SPEEDTRONICS MK V
START-UP / SHUTDOWN FLOWCHART
( MS6001B / DLN1 )
( GAS )
4/19/01
Page 1
g
_____________________________________________________________________GE Power Systems
Training and Development
4/19/01
Page 2
g
_____________________________________________________________________GE Power Systems
Training and Development
4/19/01
Page 3
g
_____________________________________________________________________GE Power Systems
Training and Development
L4PST
Protective
Status Trip
L4PRET
Pre-ignition
Trip
L4POST
Post Ignition
Trip
L4IGVT
IGV Control
Trouble [Allarm 141 }
Normal Shutdown
( L94X )
Loss Of Flame
( L28FDT ) [ Alarm 91 ]
High Exhaust
Temperature Spread
( L30SPT ) [ Alarm 160 ]
No Starting Device
Trip
( L4Z )
Fire Protection
( L45FTX )
High Vibration.
( L39VT )
TCEA HP Accel
( L12H_ACC )
Customer Trip
(L4CT)
Ignition Permissive
( L2TVX )
HP Overspeed Fault
Protective
( L12HFD_P ) [ Alarm 73 ]
Electrical Turbine
overspeed
( L12H ) [ Alarm 70 ]
No DLN Trip
( L4DLNT )
4/19/01
Page 4
g
_____________________________________________________________________GE Power Systems
Training and Development
4/19/01
Page 5
g
_____________________________________________________________________GE Power Systems
Training and Development
If gas fuel is selected ( L43FTG ) and on total gas ( L84TG ) the gas stop valve
( L20FGX ) is energized.
Unit is "CRANKING" if
Speed is above (>)0.31% speed ( L14HRZ ).
No Flame Detected ( L28FD ).
No startup firing fuel level ( L83SUFI ) { 0% FSR }.
<I> Message
CRANKING
4/19/01
Page 6
g
_____________________________________________________________________GE Power Systems
Training and Development
4/19/01
Page 7
g
_____________________________________________________________________GE Power Systems
Training and Development
Igniters energized.
FSR set for FIRING ( L83SUFI ).16.3%
<I> Message
FIRING
START-UP CONTROL
<I> Message
WARMING UP
4/19/01
Page 8
g
_____________________________________________________________________GE Power Systems
Training and Development
4/19/01
Page 9
g
_____________________________________________________________________GE Power Systems
Training and Development
Load Selection
Spinning Reserve
Pre-selected
Base
Peak
No load selected
( L83PS )
( L83B )
( L83P )
4/19/01
Page 10
g
_____________________________________________________________________GE Power Systems
Training and Development
FIRED SHUTDOWN
Turbine trips are part of the Protective Systems. These types of trips cut fuel off
immediately and unit coasts down. This is different from a FIRED SHUTDOWN
where fuel decreases gradually allowing rotor speed to decrease to reduce the
thermal stresses.
AUTO SHUTDOWN
4/19/01
Page 11
g
_____________________________________________________________________GE Power Systems
Training and Development
4/19/01
Page 12