YCWM-B

WATER COOLED
CHILLER

YCRM-B
REMOTE AIR
COOLED CHILLER
R407C REFRIGERANT
COOLING CAPACITIES
57 kW to 141 kW
YORK Water Cooled Chillers (YCWM-B)
and Remote Air Cooled Chillers
(YCRM-B) are a compact design suitable
for chilled water or glycol cooling. They are
designed to be located inside a plant
room.
YCWM-B Chillers require a cooling tower
or dry cooler for heat rejection.
YCRM-B Chillers require an air cooled
condenser for heat rejection.

CONTENTS
Specification
Accessories and Options

AVAILABLE MODELS & NOMINAL COOLING CAPACITIES TABLE 1


Model
YCWM-B
YCRM-B

60
57
57

Cooling Capacity (kW)


75
90
120
69
89
117
69
89
117

150
141
141

YCWM-B cooling capacities at 7C chilled water and 35C condenser water temperature
YCRM-B cooling capacities at 7C chilled water and 40C condensing temperature

FEATURES
A narrow width and low base area.

BENEFITS
Ideal replacement for existing chillers in
refurbished buildings.

Two refrigerant circuits.

System stand-by security.

Minimum base area/maximum capacity.

Minimum installation space.

Low weight , single power and control supplies.

Easy to install.

Full factory run test.

Operating quality control.

Optional acoustic kit.

Reduces operating sound levels.

Accessible components.

Ideal for maintenance operations.

Residual current circuit breaker.

Operator safety.

Microprocessor control with visual display of temperatures


and alarms.

Simple operation.

Manufactured to ISO 9001/EN 29001.

High standard of quality control.

Optional heat pump mode.

Year round heating and cooling.

Controls
Operating Limitations
Refrigeration Flow Diagram
Selection Guide
Water Pressure Drops
Cooling Capacities
Physical Data
Acoustic Data
Electrical Data
Electrical Connections
Space Requirements
Dimensions

SPECIFICATION
The Chillers shall be completely factory assembled with all interconnecting
refrigerant piping and wiring ready for field installation. After assembly the YCWM-B
shall have a full test run with water flowing through the evaporators. The YCWM-B
shall be pressure tested, evacuated and fully charged with refrigerant and include
an initial oil charge. The YCRM-B shall be pressure tested, evacuated and include a
nitrogen holding charge and an initial oil charge.
The unit base and frame shall be of heavy gauge galvanised steel fastened with
stainless steel nuts and bolts. All units shall have a galvanised steel enclosure with
an access panel. Galvanised steel parts shall be painted with baked on enamel
coloured white (RAL 9001).
Compressors
The hermetic compressors shall have internal motor protection and an internal
overflow valve from discharge to suction. Starting shall be direct on line. The
compressors shall be mounted on rubber anti-vibration pads and housed in a
separate acoustically lined enclosure.

Page C.1
Doc. No. PC153/10.04/GB

YCWM-B Evaporators and Condensers


YCRM-B Evaporators
Each of the two evaporators and condensers shall be stainless
steel plate type heat exchangers thermally insulated with flexible
closed cell material. Design working pressure 10 bar g on the
water side and 30 bar g on the refrigerant side.
YCRM-B Condenser
Provision shall be made for connection to a remote air cooled
condenser.
Refrigerant Circuits
Two refrigerant circuits shall be provided and each circuit shall
include: a service valve for refrigerant charging, suction,
discharge and liquid line isolating valves, a sight glass with
moisture indicator, a thermostatic expansion valve and a wire
mesh filter.

Power and Control Panel


All controls and motor starting equipment necessary for full unit
operation shall be factory wired and tested. Control and power
components shall be located in separate compartments. The
panel shall be designed to IP53 weather protection.
The control compartment shall contain an electronic circuit
board and a soft touch key control panel with display of
operating functions, alarms and stops.
The power compartment shall contain compressor contactors,
fuses and supply protection.
Polythene film packaging for shipping.

ACCESSORIES AND OPTIONS


Remote Control Kit for YCWM-B/YCRM-B
Field mounted control panel to provide remote control.

Pressostatic Valve (YCWM-B)


Pressostatic valves are remotely located in the leaving
condenser water pipework from each of the two condensers.
Manifold Kit for YCWM-B/YCRM-B
They are wired to the YCWM-B control panel. When the actual
Field mounted manifolds to provide a single point of connection
condensing pressure equals the control set point the valves
for leaving and return water circuits.
open modulating the water flow.
Shipping packaging option for seaworthiness or in a wooden
Hydro Kit
crate.
The field installed YORK Hydro Kit is a hydraulic package
complete with all components required for the correct operation
Flow Switch Kit for YCWM-B/YCRM-B
of a liquid distribution circuit.
Field mounted flow switches for evaporator water circuits.

CONTROLS

FIGURE 1
1

10 11

12

I
Setpoints
O

Display

+
SET

Circuit 1

IN

System

8888
OUT

-P

H20

-P

H20

Circuit 2

16

1. Master switch/safety cut out.


2. Setpoint selection and display key and LED
(cold/hot water temperature)
3. Setpoint change key (+). Increases desired
water temperature.
4. Display
5. Inlet water display and LED.

Control is by return water temperature control.

Page C.2
Doc. No. PC153/10.04/GB

6.
7.
8.
9.
10.
11.

Start-up key and LED.


Compressor ON LED.
High pressure alarm LED.
Low pressure alarm LED.
Antifreeze alarm.
Voltage ON LED.

15

14

12.
13.
14.
15.
16.

13

Start key and LED - Cooling.


Start key and LED - Heating.
External interlock alarm LED.
Outlet water display and LED.
Setpoint change key (-). Decreases desired
water temperature.

OPERATING LIMITATIONS
YCWM-B/YCRM-B
Chilled
Liquid

Evaporator water Water outlet


outlet temperature Temp. spread
Flow rate (1)

Pressure drop (1)


Max. working pressure
Cooling Liquid outlet
Water outlet
Liquid
temperature
Temp. spread
(2)
Flow rate (1)
Pressure drop (1)
Max. working pressure
Power supply voltage 400 V, 3 , 50 Hz (nominal)
Recommended system water volume (3)

C
C
m/h
kPa
bar
C
K
m/h
kPa
bar
V
l

Min.

60
Max.

Min.

75
Max.

4,3
6,3

20,3
112,9

5.0
6,7

24,0
125,1

6,1
15,2

24,4
212,2

7,2
15,7

29,5
230,7

730

860

TABLE 2
90
Min. Max.
6 to 12
3 to 8
6,9
32,7
6,1 113,8
10
30 to 50
3 to 8
8,3
39,2
13,8 271,4
10
360 to 440
1050

120
Min. Max.

150
Min. Max.

8,6
4,7

42,1
93,0

10,4
5,3

50,4
103,4

12,6
18,2

50,7
265,0

15,2
17,7

61,2
258,2

1550

1750

(1) Total unit flow rate and pressure drop are given
(2) YCWM-B only
(3) Table shows minimum water / brine volume of system

REFRIGERANT FLOW DIAGRAM


YCWM-B

FIGURE 2

YCWM-B Cooling Mode


Low pressure liquid refrigerant enters the cooler (Evaporator)
and is evaporated and superheated by the heat energy
absorbed from the chilled water passing through the cooler
shell. Low pressure vapour enters the compressor where
pressure and superheat are increased. Heat is rejected by the
water cooled condenser. The fully condensed and subcooled
liquid refrigerant then enters the expansion valve where
pressure reduction and further cooling takes place before
returning to the cooler.

YCWM-B HEAT PUMP

FIGURE 3

YCWM-B Heat Pump


The YCWM-B unit can operate as a water to water heat pump by
reversing the cycle on the water circuits using three way valves.
Pressostatic two way valves are available as an option for
remote location in the and condenser water pipework.
Note: This type of operation is possible only if the condensers
are supplied with well water or disposable water. The system
cannot be used if a cooling tower is used.

Page C.3
Doc. No. PC153/10.04/GB

SELECTION GUIDE
DATA REQUIRED
To select a YORK YCWM-B chiller the following information is
required:
1. Design cooling capacity.
2. Chilled water entering and leaving temperatures.
3. Condenser water entering and leaving temperature.
4. Chilled water flow (m/h) if one of the temperatures in (2) is
unknown.
5. Condenser water flow (m/h) if one of the temperatures in (3)
is unknown.
Determine the capacity from:
Cooling Capacity (kW) = Range (C) x chilled water (m/h)
0.86

5. The fouling factor required in the condenser introduces a


capacity factor of 0.955 and a kW input factor of 1.068.
The fouling factor required in the cooler introduces a capacity
factor of 0.964 and a kW input factor of 0.985 (see table 2).
Net Cooling Capacity
Net kW input

= 115.6 x 0.955 x 0.964 = 106.4 kW


= 32 x 1.068 x 0.985 = 33.7 kW

6 The heat rejection at the required fouling conditions will be


106.4 + (33.7 x 0.95*) = 138.4 kW
*5% radiation heat loss through compressor and motor
housing.
7. The chilled water flow required to satisfy the capacity
corrected for the fouling conditions
Actual capacity (kW) x 0.86 = 106.4 x 0.86 = 18.3 m/h
Range (C)
5.0

Determine the heat rejection from:


Heat Rejection (kW) = Range (C) x condenser water (m/h)
0.86
YCWM-B SAMPLE SELECTION
Select a YCWM-B chiller to cool 18 m/h of water from 11C to
6C. The condenser leaving water temperature is 33C with a
6C range.
The required fouling factor is 0.176m C/kW for cooler and
condenser.
Find the required unit size, cooling capacity, kW input and the
cooler and condenser pressure drop.

8 The evaporator water pressure drop = 20kPa (see Figure 5).


9. The condenser water flow:
Heat rejection (kW) x 0.86 = 138.4 x 0.86 = 19.8 m/h
Range (C)
6
10.Determine the condenser water pressure drop = 44kPA. (see
Figure 5).

TABLE 3

1. Chilled water range = 11 - 6 = 5C


2. Cooling Capacity (kW)

= Range (C) x chilled water (m/h)


0.86
= 5 x 18 = 104.65 kW
0.86

Fouling Factor m C/kW


0.044
0.088
0.176
0.352

EVAPORATOR
Capacity Factor
1.000
0.987
0.964
0.915

Comp. Input Factor


1.000
0.995
0.985
0.962

Fouling Factor m C/kW


0.044
0.088
0.176
0.352

CONDENSER
Capacity Factor
1.000
0.987
0.955
0.910

Comp. Input Factor


1.000
1.023
1.068
1.135

3. Select a chiller model from capacity table 4 YCWM-B 120 has


the following capacity:

Chilled Leaving
Water Temp.
Condenser Leaving
Water Temp.

(C)
30C
33C
35C

6
Chiller Capacity (kW)
121
115.6
112

4. Determine the compressor power input (kW)

Chilled Leaving
Water Temp.
Condenser Leaving
Water Temp.

Page C.4
Doc. No. PC153/10.04/GB

(C)
30C
33C
35C

6
Compressor Power Input (kW)
31
32
32.7

FOULING FACTORS

WATER PRESSURE DROPS


YCWM-B/YCRM-B EVAPORATORS
130
125

YCWM-B CONDENSERS

FIGURE 4

275
250
225

75

60

90

100

120

FIGURE 5

150

90

120

150

75

60

200
175

75

150
125
100

35

Pressure Drop kPa

Pressure Drop kPa

50
45
40

30
25
20

15

75

50
45
40
35
30
25

10
9
8

20

7
6
5
4
4

9 10

15

20

25

30

35

40 45 51

Flow Rate m/h

15
14
13
12
11
10
6

9 10

15

20

25

30

YCWM-B COOLING CAPACITIES


Model

YCWM
60

YCWM
75

YCWM
90

YCWM
120

YCWM
150

Leaving
Chilled
Liquid
Temp
C
6
7
10
12
6
7
10
12
6
7
10
12
6
7
10
12
6
7
10
12

Cool
kW
59
61
68
72
71
74
83
87
93
97
110
118
121
126
142
151
146
152
169
180

30C
Power
Input
kW
14.6
14.8
15.2
15.4
17.4
17.6
18.1
18.5
21.3
21.6
22.2
22.6
30.6
31.0
31.9
32.4
38.0
38.4
39.6
40.2

Heat
Rejection
kW
73.4
75.5
83.6
87.7
88.7
91.8
100.0
105.1
113.2
118.3
131.6
139.7
151.0
157.1
172.4
181.6
182.6
189.7
208.1
218.3

Model

YCRM
60

YCRM
75

YCRM
90

YCRM
120

YCRM
150

Cool
kW
59
61
68
72
71
74
83
87
93
97
110
118
121
126
142
151
146
152
169
180

35C
Power
Input
kW
14.6
14.8
15.2
15.4
17.4
17.6
18.1
18.5
21.3
21.6
22.2
22.6
30.6
31.0
31.9
32.4
38.0
38.4
39.6
40.2

Heat
Rejection
kW
73.4
75.5
83.6
87.7
88.7
91.8
100.0
105.1
113.2
118.3
131.6
139.7
151.0
157.1
172.4
181.6
182.6
189.7
208.1
218.3

40 45 50 55 60 65

Cool
kW
54
57
63
67
66
69
77
82
85
89
101
108
112
117
132
140
135
141
157
167

35C
Power
Input
kW
15.5
15.7
16.3
16.6
18.2
18.4
19.2
19.7
22.6
22.9
23.9
24.4
32.3
32.7
33.9
34.5
40.2
40.7
42.2
43.1

Condensing Leaving Water Temperature


40C
Heat
Cool
Power
Heat
Cool
Rejection
Input
Rejection
kW
kW
kW
kW
kW
69.4
50
16.4
66.3
46
72.4
52
16.6
68.3
48
79.6
59
17.3
75.5
54
83.6
62
17.7
79.6
58
83.6
61
19.0
79.6
58
86.7
63
19.3
82.6
60
95.9
71
20.2
90.8
65
100.0
75
20.8
95.9
69
106.1
75
23.7
98.9
68
111.2
80
24.1
103.0
71
124.4
92
25.3
116.3
83
131.6
99
26.0
123.4
90
142.8
103
33.9
135.7
94
148.9
108
34.4
140.8
99
164.2
121
35.8
156.1
112
173.4
130
36.7
165.2
119
174.4
124
42.2
165.2
114
180.5
130
42.9
171.4
119
198.9
146
44.7
188.7
134
209.1
154
45.8
198.9
142

TABLE 4
45C
Power
Input
kW
17.1
17.4
18.2
18.7
19.8
20.2
21.3
22.0
24.7
25.2
26.5
27.3
35.4
35.9
37.6
38.7
44.1
44.9
47.0
48.3

Heat
Rejection
kW
62.2
65.3
71.4
75.5
77.5
79.6
85.7
90.8
91.8
95.9
108.1
116.3
128.5
133.6
147.9
157.1
157.1
162.2
179.5
188.7

Cool
kW
42
44
50
53
50
53
60
64
60
64
73
81
86
90
102
109
104
108
122
131

YCRM-B COOLING CAPACITIES


Leaving
Chilled
Liquid
Temp
C
6
7
10
12
6
7
10
12
6
7
10
12
6
7
10
12
6
7
10
12

35

Flow Rate m/h

Cool
kW
54
57
63
67
66
69
77
82
85
89
101
108
112
117
132
140
135
141
157
167

40C
Power
Input
kW
15.5
15.7
16.3
16.6
18.2
18.4
19.2
19.7
22.6
22.9
23.9
24.4
32.3
32.7
33.9
34.5
40.2
40.7
42.2
43.1

Heat
Rejection
kW
69.4
72.4
79.6
83.6
83.6
86.7
95.9
100.0
106.1
111.2
124.4
131.6
142.8
148.9
164.2
173.4
174.4
180.5
198.9
209.1

Condenser Temperature
45C
Cool
Power
Heat
Input
Rejection
kW
kW
kW
50
16.4
66.3
52
16.6
68.3
59
17.3
75.5
62
17.7
79.6
61
19.0
79.6
63
19.3
82.6
71
20.2
90.8
75
20.8
95.9
75
23.7
98.9
80
24.1
103.0
92
25.3
116.3
99
26.0
123.4
103
33.9
135.7
108
34.4
140.8
121
35.8
156.1
130
36.7
165.2
124
42.2
165.2
130
42.9
171.4
146
44.7
188.7
154
45.8
198.9

Cool
kW
46
48
54
58
58
60
65
69
68
71
83
90
94
99
112
119
114
119
134
142

50C
Power
Input
kW
17.8
18.1
19.0
19.6
20.7
21.1
22.3
23.1
25.5
26.0
27.6
28.5
36.7
37.3
39.2
40.5
45.8
46.6
49.1
50.6

Heat
Rejection
kW
59.2
61.2
68.3
72.4
70.4
73.4
81.6
86.7
85.7
88.7
101.0
108.1
120.4
125.5
139.7
148.9
147.9
154.0
170.3
179.5

TABLE 5
50C
Power
Input
kW
17.1
17.4
18.2
18.7
19.8
20.2
21.3
22.0
24.7
25.2
26.5
27.3
35.4
35.9
37.6
38.7
44.1
44.9
47.0
48.3

Heat
Rejection
kW
62.2
65.3
71.4
75.5
77.5
79.6
85.7
90.8
91.8
95.9
108.1
116.3
128.5
133.6
147.9
157.1
157.1
162.2
179.5
188.7

Cool
kW
42
44
50
53
50
53
60
64
60
64
73
81
86
90
102
109
104
108
122
131

55C
Power
Input
kW
17.8
18.1
19.0
19.6
20.7
21.1
22.3
23.1
25.5
26.0
27.6
28.5
36.7
37.3
39.2
40.5
45.8
46.6
49.1
50.6

Heat
Rejection
kW
59.2
61.2
68.3
72.4
70.4
73.4
81.6
86.7
85.7
88.7
101.0
108.1
120.4
125.5
139.7
148.9
147.9
154.0
170.3
179.5

Page C.5
Doc. No. PC153/10.04/GB

PHYSICAL DATA

TABLE 6
YCWM-B/YCRM-B
Refrigerant Circuits
Refrigerant charge per circuit
Theoretical displacement
Compressor
Number
No. of cylinders
Revs per minute
Oil charge per compressor
No. of loading stages
Evaporator
Number
Water volume per evaporator
Water cooled
Number
Condenser (1)
Water volume per condenser
YCWM-B Weight
Operating
Shipping
YCRM-B Weight
Operating
Shipping
Length
Dimensions
Width
Height

kg
m/h

rpm
l
%
l
l
kg
kg
kg
kg
mm
mm
mm

60
2
2,3
39,8
2
3
2900
2,9
100-50
2
2,85
2
2,37
440
430
412
402
1210
758
1060

75
2
2,6
44,2
2
3
2900
3,1
100-50
2
3,32
2
2,85
450
440
422
412
1210
758
1060

90
2
4
58,2
2
6
2900
6,6
100-50
2
3,76
2
2,82
587
577
559
549
1210
758
1060

120
2
4,2
76,4
2
6
2900
6,6
100-50
2
5,64
2
3,76
600
590
572
562
1210
758
1060

150
2
4,7
88,3
2
6
2900
6,6
100-50
2
6,58
2
4,7
621
611
593
583
1210
758
1060

(1) YCWM-B only

ACOUSTIC DATA

TABLE 7

YCWM-B/YCRM-B
Sound Power (dB(A))

60
74

75
75

90
75

120
76

150
77

Tolerance 2 dB(A)

ELECTRICAL DATA
The following connections are required:

Supply cables should enter the unit via a hole provided at the
bottom of the panel.

One 400-3-50Hz supply plus earth for each power circuit.


Control interlocks if required.
The power connections and interlocks can be made to a single
terminal strip.

Model
Current
Input (A)
Power
Input (KW)

Nom. Cond.
Max. Cond.
Nom. Cond.
Max. Cond.

60
30
34
16
20

75
35
43
19
23

Mains isolator switches should be located adjacent to the unit


and should incorporate provision for locking in the off position.
Installation of differential safety cut-outs is recommended to
prevent damage due to phase failure.

YCWM-B/YCRM-B
90
45
52
23
29

120
64
73
33
41

YCWM-B nominal conditions at 7C chilled water outlet temperature, 35C condenser outlet temperature
YCWM-B maximum conditions at 12C chilled water outlet temperature, 50C condenser outlet temperature
YCRM-B nominal conditions at 7C chilled water outlet temperature, 40C condensing temperature
YCRM-B maximum conditions at 12C chilled water outlet temperature, 55C condensing temperature

Page C.6
Doc. No. PC153/10.04/GB

150
76
88
41
51

ELECTRICAL CONNECTIONS
UNIT TERMINAL BOARD

EXTERNAL TERMINAL BOARD

L1
L2

EXTERNAL EQUIPMENT TERMINALS


LINE
400-3-50

VOLTAGE FREE CONTACT

L3
UNIT ELECTRICAL TERMINALS
PE

FLOW SWITCH OR
EXTERNAL INTERLOCK

2
3

INTERLOCK
(OPTIONAL)
CIRC PUMP ETC

4
35

REMOTE INDICATION
VOLTAGE ON

36
5

(COMMON)

(NO)

GENERAL ALARM

10

(COMMON)

11

(COOLING)

12

(HEATING)

REMOTE ON/OFF
CONTROL

37
COMPRESSOR '1' ON
38
39
COMPRESSOR '2' ON
40
24

(COMMON)

25

(COOLING)

26

(HEATING)

REMOTE
INDICATION

SPACE REQUIREMENTS

600

600

600

600

1000

Page C.7
Doc. No. PC153/10.04/GB

DIMENSIONS
D
B

O
N

YCWM-B
EV 2

YCRM-B
EV 1

CD 2

EV 2

CD 1

EV 1

H
L

I
K

Note:
EV = Evaporator
CD = Condenser

YCWM-B
B

Evap.

Cond.

Pipe Conn.

Pipe Conn.

410 479 100 150

ISO-G 1"

ISO-G 1"

410 479 100 150

ISO-G 1"

ISO-G 1"

Model

60

1060

1210 758

20

500 278 479 500 500 500

75

1060

1210 758

20

500 278 479 500 500 500

90

1060

1210 758

26

555 286 456 510 538 555

420 456 100 150 ISO-G 1 1/2" ISO-G 1 1/2"

120

1060

1210 758

26

555 286 456 510 538 555

420 456 100 150 ISO-G 1 1/2" ISO-G 1 1/2"

150

1060

1210 758

26

555 286 456 510 538 555

420 456 100 150 ISO-G 1 1/2" ISO-G 1 1/2"

YCRM-B
Model

60

1060

1210 758

20

75

1060

1210 758

20

90

1060

1210 758

120

1060

150

1060

Page C.8
Doc. No. PC153/10.04/GB

Evap.

Ref.

Ref.

Pipe Conn.

Inlet Conn.

Outlet Conn.

100 150

ISO-G 1"

5/8"

7/8"

100 150

ISO-G 1"

5/8"

7/8"

100 150 ISO-G 1 1/2"

7/8"

1 1/8"

100 150 ISO-G 1 1/2"

7/8"

1 1/8"

100 150 ISO-G 1 1/2"

7/8"

1 1/8"

500 278 479 500 295 430

70

390

500 278 479 500 295 430

70

390

26

555 286 456 510 225 485

70

390

1210 758

26

555 286 456 510 225 485

70

390

1210 758

26

555 286 456 510 225 485

70

390

Dimensions in mm unless stated