures d

IEC 60079-7:2006

Electrical apparatus for explosive gas atmospheres


Part 7: Incresed safety e

IEC 60079-31:2008

Explosive atmospheres
Part 31: Equipment dust ignition protection by enclosure "t"

IEC 60529:2001

Degrees of protection provided by enclosures (IP Code)

APPLICATION
Manufacturing plants and process facilities:
chemical, petrochemical, refineries, pharmaceutical, Gas treatment and transport
Areas with risk of explosion and fire due to
abnormal, unusual or accidental presence of
ignitable concentration of gases/vapours and
dusts, even simultaneously
On-shore, off-shore, naval and harbour installations
Waste and or sewage treatment facilities
Thermal plants
Area with presence of combustible dusts such
as joineries, sugarhouses, food industries with
treatment and storage of wheat and derivatives
Painting plants

MARKET

Industry
Mechanical and electrical engineering
Agribusiness
Distillery
Oil & Gas industries
Pharmaceutical industries
Energy
Engineering and Contractors
Project Design companies
Electrical contractors
Construction companies
Electrical equipment distributors
Shipyards / harbours
Off-shore rig constructors
On-shore treatment and refining plants

19 - New Product Technical Data Sheet - REV, REVD series cable glands Rev. 3 - 05/2014

ELFIT S.P.A.

CORTEM S.P.A.

HEADQUARTERS AND FACTORY


Via Aquileia 12, 34070 Villesse (GO), ITALY
Tel +39 0481 964911
Fax +39 0481 964999
info@elfit.com
vendite@elfit.com

HEADQUARTERS AND FACTORY


Via Aquileia 10, 34070 Villesse (GO), ITALY
Tel +39 0481 964911
Fax +39 0481 964999
info@cortemgroup.com

www.cortemgroup.com

SALES OFFICES
P.le Dateo 2, 20129 Milano ITALIA
Tel +39 02 761100501
Fax +39 02 70005471
export@cortemgroup.com
www.cortemgroup.com

20 - New Product Technical Data Sheet - REV, REVD series cable glands Rev. 3 - 05/2014