Professional Documents
Culture Documents
AbstractThe
integration
of
renewable
energy
resources (RESs) in power systems poses many research
challenges. Research shows that the RES output may exceed the
consumed power during the day. Consequently, the direction
of the power flow on distribution lines can be reversed during
some periods. As the voltage regulator is normally designed for
unidirectional power flow, this may cause voltage violations on
the distribution feeder. Therefore, most utilities try to set a penetration level (PL) limit for safe operation. On the other hand,
time varying and unbalanced loading are the main characteristics of distribution systems. Moreover installation of intermittent
and nondispatchable photovoltaic (PV) devices increases the
control problems of distribution system. This paper presents an
impedance-based monitoring method for detection of distribution
system current behavior. It will be shown that by utilizing this
monitoring technique, not only the small variation of PV PL can
be easily detected, but also some fast transients such as the effect
of cloud movement on PV system can be monitored. This monitoring technique employs only local measurements of bus voltages
and line current to measure the apparent impedance seen at
the installation point. The practical application of measured
impedance as a monitoring technique shows its effectiveness for
distribution system monitoring in presence of various PV PL.
Index TermsMonitoring, photovoltaic (PV) penetration,
reverse power flow, smart grid, voltage control.
I. I NTRODUCTION
EREGULATION of power system, smart grid, electric
vehicle, and renewable energy integration pose a lot of
challenges to power systems operation. Although a lot of monitoring and protection devices are installed in transmission
system due to its complexity, traditional distribution systems
suffer lack of monitoring systems due to its high number of
feeders and load points.
Distribution systems have been designed for radial and
unidirectional power flows. In this design the active and
reactive power are transferred from the transmission system
c 2015 IEEE. Personal use is permitted, but republication/redistribution requires IEEE permission.
1949-3053
See http://www.ieee.org/publications_standards/publications/rights/index.html for more information.
This article has been accepted for inclusion in a future issue of this journal. Content is final as presented, with the exception of pagination.
2
Vi
VR + jVX
= P jQ
Li
Li
Ii
Zi =
Vi
(9)
Vi
A=
VR + jVX
2
(PLi + jQLi )
PLi + Q2Li
Vi
P2Li + Q2Li
Zi = A (VR + jVX ) (PLi + jQLi )
Zi = A (VR PLi VX QLi ) + j(PLi V X + VR QLi ) .
(10)
(11)
(12)
(13)
For node i, let Piload and Qiload be the active and reactive power of load, PLiloss and QLiloss be the active and
reactive losses of the line, and PiRES , QDiRES denote the
active and reactive generation of RES at node i, respectively.
This article has been accepted for inclusion in a future issue of this journal. Content is final as presented, with the exception of pagination.
MORTAZAVI et al.: MONITORING TECHNIQUE FOR REVERSED POWER FLOW DETECTION WITH HIGH PV PL
i+1
n
QL(i+1)
(15)
i+1
Pi = Piload PiRES
Qi = Qiload QiRES.
(16)
(17)
(18)
PLi +jQLi
Ii
Vi
PLi + jQLi
(21)
Zi =
|Vi |2 .
P2Li + Q2Li
The real and the imaginary parts of the measured impedance
shown in (21) are written as
PLi
Ri =
(22)
|Vi |2
P2Li + Q2Li
QLi
Xi =
(23)
|Vi |2 .
P2Li + Q2Li
As it can be seen from (22) and (23), the position of measured apparent impedance in R X plane depends on the
Fig. 2.
This article has been accepted for inclusion in a future issue of this journal. Content is final as presented, with the exception of pagination.
4
Fig. 3.
Fig. 4. Active power flows through feeder 650-632 and bus 632 voltage
profile with active tap changer and PV is connected to bus 680.
zero to 1.15 p.u. of model total load (P = 3800 kW) with step
size of 0.01 (115 different PLs). At each step, a power flow
was done by OpenDSS and all voltages, currents, and active
and reactive power of feeder were saved. In this paper, except
the under voltage and over voltage limits, other limiting factors such as feeders current rating, the substation transformer
capacity, power quality issues were neglected. The simulation
has been performed for both unit and nonunit pf PV operation.
As the original model of IEEE 13 node test feeder does not
have a load at bus 680 a 360 kW and 270 kvar load connected
to this bus for simulation. A three-phases 60 kvar capacitor
installed at bus 680 for voltage regulation.
IV. S IMULATION R ESULT AND D ISCUSSION
A. Impact of PV PL on Measured Impedance
To show the impact of PV PL the lumped model of PV is
connected to bus 680. Fig. 4 shows the active power flows
through feeder 650-632 and bus 632 voltage profile. As it
can be seen, by increasing PL the active power flow from
the source to grid decreases and the voltage increases. It is
obvious that by increasing the PL the voltage increases, so
the tap changer located between buses 650 and 632 operates
two times to keep the voltage within the standard boundaries.
Fig. 5 shows the measured R and X for different PLs at
bus 632. As it can be seen by increasing PL, the R and X
increase till PL = 0.58 but after this point although X increases
the R decreases. At PL = 88% the R becomes zero and
after this point the R goes negative corresponding the reversed
active power. The reason for the decreasing R is related to the
relationship between the measured R and total P and Q flows
along the line. Based on (22) by decreasing the P-due to the
increased PV PLthe measured R will decrease too.
As it can be seen from Figs. 4 and 5, at the time of
tap changing the measured impedance shows a little change.
This illustrates that the proposed method is sensitive to small
variations of voltage in the system.
Unlike at bus 632, the measured impedance at bus 680 has
a different trend. As it can be seen from Fig. 6 the measured R and X increases by increasing PV PL, but, when the
active power direction is reversed, the value of R decreases
and becomes negative. This shows that, we have reverse active
This article has been accepted for inclusion in a future issue of this journal. Content is final as presented, with the exception of pagination.
MORTAZAVI et al.: MONITORING TECHNIQUE FOR REVERSED POWER FLOW DETECTION WITH HIGH PV PL
PL=108%
PL=80%
PL=20%
(a)
PL=93%
PL=80%
PL=20%
(b)
PL=9%
Fig. 6.
PL=20%
PL=100%
(c)
Fig. 7. Measured impedance at buses 632, 671, and 680 for PV installed
at bus 680 and PL varies from zero to 115%. (a) Measured impedance at
bus 632-phase A. (b) Measured impedance at bus 671-phase A. (c) Measured
impedance at bus 680-phase A.
This article has been accepted for inclusion in a future issue of this journal. Content is final as presented, with the exception of pagination.
6
PL=88%
PL=108%
PL=111%
Fig. 8.
Fig. 10.
Fig. 9.
Three-phases measured impedance at bus 632 for normal load
variation condition.
Fig. 12. Measured impedance at buses 632, 671, and 680 for PV installed
at bus 671.
This article has been accepted for inclusion in a future issue of this journal. Content is final as presented, with the exception of pagination.
MORTAZAVI et al.: MONITORING TECHNIQUE FOR REVERSED POWER FLOW DETECTION WITH HIGH PV PL
Fig. 13. Measured impedance at bus 632-phase A, for three different load
pfs connected to bus 671.
This article has been accepted for inclusion in a future issue of this journal. Content is final as presented, with the exception of pagination.
8
Fig. 16.
Fig. 15. Measured impedance at bus 632 for three-phase to ground fault at
bus 671. The small red circle is a nondirectional impedance relay.
Fig. 17. Voltage and active power variation at bus 632 for PV installed at
bus 680 while cloud passing transients.
This article has been accepted for inclusion in a future issue of this journal. Content is final as presented, with the exception of pagination.
MORTAZAVI et al.: MONITORING TECHNIQUE FOR REVERSED POWER FLOW DETECTION WITH HIGH PV PL
Fig. 18.
Fig. 21. IEEE 34 node test feeder. Nine 200 kW PV unit installed at yellow buses. The location and direction of four impedance measuring units are
shown by red arrow [38].
Fig. 19.
Fig. 20.
This article has been accepted for inclusion in a future issue of this journal. Content is final as presented, with the exception of pagination.
10
Fig. 23. Alarm issued for reversed active power at different buses (phase A).
Fig. 24. Alarm issued for reversed active and reactive power at different
buses (phase C).
This article has been accepted for inclusion in a future issue of this journal. Content is final as presented, with the exception of pagination.
MORTAZAVI et al.: MONITORING TECHNIQUE FOR REVERSED POWER FLOW DETECTION WITH HIGH PV PL
11
[25] C. R. Mason, The Art and Science of Protective Relaying. Hoboken, NJ,
USA: Wiley, 1956.
[26] Y. Hase, Handbook of Power System Engineering. Hoboken, NJ, USA:
Wiley, 2007.
[27] H. Shateri and S. Jamali, Measured impedance by distance relay elements applied on a distribution feeder in a single phase to ground fault,
in Proc. IEEE/PES Power Syst. Conf. Expo. (PSCE), Seattle, WA, USA,
2009, pp. 17.
[28] W. H. Kersting, Distribution System Modeling and Analysis. Boca Raton,
FL, USA: CRC Press, 2012.
[29] R. C. Dugan, Reference Guide: The Open Distribution System
Simulator (OpenDSS), Elect. Power Res. Inst. Inc., Palo Alto, CA, USA,
2012.
[30] Using Matlab Version 5 Guide, The Mathworks, Inc., Natick, MA, USA,
vol. 5, 1998.
[31] A. Hoke, R. Butler, J. Hambrick, and B. Kroposki, Steady-state analysis of maximum photovoltaic penetration levels on typical distribution
feeders, IEEE Trans. Sustain. Energy, vol. 4, no. 2, pp. 350357,
Apr. 2013.
[32] H. Vahedi, K. Al-Haddad, Y. Ounejjar, and K. Addoweesh, Crossover
switches cell (CSC): A new multilevel inverter topology with maximum
voltage levels and minimum DC sources, in Proc. 39th Annu. Conf.
IEEE Ind. Electron. Soc. (IECON), Vienna, Austria, 2013, pp. 5459.
[33] Requirements for the Interconnection of Distributed Generation to the
Hydro-Qubec Medium-Voltage Distribution System (Between 750 V to
44000 V), Hydro-Qubec Standard E.12-01, 2004.
[34] Distributed Generation Technical Interconnection Requirements
Interconnections at Voltages 50 kv and Below, Rev. 3, Hydro One
Networks Inc. Standard DT-10-015, 2013.
[35] R. C. Dugan and T. E. McDermott, An open source platform for collaborating on smart grid research, in Proc. IEEE Power Energy Soc.
Gen. Meeting, San Diego, CA, USA, 2011, pp. 17.
[36] T. Godfrey et al., Modeling smart grid applications with co-simulation,
in Proc. 1st IEEE Int. Conf. Smart Grid Commun. (SmartGridComm),
Gaithersburg, MD, USA, 2010, pp. 291296.
[37] K. Christakou, J. LeBoudec, M. Paolone, and D. C. Tomozei, Efficient
computation of sensitivity coefficients of node voltages and line currents
in unbalanced radial electrical distribution networks, IEEE Trans. Smart
Grid, vol. 4, no. 2, pp. 741750, Jun. 2013.
[38] S. Shafiee, M. Fotuhi-Firuzabad, and M. Rastegar, Investigating the
impacts of plug-in hybrid electric vehicles on power distribution
systems, IEEE Trans. Smart Grid, vol. 4, no. 3, pp. 13511360,
Sep. 2013.
This article has been accepted for inclusion in a future issue of this journal. Content is final as presented, with the exception of pagination.
12
Dalal Asber received the B.Sc. degree in electrical engineering from the University of Damascus,
Damascus, Syria, in 1979, and the M.Sc. and Ph.D.
degrees in automatic control from Institut National
Polytechnique, Nancy, France, in 1988 and 1991,
respectively.
She was a Post-Doctoral Researcher at cole
de Technologie Suprieure, Montreal, QC, Canada.
In 1993, she joined the Hydro-Quebec Research
Institute, Varennes, QC, where she was involved in
power system modeling, simulation, and control.
Laurent Lenoir (M06) received the B.Sc. degree in electrical engineering from cole Suprieure dIngnieurs en lectrotechnique et lectronique
dAmiens, Amiens, France; the M.Sc.A. degree from cole Polytechnique de
Montral, Montreal, QC, Canada; and the Ph.D. degree in electrical engineering from cole de Technologie Suprieure, Montreal, in 2001, 2004, and 2009,
respectively.
He was at Hydro-Quebec Research Institute, Varennes, QC, where he was
involved in power system operation in distribution and transmission networks,
and evolution of the networks toward a smart grid.