RGA

AIR COOLED WATER CHILLERS AND HEAT PUMPS


WITH AXIAL FANS
53.5 200 kW IN COOLING MODE
53.5 202 kW IN HEATING MODE

TECHNICAL MANUAL

TABLE OF CONTENTS
THIS MANUAL IS DIVIDED INTO SECTIONS. THEIR NAMES APPEAR IN THE HEADING OF EACH PAGE.
GENERAL SPECIFICATIONS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .5
PRESENTATION OF THE UNIT . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .5
IDENTIFICATION CODE OF THE UNIT . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .5
DESCRIPTION OF THE COMPONENTS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .6
HYDRAULIC AND COOLING CIRCUIT COMPONENTS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .8
VERSION WITH DESUPERHEATER (AVAILABLE FOR BOTH IR UNITS AND IP UNITS) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .9
ACCESSORIES AND OPTIONAL EQUIPMENT . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .10
MECHANICAL ACCESSORIES . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .10
ELECTRICAL ACCESSORIES . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .12
MECHANICAL OPTIONS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .12
ELECTRICAL OPTIONS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .12
ACCESSORIES - MODEL COMBINATIONS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .13
TECHNICAL SPECIFICATIONS AND STANDARD PERFORMANCES - IR COOLING UNIT ONLY . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .15
TECHNICAL SPECIFICATIONS OF AB UNIT STANDARD UNIT . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .15
STANDARD PERFORMANCES AB STANDARD UNIT . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .16
TECHNICAL SPECIFICATIONS OF UNIT AB STANDARD UNIT + KS SILENCER KIT . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .18
STANDARD PERFORMANCES AB STANDARD UNIT + KS SILENCER KIT . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .19
TECHNICAL SPECIFICATIONS OF UNIT ASS EXTRA LOW NOISE VERSION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .21
STANDARD PERFORMANCES ASS EXTRA LOW NOISE VERSION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .22
VERSION WITH DESUPERHEATER (VD) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .24
RECOVERED HEATING CAPACITY IN VERSION WITH DESUPERHEATER (VD) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .24
SPECIFIC DATA FOT BRINE VERSION (VI) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .25
TECHNICAL SPECIFICATIONS AND STANDARD PERFORMANCES - IP HEAT PUMP UNITS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .26
TECHNICAL SPECIFICATIONS OF UNIT AB STANDARD UNIT . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .26
STANDARD PERFORMANCES IN COOLING MODE AB STANDARD UNIT . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .27
STANDARD PERFORMANCES IN HEATING MODE AB STANDARD UNIT . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .29
TECHNICAL SPECIFICATIONS OF UNIT AB STANDARD UNIT + KS SILENCER KIT . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .30
STANDARD PERFORMANCES IN COOLING MODE AB STANDARD UNIT + KS SILENCER KIT . . . . . . . . . . . . . . . . . . . . . . . . . . .31
STANDARD PERFORMANCES IN HEATING MODE AB STANDARD UNIT + KS SILENCER KIT . . . . . . . . . . . . . . . . . . . . . . . . . . .33
TECHNICAL SPECIFICATIONS OF UNIT ASS EXTRA LOW NOISE VERSION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .34
STANDARD PERFORMANCES IN COOLING MODE ASS EXTRA LOW NOISE VERSION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .35
STANDARD PERFORMANCES IN HEATING MODE ASS EXTRA LOW NOISE VERSION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .37
VERSION WITH DESUPERHEATER (VD) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .38
RECOVERED HEATING CAPACITY IN VERSION WITH DESUPERHEATER (VD) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .38
NOISE LEVELS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .39
STANDARD AB VERSION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .39
AB VERSION + LOW NOISE KIT KS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .39
ASS VERSION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .39
OPERATING RANG . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .40
OPERATING RANGE . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .40
WATER PRESSURE DROP PLATE HEAT EXCHANGER . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .41
WATER PRESSURE DROP OF THE DESUPERHEATER . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .42
WORKING HEAD OF THE PUMPING MODULE MP-AM AND MP-SS

. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .43

WORKING HEAD OF THE PUMPING MODULE MP-AM AP AND MP-SS AP

. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .44

MAXIMUM VOLUME OF WATER . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .45


MAXIMUM WATER VOLUME
OF THE SYSTEM WITH HYDRONIC KIT . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .45
DIMENSIONAL DATA . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .46
OVERALL DIMENSIONS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .46
DESCRIPTION OF THE COMPONENTS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .47
MINIMUM SPACE REQUIRED FOR OPERATION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .47
WEIGHT DURING OPERATION AND TRANSPORT . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .47

GENERAL SPECIFICATIONS
Unit description
This new series of industrial chillers and heat pumps has been designed to meet the demands of global markets in the small-medium power industrial and commercial plants. Units are compact and highly
configurable, built to fit different types of plants so to meet the needs of highly qualified engineers.
Units are water chillers and heat pumps condensed in air with axial fans suitable for outdoor installation: the structure and panels are robust, made of galvanized and painted steel; all fasteners are made
of stainless steel or galvanized steel, the frame containing the electrical equipment and all the components exposed to weather have a minimum IP54 degree of protection.
This series is composed of twelve models divided in four sizes with nominal cooling capacity from 53.5
to 200 kW and thermal capacity from 53.2 to 202 kW.
The units product cold water from 5 to 20C (in summer) and hot water from 30 to 53C (in winter) and
as standard they are equipped with continuous adjustment of axial fans rotating speed in order to
allow the units to operate both with low outdoor temperature in cooling mode and with high outdoor
temperature in heating mode as well as to reduce noise emissions.
All the units are equipped with 2 scroll compressors arranged in pairs (tandem) on 1 circuit operating
with environmental friendly R410A gas, brazed plate heat exchanger completely insulated and protected by water side with a differential pressure control and with an antifreeze electrical heater, coil
heat exchanger made of louver aluminum fins and copper tubes, axial fans with profiled blades to contain noise and with thermal protection built-in, on-board electrical control panel equipped with control
system to manage the main functions.
Hydronic group (MP) composed of fittings and connections is available as an accessory with 1 or 2
pumps and also with high available head pumps; the accessory Water Storage Tank (SAA) is completely insulated and available on delivery side or for primary-secondary hydraulic circuit (Victaulic
connections already in place) depending on the kind of plants to serve.
A variety of other accessories are available to extend the capabilities of the units.
During the design of the units particular attention has been given to achieve high system efficiency, to
reduce overall energy consumptions and sound levels in order to meet the increasingly restrictive laws
in terms of noise. Upon request, you can choose for a Standard Unit (AB) or a Low Noise Kit (KS)
which provides sound attenuation thanks to sound absorbing insulation in compressors area, sound
jackets on compressors and reduced speed axial fans, or a Extra low noise unit (ASS), which provides in addition slower axial fans and more powerful finned coils.
All units are accurately build in compliance with the existing standards and are individually tested in
factory. Only electrical and hydraulic connections are required for installation.
Identification code of the unit
The codes that identify the units are listed below and include the sequences of letters that determine
the meanings for the various versions and set-ups.
Power Supply

RGA IP - 50.2 - VB - AB - 0 - M - 5

5 - 400V - 3ph+N - 50Hz

Serie
Unit model
Unit type
IR- units suitable for
hydronic plant installation operating as chillers.
IP- units suitable for
hydronic plant installation operating as heat
pumps.

Operating climate

N Compressor

Type of Refrigerant

Unit version

0 - R410A

VB - Standard unit
VD- Desuperheater unit
VI - Brine unit

M - Medium temperature.

Units are suitable to be


installed in temperate climate sites.

Acoustic Version
AB - Standard unit
ASS - Extra low noise unit

(1)

NOTES:
(1): not available for model 80 and 160

The available special versions are described below:


VB: Basic version.
VD:
Version with Desuperheater (available forboth IR units and IP units)
Produces cold water in the same way as the standard version plus hot water from 40 to 70C at the same time. This
is achieved by installing a water-refrigerant gas heat exchanger between the compressor and coils in order to recover
15 to 20% of the heating capacity that would otherwise be dispersed in the air.
VI:
Version that produces water at a low temperature (BRINE) (available for IR units only)
The unit can produce cold water with brine at a temperature of -8 to 5C.

GENERAL SPECIFICATIONS
Description of the components
The complete series of industrial chillers and heat pumps for use in hydronic systems includes 12 constructional sizes rang
from 53.5 to 200 kW in the cooling mode and from 53.2 to 202 kW in the heating mode.
Main components:
1. Fans. These are the helical type with scythe-shaped blades to increase the efficiency and reduce the noise level. The fans
are directly coupled to the single-phase motor by means of an external rotor. Thermal protection against operating faults is
installed inside the winding. As standard they are equipped with continuous adjustment of axial fans rotating speed in order to allow the
units to operate both with low outdoor temperature in cooling mode and with high outdoor temperature in heating mode

2. Electric control and monitoring panel. This is housed in a metal casing in which the various electrical components are positioned on one metal plate.
2a. The power section includes:
Main door-locking circuit-breaker.
Fuse-holder that can be isolated with protection fuse triad for each compressor.
Fuse-holder that can be isolated with protection fuse for compressor oil heaters and antifreeze (if installed).
Control contactor for each compressor.
Protection fuse for the ventilation unit.
Fan speed regulating board.
Contactor and magnetothermic switch to protect the pump (if the Hydronic Kit accessory is installed).
Pump contactor (if the Hydronic Kit accessory is installed).
Phase presence and sequence monitoring device on power supply
2b. The auxiliary section includes:
Fuses on the auxiliary transformer.
Fuses for fans protection
Electromagnetic noise filter
MODE
Adjusting fan speed board
Insulating and safety transformer to power the auxiliary circuit.
C
2c. The microprocessor monitoring section includes:
User interfacing terminal with display.
On-off key.
Operating mode selector key.
Compressor on-off display LED.
Operational mode LED
Antifreeze heaters activated indicator LED.
Fans on-off dislay LED
Pumps on-off display LED
Check-control with fault code display
Defrosting, alarm, economy, stand-by LED.
Remote ON/OFF functions - Summer/Winter (E/I) remote selection (IP unit only).
Control system main functions: temperature control of the water produced by the unit, compressor and pump operating hour
counter, timing and cycling of start-ups, input parameters by keyboard, alarms management, smart defrosting control and operating mode change (only IP unit), dynamic set-point (climatic control), scheduling and integrative heaters control.
Digital input functions: low pressure, high pressure, high temperature on compressor supply, phase presence and sequence
monitoring device on power supply, differential water pressure control, compressors thermal protection, fans thermal protection,
pumps thermal protection (only if installed MP accessory), ON/OFF and remote operating mode change, demand limit and
Economy function.
Digital output functions: compressor start-up, pump start-up (only with MP accessory), plate heat exchanger electrical heater,
remote general alarm, 4-way valve (only IP unit), integrative heaters and clean contact on compressors start-up.
Analogic input functions: in and out water temperature, coil temperature probe, external air temperature probe (if present).
Analogic output functions: continuous adjustment of axial fans rotating speed.

GENERAL SPECIFICATIONS

7
1

2
6
5
4
3
3. Compressors. They are the SCROLL type with orbiting coil equipped with built-in thermal protection and oil heater. The version unit AB+KS and ASS includes: a soundproofing jacket for the compressors, acoustic cladding for the entire compressor
compartment to reduce the noise level and continuous adjustment of axial fans rotating speed. All units are equipped with two
compressors connected in parallel (1 single cooling circuit) which can operate at the same time (100% cooling power) or individually (50% of the cooling power), thus adapting to the different thermal loads of the system supplied.
4. Frame structure made of galvanized sheet metal panels coated with polyurethane powder paint to ensure maximun protection against adverse weather conditions.
5. Evaporator made of brazed stainless steel plates (AISI 316). It is installed in a shell of heat-insulating material to prevent
the formation of condensation and heat exchanges towards the outside. Standard supply also includes antifreeze heater a differential pressure switch on the water circuit to avoid the risk of freezing if the water flow is shut off for some reason.
6. Condensing coils, the aluminium finned pack type with shaped profile to increase the heat exchange coefficient and with
copper pipes arranged in staggered rows. A sub-cooling section is integrated into the lower part.
7. Covering panels, made of galvanized sheet metal coated with polyurethane powder paint to ensure maximun protection
against adverse weather conditions
8.One-way valves (IP unit only), allowing the coolant to pass into the appropriate exchangers, depending on the operating
cycle.
4-way cycle reversal valve (IP unit only), reverses the flow direction of the coolant as the summer/winter operating mode is
changed.

GENERAL SPECIFICATIONS

Hydraulic and cooling circuit components


10. Safety valve. Installed on the delivery pipe of the compressors, this operates if extreme faults should occur in the plant.
11. Fluid cock. Ball type, this allows the gas flow on the fluid line to be turned on and off. Along with the cock on the compressor delivery, it allows the components of the fluid line to be subjected to extraordinary maintenance work and the compressors
to be replaced if necessary (without discharging the coolant from the unit).
12. Compressor delivery cock. Ball type, allows the gas delivered to the compressors to be turned on and off.
13. Dehydrator filter. Mechanical type. Retains impurities and traces of moisture in the circuit. Hermetic type for models 5080;
cartridge type for models 90160.
14. Fluid and humidity indicator. Signals when fluid passes through the circuit, indicating that the coolant charge is correct.
The fluid indicator light also indicates the amount of moisture in the coolant by changing colour.
15. Low pressure switch (N1 of series IR version, N2 of series IP version). With fixed setting. It is installed on the suction
pipe and blocks the compressors if the operating pressures drop below the tolerated values. Automatically resets as the pressure increases. If it activates frequently, the unit will block and can only be restarted by resetting via the user interface terminal.
16. High pressure switch (n2). With fixed setting. Are is installed on the delivery pipe and blocks the compressors if the operating pressures exceed the tolerated values. If it activates, the unit will block and can only be restarted by resetting via the user
interface terminal.
17. Thermostatic valve. With external equalizer, this supplies the evaporator correctly, keeping the selected overheating degree
at a steady level.
18. Water differential pressure switch. This is standard supply and is installed on the connections between the water inlet and
outlet of the exchanger. It stops the unit if it activates.
19. Pressure taps: 1/4 " SAE (7/16" UNF) type with flow regulator. Allow the operating pressure of the system to be measured: compressor delivery, lamination component inlet, compressor intake.
20. Pressure taps: 5/16 " SAE type with flow regulator. Allow the charge/discharge of the gas from the system, precisely from
compressor outlet an expansion valve inlet.
21. Electrical heating elements to heat the compressor oil. "Belt" type. These activate when the compressor turns off and
keep the temperature of the oil sufficiently high so as to prevent coolant from migrating during these pauses.
Fluid receiver (IP unit only), this is a plenum tank that accounts for variations to the coolant charge the machine must supply
as the summer/winter operating mode varies.
Fluid separator (IP unit only), on the compressor intake to protect against possible fluid back-flows.

12
11

8
10
15
18
19

17
14

16

13
20
21

GENERAL SPECIFICATIONS

Version with Desuperheater VD (available for both IR units and IP units)


Hydraulic and chilling circuit components:
1. Desuperheater. Specially designed for the specific version. Plate type, made of stainless steel (AISI 316).
It is installed within a shell of thermal barrier insulating material to prevent heat exchanges towards the outside. Standard supply
also includes an electric antifreeze heater to prevent the parts from freezing during the winter, when the system remains at a standstill (if not drained).
2. Water safety valve.On the heat recovery inlet pipe. It acts whenever faulty service leads to an operating pressure in the plumbing system that exceeds the valve opening value (Fig.1).
3. Water drain cock for emptying the exchangers and pipes of the machine dedicated to heat recovery (Fig. 1).
4. Air vent. Accessed by removing the front panels. It consists of a manually operated valve installed in the highest part of the
water pipes. To use in conjunction with the water drain cocks situated in the rear part of the unit, for emptying the exchangers
and pipes dedicated to heat recovery.

4
3
1

ACCESSORIES AND OPTIONAL EQUIPMENT


Mechanical options
AVG - Rubber vibration dampers. Consisting of 4/6 rubber vibration dampers to fit under the unit. Reduce the extent to which
the mechanical vibrations created by the compressors and fans during normal operation are transmitted to the bearing surface
of the machine. The insulating degree of the vibration dampers is about 85%.
GM - Pressure gauge unit. Consisting of 2 pressure gauges that display the pressure values of the refrigerating fluid on the
compressor suction and delivery sides.
GP - Protective grilles. These are metal grilles installed to protect the finned banks.
SAA - Water storage tank. Made of adequately thick painted sheet metal, this reduces the number of compressor start-ups and fluctuations in
the temperature of the water conveyed to the users. It is insulated with thermal barrier material to prevent the formation of condensation and heat
exchanges towards the outside.
Water storage tank. It consists of:
Water draining. On-off action by means of a cock that can be accessed by removing the rear panel, positioned on the side of the unit opposite to the electric panel.
Air vent. Accessed by removing the rear panel positioned on the side of the unit opposite to the electric panel. It consists of a manually operated valve installed on the highest part of the wet pipes.
Water safety valve, on the rear part of the tank. It acts whenever faulty service leads to an operating pressure in the hydraulic circuit that
exceeds the valve opening value.
Antifreeze heater connection. 11/4 female threaded connection pre-engineered for installation of the antifreeze heater (RAG accessory).
KS- Low noise kit (M). Provides sound attenuation thanks to sound absorbing insulation in compressors area, sound jackets on compressors
and reduced speed axial fans
BCN- Drain Pan Kit (M). Provides a pan under the coil to drain the condensing water, fitted with 1/2" outlet connection positioned opposite to
the electric control panel.
KT - the following kits are available (this accessory is mandatory if the Hydronic Kit is not installed).
- Basic pipe kit. This accessory consists of steel pipes insulated with thermal barrier material and allows the water inlet/outlet to be connected straight inside the unit.
- Complete pipe kit. This accessory consists of steel pipes insulated with thermal barrier material and allows the water inlet/outlet connection to be routed to the machine.
- Water storage tank pipe kit. This accessory consists of steel pipes insulated with thermal barrier material and allows the water inlet/outlet
connection to be routed to the machine.
NB: YOU CAN CHOOSE ONLY ONE KIT.
MP. Hydronic Kit (M). Consists of:
1 On-off ball valves. Turn components such as the water filter, surge chamber and pump on and off when they require routine or extraordinary maintenance.
2 Metal gauze water filter. Can be turned on and off and inspected. It is installed on the pump delivery side. Prevents machining residues
(dust, swarf, etc.) in the water pipes from entering the plate-type heat exchanger.
3 Hydraulic pump. Circulates water around the system. The pumps have a low/high head and suit the majority of installation requirements.
The pumps are safeguarded by a magnetothermics installed in the chillers electric panel.
4 Surge chamber. This is a closed, diaphragm type chamber. It absorbs the variations in the volumes of water in the system caused by temperature variations.
5 Water filling. Manual function with control positioned on the side of the unit opposite the electric panel and turned on and off by a cock that
can be accessed by removing the rear panel.
6 Water pressure gauge. Connected to the water fill pipe. Displays the pressure of the water in the system.
7 Water safety valve.
8 Water outlet.
9 Air vent.
10 Antifreeze heater connection (RAG accessory).
MP. Hydronic Kit.
MP : Hydronic Kit with 1 o 2 Pumps: Besides the pumps, this accessory is equipped with all the hydraulic components (water filter, expansion tank, on-off valves, water pressure gauge, air vent, water outlet) required for complete installation and easy maintenance.
Different water accumulation tank configurations are therefore available in combination with the Hydronic Kit accessory:
MP - AM: Accumulation on the Plant Delivery side (Standard)(A): The pump draws water from the system, sends it to the plate exchanger and from thence to the inertial accumulation tank. During normal operating conditions, the pump in this configuration is able to provide
a residue head from 86 to 150 kPa (from 9 to 15 m.w.c.) for the circulating water.
MP - AM AP: Accumulation on the Plant Delivery side (High)(B).: The pump draws water from the system, sends it to the plate exchanger and from thence to the inertial accumulation tank. During normal operating conditions, the pump in this configuration is able to provide
a residue head from 198 to 255 kPa (from 20 to 25 m.w.c.) for the circulating water.
MP - PS: Accumulation pre-engineered for the primary and secondary circuit : The sole function of the pump is to circulate the water
around the primary circuit: this circuit includes the accumulation tank and plate exchanger (chiller water circuit). The installer must mount the
pumping section relative to the secondary circuit formed by the accumulation tank (with the pre-engineered wet connections) and the system
served. No high working head version available.
MP-SS: Hydronic Kit without Water Storage Tank (Standard) (A). The pump draws water from the system, sends it to the plate heat
exchanger and returns it to the system. During normal operating conditions, the pump in this configurations can provide a residue head from
86 to 150 kPa (from 9 to 15 m w.c.).
MP-SS AP: Hydronic Kit without Water Storage Tank (High Working Head) (B). The pump draws water from the system, sends it to the
plate heat exchanger and returns it to the system. During normal operating conditions, the pump in this configurations can provide a residue
head from 198 to 255 kPa (from 20 to 25 m w.c.).
(A): For the working head values depending on the water flow rate, consult the Standard Working Head MP-AM graph.
(B): For the working head values depending on the water flow rate, consult the High Working Head MP-AM graph.
NOTE: (M): Installed
(F): To be installed by customers
NOTE: It is essential to purchase the units with either the KT or MP accessory described previously.
The choice of one automatically excludes the other.

10
10

ACCESSORIES AND OPTIONAL EQUIPMENT


KT

- BASIC PIPE KIT

KT

- COMPLETE PIPE KIT

WATER STORAGE TANK PIPE KIT

MP - 1P AM

MP - 1P AM AP

MP - 1P PS

MP - 2P AM

MP - 2P AM AP

MP - 2P PS

MP - 1P SS

MP - 1P SS AP

MP - 2P SS

MP - 2P SS AP

11

ACCESSORIES AND OPTIONAL EQUIPMENT

Electrical options
CF - Electric power supply phase presence and sequence monitoring device (F). This consists of a device
installed in the electric panel that blocks the unit if one or more phases are absent or if the phase sequence is not
correct: this protects the electric motor of the compressor and the hydraulic pump (if installed) against overheating
and/or burnout.
CR - Remote control (F). This can be used to select all the monitoring and display functions of the control unit on
the machine at a maximum distance of 100 meters away. It must be installed by using a cable with three strands
or three wires in PVC of the N07-VK type with a 1mm 2 section. The transmission line must be installed in a raceway separate from any electric powering wires (230/400 V).
The control unit has the following buttons:
MODE key : used to select the operating mode
ON/OFF key : used to turn the unit ON/OFF and to reset the alarms
C
Mode + ON/OFF keys : used to access and quit the various menu levels
UP key: scrolls forwards through the menu items or increases the value of a parameter
Tasto DOWN: scrolls backwards through the menu items or decreases the value of a parameter.
MODE

KOP - Programmer clock (F). Allows the unit to be turned on and off depending on the programmed time setting (up to 14
switching actions can be programmed as required throughout the 7 days of the week).
RAG: Antifreeze heating element for the accumulation tank (M/F). Plug type. This activates in parallel with the evaporators
antifreeze heating element and keeps the water at a temperature able to prevent ice from forming when the unit remains idle
during the winter.
TAT- High Temperature Thermostat (M). Two thermostats in series on compressors outlet pipes preserve operation not allowing temperature to rise up than a specified non adjustable value.
SND- External Air Probe (M). External air probe mounted near coil allows smart defrosting and climatic variation of setpoint
INT - Serial interface (F). Allows serial communication on RS485 by MODBUS protocol
NOTE: (M): Installed

(F): To be installed by customers

Mechanical options
Special finned heat exchangers
Coils with copper fins
Coils with tin-coated copper fins
Coils with aluminium fins with acrylic coating
Electrical options
Other power source voltage rating (contact our technical department).

12

ACCESSORIES AND OPTIONAL EQUIPMENT

Accessories - Model Combinations

MODEL / ACCESSORY CODE


With Tank
Rubber vibration
dampers
Without Tank
Gas pressure gauges

Mechanical Accessories

Protective grilles

Drain pan kit

Low noise kit

Basic pipe kit

Copmplete pipe kit

Tank pipe kit

Water storage tank

NOTE:
(M): factory mounted
(F): to be installed by customer

M/F

50

60

70

80

AVG13

AVG15

AVG12

AVG14

AVG16

GM12

GP49

GP50

GP51

GP66

BCN3

BCN4

BCN12

KS5

KS6

KS7

KS8

KS9

KS15

KT30

KT29

KT31

KT33

KT40

KT34

KT35

KT41

SAA29

SAA30

SAA39

90

100

115

130

145

160

180

200

Table Continued on next page.

13

ACCESSORIES AND OPTIONAL EQUIPMENT

MODEL / ACCESSORY CODE

1 Pump
With tank on delivery (Standard
Head)
2 Pumps

1 Pump
With tank on delivery (High Head)

Mechanical Accessories
Hydronic kit

2 Pumps

1 Pump
With tank for primary - Secondary
circuit
2 Pumps

1 Pump
Without tank
(Standard Head)
2 Pumps

1 Pump1
Pump
Without tank (High
Head)
2 Pumps

M/F

50

60

70

80

MP105

MP106

MP113

MP147

MP122

MP124

MP133

MP152

MP107

MP108

MP109

MP148

MP125

MP126

MP127

MP153

MP111

MP112

MP113

MP149

MP128

MP129

MP130

MP154

MP117

MP118

MP131

MP150

MP134

MP135

MP136

MP155

MP119

MP120

MP121

MP151

MP137

MP138

MP139

MP156

Electrical Accessories

MODEL / ACCESSORY CODE

90

100

115

130

145

160

200

180

M/F

50

60

70

80

90

100

115

130

145

160

180

200

External air probe

SND3

Programming clock kit

KOP1

RAG13

Storage tank electrical heater kit

RAG14

High temperature thermostat kit (1)

TAT8

Remote control kit

CR6

Serial interface kit

INT2

NOTE:
(M): factory mounted
(F): to be installed by customer
(1): standard for Brine Version VI

14

TECHNICAL SPECIFICATIONS AND STANDARD PERFORMANCES - IR COOLING UNIT ONLY

Technical specifications of unit AB Standard Unit


Model
Power supply
Type of refrigerant
Circuits
Cooling capacity (1) (E)
Compressors power input
EER
Total power input (1) (E)
Total EER
ESEER (E)
Water flow rate (1)
Water pressure drops (1) (E)
Available static head (1) (MP)

(1)

50

60

70

80

53,5
16,3
3,28
18,1
2,96
4,08
2,56
42
135

58,6
18,5
3,17
20,3
2,89
3,98
2,80
51
116

68,8
20,9
3,29
22,7
3,03
4,18
3,29
48
97

78,7
25,6
3,07
27,4
2,87
3,96
3,76
40
75

90
100
115
400V - 3ph+N - 50
R410A
1
91,0
102
112
28,2 31,6 35,5
3,23 3,22 3,15
31,8 35,2 39,1
2,86 2,89 2,86
3,95 3,98 3,95
4,35 4,85 5,35
40
40
40
143
129
113

Compressor
Type
Quantity
Load steps
Oil charge CP1 3,25
Oil charge CP2 3,25
Heat Exchanger
Type
Quantity
Water volume

3,6

3,25
3,25

3,25
3,25

3,6

3,25
3,25

4,6

5,4

3,25
4,7

7,6

130
Hz

145

160

180

200

126
40,5
3,11
44,1
2,86
3,94
6,02
39
92

143
46,0
3,11
51,4
2,78
3,84
6,83
39
116

158
51,0
3,10
56,4
2,80
3,87
7,55
39
95

180
56,0
3,21
63,2
2,85
3,93
8,60
58
141

200
62,8
3,18
70,0
2,86
3,94
9,56
57
107

UM
V-f-Hz
/
n
kW
kW
kW
l/s
kPa
kPa

6,3
6,3

/
n
%
l
l

13,0

/
n
l

Scroll
2
0-50-100
4,7
4,7
4,7
6,8

6,8
6,8

6,8
6,3

Brazed plates
1
8,4
9,7
10,9

12,6

6,3
6,3

14,5

6,3
6,3

11,1

Fan
Type
Quantity
Maximum rotational speed (AB)
Total air flow rate
Power input

Axial
4
2
3
n
900
rpm
29050 29050 28100 27680 41460 41460 47440 47440 62190 59820 82920 79760 m3/h
7,2
1,8
3,6
5,4
kW
3

Coil
Type
Quantity
Front area

Aluminum fins and copper tubes


1
4,72
5,90

3,38

7,41

/
n
m2

Water Storage Tank (SAA accessory)


Water volume
Safety valve setting
Surge chamber volume
Surge chamber default pressure
Max. operating pressure

400

200

460

l
kPa
l
kPa
kPa

600
24

12
150

800

1000

Electrical Data
Units without pumping module
Total maximum power input [ FLA ]
Total maximum power input [ FLI ]
Total maximum starting current [ MIC ]

48,2
25,5
146

Units with pumping module MP-AM and MP-PS (1


Total maximum power input [ FLA ]
51,4
Total maximum power input [ FLI ]
27,2
Total maximum starting current [ MIC ]
149

50,9
27,7
147

58,3
31,1
173

or 2 pumps)
54,1 61,5
29,4 32,8
150
176

Units with pumping module MP-AM AP (1 or 2 pumps)


Total maximum power input [ FLA ]
54,4 57,1
Total maximum power input [ FLI ]
29,2 31,4
Total maximum starting current [ MIC ]
152
153

64,6
34,8
179

68,6
35,5
211

76,0
43,6
265

81,5
49,2
270

89,9
53,9
317

98,3
58,6
325

117
69,4
368

131
78,2
382

150
90,8
470

165
101
485

A
kW
A

71,8
37,2
214

80,8
46,5
269

86,3
52,1
275

94,7
56,8
322

103
61,5
330

123
72,7
373

137
81,5
388

158
95,6
479

173
106
493

A
kW
A

74,9
39,2
217

82,2
47,3
271

87,8
53,0
276

98,1
58,7
325

106
63,4
334

125
74,2
376

140
83,0
390

161
97,3
481

176
108
496

A
kW
A

Data referred to standard operating condition.


(1): water temperature: in 12C - out 7C air temperature: in 35C d.b.
(2): water temperature: in 40C - out 45C air temperature: in 7C d.b. 87% RH
(MP): with standard hydronic kit MP-AM and MP-SS
(SAA): with storage tank
(E): data declared according to LCP EUROVENT certification program

15

TECHNICAL SPECIFICATIONS AND STANDARD PERFORMANCES - IR COOLING UNIT ONLY


Standard performances AB Standard unit
Mod. 50-100
OUTDOOR AIR TEMPERATURE (C D.B.)

MOD.

Tw

20

25

30

35

40

45

50

kWf

kWa

kWf

kWa

kWf

kWa

kWf

kWa

kWf

kWa

kWf

kWa

kWf

kWa

50

5
6
7
8
9
10
11
12

61,1
62,8
64,6
66,4
68,2
70,1
71,8
73,8

11,4
11,5
11,7
11,8
11,9
12,0
12,1
12,3

57,0
58,6
60,3
62,0
63,7
65,4
67,1
68,9

13,2
13,3
13,4
13,6
13,7
13,8
14,0
14,1

53,9
55,4
57,0
58,6
60,2
61,8
63,4
65,1

14,5
14,6
14,8
14,9
15,1
15,2
15,4
15,5

50,6
52,0
53,5
55,0
56,5
58,0
59,5
61,1

16,0
16,1
16,3
16,5
16,6
16,8
17,0
17,1

47,1
48,4
49,8
51,2
52,6
54,0
55,4
56,9

17,6
17,8
18,0
18,2
18,3
18,5
18,7
18,9

43,6
44,8
46,1
47,4
48,7
50,0
51,3
52,7

19,2
19,4
19,6
19,8
20,0
20,2
20,4
20,6

40,0
41,1
42,3
-

20,8
21,0
21,2
-

60

5
6
7
8
9
10
11
12

66,9
68,7
70,7
72,8
74,8
76,7
78,7
80,8

13,0
13,1
13,2
13,4
13,5
13,7
13,8
13,9

62,4
64,2
66,0
67,9
69,8
71,6
73,5
75,5

14,9
15,1
15,2
15,4
15,6
15,7
15,9
16,0

59,0
60,7
62,4
64,2
66,0
67,7
69,5
71,3

16,5
16,6
16,8
17,0
17,1
17,3
17,5
17,6

55,4
56,9
58,6
60,3
61,9
63,6
65,2
67,0

18,1
18,3
18,5
18,7
18,9
19,1
19,3
19,5

51,5
53,0
54,5
56,1
57,6
59,1
60,7
62,3

20,0
20,2
20,4
20,6
20,8
21,0
21,2
21,4

47,7
49,1
50,5
51,9
53,4
54,8
56,2
57,7

21,8
22,0
22,2
22,5
22,7
22,9
23,2
23,4

43,9
45,1
46,4
-

23,6
23,8
24,0
-

70

5
6
7
8
9
10
11
12

78,5
80,7
83,1
85,4
87,8
90,1
92,4
94,9

14,7
14,8
15,0
15,1
15,3
15,4
15,6
15,7

73,3
75,3
77,5
79,7
81,9
84,1
86,2
88,6

16,9
17,0
17,2
17,4
17,6
17,7
17,9
18,1

69,3
71,2
73,3
75,4
77,5
79,5
81,6
83,8

18,6
18,8
19,0
19,2
19,4
19,5
19,7
19,9

65,0
66,9
68,8
70,7
72,7
74,6
76,5
78,6

20,5
20,7
20,9
21,1
21,3
21,6
21,8
22,0

60,5
62,2
64,0
65,8
67,6
69,4
71,2
73,1

22,6
22,8
23,0
23,3
23,5
23,8
24,0
24,2

56,1
57,6
59,3
61,0
62,6
64,3
66,0
67,7

24,6
24,9
25,1
25,4
25,6
25,9
26,2
26,4

51,5
52,9
54,5
-

26,6
26,9
27,2
-

5
6
7
8
9
10
11
12
5
6
7
8
9
10
11
12
5
6
7
8
9
10
11
12

89,8
92,3
95,0
97,7
100
103
106
109
104
107
110
113
116
119
122
126
116
120
123
127
130
134
137
141

18,0
18,1
18,3
18,5
18,7
18,9
19,1
19,3
19,8
20,0
20,2
20,4
20,6
20,8
21,0
21,2
22,2
22,4
22,6
22,9
23,1
23,3
23,5
23,8

83,9
86,2
88,7
91,2
93,7
96,2
98,7
101
97,0
100
103
105
108
111
114
117
109
112
115
118
121
125
128
131

20,7
20,9
21,1
21,3
21,5
21,7
21,9
22,2
22,8
23,0
23,2
23,5
23,7
23,9
24,2
24,4
25,5
25,7
26,0
26,3
26,6
26,8
27,1
27,4

79,3
81,5
83,9
86,2
88,6
91,0
93,3
95,8
91,7
94,2
97,0
100
102
105
108
111
103
106
109
112
115
118
121
124

22,8
23,0
23,2
23,5
23,7
23,9
24,2
24,4
25,1
25,3
25,6
25,9
26,1
26,4
26,6
26,9
28,1
28,4
28,7
29,0
29,3
29,6
29,8
30,1

74,4
76,5
78,7
80,9
83,2
85,4
87,5
89,9
86,0
88,4
91,0
93,6
96,2
98,7
101
104
96,4
99,1
102
105
108
111
113
117

25,1
25,3
25,6
25,9
26,1
26,4
26,7
26,9
27,7
27,9
28,2
28,5
28,8
29,1
29,4
29,7
31,0
31,3
31,6
31,9
32,3
32,6
32,9
33,2

69,2
71,1
73,2
75,3
77,4
79,4
81,5
83,7
80,1
82,3
84,7
87,1
89,5
91,8
94,2
96,7
89,7
92,2
94,9
97,6
100
103
106
108

27,7
27,9
28,2
28,5
28,8
29,1
29,4
29,7
30,5
30,8
31,1
31,4
31,7
32,1
32,4
32,7
34,2
34,5
34,8
35,2
35,6
35,9
36,3
36,6

64,1
65,9
67,8
69,7
71,7
73,6
75,4
77,5
74,1
76,2
78,4
80,6
82,9
85,1
87,2
89,6
83,1
85,4
87,9
90,4
92,9
95,3
97,8
100

30,2
30,5
30,8
31,1
31,4
31,7
32,0
32,3
33,2
33,5
33,9
34,3
34,6
34,9
35,3
35,6
37,2
37,6
38,0
38,4
38,8
39,2
39,5
39,9

58,9
60,5
62,3
68,1
70,0
72,0
76,3
78,4
80,7
-

32,6
32,9
33,3
35,9
36,3
36,6
40,3
40,6
41,1
-

80

90

100

Tw= Outlet water temperature C


kWf = refrigerating power (kW).
kWa = Power input of compressors (kW)
The standard performances refer to a 5C temperature difference between the water entering and leaving the plate-type heat exchanger and to operation of the unit
with all fans at top speed. A 0.44 x 10-4 m2 K/W fouling factor has also been considered with the unit installed at zero meters above sea level (Pb = 1013mbar).

16

TECHNICAL SPECIFICATIONS AND STANDARD PERFORMANCES - IR COOLING UNIT ONLY

Mod. 115-160
OUTDOOR AIR TEMPERATURE (C D.B.)

MOD.

115

130

145

160

180

200

Tw
5
6
7
8
9
10
11
12
5
6
7
8
9
10
11
12
5
6
7
8
9
10
11
12
5
6
7
8
9
10
11
12
5
6
7
8
9
10
11
12
5
6
7
8
9
10
11
12

20
kWf
128
131
135
139
143
147
150
154
144
148
152
156
161
165
169
174
163
168
173
178
182
187
192
197
180
185
191
196
202
207
212
218
205
211
217
223
230
236
242
248
228
235
241
248
255
262
269
276

25
kWa
24,9
25,1
25,4
25,7
25,9
26,2
26,5
26,7
28,4
28,7
29,0
29,3
29,6
29,9
30,2
30,5
32,3
32,6
32,9
33,3
33,6
33,9
34,3
34,6
35,8
36,1
36,5
36,9
37,3
37,6
38,0
38,4
39,3
39,7
40,1
40,5
40,9
41,3
41,7
42,1
44,1
44,5
44,9
45,4
45,9
46,3
46,8
47,2

kWf
119
123
126
130
133
137
140
144
134
138
142
146
150
154
158
162
152
157
161
166
170
175
179
184
168
173
178
183
188
193
198
203
192
197
203
209
214
220
226
232
213
219
225
232
238
244
251
258

30
kWa
28,7
28,9
29,2
29,5
29,8
30,1
30,4
30,7
32,7
33,0
33,3
33,7
34,0
34,4
34,7
35,1
37,1
37,5
37,9
38,3
38,7
39,1
39,4
39,8
41,2
41,6
42,0
42,4
42,9
43,3
43,7
44,1
45,2
45,6
46,1
46,6
47,1
47,5
48,0
48,5
50,7
51,2
51,7
52,3
52,8
53,3
53,8
54,4

kWf
113
116
119
123
126
129
133
136
127
130
134
138
142
146
149
153
144
148
152
157
161
165
170
174
159
164
168
173
178
183
187
192
181
186
192
197
203
208
213
219
202
207
213
219
225
231
237
244

35
kWa
31,6
31,9
32,2
32,6
32,9
33,2
33,5
33,9
36,0
36,4
36,7
37,1
37,5
37,9
38,3
38,6
40,9
41,3
41,7
42,2
42,6
43,0
43,5
43,9
45,4
45,8
46,3
46,8
47,2
47,7
48,2
48,6
49,8
50,3
50,8
51,4
51,9
52,4
52,9
53,4
55,9
56,4
57,0
57,6
58,2
58,7
59,3
59,9

kWf
106
109
112
115
118
121
125
128
119
122
126
130
133
137
140
144
135
139
143
147
151
155
159
163
149
154
158
162
167
171
176
181
170
175
180
185
190
195
200
206
189
194
200
206
211
217
222
229

40
kWa
34,8
35,1
35,5
35,9
36,3
36,6
37,0
37,3
39,7
40,1
40,5
40,9
41,4
41,8
42,2
42,6
45,1
45,5
46,0
46,5
47,0
47,4
47,9
48,4
50,0
50,5
51,0
51,6
52,1
52,6
53,1
53,6
54,9
55,4
56,0
56,6
57,2
57,8
58,3
58,9
61,6
62,2
62,8
63,5
64,1
64,8
65,4
66,0

kWf
98,5
101
104
107
110
113
116
119
111
114
117
121
124
127
130
134
126
129
133
137
141
144
148
152
139
143
147
151
155
159
164
168
158
163
167
172
177
182
186
191
176
181
186
191
197
202
207
213

45
kWa
38,4
38,7
39,1
39,6
40,0
40,4
40,7
41,1
43,8
44,2
44,6
45,1
45,6
46,0
46,5
46,9
49,7
50,2
50,7
51,3
51,8
52,3
52,8
53,3
55,1
55,6
56,2
56,8
57,4
58,0
58,5
59,1
60,5
61,1
61,7
62,4
63,0
63,7
64,3
64,9
67,9
68,5
69,2
70,0
70,7
71,4
72,1
72,8

kWf
91,3
93,8
96,5
99,2
102
105
107
110
103
106
109
112
115
118
121
124
117
120
123
127
130
134
137
141
129
132
136
140
144
148
151
156
147
151
155
160
164
168
173
177
163
167
172
177
182
187
192
197

50
kWa
41,8
42,2
42,7
43,1
43,6
44,0
44,4
44,9
47,7
48,2
48,7
49,2
49,7
50,2
50,7
51,2
54,2
54,7
55,3
55,9
56,4
57,0
57,6
58,1
60,1
60,7
61,3
62,0
62,6
63,2
63,8
64,4
66,0
66,6
67,3
68,0
68,7
69,4
70,1
70,8
74,0
74,7
75,5
76,3
77,1
77,8
78,6
79,4

kWf
83,8
86,1
88,6
94,3
96,9
100
107
110
113
118
122
125
135
138
142
150
154
158
-

kWa
45,2
45,7
46,1
51,6
52,1
52,6
58,6
59,2
59,8
65,0
65,6
66,3
71,4
72,0
72,8
80,0
80,8
81,6
-

Tw= Outlet water temperature C


kWf = refrigerating power (kW).
kWa = Power input of compressors (kW)
The standard performances refer to a 5C temperature difference between the water entering and leaving the plate-type heat exchanger and to operation of the unit
with all fans at top speed. A 0.44 x 10-4 m2 K/W fouling factor has also been considered with the unit installed at zero meters above sea level (Pb = 1013mbar).

17

TECHNICAL SPECIFICATIONS AND STANDARD PERFORMANCES - IR COOLING UNIT ONLY


Technical specifications of unit AB Standard Unit + KS Silencer kit
Model
Power supply
Type of refrigerant
Circuits
Cooling capacity (1) (E)
Compressors power input
EER
Total power input (1) (E)
Total EER
ESEER (E)
Water flow rate (1)
Water pressure drops (1) (E)
Available static head (1) (MP)

(1)

50

60

70

80

51,9
17,0
3,04
18,8
2,75
3,80
2,48
39
144

56,8
19,3
2,94
21,1
2,69
3,71
2,71
48
124

66,7
21,8
3,05
23,6
2,82
3,89
3,19
45
103

76,3
26,8
2,85
28,6
2,67
3,69
3,64
38
80

90
100
115
400V - 3ph+N - 50
R410A
1
88,2 98,5
109
29,5 33,0 37,1
2,99 2,98 2,93
33,1 36,6 40,7
2,67 2,69 2,67
3,68 3,71 3,68
4,21 4,71 5,19
37
38
38
153
137
119

Compressor
Type
Quantity
Load steps
Oil charge CP1 3,25
Oil charge CP2 3,25
Heat Exchanger
Type
Quantity
Water volume

3,6

3,25
3,25

3,25
3,25

3,6

3,25
3,25

4,6

5,4

3,25
4,7

7,6

130
Hz

145

160

180

200

122
42,3
2,89
45,9
2,66
3,67
5,84
37
98

139
48,1
2,88
53,5
2,59
3,58
6,62
37
123

153
53,3
2,87
58,7
2,61
3,60
7,32
37
101

174
58,5
2,98
65,7
2,65
3,66
8,34
54
151

194
65,6
2,95
72,8
2,66
3,67
9,26
54
114

UM
V-f-Hz
/
n
kW
kW
kW
l/s
kPa
kPa

6,3
6,3

/
n
%
l
l

13,0

/
n
l

Scroll
2
0-50-100
4,7
4,7
4,7
6,8

6,8
6,8

6,8
6,3

Brazed plates
1
8,4
9,7
10,9

12,6

6,3
6,3

14,5

6,3
6,3

11,1

Fan
Type
Quantity
Maximum rotational speed
Total air flow rate
Power input

Axial
4
2
3
n
900
rpm
24208 24208 23417 23067 34550 34550 39533 39533 51825 49850 69100 66467 m3/h
7,2
1,8
3,6
5,4
kW
3

Coil
Type
Quantity
Front area

Aluminum fins and copper tubes


1
4,72
5,90

3,38

7,41

/
n
m2

Water Storage Tank (SAA accessory)


Water volume
Safety valve setting
Surge chamber volume
Surge chamber default pressure
Max. operating pressure

400

200

460

600
24

12
150

800

1000

l
kPa
l
kPa
kPa

Dati elettrici
Units without pumping module
Total maximum power input [ FLA ]
Total maximum power input [ FLI ]
Total maximum starting current [ MIC ]

48,2
25,5
146

Units with pumping module MP-AM and MP-PS (1


Total maximum power input [ FLA ]
51,4
Total maximum power input [ FLI ]
27,2
Total maximum starting current [ MIC ]
149

50,9
27,7
147

58,3
31,1
173

or 2 pumps)
54,1 61,5
29,4 32,8
150
176

Units with pumping module MP-AM AP (1 or 2 pumps)


Total maximum power input [ FLA ]
54,4 57,1
Total maximum power input [ FLI ]
29,2 31,4
Total maximum starting current [ MIC ]
152
153

64,6
34,8
179

68,6
35,5
211

76,0
43,6
265

81,5
49,2
270

89,9
53,9
317

98,3
58,6
325

117
69,4
368

131
78,2
382

150
90,8
470

165
101
485

A
kW
A

71,8
37,2
214

80,8
46,5
269

86,3
52,1
275

94,7
56,8
322

103
61,5
330

123
72,7
373

137
81,5
388

158
95,6
479

173
106
493

A
kW
A

74,9
39,2
217

82,2
47,3
271

87,8
53,0
276

98,1
58,7
325

106
63,4
334

125
74,2
376

140
83,0
390

161
97,3
481

176
108
496

A
kW
A

Data referred to standard operating condition.


(1): water temperature: in 12C - out 7C air temperature: in 35C d.b.
(2): water temperature: in 40C - out 45C air temperature: in 7C d.b. 87% RH
(MP): with standard hydronic kit MP-AM and MP-SS
(SAA): with storage tank
(E): data declared according to LCP EUROVENT certification program

18

TECHNICAL SPECIFICATIONS AND STANDARD PERFORMANCES - IR COOLING UNIT ONLY


Standard performances AB Standard Unit + KS Silencer kit
Mod. 50-100
OUTDOOR AIR TEMPERATURE (C D.B.)

MOD.

Tw
kWf

kWa

kWf

kWa

kWf

kWa

kWf

kWa

kWf

kWa

kWf

kWa

kWf

kWa

50

5
6
7
8
9
10
11
12

59,2
60,9
62,7
64,4
66,2
68,0
69,7
71,6

11,9
12,0
12,2
12,3
12,4
12,5
12,7
12,8

55,3
56,8
58,5
60,1
61,8
63,4
65,1
66,8

13,7
13,9
14,0
14,1
14,3
14,4
14,6
14,7

52,3
53,7
55,3
56,9
58,4
60,0
61,5
63,2

15,1
15,3
15,4
15,6
15,7
15,9
16,1
16,2

49,1
50,4
51,9
53,4
54,8
56,3
57,7
59,3

16,7
16,8
17,0
17,2
17,4
17,5
17,7
17,9

45,7
46,9
48,3
49,7
51,0
52,4
53,7
55,2

18,4
18,5
18,7
18,9
19,1
19,3
19,5
19,7

42,3
43,5
44,7
46,0
47,3
48,5
49,8
51,1

20,0
20,2
20,4
20,7
20,9
21,1
21,3
21,5

38,8
39,9
41,1
-

21,7
21,9
22,1
-

60

5
6
7
8
9
10
11
12

64,8
66,6
68,6
70,5
72,5
74,4
76,3
78,4

13,5
13,7
13,8
14,0
14,1
14,2
14,4
14,5

60,5
62,2
64,0
65,8
67,6
69,4
71,2
73,1

15,6
15,7
15,9
16,1
16,2
16,4
16,5
16,7

57,2
58,8
60,5
62,2
64,0
65,7
67,3
69,2

17,2
17,3
17,5
17,7
17,9
18,1
18,2
18,4

53,7
55,2
56,8
58,4
60,0
61,6
63,2
64,9

18,9
19,1
19,3
19,5
19,7
19,9
20,1
20,3

50,0
51,3
52,8
54,3
55,8
57,3
58,8
60,4

20,9
21,1
21,3
21,5
21,7
21,9
22,2
22,4

46,3
47,6
48,9
50,3
51,7
53,1
54,4
55,9

22,7
23,0
23,2
23,4
23,7
23,9
24,2
24,4

42,5
43,7
45,0
-

24,6
24,8
25,1
-

70

5
6
7
8
9
10
11
12

76,1
78,2
80,5
82,8
85,1
87,3
89,6
92,0

15,3
15,4
15,6
15,8
15,9
16,1
16,2
16,4

71,1
73,0
75,2
77,3
79,4
81,5
83,6
85,9

17,6
17,8
17,9
18,1
18,3
18,5
18,7
18,9

67,2
69,1
71,1
73,1
75,1
77,1
79,1
81,2

19,4
19,6
19,8
20,0
20,2
20,4
20,6
20,8

63,1
64,8
66,7
68,6
70,5
72,3
74,2
76,2

21,4
21,6
21,8
22,0
22,3
22,5
22,7
22,9

58,7
60,3
62,1
63,8
65,6
67,3
69,0
70,9

23,6
23,8
24,0
24,3
24,5
24,8
25,0
25,3

54,3
55,8
57,5
59,1
60,7
62,3
63,9
65,7

25,7
25,9
26,2
26,5
26,8
27,0
27,3
27,5

49,9
51,3
52,8
-

27,8
28,0
28,3
-

5
6
7
8
9
10
11
12
5
6
7
8
9
10
11
12
5
6
7
8
9
10
11
12

87,1
89,5
92,1
94,7
97,3
100
102
105
101
103
106
109
113
115
118
122
112
116
119
122
126
129
132
136

18,8
19,0
19,2
19,4
19,6
19,8
20,0
20,2
20,7
20,9
21,1
21,3
21,6
21,8
22,0
22,2
23,2
23,4
23,6
23,9
24,1
24,3
24,6
24,8

81,3
83,5
86,0
88,4
90,9
93,3
95,6
98,2
94,0
96,6
99,4
102
105
108
111
114
105
108
111
114
117
120
123
127

21,6
21,8
22,1
22,3
22,5
22,8
23,0
23,2
23,8
24,0
24,3
24,6
24,8
25,0
25,3
25,5
26,6
26,9
27,2
27,5
27,7
28,0
28,3
28,6

76,9
79,0
81,3
83,6
85,9
88,2
90,4
92,9
88,9
91,3
94,0
96,6
99,3
102
105
107
99,2
102
105
108
111
114
117
120

23,8
24,1
24,3
24,6
24,8
25,1
25,3
25,6
26,2
26,5
26,8
27,1
27,3
27,6
27,9
28,1
29,4
29,6
29,9
30,3
30,6
30,9
31,2
31,5

72,1
74,1
76,3
78,5
80,6
82,8
84,9
87,2
83,4
85,7
88,2
90,7
93,2
95,7
98,1
101
93,1
95,7
98,5
101
104
107
110
113

26,3
26,5
26,8
27,1
27,4
27,6
27,9
28,2
28,9
29,2
29,5
29,8
30,1
30,4
30,7
31,0
32,4
32,7
33,0
33,4
33,7
34,0
34,4
34,7

67,1
69,0
71,0
73,0
75,0
77,0
79,0
81,1
77,6
79,7
82,1
84,4
86,7
89,0
91,3
93,8
86,6
89,0
91,6
94,2
96,8
99,4
102
105

29,0
29,2
29,5
29,9
30,2
30,5
30,8
31,1
31,9
32,2
32,5
32,9
33,2
33,5
33,9
34,2
35,7
36,0
36,4
36,8
37,1
37,5
37,9
38,2

62,2
63,9
65,7
67,6
69,5
71,3
73,1
75,1
71,9
73,9
76,0
78,2
80,3
82,4
84,5
86,8
80,3
82,5
84,9
87,3
89,7
92,1
94,4
97,0

31,6
31,9
32,2
32,6
32,9
33,2
33,5
33,9
34,8
35,1
35,4
35,8
36,2
36,6
36,9
37,3
38,9
39,3
39,7
40,1
40,5
40,9
41,3
41,7

57,1
58,7
60,4
66,0
67,8
69,8
73,7
75,8
78,0
-

34,1
34,5
34,8
37,6
37,9
38,3
42,0
42,4
42,9
-

80

90

100

20

25

30

35

40

45

50

Tw= Temperatura acqua in uscita in C


kWf = Potenza frigorifera netta(kW).
kWa = Potenza assorbita dai compressori (kW)
Le prestazioni standard si riferiscono ad un differenza di 5 C di temperatura tra acqua entrante ed uscente dallo scambiatore a piastre, e al funzionamento dell'unit con
tutti i ventilatori alla massima velocit. Si considera inoltre un fattore di sporcamento di 0.44 x 10-4 m2 K/W e l'unit posta a zero metri sul livello del mare (Pb = 1013mbar).

19

TECHNICAL SPECIFICATIONS AND STANDARD PERFORMANCES - IR COOLING UNIT ONLY

Mod. 115-160
OUTDOOR AIR TEMPERATURE (C D.B.)

MOD.

115

130

145

160

180

200

Tw
5
6
7
8
9
10
11
12
5
6
7
8
9
10
11
12
5
6
7
8
9
10
11
12
5
6
7
8
9
10
11
12
5
6
7
8
9
10
11
12
5
6
7
8
9
10
11
12

20
kWf
124
128
132
135
139
143
146
150
139
143
147
151
156
160
164
168
159
163
168
173
177
182
187
192
175
179
185
190
195
200
205
211
199
204
210
216
222
228
234
240
221
228
234
241
247
254
261
268

25
kWa
26,0
26,3
26,5
26,8
27,1
27,4
27,6
27,9
29,7
30,0
30,3
30,6
30,9
31,2
31,5
31,8
33,7
34,1
34,4
34,8
35,1
35,5
35,8
36,2
37,4
37,7
38,1
38,6
38,9
39,3
39,7
40,1
41,0
41,4
41,9
42,3
42,7
43,2
43,6
44,0
46,0
46,5
46,9
47,5
47,9
48,4
48,9
49,4

kWf
116
119
123
126
130
133
137
140
130
134
137
141
145
149
153
157
148
152
157
161
166
170
174
179
163
168
172
177
182
187
192
197
185
191
196
202
207
213
218
224
207
212
219
225
231
237
243
250

30
kWa
30,0
30,2
30,5
30,9
31,2
31,5
31,8
32,1
34,1
34,5
34,8
35,2
35,6
35,9
36,3
36,6
38,8
39,2
39,6
40,0
40,4
40,8
41,2
41,6
43,0
43,4
43,9
44,4
44,8
45,3
45,7
46,1
47,2
47,7
48,2
48,7
49,2
49,7
50,2
50,6
53,0
53,5
54,0
54,6
55,1
55,7
56,2
56,8

kWf
110
113
116
119
123
126
129
133
123
126
130
134
137
141
145
149
140
144
148
152
157
161
165
169
154
158
163
168
172
177
181
186
175
180
185
191
196
201
206
212
195
201
207
213
218
224
230
236

35
kWa
33,0
33,3
33,6
34,0
34,4
34,7
35,0
35,4
37,6
38,0
38,4
38,8
39,2
39,6
40,0
40,3
42,8
43,2
43,6
44,1
44,6
45,0
45,4
45,9
47,4
47,9
48,3
48,9
49,4
49,9
50,3
50,8
52,0
52,5
53,1
53,6
54,2
54,7
55,3
55,8
58,3
58,9
59,5
60,2
60,8
61,4
62,0
62,6

kWf
103
106
109
112
115
118
121
125
115
119
122
125
129
132
136
139
131
135
139
143
147
151
155
159
145
149
153
157
162
166
170
175
165
169
174
179
184
189
194
199
183
189
194
199
205
210
216
222

40
kWa
36,4
36,7
37,1
37,5
37,9
38,3
38,6
39,0
41,5
41,9
42,3
42,8
43,2
43,6
44,1
44,5
47,2
47,6
48,1
48,6
49,1
49,6
50,1
50,6
52,3
52,8
53,3
53,9
54,4
55,0
55,5
56,0
57,4
57,9
58,5
59,1
59,7
60,3
60,9
61,5
64,3
64,9
65,6
66,3
67,0
67,7
68,3
69,0

kWf
95,9
98,5
101
104
107
110
113
116
107
110
114
117
120
123
126
130
122
126
129
133
137
140
144
148
135
138
142
146
150
154
158
163
153
157
162
166
171
176
180
185
171
175
180
186
191
196
201
206

45
kWa
40,1
40,5
40,9
41,3
41,8
42,2
42,6
43,0
45,7
46,2
46,6
47,1
47,6
48,1
48,6
49,0
52,0
52,5
53,0
53,6
54,1
54,7
55,2
55,8
57,6
58,2
58,7
59,4
60,0
60,6
61,2
61,8
63,2
63,8
64,5
65,2
65,8
66,5
67,2
67,8
70,9
71,6
72,3
73,1
73,8
74,6
75,3
76,0

kWf
88,8
91,3
93,9
96,6
99,2
102
104
107
99,4
102
105
108
111
114
117
120
113
116
120
123
127
130
133
137
125
128
132
136
139
143
147
151
142
146
150
154
158
163
167
171
158
162
167
172
177
181
186
191

50
kWa
43,7
44,1
44,6
45,1
45,5
46,0
46,4
46,9
49,8
50,3
50,8
51,4
51,9
52,4
52,9
53,5
56,7
57,2
57,8
58,4
59,0
59,6
60,2
60,8
62,8
63,4
64,0
64,8
65,4
66,1
66,7
67,4
68,9
69,6
70,3
71,1
71,8
72,5
73,2
73,9
77,3
78,0
78,8
79,7
80,5
81,3
82,1
82,9

kWf
81,6
83,8
86,3
91,3
93,8
96,6
104
107
110
114
118
121
130
134
138
145
149
154
-

kWa
47,3
47,7
48,2
53,9
54,4
55,0
61,3
61,9
62,5
67,9
68,5
69,3
74,5
75,2
76,0
83,6
84,4
85,2
-

Tw= Temperatura acqua in uscita in C


kWf = Potenza frigorifera netta(kW).
kWa = Potenza assorbita dai compressori (kW)
Le prestazioni standard si riferiscono ad un differenza di 5 C di temperatura tra acqua entrante ed uscente dallo scambiatore a piastre, e al funzionamento dell'unit con
tutti i ventilatori alla massima velocit. Si considera inoltre un fattore di sporcamento di 0.44 x 10-4 m2 K/W e l'unit posta a zero metri sul livello del mare (Pb = 1013mbar).

20

TECHNICAL SPECIFICATIONS AND STANDARD PERFORMANCES - IR COOLING UNIT ONLY

Technical specifications of unit ASS Extra low noise version


Model
Power supply
Type of refrigerant
Circuits
Cooling capacity (1) (E)
Compressors power input
EER
Total power input (1) (E)
Total EER
ESEER (E)
Water flow rate (1)
Water pressure drops (1) (E)
Available static head (1) (MP)

(1)

50

60

70

80

50,7
17,6
2,88
19,4
2,62
3,61
2,42
38
151

55,5
19,9
2,78
21,7
2,55
3,52
2,65
46
130

65,2
22,5
2,89
24,3
2,68
3,70
3,11
43
108

90
100
115
400V - 3ph+N - 50
R410A
1
86,2 96,2
106
30,4 34,1 38,3
2,83 2,82 2,77
32,2 37,7 41,9
2,68 2,55 2,53
3,69 3,53 3,50
4,12 4,60 5,07
36
36
36
159
143
126

Compressor
Type
Quantity
Load steps
Oil charge CP1 3,25
Oil charge CP2 3,25
Heat Exchanger
Type
Quantity
Water volume

3,6

3,25
3,25

3,25
3,25

3,6

4,6

3,25
4,7

7,6

130
Hz

145

160

180

200

119
43,7
2,73
47,3
2,52
3,48
5,70
35
103

135
49,6
2,73
55,0
2,46
3,40
6,47
35
130

170
60,4
2,82
67,6
2,52
3,48
8,14
52
158

Scroll
2
0-50-100
4,7
4,7
4,7
6,8

6,8
6,8

6,8
6,3

Brazed plates
1
8,4
9,7
10,9

12,6

6,3
6,3

11,1

UM
V-f-Hz
/
n
kW
kW
kW
l/s
kPa
kPa

/
n
%
l
l

/
n
l

Fan
Type
Quantity
Maximum rotational speed
Total air flow rate
Power input

3
19367 19367 18733
1,8

Axial
2
3
900
27640 27640 31627 31627 41460
3,6
5,4

4
55280
7,2

n
rpm
m3/h
kW

Coil
Type
Quantity
Front area

Aluminum fins and copper tubes


1
4,72
5,90

3,38

7,41

/
n
m2

Water Storage Tank (SAA accessory)


Water volume
Safety valve setting
Surge chamber volume
Surge chamber default pressure
Max. operating pressure

400

200

460

600
24

12
150

800

1000

l
kPa
l
kPa
kPa

Electrical Data
Units without pumping module
Total maximum power input [ FLA ]
Total maximum power input [ FLI ]
Total maximum starting current [ MIC ]

48,2
25,5
146

Units with pumping module MP-AM and MP-PS (1


Total maximum power input [ FLA ]
51,4
Total maximum power input [ FLI ]
27,2
Total maximum starting current [ MIC ]
149

50,9
27,7
147

58,3
31,1
173

or 2 pumps)
54,1 61,5
29,4 32,8
150
176

Units with pumping module MP-AM AP (1 or 2 pumps)


Total maximum power input [ FLA ]
54,4 57,1
Total maximum power input [ FLI ]
29,2 31,4
Total maximum starting current [ MIC ]
152
153

64,6
34,8
179

68,6
35,5
211

76,0
43,6
265

81,5
49,2
270

89,9
53,9
317

98,3
58,6
325

117
69,4
368

131
78,2
382

150
90,8
470

165
101
485

A
kW
A

71,8
37,2
214

80,8
46,5
269

86,3
52,1
275

94,7
56,8
322

103
61,5
330

123
72,7
373

137
81,5
388

158
95,6
479

173
106
493

A
kW
A

74,9
39,2
217

82,2
47,3
271

87,8
53,0
276

98,1
58,7
325

106
63,4
334

125
74,2
376

140
83,0
390

161
97,3
481

176
108
496

A
kW
A

Data referred to standard operating condition.


(1): water temperature: in 12C - out 7C air temperature: in 35C d.b.
(2): water temperature: in 40C - out 45C air temperature: in 7C d.b. 87% RH
(MP): with standard hydronic kit MP-AM and MP-SS
(SAA): with storage tank
(E): data declared according to LCP EUROVENT certification program

21

TECHNICAL SPECIFICATIONS AND STANDARD PERFORMANCES - IR COOLING UNIT ONLY


Standard performances ASS Extra low noise version
Mod. 50-100
OUTDOOR AIR TEMPERATURE (C D.B.)

MOD.

Tw

20

25

30

35

40

45

50

kWf

kWa

kWf

kWa

kWf

kWa

kWf

kWa

kWf

kWa

kWf

kWa

kWf

kWa

50

5
6
7
8
9
10
11
12

57,9
59,5
61,2
62,9
64,7
66,4
68,1
69,9

12,3
12,5
12,6
12,7
12,9
13,0
13,1
13,2

54,0
55,5
57,1
58,8
60,4
62,0
63,6
65,3

14,2
14,3
14,5
14,6
14,8
14,9
15,1
15,2

51,1
52,5
54,0
55,6
57,1
58,6
60,1
61,7

15,7
15,8
16,0
16,1
16,3
16,5
16,6
16,8

47,9
49,3
50,7
52,1
53,6
55,0
56,4
57,9

17,3
17,4
17,6
17,8
18,0
18,2
18,3
18,5

44,6
45,8
47,2
48,5
49,8
51,2
52,5
53,9

19,0
19,2
19,4
19,6
19,8
20,0
20,2
20,4

41,3
42,5
43,7
44,9
46,2
47,4
48,6
49,9

20,7
20,9
21,1
21,4
21,6
21,8
22,0
22,2

37,9
39,0
40,1
-

22,4
22,6
22,9
-

60

5
6
7
8
9
10
11
12

63,4
65,1
67,0
68,9
70,8
72,7
74,5
76,6

14,0
14,1
14,2
14,4
14,5
14,7
14,8
15,0

59,1
60,8
62,5
64,3
66,1
67,8
69,6
71,5

16,1
16,2
16,4
16,6
16,7
16,9
17,1
17,2

55,9
57,5
59,1
60,8
62,5
64,1
65,8
67,6

17,7
17,9
18,0
18,2
18,4
18,6
18,8
19,0

52,5
53,9
55,5
57,1
58,6
60,2
61,7
63,4

19,5
19,7
19,9
20,1
20,3
20,5
20,7
20,9

48,8
50,2
51,6
53,1
54,6
56,0
57,4
59,0

21,5
21,7
21,9
22,2
22,4
22,6
22,8
23,1

45,2
46,5
47,8
49,2
50,5
51,9
53,2
54,6

23,5
23,7
23,9
24,2
24,4
24,7
24,9
25,1

41,5
42,7
43,9
-

25,4
25,6
25,9
-

70

5
6
7
8
9
10
11
12

74,4
76,5
78,7
80,9
83,2
85,4
87,6
89,9

15,8
15,9
16,1
16,3
16,4
16,6
16,8
16,9

69,5
71,4
73,5
75,6
77,6
79,7
81,7
83,9

18,2
18,3
18,5
18,7
18,9
19,1
19,3
19,5

65,7
67,5
69,5
71,4
73,4
75,4
77,3
79,4

20,0
20,2
20,4
20,6
20,8
21,0
21,3
21,5

61,6
63,4
65,2
67,0
68,9
70,7
72,5
74,5

22,1
22,3
22,5
22,7
23,0
23,2
23,4
23,7

57,4
58,9
60,7
62,4
64,1
65,8
67,5
69,3

24,3
24,5
24,8
25,1
25,3
25,6
25,8
26,1

53,1
54,6
56,2
57,8
59,4
60,9
62,5
64,2

26,5
26,8
27,0
27,3
27,6
27,9
28,2
28,4

48,8
50,1
51,6
-

28,7
28,9
29,2
-

5
6
7
8
9
10
11
12
5
6
7
8
9
10
11
12
5
6
7
8
9
10
11
12

98,4
101
104
107
110
113
116
119
110
113
116
119
123
126
129
133

21,3
21,5
21,8
22,0
22,2
22,4
22,7
22,9
23,9
24,2
24,4
24,7
24,9
25,2
25,4
25,7

91,8
94,4
97,1
100
103
105
108
111
102
105
108
111
115
118
121
124

24,5
24,8
25,0
25,3
25,6
25,8
26,1
26,3
27,5
27,8
28,1
28,4
28,7
29,0
29,2
29,5

86,8
89,3
91,9
94,5
97,1
100
102
105
96,9
100
103
105
108
111
114
117

27,0
27,3
27,6
27,9
28,2
28,4
28,7
29,0
30,3
30,6
30,9
31,3
31,6
31,9
32,2
32,5

81,5
83,8
86,2
88,6
91,1
93,5
95,9
98,5
91,0
93,5
96,2
98,9
102
104
107
110

29,8
30,1
30,4
30,7
31,0
31,4
31,7
32,0
33,4
33,8
34,1
34,5
34,8
35,2
35,5
35,9

75,8
77,9
80,2
82,5
84,7
87,0
89,2
91,6
84,6
87,0
89,5
92,0
94,6
97,1
100
102

32,9
33,2
33,5
33,9
34,2
34,6
34,9
35,2
36,9
37,2
37,6
38,0
38,4
38,8
39,1
39,5

70,2
72,2
74,3
76,4
78,5
80,6
82,6
84,9
78,4
80,5
82,9
85,2
87,6
89,9
92,2
94,7

35,8
36,2
36,5
36,9
37,3
37,7
38,0
38,4
40,2
40,6
41,0
41,4
41,8
42,3
42,7
43,1

64,5
66,3
68,2
72,0
74,0
76,1
-

38,7
39,1
39,5
43,4
43,9
44,3
-

80

90

100

Tw= Temperatura acqua in uscita in C


kWf = Potenza frigorifera netta(kW).
kWa = Potenza assorbita dai compressori (kW)
Le prestazioni standard si riferiscono ad un differenza di 5 C di temperatura tra acqua entrante ed uscente dallo scambiatore a piastre, e al funzionamento dell'unit con
tutti i ventilatori alla massima velocit. Si considera inoltre un fattore di sporcamento di 0.44 x 10-4 m2 K/W e l'unit posta a zero metri sul livello del mare (Pb = 1013mbar).

22

TECHNICAL SPECIFICATIONS AND STANDARD PERFORMANCES - IR COOLING UNIT ONLY

Mod. 115-160
OUTDOOR AIR TEMPERATURE (C D.B.)

MOD.

115

130

145

160

180

200

Tw
5
6
7
8
9
10
11
12
5
6
7
8
9
10
11
12
5
6
7
8
9
10
11
12
5
6
7
8
9
10
11
12
5
6
7
8
9
10
11
12
5
6
7
8
9
10
11
12

20
kWf
121
124
128
132
135
139
142
146
136
140
144
148
152
156
160
164
154
158
163
168
172
177
181
186
194
199
205
211
217
223
228
235
-

25
kWa
26,9
27,1
27,4
27,7
28,0
28,3
28,5
28,8
30,7
30,9
31,3
31,6
31,9
32,2
32,6
32,9
34,8
35,1
35,5
35,9
36,2
36,6
37,0
37,3
42,4
42,8
43,2
43,7
44,1
44,6
45,0
45,4
-

kWf
113
116
119
123
126
130
133
136
127
130
134
138
142
145
149
153
144
148
152
156
161
165
169
174
181
186
192
197
202
208
213
219
-

30
kWa
30,9
31,2
31,5
31,9
32,2
32,5
32,8
33,2
35,3
35,6
36,0
36,4
36,7
37,1
37,5
37,8
40,0
40,4
40,8
41,3
41,7
42,1
42,5
42,9
48,8
49,2
49,7
50,3
50,8
51,3
51,8
52,3
-

kWf
107
110
113
116
119
123
126
129
120
123
127
130
134
138
141
145
136
140
144
148
152
156
160
164
171
176
181
186
191
196
202
207
-

35
kWa
34,1
34,4
34,7
35,1
35,5
35,8
36,2
36,5
38,9
39,2
39,6
40,1
40,5
40,9
41,3
41,7
44,1
44,5
45,0
45,5
45,9
46,4
46,9
47,3
53,7
54,2
54,8
55,4
55,9
56,5
57,1
57,6
-

kWf
100
103
106
109
112
115
118
121
113
116
119
122
126
129
132
136
128
131
135
139
143
146
150
154
161
165
170
175
180
184
189
194
-

40
kWa
37,6
37,9
38,3
38,7
39,1
39,5
39,9
40,3
42,9
43,3
43,7
44,2
44,6
45,1
45,5
46,0
48,6
49,1
49,6
50,1
50,7
51,2
51,7
52,2
59,2
59,8
60,4
61,1
61,7
62,3
62,9
63,5
-

kWf
93,2
95,8
98,6
101
104
107
110
113
105
108
111
114
117
120
123
127
119
122
126
129
133
136
140
144
150
154
158
163
167
172
176
181
-

45
kWa
41,4
41,8
42,2
42,7
43,1
43,5
44,0
44,4
47,2
47,7
48,2
48,7
49,2
49,7
50,2
50,7
53,6
54,1
54,7
55,3
55,8
56,4
56,9
57,5
65,3
65,9
66,6
67,3
68,0
68,7
69,3
70,0
-

kWf
86,4
88,8
91,3
93,9
96,5
99,1
102
104
97,0
100
103
105
108
111
114
117
110
113
116
120
123
126
129
133
139
142
146
151
155
159
163
167
-

50
kWa
45,1
45,6
46,0
46,5
47,0
47,5
47,9
48,4
51,5
52,0
52,5
53,1
53,6
54,2
54,7
55,2
58,4
59,0
59,6
60,3
60,9
61,5
62,1
62,7
71,2
71,8
72,6
73,4
74,1
74,9
75,6
76,3
-

kWf
79,3
81,5
83,9
89,1
91,5
94,2
101
104
107
127
131
135
-

kWa
48,8
49,3
49,8
55,7
56,2
56,8
63,2
63,8
64,4
77,0
77,7
78,5
-

Tw= Temperatura acqua in uscita in C


kWf = Potenza frigorifera netta(kW).
kWa = Potenza assorbita dai compressori (kW)
Le prestazioni standard si riferiscono ad un differenza di 5 C di temperatura tra acqua entrante ed uscente dallo scambiatore a piastre, e al funzionamento dell'unit con
tutti i ventilatori alla massima velocit. Si considera inoltre un fattore di sporcamento di 0.44 x 10-4 m2 K/W e l'unit posta a zero metri sul livello del mare (Pb = 1013mbar).

23

TECHNICAL SPECIFICATIONS AND STANDARD PERFORMANCES - IR COOLING UNIT ONLY


Version with Desuperheater (VD)
Recovery heat exchanger specifications
Model
50
60
70
80
90
100 115 130 145 160 180 200
Type of recovery exchanger
STAINLESS STEEL BRAZE PLATES
Quantity
1
Max. operating pressure on wet side
600
Total water content of recovery exchangers
0,6
0,8
1,3
1,8
Unit specification
Recovered heating capacity (1)
15,7 17,6 20,0 23,6 27,1 30,4 34,4 38,4 44,0 49,3 55,4 61,3
Recovered water flow rate (1)
0,75 0,84 0,96 1,13 1,29 1,45 1,64 1,83 2,10 2,36 2,65 2,93
Recovered water pressure drop (1)
9
11
14
19
15
18
11
14
18
22
18
21
(1):

UM
N
kPa
l
kW
l/s
kPa

The data refer to: Water temperature: evaporator inlet :12C - evaporator outlet: 7C, Outdoor air temperature 35C.
The data refer to: Water temperature: recovery inlet :40C - recovery outlet: 45C.

Recovered heating capacity in Version with Desuperheater (VD)

MOD. TWR

50

55

60

70

90

100

24

30
35
40
45
50
55
60
65
70
30
35
40
45
50
55
60
65
70
30
35
40
45
50
55
60
65
70
30
35
40
45
50
55
60
65
70
30
35
40
45
50
55
60
65
70
30
35
40
45
50
55
60
65
70

OUTDOOR AIR TEMPERATURE (C D.B.)


40
25
30
35
45
kWtr = RECOVERED HEATING CAPACITY [KW]
12,8
12,9
12,6
11,9
10,9
9,5
7,7
5,5
3,0
14,6
14,6
14,2
13,5
12,4
10,9
9,0
6,8
4,3
16,6
16,6
16,1
15,3
14,0
12,4
10,3
7,8
4,8
19,4
19,4
19,0
18,0
16,4
14,4
11,8
8,6
5,0
22,5
22,6
22,1
20,9
19,1
16,7
13,7
10,1
5,9
25,5
25,3
24,7
23,5
21,7
19,5
16,7
13,4
9,5

14,7
14,8
14,4
13,7
12,5
10,9
8,8
6,4
3,5
16,8
16,8
16,3
15,5
14,2
12,5
10,4
7,9
4,9
19,0
19,0
18,6
17,6
16,2
14,2
11,8
8,9
5,6
22,2
22,3
21,7
20,6
18,8
16,5
13,5
9,9
5,7
25,6
25,7
25,1
23,8
21,8
19,1
15,6
11,5
6,7
29,0
28,8
28,1
26,7
24,7
22,1
19,0
15,2
10,8

16,9
17,0
16,6
15,7
14,3
12,5
10,1
7,3
4,0
19,0
19,0
18,6
17,6
17,0
15,0
12,5
9,4
5,9
21,6
21,6
21,1
20,0
18,4
16,2
13,4
10,2
6,3
25,4
25,5
24,9
23,6
21,6
18,9
15,5
11,3
6,5
29,2
29,3
28,6
27,1
24,8
21,7
17,8
13,1
7,6
33,0
32,8
32,0
30,4
28,2
25,2
21,6
17,3
12,3

19,3
19,4
18,9
17,9
16,4
14,3
11,6
8,4
4,6
21,7
21,7
21,2
20,1
18,5
16,3
13,5
10,2
6,4
24,7
24,7
24,1
22,8
21,0
18,5
15,4
11,6
7,2
29,2
29,3
28,6
27,1
24,8
21,7
17,8
13,0
7,5
33,3
33,4
32,6
30,9
28,3
24,7
20,3
14,9
8,7
37,5
37,3
36,3
34,5
32,0
28,6
24,5
19,6
14,0

22,0
22,1
21,6
20,5
18,7
16,3
13,2
9,5
5,2
24,6
24,6
24,0
22,8
20,9
18,4
15,3
11,6
7,2
28,0
28,0
27,3
25,9
23,8
20,9
17,4
13,1
8,2
33,4
33,6
32,8
31,1
28,4
24,8
20,4
14,9
8,6
37,8
38,0
37,1
35,1
32,1
28,1
23,1
17,0
9,9
42,5
42,2
41,1
39,1
36,2
32,4
27,8
22,2
15,8

kWtr = RECOVERED HEATING CAPACITY [KW]


Twr = Desuperheater outlet water temperature, tin-out= 5C

MOD. TWR

115

130

145

160

180

200

30
35
40
45
50
55
60
65
70
30
35
40
45
50
55
60
65
70
30
35
40
45
50
55
60
65
70
30
35
40
45
50
55
60
65
70
30
35
40
45
50
55
60
65
70
30
35
40
45
50
55
60
65
70

OUTDOOR AIR TEMPERATURE (C D.B.)


40
25
30
35
45
kWtr = RECOVERED HEATING CAPACITY [KW]
29,1
28,9
28,2
26,7
24,7
21,9
18,6
14,6
10,0
32,3
32,3
31,5
29,8
27,4
24,2
20,1
15,2
9,6
36,7
36,8
35,9
34,1
31,3
27,5
22,8
17,1
10,5
41,5
41,4
40,3
38,3
35,2
31,2
26,1
20,1
13,1
46,6
46,5
45,3
43,0
39,6
35,0
29,4
22,6
14,7
51,6
51,5
50,2
47,6
43,8
38,8
32,5
25,0
16,2

33,0
32,8
31,9
30,3
28,0
24,9
21,1
16,6
11,4
36,6
36,6
35,6
33,8
31,1
27,4
22,8
17,3
10,8
41,7
41,8
40,8
38,7
35,6
31,3
25,9
19,5
11,9
47,1
47,1
45,8
43,5
40,0
35,4
29,7
22,8
14,8
53,0
52,9
51,5
48,9
45,0
39,8
33,4
25,7
16,7
58,6
58,5
57,0
54,1
49,8
44,0
36,9
28,4
18,5

37,5
37,3
36,2
34,4
31,7
28,3
24,0
18,8
12,9
41,5
41,5
40,5
38,4
35,3
31,1
25,9
19,6
12,3
47,4
47,5
46,4
44,0
40,4
35,5
29,4
22,1
13,5
53,4
53,3
52,0
49,3
45,4
40,1
33,7
25,9
16,8
60,0
59,9
58,4
55,4
51,0
45,1
37,8
29,1
18,9
66,4
66,3
64,6
61,3
56,4
49,9
41,8
32,2
20,9

42,5
42,3
41,1
39,0
36,0
32,0
27,2
21,4
14,6
47,1
47,1
45,9
43,5
40,0
35,2
29,3
22,2
14,0
53,6
53,8
52,5
49,8
45,7
40,2
33,3
25,0
15,3
60,5
60,4
58,8
55,8
51,3
45,4
38,1
29,3
19,0
68,0
67,8
66,1
62,7
57,7
51,1
42,8
32,9
21,4
75,2
75,1
73,1
69,4
63,8
56,5
47,4
36,4
23,7

48,1
47,8
46,5
44,1
40,7
36,2
30,7
24,2
16,5
53,2
53,2
51,9
49,2
45,2
39,9
33,2
25,1
15,8
60,5
60,6
59,2
56,2
51,5
45,4
37,6
28,2
17,3
68,2
68,1
66,3
62,9
57,9
51,2
42,9
33,0
21,5
76,6
76,5
74,5
70,7
65,0
57,6
48,3
37,1
24,1
84,8
84,6
82,4
78,2
72,0
63,7
53,4
41,1
26,7

TECHNICAL SPECIFICATIONS AND STANDARD PERFORMANCES - IR COOLING UNIT ONLY

Specific data fot Brine Version (VI)


Correction factors to apply to the basic version data
Brine pencentage
freezing point [C]
Produced water temperature
Cooling capacityr c.f.
Compressor power input c.f.
Water flow rate c.f.
Water pressure drop c.f.
Brine pencentage
freezing point [C]
Produced water temperature
Cooling capacityr c.f.
Compressor power input c.f.
Water flow rate c.f.
Water pressure drop c.f.
Brine pencentage
freezing point [C]
Produced water temperature
Cooling capacityr c.f.
Compressor power input c.f.
Water flow rate c.f.
Water pressure drop c.f.

4
0,912
0,967
0,984
1,289

4
0,899
0,960
1,013
1,431

4
0,884
0,880
1,062
1,542

2
0,855
0,957
0,899
1,071

20% Ethylene Glicol


-8
0
-2
-4
0,798
0,738
0,683
0,947
0,927
0,897
0,821
0,750
0,685
0,890
0,740
0,615

-6
0,620
0,490

-8
0,561
0,390

2
0,842
0,950
0,928
1,184

30% Ethylene Glicol


-14
0
-2
-4
0,785
0,725
0,670
0,940
0,920
0,890
0,851
0,780
0,715
0,979
0,810
0,670

-6
0,613
0,870
0,650
0,530

-8
0,562
0,840
0,591
0,419

2
0,827
0,870
0,970
1,279

40% Ethylene Glicol


-22
0
-2
-4
0,770
0,710
0,655
0,860
0,840
0,810
0,887
0,810
0,740
1,061
0,880
0,730

-6
0,598
0,790
0,670
0,580

-8
0,547
0,760
0,607
0,461

A calculation example showing how the table is used is given below.


Consider unit IR 160.2 in the Basic Version with:
- Cooling capacity of the Basic Version unit (VB):
- Power input of the Compressors in the Basic Version unit (VB):
- Water Flow Rate of the Basic Version unit (VB):
- Water pressure drop of the Basic Version unit (VB):
- with 30% brine and -2C temperature of the water produced

PfVB = 158 kW
PassCP,VB= 53.2 kW
QVB= 7.55 l/s
pVB= 39 kPa

The corresponding values for the Brine Version are:


- Cooling capacity
PfVI = PfVB x (0.725) = 115 kW
- Compressor power input
PassCP,VI = PassCP,VB x (0.92)= 48.9 kW
- Water flow rate
QVI= QVB x (0.78)= 5.89 l/s
- Water pressure drop
pVI =pVB x (0.81)= 32 kPa
If you need to calculate the performances of the unit with outdoor air temp. different than 35C, you have to use the values for
PfVB and PassCP,VB reported on the tables standard performances for the requisited air temp. and with water leaving
temp=7C.
With PfVB calculate QVB and using the graph water pressure drop Basic Version you have pVB. Then apply the corrective
coefficients indicated on the tables for VI.
In case of other type of antifreezing fluid please contact our sales office.

25

TECHNICAL SPECIFICATIONS AND STANDARD PERFORMANCES - IP HEAT PUMP UNITS


Technical specifications of unit AB Standard unit
Model
Power supply
Type of refrigerant
Circuits
Cooling capacity (1) (E)
Compressors power input
EER
Total power input (1) (E)
Total EER
ESEER (E)
Water flow rate (1)
Water pressure drops (1) (E)
Available static head (1) (MP)
Heating capacity (2) (E)
Compressors power input
COP
Total power input (2) (E)
Total COP
Water flow rate (2)
Water pressure drops (2) (E)
Available static head (2) (MP)

(1)

(2)

50

60

70

80

52,9
16,2
3,27
18,0
2,94
4,06
2,53
41
138
53,2
16,2
3,28
18,0
2,96
2,54
41
137

57,5
18,4
3,13
20,2
2,85
3,93
2,75
49
120
58,0
18,0
3,22
19,8
2,93
2,77
50
119

67,2
20,7
3,25
22,5
2,99
4,12
3,21
46
102
67,7
20,3
3,34
22,1
3,07
3,23
46
101

74,1
24,7
3,00
26,5
2,80
3,86
3,54
35
85
76,2
23,1
3,30
24,9
3,06
3,64
37
80

90
100
115
400V - 3ph+N - 50
R410A
1
89,2 99,0
110
28,0 31,4 35,4
3,19 3,15 3,11
31,6 35,0 39,0
2,82 2,83 2,82
3,90 3,90 3,89
4,26 4,73 5,26
38
38
39
149
136
117
91,4
103
113
28,2 31,4 34,8
3,24 3,28 3,25
31,8 35,0 38,4
2,87 2,94 2,94
4,37 4,92 5,40
40
41
41
142
125
111

Compressor
Type
Quantity
Load steps
Oil charge CP1 3,25
Oil charge CP2 3,25
Heat Exchanger
Tipo
Quantit
Contenuto acqua

3,6

3,25
3,25

3,25
3,25

3,6

4,6

3,25
3,25

5,4

3,25
4,7

7,6

130
Hz

145

160

180

200

122
40,0
3,05
43,6
2,80
3,86
5,83
37
98
125
39,0
3,21
42,6
2,93
5,97
38
94

138
45,8
3,01
51,2
2,70
3,72
6,59
36
125
143
45,1
3,17
50,5
2,83
6,83
39
116

154
50,5
3,05
55,9
2,75
3,80
7,36
37
100
156
49,8
3,13
55,2
2,83
7,45
38
98

178
55,0
3,24
62,2
2,86
3,95
8,50
57
144
184
54,0
3,41
61,2
3,01
8,79
61
135

198
62,5
3,17
69,7
2,84
3,92
9,46
56
109
202
61,0
3,31
68,2
2,96
9,65
58
105

UM
V-f-Hz
/
n
kW
kW
kW
l/s
kPa
kPa
kW
kW
kW
l/s
kPa
kPa

6,3
6,3

/
n
%
l
l

13,0

/
n
l

Scroll
2
0-50-100
4,7
4,7
4,7
6,8

6,8
6,8

6,8
6,3

Brazed plates
1
8,4
9,7
10,9

12,6

6,3
6,3

14,5

6,3
6,3

11,1

Fan
Type
Quantity
Maximum rotational speed
Total air flow rate
Power input

Axial
4
2
3
n
900
rpm
29050 29050 28100 27680 41460 41460 47440 47440 62190 59820 82920 79760 m3/h
7,2
1,8
3,6
5,4
kW
3

Coil
Type
Quantity
Front area

Aluminum fins and copper tubes


1
4,72
5,90

3,38

7,41

/
n
m2

Water Storage Tank (SAA accessory)


Water volume
Safety valve setting
Surge chamber volume
Surge chamber default pressure
Max. operating pressure

400

200

460

600
24

12
150

800

1000

l
kPa
l
kPa
kPa

Electrical Data
Units without pumping module
Total maximum power input [ FLA ]
Total maximum power input [ FLI ]
Total maximum starting current [ MIC ]

48,2
25,5
146

Units with pumping module MP-AM and MP-PS (1


Total maximum power input [ FLA ]
51,4
Total maximum power input [ FLI ]
27,2
Total maximum starting current [ MIC ]
149

50,9
27,7
147

58,3
31,1
173

or 2 pumps)
54,1 61,5
29,4 32,8
150
176

Units with pumping module MP-AM AP (1 or 2 pumps)


Total maximum power input [ FLA ]
54,4 57,1
Total maximum power input [ FLI ]
29,2 31,4
Total maximum starting current [ MIC ]
152
153

64,6
34,8
179

Data referred to standard operating condition.


(1): water temperature: in 12C - out 7C air temperature: in 35C d.b.
(2): water temperature: in 40C - out 45C air temperature: in 7C d.b. 87% RH
(MP): with standard hydronic kit MP-AM and MP-SS
(SAA): with storage tank
(E): data declared according to LCP EUROVENT certification program

26

68,6
35,5
211

76,0
43,6
265

81,5
49,2
270

89,9
53,9
317

98,3
58,6
325

117
69,4
368

131
78,2
382

150
90,8
470

165
101
485

A
kW
A

71,8
37,2
214

80,8
46,5
269

86,3
52,1
275

94,7
56,8
322

103
61,5
330

123
72,7
373

137
81,5
388

158
95,6
479

173
106
493

A
kW
A

74,9
39,2
217

82,2
47,3
271

87,8
53,0
276

98,1
58,7
325

106
63,4
334

125
74,2
376

140
83,0
390

161
97,3
481

176
108
496

A
kW
A

TECHNICAL SPECIFICATIONS AND STANDARD PERFORMANCES - IP HEAT PUMP UNITS


Standard performances in cooling mode AB Standard Unit
Mod. 50-100
OUTDOOR AIR TEMPERATURE (C D.B.)

MOD.

Tw
kWf

kWa

kWf

kWa

kWf

kWa

kWf

kWa

kWf

kWa

kWf

kWa

kWf

kWa

50

5
6
7
8
9
10
11
12

60,4
62,1
63,9
65,7
67,5
69,3
71,0
73,0

11,4
11,5
11,6
11,7
11,8
12,0
12,1
12,2

56,4
57,9
59,6
61,3
63,0
64,7
66,3
68,1

13,1
13,2
13,3
13,5
13,6
13,8
13,9
14,0

53,3
54,8
56,4
58,0
59,6
61,1
62,7
64,4

14,4
14,5
14,7
14,9
15,0
15,2
15,3
15,5

50,0
51,4
52,9
54,4
55,9
57,4
58,8
60,4

15,9
16,0
16,2
16,4
16,5
16,7
16,9
17,0

46,5
47,8
49,2
50,6
52,0
53,4
54,8
56,2

17,5
17,7
17,9
18,1
18,2
18,4
18,6
18,8

43,1
44,3
45,6
46,9
48,2
49,4
50,7
52,1

19,1
19,3
19,5
19,7
19,9
20,1
20,3
20,5

39,6
40,7
41,9
-

20,6
20,8
21,0
-

60

5
6
7
8
9
10
11
12

65,6
67,5
69,4
71,4
73,4
75,3
77,2
79,3

12,9
13,0
13,2
13,3
13,4
13,6
13,7
13,8

61,3
63,0
64,8
66,6
68,5
70,3
72,1
74,0

14,9
15,0
15,1
15,3
15,5
15,6
15,8
15,9

57,9
59,5
61,3
63,0
64,7
66,5
68,2
70,0

16,4
16,5
16,7
16,9
17,0
17,2
17,4
17,5

54,4
55,9
57,5
59,1
60,8
62,4
64,0
65,7

18,0
18,2
18,4
18,6
18,8
19,0
19,2
19,3

50,6
52,0
53,5
55,0
56,5
58,0
59,5
61,1

19,9
20,1
20,3
20,5
20,7
20,9
21,1
21,3

46,8
48,1
49,5
51,0
52,4
53,7
55,1
56,6

21,7
21,9
22,1
22,4
22,6
22,8
23,0
23,3

43,0
44,2
45,5
-

23,4
23,7
23,9
-

70

5
6
7
8
9
10
11
12

76,7
78,8
81,1
83,4
85,7
88,0
90,2
92,7

14,5
14,7
14,8
15,0
15,1
15,3
15,4
15,6

71,6
73,6
75,7
77,9
80,0
82,1
84,2
86,5

16,7
16,9
17,0
17,2
17,4
17,6
17,7
17,9

67,7
69,6
71,6
73,6
75,7
77,7
79,7
81,8

18,4
18,6
18,8
19,0
19,2
19,4
19,6
19,7

63,5
65,3
67,2
69,1
71,0
72,9
74,8
76,8

20,3
20,5
20,7
20,9
21,1
21,3
21,6
21,8

59,1
60,8
62,5
64,3
66,1
67,8
69,6
71,4

22,4
22,6
22,8
23,1
23,3
23,5
23,8
24,0

54,8
56,3
57,9
59,5
61,2
62,8
64,4
66,2

24,4
24,6
24,9
25,1
25,4
25,7
25,9
26,2

50,3
51,7
53,2
-

26,4
26,6
26,9
-

5
6
7
8
9
10
11
12
5
6
7
8
9
10
11
12
5
6
7
8
9
10
11
12

84,6
86,9
89,5
92,0
94,5
97,0
100
102
102
105
108
111
114
117
120
123
113
116
120
123
126
130
133
137

17,3
17,5
17,7
17,9
18,0
18,2
18,4
18,6
19,6
19,8
20,0
20,3
20,5
20,7
20,9
21,1
22,0
22,2
22,5
22,7
22,9
23,2
23,4
23,6

79,0
81,1
83,5
85,9
88,2
90,6
92,9
95,4
95,0
97,7
101
103
106
109
112
115
105
108
112
115
118
121
124
127

19,9
20,1
20,3
20,6
20,8
21,0
21,2
21,4
22,6
22,8
23,0
23,3
23,5
23,8
24,0
24,2
25,3
25,6
25,8
26,1
26,4
26,7
26,9
27,2

74,7
76,7
79,0
81,2
83,4
85,6
87,8
90,2
89,9
92,4
95,1
97,7
100
103
106
109
100
103
105
108
111
114
117
121

22,0
22,2
22,4
22,7
22,9
23,1
23,3
23,6
24,9
25,1
25,4
25,7
25,9
26,2
26,4
26,7
27,9
28,2
28,5
28,8
29,1
29,4
29,7
29,9

70,1
72,0
74,1
76,2
78,3
80,4
82,4
84,7
84,3
86,7
89,2
91,7
94,3
96,8
99,2
102
93,6
96,2
99,0
102
105
107
110
113

24,2
24,4
24,7
25,0
25,2
25,5
25,7
26,0
27,5
27,7
28,0
28,3
28,6
28,9
29,2
29,4
30,8
31,1
31,4
31,7
32,1
32,4
32,7
33,0

65,2
67,0
68,9
70,9
72,8
74,8
76,7
78,8
78,5
80,6
83,0
85,3
87,7
90,0
92,3
94,8
87,1
89,5
92,1
94,7
97,3
100
102
105

26,7
26,9
27,2
27,5
27,8
28,1
28,4
28,6
30,3
30,5
30,9
31,2
31,5
31,8
32,1
32,5
33,9
34,3
34,6
35,0
35,3
35,7
36,0
36,4

60,4
62,0
63,9
65,7
67,5
69,3
71,0
73,0
72,7
74,7
76,9
79,0
81,2
83,4
85,5
87,8
80,7
82,9
85,3
87,7
90,1
92,5
94,9
97,5

29,1
29,4
29,7
30,0
30,3
30,6
30,9
31,2
33,0
33,3
33,6
34,0
34,4
34,7
35,0
35,4
37,0
37,3
37,7
38,1
38,5
38,9
39,3
39,7

55,5
57,0
58,7
66,8
68,6
70,6
74,1
76,1
78,4
-

31,5
31,8
32,1
35,7
36,0
36,4
40,0
40,4
40,8
-

80

90

100

20

25

Tw= Outlet water temperature in C

30

kWf

35

40

= refrigerating power (kW).

45

50

kWa = Power input of compressors (kW)

The standard performances refer to a 5C temperature difference between the water entering and leaving the plate-type heat exchanger and to operation of the unit
with all the fans to top speed. A 0.44 x 10-4 m2 K/W fouling factor has also been considered with the unit installed at zero meters above sea level (Pb = 1013mbar).

27

TECHNICAL SPECIFICATIONS AND STANDARD PERFORMANCES - IP HEAT PUMP UNITS

Mod. 115-160
OUTDOOR AIR TEMPERATURE (C D.B.)

MOD.

115

130

145

160

180

200

Tw
5
6
7
8
9
10
11
12
5
6
7
8
9
10
11
12
5
6
7
8
9
10
11
12
5
6
7
8
9
10
11
12
5
6
7
8
9
10
11
12
5
6
7
8
9
10
11
12

20
kWf
126
129
133
137
140
144
148
152
139
143
147
151
156
160
164
168
158
162
167
171
176
181
185
190
176
181
186
191
196
202
207
212
203
209
215
221
227
233
239
246
226
232
239
246
253
259
266
273

25
kWa
24,8
25,1
25,3
25,6
25,9
26,1
26,4
26,6
28,1
28,3
28,6
28,9
29,2
29,5
29,8
30,1
32,1
32,4
32,8
33,1
33,5
33,8
34,1
34,5
35,4
35,8
36,1
36,5
36,9
37,3
37,6
38,0
38,6
39,0
39,4
39,8
40,2
40,6
41,0
41,4
43,9
44,3
44,7
45,2
45,7
46,1
46,6
47,0

Tw= Outlet water temperature in C

kWf
117
120
124
127
131
134
138
142
130
134
137
141
145
149
153
157
147
151
156
160
164
169
173
178
164
169
174
178
183
188
193
198
190
195
201
206
212
218
223
229
211
217
223
229
236
242
248
255

30
kWa
28,6
28,8
29,1
29,5
29,8
30,1
30,3
30,6
32,3
32,6
32,9
33,3
33,6
34,0
34,3
34,6
37,0
37,3
37,7
38,1
38,5
38,9
39,3
39,6
40,8
41,2
41,6
42,0
42,5
42,9
43,3
43,7
44,4
44,8
45,3
45,8
46,2
46,7
47,2
47,6
50,5
50,9
51,5
52,0
52,5
53,1
53,6
54,1

kWf
111
114
117
121
124
127
130
134
123
126
130
134
137
141
145
149
139
143
147
151
155
160
164
168
155
159
164
169
173
178
183
188
179
184
190
195
200
206
211
217
199
205
211
217
223
229
235
241
kWf

35
kWa
31,5
31,8
32,1
32,5
32,8
33,1
33,4
33,8
35,6
35,9
36,3
36,7
37,0
37,4
37,8
38,2
40,7
41,1
41,5
42,0
42,4
42,8
43,3
43,7
44,9
45,3
45,8
46,3
46,8
47,2
47,7
48,2
48,9
49,4
49,9
50,4
50,9
51,4
52,0
52,5
55,6
56,1
56,7
57,3
57,9
58,5
59,0
59,6

kWf
104
107
110
113
116
119
122
126
115
119
122
125
129
132
136
139
130
134
138
142
146
150
154
158
146
150
154
158
163
167
171
176
168
173
178
183
188
193
198
203
187
192
198
204
209
215
220
226

40
kWa
34,7
35,0
35,4
35,8
36,1
36,5
36,9
37,2
39,2
39,6
40,0
40,4
40,8
41,3
41,7
42,1
44,9
45,3
45,8
46,3
46,8
47,2
47,7
48,2
49,5
50,0
50,5
51,1
51,6
52,1
52,6
53,1
53,9
54,4
55,0
55,6
56,2
56,7
57,3
57,8
61,3
61,9
62,5
63,2
63,8
64,5
65,1
65,7

= refrigerating power (kW).

kWf
96,8
99,4
102
105
108
111
114
117
107
110
114
117
120
123
126
130
121
125
128
132
136
139
143
147
135
139
143
147
151
155
159
164
157
161
166
170
175
180
184
189
174
179
184
189
195
200
205
210

45
kWa
38,3
38,6
39,0
39,4
39,8
40,2
40,6
41,0
43,2
43,6
44,1
44,6
45,0
45,5
45,9
46,4
49,5
50,0
50,5
51,0
51,6
52,1
52,6
53,1
54,6
55,1
55,7
56,3
56,8
57,4
58,0
58,5
59,4
60,0
60,6
61,3
61,9
62,5
63,1
63,7
67,6
68,2
68,9
69,6
70,3
71,0
71,7
72,4

kWf
89,6
92,1
94,8
97,5
100
103
105
108
99,4
102
105
108
111
114
117
120
112
116
119
122
126
129
132
136
125
129
133
136
140
144
148
152
145
149
153
158
162
166
171
175
161
166
171
175
180
185
190
195

50
kWa
41,7
42,1
42,5
43,0
43,4
43,9
44,3
44,7
47,1
47,6
48,1
48,6
49,1
49,6
50,1
50,5
54,0
54,5
55,0
55,6
56,2
56,8
57,3
57,9
59,5
60,1
60,7
61,4
62,0
62,6
63,2
63,8
64,8
65,4
66,1
66,8
67,5
68,2
68,8
69,5
73,7
74,3
75,1
75,9
76,7
77,5
78,2
79,0

kWf
82,3
84,6
87,1
91,3
93,8
96,6
103
106
109
115
118
122
133
137
141
148
152
157
-

kWa
45,1
45,5
46,0
51,0
51,4
52,0
58,4
58,9
59,5
64,3
64,9
65,6
70,1
70,7
71,5
79,6
80,4
81,2
-

kWa = Power input of compressors (kW)

The standard performances refer to a 5C temperature difference between the water entering and leaving the plate-type heat exchanger and to operation of the unit
with all the fans to top speed. A 0.44 x 10-4 m2 K/W fouling factor has also been considered with the unit installed at zero meters above sea level (Pb = 1013mbar).

28

TECHNICAL SPECIFICATIONS AND STANDARD PERFORMANCES - IP HEAT PUMP UNITS


Standard performances in heating mode AB Standard Unit
OUTDOOR AIR TEMPERATURE (C D.B.)

MOD.

50

60

70

80

90

100

115

130

145

160

180

200

Tw
30
35
40
45
50
30
35
40
45
50
30
35
40
45
50
30
35
40
45
50
30
35
40
45
50
30
35
40
45
50
30
35
40
45
50
30
35
40
45
50
30
35
40
45
50
30
35
40
45
50
30
35
40
45
50
30
35
40
45
50

-6

-2

12

15

kWt

kWa

kWt

kWa

kWt

kWa

kWt

kWa

kWt

kWa

kWt

kWa

kWt

kWa

40,6
40,4
40,2
39,9
39,6
44,3
44,1
43,8
43,5
43,2
51,7
51,4
51,1
50,8
50,4
58,2
57,9
57,6
57,2
56,8
69,8
69,4
69,0
68,6
68,1
78,7
78,3
77,8
77,3
76,7
86,3
85,8
85,4
84,8
84,2
95,5
95,0
94,4
93,8
93,1
109
109
108
107
107
119
119
118
117
116
141
140
139
138
137
154
153
153
152
150

11,5
12,8
14,2
15,8
17,6
12,8
14,2
15,8
17,5
19,5
14,5
16,0
17,8
19,8
22,0
16,4
18,2
20,3
22,5
25,0
20,1
22,2
24,7
27,5
30,6
22,4
24,8
27,5
30,6
34,0
24,8
27,5
30,5
33,9
37,7
27,8
30,8
34,2
38,0
42,3
32,1
35,6
39,6
44,0
48,9
35,5
39,3
43,7
48,6
54,0
38,4
42,6
47,4
52,6
58,5
43,4
48,1
53,5
59,5
66,1

46,6
46,3
46,1
45,7
45,4
50,8
50,5
50,2
49,9
49,5
59,2
58,9
58,6
58,2
57,8
66,7
66,3
66,0
65,5
65,1
80,0
79,6
79,1
78,6
78,0
90,1
89,7
89,2
88,6
87,9
98,9
98,4
97,8
97,1
96,5
109
109
108
107
107
125
125
124
123
122
137
136
135
134
133
161
160
159
158
157
177
176
175
174
172

11,6
12,9
14,3
15,9
17,7
12,9
14,3
15,9
17,7
19,6
14,5
16,1
17,9
19,9
22,1
16,5
18,3
20,4
22,7
25,2
20,2
22,4
24,9
27,7
30,7
22,5
24,9
27,7
30,8
34,2
24,9
27,6
30,7
34,1
37,9
27,9
31,0
34,4
38,2
42,5
32,3
35,8
39,8
44,2
49,2
35,7
39,5
43,9
48,8
54,3
38,7
42,9
47,7
53,0
58,9
43,7
48,4
53,8
59,8
66,5

50,9
50,7
50,4
50,0
49,7
55,5
55,2
54,9
54,5
54,2
64,8
64,5
64,1
63,7
63,2
72,9
72,6
72,1
71,7
71,2
87,5
87,0
86,5
85,9
85,3
98,6
98,1
97,5
96,8
96,2
108
108
107
106
106
120
119
118
118
117
137
136
135
134
134
149
149
148
147
146
176
175
174
173
172
193
192
191
190
189

11,8
13,0
14,5
16,1
17,9
13,1
14,5
16,1
17,9
19,9
14,7
16,3
18,2
20,2
22,4
16,8
18,6
20,7
23,0
25,5
20,5
22,7
25,2
28,0
31,2
22,8
25,3
28,1
31,2
34,7
25,3
28,0
31,1
34,6
38,5
28,3
31,4
34,9
38,8
43,1
32,7
36,3
40,3
44,8
49,9
36,2
40,1
44,6
49,5
55,0
39,2
43,4
48,3
53,7
59,7
44,3
49,1
54,6
60,6
67,4

54,2
53,9
53,6
53,2
52,8
59,0
58,7
58,4
58,0
58,0
68,9
68,6
68,2
67,7
67,2
77,6
77,2
76,7
76,2
75,7
93,0
92,6
92,0
91,4
90,8
105
104
104
103
102
115
114
114
113
112
127
127
126
125
124
146
145
144
143
142
159
158
157
156
155
187
186
185
184
183
206
205
203
202
201

11,8
13,1
14,6
16,2
18,0
13,1
14,6
16,2
18,0
20,0
14,8
16,4
18,3
20,3
22,6
16,9
18,7
20,8
23,1
25,7
20,6
22,8
25,4
28,2
31,4
22,9
25,4
28,3
31,4
34,9
25,4
28,2
31,3
34,8
38,7
28,5
31,6
35,1
39,0
43,4
32,9
36,5
40,6
45,1
50,1
36,4
40,3
44,8
49,8
55,4
39,4
43,7
48,6
54,0
60,0
44,5
49,4
54,9
61,0
67,8

58,1
57,8
57,5
57,1
56,7
63,3
63,0
62,6
62,2
61,8
73,9
73,5
73,1
72,6
72,1
83,2
82,8
82,3
81,7
81,2
99,8
99,3
98,7
98,0
97,3
112
112
111
110
110
123
123
122
121
120
136
136
135
134
133
156
155
154
153
152
170
169
168
167
166
201
200
199
197
196
221
219
218
217
215

12,0
13,3
14,7
16,4
18,2
13,3
14,7
16,4
18,2
20,2
15,0
16,6
18,5
20,5
22,8
17,1
18,9
21,0
23,4
26,0
20,8
23,1
25,7
28,5
31,7
23,2
25,7
28,6
31,8
35,3
25,7
28,5
31,7
35,2
39,1
28,8
31,9
35,5
39,5
43,9
33,3
36,9
41,1
45,6
50,7
36,8
40,8
45,3
50,4
56,0
39,9
44,2
49,2
54,6
60,7
45,1
49,9
55,5
61,7
68,6

62,1
61,8
61,4
61,0
60,6
67,7
67,4
67,0
66,5
66,0
79,0
78,6
78,2
77,6
77,1
88,9
88,5
88,0
87,4
86,8
107
106
106
105
104
120
120
119
118
117
132
131
130
130
129
146
145
144
143
142
167
166
165
164
163
182
181
180
179
178
215
214
212
211
210
236
235
233
232
230

12,1
13,4
14,9
16,6
18,4
13,4
14,9
16,6
18,4
20,5
15,2
16,8
18,7
20,8
23,1
17,3
19,1
21,3
23,6
26,3
21,1
23,3
26,0
28,9
32,1
23,5
26,0
28,9
32,1
35,7
26,0
28,8
32,0
35,6
39,6
29,1
32,3
35,9
39,9
44,4
33,7
37,3
41,5
46,1
51,3
37,2
41,2
45,8
51,0
56,6
40,3
44,7
49,7
55,2
61,4
45,6
50,5
56,2
62,4
69,4

66,4
66,1
65,7
65,3
64,8
72,4
72,1
71,6
71,1
70,7
84,5
84,1
83,6
83,0
82,5
95,2
94,7
94,1
93,5
92,8
114
114
113
112
111
129
128
127
126
125
141
140
140
139
138
156
155
154
153
152
179
178
177
175
174
195
194
193
191
190
230
229
227
226
224
252
251
250
248
246

12,2
13,6
15,1
16,8
18,6
13,6
15,1
16,8
18,6
20,7
15,3
17,0
18,9
21,0
23,4
17,5
19,3
21,5
23,9
26,6
21,3
23,6
26,3
29,2
32,4
23,7
26,3
29,2
32,5
36,1
26,3
29,1
32,4
36,0
40,0
29,5
32,7
36,3
40,4
44,9
34,1
37,8
42,0
46,7
51,9
37,6
41,7
46,4
51,5
57,3
40,8
45,2
50,3
55,9
62,1
46,1
51,1
56,8
63,1
70,2

Tw= Outlet water temperature in C

kWt

= heating output (kW).

kWa = Power input of compressors (kW)

The standard performances refer to a 5C temperature difference between the water entering and leaving the plate-type heat exchanger, outdoor air with 87% relative humidity and to operation of the unit with all the fans to top speed. A 0.44 x 10-4 m2 K/W fouling factor has also
been considered with the unit installed at zero meters above sea level (Pb = 1013mbar).
NOTE
For air temperatures of less than 7C, the heating capacity is declared without considering the effect of the thawing cycles, strictly
correlated with the humidity in the outdoor air.

29

TECHNICAL SPECIFICATIONS AND STANDARD PERFORMANCES - IP HEAT PUMP UNITS


Technical specifications of unit AB Standard Unit + KS Silencer kit
Model
Power supply
Type of refrigerant
Circuits
Cooling capacity (1) (E)
Compressors power input
EER
Total power input (1) (E)
Total EER
ESEER (E)
Water flow rate (1)
Water pressure drops (1) (E)
Available static head (1) (MP)
Heating capacity (2) (E)
Compressors power input
COP
Total power input (2) (E)
Total COP
Water flow rate (2)
Water pressure drops (2) (E)
Available static head (2) (MP)

(1)

(2)

50

60

70

80

51,3
16,9
3,03
18,7
2,74
3,78
2,45
38
147
51,6
16,9
3,05
18,7
2,75
2,46
39
145

55,7
19,2
2,90
21,0
2,65
3,66
2,66
46
129
56,2
18,8
2,99
20,6
2,73
2,69
47
126

65,1
21,6
3,01
23,4
2,78
3,84
3,11
43
109
65,6
21,2
3,10
23,0
2,85
3,14
43
107

71,8
25,8
2,78
27,6
2,60
3,59
3,43
33
90
73,9
24,1
3,06
25,9
2,85
3,53
35
85

90
100
115
400V - 3ph+N - 50
R410A
1
86,5 96,0
107
29,3 32,8 37,0
2,95 2,92 2,88
32,9 36,4 40,6
2,63 2,63 2,63
3,63 3,64 3,62
4,13 4,58 5,09
36
36
36
159
144
124
88,6 99,8
110
29,5 32,8 36,4
3,01 3,04 3,01
33,1 36,4 40,0
2,68 2,74 2,74
4,23 4,77 5,23
38
39
39
151
133
117

Compressor
Type
Quantity
Load steps
Oil charge CP1 3,25
Oil charge CP2 3,25
Heat Exchanger
Type
Quantity
Water volume

3,6

3,25
3,25

3,25
3,25

3,6

4,6

3,25
3,25

5,4

3,25
4,7

7,6

130
Hz

145

160

180

200

118
41,8
2,83
45,4
2,60
3,59
5,65
34
105
121
40,8
2,97
44,4
2,73
5,79
36
100

134
47,9
2,79
53,3
2,51
3,47
6,39
34
132
139
47,1
2,94
52,5
2,64
6,62
37
123

149
52,8
2,83
58,2
2,57
3,54
7,13
35
107
151
52,1
2,91
57,5
2,63
7,22
36
104

173
57,5
3,00
64,7
2,67
3,68
8,24
54
152
178
56,4
3,16
63,6
2,80
8,52
57
144

192
65,3
2,94
72,5
2,65
3,65
9,17
52
116
196
63,8
3,07
71,0
2,76
9,35
55
112

UM
V-f-Hz
/
n
kW
kW
kW
l/s
kPa
kPa
kW
kW
kW
l/s
kPa
kPa

6,3
6,3

/
n
%
l
l

13,0

/
n
l

Scroll
2
0-50-100
4,7
4,7
4,7
6,8

6,8
6,8

6,8
6,3

Brazed plates
1
8,4
9,7
10,9

12,6

6,3
6,3

14,5

6,3
6,3

11,1

Fan
Type
Quantity
Maximum rotational speed
Total air flow rate
Power input

Axial
4
2
3
n
900
rpm
24208 24208 23417 23067 34550 34550 39533 39533 51825 49850 69100 66467 m3/h
7,2
1,8
3,6
5,4
kW
3

Coil
Type
Quantity
Front area

Aluminum fins and copper tubes


1
4,72
5,90

3,38

7,41

/
n
m2

Water Storage Tank (SAA accessory)


Water volume
Safety valve setting
Surge chamber volume
Surge chamber default pressure
Max. operating pressure

400

200

460

600
24

12
150

800

1000

l
kPa
l
kPa
kPa

Electrical Data
Units without pumping module
Total maximum power input [ FLA ]
Total maximum power input [ FLI ]
Total maximum starting current [ MIC ]

48,2
25,5
146

Units with pumping module MP-AM and MP-PS (1


Total maximum power input [ FLA ]
51,4
Total maximum power input [ FLI ]
27,2
Total maximum starting current [ MIC ]
149

50,9
27,7
147

58,3
31,1
173

or 2 pumps)
54,1 61,5
29,4 32,8
150
176

Units with pumping module MP-AM AP (1 or 2 pumps)


Total maximum power input [ FLA ]
54,4 57,1
Total maximum power input [ FLI ]
29,2 31,4
Total maximum starting current [ MIC ]
152
153

64,6
34,8
179

Data referred to standard operating condition.


(1): water temperature: in 12C - out 7C air temperature: in 35C d.b.
(2): water temperature: in 40C - out 45C air temperature: in 7C d.b. 87% RH
(MP): with standard hydronic kit MP-AM and MP-SS
(SAA): with storage tank
(E): data declared according to LCP EUROVENT certification program

30

68,6
35,5
211

76,0
43,6
265

81,5
49,2
270

89,9
53,9
317

98,3
58,6
325

117
69,4
368

131
78,2
382

150
90,8
470

165
101
485

A
kW
A

71,8
37,2
214

80,8
46,5
269

86,3
52,1
275

94,7
56,8
322

103
61,5
330

123
72,7
373

137
81,5
388

158
95,6
479

173
106
493

A
kW
A

74,9
39,2
217

82,2
47,3
271

87,8
53,0
276

98,1
58,7
325

106
63,4
334

125
74,2
376

140
83,0
390

161
97,3
481

176
108
496

A
kW
A

TECHNICAL SPECIFICATIONS AND STANDARD PERFORMANCES - IP HEAT PUMP UNITS


Standard performances in cooling mode AB Standard Unit + KS Silencer kit
Mod. 50-100
OUTDOOR AIR TEMPERATURE (C D.B.)

MOD.

Tw

20

25

30

35

40

45

50

kWf

kWa

kWf

kWa

kWf

kWa

kWf

kWa

kWf

kWa

kWf

kWa

kWf

kWa

50

5
6
7
8
9
10
11
12

58,6
60,2
61,9
63,7
65,4
67,2
68,9
70,8

11,9
12,0
12,1
12,2
12,3
12,5
12,6
12,7

54,7
56,2
57,8
59,4
61,1
62,7
64,3
66,1

13,6
13,8
13,9
14,1
14,2
14,3
14,5
14,6

51,7
53,1
54,7
56,2
57,8
59,3
60,8
62,5

15,0
15,2
15,3
15,5
15,7
15,8
16,0
16,1

48,5
49,8
51,3
52,8
54,2
55,6
57,1
58,6

16,6
16,7
16,9
17,1
17,3
17,4
17,6
17,8

45,1
46,4
47,7
49,1
50,4
51,8
53,1
54,5

18,3
18,4
18,6
18,8
19,0
19,2
19,4
19,6

41,8
43,0
44,2
45,5
46,7
48,0
49,2
50,5

19,9
20,1
20,3
20,5
20,7
20,9
21,1
21,4

38,4
39,5
40,6
-

21,5
21,7
22,0
-

60

5
6
7
8
9
10
11
12

63,6
65,3
67,2
69,2
71,1
72,9
74,8
76,8

13,5
13,6
13,7
13,9
14,0
14,2
14,3
14,4

59,3
61,0
62,8
64,5
66,3
68,1
69,8
71,7

15,5
15,6
15,8
16,0
16,1
16,3
16,5
16,6

56,1
57,7
59,4
61,0
62,7
64,4
66,0
67,8

17,1
17,2
17,4
17,6
17,8
18,0
18,1
18,3

52,7
54,1
55,7
57,3
58,9
60,4
62,0
63,6

18,8
19,0
19,2
19,4
19,6
19,8
20,0
20,2

49,0
50,4
51,8
53,3
54,8
56,2
57,6
59,2

20,8
20,9
21,2
21,4
21,6
21,8
22,0
22,3

45,4
46,6
48,0
49,4
50,7
52,1
53,4
54,8

22,6
22,8
23,1
23,3
23,6
23,8
24,0
24,3

41,7
42,8
44,1
-

24,5
24,7
24,9
-

70

5
6
7
8
9
10
11
12

74,3
76,4
78,6
80,8
83,0
85,2
87,4
89,8

15,2
15,3
15,5
15,6
15,8
15,9
16,1
16,3

69,4
71,3
73,4
75,4
77,5
79,6
81,6
83,8

17,4
17,6
17,8
18,0
18,2
18,3
18,5
18,7

65,6
67,4
69,4
71,3
73,3
75,2
77,2
79,3

19,2
19,4
19,6
19,8
20,0
20,2
20,4
20,6

61,6
63,3
65,1
66,9
68,8
70,6
72,4
74,4

21,2
21,4
21,6
21,8
22,1
22,3
22,5
22,7

57,3
58,9
60,6
62,3
64,0
65,7
67,4
69,2

23,3
23,6
23,8
24,1
24,3
24,6
24,8
25,0

53,0
54,5
56,1
57,7
59,3
60,8
62,4
64,1

25,5
25,7
26,0
26,2
26,5
26,8
27,0
27,3

48,7
50,1
51,5
-

27,5
27,8
28,1
-

5
6
7
8
9
10
11
12
5
6
7
8
9
10
11
12
5
6
7
8
9
10
11
12

82,0
84,2
86,7
89,1
91,6
94,0
96,4
99,0
98,7
101
104
107
110
113
116
119
110
113
116
119
122
126
129
132

18,1
18,3
18,5
18,7
18,9
19,0
19,2
19,4
20,6
20,8
21,0
21,2
21,4
21,6
21,8
22,0
23,0
23,2
23,5
23,7
24,0
24,2
24,4
24,7

76,5
78,6
80,9
83,2
85,5
87,8
90,0
92,4
92,2
94,7
97,5
100
103
106
108
111
102
105
108
111
114
117
120
124

20,8
21,0
21,2
21,5
21,7
21,9
22,1
22,3
23,7
23,9
24,1
24,4
24,6
24,9
25,1
25,4
26,5
26,7
27,0
27,3
27,6
27,8
28,1
28,4

72,3
74,3
76,5
78,7
80,8
83,0
85,1
87,4
87,1
89,6
92,2
94,8
97,4
100
103
105
96,7
99,4
102
105
108
111
114
117

22,9
23,2
23,4
23,7
23,9
24,1
24,4
24,6
26,1
26,3
26,6
26,9
27,1
27,4
27,7
27,9
29,2
29,4
29,7
30,1
30,4
30,7
31,0
31,3

67,9
69,8
71,8
73,8
75,9
77,9
79,9
82,0
81,8
84,0
86,5
89,0
91,4
93,8
96,2
98,8
90,8
93,3
96,0
98,7
101
104
107
110

25,3
25,5
25,8
26,1
26,3
26,6
26,9
27,1
28,7
29,0
29,3
29,6
29,9
30,2
30,5
30,8
32,2
32,5
32,8
33,2
33,5
33,8
34,2
34,5

63,2
64,9
66,8
68,7
70,6
72,5
74,3
76,3
76,1
78,2
80,5
82,8
85,0
87,3
89,5
92,0
84,4
86,8
89,3
91,8
94,4
96,9
99,4
102

27,9
28,1
28,4
28,8
29,0
29,3
29,6
29,9
31,7
32,0
32,3
32,7
33,0
33,3
33,6
34,0
35,5
35,8
36,2
36,6
36,9
37,3
37,7
38,0

58,5
60,1
61,9
63,6
65,4
67,1
68,8
70,7
70,5
72,4
74,5
76,7
78,8
80,9
82,9
85,2
78,2
80,4
82,7
85,1
87,4
89,7
92,0
94,5

30,4
30,7
31,0
31,3
31,7
32,0
32,3
32,6
34,5
34,9
35,2
35,6
36,0
36,3
36,7
37,0
38,7
39,0
39,4
39,8
40,2
40,6
41,0
41,4

53,7
55,2
56,8
64,7
66,5
68,5
71,8
73,8
76,0
-

32,9
33,2
33,5
37,3
37,7
38,1
41,8
42,2
42,6
-

80

90

100

Tw= Outlet water temperature in C

kWf

= refrigerating power (kW).

kWa = Power input of compressors (kW)

The standard performances refer to a 5C temperature difference between the water entering and leaving the plate-type heat exchanger and to operation of the unit
with all the fans to top speed. A 0.44 x 10-4 m2 K/W fouling factor has also been considered with the unit installed at zero meters above sea level (Pb = 1013mbar).

31

TECHNICAL SPECIFICATIONS AND STANDARD PERFORMANCES - IP HEAT PUMP UNITS

Mod. 115-160
OUTDOOR AIR TEMPERATURE (C D.B.)

MOD.

115

130

145

160

180

200

Tw
5
6
7
8
9
10
11
12
5
6
7
8
9
10
11
12
5
6
7
8
9
10
11
12
5
6
7
8
9
10
11
12
5
6
7
8
9
10
11
12
5
6
7
8
9
10
11
12

20
kWf
122
126
129
133
136
140
144
148
135
138
142
146
151
155
158
163
153
157
162
166
171
175
180
185
170
175
180
185
190
195
200
206
197
203
209
215
221
227
232
239
219
225
232
238
245
251
258
265

25
kWa
26,0
26,2
26,5
26,8
27,0
27,3
27,6
27,8
29,3
29,6
29,9
30,2
30,5
30,8
31,1
31,4
33,6
33,9
34,3
34,6
35,0
35,3
35,7
36,0
37,0
37,4
37,8
38,2
38,6
39,0
39,3
39,7
40,3
40,7
41,1
41,6
42,0
42,4
42,8
43,3
45,8
46,2
46,7
47,2
47,7
48,2
48,7
49,1

Tw= Outlet water temperature in C

kWf
114
117
121
124
127
131
134
138
126
129
133
137
141
144
148
152
143
147
151
155
160
164
168
173
159
163
168
173
177
182
187
192
184
189
195
200
206
211
217
223
205
210
216
222
229
235
241
247

30
kWa
29,9
30,2
30,5
30,8
31,1
31,4
31,7
32,0
33,7
34,1
34,4
34,8
35,1
35,5
35,8
36,2
38,7
39,0
39,4
39,9
40,3
40,7
41,1
41,5
42,6
43,0
43,5
43,9
44,4
44,8
45,3
45,7
46,4
46,9
47,3
47,9
48,3
48,8
49,3
49,8
52,7
53,2
53,8
54,3
54,9
55,4
56,0
56,5

kWf
108
111
114
117
120
124
127
130
119
122
126
129
133
136
140
144
135
139
143
147
151
155
159
163
150
154
159
163
168
172
177
181
174
179
184
190
195
200
205
211
193
199
205
210
216
222
228
234
kWf

35
kWa
32,9
33,2
33,6
33,9
34,3
34,6
34,9
35,3
37,2
37,5
37,9
38,3
38,7
39,1
39,5
39,9
42,6
43,0
43,4
43,9
44,4
44,8
45,2
45,7
47,0
47,4
47,9
48,4
48,9
49,4
49,9
50,4
51,1
51,6
52,2
52,7
53,3
53,8
54,3
54,8
58,1
58,6
59,2
59,9
60,5
61,1
61,7
62,3

kWf
101
104
107
110
113
116
119
122
112
115
118
121
125
128
131
135
127
130
134
138
142
145
149
153
141
145
149
153
157
162
166
170
164
168
173
178
183
188
192
198
182
187
192
197
203
208
214
219

40
kWa
36,3
36,6
37,0
37,4
37,8
38,2
38,5
38,9
41,0
41,4
41,8
42,3
42,7
43,1
43,5
44,0
47,0
47,4
47,9
48,4
48,9
49,4
49,9
50,4
51,8
52,3
52,8
53,4
53,9
54,5
55,0
55,5
56,4
56,9
57,5
58,1
58,7
59,3
59,9
60,5
64,0
64,6
65,3
66,0
66,7
67,3
68,0
68,7

= refrigerating power (kW).

kWf
94,1
96,7
100
102
105
108
111
114
104
107
110
113
116
119
122
125
118
121
125
128
132
135
139
142
131
135
139
143
146
150
154
158
152
156
161
166
170
175
179
184
169
174
179
184
189
194
199
204

45
kWa
40,0
40,4
40,8
41,2
41,6
42,1
42,5
42,9
45,2
45,6
46,1
46,6
47,0
47,5
48,0
48,4
51,8
52,3
52,8
53,4
53,9
54,4
55,0
55,5
57,1
57,6
58,2
58,8
59,4
60,0
60,6
61,2
62,2
62,7
63,4
64,1
64,7
65,4
66,0
66,6
70,6
71,2
72,0
72,8
73,5
74,2
75,0
75,7

kWf
87,2
89,6
92,2
94,8
97,4
100
103
105
96,1
98,8
102
105
107
110
113
116
109
112
115
119
122
125
128
132
121
125
128
132
136
139
143
147
141
145
149
153
158
162
166
170
156
161
165
170
175
179
184
189

50
kWa
43,6
44,0
44,5
45,0
45,4
45,9
46,3
46,8
49,3
49,7
50,2
50,8
51,3
51,8
52,3
52,8
56,4
57,0
57,6
58,2
58,8
59,4
59,9
60,5
62,2
62,8
63,4
64,1
64,8
65,4
66,1
66,7
67,8
68,4
69,1
69,9
70,6
71,3
72,0
72,7
77,0
77,7
78,5
79,3
80,1
80,9
81,7
82,5

kWf
80,1
82,3
84,7
88,3
90,8
93,4
100
103
106
112
115
118
129
133
137
144
148
152
-

kWa
47,1
47,6
48,1
53,3
53,8
54,3
61,0
61,6
62,2
67,3
67,9
68,6
73,3
74,0
74,7
83,2
84,0
84,8
-

kWa = Power input of compressors (kW)

The standard performances refer to a 5C temperature difference between the water entering and leaving the plate-type heat exchanger and to operation of the unit
with all the fans to top speed. A 0.44 x 10-4 m2 K/W fouling factor has also been considered with the unit installed at zero meters above sea level (Pb = 1013mbar).

32

TECHNICAL SPECIFICATIONS AND STANDARD PERFORMANCES - IP HEAT PUMP UNITS


Standard performances in heating mode AB Standard Unit + KS Silencer kit
OUTDOOR AIR TEMPERATURE (C D.B.)

MOD.

50

60

70

80

90

100

115

130

145

160

180

200

Tw
30
35
40
45
50
30
35
40
45
50
30
35
40
45
50
30
35
40
45
50
30
35
40
45
50
30
35
40
45
50
30
35
40
45
50
30
35
40
45
50
30
35
40
45
50
30
35
40
45
50
30
35
40
45
50
30
35
40
45
50

-6

-2

12

15

kWt

kWa

kWt

kWa

kWt

kWa

kWt

kWa

kWt

kWa

kWt

kWa

kWt

kWa

39,4
39,2
39,0
38,7
38,4
42,9
42,7
42,5
42,2
41,9
50,1
49,8
49,6
49,2
48,9
56,4
56,1
55,8
55,4
55,1
67,7
67,3
66,9
66,5
66,0
76,2
75,8
75,4
74,9
74,3
84,0
83,6
83,1
82,5
81,9
92,4
91,9
91,4
90,8
90,1
106
106
105
104
104
115
115
114
113
112
136
135
134
134
133
150
149
148
147
146

12,0
13,3
14,8
16,5
18,3
13,4
14,8
16,5
18,3
20,4
15,1
16,7
18,6
20,7
23,0
17,2
19,0
21,1
23,5
26,1
21,0
23,3
25,9
28,8
32,0
23,4
25,9
28,8
32,0
35,6
25,9
28,7
31,9
35,5
39,5
29,0
32,2
35,8
39,8
44,2
33,5
37,2
41,3
45,9
51,1
37,1
41,1
45,7
50,8
56,5
40,2
44,5
49,5
55,0
61,1
45,4
50,3
56,0
62,2
69,2

45,2
44,9
44,7
44,4
44,1
49,2
48,9
48,7
48,3
48,0
57,4
57,1
56,8
56,4
56,0
64,7
64,3
64,0
63,5
63,1
77,5
77,1
76,7
76,2
75,6
87,3
86,9
86,4
85,8
85,2
96,3
95,8
95,2
94,6
93,9
106
105
105
104
103
122
121
120
119
119
132
131
131
130
129
156
155
154
153
152
172
171
170
169
167

12,1
13,4
14,9
16,6
18,4
13,5
14,9
16,6
18,4
20,5
15,2
16,8
18,7
20,8
23,1
17,3
19,1
21,3
23,6
26,3
21,1
23,4
26,0
28,9
32,2
23,5
26,0
28,9
32,2
35,8
26,1
28,9
32,1
35,7
39,7
29,2
32,4
36,0
40,0
44,5
33,7
37,4
41,6
46,2
51,4
37,3
41,3
46,0
51,1
56,8
40,4
44,8
49,8
55,3
61,5
45,7
50,6
56,3
62,6
69,6

49,4
49,1
48,9
48,5
48,2
53,8
53,5
53,2
52,8
52,5
62,8
62,5
62,1
61,7
61,3
70,7
70,4
70,0
69,5
69,0
84,8
84,4
83,9
83,3
82,7
95,5
95,0
94,5
93,8
93,2
105
105
104
103
103
116
115
115
114
113
133
132
132
131
130
145
144
143
142
141
170
170
169
167
166
188
187
186
184
183

12,3
13,6
15,1
16,8
18,7
13,6
15,1
16,8
18,7
20,8
15,4
17,1
19,0
21,1
23,4
17,5
19,4
21,6
24,0
26,6
21,4
23,7
26,4
29,3
32,6
23,8
26,4
29,3
32,6
36,3
26,4
29,3
32,6
36,2
40,2
29,6
32,8
36,5
40,6
45,1
34,2
37,9
42,1
46,8
52,1
37,8
41,9
46,6
51,8
57,6
40,9
45,4
50,5
56,1
62,3
46,3
51,3
57,1
63,4
70,5

52,5
52,3
52,0
51,6
51,2
57,2
56,9
56,6
56,2
56,2
66,8
66,4
66,1
65,6
65,1
75,2
74,8
74,4
73,9
73,4
90,2
89,7
89,2
88,6
88,0
102
101
100
99,8
99,1
112
111
111
110
109
123
123
122
121
120
141
141
140
139
138
154
153
152
151
150
181
180
179
178
177
200
198
197
196
195

12,3
13,7
15,2
16,9
18,8
13,7
15,2
16,9
18,8
20,9
15,5
17,2
19,1
21,2
23,6
17,6
19,5
21,7
24,1
26,8
21,5
23,9
26,5
29,5
32,8
24,0
26,5
29,5
32,8
36,5
26,6
29,5
32,8
36,4
40,5
29,8
33,0
36,7
40,8
45,4
34,4
38,1
42,4
47,1
52,4
38,0
42,2
46,9
52,1
57,9
41,2
45,6
50,7
56,4
62,7
46,6
51,6
57,4
63,8
70,9

56,3
56,0
55,7
55,3
55,0
61,4
61,0
60,7
60,3
59,9
71,6
71,3
70,8
70,4
69,9
80,7
80,3
79,8
79,3
78,7
96,7
96,2
95,7
95,0
94,4
109
108
108
107
106
120
119
119
118
117
132
131
131
130
129
152
151
150
149
148
165
164
163
162
161
194
193
192
191
190
214
213
212
210
209

12,5
13,8
15,4
17,1
19,0
13,9
15,4
17,1
19,0
21,1
15,7
17,4
19,3
21,4
23,8
17,8
19,7
21,9
24,4
27,1
21,8
24,1
26,9
29,8
33,2
24,2
26,9
29,9
33,2
36,9
26,9
29,8
33,1
36,8
40,9
30,1
33,4
37,1
41,3
45,9
34,8
38,6
42,9
47,6
53,0
38,5
42,6
47,4
52,7
58,6
41,7
46,2
51,3
57,1
63,4
47,1
52,2
58,1
64,5
71,7

60,2
59,9
59,6
59,2
58,8
65,6
65,3
64,9
64,4
64,0
76,6
76,2
75,7
75,2
74,7
86,3
85,8
85,3
84,7
84,1
103
103
102
102
101
116
116
115
114
114
128
128
127
126
125
141
141
140
139
138
162
161
160
159
158
176
175
174
173
172
208
207
206
204
203
229
228
226
225
223

12,6
14,0
15,6
17,3
19,2
14,0
15,6
17,3
19,2
21,4
15,8
17,6
19,5
21,7
24,1
18,0
20,0
22,2
24,7
27,4
22,0
24,4
27,2
30,2
33,6
24,5
27,2
30,2
33,6
37,3
27,2
30,1
33,5
37,2
41,4
30,5
33,8
37,6
41,7
46,4
35,2
39,0
43,4
48,2
53,6
38,9
43,1
48,0
53,3
59,3
42,1
46,7
51,9
57,7
64,2
47,7
52,8
58,7
65,3
72,6

64,4
64,1
63,7
63,3
62,9
70,2
69,8
69,4
68,9
68,5
81,9
81,5
81,0
80,5
79,9
92,3
91,8
91,3
90,7
90,0
111
110
109
109
108
125
124
123
122
122
137
137
136
135
134
151
150
149
148
147
174
173
172
171
169
189
188
187
185
184
222
221
220
218
217
245
243
242
240
239

12,8
14,2
15,7
17,5
19,4
14,2
15,7
17,5
19,5
21,6
16,0
17,8
19,7
21,9
24,4
18,2
20,2
22,4
24,9
27,7
22,3
24,7
27,5
30,5
33,9
24,8
27,5
30,5
33,9
37,7
27,5
30,5
33,9
37,7
41,9
30,8
34,2
38,0
42,2
46,9
35,6
39,4
43,9
48,7
54,2
39,4
43,6
48,5
53,9
59,9
42,6
47,2
52,5
58,4
64,9
48,2
53,4
59,4
66,0
73,4

Tw= Outlet water temperature in C

kWt

= heating output (kW).

kWa = Power input of compressors (kW)

The standard performances refer to a 5C temperature difference between the water entering and leaving the plate-type heat exchanger, outdoor air with 87% relative humidity and to operation of the unit with all the fans to top speed. A 0.44 x 10-4 m2 K/W fouling factor has also
been considered with the unit installed at zero meters above sea level (Pb = 1013mbar).
NOTE
For air temperatures of less than 7C, the heating capacity is declared without considering the effect of the thawing cycles, strictly
correlated with the humidity in the outdoor air.
33

TECHNICAL SPECIFICATIONS AND STANDARD PERFORMANCES - IP HEAT PUMP UNITS


Technical specifications of unit ASS Extra low noise version
Model
Power supply
Type of refrigerant
Circuits
Cooling capacity (1) (E)
Compressors power input
EER
Total power input (1) (E)
Total EER
ESEER (E)
Water flow rate (1)
Water pressure drops (1) (E)
Available static head (1) (MP)
Heating capacity (2) (E)
Compressors power input
COP
Total power input (2) (E)
Total COP
Water flow rate (2)
Water pressure drops (2) (E)
Available static head (2) (MP)

(1)

(2)

50

60

70

80

50,1
17,5
2,87
19,3
2,60
3,59
2,39
37
155
50,5
17,0
2,97
18,8
2,69
2,41
37
152

54,5
19,8
2,75
21,6
2,52
3,47
2,60
44
135
55,1
18,9
2,92
20,7
2,66
2,63
45
131

63,6
22,3
2,85
24,1
2,64
3,64
3,04
41
114
64,3
21,3
3,02
23,1
2,78
3,07
42
111

90
100
115
400V - 3ph+N - 50
R410A
1
84,5 93,8
104
30,2 33,8 38,2
2,80 2,77 2,73
33,8 37,4 41,8
2,50 2,50 2,49
3,45 3,45 3,44
4,04 4,48 4,98
35
34
35
166
151
131
86,8 97,9
107
29,6 33,0 36,5
2,93 2,97 2,94
31,4 36,6 40,1
2,76 2,68 2,67
4,15 4,68 5,13
36
37
36
157
139
124

Compressor
Type
Quantity
Load steps
Oil charge CP1 3,25
Oil charge CP2 3,25
Heat Exchanger
Type
Quantity
Water volume

3,6

3,25
3,25

3,25
3,25

3,6

4,6

3,25
4,7

7,6

130
Hz

145

160

180

200

116
43,1
2,68
46,7
2,47
3,41
5,52
33
109
119
41,0
2,90
44,6
2,67
5,67
35
103

131
49,4
2,65
54,8
2,39
3,29
6,24
33
138
136
47,4
2,87
52,8
2,58
6,49
35
128

169
59,3
2,84
66,5
2,54
3,50
8,05
51
160
175
56,7
3,08
63,9
2,74
8,35
55
149

UM
V-f-Hz
/
n
kW
kW
kW
l/s
kPa
kPa
kW
kW
kW
l/s
kPa
kPa

/
n
%
l
l

/
n
l

Scroll
2
0-50-100
4,7
4,7
4,7
6,8

6,8
6,8

6,8
6,3

Brazed plates
1
8,4
9,7
10,9

12,6

6,3
6,3

11,1

Fan
Type
Quantity
Maximum rotational speed
Total air flow rate
Power input

3
19367 19367 18733
1,8

Axial
2
3
900
27640 27640 31627 31627 41460
3,6
5,4

4
55280
7,2

n
rpm
m3/h
kW

Coil
Type
Quantity
Front area

Aluminum fins and copper tubes


1
4,72
5,90

3,38

/
n
m2

7,41

Water Storage Tank (SAA accessory)


Water volume
Safety valve setting
Surge chamber volume
Surge chamber default pressure
Max. operating pressure

400

200

460

l
kPa
l
kPa
kPa

600
24

12
150

800

1000

Electrical Data
Units without pumping module
Total maximum power input [ FLA ]
Total maximum power input [ FLI ]
Total maximum starting current [ MIC ]

48,2
25,5
146

Units with pumping module MP-AM and MP-PS (1


Total maximum power input [ FLA ]
51,4
Total maximum power input [ FLI ]
27,2
Total maximum starting current [ MIC ]
149

50,9
27,7
147

58,3
31,1
173

or 2 pumps)
54,1 61,5
29,4 32,8
150
176

Units with pumping module MP-AM AP (1 or 2 pumps)


Total maximum power input [ FLA ]
54,4 57,1
Total maximum power input [ FLI ]
29,2 31,4
Total maximum starting current [ MIC ]
152
153

64,6
34,8
179

Data referred to standard operating condition.


(1): water temperature: in 12C - out 7C air temperature: in 35C d.b.
(2): water temperature: in 40C - out 45C air temperature: in 7C d.b. 87% RH
(MP): with standard hydronic kit MP-AM and MP-SS
(SAA): with storage tank
(E): data declared according to LCP EUROVENT certification program

34

76,0
43,6
265

81,5
49,2
270

89,9
53,9
317

98,3
58,6
325

117
69,4
368

150
90,8
470

A
kW
A

80,8
46,5
269

86,3
52,1
275

94,7
56,8
322

103
61,5
330

123
72,7
373

158
95,6
479

A
kW
A

82,2
47,3
271

87,8
53,0
276

98,1
58,7
325

106
63,4
334

125
74,2
376

161
97,3
481

A
kW
A

TECHNICAL SPECIFICATIONS AND STANDARD PERFORMANCES - IP HEAT PUMP UNITS


Standard performances in cooling mode ASS Extra low noise version
Mod. 50-100
OUTDOOR AIR TEMPERATURE (C D.B.)

MOD.

Tw
kWf

kWa

kWf

kWa

kWf

kWa

kWf

kWa

kWf

kWa

kWf

kWa

kWf

kWa

50

5
6
7
8
9
10
11
12

57,2
58,8
60,5
62,2
63,9
65,6
67,3
69,1

12,3
12,4
12,5
12,7
12,8
12,9
13,0
13,2

53,4
54,9
56,5
58,1
59,7
61,2
62,8
64,5

14,1
14,3
14,4
14,6
14,7
14,9
15,0
15,1

50,5
51,9
53,4
54,9
56,4
57,9
59,4
61,0

15,6
15,7
15,9
16,0
16,2
16,4
16,5
16,7

47,4
48,7
50,1
51,5
52,9
54,3
55,7
57,2

17,2
17,3
17,5
17,7
17,9
18,0
18,2
18,4

44,1
45,3
46,6
47,9
49,3
50,6
51,9
53,3

18,9
19,1
19,3
19,5
19,7
19,9
20,1
20,3

40,8
41,9
43,2
44,4
45,6
46,8
48,0
49,3

20,6
20,8
21,0
21,3
21,5
21,7
21,9
22,1

37,5
38,5
39,7
-

22,3
22,5
22,7
-

60

5
6
7
8
9
10
11
12

62,2
63,9
65,8
67,7
69,5
71,4
73,2
75,2

13,9
14,0
14,2
14,3
14,5
14,6
14,8
14,9

58,1
59,7
61,4
63,2
64,9
66,6
68,3
70,2

16,0
16,1
16,3
16,5
16,6
16,8
17,0
17,1

54,9
56,4
58,1
59,7
61,4
63,0
64,6
66,4

17,6
17,8
18,0
18,2
18,3
18,5
18,7
18,9

51,5
53,0
54,5
56,0
57,6
59,1
60,6
62,3

19,4
19,6
19,8
20,0
20,2
20,4
20,6
20,8

47,9
49,3
50,7
52,1
53,6
55,0
56,4
57,9

21,4
21,6
21,8
22,1
22,3
22,5
22,7
22,9

44,4
45,6
47,0
48,3
49,6
50,9
52,2
53,7

23,3
23,6
23,8
24,1
24,3
24,5
24,8
25,0

40,8
41,9
43,1
-

25,2
25,5
25,7
-

70

5
6
7
8
9
10
11
12

72,6
74,6
76,8
79,0
81,1
83,3
85,4
87,7

15,6
15,8
16,0
16,1
16,3
16,5
16,6
16,8

67,8
69,6
71,7
73,7
75,7
77,7
79,7
81,9

18,0
18,2
18,4
18,6
18,7
18,9
19,1
19,3

64,1
65,9
67,8
69,7
71,6
73,5
75,4
77,4

19,8
20,0
20,2
20,4
20,7
20,9
21,1
21,3

60,1
61,8
63,6
65,4
67,2
69,0
70,7
72,7

21,9
22,1
22,3
22,5
22,8
23,0
23,2
23,4

55,9
57,5
59,2
60,8
62,5
64,2
65,8
67,6

24,1
24,3
24,6
24,9
25,1
25,3
25,6
25,8

51,8
53,3
54,8
56,4
57,9
59,4
61,0
62,6

26,3
26,5
26,8
27,1
27,4
27,6
27,9
28,2

47,6
48,9
50,3
-

28,4
28,7
29,0
-

5
6
7
8
9
10
11
12
5
6
7
8
9
10
11
12
5
6
7
8
9
10
11
12

96,5
99,1
102
105
108
111
113
117
107
110
113
116
120
123
126
129

21,2
21,4
21,6
21,8
22,1
22,3
22,5
22,7
23,7
23,9
24,2
24,5
24,7
24,9
25,2
25,4

90,0
92,5
95,2
97,9
101
103
106
109
100
103
106
109
112
115
118
121

24,4
24,6
24,9
25,1
25,4
25,6
25,9
26,1
27,3
27,5
27,8
28,1
28,4
28,7
29,0
29,3

85,1
87,5
90,0
92,6
95,1
97,7
100
103
94,5
97,1
100
103
106
108
111
114

26,9
27,1
27,4
27,7
28,0
28,2
28,5
28,8
30,1
30,3
30,7
31,0
31,3
31,6
31,9
32,2

79,9
82,1
84,5
86,9
89,3
91,7
94,0
96,5
88,7
91,1
93,8
96,5
99,1
102
104
107

29,6
29,9
30,2
30,5
30,8
31,1
31,5
31,8
33,1
33,5
33,8
34,2
34,5
34,9
35,2
35,5

74,3
76,4
78,6
80,8
83,1
85,3
87,5
89,8
82,5
84,8
87,3
89,7
92,2
94,7
97,1
100

32,6
32,9
33,3
33,7
34,0
34,3
34,7
35,0
36,5
36,9
37,3
37,7
38,0
38,4
38,8
39,2

68,8
70,8
72,8
74,9
76,9
79,0
81,0
83,2
76,4
78,5
80,8
83,1
85,4
87,7
89,9
92,4

35,6
35,9
36,3
36,7
37,1
37,4
37,8
38,2
39,8
40,2
40,6
41,1
41,5
41,9
42,3
42,7

63,2
65,0
66,9
70,2
72,1
74,2
-

38,5
38,8
39,2
43,1
43,5
43,9
-

80

90

100

20

25

Tw= Outlet water temperature in C

30

kWf

35

40

= refrigerating power (kW).

45

50

kWa = Power input of compressors (kW)

The standard performances refer to a 5C temperature difference between the water entering and leaving the plate-type heat exchanger and to operation of the unit
with all the fans to top speed. A 0.44 x 10-4 m2 K/W fouling factor has also been considered with the unit installed at zero meters above sea level (Pb = 1013mbar).

35

TECHNICAL SPECIFICATIONS AND STANDARD PERFORMANCES - IP HEAT PUMP UNITS

Mod. 115-160
OUTDOOR AIR TEMPERATURE (C D.B.)

MOD.

115

130

145

160

180

200

Tw
5
6
7
8
9
10
11
12
5
6
7
8
9
10
11
12
5
6
7
8
9
10
11
12
5
6
7
8
9
10
11
12
5
6
7
8
9
10
11
12
5
6
7
8
9
10
11
12

20
kWf
119
122
126
129
133
136
140
143
132
136
140
144
148
152
156
160
150
154
158
163
167
172
176
181
193
198
204
210
216
221
227
233
-

25
kWa
26,8
27,1
27,3
27,6
27,9
28,2
28,5
28,7
30,2
30,5
30,8
31,2
31,5
31,8
32,1
32,4
34,7
35,0
35,3
35,7
36,1
36,5
36,8
37,2
41,6
42,0
42,4
42,9
43,3
43,8
44,2
44,6
-

Tw= Outlet water temperature in C

kWf
111
114
117
121
124
127
130
134
124
127
131
134
138
142
145
149
140
143
148
152
156
160
164
169
180
185
190
196
201
207
212
218
-

30
kWa
30,8
31,1
31,4
31,8
32,1
32,4
32,7
33,1
34,8
35,1
35,5
35,9
36,2
36,6
37,0
37,3
39,9
40,3
40,7
41,1
41,5
41,9
42,4
42,8
47,9
48,3
48,8
49,4
49,8
50,3
50,8
51,3
-

kWf
105
108
111
114
117
120
123
127
117
120
124
127
131
134
138
141
132
136
140
144
148
151
155
159
170
175
180
185
190
195
200
206
kWf

35
kWa
34,0
34,3
34,6
35,0
35,4
35,7
36,1
36,4
38,3
38,7
39,1
39,5
39,9
40,3
40,7
41,1
43,9
44,4
44,8
45,3
45,8
46,2
46,7
47,1
52,7
53,2
53,8
54,4
54,9
55,5
56,0
56,6
-

kWf
98,3
101
104
107
110
113
116
119
110
113
116
119
123
126
129
133
124
127
131
135
138
142
146
150
160
164
169
174
179
183
188
193
-

40
kWa
37,5
37,8
38,2
38,6
39,0
39,4
39,8
40,2
42,3
42,7
43,1
43,6
44,0
44,4
44,9
45,3
48,4
48,9
49,4
49,9
50,4
50,9
51,4
51,9
58,2
58,7
59,3
60,0
60,6
61,2
61,8
62,4
-

= refrigerating power (kW).

kWf
91,5
94,0
96,8
100
102
105
108
111
102
105
108
111
114
117
120
123
115
118
122
125
129
132
136
139
149
153
157
162
166
171
175
180
-

45
kWa
41,3
41,7
42,1
42,6
43,0
43,4
43,8
44,3
46,6
47,0
47,5
48,0
48,5
49,0
49,5
50,0
53,4
53,9
54,4
55,1
55,6
56,2
56,7
57,3
64,1
64,7
65,4
66,1
66,7
67,4
68,1
68,7
-

kWf
84,7
87,1
89,6
92,2
94,7
97,2
100
102
94,5
97,1
100
103
106
108
111
114
107
110
113
116
119
122
126
129
138
142
146
150
154
158
162
166
-

50
kWa
45,0
45,4
45,9
46,4
46,9
47,3
47,8
48,3
50,8
51,3
51,8
52,4
52,9
53,4
53,9
54,5
58,2
58,8
59,4
60,0
60,6
61,2
61,8
62,4
69,9
70,5
71,3
72,0
72,8
73,5
74,2
74,9
-

kWf
77,8
80,0
82,3
86,8
89,2
91,8
98,0
101
104
126
130
134
-

kWa
48,7
49,1
49,6
54,9
55,4
56,0
62,9
63,5
64,2
75,6
76,3
77,0
-

kWa = Power input of compressors (kW)

The standard performances refer to a 5C temperature difference between the water entering and leaving the plate-type heat exchanger and to operation of the unit
with all the fans to top speed. A 0.44 x 10-4 m2 K/W fouling factor has also been considered with the unit installed at zero meters above sea level (Pb = 1013mbar).

36

TECHNICAL SPECIFICATIONS AND STANDARD PERFORMANCES - IP HEAT PUMP UNITS


Standard performances in heating mode ASS Extra low noise version
OUTDOOR AIR TEMPERATURE (C D.B.)

MOD.

50

60

70

80

90

100

115

130

145

160

180

200

Tw
30
35
40
45
50
30
35
40
45
50
30
35
40
45
50
30
35
40
45
50
30
35
40
45
50
30
35
40
45
50
30
35
40
45
50
30
35
40
45
50
30
35
40
45
50
30
35
40
45
50
30
35
40
45
50
30
35
40
45
50

-6

-2

12

15

kWt

kWa

kWt

kWa

kWt

kWa

kWt

kWa

kWt

kWa

kWt

kWa

kWt

kWa

38,6
38,4
38,1
37,9
37,6
42,1
41,9
41,6
41,3
41,0
49,1
48,8
48,6
48,2
47,9
66,3
65,9
65,6
65,1
64,7
74,8
74,4
74,0
73,4
72,9
81,7
81,3
80,8
80,3
79,7
90,9
90,4
89,9
89,3
88,6
104
103
103
102
101
134
133
132
131
130
-

12,1
13,4
14,9
16,6
18,4
13,5
14,9
16,6
18,4
20,5
15,2
16,8
18,7
20,8
23,1
21,1
23,4
26,0
28,9
32,1
23,5
26,0
28,9
32,2
35,8
26,0
28,8
32,0
35,6
39,6
29,2
32,3
36,0
40,0
44,4
33,7
37,4
41,6
46,2
51,4
40,4
44,7
49,7
55,3
61,5
-

44,2
44,0
43,7
43,4
43,1
48,2
48,0
47,7
47,4
47,0
56,3
56,0
55,7
55,3
54,9
76,0
75,6
75,1
74,6
74,1
85,7
85,2
84,8
84,2
83,6
93,6
93,2
92,6
92,0
91,3
104
104
103
102
102
119
118
118
117
116
153
152
151
150
149
-

12,2
13,5
15,0
16,7
18,5
13,5
15,0
16,7
18,5
20,6
15,3
16,9
18,8
20,9
23,2
21,2
23,5
26,1
29,0
32,3
23,6
26,2
29,1
32,4
36,0
26,1
29,0
32,2
35,8
39,8
29,4
32,5
36,2
40,2
44,7
33,9
37,6
41,8
46,5
51,7
40,6
45,0
50,0
55,6
61,8
-

48,3
48,1
47,8
47,5
47,2
52,7
52,5
52,2
51,8
51,4
61,5
61,2
60,9
60,5
60,0
83,1
82,7
82,2
81,6
81,0
93,7
93,2
92,7
92,1
91,4
102
102
101
101
99,9
114
113
113
112
111
130
130
129
128
127
168
167
166
165
163
-

12,3
13,7
15,2
16,9
18,8
13,7
15,2
16,9
18,8
20,9
15,5
17,1
19,1
21,2
23,5
21,5
23,8
26,5
29,4
32,7
24,0
26,6
29,5
32,8
36,5
26,5
29,4
32,7
36,3
40,3
29,8
33,0
36,7
40,8
45,3
34,4
38,1
42,4
47,1
52,4
41,2
45,6
50,7
56,4
62,7
-

51,4
51,1
50,9
50,5
50,1
56,1
55,8
55,5
55,1
55,1
65,5
65,1
64,7
64,3
63,9
88,4
87,9
87,4
86,8
86,2
99,7
99,1
98,6
97,9
97,2
109
108
108
107
106
121
121
120
119
118
138
138
137
136
135
178
177
176
175
174
-

12,4
13,8
15,3
17,0
18,9
13,8
15,3
17,0
18,9
21,0
15,6
17,2
19,2
21,3
23,7
21,6
24,0
26,6
29,6
32,9
24,1
26,7
29,7
33,0
36,7
26,7
29,5
32,8
36,5
40,6
29,9
33,2
36,9
41,0
45,6
34,6
38,4
42,7
47,4
52,7
41,4
45,9
51,0
56,7
63,0
-

55,1
54,9
54,5
54,2
53,8
60,2
59,8
59,5
59,1
58,7
70,2
69,8
69,4
69,0
68,5
94,8
94,3
93,7
93,1
92,4
107
106
106
105
104
117
116
116
115
114
130
129
129
128
127
148
148
147
146
145
191
190
189
188
186
-

12,6
13,9
15,5
17,2
19,1
14,0
15,5
17,2
19,1
21,3
15,7
17,4
19,4
21,5
24,0
21,9
24,2
26,9
29,9
33,3
24,4
27,0
30,0
33,4
37,1
27,0
29,9
33,2
36,9
41,0
30,3
33,6
37,3
41,5
46,1
35,0
38,8
43,1
47,9
53,3
41,9
46,4
51,6
57,4
63,8
-

58,9
58,6
58,3
57,9
57,5
64,3
64,0
63,6
63,2
62,7
75,1
74,7
74,2
73,7
73,2
101
101
100
99,5
98,8
114
114
113
112
111
125
124
124
123
122
139
138
137
136
136
159
158
157
156
155
204
203
202
201
199
-

12,7
14,1
15,7
17,4
19,3
14,1
15,6
17,4
19,3
21,5
15,9
17,6
19,6
21,8
24,2
22,1
24,5
27,3
30,3
33,7
24,7
27,3
30,4
33,8
37,5
27,3
30,2
33,6
37,3
41,5
30,6
33,9
37,7
41,9
46,6
35,4
39,2
43,6
48,5
53,9
42,4
46,9
52,2
58,0
64,5
-

63,1
62,7
62,4
61,9
61,5
68,8
68,5
68,1
67,6
67,1
80,3
79,9
79,4
78,9
78,3
108
108
107
106
106
122
122
121
120
119
134
133
132
131
130
149
148
147
146
145
170
169
168
167
166
219
217
216
215
213
-

12,8
14,2
15,8
17,6
19,6
14,3
15,8
17,6
19,6
21,7
16,1
17,8
19,8
22,0
24,5
22,4
24,8
27,6
30,6
34,0
24,9
27,6
30,7
34,1
38,0
27,6
30,6
34,0
37,8
42,0
31,0
34,3
38,2
42,4
47,2
35,8
39,7
44,1
49,0
54,5
42,8
47,5
52,8
58,7
65,2
-

Tw= Outlet water temperature in C

kWt

= heating output (kW).

kWa = Power input of compressors (kW)

The standard performances refer to a 5C temperature difference between the water entering and leaving the plate-type heat exchanger, outdoor air with 87% relative humidity and to operation of the unit with all the fans to top speed. A 0.44 x 10-4 m2 K/W fouling factor has also
been considered with the unit installed at zero meters above sea level (Pb = 1013mbar).
NOTE
For air temperatures of less than 7C, the heating capacity is declared without considering the effect of the thawing cycles, strictly
correlated with the humidity in the outdoor air.
37

TECHNICAL SPECIFICATIONS AND STANDARD PERFORMANCES - IP HEAT PUMP UNITS


Version with Desuperheater (VD)
Recovery heat exchanger specifications
Model
Type of recovery exchanger
Quantity
Max. operating pressure on wet side
Total water content of recovery exchangers
Unit specification
Recovered heating capacity (1)
Recovered water flow rate (1)
Recovered water pressure drop (1)
(1):

50

60

70

0,6

80
90
100 115 130 145 160
STAINLESS STEEL BRAZE PLATES
1
600
0,8
1,3

180

200

1,8

15,2 17,0 19,4 22,9 26,2 29,2 33,2 37,1 42,4 47,5 52,4 58,1
0,73 0,81 0,93 1,10 1,25 1,39 1,58 1,77 2,03 2,27 2,50 2,78
8
10
13
18
14
17
10
13
17
20
16
19

UM
N
kPa
l
kW
l/s
kPa

The data refer to: Water temperature: evaporator inlet :12C - evaporator outlet: 7C, Outdoor air temperature 35C.
The data refer to: Water temperature: recovery inlet :40C - recovery outlet: 45C.

NOTE : THE HEATING CAPACITY RECOVERED BY THE DESUPERHEATER EXCLUSIVELY REFERS TO UNITS
OPERATING IN THE COOLING MODE.

Recovered heating capacity in Version with Desuperheater (VD)

MOD. TWR

50

55

60

70

90

100

30
35
40
45
50
55
60
65
70
30
35
40
45
50
55
60
65
70
30
35
40
45
50
55
60
65
70
30
35
40
45
50
55
60
65
70
30
35
40
45
50
55
60
65
70
30
35
40
45
50
55
60
65
70

OUTDOOR AIR TEMPERATURE (C D.B.)


40
25
30
35
45
kWtr= RECOVERED HEATING CAPACITY [KW]
12,4
12,4
12,2
11,5
10,6
9,3
7,6
5,7
3,3
13,9
14,0
13,7
13,0
11,9
10,4
8,6
6,4
3,8
15,9
15,9
15,6
14,8
13,6
11,9
9,8
7,3
4,3
18,7
18,8
18,3
17,4
15,9
13,9
11,4
8,4
4,9
21,7
21,8
21,2
20,1
18,4
16,1
13,2
9,8
5,7
24,4
24,5
23,9
22,6
20,7
18,1
14,8
10,8
6,2

14,2
14,2
13,9
13,2
12,1
10,6
8,8
6,5
3,8
15,9
16,0
15,7
14,9
13,7
12,0
9,9
7,3
4,3
18,2
18,3
17,9
17,0
15,6
13,7
11,3
8,3
4,9
21,5
21,6
21,1
20,0
18,3
16,0
13,2
9,7
5,7
24,8
24,9
24,3
23,0
21,1
18,5
15,2
11,2
6,5
27,8
27,9
27,2
25,7
23,5
20,6
16,8
12,3
7,0

16,3
16,4
16,0
15,2
13,9
12,2
10,1
7,5
4,4
18,2
18,3
17,9
17,0
16,4
14,4
11,9
8,8
5,2
20,8
20,9
20,4
19,4
17,8
15,6
12,9
9,5
5,6
24,6
24,7
24,2
22,9
21,0
18,4
15,1
11,1
6,5
28,2
28,3
27,6
26,2
24,0
21,0
17,2
12,7
7,4
31,5
31,6
30,8
29,2
26,7
23,3
19,1
14,0
8,0

18,6
18,7
18,3
17,4
15,9
14,0
11,5
8,5
5,0
20,8
20,9
20,4
19,4
17,8
15,6
12,9
9,5
5,6
23,7
23,9
23,3
22,2
20,3
17,8
14,7
10,9
6,4
28,2
28,3
27,6
26,2
24,0
21,0
17,2
12,7
7,4
32,3
32,4
31,6
30,0
27,4
24,0
19,7
14,5
8,5
35,8
35,9
35,0
33,2
30,3
26,5
21,7
15,9
9,1

21,2
21,3
20,8
19,8
18,1
15,9
13,1
9,7
5,7
23,6
23,8
23,2
22,1
20,2
17,7
14,6
10,8
6,4
27,0
27,1
26,5
25,2
23,1
20,3
16,7
12,4
7,3
32,0
32,2
31,4
29,8
27,3
23,9
19,6
14,5
8,4
36,7
36,8
36,0
34,1
31,2
27,3
22,4
16,5
9,6
40,5
40,6
39,6
37,5
34,3
30,0
24,5
18,0
10,3

kWtr = RECOVERED HEATING CAPACITY [KW]


Twr = Desuperheater outlet water temperature, tin-out= 5C

38

MOD. TWR

115

130

145

160

180

200

30
35
40
45
50
55
60
65
70
30
35
40
45
50
55
60
65
70
30
35
40
45
50
55
60
65
70
30
35
40
45
50
55
60
65
70
30
35
40
45
50
55
60
65
70
30
35
40
45
50
55
60
65
70

OUTDOOR AIR TEMPERATURE (C D.B.)


40
25
30
35
45
kWtr= RECOVERED HEATING CAPACITY [KW]
27,8
27,8
27,1
25,7
23,7
20,9
17,5
13,4
8,6
31,2
31,2
30,4
28,9
26,5
23,4
19,5
14,8
9,4
35,7
35,7
34,7
33,0
30,3
26,9
22,5
17,4
11,3
39,8
39,9
39,0
36,9
33,8
29,5
24,2
17,7
10,1
43,9
44,1
43,0
40,7
37,3
32,6
26,6
19,5
11,2
48,7
48,8
47,7
45,2
41,3
36,1
29,5
21,6
12,4

31,6
31,6
30,8
29,3
26,9
23,8
19,9
15,2
9,8
35,3
35,3
34,5
32,7
30,0
26,5
22,1
16,8
10,6
40,6
40,5
39,5
37,4
34,5
30,5
25,6
19,7
12,9
45,2
45,3
44,3
41,9
38,3
33,5
27,4
20,1
11,5
49,8
50,0
48,8
46,3
42,3
37,0
30,3
22,2
12,7
55,3
55,5
54,1
51,3
46,9
41,0
33,5
24,6
14,1

35,9
35,9
35,0
33,2
30,5
27,0
22,6
17,3
11,1
40,1
40,1
39,1
37,1
34,1
30,1
25,1
19,1
12,0
46,0
45,9
44,7
42,4
39,0
34,6
29,0
22,3
14,6
51,2
51,4
50,1
47,5
43,4
38,0
31,1
22,8
13,0
56,5
56,7
55,3
52,4
47,9
41,9
34,3
25,1
14,4
62,6
62,8
61,3
58,1
53,1
46,4
38,0
27,8
15,9

40,6
40,6
39,6
37,6
34,6
30,6
25,6
19,6
12,6
45,4
45,4
44,3
42,0
38,6
34,1
28,4
21,6
13,6
52,1
52,0
50,6
48,1
44,2
39,2
32,9
25,3
16,5
58,0
58,2
56,8
53,8
49,2
43,0
35,2
25,8
14,8
64,0
64,2
62,7
59,4
54,3
47,5
38,8
28,5
16,3
70,9
71,2
69,5
65,8
60,2
52,6
43,1
31,5
18,1

45,8
45,8
44,7
42,5
39,1
34,5
28,9
22,1
14,2
51,4
51,4
50,1
47,5
43,7
38,5
32,1
24,4
15,4
58,8
58,7
57,2
54,3
49,9
44,2
37,1
28,6
18,7
65,5
65,7
64,2
60,8
55,6
48,6
39,7
29,1
16,7
72,2
72,5
70,8
67,0
61,3
53,6
43,8
32,1
18,4
80,1
80,4
78,5
74,3
68,0
59,4
48,6
35,6
20,4

NOISE LEVELS
The noise levels refer to units operating in the nominal conditions (water temperature: inlet: 12C - outlet: 7C, Outdoor air temperature 35C), due to a change of external air temperature noise levels may change to ensure proper functioning of the unit
within operating range.
The acoustic pressure levels are measured 1/ 5 / 10 meters away from the outer surface of the unit operating in the free field
and resting on a reflecting surface (directional factor of 2).
SWL = Sound power levels, with reference to 2x10-12 W.
The Total sound power level in dB(A) measured in compliance with ISO 9614 standards, is certified according to the
Eurovent certification program.
Eurovent certification (E) exclusively refers to the Total Sound Power in db(A), which is therefore the only binding acoustic
specification (the values of the Octave bands in the table are indicative).
SPL = Sound pressure levels, with reference to 2x10-5 Pa.
The sound pressure levels are values calculated by applying the ISO-3744 relation (Eurovent 8/1) and refer to a distance of
1 meter away from the external surface of units operating in the open field with directivity factor 2 and the units operating in
nominal conditions in the cooling mode.
AB Standard version
Mod.
50
60
70
80
90
100
115
130
145
160
180
200

63
94,2
94,2
94,2
94,2
92,4
92,4
92,4
92,4
96,1
96,1
96,4
96,4

125
91,9
91,9
91,9
91,9
90,1
90,1
90,1
90,1
92,2
92,2
94,1
94,1

SWL (dB) (E)


Octave bands (Hz)
250
500
1000 2000 4000
89,4
85,3
81,0
74,6
67,0
89,4
85,3
81,0
74,6
67,0
89,4
85,3
81,0
74,6
67,0
89,4
85,3
81,0
74,6
67,0
88,6
86,0
83,2
77,8
71,2
88,6
86,0
83,2
77,8
71,2
88,6
86,0
83,2
77,8
71,2
88,6
86,0
83,2
77,8
71,2
91,3
89,2
86,1
81,0
74,4
91,3
89,2
86,1
81,0
74,4
92,6
90,0
87,2
81,8
75,2
92,6
90,0
87,2
81,8
75,2

8000
58,6
58,6
58,6
58,6
62,8
62,8
62,8
62,8
66,9
66,9
66,8
66,8

dB
97
97
97
97
96
96
96
96
99
99
100
100

Total
dB(A)
87
87
87
87
88
88
88
88
91
91
92
92

dB
94
94
94
94
95
95
95
95
96
96
99
99

Total
dB(A)
84
84
84
84
85
85
85
85
88
88
89
89

dB
91
91
91
92
92
92
92
95
96
-

Total
dB(A)
81
81
81
82
82
82
82
85
86
-

SPL (dBA)
1m
69
69
69
69
70
70
70
70
72
72
73
73

5m
60
60
60
60
61
61
61
61
64
64
65
65

10m
55
55
55
55
56
56
56
56
59
59
60
60

AB Standard version + Low noise Kit KS


Mod.
50
60
70
80
90
100
115
130
145
160
180
200

63
91,2
91,2
91,2
91,2
92,2
92,2
92,2
92,2
92,4
92,4
95,4
95,4

125
88,9
88,9
88,9
88,9
89,9
89,9
89,9
89,9
90,1
90,1
93,0
93,0

SWL (dB) (E)


Octave bands (Hz)
250
500
1000 2000 4000
86,4
82,3
78,0
71,6
64,0
86,4
82,3
78,0
71,6
64,0
86,4
82,3
78,0
71,6
64,0
86,4
82,3
78,0
71,6
64,0
87,4
83,3
79,0
72,6
65,0
87,4
83,3
79,0
72,6
65,0
87,4
83,3
79,0
72,6
65,0
87,4
83,3
79,0
72,6
65,0
88,6
86,0
83,2
77,8
71,2
88,6
86,0
83,2
77,8
71,2
90,8
86,3
83,4
79,8
71,3
90,8
86,3
83,4
79,8
71,3

8000
55,6
55,6
55,6
55,6
56,6
56,6
56,6
56,6
62,8
62,8
62,0
62,0

SPL (dBA)
1m
66
66
66
66
67
67
67
67
69
69
70
70

5m
57
57
57
57
58
58
58
58
61
61
62
62

10m
52
52
52
52
53
53
53
53
56
56
57
57

AB Standard version + Low noise Kit KS


Mod.
50
60
70
80
90
100
115
130
145
160
180
200

63
84,4
84,4
84,4
85,4
85,4
85,4
85,4
92,2
92,4
-

125
87,3
87,3
87,3
88,3
88,3
88,3
88,3
89,9
90,0
-

SWL (dB) (E)


Octave bands (Hz)
250
500
1000 2000 4000
83,6
78,8
75,3
68,8
60,2
83,6
78,8
75,3
68,8
60,2
83,6
78,8
75,3
68,8
60,2
84,6
79,8
76,3
69,8
61,2
84,6
79,8
76,3
69,8
61,2
84,6
79,8
76,3
69,8
61,2
84,6
79,8
76,3
69,8
61,2
87,4
83,3
79,0
72,6
65,0
87,8
83,3
80,4
76,8
68,3
-

8000
51,3
51,3
51,3
52,3
52,3
52,3
52,3
56,6
59,0
-

SPL (dBA)
1m
63
63
63
64
64
64
64
66
67
-

5m
54
54
54
55
55
55
55
58
59
-

10m
49
49
49
50
50
50
50
53
54
39

OPERATING RANGE
Operating range
The graphs below give the operating ranges within which correct operation of the units is guaranteed.
The use of the units in conditions differing from those indicated will void the warranty with which the product is supplied.
In the following table, there are the thermal water head limit values of the unit.
Thermal Water Head

Limit value

Minimum

Maximum

Note: Make sure the water flow is within the minimum and maximum pressure drop as reported "water pressure
drop plate heat exchanger ".
COOLING MODE

[C]

OUTLET WATER
TEMPERATURE

T Acqua= 5C

20

OUTDOOR AIR
TEMPERATURE

-10

15

35

40

50

[C B.S.]

In these applications, its advisable to use brine.


HEATING MODE

OUTLET WATER
TEMPERATURE

[C]
53

45

OUTDOOR AIR
TEMPERATURE

30

-7

30

[C B.S.]

COOLING MODE BRINE VERSION (VI)

[C]

OUTLET WATER
TEMPERATURE

-5

OUTDOOR AIR
TEMPERATURE

-8

-10

35

43 46

[C B.S.]

Use water glicol as specified in the paragraph Specification data for Brine Version (VI).

40

WATER PRESSURE DROP PLATE HEAT EXCHANGER


The graph below illustrates the water pressure drop values in kPa depending on the flow rate in liters/second. The operating
range is delimited by the minimum and maximum values given in the next table.

150

8 10

11

140
130
120
110

Water pressure drop (kPa)

100
90
80
70
60
50
40
30
20
10
0,50

2,50

4,50

6,50

8,50

10,50

12,50

14,50

16,50

Water flow rate (l/s)


Operation limit

50

Unit Size
Graph reference

60
1

1,2

70

80

90 100 115 130 145 160 180 200


4

10

UM

11

1,5 1,9 2,2 2,4 2,7 3,1 3,5 3,8 3,6 4,0

l\s

NOTES
Q=Water flow
rate

Lower limit value


p
Q

10

4,8

5,8 7,3 8,5 9,3 10,4 11,9 13,4 14,9 13,8 15,5

kPa

p=Water pressure drop

l\s

Upper limit value


p
Max. operating pressure on
wet side

150

kPa

600

kPa

41

WATER PRESSURE DROP OF THE DESUPERHEATER

The graph below illustrates the water pressure drop values in kPa depending on the flow rate in liters/second, for the Special
Versions with Desuperheater (VD) in both the units that operate in the Cooling mode only (IR) and in Heat Pump units (IP).
The operating range is delimited by the minimum and maximum values given in the next table.

150

140
130
120

Water pressure drop (kPa)

110
100
90
80
70
60
50
40
30
20
10
0,00

1,00

2,00

3,00

4,00

5,00

6,00

7,00

8,00

Water flow rate (l/s)


Limits to operation

50

Unit Size
Graph reference
Q

60

70

80

90 100 115 130 145 160 180 200

0,8

1,0

1,5

1,9

UM

l\s

NOTES
Q=Water flow
rate

Lower limit value


p
Q

10
3,0

3,9

kPa

5,7

7,4

l\s

Upper limit value


p

42

150

kPa

p=Water pressure drop

WORKING HEAD OF THE PUMPING MODULE MP-AM AND MP-SS

The following graph gives the head values (kPa) depending on the water flow rate (liters/second). The operating range is delimited by the minimum and maximum values given in the next table.
Working head is the one on the wet module outlet minus all the load losses of the unit.

400

350

Working head (kPa)

300

250

200

10
150

11

8
9

100

5
2

50

6
7

3
0
1,00

2,00

3,00

4,00

5,00

6,00

7,00

8,00

9,00

10,00

11,00

Water flow rate (l/s)

Operation limit

50

Unit Size

60
1

Graph reference
Lower limit value

70

80

90

100

115

130

145

160

180

200

10

11

UM

NOTES
Q=Water
flow rate

1,25

1,50 1,88 2,19 2,41 2,68 3,06 3,47 3,85 3,57 4,00

l\s

4,00

4,36 4,61 6,71 7,00 7,29 7,48 9,32 9,58 11,00 11,40

l\s

Q
Upper limit value
Max. operating pressure on wet side

600

kPa

43

HIGH WORKING HEAD OF THE PUMPING MODULE MP-AM AP AND MP-SS AP

The following graph gives the head values (kPa) depending on the water flow rate (liters/second). The operating range is delimited by the minimum and maximum values given in the next table.
Working head is the one on the wet module outlet minus all the load losses of the unit.

500
450
400

Working Head (kPa)


(
)

350
300

250

7
200
150

100

10

11

50

3
0
1,00

2,00

3,00

4,00

5,00

6,00

7,00

8,00

9,00

10,00

11,00

12,00

Water flow rate (l/s)

Operation limit

50

Unit Size

60
1

Graph reference
Lower limit value

70

80

90

100

115

130

145

160

180

200

10

11

UM

NOTES
Q=Water
flow rate

1,25

1,50 1,88 2,19 2,41 2,68 3,06 3,47 3,85 3,57 4,00

l\s

4,82

5,31 5,65 7,67 7,96 9,29 9,65 11,03 11,32 11,85 12,21

l\s

Q
Upper limit value
Max. operating pressure on wet side

44

600

kPa

MAXIMUM VOLUME OF WATER


Maximum volume of water in the system with wet module
Before filling the water system, it is advisable to consider the type of installation in question, i.e. check the difference in level between the wet module and user. The following table gives the maximum water content of the water supply system in liters, depending on the capacity of the standard surge chamber supplied and the pressure at which it should be charged. The surge chamber setting must be regulated to suit the maximum positive difference in level of the user.
Maximum setting value 600 kPa.
With a positive H of more than 12.25 meters, calculate the surge chambers service charge value in kPa using the formula below:

Surge chamber service charge= [H/10.2+0.3]x100 = [kPa]


NOTE: In case A, make sure that the users lowest point is able to withstand the global pressure.

Tab.1
Model

50-60-70-80

Surge chamber volume (liters)

12

90-100-110-115-130-145-160-180-200
24

Thermal expansion of water (10-40C)

0.0074

Thermal expansion of water (10-60C)

0.0167

Case A

Case B

Maximum total volume of water supply system (liters)

Surge chamber
pressure (kPa)

IR

IP

IR

IP

H <0

150 (standard)

1043

461

2085

921

0 < H < 12.25

150 (standard)

1043

461

2085

921

15

177

980

435

1960

870

20

226

866

384

1732

768

25

275

753

334

1505

667

30

324

640

283

1279

566

H (meters)

NOTE: If the unit operates with brine, calculate the real volume of the system by taking into account the corrective factors for the
volume of the system given in the table below.
Corrective factors per total maximum volume of the system with brine
% of brine

0%

10%

20%

30%

40%

Cooling Mode

1.000

0.738

0.693

0.652

0.615

Heating Mode

1.000

0.855

0.811

0.769

0.731

U
U= User

CASE B

CASE A

45

DIMENSIONAL DATA

176

Overall dimensions
Mod. 50-60-70-80

954

2501

25

10

708
445
435
335

234
169
70

11

897*

25

947

13

12

1754

1930

631
587

120
110

1730
1783

256

1849*
2480

375

Mod. 90-100
1104

3343

234
169

70

12

13

11

842
510
500
370

1793

25

1047*

25

1097

10

862
826
476

120
130
1185*

2341
2366
1298*

363

3322

Mod. 115-130-145-160
3343

1104

2193

12

10

842
510
500
370

234
169

25

11

70

13

1047*

25

1097

862
826
476

120

2341

130

2366

1185*

1298*

363

3322

Mod. 180-200

1104

4097

2193

1
11

6
234
169
70

25

10

842
532
518
388

1047*
1097

25

1735
852
502

120

2222

130

3094
1550 *

1661*
4076

46

363

DIMENSIONAL DATA
Description of the components
1 - Access panel to electric panels power section
2 - Access panel to compressor compartment
3 - Vibration damper fixing holes (4 pcs)
4 - Coil protection grilles (accessory)
5 - 65 mm lifting holes
6 - 22 mm input hole for accessory cables
7- 60 mm hole for electric power supply input
8 - Access panel to pump compartment
9 - Water inlet for MP-AM and MP-SS
10 - Water inlet for KT and MP-PS
11 - Water outlet
12 - Water inlet for Desuperheater (only VD
version)
13 - Water outlet for Desuperheater (only VD
version)
*: Center distance of vibration damper holes
Note (1): Basic pipe kit do not allow external connections.

Rif.
50
60
70
80
90
100
115
130
145
160
180
200

KT

KT

KT

BASIC

COMPLETE

WATER
STORAGE
TANK

MP-AM MP-AM
AP

MP-SS

MP-SS
AP

MP-PS

VD

IN OUT IN OUT IN OUT IN OUT IN OUT IN OUT IN OUT IN OUT IN OUT


(1) 10 11 10 11
9
11
9
11
9
11
9
11 10 11 12 13

(1)

2"M

1 1/2"

2 1/2"M

2"

1
2"
1/2"

2"

2
1/2"

2"

2"

2 1/2"

2 1/2"

2"

1
1
2"
1/2"
1/2"

2
2
2"
2"
1/2"
1/2"

2"

1 1/4"

2 1/2"

1 1/4"

1000
E

Minimum space required for operation

1000

To correctly install the unit, comply with the measurements for the free
area that must be left around the machine, as shown in the figure.
This will ensure good air circulation, allow the unit to operate correctly and
facilitate future maintenance work.
The distances must be doubled if the unit is to be installed in a pit.

1000

NOTE. Allow for an uncluttered area of not less than 2.5 meters
above the unit.

Modello
E [mm]

50-80

90-100

115-200
2000

1600

Weight during operation and transport


To correctly install the unit, comply with the measurements for the free area that must be left around the machine, as shown in
the drawing.
IR VERSION
VB AB / VB AB + KS
Mod.
Trasport [kg]
Operation [kg]

50
591
595

60
592
595

70
630
635

80
656
661

90
893
900

100
973
981

115
1083
1093

130
1110
1121

145
1163
1177

160
1211
1225

180
1356
1367

200
1400
1413

VB AB / VB AB + KS with Water storage tank (SA) and Hydronic Kit with 2 Pumps (MP)
Trasport [kg]
Operation [kg]

770
998

771
999

810
1038

835
1064

1127
1527

1207
1608

1329
1733

1355
1761

1408
1818

1457
1866

1675
2176

1719
2222

50
614
617

60
614
618

70
646
651

80
-

90
913
921

100
993
1002

115
1112
1121

130
1138
1149

145
1191
1206

160
-

180
1389
1400

200
-

VB ASS
Mod.
Trasport [kg]
Operation [kg]

VB ASS + KS with Water storage tank (SA) and Hydronic Kit with 2 Pumps (MP)
Trasport [kg]
Operation [kg]

793
1021

794
1021

825
1054

1147
1548

1227
1628

1357
1762

1384
1790

1437
1846

1708
2209

50
623
627

60
624
627

70
663
668

80
688
693

90
932
939

100
1012
1020

115
1126
1136

130
1153
1164

145
1210
1222

160
1260
1275

180
1407
1418

200
1451
1464

IP VERSION
VB AB / VB AB + KS
Mod.
Trasport [kg]
Operation [kg]

VB AB / VB AB + KS with Water storage tank (SA) and Hydronic Kit with 2 Pumps (MP)
Trasport [kg]
Operation [kg]

802
1030

803
1031

843
1071

867
1096

1165
1566

1245
1647

1372
1777

1399
1805

1456
1863

1506
1915

1726
2226

1770
2272

50
646
649

60
646
650

70
679
684

80
-

90
952
960

100
1032
1040

115
1155
1165

130
1182
1193

145
1238
1251

160
-

180
1440
1451

200
-

1484
1892

1759
2259

VB ASS
Mod.
Trasport [kg]
Operation [kg]

VB ASS + KS with Water storage tank (SA) and Hydronic Kit with 2 Pumps (MP)
Trasport [kg]
Operation [kg]

825
1053

826
1053

858
1087

1186
1587

1266
1667

1401
1805

The manufacturer declines all responsibility for any inaccuracies in this manual due to printing or typing errors.
The reserves the right to modify the products contents in this catalogue without previous notice.

1427
1833

47

Cod. 3QE24621