You are on page 1of 5

Samson

Common comments for all control valves (PCV/TCV/FCV):

Air failure action to be mention clearly in each technical offer sheet


DP shut off to be mention clearly in each technical offer sheet
MOC of each valve must be same as mention in data sheet.
All control valves opening at normal condition must be in range of 50-60%

PCV
SR
NO
1.
2.
3.
4.
5.
6.
7.
8.
9.

11-PCV-01
11-PCV-02
12-PCV-01
12-PCV-02
14-PCV-02
14-PCV-03
14-PCV-04
31-PCV-01
31-PCV-02

10

33-PCV-02

Tag No

Comment
All wetted part MOC should be SS-304L
All wetted part MOC should be SS-304L
Valve tag No from 33-PCV-02 to be revised as 14-PCV-03
All wetted part MOC should be SS-304L
All wetted part MOC should be SS-304L
All wetted part MOC should be SS-304L
Please consider Air fail to open

TCV
Sizing of control valve for steam (in series 13 & 32) minimum pressure to be
consider as 10.0 kg/cm2g
SR
NO
1.
2.
3.
4.
5.
6.
7.
8.
9.
10
11.
12.
13.
14.
15.

Tag No
13-TCV-01
13-TCV-02
13-TCV-03
13-TCV-04
13-TCV-05
21-TCV-01
32-TCV-01
32-TCV-02
32-TCV-03
32-TCV-04
32-TCV-05
51-TCV-01
61-TCV-01
61-TCV-02
61-TCV-03

Comment
-

16.
17.

61-TCV-04
92-TCV-01

FCV
SR
NO
1.
2.
3.
4.
5.

11-FCV-01
11-FCV-02
51-FCV-01
51-FCV-02
61-FCV-01

6.

71-FCV-01

7.

71-FCV-02

Tag No

Comment
Please consider Line size 1.5 in. SCH STD
Please Consider flow (min/nor/max) as 200/2500/3500
kg/hr.
Please Consider all wetted part MOC as SS-304L
Consider Minimum Temperature as 40OC

FISHER: PCV
SR
NO
1.
2.
3.
4.
5.
6.
7.
8.
9.

11-PCV-01
11-PCV-02
12-PCV-01
12-PCV-02
14-PCV-02
14-PCV-03
14-PCV-04
31-PCV-01
31-PCV-02

10

33-PCV-02

Tag No

Comment
All wetted part MOC should be SS-304L
All wetted part MOC should be SS-304L
All wetted part MOC should be SS-304L
All wetted part MOC should be SS-304L
All wetted part MOC should be SS-304L
Please consider Air fail to open

FCV
SR
NO
1.
2.
3.
4.
5.

11-FCV-01
11-FCV-02
51-FCV-01
51-FCV-02
61-FCV-01

6.

71-FCV-01

7.

71-FCV-02

Tag No

Comment
Please consider Line size 1.5 in. SCH STD
Please Consider flow (min/nor/max) as 1500/2500/3500
kg/hr
Please Consider all wetted part MOC as SS-304L

TCV
SR
NO
1.

13-TCV-01

2.

13-TCV-02

3.

13-TCV-03

4.

13-TCV-04

5.
6.
7.

13-TCV-05
21-TCV-01
32-TCV-01

8.

32-TCV-02

Tag No

Comment
Valve
60%
Valve
60%
Valve
60%
Valve
60%

opening at normal condition must be in range of 50opening at normal condition must be in range of 50opening at normal condition must be in range of 50-

opening at normal condition must be in range of 50-

9.

32-TCV-03

10

32-TCV-04

11.

32-TCV-05

12.

51-TCV-01

13.

61-TCV-01

14.

61-TCV-02

15.

61-TCV-03

16.

61-TCV-04

17.

92-TCV-01

Valve
60%
Valve
60%
Valve
60%
Valve
60%
Valve
60%
Valve
60%
Valve
60%
Valve
60%

opening at normal condition must be in range of 50-

opening at normal condition must be in range of 50opening at normal condition must be in range of 50opening at normal condition must be in range of 50opening at normal condition must be in range of 50opening at normal condition must be in range of 50opening at normal condition must be in range of 50opening at normal condition must be in range of 50-

MIL: PCV
Common comments for all control valves (PCV/TCV/FCV):

MOC of each valve must be same as mention in data sheet.


All control valves opening at normal condition must be in range of 50-60%

SR
NO
1.
2.
3.
4.
5.
6.
7.
8.
9.

11-PCV-01
11-PCV-02
12-PCV-01
12-PCV-02
14-PCV-02
14-PCV-03
14-PCV-04
31-PCV-01
31-PCV-02

10

33-PCV-02

Tag No

Comment
All wetted part MOC should be SS-304L
All wetted part MOC should be SS-304L
All wetted part MOC should be SS-304L
All wetted part MOC should be SS-304L
All wetted part MOC should be SS-304L
Please consider Air fail to open

FCV
SR
NO
1.
2.
3.
4.
5.

Tag No
11-FCV-01
11-FCV-02
51-FCV-01
51-FCV-02
61-FCV-01

Comment
Please consider Line size 1.5 in. SCH STD

6.

71-FCV-01

7.

71-FCV-02

Please Consider flow (min/nor/max) as 1500/2500/3500


kg/hr
Please Consider all wetted part MOC as SS-304L

TCV
Sizing of control valve for steam (in series 13 & 32) minimum temperature to
be consider as 175OC (at pressure of 10 Kg/cm2g)
2 sheet added for 13-TCV-05 and 32-TCV-04 is missing in offer
SR
NO
1.
2.
3.
4.
5.
6.
7.
8.
9.
10
11.
12.
13.
14.
15.
16.
17.

Tag No
13-TCV-01
13-TCV-02
13-TCV-03
13-TCV-04
13-TCV-05
21-TCV-01
32-TCV-01
32-TCV-02
32-TCV-03
32-TCV-04
32-TCV-05
51-TCV-01
61-TCV-01
61-TCV-02
61-TCV-03
61-TCV-04
92-TCV-01

Comment