Tank Vent Sizing & Selection Report


16-ene-2014

Venezuela
+58-212-9440966
rdiaz@controval.com
Quote Number:

No

Prpd. Chk. Appr.

Date

Revision

Client: PDVSA GAS


Location: ESTACION FLUJO CHIMIRE 6 (CHEF-6)

End-User Ref. No.:

Project: FACILIDADES DE PRODUCCION CHIMIRE


1

Project Ref. No.: DB410901


41

Valve ID

SIZING DATA
Non-Code

Tag No. PSV-300200

42

Design Code

Service AlivioTanque de Prueba TK-02

43

Sizing Basis

PID No. DB410301-EF1D3-PP03007

44

Fluid State at Inlet

Gas / Vapor

Line No. TK-02

45

Relieving Case

Pressure & Vacuum Relief

5
6
7

Quantity
1

GENERAL
Weight Loaded Tank Vent - Vent to Atm.

Valve Type

46
47

System Conditions
Operating Pressure

48
49

MAWV

10

50

Atmospheric Pressure

51

Operating Temperature

12

Inlet

4"

13

Outlet

Vent

14

CONNECTIONS
FF
150#
To

Standard

52

Min. Design Temperature

ANSI B16.5

53

Max. Design Temperature

Drilling

Atm.

0 psig

14.696 psia

MATERIALS OF CONSTRUCTION
Body
Aluminum

54

16

Trim

Aluminum

56

Molecular Weight, M

17

Trim Coating

None

57

Compressibility, Z

0.989

18

Insert

Buna-N

58

Ratio of Sp. Heats, k (Cp / Cv)

1.148

19

Gaskets

Buna-N

59

Subsonic Flow Factor, Fs

20

O-ring

Buna-N

60

Pressure Set

0.25 psig

21

Screen

304 SST

61

Over Pressure

0.025 psig

22

Retainer

316 SST

62

Built-Up

0 psig

23

Pressure Range

Low Pressure Setting

63

Constant

0 psig

24

Vacuum Range

Low Pressure Setting

Variable Superimposed

0 psig

25

Spring

15

Pressure Relief Conditions


Fluid Name
Natural Gas (SG=0.6)

55

Back
64 Pressure
65

Total

26

66

Inlet Loss

27

67

Relieving Temperature

28

68

29

69

30

70

31

Valve Model No.

32

Brand

33
34

Required Flow

35

Max. Flow per Valve

36

Total Selected Flow

37

SIZING / SELECTION
2010B41BFFBS0202

71

Vacuum Relief Conditions


Fluid Name

37.142

0.134

0 psig
0 psig
101.1 F

Air

Molecular Weight, M

28.970

72

Compressibility, Z

1.000

Pressure Case
0.111 MMSCFD

73

Ratio of Sp. Heats, k (Cp / Cv)

1.400

74

Subsonic Flow Factor, Fs

0.784 MMSCFD

75

Pressure Set

Varec

API2000

MAWP

9
11

Sizing Std.

Blocked Discharge

0.784 MMSCFD

76

Under Pressure

Vacuum Case
0.111 MMSCFD

77

Relieving Temperature

Required Flow

39

Max. Flow per Valve

0.189 MMSCFD

79

Estimated Reaction Force

40

Total Selected Flow

0.189 MMSCFD

80

Estimated Noise Level (db)

0.084 in wc g
101.1 F

78
56.9 at 100-ft

Tag Notes

38

0.048
0.84 in wc g

Printed On: 25-mar-2014

Pentair PRVSIZE Software Version pr5_20131223.1

Page : 1

Pentair Valves & Controls and its parent, subsidiaries, and affiliates assume no liability in any way whatsoever for any direct or indirect loss or damage through the application of this software. See terms of license
agreement. Not for resale. All rights reserved. All trademarks, trade names and/or registered trademarks referred to in this program are the property of their respective owners. Copyright 2014 Pentair Valves & Controls.

CONTROVAL
Edif. 446A, Calle San Rafael c/

Pressure Relief Valve Calculation Report


16-ene-2014

Venezuela
+58-212-9440966
rdiaz@controval.com
Quote Number:

No

Prpd. Chk. Appr.

Date

Revision

Client: PDVSA GAS


Location: ESTACION FLUJO CHIMIRE 6 (CHEF-6)

End-User Ref. No.:

Project: FACILIDADES DE PRODUCCION CHIMIRE


1

Tag No. PSV-300200

Valve Model No. 2010B41BFFBS0202

4
6

VALVE ID

Project Ref. No.: DB410901

Qty. 1

9
10

CALCULATION SUMMARY
Flow

CALCULATION NOTES

Required

0.111 MMSCFD

11

Max. Flow per Valve

0.784 MMSCFD

12

PRESSURE CONDITION
Variable Type

Variable Name

Fluid Properties

Molecular Weight

37.142

37.142

Ratio of Specific Heats

1.148

1.148

Compressibility

0.989

Process Cond.

Symbol

Required Volumetric Flow

Vreq

Set Pressure

Valve Data

Input Value

0.111 MMSCFD

Equation Value

0.989
4625.000 SCFH

Pset

0.25 psig

0.25 psig

Over Pressure

Pover

0.025 psig

0.025 psig

Atmospheric Pressure

Patm

14.696 psia

Relieving Temperature

101.1 F

14.696 psia
560.770 R

Distance from Valve (noise)

100 ft

100 ft

Maximum Flow Coefficient

Kmax

0.97

0.97

Transition to Full Open

Tp

1.75

1.75

Shape Factor

0.16

Orifice Area

12.73 in

0.16
12.73 in

Calculate Inlet Relieving Pressure, Outlet Pressure, Absolute Pressure Ratio


P1 = Pset + Pover + Patm

P1

14.971 psia

P2 = Patm

P2

14.696 psia

PR = P2 / P1

PR

0.982

Fs

0.134

0.1

Calculate Sub-Critical Flow Factor


Fs = {[k / (k - 1)] * [PR^(2 / k) - PR^((k+1)/k)]}^0.5
Calculate Over Pressure Ratio
X = Pover / Pset
Calculate Discharge Coefficient

0.659

Kd

If X > Tp, then Kd = Kmax, else Kd = Kmax * {sin[(X / Tp) * ( / 2)]}^E


Calculate Volumetric Flow

0.784 MMSCFD

32676.998 SCFH

V = 278700 * Kd * A * P1 * Fs / (M * T * Z)^0.5
Calculate Required Orifice Area

Areq

1.802 in

1.802 in

Areq = A * Vreq / V
Calculate Mass Flow (for Noise Calc)

3198.257 lb/hr

W = 735 * Kd * A * P1 * Fs * [M / (T * Z)]^0.5
Calculate Noise Level at 100-ft (30-m)

L100

56.9 db

L100 = [87.75 * log( 1/PR ) + 14.09] + [10 * log(0.29354 * W * k * T / M)]

Printed On: 25-mar-2014

Pentair PRVSIZE Software Version pr5_20131223.1

Page : 2

Pentair Valves & Controls and its parent, subsidiaries, and affiliates assume no liability in any way whatsoever for any direct or indirect loss or damage through the application of this software. See terms of license
agreement. Not for resale. All rights reserved. All trademarks, trade names and/or registered trademarks referred to in this program are the property of their respective owners. Copyright 2014 Pentair Valves & Controls.

CONTROVAL
Edif. 446A, Calle San Rafael c/

Pressure Relief Valve Calculation Report


16-ene-2014

Venezuela
+58-212-9440966
rdiaz@controval.com
Quote Number:

No

Prpd. Chk. Appr.

Date

Revision

Client: PDVSA GAS


Location: ESTACION FLUJO CHIMIRE 6 (CHEF-6)

End-User Ref. No.:

Project: FACILIDADES DE PRODUCCION CHIMIRE


1

Tag No. PSV-300200

Valve Model No. 2010B41BFFBS0202

4
6

VALVE ID

Project Ref. No.: DB410901

Qty. 1

9
10

CALCULATION SUMMARY
Flow

Required

0.111 MMSCFD

11

Max. Flow per Valve

0.784 MMSCFD

12

Calculate Noise Level at Distance, r

CALCULATION NOTES

Lp

56.9 db

Lp = L100 - 20 * log(r / 100)

Printed On: 25-mar-2014

Pentair PRVSIZE Software Version pr5_20131223.1

Page : 3

Pentair Valves & Controls and its parent, subsidiaries, and affiliates assume no liability in any way whatsoever for any direct or indirect loss or damage through the application of this software. See terms of license
agreement. Not for resale. All rights reserved. All trademarks, trade names and/or registered trademarks referred to in this program are the property of their respective owners. Copyright 2014 Pentair Valves & Controls.

CONTROVAL
Edif. 446A, Calle San Rafael c/

Pressure Relief Valve Calculation Report


16-ene-2014

Venezuela
+58-212-9440966
rdiaz@controval.com
Quote Number:

No

Prpd. Chk. Appr.

Date

Revision

Client: PDVSA GAS


Location: ESTACION FLUJO CHIMIRE 6 (CHEF-6)

End-User Ref. No.:

Project: FACILIDADES DE PRODUCCION CHIMIRE


1

Tag No. PSV-300200

Valve Model No. 2010B41BFFBS0202

4
6

VALVE ID

Project Ref. No.: DB410901

Qty. 1

9
10

CALCULATION SUMMARY
Flow

CALCULATION NOTES

Required

0.111 MMSCFD

11

Max. Flow per Valve

0.189 MMSCFD

12

VACUUM CONDITION
Variable Type

Variable Name

Fluid Properties

Molecular Weight

28.970

28.970

Ratio of Specific Heats

1.400

1.400

Compressibility

1.000

Process Cond.

Symbol

Required Volumetric Flow

Vreq

Set Pressure

0.111 MMSCFD

Vset

0.84 in wc g

Over Pressure

Vover

0.084 in wc g

Atmospheric Pressure

Patm

14.696 psia

101.1 F

Relieving Temperature
Valve Data

Input Value

Maximum Flow Coefficient

Kmax

0.64

Equation Value

1.000
4625.000 SCFH
0.030 psig
0.003 psig
14.696 psia
560.770 R
0.64

Transition to Full Open

Tp

Shape Factor

0.18

0.18

Orifice Area

12.73 in

12.73 in

Calculate Inlet Relieving Pressure, Outlet Pressure, Absolute Pressure Ratio


P1 = Patm

P1

14.696 psia

P2 = Patm - Vset - Vover

P2

14.663 psia

PR = P2 / P1

PR

0.998

Fs

0.048

0.1

Calculate Sub-Critical Flow Factor


Fs = {[k / (k - 1)] * [PR^(2 / k) - PR^((k+1)/k)]}^0.5
Calculate Over Pressure Ratio
X = Vover / Vset
Calculate Discharge Coefficient

0.405

Kd

If X > Tp, then Kd = Kmax, else Kd = Kmax * {sin[(X / Tp) * ( / 2)]}^E


Calculate Volumetric Flow

0.189 MMSCFD

7882.040 SCFH

V = 278700 * Kd * A * P1 * Fs / (M * T * Z)^0.5
Calculate Required Orifice Area

Areq

7.47 in

7.47 in

Areq = A * Vreq / V

Printed On: 25-mar-2014

Pentair PRVSIZE Software Version pr5_20131223.1

Page : 4

Pentair Valves & Controls and its parent, subsidiaries, and affiliates assume no liability in any way whatsoever for any direct or indirect loss or damage through the application of this software. See terms of license
agreement. Not for resale. All rights reserved. All trademarks, trade names and/or registered trademarks referred to in this program are the property of their respective owners. Copyright 2014 Pentair Valves & Controls.

CONTROVAL
Edif. 446A, Calle San Rafael c/

Pressure Relief Valve Dimensional Drawing


16-ene-2014

Venezuela
+58-212-9440966
rdiaz@controval.com
Quote Number:

No

Prpd. Chk. Appr.

Date

Revision

Client: PDVSA GAS


Location: ESTACION FLUJO CHIMIRE 6 (CHEF-6)

End-User Ref. No.:

Project: FACILIDADES DE PRODUCCION CHIMIRE


1

Project Ref. No.: DB410901


7

Valve ID

SELECTION SUMMARY

Tag No. PSV-300200

Valve Model No.

2010B41BFFBS0202

Service AlivioTanque de Prueba TK-02

Brand

Varec

PID No. DB410301-EF1D3-PP03007

10

Line No. TK-02

2
3

11

Inlet

4"

12

Outlet

Vent

Drilling

FF

Standard

Atm.

To

ANSI B16.5

28.20 lb

12.79 kg

A=

19.13 in

485.90 mm

B=

13.38 in

339.85 mm

C=

14.5 in

368.30 mm

D=

12.44 in

315.98 mm

E=

F=

G=

H=

Tag Notes
Printed On: 25-mar-2014

150#

Wt.=

Dimension Notes

CONNECTIONS

Quantity

Pentair PRVSIZE Software Version pr5_20131223.1

Accessories not shown.


Weight and dimensions shown
are approximate.
Actual valve may vary from.
image.

Page : 5

Pentair Valves & Controls and its parent, subsidiaries, and affiliates assume no liability in any way whatsoever for any direct or indirect loss or damage through the application of this software. See terms of license
agreement. Not for resale. All rights reserved. All trademarks, trade names and/or registered trademarks referred to in this program are the property of their respective owners. Copyright 2014 Pentair Valves & Controls.

Pentair PRVSIZE Software


Brand:

Varec

Printed On: 25-mar-2014

Valve Type:

4" 2010B

Pentair PRVSIZE Software Version pr5_20131223.1

Page : 6

Pentair Valves & Controls and its parent, subsidiaries, and affiliates assume no liability in any way whatsoever for any direct or indirect loss or damage through the application of this software. See terms of license
agreement. Not for resale. All rights reserved. All trademarks, trade names and/or registered trademarks referred to in this program are the property of their respective owners. Copyright 2014 Pentair Valves & Controls.

Pentair PRVSIZE Software


Summary Report
Project Information
Company:
Location:

PDVSA GAS
ESTACION FLUJO CHIMIRE 6 (CHEF-6)

Project:
Project Ref. No.:

FACILIDADES DE PRODUCCION CHIMIRE


DB410901

Tag Information
Tag Number:
Revision:
Prepared By:

PSV-300200
Last Modified:
Checked By:

16/01/2014 12:55:28 p.m.


Approved By:

Specific Tank Data


Sized Using User Defined Flow
Pressure Fluid:
Natural Gas (SG=0.6)
Pressure Set Point:
0.25 psig
Allowed Over Pressure:
0.025 psig
Pressure Flow Rate:
0.111

Product in Tank:
Vacuum Fluid:
Vacuum Set Point:
Allowed Under Pressure:
Vacuum Flow Rate:

Crudo
Air
0.84 in wc g
0.084 in wc g
0.111

Valve Sizing Information


Valve Type:
2010B, 4"
Part Number: 2010B41BFFBS0202
Max Pressure Flow Capacity:
0.784 MMSCFD

Quantity to Order:
1
Max Vacuum Flow Capacity:

0.189 MMSCFD

Selected Valve Description


Code
201
0
B
4
1
B
F
F
B
S
02
02

Category
Style1
Trim Coating
Style2
Size
Body Trim
Insert
Flange Drilling
Flange Face
Gaskets
Screen Retainer
Pressure Range
Vacuum Range

Printed On: 25-mar-2014

Description
Pressure & Vacuum Relief, Vented Pressure Outlet
Air Cushion Seating
Weight Loaded Modular
4"
Alum Body / Alum Trim
BUNA-N
ANSI 150# Drilling & Fractional Studs
FF Flange
BUNA-N Gasket / BUNA-N O-Ring
304 SST Screen / 316 SST Retainer
Low Pressure Setting
Low Vacuum Setting

Pentair PRVSIZE Software Version pr5_20131223.1

Page : 7

Pentair Valves & Controls and its parent, subsidiaries, and affiliates assume no liability in any way whatsoever for any direct or indirect loss or damage through the application of this software. See terms of license
agreement. Not for resale. All rights reserved. All trademarks, trade names and/or registered trademarks referred to in this program are the property of their respective owners. Copyright 2014 Pentair Valves & Controls.