Professional Documents
Culture Documents
Author
P. Johnson
Table of Contents
1
ND
1.5.11
Spreadsheet .......................................................................................................................................... 13
1.6
SELECTING INPUTS TO USE ............................................................................................................................. 14
1.6.1
Degrees of Freedom.................................................................................................................................. 14
1.6.2
Finding the Physical Properties of a Stream ............................................................................................ 14
1.7
DEALING WITH THE SPREADSHEET FUNCTION ................................................................................................ 16
1.7.1
Importing Information .............................................................................................................................. 16
1.7.2
Exporting Information .............................................................................................................................. 16
1.7.3
How to Find Help with Formulas ............................................................................................................. 16
1.8
USEFUL NOTES ............................................................................................................................................... 18
1.8.1
Colours of Items........................................................................................................................................ 18
1.8.1.1
1.8.1.2
1.8.1.3
1.8.1.4
1.8.1.5
1.8.2
Warnings................................................................................................................................................... 18
1.8.2.1
1.8.2.2
1.8.2.3
1.8.2.4
1.8.2.5
1.8.2.6
1.8.2.7
Overdefined ......................................................................................................................................................19
Calculation Error ..............................................................................................................................................19
Incremental Error..............................................................................................................................................19
Not Solved ........................................................................................................................................................19
Input not Valid..................................................................................................................................................19
Temperature Cross............................................................................................................................................19
Other Errors ......................................................................................................................................................19
B2
B3
Tabs
From this screen all of the workings behind the simulation may be assembled such as the
components or materials, fluids packages, Hypothetical components, reactions and others. These are
the key factors in any chemical process simulation. There is a list of tabs towards the bottom of this
window, which allow each different function to be explored. In order to return to this menu at any
time simply click on the Enter Basis Environment button (B2)
Lets start simple, click on the Add button (B3) then you will see another new screen pop up.
This is shown below in Figure 1-3.
At this screen it is possible to use the in built search engine for a material that will be used in the
simulation.
For the demonstration below air was chosen and added into the match box (R1). This found the
material in the list and the <--- Add Pure Button (B4) was pressed when air was selected. To
delete a component from the list just highlight the wring component and press the Remove --->
button (B5) and try again.
When you have finished, simply close the window. This may be done using the button at the top
right of the window (x).
NOTE: Air is a combined property set for an Oxygen/Nitrogen mixture. If oxygen is required define
the air as the multi-component system with Oxygen and Nitrogen. This is particularly important for
reactions such as combustion.
R1
B4
Close
List of
added
material
B5
List of
Materials
Next a fluid package must be selected. In order to do this we need to find the Fluids Package tab on
the basis manager screen (Figure 1-2). The screen should now look like Figure 1-4 below. From this
screen you are able to view any active fluids packages and create some new ones. To create a new
fluid basis, simply click the Add button (B6).
B6
Current
B7
The following window will appear once this is done. This can be seen below in Figure 1-5.
B7a
If you are unsure of which Fluids Package to choose, click on the Launch Property Wizard
Button (B7a). This will bring up a new window that looks like the one in Figure 1-6 below. Follow
the prompts until a few options are given to you. Commonly used packages are Peng-Robinson for
general purpose, ASME Steam or NBS Steam for water systems and PRSV or UNIQUAC for polar
mixtures such as Water/ Ethanol. There are a variety of Fluids packages in Hysys, their uses will be
discussed later in Section 4.
For now scroll down and select Peng-Robinson. Once
this is completed close this window. This will return you
to the Fluids package tab where your new fluids package
will be shown in the list.
B8
R2
B9
R4
R3
Figure 1-8:
Material Stream
Figure 1-9:
Energy Stream
These are usually placed from inside the operation that requires them. There are only a few
specifications that can be made in these. However these items are usually left alone and are
calculated from unit operations. The energy stream is used in two ways; finding the required energy
or the effects of a certain amount of energy, (temperature and pressure changes). The location is
shown as a RED arrow on the toolbar. (Figure 1-9)
Energy Flow
Inlet Delta P
Tank Geometry
Tank Type
Tank Volume
Reactions
Vapour Outlet Delta P
Heat Loss Type
Liquid Level (%)
The commonly used parameters are the Inlet and Outlet Delta P, Tank Type/Geometry and
reactions.
The Heater and cooler are simple in comparison to the heat exchanger units that Hysys has to offer.
These simple operations are important for initial heat exchange design of any plant. These functions
may be found where indicated on the right. Blue is cooler, Red is heater, (Figure 1-11). For later
stage design it is better to replace these couples with the Heat Exchanger unit, this is a much more
detailed of the heat exchanger with construction materials taken into account.
The available specifications for these units are listed below. It is better to define most of the
variables in external streams leaving only one variable left to be calculated.
Delta P
Delta T
Duty/ Heat
Heat Loss
Various other variables that are not necessary for 2nd and 3rd year Hysys
The most commonly used variables are the Pressure and Temperature change.
10
exchanger is to transfer heat efficiently from one stream to another. The heat exchanger function
simulates heat loss and transfer rates for sizing options and handles 2 stream sets; these are
described as the Shell and Tube sides. (The LNG heat exchanger handles multiple streams and has
complex design options such as layering).
These heat exchanger functions do detect temperature crossovers and will even warn when the Ft
Factor is too low. The heat exchangers design or configuration may be changed to fix this type of
error. In practice you do this by having 2 or more exchangers. For simplicity you can increase the
Tube Passes per Shell or change the Shell TEMA Type to F as an approximation to this.
NOTE: Ft Factors are a measure of heat exchanger design efficiency.
It is not recommended to alter any other parameters until they are understood, simply leave the
assumed figures. These other parameters will be discussed later on, usually during the CHNG 380x
courses.
1.5.6 Pump
The Pump unit operation is used for liquids or slurries only. There is a lot
you can do with a pump but we only want to concentrate on the basics for
now. In complex dynamic design you can model the pump curves and
motor efficiency. In the following examples we will go through how to
define a pump. The specifications that are available for simple calculations
are listed below. This unit operation may be located on the toolbar at the
indicated location. (Figure 1-12)
Delta P
Duty/ Power
Pump Curves
NPSH
11
1.5.9 Valve
The valve has limited uses in flow-sheeting, but is useful in Fluid Dynamics
and in a refrigeration cycle explained below in Section 3.6; apart from this the
valve is an important operation that is used in commonly in Dynamic mode,
primarily for control. The considerations for a simple valve are listed below.
The use of Relief Valve will be explained in Section 8. The valves are
located at the indicated position on the toolbar. (Figure 1-15)
Delta P
Valve Position
The valve position is assumed to be 50 % open.
1.5.10
Mixer/ Tee
Figure 1-15:
Simple Valve
These are very simple unit functions that combine and split streams.
Figure 1-16:
Mixer and Tee.
12
1.5.11
Spreadsheet
Figure 1-17:
Spreadsheet
13
14
15
To input a variable, click on the Add Import button located on the right hand side of the top
table. This will bring up the screen shown in Figure 1-20 below. There are multiple options on this
screen, so select the variable from left to right.
16
B10
17
1.8.2 Warnings
These are displayed in the status strip of an item screen and in the Object status list (R3) in Figure
1-7 above. A list of common warnings and solutions will be listed on the following page. As a rule
of thumb follow any instructions given by Hysys, or remove some specifications and start again.
This allows for the option of seeing where the problem stemmed and if specifications were not
needed. To avoid most complications either add in all of the operations and streams then connect
them up as start defining parameters, or add in the operations one by one and define the parameters
as you go along the lines.
18
1.8.2.1 Overdefined
This is when you have supplied too many specifications.
Solution
Remove at least one specified variable.
19
2.2.2
2.2.2.1
2.2.2.2
2.2.3
Valves........................................................................................................................................................ 26
2.2.3.1
2.2.3.2
2.2.3.3
2.2.3.4
2.2.3.5
2.2.3.6
2.2.4
Pipes with Heat Transfer .......................................................................................................................... 28
2.3
USING CASE STUDIES ..................................................................................................................................... 30
2.3.1
Using the Pipe as an example................................................................................................................... 30
PIPE TUTORIALS...........................................................................................................................................................31
2.4
PUMPS ............................................................................................................................................................ 39
2.4.1
Standalone Pumps..................................................................................................................................... 39
2.4.1.1
2.4.1.2
2.4.1.3
2.4.2
2.4.2.1
2.4.2.2
2.4.2.3
2.4.3
Pumping Curves........................................................................................................................................ 41
2.4.3.1
2.4.3.2
2.4.4
2.4.5
2.4.6
NPSH Inclusion......................................................................................................................................... 44
Pump Location.......................................................................................................................................... 44
Other Considerations................................................................................................................................ 44
2.4.6.1
Type of pump ...................................................................................................................................................44
PUMP TUTORIAL ..........................................................................................................................................................45
2.5
ENERGY BALANCES........................................................................................................................................ 46
2.5.1
Hysys Energy Balance .............................................................................................................................. 46
2.5.2
Heat Integration (Heater/ Cooler Couple) ............................................................................................... 46
2.5.3
Heat Exchangers....................................................................................................................................... 46
HEAT EXCHANGER TUTORIAL .................................................................................................................................48
2.6
MASS TRANSFER ............................................................................................................................................ 49
2.6.1
Introduction .............................................................................................................................................. 49
2.6.1.1
2.6.1.2
2.6.2
Absorber ................................................................................................................................................... 50
2.6.2.1
2.6.2.2
2.6.2.3
2.7
2.8
20
2.1.1 Streams
The following section will be a continuation from the example in Section 1.2.2. Streams are the
most used item in the program, and the easiest to manipulate. To use one simply add one to the
workspace and simply double click on it. This will bring up the following screen in Figure 2-1
below.
Define the system by the specifications below in Table 2-1, and then we can proceed. In order to
define the stream, try to follow the instructions in the yellow strip at the bottom of the window.
For this message, (Unknown Composition), click on Composition located in the menu on the left
of the box; this will bring up a new view in the same box; this is displayed in Figure 2-2 below.
Entering a fraction into one of the materials will bring up a dialogue box similar to the one shown in
Figure 2-3 located over page.
From this screen define the composition of the stream and type Enter or click OK to finish. You
will notice that a new message pops up, (Unknown Temperature), to define the temperature simply
click on the Conditions Menu item located at the top left of the window, this will bring up the
table shown below in Figure 2-1.
Insert a temperature of 25 oC, a new message will appear at the bottom of the window, (Unknown
Pressure), Insert 1 into the Pressure box and select atm from the drop down menu that appears,
this is shown in Figure 2-4 below.
Notice that Hysys will automatically change the units back into the standard SI units, which has
been set as default. The next message will say Unknown Flowrate; this is where things become
difficult. There are three (3) different possible flow options, enter 60 into Mass Flow to see what
happens. All of the undefined data will be calculated and that data will be filled in with black text.
NOTE: that all of the defined data is in Blue as shown below in Figure 2-5.
Table 2-1: The System Settings
Component
Fluids Package
Air
Peng-Robinson
21
Menu
Composition
22
2.2 Pipes
One of the first things you will notice at any chemical plant or building is the large number and
variety of pipes. Hysys is a very useful in performing calculations around pipes. There will be a
series of walkthroughs and tutorials that will assist in learning fluid mechanics subject material.
PIPE WORKSHOP
The process of finding the Reynolds number and frictional pressure drop is shown below. Firstly we
can do some hand calculations as shown in class. Work out the Friction Factor from a chart or
formula (Equation 2-1) and Reynolds Number (Equation 2-2) based on the following parameters in
Table 2-3. The next step is to work out the frictional pressure drop along the pipe. Remember there
are several different definitions of Friction factor that are used in different books. Hysys does not
give us a friction factor but it gives a friction profile along the pipe length.
Equation 2-1: Swamee-Jain equation for Friction
Factor
f =
0.25
2
5.74
log10 3.7 D + Re 0.9
where :
f = Friction Factor
= Absolute Internal Pipe Roughness
Re = Reynolds Number
D = Characteristic Length (Inside Diameter)
Table 2-2: The Hysys Setup
Components
Fluids Package
Water
ASME Steam
Re =
vD
where :
= Fluid Density
v = Fluid Velocity
D = Characteristic Length (Inside Diameter)
= Fluid Viscosity
Table 2-3: Data for hand calculations
Parameter
Value
Units
Density
1000
kg/m3
-3
Viscosity
1x10
Pa.s
Pipe Inside Diameter
26.64
mm
Pipe Outside Diameter
33.40
mm
Height Change
0
m
Pipe Length
10
m
Roughness
1.4x10-5
m
Flowrate
8
m3/hr
23
Table 2-4: The data to enter for the pipes pressure drop
Item
TAB/ Menu
Parameter
Value
Units
S-100
Worksheet/ Conditions
Temperature
25 oC
Pressure
1.5 atm
Vol. Flow
8 m3/hr
Worksheet/ Composition
Water
1
S-101
*Worksheet/ Conditions
Temperature
25 oC
*NOTE: This specification will be discarded once heat transfer is discussed. It will
be calculated with the heat transfer specifications defined.
Pipe-100
Design/ Connections
Inlet
S-100
Outlet
S-101
Energy
H-100
Rating/ Sizing
Fitting/Pipe
Pipe
Length
10 m
Elevation change
0 m
Material
Plastic Tubing
Rating/ View Segment
Pipe Schedule
40
(B12)
Available Diameters
25.4 mm
Increments
20
The information that may be difficult to enter from the table above is the sizing and segment
information; the following instructions will guide you through these.
These may be entered by clicking on the Append Segment button (B11) and then the segment
information on the left of Figure 2-6 may be entered. Do not enter the Diameters. To finalise the
pipe segment click on the View Segment button (B12), doing this will bring up the window on
the right. Enter the pipe schedule and the table at the base of the window will be filled out. Select
the top left value and click Specify (B13). From here the pipe should solve.
B11
B12
B13
Next we need to see the results for the pressure drop and other calculations that Hysys has
completed.
To do this, go to the Performance Tab, and then click on View Profile, this action will bring
up a new window filled with data that Hysys has calculated. Maximise this window and find the
relevant data such as Length, Liquid Re, Pressure, Friction Gradient and Liquid Velocity.
Re =120,000, Friction Gradient ~= 5.99 kPa/m, Liquid Velocity ~4 m/s. This window is
demonstrated below in Figure 2-7.
24
Notice that the number of rows or results is the same as the number of increments within the pipe.
Compare the Hysys Reynolds number, frictional gradient, pressure drop and liquid velocity
values to the ones you calculated.
Comment on how the pressure drop and flow calculations may be different from the ones
done by you.
Value
Units
Water
ASME Steam
25 oC
1.5 atm
1
25 oC
S-100
S-101
H-100
60 kPa
Pipe
10 m
0 m
Plastic Tubing
40
25.4 mm
20
25
2.2.3 Valves
This section will introduce the different types of valves, where to use them and why.
Most of this information will not be necessary until later when the design of valves is required.
2.2.3.2Gate Valves
Best Suited Characteristic: Quick Opening
Recommended Uses:
1. Fully open/closed, non-throttling
2. Infrequent operation
3. Minimal fluid trapping in line
Applications: Oil, gas, air, slurries, heavy liquids, steam, non-condensing
gases, and corrosive liquids
26
Advantages:
1. High capacity
2. Tight shutoff
3. Low cost
4. Little resistance to flow
Disadvantages:
1. Poor control
2. Cavitate at low pressure drops
3. Cannot be used for throttling
Disadvantages:
1. High pressure drop
2. More expensive than other valves
Disadvantages:
1. Poor throttling characteristics
2. Prone to cavitation
27
Advantages:
1. Low pressure drop
2. High capacity
3. Good flow control
4. Low cost and maintenance
Disadvantages:
1. High torque required for control
2. Prone to cavitation at lower flows
28
Nu = 0.027 Re 4p/ 5 Pr 1 / 3
w
Where :
B14
B15
B16
B17
0.14
Nu = Nusselt number
Re = Reynolds Number
Pr = Prandtl Number
0.7 Pr 16,700
Re 10,000
L/D 10
29
Then click on the Case Studies tab on the Data Book window. This should change the view to
the one at the base of Figure 2-12. From the new screen click Add then your variables will appear.
Select which variables are independent (the ones that you want to change) and the dependent
variables (the ones that are calculated- These usually have the independent box crossed/ shaded
out). Then click on View, located below the Add button. A new window should appear like the
one on the top half of Figure 2-12. Enter the low and high bounds on the independent variables,
including a step size, 5 to 10 steps is enough to start with, the step size can be narrowed with the
field later on. Remember the more steps there are the longer Hysys will take to find the values but
will give a smoother curve.
To finish up click on Start, Hysys will take a few seconds to calculate the case study.
To view the results, click on the Results button near the bottom left of the window.
This will bring up a table or a graph representation of the data in a new window. (Maximise this
window for the best view)
To switch between the two click the tabs at the base of this window.
PIPE TUTORIALS
For all of these pipe tutorials the only component will be Water and the fluids package is ASMESteam, there are no elevation changes, and assume no heat loss.
For all of these examples the schedule is 40.
System A simulates a straight piece of pipe.
System B simulates a pipe with a change in diameter and back
System C simulates the effects of bends and elbows
System D simulates Tees as bends and stream splitting.
System E simulates a simple Pipe Network
System F (not shown) simulates the different valves
Piping/ System Curves (Case Studies)
In this Tutorial we will be trying to find the friction factors and frictional pressure drop along a
length of pipe. Assume no temperature change for A and no heat loss for B and C (i.e. set heat
loss to zero (0) in the heat transfer menu).
Complete a series of calculations based on the Flowrate ( V& ) or Head Loss (h ). For system
v
B and C calculate the overall pressure drop and determine an average friction factor.
Have the outlet pressures at 1 atm, to allow for large pressure drops.
These relationships between head loss and flowrate will give the system curves.
Under different flowrates (4-52 L/min, step change 12 L/min) determine the theoretical head
loss using the relevant correlations and compare these with the values calculated by Hysys.
Use the table below to help you with this analysis.
Plot the head loss against the volumetric flow, (this may be done using the case study tool
for the simulation and excel for the calculated values).
Evaluate and discuss the trend/relationship.
NOTE: These are system curves which may be used for the pump systems and pump selection later
on.
NOTE: Some results may need the assistance of the spreadsheet functions
Give a discussion based on the head loss calculations and determining the friction factor.
31
1.4e-3
Set 3
Set 4
Set 5
16
28
40
52
1.4e-3
1.4e-3
1.4e-3
1.4e-3
1.4e-3
Set 3
Set 4
Set 5
16
28
40
52
1.4e-3
1.4e-3
1.4e-3
1.4e-3
32
NOTE: Remember to use the Coupling/Union segment for any multi diameter joints mentioned.
Have the internal diameter the same as the smaller pipe diameter
Table 2-9: Table of Answers for system 'C'
Parameter
Set 1
Set 2
Hysys Head Loss
hv (m)
Flow (L/min)
4
3
&
Flow V (m /s)
Flow Speed
v (m/s)
Pipe Roughness (mm)
Reynolds Number
Re
Pipe Friction Co-efficient
(Blasius Eqn.)
Pipe Friction Co-efficient
(Swamee Eqn.)
Calculated Head Loss
hv (m)
Difference in hv %
1.4e-3
Set 3
Set 4
Set 5
16
28
40
52
1.4e-3
1.4e-3
1.4e-3
1.4e-3
33
Tees
Plot the system curve (Flow 4-52 L/min) and compare the curve with the ones from A, B
and C.
Pipe Network
Discuss why the stream splits at Tee-100 are so narrow for the system to function. Use the
illustration above to help if required.
Change set the flow at 1000 L/min and run a study for the system curve on the inlet pressure
from 3.4 atm to 100 atm.
34
Valve Type
on
with
air
at
m/s.
35
TUTORIAL RESOURCES
Equation 2-4: The Pipe Tutorial Equation Sheets
Flow Speed
4V&
d 2
Pressure Loss
P pipe =
L pipe
2d
v12
P fitting =
v 2
= (VH )
Ptotal =
v2
2
pipe (i )
fitting ( j )
P pump +
(v12 v 22 ) + g (h1 h 2 )
NOTE : To Convert between Delta Head and Delta Pressure use the pressure equation.
P = gh
REYNOLDS' Number
Re =
vd
0.3164
4
Re
Colebrook Friction Factor
2.51
0.27
= 2 log 10
+
Re
Swamee - Jain Friction Factor
0.25
5.74
+
log 10
Re 0.9
3 .7 d
d 2 1 l 1 d 2 2 l 2
1 4
d d + d
d
v 22
1
1
1
2
=2
=2
Ptotal
Ptotal
v 22
2l 2
d2
Where :
= Absolute Internal Pipe Roughness
= Fluid Density
v = Fluid Velocity
VH = Velocity Heads
36
Table 2-10: VH's used by Hysys for fittings (Perrys Chemical Engineering handbook)
Type of Fitting or Valve
(VH), K
Type of Fitting or Valve
(VH), K
45 elbow,
Plug disk
Standard
0.35 open
9.00
Long radius
0.20 open
13.00
open
36.00
90 elbow
Standard
0.75 open
112.00
Long radius
0.45 Angle valve
Square or mitre
1.30 Open
2.00
1.50 Y or blow-off valve
180 bend
Close Return
1.50 Open
3.00
Tee
Plug cock
Standard, along run, branch blanked off
0.40 = 5
0.05
Used as elbow, entering run
1.00 = 10
0.29
Used as elbow, entering branch
1.00 = 20
1.56
Branching flow
1.00 = 40
17.30
= 60
206.00
Gate valve
Open
0.17 Butterfly valve
open
0.90 = 5
0.24
open
4.50 = 10
0.52
open
24.00 = 20
1.54
= 40
10.80
Diaphragm valve
Open
2.30 = 60
118.00
open
2.60 Check valve
open
4.30 Swing
2.00
open
21.00 Disk
10.00
Ball
70.00
Globe valve
Bevel Seat
Water meter
Open
6.00 Disk
7.00
open
9.50 Piston
15.00
Composition Seat
Rotary (star-shaped disk)
10.00
open
6.00 Turbine-wheel
6.00
open
8.50 Coupling
0.04
15.00 Union
0.04
Foot valve
37
38
2.4 Pumps
2.4.1 Standalone Pumps
For simple problems a pump may be used on its own. Give stream properties on either side of the
pump the system will solve. Firstly open up a Pump unit operation by placing one in the workspace
and double clicking on it. The view should be similar to Figure 2-15 below. There are a few
options that will create a solution in Hysys. Given 2 of the 3 variables it is possible to achieve the
other one. (POWER, FLOWRATE and DELTA P) Given an initial guess for an outlet or inlet set of
conditions such as temperature and pressure are required for an initial solution. The result is still the
same with these conditions changed.
Value
25
1
500
1
S-100
S-200
Q-100
75 %
2
Units
o
C
atm
kgmol/h
atm
39
Worksheet/ Conditions
Temperature
Pressure
25
1
C
atm
40
If you attach all of streams up and define the parameters from the pump to the pipe you will notice
the system will not solve. Disconnect the pump from S-101 and set the flowrate and temperature in
the pipe outlet stream (S-102). The pipe segment will now solve on its own. Re-connect up the
pump and the pump will now solve. Remove all but the pressure specification in S-100. This is so
that if you change a parameter the system will not be over-defined. This will also solve if you set
the flow and temperature outlet without disconnecting streams.
NOTE: There are several figures that are important for the ease of curve creation. These are Speed
RPM, Maximum efficiency, Flow and Head.
=
H2 N2
3
BHP1 N1
=
BHP2 N 2
=
H 2 D2
3
BHP1 D1
=
BHP2 D2
Where:
Q
= Capacity, GPM
H
= Total Head, Feet
BHP = Brake Horsepower
N
= Pump Speed, RPM
When the performance (Q1, H1, & BHP1) is known at some particular speed (N1) or diameter (D1),
the formulas can be used to estimate the performance (Q2, H2, & BHP2) at some other speed (N2) or
diameter (D2). The efficiency remains nearly constant for speed changes and for small changes in
impeller diameter. 2
Pump Affinity Laws, Perrys Chemical Engineering Handbook, Seventh Edition, 1997, Table 10-7, page 10-25
42
Three curves will be generated and their windows will open up, close these. To see where the
system has placed the operating conditions on the pump, click on Plot Curves, look for the
RED dot.
If no red dot is currently in the window. Check the Use Curves box and input a desired pump
speed, in the Pump Speed Box.
NOTE: The efficiency plot is parabolic. (Hysys has a tendency to mis-label curves)
43
44
PUMP TUTORIAL
1. To see the effects of flowrate and the system curves from Section 2.4.3.2 (Pump Curves) above
on a standalone pump with, change the flow either side of an assumed position (200 L/min) and see
if you can maximise the pumps efficiency. (use 1 to 1000 L/min with a step of 100)
You should plot the curves of Flow, Head, Efficiency and Power using a case study and save the
results.
NOTE: Viewing the pump curves with the operating point while the case study is running is a good
way to see the results effects.
2. Work out how many of the pumps defined above running at 435 rpm, in series or parallel, are
needed for 3 atm at the outlet (thats a pressure change of 2 atm) for 166 L/min.
NOTE: Do not define the outlet pressure, simply work out how many pumps are required for that
pressure change. SET THE FLOWRATE AND RPM.
What power requirement would be needed? What is the new efficiency? Comment on any
differences in power requirements. (HINT: Change the RPM in the curves menu. Then divide the
actual requirements by what you can achieve)
Comment on the significance of these results. (I.e. why does a small change in speed result in so
many more pumps being needed)
3. If we have a Pressure outlet Requirement of 3 atm what speed would the pump need to run at?
(HINT: using Q1 remove the Speed in the curves menu and set the outlet pressure)
4. Write down why NPSH is important and how to calculate it by hand. Try to find the NPSH
system boundaries for inlet pressure and flowrate. Remember no warnings will show in Steady
State mode.
5. In dot form write down where the effects of NPSH would be most prominent, i.e. what
applications of pumps does this problem most affect?
Hand the tutorial answers to the tutor at the end of the session.
45
NOTE: This bit gets confusing on occasion; the name of the Heater or Cooler is given based on
the stream they are acting on.
Once this has been done add in the material streams from the heater and cooler and only one energy
stream. Connect the common energy stream to both units. Then define the heater with air as the
only component water in the cooler. Set some inlet temperatures, pressures and flows (Heater: 25
o
C, 1 atm, 1 kgmol/hr) (Cooler: 80 oC, 1 atm, 1 kgmol/hr). Then set the units pressure drops to zero
(0). Setting one outlet temperature should solve the system (temperature Cooler out 50 oC).
Check that there are no poorly defined values. I.e. the temperature in the hot out is cooler than the
cold out/in. Then try the system again only set the cooler outlet temperature to 5 oC.
What is wrong with the system that Hysys will not acknowledge? (The second law of
thermodynamics is violated)
46
R6
R8
R7
R9
R10
R11
Insert some streams and move on to the Parameters page. A new view of the exchanger will appear
similar to the one below in Figure 2-21. Here it asks for pressure drop and UA (U is the overall
heat transfer co-efficient while A is the heat transfer area) information; ignore the UA for now. UA
will be handled later on in 3rd year Heat exchanger design; this is because UA is related to the
materials used and the sizing of the exchanger.
There are currently four options in the Heat Exchanger Model drop down menu these are:
Exchanger Design (Weighted); this model approach simulates multi phase systems such as a
condenser. This model can only handle single component systems and assumes counter current
flow only. No Ft factor is considered in this model.
Exchanger Design (End Point); this model approach simulates linear heat systems (i.e. no phase
changes), other assumptions are the overall heat transfer coefficient and specific heats on both sides
of the exchanger are constant throughout the system. This simulation uses the standard Heat
exchanger design equations.
47
Steady State Rating; this model is required for rating the system, this mode requires the geometry
of the exchanger. This model is based on the End point model with the same assumptions.
Dynamic Rating; This will not be used in this booklet. This has a considerable more amount of
detail for rating a heat exchanger than the Steady state option.
NOTE: Hysys does assume sizes so make sure these are defined correctly.
For this example keep the default value of Exchanger Design (End Point); these assumptions are
fine if there is no phase change. Just define the streams surrounding the Heat exchanger leaving
only one variable. Hysys will calculate the remaining values and sizing information. To find the
sizing and other calculated/defined parameters are found within the radio buttons located in the
Rating Tab, Sizing Menu, Sizing Options (top left drop down menu).
Trial 4
1 atm
2.5 kg/h
50 oC
40 oC
1 atm
1 kg/h
45 oC
0 kPa
Trial 5
35 oC
1 atm
25 kg/h
30 oC
-10 oC
1 atm
25 oC
0 kPa
Trial 6
80 oC
1 atm
2 kg/h
45 oC
25 oC
6 bar
10 kg/h
4 bar
48
2.6.1 Introduction
In this section we will be using Antoine as the Fluids Package.
Have n-Hexane and n-Heptane as the components; insert a material stream into the workspace.
Set the Pressure at 2 atm.
n-Hexane Composition 0.4
n-Heptane Composition 0.6
NOTE: DO NOT DEFINE THE TEMPERATURE.
NOTE: This Question may be found on page 9 of CHNG2802 Module 1 notes.
NOTE: ONLY DEFINE THE VAPOUR FRACTION WHEN AFTER THESE BUBBLE OR DEW
POINTS.
49
2.6.2 Absorber
This unit operation is used to simulate absorption. Examples of absorption are scrubbing and gas
cleaning.
R12
R13
Simply define the Inlet and outlet stream names and the number of stages (R12).
Click next> to continue to the next page, Figure 2-24, Define the pressures of the outlets (1 atm
for this example) and click next> again.
Figure 2-25 should appear. You do not need to fill in anything here so just click on Done. This
should bring up the overall screen shown in Figure 2-26. If the inlet streams have been defined the
system will solve.
NOTE: Always have the liquid stream at the top of the absorber with the gas stream at the base.
50
Change the number of stages to two (2) on the design connections page and hit the run
button at the base of the window. What effect did this have on the recoveries of the
ammonia in the outlet streams?
Now change the water flowrate to 1 kgmol/s. What effect did changing the flowrate have on
the ammonia recoveries?
51
You will recognise all of the features here from Section 1. From here you can add, change and
remove system parameters such as components, Fluid Packages and reactions (refer to the next
section).
52
1:1:0
1:8:1
8:1:1
1:1:8
2:2:1
3. Run a case study of the pressure (0.5-5.0 atm) on the system (i.e. each component vapour
compositions and bubble point temperatures).
4. Using an Absorber, determine the compositions of the outlet streams for an
Air/Ammonia/Water system using SOUR-PR as the Fluids package. Using the data already
in the table, fill out the missing data.
Table 2-18: Mass Transfer Air/Ammonia/Water Data Table
Item
Menu
Parameter
Value
Units
Item
T-100
Page 1
# of Stages
5
S-102
Page 2
S-100
Cond
Comp
Mol
fraction
S-101
Cond
Compn
Mol
fraction
Top Stage
Bottom Stage
Temperature
25
atm
atm
o
atm
Flow
kgmol/s
Water
Ammonia
Temperature
Pressure
Flow
Air
Water
Ammonia
25
1
1
0. 8
0
0.2
Comp
Mol
fraction
Pressure
Air
Menu
Condn
atm
kgmol/s
Value
Units
C
Pressure
atm
Flow
kgmol/s
Air
Water
Ammonia
S-103
Parameter
Temperature
Cond
Comp
Mol
fraction
Temperature
Pressure
atm
Flow
kgmol/s
Air
Water
Ammonia
53
B21
R12
B23
B22
B25
B24
From this screen it is possible to view reaction sets, components that are involved and associations
between fluids packages and reactions. To make life simple it is best to have appropriate names for
reactions and Groups of them.
Click on the Add Rxn Button (B21) and a new window will appear, Figure 2-30 below, asking for
what type of reaction you wish to define. These are to be chosen based on the reaction data that is
currently available; for this example select Conversion, and click on Add Reaction. Another
new window will appear, this looks similar to the one shown in Figure 2-31 below. Define the
parameters listed in Table 2-19 below to complete the reaction parameters; to add in each
component click on the **Add Comp** cell and scroll down the list until the desired item is
highlighted and click on it.
54
Location
Basis Tab
Variable
Basis Component
Co
Value
Methane
100
NOTE: It is also possible to size the reactor using the solving helpers like Adjust later on.
55
3.3
ITEM TABLES .................................................................................................................................................. 62
3.3.1
Viewing ..................................................................................................................................................... 62
3.3.2
Modifying .................................................................................................................................................. 63
3.4
GAS EXPANSION ............................................................................................................................................. 64
3.4.1
Isothermal Expansion ............................................................................................................................... 64
3.4.2
Adiabatic Expansion ................................................................................................................................. 64
Turbine TUTORIAL ........................................................................................................................................................65
3.5
POWER CYCLES .............................................................................................................................................. 66
3.5.1
Single-Stage Steam Rankine Cycle ........................................................................................................... 66
3.5.1.1
The Turbine ......................................................................................................................................................66
3.5.1.2
The Condenser..................................................................................................................................................66
3.5.1.3
The Pump..........................................................................................................................................................67
3.5.1.4
The Boiler.........................................................................................................................................................68
Single-Stage Rankine Cycle Tutorial ...............................................................................................................................69
3.5.2
3.5.3
3.5.3.1
Air Compressor.................................................................................................................................................71
3.5.3.2
Combustion Reactor .........................................................................................................................................71
3.5.3.3
Adding a Reaction to a Reactor ........................................................................................................................71
3.5.3.4
Turbine .............................................................................................................................................................72
SIMPLE BRAYTON (GAS) CYCLE TUTORIAL .........................................................................................................72
3.5.4
The Adjust Function.................................................................................................................................. 73
3.5.5
Regenerated Brayton Cycle ...................................................................................................................... 73
3.5.6
Combined Power Cycles ........................................................................................................................... 73
3.6
HYSYS STEADY STATE CONTROLS (SET/ADJUST/RECYCLE) .......................................................................... 74
3.6.1
SET............................................................................................................................................................ 74
3.6.2
RECYCLE ................................................................................................................................................. 74
3.7
REFRIGERATION AND AIR CONDITIONING ...................................................................................................... 74
3.7.1
Refrigeration............................................................................................................................................. 74
3.7.1.1
3.7.2
Domestic Refrigeration.....................................................................................................................................75
3.7.2.1
Evaporating and Condensing Pressures ............................................................................................................77
3.7.2.2
Discharge Temperature.....................................................................................................................................77
3.7.2.3
Toxicity ............................................................................................................................................................77
3.7.2.4
Flammability.....................................................................................................................................................78
3.7.2.5
Thermal Conductivity.......................................................................................................................................78
3.7.2.6
Inertness............................................................................................................................................................78
Refrigeration Tutorial.......................................................................................................................................................79
3.7.3
Air-Conditioning....................................................................................................................................... 80
3.7.3.1
56
Once this has been completed enter the simulation environment then the following steps may be
taken. Firstly you will notice a toolbar on the right of the screen. This is described above in the unit
operations section. Click on the Blue arrow. Then click somewhere on the blank workspace to place
the stream. Then Select the Compressor (Shown Above). Place this on the screen also. The
workspace should look similar to Figure 3-1 below.
From here double click on the Feed stream 1. A window will pop open displaying the possible
inputs for the stream properties. We only need to fill in a few of these to remove the degrees of
freedom for the system so far.
The parameters that will be used to remove the degrees of freedom are listed in Table 3-2.
57
Figure 3-2 shows that the stream is now dark blue instead of light blue as above in Figure 3-1
New Colour
Figure 3-2: The stream changes colour to show the stream is ready
Next are the Compressor properties. From the worksheet screen double click on the compressor.
This should be coloured RED this means that it has not yet been specified. The following screen
should appear (Figure 3-3). The following information should be entered on this screen. From here
we will also be creating streams. These are the Energy stream and Outlet stream. This is
another way of creating streams apart from the menu. This is demonstrated in Figure 3-3 to Figure
3-8. Each figure will be described in detail below.
Figure 3-3 shows that there are drop down menus for each of the stream options so that it is easy to
find the one that is required. Hysys will only give you the option of using unconnected streams
here.
Figure 3-4 shows that it is also possible to create streams from these connection screens. In order to
do so just click in the connection name box and type in the stream name that is required, and Hysys
will automatically create a stream for you. Do the same for the Energy stream.
58
Figure 3-5 shows what happens when you create streams from the compressor connections screen.
This is a much faster process than inputting the streams from the item toolbar. Notice that the
energy and flow streams are light colours and the compressor has a yellow outline. Now we need to
define either the compressors power capability or the outlet streams pressure. Figure 3-6 shows the
way to define the pressure from inside the stream properties screen. However this is not always the
best way to complete this task. In order to define the compressor completely and keep track of
errors it would be best to keep open the compressor window and define that property from in there.
This is demonstrated in Figure 3-7 and Figure 3-8 on the next page. There is no need to input a duty
number for any unit operation; its for Hysys to calculate, use another parameter such as pressure in
this case.
Go To
Worksheet tab
to see adjacent
items
properties
59
Figure 3-8 shows only one parameter (Pressure) is required to complete the stream. This is because
the compressor has completed the rest of the calculations for you; this includes any assumptions
that have been made. For example Hysys assumes that the compressor operates at an adiabatic
efficiency of 75 % and the motor specifications have also been filled in. These assumed values are
RED. Figure 3-9 shows the calculated values after the parameter was entered. Make a note that the
temperature has risen by over 50 oC. This is a significant temperature increase.
Try to duplicate this with hand calculations.
Inlet
Energy
Property
Outlet
60
COMPRESSION TUTORIAL
The previous example has covered simple single staged compression. The following example will
demonstrate staged compression with intermediate inter-cooling.
1. Assumptions:
Use an adiabatic efficiency of 100 % for this Question
a. A centrifugal air compressor takes 0.5 kg/hr of air at 22 oC to and 1 atm to 10 atm. What
would be the power requirement for a single stage compressor to achieve this?
b. If a two stage compressor with intermediate cooling back to 40 oC is used for the same
compression (1-10 atm), what is the minimum power (kW & hp) required assuming the
intermediate pressure is 3 atm?
c. Compare the power requirements of the part a and b and comment especially on the
two outlet temperatures.
d. Run a case study on the effects of the intermediate pressure (1.1-9.9 atm) on outlet
temperature. Discuss the trend and results, where they expected?
2. Repeat question 1 with an adiabatic efficiency of 75 %.
3. Carbon Dioxide is to be compressed from 1 bar, 25 oC to 5 bar.
a. Compare the work needed using a single reversible, adiabatic compressor to twostage compression with inter-cooling. The inter-stage pressure is 2.25 bar; intercooling is to 40 oC.
b. What are the exit temperatures in both cases and why would they vary if at all?
61
3.3.1 Viewing
Figure 3-10 shows how to access the tables on the workspace screen. This eliminates having to
open up each item to see what the values are. This is useful if you are constantly changing the
inputs and are trying to determine the effects. Figure 3-11 shows all of the available tables for this
example. There are a variety of different tables that show similar values. Some of these numbers
can be changed to different units such as the flowrate may be changed to mass flow units such as
kg/h.
To get these tables to appear right click on the object that you wish to view. Scroll down the list to
Show Table and select that option. The table should appear in the workspace.
62
3.3.2 Modifying
In order to view different types of information available in Hysys in these tables a quick
modification step may take place. This is as follows:
Right click on a table
Select View Properties
Click Add Variable
Select the Variable you desire
If there are any further specifications select the one you wish
Click on OK
From here you can name the selected item
Close the window
These steps are illustrated in Figure 3-12 to Figure 3-14 below.
63
We now need to see some results. For this we will need to modify the item tables.
Insert the Actual Volume Flow Variable to the table as above. This then allows for a quick view
of the volume change over the expander.
NOTE: This example is unrealistic and will not work in practice due to the fact that work is done
by the system, this means that heat will need to dissipate. It is impossible to build a perfectly
isothermal device due to the large surface area that would be required along with frictionless
parts. This application should never be used for design or scoping calculations in Hysys. Use the
Adiabatic Expansion example to give a better estimate.
64
Now insert an expander onto the workspace and enter the relevant information into these forms.
These are listed below in Table 3-5 above.
The Expander should now solve. Have a look around at the options that are the set standards for the
expander. Changing some of these will give different circumstances, and solutions to the problem.
Final temperature should be 122.3 oC
NOTE: Like the Pump and Compressor the efficiency is assumed to be 75 %.
TURBINE TUTORIAL
1. From the Expander defined above in Section 3.4.2, run a case study on the effects of
adiabatic efficiency (0-100 %) on the outlet temperature of the system.
2. Insert a second expander with an intermediate re-heater. Set the intermediate pressure to 4
atm, and the re-heater outlet temperature of 250 oC.
3. What is the effect on the outlet temperature (percentage difference) and power production
(sum of K-xxx) in comparison to part 1?
4. Run separate case studies of the intermediate pressure (1.5-4.5 atm) on inlet and
intermediate temperature (250-500 oC) while the inlet temperature is at 500 oC, on the Outlet
Temperature and Power production. Where the results expected? (i.e. do they match up with
hand calculated answers)
65
One this has been completed you will see the fully defined Turbine above in Figure 3-15.
66
Value
S-101
S-200
S-104
S-201
Units
0
0
None
22
1
1
30
0
kPa
kPa
o
C
atm
o
The vapour fraction is required in this example so as to specify that there is no vapour entering into
the next operation (the pump); this is the function of a condenser. The design of the condenser
should result in no vapour going into the pump with system disturbances taken into account. In
practice a set temperature of sub-cooling would be required to allow for disturbances in a real
system something along the lines of 5-10oC. To test this out set the temperature lower in this stream
after the cycle has been completed to see the effects.
Once this has been done the workspace should resemble Figure 3-16 below.
Value
S-104
S-105
Q-102
63
70
Units
%
bar
NOTE: That the work load for a pump is significantly lower than that of a compressor/ turbine
(~0.03). This is essential for the system to produce electricity.
The product should look like that in Figure 3-17 below.
67
From here it is possible to rearrange the parts to make a cleaner representation of the cycle. Right
clicking on the items and rotating the parts from the Transform menu will allow for a cleaner
representation such as the one in Figure 3-19 below. It does not matter if the loop is clockwise or
anti-clockwise.
68
From here define the following parameters on parts as listed in Table 3-9 below.
Table 3-9: The Extra Parameter definitions
Item
Parameter
S-101
Pressure
E-102 (Design/Parameters)
Delta P
S-102
Temperature
K-101 (Design/Parameters)
Adiabatic Efficiency
S-103
Pressure
Value
200
0
550
53.6
1
Units
psia
kPa
o
C
%
atm
The system should now be completely solved. Note down any major results on the parameters listed
below and comment on the differences to the single stage steam cycle.
Total power out
Cooling water flowrate
Temperature in the stream before the condenser
Total Heat required in the system (H-100+H-101)
Efficiency: (Q-100+Q-101-Q-102)/(H-100+H-101)
69
An easy way to comment on the differences is to create a spreadsheet and do some simple
calculations on the Maximum Efficiency, Thermal Efficiency (Net energy out/Heat in) and outlet
Power. The easiest way to compare is to have both systems in the same workspace. Make sure the
variables heading in to the cooler are consistent for both systems.
The final view may look like Figure 3-21 below. I have labelled the single system as stream set 3.
To get the streams to have the colour scheme similar to that is shown below, change the scheme to
Temperature at (R12).
R12
Figure 3-21: The comparison Between Single and Multi Turbine Rankine Systems
70
Value
25
1
1300
5
85
Units
C
atm
kgmol/hr
atm
%
o
Insert the reactor into the workspace, open up the reactor. Add in the
required connections. Now we need to add in the reaction to the reactor. If
the reaction was defined correctly and added into the current fluids
package then this step will be quite simple. Refer to Section 2.8 (Simple Reactions) above for a
refresher. Firstly open up the reactor screen, then go to the Reactions tab Details menu. From
the Reaction Set drop down menu select the reaction set. This is usually Global Reaction Set-1
if there is only one reaction set. If you have named the reaction set, that is what you should find.
The reaction is now ready to proceed.
71
Table 3-11 below has the specifications for the reactor that are required for this example.
Table 3-11: The Parameters for the Conversion Reactor
Item
Parameter
S-101
Vapour/ Phase Fraction
Pressure
Flow
CRV-100 (Design/Connections)
Inlets
Vapour Outlet
Liquid Outlet
CRV-100 (Design/Parameters)
Delta P
Liquid Level
Value
Units
0.000
6 atm
33 kgmol/hr
S-101, S-103
S-104
S-000
0 kPa
0 %
3.5.3.4 Turbine
The pressurised combustion gases are expanded in the turbine. The turbine creates the electricity.
The parameters are listed below in Table 3-12.
Table 3-12: The Turbine Specifications
Item
Parameter
S-102
Temperature
Pressure
Flow
S-103
Pressure
K-101 (Design/Parameters)
Adiabatic Efficiency
Value
25
1
315
5
85
Units
C
atm
kgmol/hr
atm
%
o
Once this has been completed the Hysys workspace should look similar to Figure 3-23 below.
Initially the Combustion outlet temperatures (S-104) are excessive (2,109.4 oC). Most materials
cannot handle this kind of temperature range. This problem may be fixed by changing the flowrate
of air to extreme excess. Approximately 351 kgmol/hr is sufficient to reduce the outlet temperature
to a workable 1100 K which is below the safety limitations for most common steels.
72
Units
Figure
3-24:
The location of
the
Adjust
function
K
kgmol/h
kgmol/h
73
3.6.1 SET
This sets a variable of a stream to be the same or in a ratio to another one. For example if you have
2 flowrates that need to be solved simultaneously but you know that one is 3 times larger than the
other one. Insert the Set Unit (S in a green diamond, right of the Adjust function)
Set the Target variable and the source of the solved variable.
On the Parameters tab you can set the ratio of the two parameters with any offset.
3.6.2 RECYCLE
Like the Adjust function this is an iterative solver. (R in a green diamond, far right of the Adjust
function) Whenever there is a change in composition in a cycle this is to be used. Simply attach a
Recycle unit into a returning stream. Set an initial guess for the outlet of the recycle (usually the
other inlet) and let the solution come. Make sure the initial run solves before linking the recycled
stream back, and check that any inert material is mostly removed from the recycling stream.
NOTE: The recycle may not converge if there is complete recycle or an accumulation within the
circuit, i.e. recycling of an inert gas that is also in the feed stream, this system will need a purge
stream.
3.7.1 Refrigeration
Refrigeration is a complex process which has several considerations that need to be addressed
during the process of design. These include:
Safety
Refrigerant selection
Pressures
Flammability
Temperatures
Toxicity
Thermal expansion
Leakage direction
The general form of Refrigeration is:
Evaporation This process is where the refrigerant evaporates and takes in the energy from
the surroundings. (INSIDE)
Superheat This is to ensure that the refrigerant wont condense in the compressor
Compression Compressing the gas to a higher pressure and temperature for condensation
Condensation This is where the refrigerant is cooled down using a cooler environment
than the one it is currently in.(OUTSIDE)
Throttling/ Expansion The now higher pressure fluid expands through a valve (capillary)
to the start of the cycle at much lower pressures. (cooling the fluid down further)
74
75
Fluids Package
T-S-T
Peng-Robinson
Component
R134a
Air
Parameter
Tube side Basis
Shell Side Basis
Tube side Delta P
Shell Side Delta P
Temperature
Adiabatic Efficiency
Tube Side Delta P
Vapour Fraction
Temperature
Temperature
Pressure
Value
Basis-1
Basis-2
0
0
2
65
0
0
100
30
1
Units
kPa
kPa
o
C
%
kPa
o
F
C
atm
Handbook of Air conditioning and Refrigeration, Second Edition, by Shan K. Wang, pg 9.8-9.11
Published by McGraw-Hill 2001
76
Refrigeration Capacity
Oil Miscibility
Di-electric Properties
Leakage detection ability
Ozone Depletion Potential
3.7.2.3 Toxicity
Due to the high pressures involved in the refrigeration systems the problem of leakage is evident4.
Since leakage is almost inevitable in older or more warn systems toxicity of the leaked gas is an
important consideration to take into account. Refrigerants need to be safe enough to use without
causing too much discomfort. In the ANSI/ASHRE Standard 34-1997, the toxicity of refrigerants is
classified as class A or B. Class A having very low toxicity in terms of exposure while class B have
exposure limitations.
77
3.7.2.4 Flammability
In the ANSI/ASHRE Standard 34-1997 there are 3 classes of refrigerants in terms of flammability4.
NOTE: Safety Groups are classified as (Toxicity class letter), (Flammability class number). I.e.
Classification A2 has lower toxicity with a low flammability.
3.7.2.6 Inertness
Inert refrigerants are preferred due to the lower maintenance requirements for internal corrosion and
damage4.
78
REFRIGERATION TUTORIAL
1. Define the following simple refrigeration cycle.
Unit
S-100
E-100
S-102
Q1
K-100
E-ATM2
S-104
S-ATM5
Parameter
Temperature
Basis
DeltaP
Temperature
Heat Flow
Adiabatic Efficiency
Shell Side Delta P
Tube Side Delta P
Vapour Fraction
Temperature
Pressure
Tempearture
Flow
Air-Composition
Value
10
Basis-1
0
20
12,000
65
0
0
0
100
1
33
5
1
Units
o
F
kPa
o
F
BTU/hr
%
kPa
kPa
o
F
atm
o
C
m3/hr
mol frac
Remove the heat specification in Q1. Insert a spreadsheet function, have the import as Q1 Heat
flow. In the cell directly below the import enter the formula:
= (import cell)/ 12000 (BTU/hr)
For the units that Q1 are in you will need to convert back to instead of the 12000
This is to work out how much ice at 0 oC we can make in tonnes per day.
How much refrigerant will it take to make 30 kg of ice a minute?
2. What other sets of specifications would solve the system for an unlimited range of flows for the
refrigerator?
Remember any system limitations such as there is to be no liquid entering the compressor and that
overlapping temperatures (around the heater, water is flowing/freezing there) are not realistic.
79
3.7.3 Air-Conditioning
3.7.3.1 Domestic Air Conditioning
A common type of air conditioning in house-holds is known as a heat pump and can be a ReverseCycle Air-conditioner. This essentially means that the flow of the refrigerant through the
exchangers is reversed and sends the heat in the other direction. For most simple refrigerator
systems the throttle is a capillary valve in other words the tube diameter gets very small and then
enters into another tube of significantly larger diameter. However this type of valve is not suited to
heat pumps as having the flow in the wrong direction will simply ruin such the valve. In order to
stop this from happening there are two generic solutions. Have a single diameter pipe all the way
through the system with an electronically controlled valve to control the pressures. The other option
is to have a secondary system around the valves. The general system in Hysys is illustrated below in
Figure 3-27, A shows the summer cycle, while B shows the winter cycle. This figure is
accompanied by Figure 3-26 which shows the schematics.
To define the heating half of the system, simply copy the cooling system from above but have the
flow in the reverse direction. The parameters for both of the systems are listed below in Table 3-16.
NOTE: Heaters and cooler couples may also be used when building these cycles.
80
Parameter
Temperature
Composition
(R-134a)
Temperature
Temperature
Vapour Fraction
Temperature
Pressure
Flow
Composition
(Air)
Temperature
Temperature
Pressure
Flow
Adiabatic
Efficiency
Delta P Shell
Delta P Tube
Delta P Shell
Delta P Tube
Value
-20
1
-10
100
0
24
1
4
1
28
4
1
5
65
0
0
0
0
Units
F
C
atm
kg/hr
o
C
C
atm
kg/hr
o
kPa
kPa
kPa
kPa
Calculate the co-efficient of performance (COP). This may be done by using the following
ideas:
1kW used in the compressor will give how many kW of heating (heating efficiency) and
cooling (cooling efficiency).
Or
81
4.3.2
4.3.2.1
4.3.2.2
4.3.2.3
4.3.2.4
4.3.2.5
4.3.2.6
4.3.3
4.3.4.1
4.3.4.2
4.3.4.3
4.3.5
Semi-Impirical Methods............................................................................................................................ 89
4.3.3.1
4.3.3.2
4.3.4
Antoine .............................................................................................................................................................90
Braun K10 ........................................................................................................................................................90
Esso Tabular .....................................................................................................................................................91
Miscellaneous ........................................................................................................................................... 91
4.3.5.1
4.3.5.2
4.3.5.3
4.3.5.4
4.3.5.5
4.3.5.6
4.3.5.7
4.4
BAD THERMODYNAMIC PACKAGE EXAMPLES ................................................................................................ 93
4.4.1
Combustion in UNIQUAC ........................................................................................................................ 93
4.4.2
3-Phase Separator Case Study with multiple-polar components .............................................................. 93
82
The basics of package choices, more information on operational conditions and functionality are
described below.
The equations of state (EoS) models, such as the Peng Robinson model, were developed originally
to deal with hydrocarbon gas systems. Although they have proven to be very reliable in predicting
properties of most hydrocarbon based fluids over a large range of operating conditions, their
application has been limited to primarily non-polar or slightly polar components. Polar or non-ideal
chemical systems have traditionally been handled using dual model approaches. In this approach, an
equation of state is used for predicting the vapour fugacity coefficients, (normally ideal gas
assumption or the RK, PR, or SRK equations of state), and an activity coefficient model is used for
the liquid phase.
However, whether an activity coefficient model can be used in a specific case depends heavily on
the pressure involved in your simulation. These models cannot be used in a generalized way or
extrapolating into untested operating conditions. Their tuning parameters should be fitted against a
representative sample of experimental data and their application should be limited to moderate
pressure. Consequently, more caution should be exercised when selecting these models for your
simulation.
If the operating pressure in your simulation is too high for activity coefficient models, an equation
of state method will become the only applicable approach. In the case that your system exhibits
some degree of non-ideality, you can consider using the modified PR model, called PRSV. With an
additional component dependent parameter and a more flexible mixing rule, this model has
extended the applicability of the original PR model to moderately non-ideal systems.
These are just some general guidelines in selecting property packages. More detailed information on
different property packages and their applicabilitys can be found below.
NOTE: If there is only water, use the steam table packages. These and other specialty packages are
described in Section 4.3.5.
83
84
Each type of model fits different conditions. Within these categories there are basic fluids packages
and modified versions of some of these.
Base Packages:
GCEoS
Lee-Kessler Plocker
Peng-Robinson
SRK
BWRS
TST
Modified versions of EoS packages in Hysys:
PR-Twu
PRSV
Sour PR
SRK-Twu
Sour SRK
Kabadi Danner (KD)
Zudkevitch Joffee (ZJ)
This Type of Package is used in near ideal situations such as high pressure fluids (ideal gases are
assumed to have a large specific volume, the enthalpy of the fluid is assumed to be independent of
the density) or liquids, these packages are limited in functionality and the limits need to be
considered. The recommended starting packages are:
85
For Oil, Gas, or Petrochemical applications, the PR EoS is the generally recommended property
package.
The SRK EoS should not be used for non-ideal chemicals such as alcohols, acids or other
components. These chemicals are more accurately handled by the Activity Models (highly nonideal) or the PRSV EoS (moderately non-ideal).
In General it is better to use the PR property package as a starting point.
4.3.1.7 PR-Twu
The PR-Twu property package is based on P-R and incorporates the Twu EoS Alpha function for
improved vapour pressure prediction of all HYSYS library components.
4.3.1.8 PRSV
The PRSV model extends the application of the original Peng-Robinson method for moderately
non-ideal systems. This EOS is shown to match vapour pressures curves of pure components and
mixtures more accurately than the PR method, especially at low vapour pressures. It is successfully
extended to handle non-ideal systems giving results as good as those obtained using excess Gibbs
energy functions like the Wilson, NRTL, or UNIQUAC equations.
The advantages of the PRSV equation are:
It has the potential to more accurately predict the phase behaviour of hydrocarbon systems,
particularly for systems composed of dissimilar components.
It can be extended to handle non-ideal systems with accuracies that rival traditional activity
coefficient models.
The only compromise for PRSV equation of state is the increased computational time and the
additional interaction parameter that is required for the equation.
The PRSV equations of state perform rigorous three-phase flash calculations for aqueous
systems containing H2O, CH3OH or glycols, as well as systems containing other hydrocarbons
or non-hydrocarbons in the second liquid phase.
4.3.1.9 Sour PR
The Sour PR model combines the Peng-Robinson equation of state and Wilson's API-Sour Model
for handling sour water systems and can be applied to sour water strippers, hydrotreater loops,
crude columns, or any process containing hydrocarbons, acid gases, and H2O.
In the Sour PR model, the K-values for the aqueous phase are calculated using Wilson's API-Sour
method. This option uses Wilson's model to account for the ionization of the H2S, CO2, and NH3
in the aqueous water phase.
NOTE: The flash calculation is much slower than the standard EOS because the method performs
an ion balance for each K-value calculation.
4.3.1.10 SRK-Twu
The Soave-Redlich-Kwong-Twu (SRK-Twu) property package is based on SRK property package
and incorporates the Twu EoS Alpha function for improved vapour pressure prediction of all
HYSYS library components. This package uses the SRK method to calculate VLE and the SRK or
Lee-Kesler method to calculate Enthalpy and Entropy.
4.3.2.2 Wilson
The Wilson equation offers a thermodynamically consistent approach to predicting multicomponent behaviour from regressed binary equilibrium data.
However, the Wilson model cannot be used for systems with two liquid phases.
The Wilson equation gives similar results as the Margules and van Laar equations for weak nonideal systems, but consistently outperforms them for increasingly non-ideal systems.
88
Unlike the van Laar equation, NRTL can be used for dilute systems and hydrocarbon-alcohol
mixtures, although it may not be as good for alcohol-hydrocarbon systems as the Wilson
equation.
NOTE: Due to the mathematical structure of the NRTL equation, it can produce erroneous multiple
miscibility (LLE) gaps.
4.3.2.4 Margules
The Margules model equation does not have any theoretical basis, but is useful for quick estimates
and data interpolation. HYSYS has an extended multi-component Margules equation.
NOTE: The equation should not be used for extrapolation beyond the range over which the energy
parameters are fitted.
4.3.2.5 UNIQUAC
The UNIversal QUAsi Chemical (UNIQUAC) equation is capable of representing LLE, VLE, and
VLLE with accuracy comparable to the NRTL equation, but without the need for a non-randomness
factor.
The UNIQUAC equation has a good representation of both VLE and LLE can be obtained for a
large range of non-electrolyte mixtures.
The UNIQUAC equation utilizes the concept of local composition as proposed by Wilson. Since the
primary concentration variable is a surface fraction as opposed to a mole fraction, it is applicable to
systems containing molecules of very different sizes and shape, such as polymer solutions. The
UNIQUAC equation can be applied to a wide range of mixtures containing H2O, alcohols, nitriles,
amines, esters, ketones, aldehydes, halogenated hydrocarbons, and hydrocarbons.
89
Antoine
Braun K10
Esso Tabular
4.3.4.1 Antoine
The Antoine model is applicable for low pressure systems that behave ideally.
Antoine property package is applicable to the following ranges:
Temperature
Press (psia)
Press (kPa)
<1.6 Tci *
<100
<700
* Tci is the components Critical Temperature.
When using this method for super-critical components, it is recommended that the vapour pressure
coefficients be replaced with Henry's Law coefficients. Changing Vapour Pressure coefficients can
only be accomplished if your component is being installed as a Hypothetical.
90
4.3.5 Miscellaneous
The Miscellaneous group contains Property Packages that are unique and do not fit into the groups
previously mentioned.
MBWR
Amine Pkg
ASME Stream
DBR Amine Package
NBS Stream
OLI_Electrolyte
Glycol PPkg
option with HYSYS giving you access to a proven third party property package for reliable amine
plant simulation, while maintaining the ability to use HYSYS' powerful flow sheeting capabilities.
The amines property package is fitted to extensive experimental data gathered from a combination
of D.B. Robinson's in-house data, several unpublished sources, and numerous technical references.
The Amines method does not allow any hypotheticals.
The absorption of H2S and CO2 by aqueous alkanolamine solutions involves exothermic reactions.
The heat effects are an important factor in amine treating processes and are properly taken into
account in the amines property package.
92
Value
25
11
1300
0.1
0.2
0.7
Units
o
C
bar
kgmol/hr
S-100
S-101
N-100
Basis-1
0
0
kPa
%
Set-1
Combust-1
Notice any major problems with the reactor temperature or exiting streams (S-101, N-100).
Now change the package to one that works for these conditions (use the Wizard).
The actual reactor temperature for this example should be around 2126 oC and there should be no
liquid flows. (Hence the N-XXX stream name)
93
The actual answer for the correctly defined system is shown in Table 4-3 below.
Table 4-3: The Correct result for the problem above (Found using PRSV)*
Mol Fraction
S-100
S-101
S-102
S-103
0.2
0.0274
0.1374
0.2966
Ethanol
0.2
0.0105
0.0004
0.3665
Water
0.2
0.0568
0.0202
0.3366
Methanol
0.2
0.0015
0.9403
0.0003
Methane
0.2
0.8009
0.0015
0.0000
n-Decane
Total (L/min)
1.0
0.1547
0.5686
0.2767
94
5.1
ADDITIONAL 2 YEAR HYSYS UNIT OPERATIONS ......................................................................................... 96
5.2
PHASE SEPARATORS ....................................................................................................................................... 96
5.2.1
Separator (2 Phase) .................................................................................................................................. 96
5.2.2
Separator (3 Phase) .................................................................................................................................. 96
5.3
BASIC DISTILLATION CONCEPTS (COMPONENT SPLITTER) ............................................................................. 97
SEPARATION WORKSHOP ..........................................................................................................................................98
SEPARATION TUTORIAL ............................................................................................................................................99
5.4
95
96
Figure 5-1:
The Location
of the
Component
splitter
This is an over simplified version of a separation operation. However, this has its
advantages in that it can loosely simulate operations such as distillation,
molecular sieves and membrane facilities. It is good for flowsheeting for mass
balances over a separation system. Take these factors into consideration when using this operation.
Since this is relatively complex in comparison to the separators that have been used up till now, we
will do an example together to help our understanding of the systems and defined variables that are
available.
NOTE: The distillation section of the toolbar is found below the unit operation section. The
columns look like Es.
97
SEPARATION WORKSHOP
Set up the system with Water, Ethanol as the components. Set the Fluids package to PRSV or
UNIQUAC. Insert a component splitter into the workspace. Add in the streams and no energy
stream for this application.
For the inlet conditions it is usually set that the temperature is slightly above that of a saturated
liquid (i.e. set the vapour phase fraction to zero, 0, or just above it 0.05). Initially set the pressure to
1 atm, 2 kg/min and the inlet composition to 20 % ethanol, 80 % water.
The splitter will now need to know the required splits for the system. These can be entered in the
Design tab, Splits menu. Set the splits to 99 % ethanol and 5 % water in the overhead outlet.
The other stream will solve.
REMEMBER: Splits are not compositions; they are more of a recovery than a concentration.
NOTE: Setting the splits to 100 % is possible in Hysys but this is highly unrealistic for most
applications. It is possible to violate azeotropes using the component splitter; this is because the
splitter can simulate complex separations such as molecular sieves in separation efficiency;
however with that operation the temperature is not as important.
After this Hysys will ask for an Overhead Pressure this may be solved in a variety of ways, all of
which may be completed from the Design tab, Parameters menu.
In this menu there are several options available to change the solving method for the splitter, these
are:
1) Use Stream Pressure Specifications, (P) this is the default selection.
(all pressures will need to be defined here)
2) Equalise all Stream Pressures, (P) this is to be used if there is no pressure drop through the
system (useful for atmospheric columns)
(Only one pressure specification will need to be defined [Feed] and at least 1 outlet
condition)
3) Use Stream Flash Specifications, (T) this is the default selection. At least one temperature
must be defined.
4) Set lowest feed pressure for all product streams (equalise in Dynamics mode), (P) this is
the same as 2) for all of our applications. (This mode is not recommended for use at any
time, it is difficult and beyond the scope of any of our work)
5) Calculate Equal Temperatures, (T) this option sets the temperatures of the outlets as the
same. (This mode is not recommended for use at any time because it is unrealistic)
For this example we will define no pressure change (option 2) and a no vapour out of the Bottoms
(Vapour fraction = 0).
Perform a mass balance over the Splitter to mimic the results.
98
SEPARATION TUTORIAL
1. Effect of Pressure
a. Run a case study on the effects of pressure (0.1-3.1 atm) on a water-ethanol system
described in the worked example above.
b. When does the overhead stream temperature drop below 60 oC and when does the
bottoms stream temperature go above 110 oC?
Table 5-1: The Separation Tute Q1 table
0.1
0.6
Pressure (atm)
Temperature Overhead
Temperature Bottoms
1.1
1.6
2.1
2.6
3.1
2. Determine the effect of changing the feed composition (Ethanol 0.05, 0.2, 0.4, 0.6, 0.8, 0.95 mol
fraction) on the system used in Question 1. Set the pressure at 1 atm. What do you notice about the
temperature ranges?
NOTE: You will not be able to run a case study on this which means that the composition will need
to be changed each time.
Table 5-2: The Separation Tute Q2 table
0.05
Ethanol (mol. frac.)
Temperature Overhead
Temperature Bottoms
0.2
0.4
0.6
0.8
0.95
To define the Air Cooler simply add in the inlet and desired outlet stream properties. From here it is
quite simple. Set the configuration of the exchanger on the Design Tab, Parameters menu to the
desired configuration. In general the greater the Delta T, the more passes that are required while the
greater the flowrate the more tubes that should be used.
NOTE: Calculating the flow and tube length limits are essential in later design, this is because
Hysys will not help you size the system. The ACOL design will if the licence is installed and the
application added.
99
6 Introduction to 3rd yr
6.1 More Unit operations
6.1.1 General Reactors
This set of Reactors (Conversion/Gibbs/Equilibrium/Yield Shift) shown in
the sub toolbar on the right of the main toolbar are important for Reactor
design and reaction completion calculations based on the different types of
Reactions.
6.1.2 PFR
This simulates a PFR and is located to the left of the General Reactors
button. (The button that looks like a pipe with mesh in the middle of it)
This reactor is best to be used after a general reactor has been used and
defined. This reactor is good for mass balances and reactor sizing. This type
of reactor can only handle rate type reactions.
6.1.3 CSTR
This is located to the left (far left) of the PFR button. This looks like a tank
with a stirrer in it. This reactor simulates a CSTR and is best to be used after
a general reactor has been used and defined. This reactor is good for mass
balances and reactor sizing. This type of reactor can only handle rate type
reactions.
6.1.5 Sub-Flowsheet
The sub Flowsheet is for neatening up Complex Process Flowsheets and
linking group-work together. Simply add in a Sub-flowsheet, from here you
can import a sub flowsheet, start blank of copy cut items into the sheet.
Simply set up the links between the sub and the parent flowsheet in the
interface.
Click on Sub-Flowsheet Environment to enter the flowsheet.
The Location of the Sub-Flowsheet is shown on the right.
6.1.6 Solid-Operations
Just be aware of these mainly for second semester and for 4th year.
The Fluids package is only important for the solids interaction to the
transportation fluid.
The location of the Solid Operations Sub-Toolbar is shown right.
Within this Toolbar are several Solids Processing Tools. These include:
These units are for solids separations. Hysys has only a few select solids
within the database.
Figure
6-5:
The
location of the control
toolbar
101
You will notice the components list gets filtered and sorted through the filter
and now only the solid materials are left. These include:
NOTE: To remove the filters just click on the Use Filter button again.
102
7.1.2
Conversion......................................................................................................................................................104
Equilibrium.....................................................................................................................................................104
Kinetic ............................................................................................................................................................105
Simple Rate ....................................................................................................................................................105
Heterogeneous Catalytic .................................................................................................................................105
7.1.2.1
7.1.2.2
7.1.2.3
PFR.................................................................................................................................................................106
CSTR ..............................................................................................................................................................106
General Reactors.............................................................................................................................................106
7.2
HARDER DISTILLATION ................................................................................................................................ 107
7.2.1
Hand Calculations .................................................................................................................................. 107
7.2.1.1
7.2.1.2
7.2.1.3
7.2.2
7.2.3
7.2.3.1
103
Conversion
Equilibrium
Heterogeneous Catalyst
Kinetic
Simple Rate
7.1.1.1 Conversion
The conversion reaction may be defined using the components stoichiometric co-efficients and a
basis. The basis is a reactant component that is the basis of the conversion. A simple temperature
dependant equation may be used given the stoichiometric co-efficients and the reaction phase, if
unsure of the reaction phase properties select overall.
7.1.1.2 Equilibrium
After the stoichiometry has been entered the equilibrium reaction rates may be defined in a variety
of ways. Set the basis to the desired setting (Activity or a concentration), the phase should be set as
either liquid or vapour phase. The temperature limitations for the reaction may also be entered if
they are available. Set the Basis units if a concentration has been selected. Keq Source (Radio
button section on the right of the basis information) is the equation type for the Equilibrium K
source. The preview of the selected K values/Equations may be seen in the Keq tab. A
temperature approach may also be entered in the Approach tab.
Most of the time Algebra will need to be completed first and some assumptions such as pressure
independence will need to be made to get the rate law co-efficients in the right form.
This reaction is of Rate Type.
NOTE: Some reactions have been pre-defined. These may be found on the library tab of the
Equilibrium Reactions option only.
104
7.1.1.3 Kinetic
After adding in the stoichiometry the Basis (same as Equilibrium) the reaction rates in both
directions (forward and Reverse) may be entered in the Parameters tab. Keep the format the same
as in the Equation Help zone (extended Arrhenius Equation) to the right of the co-efficient input
tables.
This reaction is of Rate Type.
Numerator
Denominator
e RT
E '
Ki = Ai e RT
Where :
fx (basis) = The functions of basis, the product of ' Concentration' to specified exponents
The indexes (1, 2 , ...i) in the constants K , A and E indicate the matrix location
n is the denominator exponent
Figure 7-1: The Catalytic Reaction Kinetics basic setup
105
7.1.2.1 PFR
A Plug Flow Reactor (PFR) is essentially a pipe with the reaction progressing along the length of
the reactor. At steady state the reaction completion is defined using the Volume/Length of the
reactor. Several extra parameters are required for this unit to solve for the volume, length, diameter
etc.
7.1.2.2 CSTR
A Constantly Stirred Tank Reactor (CSTR) is a tank with a stirrer for mixing the reactants. Several
extra parameters are required for this unit to solve for the volume, stir rate etc.
106
Open a new worksheet in Hysys and add the components Benzene and Chloro-Benzene.
Choose the fluid package (PRSV this is the package we will be using in Hysys) and then
enter the simulation environment.
Create a material stream and set the vapour fraction to zero (0), i.e. a saturated liquid. Set
the pressure to 1 atm, a flow of 1 kg-mol/hr and the composition of benzene to 0.05 mole
fraction. We use benzene as it is the lighter key in this system.
Open the composition window of the stream and note the liquid and vapour phase fractions
of benzene. Change the mole fraction of benzene from 0.05-0.95 in steps of 0.05 and note
down the vapour and liquid fractions for each condition. This is the equilibrium data for the
Benzene/ Chloro-Benzene system.
can be calculated from the obtained liquid and vapour fractions of benzene using Equation
7-1 below. Check that they are relatively constant. This data assumes constant volatility, for
this system is acceptable. i.e. ONLY IF is approximately constant the formula below can
be used.
x = Mole Fraction of the more volitile (lighter) component in the Liquid Phase
y = Mole Fraction of the more volitile (lighter) component in the Vapour Phase
Now conduct tray by tray calculations using the constant relative volatility value obtained
from above, a reflux of 2.40 and the procedure found in Section 7.2.1.2. Determine the
number of stages and composition of benzene vapour and liquid on each stage.
107
Based on tray numbering from top to bottom, the vapour and liquid compositions at the
reflux return stage (usually tray 1) are the same.
From the assumptions above, the equations shown in Equation 7-2 below it is possible to complete
the tray by tray calculations.
Then draw a tray diagram similar to the one below in Figure 7-2 to help keep track of the
calculations.
Vn-1
Yn-1
Stage n-
Ln-2
Xn-2
(2) Vn +1 = Vn = V
Stage n
Ln-1
Xn-1
Ln
Xn
(4) y n =
(1) L n 1 = L n = L
Vn
Yn
Vn+1
Yn+1
Stage n+1
Where: n is the tray number
(3) Vn +1 y n +1 + L n -1 x n -1 = Vn y n + L n x n
xn
1 + ( - 1) x n
108
Insert a short-cut distillation column. The location of this is shown on the right (Figure 6-2). The
short-cut method column is the one in the second row on the right (grey with column lines), just
under the splitter. Use the same specifications as outlined in the notes:
Table 7-2: The Specifications for the short cut method
Property
Value
Units
Feed (F)
160.00 kg-mol/h
xF
0.55
xD
0.90
xB
0.05
All Pressures
1.00 atm
Step 1: Name and define all of the material and energy streams. Select the type of
required. Set the number of stages and the feed stage for the column.
condenser
NOTE: You can define the streams to be exactly the same by clicking on the Define from Other
Stream Button located at the base of the stream properties window (below the tabs). A new
window will pop up with options such as what values you wish to duplicate.
Step 2: Set the pressure of the condenser and re-boiler. This can be approximated as the same
pressure as your feed stream.
Step 3: Ignore all the side-ops and click next. The side ops are used for pumping and piping
requirements, extra condensers/re-boilers and other useful modifications to a column. The level
controllers show up here when you enter Dynamic mode.
Step 4: Set the reflux ratio to that noted down from the short-cut model. (~2.4)
You must now define the some specifications in the column to remove the degrees of freedom.
These are generally the requested recoveries of the components.
109
110
8.3
ENTERING DYNAMIC MODE ......................................................................................................................... 117
8.3.1
Dynamics Assistant ................................................................................................................................. 117
8.3.2
Strip charts.............................................................................................................................................. 118
8.4
SIMPLE DYNAMIC EXAMPLES ....................................................................................................................... 119
8.4.1
Tank Gravity Drained ............................................................................................................................. 119
8.5
CONTROLLERS .............................................................................................................................................. 120
8.5.1
Setting up a Controller............................................................................................................................ 120
8.5.2
Gathering Data for the Control Parameters........................................................................................... 120
8.5.2.1
8.5.2.2
8.6
CONTROLLER EXAMPLES ............................................................................................................................. 122
8.6.1
Tank Control ........................................................................................................................................... 122
8.6.1.1
8.6.1.2
8.6.1.3
111
Liquid-Liquid cyclone
Shortcut distillation
112
8.2.2.3 Tanks
The tank units can simulate fluid hold-up, level fluctuations, heat loss (heat exchanger menu) using
heat exchanger sizing, pressure drops over the tanks and even add in a Level Controller. In order to
113
set up the initial setting for dynamics mode simply size the tank. 2 m3 is usually assumed for the
tank size. This menu is displayed below in Figure 8-2.
The Dynamic specification for Vessel Pressure is usually not set here but by the pressure drop into
and out of the tank with the inlet pressure set by either a pressure device such as a pump,
compressor, expander
or pipe etc.
The main dynamic
functionality of the tank
operations are the liquid
Level Controllers, these
are usually connected to
a valve on the bottoms
outlet stream with a
valve attached. If the
valve has not been
attached, one will be
inserted for you.
To add in a Level Controller simply click on the Add/Configure Level Controller Button.
More on the controller will be shown later.
114
Material flow is driven by pressure differences and resistances, the change in flowrate stops when
the pressures have been equalized. A fixed pressure drop specification does not allow for this
natural process.
8.2.2.6 Valves
The valve really is an important unit in Dynamics mode. These are used as the controllers of flow
and pressure. Almost all of the control loops utilise a valve as a counter disturbance device.
IN LIQUIDS the valve manipulates Flowrate.
IN GASES/Vapours the valve manipulates Pressure, which in turn changes the flowrate.
Firstly the Valve needs to be sized. Do this in steady state mode before entering Dynamics, sizing
the valve may be completed in the Rating tab of the valve, as shown in Figure 8-5 below. The
Valve Characteristics (Section 2.2.3) may also be set here.
Figure 8-5: The Sizing options for a valve. Left is the Universal Gas Sizing Parameters and on the right is the
Simple Resistance Equation Parameters
115
Next the Dynamic specifications need to be set. This may be done on the Dynamics Tab shown
below in Figure 8-6. In this section you can simulate the surrounding pipe, the manual actuator
specifications and flow limitations. (These are in the different menus)
If a valve has not been sized, click on one of the Size Valve buttons on either the Rating, Sizing
menu or the Dynamics, Specs menu.
NOTE: A pressure drop and a flow must be present for the valve to be sized.
8.2.2.7 Pipe
This operation changes quite a bit in Dynamics mode. Firstly the pipes duty is not calculated in
Dynamics mode. The heat loss correlations are replaced with simplified heat transfer/loss
calculations. There are 3 modes for heat loss calculations.
None
Simple- this involves a calculation based on the feed. Using only the Q=UAT
Detailed- this includes temperature profiles through the pipe walls
o Included are the wall Conduction /Insulation
o Included are the convection Calculations
There is no need to go to the dynamics Tab in the pipe segment unless a Pipe Flow model is to be
selected. These are located on the Design, Parameters menu.
116
Figure 8-8: The location of the Dynamics Mode and steady state mode buttons
UTILISE THIS RESOURCE AT ALL TIMES IN DYNAMICS and for setting up for
Dynamics Mode.
117
118
NOTE: If there is a major problem with the model. Return to steady state mode; redefine the
problem and start-up dynamics again.
=a1 rt 2 * 0.4
Where:
into a2
119
8.5 Controllers
There are several types of controllers catered by Hysys,
however we will only be using the PID controller
function; this is the most generic type of controller, the
Connections tab is shown on the right in Figure 8-10.
Once inserted the controller is a generalised IC controller. However once the PV and OP have been
entered the type of controller will change to:
LIC for level control
PIC for pressure control
FIC for flow control
TIC for temperature control
XIC for concentration control
Next we need to set the boundaries for the
Process Variable.
Go
to
the
Parameters
tab,
Configuration menu, the window should
be similar to the one shown to the right in
Figure 8-11. In this menu set the limitations
on the process variable (Range box). These
are usually the limits to what the system can
handle (e.g. where the valve is at 0 % and
100 % open).
In this menu you can enter the controller Figure 8-11: The LIC Parameters, Configuration Menu
tuning parameters, set point, operational modes and the PV range.
Other menus in the Parameters tab may be used for advanced tuning, signal disturbances etc.
To view a convenient interface with the SP, PV and OP points click on the Face Plate button
located at the base of the window.
120
8.5.2.2 Auto-Tuner
If the controller is inserted, the ability to automatically tune the controller is available. To do this
make sure the system is in a steady state and the system is within its stable range.
Go to the Parameters tab, Autotuner menu. Figure 8-12 below shows this view.
Set the amplitude (1 % is fine) as the step change as a percentage of the current value
Click on the Start Autotuner button
Once the process has been completed (this should only take a few seconds) the bottom table
on the screen will be filled out.
Click Accept to accept the new tuning parameters
NOTE: If the autotuner does not start the system is not steady. To check this, turn the controller to
manual and find a steady state solution first. Turn the controller back on after the tuning has been
completed.
121
Kc
Ti
Hysys Tuned
1.8
1.31x103 minutes
Hand Tuned
38
0.8 minutes
Change the flowrate in to the tank and view the effects on the system. You can also change the set
points using the face plates.
Kc
Ti
First Guess
0.01
1 minute
123
124
125
NOTE: If the PSD Property menu option is not available to you make sure the solid material has
been defined in the composition menu.
To enter a PSD, select the solid component from the list (useful if there are different types), then
click on Edit.
The window on the right should appear, Figure 9-2. In this window you can change the Particle
Density; this is the density of the particle not the fluid mixture.
126
If the Discrete PSD is only a simplified version of the distribution a Fit Type option may be
selected. If you are unsure of what fit to use simply click on AutoFit, this will bring up the given
distribution and the fit types on a Log-Log Plot for you. Simply select the correct one for the
application.
NOTE: This distribution graph will only appear for the Mass Percentage basis Distributions.
Once this has been done, click OK, located at the base of the window. The window will now close
and the distribution will show in the table shown in Figure 9-2, above, the Calculations status
(bottom right with a coloured strip) will still say PSD was Not Calculated. To finish this up click
the Calculate PSD button on the bottom left of the window. The Calculation status bar should
turn green and should PSD was Calculated. The PSD has now been fully defined and ready to be
separated.
127
128
9.3 Operations
There are several types of Solids separators. These are shown solved
with streams and the sub-toolbar with the symbols that match the
operations in the worksheet on the right in Figure 9-3.
9.3.2 Cyclone
This is the most common type of gas suspended solids separation device. These are used for
medium particle size separations. Defining a cyclone is easy once the PSD has been completed.
In the Design, Solids menu, select the solid that you wish to define as the basis of the separation.
Only in the cyclone can you select to separate the particles on a particle size distribution basis.
To select the particle size distribution efficiency option select the option from the left of the
window in the Efficiency Basis options box.
Define the particle efficiency in the Design parameters menu.
NOTE: To select a custom cut size select the cut size in the Solids menu before connecting up the
feed stream. Otherwise the default 1mm will be selected for you.
129
Also changing the configuration between High-Efficiency, High flow and User defined will not
effect the calculations; but this will affect the sizing of the cyclone and potentially the limitations on
the efficiency of the cyclone.
There will be a restriction on the maximum efficiency based on the PSD and if there are any
particles less than 0.1mm in diameter.
The calculation method should not be changed until these calculations are understood of covered in
class.
9.3.3 Hydro-Cyclone
The Hydro-Cyclone is a similar device to the gas cyclone above but deals only with a liquid solvent
phase. Although the delta PSD calculations are not completed as in the cyclone, an overall
efficiency is calculated based on the cut size or particle diameter. I.e. only a composition split is
calculated.
NOTE: The configurations are: MODE1=High Efficiency equivalent, MODE2=High Output
equivalent.
10 Advanced Material
10.1 Pipesys
Pipesys is a third party operation that simulates pipes with more advanced options, profiles and
materials than that of Hysys. This should only be used when the pipe has specific properties that the
Hysys pipe function does not allow. For more finalised design
The basics for this operation are the same as the pipe function used above.
To start up Pipesys follow these few easy steps:
Go to the standard menu bar at the top of the window
Click on Flowsheet
Click on Add Operation, or press the F12 button on the keyboard. Then the window shown in
Figure 10-1 should appear.
B18
B19
R5
Click on the Piping Equipment Radio Button (B18), then click on PIPESYS Extension (R5),
and finally click Add (B19).
This should bring up Figure 10-2; this shows the connections tab and the instructions in the yellow
strip at the bottom.
Figure 10-2: The Worksheet View and the PIPESYS properties window
131
B20
Choose the Nominal Diameter of the pipe. This is required; Hysys or Pipesys will not work it out
for you. Select 2 inches. (Industrial diameters are commonly in Inches or round numbers in mm). A
new box will appear this will ask for the Pipe Schedule.
NOTE: It is not common to buy pipes of a custom diameter.
132
Select 40 from the drop down menu; this is one of the most common schedules for chemical
plants.
The screen should look like the one in
Figure 10-4: The Dimensions Tab
above.
From the Choose Roughness Cell select PVC to keep similar to the above example
NOTE: The choices available such as Steel, Concrete, Iron and Fibreglass
Next we need to define the heat transfer. Go to the Heat Transfer Tab, shown in
Figure 10-5 above. From here we define the conditions around the pipe.
Select the Above Ground radio button from the top left option box (Heat Transfer Environment)
Define the Default Conduciveness as PVC in the drop down menu.
Then we need to define the Air Properties. This can be done by selecting the property and clicking
the Default button (B20)
We will not define a Pipe Coating, (Insulation), at this stage but the process is simple. Next we
need to close this window and return to the Elevation Profile screen. Now we need to define the
pipe length and elevation changes.
Enter the figures in Table 10-1 below.
Table 10-1: The pipeline length specifications
Distance (m)
Elevation (m)
Run (m)
Rise (m)
10
5
10
3
The warning in the yellow strip will now change to Insufficient Information on the Temperature
Profile screen. To solve this co to the Temperature Profile tab. Insert 25 oC into the
Ambient Temperature cell of the table.
The warning in the yellow strip will now change to Insufficient Information in the Attached
Streams. To solve this co to the Worksheet tab. Insert the following information from Table
10-2.
Table 10-2: The stream properties
Parameter
Inlet Stream
Outlet Stream
Temperature
60
Pressure
2
Mass Flow
10
-
Units
o
C
atm
kg/h
From here the Operation should solve. This gives an outlet pressure of 173.5 kPa, with an energy
transfer of around 0.6 kW and a negligible temperature change.
To View the profile results go to the Results tab and click on one of the three viewing options.
(Detail, Report, Plot).
133
11.1.1
This has been visited briefly in the heat exchanger section. This section will reinforce the problem
that Hysys seems to have with the heater/cooler couple.
With any defined system. Its not important here. Insert a heater and a cooler then link the two
operations with an energy stream.
Define the following parameters.
Cooler In
50oC
Cooler Out
5 oC
Heater In
25oC
Heater Out
80oC
Assume 1 of the flowrates
For a counter current exchange the LMTD would be 24.66. For a co-current exchanger the
DeltaTin/DeltaTout would be -1/3. This example defies the thermodynamic laws. Looking at this
temperature profile should ring alarm bells straight away. You cannot boil steam using the heat
from making ice. This is why I use the item tables to show the temperatures of the streams
whenever I am changing a condition that will effect such a unit.
11.1.2
134
135