You are on page 1of 2

O

WA-300 Dual Relay Automatic Wall Switch


SmartSet technology
automatically selects optimal
settings for each space

Two relays for control of


two separate lighting
loads or circuits

Optional walk-through
mode for increased
savings

Dual switch buttons; each


controls a separate relay

Light level sensor holds lights


off on secondary relay when
enough daylight is present
PROJECT
LOCATION/TYPE

Product
Overview

Description

Bi-level Control

The WA-300 passive infrared automatic wall switch


turns lighting on and off based on occupancy.
These switches contain two relays for controlling
two independent lighting loads or circuits.

The WA-300 features a built-in light level sensor


that affects the second (secondary) relay. If adequate daylight is present, the sensor will hold
secondary lights off until daylight levels drop, providing increased energy savings. The WA-300
satisfies energy codes requiring bi-level or daylight
control switching. The two relays in the sensor give
it the unique ability to control two lighting loads
independently. This provides A/B switching where
the user can achieve half-lighting (or another
desired portion) from a single switch.

Operation
The WA-300 replaces existing wall switches and
operates between 100 and 300 volts. The sensor
uses advanced passive infrared technology to
detect occupancy. It detects the difference
between infrared energy from a human body in
motion and the background space. Each of the WA300s relays can simultaneously control a separate
lighting load and each can be set for either automatic or manual on. Dual ON/OFF buttons allow
the user to manually turn on and off each of the
loads. After a period of time when no occupancy is
detected, lighting automatically switches off.

Features

Applications
Achieving bi-level lighting control greatly enhances
energy savings in building areas such as offices
and conference rooms. For exhaust fan applications, the sensor can shutoff the exhaust fan relay
10 minutes after the lighting relay is shutoff. In
addition, the sensors hard lens enables it to be
used in public spaces susceptible to vandalism.

Contains two relays for controlling two independent lighting loads or circuits; secondary relay is
isolated

Zero-cross relay guarantees reliable operation


with non-linear loads even with temperature
changes and product aging

Advanced control logic based on RISC microcontroller provides:

Choice of automatic-ON or manual-ON operation; selectable for each relay

Detection Signature Processing eliminates false Built-in light level sensor in the second relay
triggers and provides immunity to RFI and EMI
holds lights off until natural light levels drop
SmartSet automatically adjusts sensitivity and
time delay settings to fit occupant patterns
Walk-through mode turns lights off 3 minutes
after the area is initially occupied if no movement is detected within 30 seconds
www.wattstopper.com
800.879.8585

One-step light level control set-up learns


desired hold-OFF level

Optional audible alert for impending shutoff


For safety, there is no leakage to load in the
OFF mode and sensor is safety grounded
Hard lens makes sensor resistant to vandalism
Units are tamper resistant
LED indicates occupancy detection

WA-300 Technical Information


Specifications

Controls &
Installation

Universal 120/230/277 VAC; 50/60 Hz operation


Coverage of 180 degrees, maximum 300 ft2, 150
ft2 for desktop activity
Time delays: SmartSet (automatic), fixed (5, 10,
15, 20, 20 + 10, or 30 minutes), walk-through,
test-mode
Sensitivity adjustment: SmartSet (automatic) or
reduced sensitivity

1.0 mm hard, poly IR 2 lens; 2 level lens for


superior desktop detection
Built-in light level sensor, works from 8 to 180
footcandles (86 to 1,937 lux), on secondary relay
Compatible with all electronic ballasts and PL
lamp ballast systems
Dimensions: 2.6" x 1.7" x 1.9"
(67mm x 43mm x 49mm) L x W x D
UL and CUL listed; 5 year warranty

Product Controls

Installation

ON/OFF Buttons
Relay 1
Relay 2
1

LED

Lens

Wiring

DIP
Switches

Bi-level Wiring

2 Circuit Wiring

Neutral

White

Neutral

White

Line 1 Black

Line

Red

Black
Blue

Primary
Load

Red

Brown Secondary
Load

Line 2 Blue

Brown Secondary
Load

Primary
Load

Ground

Ground
White

Neutral

Coverage &
Settings

DIP Switch Settings

Coverage

DIP Switch #s:


Time Delay

1 2 3

DIP Switch #

25'
(7.6m)

4.0'
(1.2m)
floor

The 2-level lens provides


superior coverage at a desktop level by allowing the
sensor to detect vertical as
well as horizontal motion

5 minutes
10 minutes
15 minutes
20 minutes
20 + 10* minutes
30 minutes
override

Watt Stopper/Legrand
Pub. No. 17104

Catalog No.

DIP Switch #
Audible Alerts

Auto On
Manual On

Disabled
Enabled

DIP Switch #
Relay 2 ON Mode

DIP Switch #
Sensitivity

Auto On
Manual On

Low, 50%
Time Delay

Bypass occupancy & light level functions.


Loads manually controlled with WA-300 buttons.

DIP Switch #

25'
(7.6m)

FACTORY
PRESETS

Walk Through

Disabled
Enabled
=ON

Relay 1 On Mode
Audible Alerts

ON

10'
(3.1m)

High

Relay 2 shuts off 10 min. after relay 1

Factory Settings

Ordering
Information

Relay 1 ON Mode

SmartSet/Test

Walk Through

Sensitivity

Relay 2 On Mode

=OFF

Color

Voltage

Load Requirement

Coverage

WA-300-W

White
Lt. Almond

0-800 Watt Ballast,


1/4 hp

180, 300 ft2 (27.9 m2)

WA-300-A

120 VAC;
50/60 Hz

WA-300-I

Ivory

or

WA-300-G

Grey

WA-300-B

Black

230/277 VAC;
50/60 Hz

or
0-1200 Watt Ballast,
1/4 hp

One ASP-211 single-gang cover plate included. Order ASP-422 for blank 2-gang cover plate, ASP-432 for 2-gang cover plate
with switch option (specify color).