You are on page 1of 41

Axial Forces and Combined

Axial and Bending Forces

www.sgh.com

Axial Forces and Combined Bending and


Axial Forces
Four Types of Applications:
Axial Tension
Axial Compression
Combined Bending and Tension
Combined Bending and Compression
Most common axial load members are columns
Most common combined stress member is beamcolumn
Magnitude of lateral force in wall elements depends
on design load and how the wall is framed
(horizontally or vertically).

Examples of
Axial and Axial
plus Bending
Elements

Axial Tension Members


Number of structural applications:
Trusses have numerous axial force members;
about in tension
Chords of shearwalls and diaphragms
Collector or drag strut members (when length of
diaphragm is greater than shearwall).
Axial members allow for direct solution in design
Parallel to grain applications avoid cross grain
tension
General formula:
ft = P/An Ft

Capacity of
tension
members is
affected by
connections

Axial Tension Members


Gross area vs. Net area (projected fastener area is
subtracted - nails usually disregarded)
Avoid tight-fitting installations that require forcible
driving of the bolt
Perfect installations are difficult may have to drill
from both sides
Hole diameter can be taken to be bolt diameter
plus 1/16 in., as specified in NDS

Axial Tension Members


General formula:
ft = P/An Ft
Where Ft = Ft (CD)(CM)(Ct)(CF)(Ci)

Example Size truss bottom chord


16 ft

12 ft

12 ft

DEAD + LIVE LOADS 44 psf

44 psf
5

12

2.5 ft

8 ft

Determine required size


of truss bottom chord
Loads only applied to
top chord (convert to
point loads)
Use method of joints
truss joints assumed
pinned
Connections made with
a single row of 1/2 in.
bolts
Trusses 4 ft o.c., lumber
No. 1 SPF South
MC < 19%, normal
temperatures

Example Size truss bottom chord


44 psf (4 ft o.c.) = 176 plf

P = 176(6) =1056 lb

1056 lb
1056 lb

P/2 = 528 lb

528 lb

2,112 lb

2,112 lb

4(6) = 24

Example Size truss bottom chord cont.


44 psf (4 ft o.c.) = 176 plf
P = 1056 lb
P/2 = 528 lb

2,112 528 = 1,584 lb

1056 lb
1056 lb

528 lb
528 lb 5

FBD
2,112 lb

TAC =3,802 lb

2,112 lb
4(6) = 24

1,584(12)/5 = 3,802 lb

RA = 2,112 lb

FBD

Find forces by method of joints; T = 3.8k


From Table 4A for No.1 SPF South: Ft = 400 psi
Factors cD = 1.15, and assume cF = 1.3
Determine Ft init. = Ft (cD) (cF) = 400(1.15)(1.3) = 598 psi
Find required An = P/Ft = 3,802/598 = 6.36 in.2
Consider bolt holes:
Reqd Ag = An+Ah = 6.36+1.5(1/2 + 1/16) = 7.2 in.2

Try 2 x 6: A = 8.25 in.2 > 7.2 in.2 OK


Backcheck size factor for 2x8: cF = 1.3 - same as assumed.

Columns
Columns are generally sufficiently long that buckling
needs to be considered
Direct design is not feasible (trial size, iteration)
General formula:
fc = P/A Fc
Where Fc = Fc (CD)(CM)(Ct)(Cp)(CF)
Cross sectional area to be used (gross or net) should
be considered along the length of member, together
with tendency of member at that point to buckle
laterally

Column Design Considerations


Size factor applies only to dimension lumber
Column stability factor CP takes buckling into
consideration slenderness ratio is a measure of
buckling propensity
Slenderness ratio is generally expressed in terms of
effective (unbraced, corrected for end condition)
length, divided with least radius of gyration: (le/r).
For rectangular columns, slenderness ratio can be
expressed as le/d (radius of gyration is a direct
function of the width)
For non-rectangular columns, r 12 can be substituted
for d

Column Design Considerations


Behavior of wood columns is the result of
interaction between two modes of failure:
buckling and crushing
For use in design, the Euler critical buckling stress
is expressed in NDS as:

Crushing is measured by compressive design value


multiplied by all factors except CP:
F*c = Fc (CD)(CM)(Ct)(Ci)(CF)

Column Stability Factor


Takes into consideration Euler critical stress and
crushing strength:

where buckling and crushing interaction factor


for columns c:
= 0.8 for sawn lumber
= 0.85 for timber poles and piles
= 0.9 for SCL columns

Slenderness can really affect column strength

Slenderness Considerations

By inspection the slenderness ratio about the y axis is


larger and therefore critical

Slenderness Considerations
Conditions can exist under which the column may
buckle about the strong axis

In this case, (l/d)x may govern

In Stud walls, weak axis is


braced, but strong is not

Slenderness Considerations
End conditions are important
The effective length le used in slenderness ratios is
theoretically the unbraced length of a pinned-end
column
For other column-end conditions, the effective
length is taken as the distance between inflection
points (point of reverse curvature and zero
moment)
For purposes of column analysis, the inflection
point is considered as pinned end

Effective
length
factor: ke

10

Sidesway means
that top of column
is relatively free to
displace laterally:
In braced
situations or in
shearwalls,
sidesway is
prevented)
In rigid frames,
system is
flexible, and
sidesway can
occur

Slenderness Considerations
Effective length = effective length factor x unbraced
length: Le = Ke x L

11

Example: Interior Bearing Wall Capacity


12 ft

16 ft

12 ft

44 psf
8 ft
5

12

17 psf

750 plf
330 plf

72 plf
45 psf

96 plf

96 plf
55 psf
7 ft

No bending although on
exterior walls there could
be wind loads
Continuous lateral support
provided in y direction
Need to consider bearing
capacity of top and bottom
plates
Load is D + L, disregard self
weight of wall
See if Standard grade HemFir, 2 x 4 studs at 16 in. o.c.
are adequate
No special temperature
and moisture requirements

Total load: 17(12) + 45(12) + 72 = 816 lb/ft

Example: Interior Bearing Wall Capacity


Total wall height, including top and bottom plates, is 8 ft
Total load per stud, assuming 16 in. o.c.:
P = 816 lb/ft (16/12) = 1,088 lbs
From Table 4A, for Standard grade Hem-Fir:
Fc = 1300 psi, Fc = 405 psi, Emin = 440,000 psi

12

Example Continued

P = 1,088 lb
Fc = 1300 psi,
Fc = 405 psi,
Emin = 440,000 psi

CF = 1.0 for compression standard grade,


A = 5.25 in2; le = 8(12) 3(1.5) = 91.5 in.
(le/d)x = 1(91.5)/3.5 = 31.3 (about y axis studs are braced)
Emin = Emin = 440,000psi
c = 0.8 for visually graded lumber
x
x

= 369 psi;

Fc* = 1300(1.0) = 1,300 psi


= 0.265 ;

Fc = 1,300(.265) = 344 psi;


P = Fc A = 344(5.25) = 1,806 lb > 1,088 lb OK
Fc = Fc = 405 psi > 344 psi; so column capacity governs

Example Design of a Column


12 ft

16 ft

BASEMENT COLUMN

12 ft

Column height 7 ft
44 psf
8 ft

12

From before, load on beam


due to D+L: w = 1,583 plf

17 psf

750 plf
330 plf

72 plf
96 plf 3

Trib. L = 12 ft

96 plf
W

45 psf
5

72 plf

96 plf
55 psf

7 ft

Trib. length for column = 12 ft


Column load:
PD+L = 12(1,583) = 18,996 lb

13

Example Design Sawn Lumber Column


Design column, No. 1 Douglas Fir - Larch
Bracing the same for buckling about x and y axes
(non existent)
Dead and live load apply
Temperature, moisture, incision do not apply
Try 4x6 (dimension lumber):

L = 7 ft

P = 19k (D + L)

Example Design Sawn Lumber Column


From Table 4A for No 1 DFL:
Fc = 1500 psi, Emin = 620,000 psi; A = 19.25 in2, CF = 1.1
(le/d)max =kle/dy=1(84)/3.5 = 24; Emin = Emin = 620,000psi
c = 0.8 for visually graded lumber
= 885 psi; Fc* = 1500(1.0)(1.1) = 1,650 psi
= 0.46 ;
Fc = 1650(.46) = 757 psi
NG

P = 19k (D + L)

L = 7 ft

Pallow. = Fc A = .757(19.25) = 14.57k < 19k

14

Example Design Sawn Lumber Column


Trial 2: Try 6x6 (P&T); From Table 4D for No 1 DFL:
Fc = 1000 psi, Emin = 580,000 psi, CF = 1.0, A = 30.25 in2
(le/d)max =kle/dy=1(84)/5.5 = 15.3; Emin=Emin=580,000psi
c = 0.8 for visually graded lumber
= 2037 psi;

Fc* = 1000(1.0)(1.0) = 1,000 psi


= 0.87 ;

Fc = 1000(.87) = 870 psi


Allow. P = Fc A = .87(30.25) = 26.3 k > 19 k OK,
Use 6x6 column, No. 1 DF-L
L = 7 ft

P = 19k (D + L)

Example: Axial Capacity of Glulam


1
3

3.5 ft

3.5 ft

Determine if a 3-1/8x6 axialload glulam combination 2 DF


works for the previous
example.
MC less than 16%, normal
temp.
Loads are D+L assumed to
govern
Different unbraced lengths
about x and y axes (due to
installed kickers).

15

Example: Axial Capacity of Glulam


A = 18.75 in2, and from Table 5B:

(le/d)x =1(7)(12)/6 = 14; Governs


(le/d)y =1(3.5)(12)/3.125 = 13.44
c = 0.9 for glulam;
= 3,481 psi;

Fc= 1,950 psi;


Exmin = 830,000psi
Eymin = 830,000psi
In this case, same Emin properties
apply for x and y axes, but could
be different in glulam.

Emin = Emin
Fc* = 1,950(1.0) = 1,950 psi
= 0.91;

Fc = Fc* (CP) = 1,950(0.91) = 1,767 psi


P = Fc A = 1.767(18.75) = 33.1 k > 19 k OK

Built-Up Columns
Constructed from several parallel wood members
that are nailed or bolted together to function as a
composite column
NDS Section 15.2
Connecting fasteners do not fully transfer the shear
between the various pieces, and capacity of a builtup column is less than that of a solid sawn or glulam
column of same size and grade
Capacity of an equivalent solid column is reduced by
an adjustment factor Kf (only applies to the column
slenderness ratio for the axis parallel to the weak
axis of individual laminations)

16

Built-Up Columns

Questions?

17

Combined Axial and Bending


Forces

www.sgh.com

Combined Bending and Tension


Effects of simultaneous bending and tensile stresses
must be considered

On one face, axial stresses add to bending stresses, on


other face they cancel each other
Therefore, capacity of member is either governed by
combined tension criterion or by net compression
criterion

18

Combined Bending and Tension


Interaction equation:

Because actual bending stress fb is a bending tensile


stress, F*b is used (does not include CL)
If combined stress is compressive, bending analysis
must be performed (CL is included but Cv is not):

Fb** = Fb

CL applies, but CV does not

Combined Bending and Tension


Designer should be cautious about net compressive
stress: maximum bending compressive stress may occur
with or without tensile stress to cancel it.
Truss bottom chords are good example (tensile force
may or may not be present)
Conservative approach is to ignore reduction in bending
stress due to tension:

Fb** = Fb

CL applies, but CV does not

19

Combined Biaxial Bending and Tension


Axial tension and bending tension:

Net Compressive stress

Example: Combined Bending and Tension


16 ft

12 ft

12 ft

Truss example similar to


earlier example
additional uniform load
applied to bottom chord

44 psf
5

12

17 psf
2.5 ft

Use Select Structural DFL


with MC<19%
Pinned connections with
a single row of 1/2 in.
bolts

8 ft

Trusses at 4 ft o.c., w/
loads applied to top and
bottom chord assume
ends of member held in
position (not allowed to
rotate laterally); lateral
buckling not an issue

20

Example: Combined Bending and Tension


44 psf (4 ft o.c.) = 176 plf

6(176) = 1056 lb
P = 1056 lb

1056 lb

5
P/2=528+408 = 936 lb

936 lb

P = 68(12)= 816 lb

W = 17 psf (4 ft o.c.) = 68 plf


2,928 lb

RA = 2,928 lb

4(6) = 24

Example: Combined Bending and Tension


176 plf

2,928 938 = 1,990 lb


936 lb

P = 1056 lb

1056 lb

5
P/2 = 936 lb

936 lb

FBD
RA = 2,928 lb P = 816 lb

1,990(12)/5 = 4,776 lb

1056 lb

TAC = 4,776 lb
RA = 2,928 lb

FBD
W = 68 plf

W = 68 plf

4,776 k

2,928 lb

24

12

Trial and error procedure try a nominal 2x8:


Ag=10.88 in.2; S=13.14 in.3; An=1.5(7.25 9/16) = 10.03 in2
Fb = 1500 psi, Ft = 1000 psi; cF=1.2 for tension & bending
Check axial tension at An: ft = T/An = 4.78/10.03 = 476 psi
Ft = Ft(cD)(cF) = 1000(1.15)(1.2) = 1380 psi > 476 psi OK
Check Bending: M=wl2/8= 14,688 in-lb; fb = M/S= 1118 psi
Fb = Fb(cD)(cF) = 1,500(1.0)(1.2) = 1800 psi > 1118 psi OK

21

Example: Combined Bending and Tension


Combined Stresses:
Fb = 1500 psi, Ft = 1000 psi;
cF = 1.2 for tension & bending
Ag = 10.88 in.2; S = 13.14 in.3;

W = 68 plf
4,776 k
12

ft =T/Ag= 4,776/10.88 = 439 psi


F*b = Fb(cD)(cF) = 1500(1.15)(1.2) = 2,070 psi
ft/Ft + fbx/F*bx = 439/1380+1118/2070 = 0.86 < 1 OK
(D+S governs; typically would need to check D alone too)
Net bending compressive stress: automatically ok, since we already
checked it.
Also, since combined stress index is 0.86, we theoretically could find
a smaller size that would work (likely wont).
In general, CSI values of 1.02 or 1.03 could be acceptable.

Combined Bending and Compression


NDS interaction formula considers column buckling,
lateral torsional buckling of beams, and beam-column
interaction
In a beam-column, additional bending stress is created
due to P- effect
To analyze combined stresses, following convention
used:
Column buckling is governed by whichever the
larger slenderness ratio is (Fc includes CP)
When bending moment about x axis, the value of
FCE for use in amplification factor is to be based on
(le/d)x

22

Combined Bending and Compression

General formula:

Where

Combined Bending and Compression


Effect of column buckling, lateral torsional buckling,
and P-D effect is demonstrated on the following
interaction diagrams:

23

Biaxial Bending and Compression

General formula:

where:

Truss T.C. Example: Beam-Column


Determine required size of truss top chord
D + S loads, effects of roof slope already
accounted for
Connections made with a single row of in.
bolts
Trusses 4 ft o.c., lumber is No. 1 Dense
Southern Pine
MC < 19%, normal temperatures, top chord
laterally braced
L =6 ft
2,928 938 = 1,990 lb
936 lb

5,174 lb
1,990(12)/5 = 4,776 lb
TAC = 4,776 lb

RA = 2,928 lb

FBD

24

Example Beam-Column cont.


Try 2x8: A = 10.88 in.2; S = 13.14 in.3 CF = 1 for both C & B
Fc = 1,800 psi, Fb = 1,650 psi, Emin = 620,000 psi
Axial check: fc = P/A = 5174/10.88 = 476 psi;
Stability: (le/d)x =kle/dx=1(6.5)(12)/7.25 = 10.75;
Emin= Emin = 620,000 psi; c = 0.8 for visually graded lumber
x
x

= 4,410 psi;

Fc* = 1,800(1.15)(1.0) = 2,070 psi


= 0.88; Fc = 2,070(.88) = 1,822 psi
L =6 ft

Fc = 1,822 > fc = 476 OK


5

Example Beam-Column cont.


From before: Fc = 1,800 psi, Fb=1,650 psi, Emin = 620,000 psi
2x8: A = 10.88 in.2; S = 13.14 in.3 CF = 1 for both C & B
Net section compression check (not really needed here):
An=1.5(7.25 (9/16)) = 10.03 in2
fc = P/A = 5,174/10.03 = 516 psi
Fc = Fc* = 1,650(1.15)(1.0) = 1,898 psi > 516 OK
Bending Check:
M = wl2/8 = 176(6)2/8 = 792 ft-lb; fb = M/S = 723 psi
Fb = 1800(1.15)(1.0) = 2,070psi > 723 psi OK
L =6 ft

25

Example Beam-Column cont.


From before: Fc = 1,800 psi, Fb=1,650 psi, Emin = 620,000 psi
2x8: A = 10.88 in.2; S = 13.14 in.3 CF = 1 for both C & B
Combined Stress check :
CD based on shortest duration of load in combination
FcEx = FcE = 4,410 psi (coincidence that le/dx = le/dmax)
fb = 849 psi; Fbx = 2,070 psi; fc = 476 psi ; Fc = 1,822 psi
(476/1822)2 + (1/(1 476/4410))(723/2070) = 0.46 < 1 OK
L =6 ft

Can use 2 x 8 No. 1 SP, but


perhaps another, weaker
grade or a smaller size works.

Beam Columns with Transverse and


Eccentric Loads

In most cases with square-cut column ends, effects of


eccentricity are ignored by designers
Minimum recommended eccentricity to consider is 1 in.
or one tenth of column width.
No code requirement to design for minimum eccentric
load left to the judgment of engineer

26

Example Exterior Wall Beam-Column


Check column in
exterior wall that
supports gravity and
wind loads
Consider two L.C.:

Large double windows


on either side

D+S =14+30 = 44 psf

12

L.C.1: D+.75(L)+.75(S)
L.C. 2: D + W

D + L = 7 +10 = 17 psf

8 ft
W = 20 psf

8 ft

(there are others that may govern:


D+L; D+S; D+.75W+.75L+.75 S)

Try 4x4 SPF#2 column,


disregard self weight.

Example Exterior Wall Beam-Column


6

Gravity Loads:
PD = 14(6)(12)+7(6)(6)
PD = 1260 lb
PL = 10(6)(6) = 360 lb
PS = 30(6)(12) = 2160 lb

4x4

5.5

PS =

20 psf

Roof

2160 lb
1260 lb

PT = PD+.75PL+.75PS =
= 1260+.75(360+2160)
PT = 3,150 lb

360lb

512

8 ft
8 ft

TA 1

24

TA 2 Attic

27

Example Exterior Wall Beam-Column


Table 4A:
L.C. 1, Gravity loads: PD + 0.75 (PL+S) = 3.15 k; cD = 1.15; From
F = 1150 psi;
F = 875 psi;
Neglect column fixity @ ends, assume k=1:
E = 510,000 psi
(le/d)x = 1(8)(12)/3.5 = 27. 4
A =12.25 in2;
(le/d)y = 1(5)(12)/3.5 = 17.14; 27.4 governs
S = 7.15 in3
c

min

Emin = 510,000 psi, c = 0.8 for sawn lumber


x

= 558 psi;

Fc* = 1150(1.15) = 1,322 psi


= 0.38;

Fc = 1,322(0.38) = 502 psi


fc = P/A=3,150/12.25 = 257 psi

OK
20 psf

OK

PT = 3.15k
840lb

Example Exterior Wall Beam-Column


Fc = 1150 psi;
Fb = 875 psi;
Emin= 510,000 psi
A =12.25 in2;
S = 7.15 in3

L.C. 2: (D + W)
Axial alone (dead load): PD = 1260 lb
(le/d)max = (le/d)x = 27.4 from before
Emin = 510,000 psi, c = 0.8 for sawn lumber
x

= 558 psi;

Fc* = 1150(1.6) = 1,840 psi

1.6 taken throughout combined stress check

= 0.28;
Fc = 1840(0.28) = 517 psi
fc = P/A = 1260/12.25 = 103 psi
fc/Fc = 0.2
8

20 psf

PD = 1.26k
840lb

28

Example Exterior Wall Beam-Column


Fc = 1150 psi;
Fb = 875 psi;
Emin= 510,000 psi
A =12.25 in2;
S = 7.15 in3

L.C. 2 (D +W): Bending alone (wind)

Wind on header: w1 = 20(3) = 60 lb/ft


Wind on sill:
w2 = 20(3.5) = 70 lb/ft
Reaction on column from headers:
P1 = 60(6) = 360 lb
Reaction on column from sills:
P2 = 70(6) = 420 lb

fb = M/S = 8,640/7.15 = 1208 psi

420

P=1.26k

P1=.36k

.5

P=1.26k

420

1260 lb

60

Mx = 720(12) = 8640 in-k;


Fb=Fb(cD)(cL)

P=1.26k

Wall Framing and Tributary heights

P=1.26k

720
360

3.5

P2=.42k

Load & shear & moment

Example Exterior Wall Beam-Column


L.C. 2 Bending alone (wind) - continued:
Find cL: Lu = 5 ft (window height); Lu/d=60/3.5=17.1
14.3 17.1: Le = 1.84Lu = 110.4 (Table 3.3.3)*

Fc = 1150 psi;
Fb = 875 psi;
Emin= 510,000 psi
A =12.25 in2;
S = 7.15 in3

* formula applies conservatively for all cases

= 5.6;

= 19,402; Fb*= 875(1.6) = 1400 psi


= 0.996;

Fb = 1400(.996) = 1,395 psi


Stress ratio:
fb/Fb = 1208/1395 = 0.866

29

Example Exterior Wall Beam-Column


L.C. 2 Combined Stresses D+W:
(le/d)bending = (le/d)x = 27.4
x

= 558;

Fc = 1150 psi;
Fb = 875 psi;
Emin= 510,000 psi
A =12.25 in2;
S = 7.15 in3

From before:

fc = 103 psi; fc/Fc = 0.2; fb/Fb = 0.866


Amplification factor: 1/(1-fc/FcE) = 1/(1-103/558) = 1.226;
= (0.2)2 + 1.226(0.866) = 1.1 NG
NOTE: 4x6 would work for sure, but more effective to use better grade
NOTE: D+L; D+S; D+.75W+.75L+.75 S should also be checked
NOTE: Shear, deflection, and bearing perpendicular to grain need checking too
also need to be checked.

QUESTIONS?

30

Example 7.2 Size truss bottom chord

Determine required size of truss bottom chord


Loads only applied to top chord
Loads assumed to be applied to T.C. joints
Use method of joints truss joints assumed pinned
D + S loads, effects of roof slope already accounted for
Connections made with a single row of in. bolts
Trusses 4 ft o.c., lumber No. 1 SPF South
MC < 19%, normal temperatures

Example 7.2 Size truss bottom chord

Find forces by method of joints; T = 3.96k


Factors cD = 1.15, and assume cF = 1.3
Determine Ft = Ft (cD) (cF) = 400 (1.15)(1.3) = 598 psi
Find required An = P/Ft = 3960/598 = 6.62 in.2
Consider bolt holes:
Reqd Ag = An+Ah = 6.62+1.5(3/4 + 1/16) = 7.84 in.2

Try 2 x 6: A = 8.25 in.2 > 7.84 in.2 OK


Backcheck size factor cF = 1.3 - same as assumed.

FBD

31

Example 7.7 Design Sawn Lumber Column

Design column, No. 1 Douglas Fir - Larch


Bracing the same for buckling about x and y axes
Dead and roof live load apply
Temperature, moisture, incision do not apply

Example 7.7 Design Sawn Lumber Column


Try 4x6 (dimension lumber); From Table 4A for No 1 DFL:
Fc = 1500 psi, Emin = 620,000 psi, CF = 1.1, A = 19.25 in2
(le/d)max =kle/dy=1(120)/3.5 = 34.3; Emin=Emin=620,000psi
c = 0.8 for visually graded lumber
= 433 psi; Fc* = 1500(1.25)(1.1) = 2062 psi

= 0.2 ;

Fc = 2062(.2) = 412 psi


Allow. P = Fc A = .412(19.25) = 7.94 k < 15 k
NG

32

Example 7.7 Design Sawn Lumber Column


Trial 2: 6x6 (P&T); From Table 4D for No 1 DFL:
Fc = 1000 psi, Emin = 580,000 psi, CF = 1.0, A = 30.25 in2
(le/d)max =kle/dy=1(120)/5.5 = 21.8; Emin=Emin=580,000psi
c = 0.8 for visually graded lumber
= 1003 psi; Fc* = 1000(1.25)(1.0) = 1250 psi

= 0.611 ;

Fc = 1250(.611) = 764 psi


Allow. P = Fc A = .764(30.25) = 23.1 k > 15 k
OK, use 6x6 column, No. 1 DF-L

Example 7.9 Axial Capacity of Glulam


Determine axial compression capacity of 6-3/4 x 11
24F-1.7E Southern Pine glulam
MC will exceed 16% (consider treatment), normal temp
Loads are D+S assumed to govern
Different unbraced lengths about x and y axes,
different material properties for x and y axes
A = 74.25 in2

33

Example 7.9 Axial Capacity of Glulam


Table 5A:

Fc = 1000 psi (CM = 0.73),


Exmin = 880,000 psi (CM = 0.833)
Eymin = 670,000 psi (CM = 0.833)

(le/d)x =1(22)(12)/11 = 24; Exmin= 860,000(.833) = 733000 psi


(le/d)y =1(11)(12)/6.75 = 19.6; Eymin= 670,000(.83) = 558000 psi
c = 0.9 for glulam
x
x

y
y

= 1046 psi; Fc* = 1000(1.15)(0.73) = 840 psi


=1200 psi; Fc* is the same;

cPx = .832; cPy = .867; Fc = 1000(1.15)(.73)(.832) = 699 psi


P = Fc A = .699(74.25) = 51.9 k

Example 7.11 Capacity of a Bearing Wall


No bending although on exterior walls there could be
wind loads
Continuous lateral support provided in x direction
Need to consider bearing capacity of top and bottom plates
Load is D + S
Lumber is Standard grade Hem-Fir, 2 x 4 studs
No special temperature and moisture requirements

34

Example 7.11 Capacity of a Bearing Wall


Table 4A: Fc = 1300 psi, Fc = 405 psi, Emin = 440,000 psi,
CF = 1.0 for compression, A = 5.25 in2
le = 9.5(12) 3(1.5) = 109.5 in.
(le/d)x = 1(109.5)/3.5 = 31.3; Emin = Emin = 440,000psi
c = 0.8 for visually graded lumber
x
x

= 370 psi; Fc* = 1300(1.15) = 1495 psi


= 0.233 ;

Fc = 1495(.233) = 348 psi;


P = Fc A = 348(5.25) = 1829 lb ; max w = 1829/1.33 = 1371 lb/ft
Fc = Fc = 405 psi > 348 psi; column capacity
governs

Example 7.15 Combined Bending and Tension


Truss example similar to truss in example 7.2
additional uniform load applied to bottom chord
Use No.1 and Better Hem-Fir with MC<19%
Pinned connections with a single row of in. bolts
Trusses at 4 ft o.c., w/ loads applied to top and bottom
chord assume ends of member held in position (not
allowed to rotate laterally)

35

Example 7.15 Combined Bending and Tension

Trial and error procedure try a nominal 2x8 first:


Fb = 1100 psi, Ft = 725 psi; cF = 1.2 for tension & bending
Ag=10.875 in.2; S=13.14 in.3; An=1.5(7.25 (13/16)=9.66 in2
Check axial tension at An: ft = T/An = 4.44/9.66 = 460 psi
Ft = Ft(cD)(cF) = 725 (1.15)(1.2) = 1000 psi > 460 psi OK
Check Bending: M = wl2/8=10,800 in-lb; fb = M/S = 822 psi
Fb = Fb(cD)(cF) = 1100(0.9)(1.2) = 1188 psi > 822 psi OK

Example 7.15 Combined Bending and Tension


Combined Stresses:
Fb = 1100 psi, Ft = 725 psi; cF = 1.2 for tension & bending
Ag=10.875 in.2; S=13.14 in.3; ft =T/Ag=4440/10.875= 408psi
F*b = Fb(cD)(cF) = 1100(1.15)(1.2) = 1518 psi
ft/Ft + fbx/F*bx = 408/1000+822/1518 = 0.95 < 1 OK
(D+S governs, but D alone is close)
Net bending compressive stress: automatically ok, since
we already checked it.
Also, since combined stress index is 0.95, we are likely
not going to find a smaller size that would work.
In general, CSI values of 1.02 or 1.03 could be
acceptable.

36

Example 7.18 Beam-Column

Determine required size of truss top chord (example 7.15)


D + S loads, effects of roof slope already accounted for
Connections made with a single row of in. bolts
Trusses 4 ft o.c., lumber is No. 1 Southern Pine
MC < 19%, normal temperatures, top chord laterally braced

Example 7.18 Beam-Column


Try 2x8: A = 10.875 in.2; S = 13.14 in.3 CF = 1 for both C & B
Fc = 1650 psi, Fb = 1500 psi, Emin = 620,000 psi
Axial: Stability check: fc = P/A = 4960/10.875 = 456 psi
(le/d)x =kle/dx=1(8.39)(12)/7.25 = 13.9;
Emin=Emin= 620,000psi c = 0.8 for visually graded lumber
x
x

= 2638 psi; Fc* = 1650(1.15)(1.0) = 1898 psi

S = 0.791; Fc = 1898(.791)=1501 psi


1501 > 456 OK

37

Example 7.18 Beam-Column


Try 2x8: A = 10.875 in.2; S = 13.14 in.3 CF = 1 for both C & B
Fc = 1650 psi, Fb = 1500 psi, Emin = 620,000 psi
Net section check:
An=1.5(7.25 (13/16)) = 9.66 in2
fc = P/A = 4960/9.66 = 514 psi
Fc = Fc* = 1650(1.15)(1.0) = 1898 psi > 514 OK
Bending Check:
M = wl2/8 = 0.176(7.5)2/8 = 1.24 ft-k; fb = M/S = 1130 psi
Fb = 1500(1.15)(1.0) = 1725 psi > 1130 psi OK

Example 7.18 Beam-Column


Try 2x8: A = 10.875 in.2; S = 13.14 in.3 CF = 1 for both C & B
Fc = 1650 psi, Fb = 1500 psi, Emin = 620,000 psi
Combined Stress check :
CD based on shortest duration of load in combination
FcEx = FcE = 2638 psi (coincidence that le/dx = le/dmax)
Fb = 1130 psi; Fbx = 1725 psi; fc = 456 psi; ; Fc = 1501 psi
(456/1501)2 + (1/(1 456/2638)(1130/1725) = 0.884 < 1 OK

Use 2 x 8 No. 1 SP

38

Example 7.20 Glulam Beam-Column


Check glulam column that supports gravity and wind loads
L.C. 1: D +LR ; L.C. 2: D + W
Axial-load glulam combination: 5-1/8x7-1/2; 2 DF glulam

Example 7.20 Glulam Beam-Column


L.C. 1: Gravity loads: D + LR = 5+4 = 9k; cD = 1.25;
(D alone should be checked as well)
neglect column fixity @ ends, assume k=1:

Table 5B:
Fc=1950 psi;
Fbx=1700 psi;
Exmin= 830,000psi
Eymin = 830,000psi
A = 38.4 in2;
S = 48 in3

(le/d)x = 1(16)(12)/7.5 = 25.6


(le/d)y = 1(8)(12)/5.125 = 18.7 < 25.6
Exmin = Eymin = Emin = 830,000 psi, c = 0.9 for glulam
x

= 1041 psi; Fc* = 1950(1.25) = 2438 psi


= 0.4;

Fc = 2438(0.4) = 975 psi


fc = P/A = 9000/38.4 = 234 psi;
OK

39

Example 7.20 Glulam Beam-Column


L.C. 2: Could be (D +W) or (D + 0.75(W + Lr))
(predetermined that D+W governs)
Axial (dead load):
(le/d)max = (le/d)x = 25.6 from before
Emin = 830,000 psi, c = 0.9 for glulam
x

Table 5B:
Fc=1950 psi;
Fbx=1700 psi;
Exmin= 830,000psi
Eymin = 830,000psi
A = 38.4 in2;
S = 48 in3

= 1041 psi; Fc* = 1950(1.6) = 3120 psi


1.6 taken throughout combined stress check

= 0.319; Fc = 3120(0.319) = 995 psi


fc = P/A = 5000/38.4 = 130 psi
fc/Fc = 0.131

Example 7.20 Glulam Beam-Column


Table 5B:
Fc=1950 psi;
Fbx=1700 psi;
Exmin= 830,000psi
Eymin = 830,000psi
A = 38.4 in2;
S = 48 in3

L.C. 2 (D +W): Bending (wind)

Wind on header: w1 = 22.2(6.5) = 144 lb/ft


Wind on sill: w2 = 22.2(5.5) = 122 lb/ft
Reaction on column from headers: P1 = 144(12) = 1728 lb
Reaction on column from sills: P2 = 122(12) = 1463 lb
Mx = 87.8 in-k;
fb = M/S = 87.8/48 = 1830 psi
Fb=Fb(cD)(cL) or Fb=Fb(cD)(cV); determine which governs

Wall Framing and Tributary heights

Load & shear & moment

40

Example 7.20 Glulam Beam-Column


L.C. 2 Bending (wind):
Find cL: lu = 8 ft (window height); lu/d=96/7.5=12.8.
7 12.8 14.3: le = 1.63lu+3d = 179 (Table 3.3.3)*
* formula applies conservatively for all cases

= 7.15;

Table 5B:
Fc=1950 psi;
Fbx=1700 psi;
Exmin= 830,000psi
Eymin = 830,000psi
A = 38.4 in2;
S = 48 in3

= 19,483; Fb*= 1700(1.6)=2720 psi


= 0.993

Find cV: (21/L)1/x(12/d)1/x(5.125/b)1/x

x for DF glulam = 10

Cv = (21/16).1(12/7.5).1(5.125/5.125).1 =
Cv = 1.007 > 1 : Cv = 1, CL governs:
Fb = 1700(1.6)(.993) = 2700 psi
Stress ratio: fb/Fb = 1830/2700 = 0.678

Example 7.20 Glulam Beam-Column


L.C. 2 Combined Stresses:
(le/d)bending = (le/d)x = 25.6 coincidence, could differ

Table 5B:
Fc=1950 psi;
Fbx=1700 psi;
Exmin= 830,000psi
Eymin = 830,000psi
A = 38.4 in2;
S = 48 in3

= 1041; From before:


fc = 130 psi; fc/Fc = 0.131; fb/Fb = 0.678
Amplification factor: 1/(1-fc/FcE) = 1/(1-130/1041) = 1.14;
x

= (0.131)2 + 1.14(0.678) = 0.79 OK


Note: if D + 0.75(W + LR) was used, the interaction value
would be considerably less.
NOTE: shear, deflection, and bearing perpendicular to
grain also need to be checked

41

You might also like