voltage rating and the nominal voltage between any two conductors does not exceed the higher value of the circuit
breakers voltage rating.
Frequency - Molded-case circuit breakers are normally suitable for 50Hz or 60Hz. Some have DC ratings as well.
Continuous current or Rated current - This is the maximum current a circuit breaker can carry continuously at a
given ambient temperature rating without tripping (typically 40C).
In accordance with NEC article 210.20 a circuit breaker (or any branch circuit overcurrent device) should not be
loaded to over 80% of its continuous current unless the assembly, including the circuit breaker and enclosure, is listed
for operation at 100% of its rating.
Poles - The number of poles is the number of ganged circuit breaker elements in a single housing. Circuit breakers
are available with one, two, or three poles, and also four poles for certain applications.
Per NEC article 240.85 a two-pole circuit breaker cannot be used for protecting a 3-phase, corner-grounded delta
circuit unless the circuit breaker is marked 1 3 to indicate such suitability.
Control voltage - The control voltage rating is the AC or DC voltage designated to be applied to control devices
intended to open or close a circuit breaker. In most cases this only applies to accessories that are custom-ordered,
such as motor operators.
Interrupting rating - This is the highest current at rated voltage that the circuit breaker is intended to interrupt under
standard test conditions.
Short-time or Withstand Rating - This characterizes the circuit-breakers ability to withstand the effects of shortcircuit current flow for a stated period. Molded-case circuit breakers typically do not have a withstand
rating, although some newer-design breakers do.
Instantaneous override - A function of an electronic trip circuit breaker that causes the instantaneous function
to operate above a given level of current if the instantaneous function characteristic has been disabled.
Current Limiting Circuit Breaker - This is a circuit breaker which does not employ a fusible element and,
when operating in its current-limiting range, limits the let-through I 2t to a value less than the I 2t of a _-cycle wave
of the symmetrical prospective current.
HID - This is a marking that indicates that a circuit breaker has passed additional endurance and temperature
rise tests to assess its ability to be used as the regular switching device for high intensity discharge lighting. Per
NEC 240.80 (D) a circuit breaker which is used as a switch in an HID lighting circuit must be marked as HID.
HID circuit breakers can also be used as switches in fluorescent lighting circuits.
SWD - This is a marking that indicates that a circuit breaker has passed additional endurance and temperature rise
tests to assess its ability to be used as the regular switching device fluorescent lighting.
Per NEC 240.80 (D) a circuit breaker which is used as a switch in an HID lighting circuit must be
marked as SWD or HID.
Frame - The term Frame is applied to a group of circuit breakers of similar configuration. Frame size is
expressed in amperes and corresponds to the largest ampere rating available in that group.
Thermal-magnetic circuit breaker - This type of circuit breaker contains a thermal element to trip the circuit breaker
for overloads and a faster magnetic instantaneous element to trip the circuit breaker for short circuits.
On many larger thermal-magnetic circuit breakers the instantaneous element is adjustable.
Electronic trip circuit breaker - An electronic circuit breaker contains a solid-state adjustable trip unit. These circuit
breakers are extremely flexible in coordination with other devices.
Sensor - An electronic-trip circuit breakers sensor is usually an air-core current transformer (CT)
designed specifically to work with that circuit breakers trip unit.
The sensor size, in conjunction with the rating plug, determines the electronic-trip circuit breakers continuous
current rating.
Rating plug - An electronic trip circuit breakers rating plug can vary the circuit breakers continuous current rating as
a function of its sensor size.
Typical molded-case circuit breakers are shown in Figure 1, where on the left is a thermal-magnetic circuit breaker,
and on the right is an electronic-trip circuit breaker. The thermal-magnetic circuit breaker is designed for cable
connections and the electronic circuit breaker is designed for bus connections, but neither type is inherently suited for
one connection type over another.
Circuit breakers may be mounted in stand-alone enclosures, in switchboards, or in panelboards.
This adjustability makes the electronic-trip circuit breaker very flexible when coordinating with other
devices. The adjustable parameters for an electronic trip circuit breaker are features of the trip unit.
In many cases the trip unit is also available without the short-time function.
In catalog data the long-time characteristic is listed as L, the short-time is listed as S, and the instantaneous as I.
Therefore an LSI trip unit has long-time, short-time, and instantaneous characteristics, whereas an LI trip unit has only
the long-time and instantaneous characteristics.
For circuit breakers that have a short-time rating, the instantaneous feature may be disabled, enhancing coordination
with downstream devices.
If the instantaneous feature has been disabled one must still be cognizant of any instantaneous override feature the
breaker has, which will engage the instantaneous function above a given level of current even if it has been disabled
in order to protect the circuit breaker from damage.
Coordination
Typical coordination between an electronic and a thermal magnetic circuit breaker is shown in figure 4
below. Because the time bands do not overlap, these two devices are considered to be coordinated.
A further reduction in the let-through energy for a fault in the region between two electronic-trip circuit breakers can be
accomplished through zone-selective interlocking. This consists of wiring the two trip units such that if the downstream
circuit breaker senses the fault (typically this will be based upon the short-time pickup) it sends a restraining signalto
the upstream circuit breaker.
The upstream circuit breaker will then continue to time out as specified on its characteristic curve, tripping if the
downstream device does not clear the fault.
However, if the downstream device does not sense the fault and the upstream devices does, the upstream device will
not have the restraining signal from the downstream device and will trip with no intentional delay.
Example
For example, if zone selective interlocking were present in the system of figure 4 and fault occurs on bus C circuit
breaker B will sense the fault and send a restraining signal to circuit breaker A. Circuit breaker A is coordinated with
circuit breaker B, so circuit breaker B will trip first.
If circuit breaker B fails to clear the fault, circuit breaker A will time out on its time-current characteristic per figure 4
and trip. If the fault occurs at bus B, circuit breaker B will not detect the fault and thus will not send the restraining
signal to circuit breaker A. Circuit breaker A will sense the fault and will trip with no intentional delay, which is faster
than dictated by its time-current characteristic per figure 4.
Care must be used when applying zone-selective interlocking where there are multiple sources of power and fault
currents can flow in either direction through a circuit breaker.
Table 1 shows typical characteristics of molded-case circuit breakers for commercial and industrial applications. This
table is for reference only; when specifying circuit breakers manufacturers actual catalog data should be used.
Frame Size (A)
100
100, 150
225, 250
400, 600
800, 1000
1200
Number of
Poles
10
14
65
65
120 V
240 V
277 V
480 V
600 V
2, 3
18
14
14
2, 3
65
25
18
2, 3
100
65
25
2, 3
25
22
22
2, 3
65
25
22
2, 3
100
65
25
2, 3
42
30
22
2, 3
65
65
25
2, 3
100
42
30
22
65
50
25
200
100
65
42
30
22
35
1600, 2000
3000, 4000
65
50
25
200
100
65
65
50
42
125
100
65
100
100
85
200
150
100
Note that the continuous current rating is set by the sensor and rating plug sizes for a given electronic-trip
circuit breaker. This can be smaller than the frame size. As can be seen from table 1, more than one interrupting
rating can be available for a given frame size.
Current-limiting circuit breakers are also available. Coordination between two current-limiting circuit breakers
when they are both operating in the current limiting range is typically determined by test.
By definition, low voltage molded case circuit breakers are not maintainable devices. Failure of a component
generally requires replacement of the entire circuit breaker unless the circuit breaker has been specifically designed
for maintainability.
Magnetic-only circuit breaker swhich have only magnetic tripping capability are available. These are often used as
short-circuit protection for motor circuits. For this reason these are often referred to as motor circuit protectors.
Reference: System Protection Bill Brown, P.E., Square D Engineering Services