ODW-720-F2
Fibre Optic Modem
Industrial Converter
RS-232 to Fibre Optic Link.
Repeater, line and redundant ring
www.westermo.com
Westermo Teleindustri AB
User Guide
Legal information
The contents of this document are provided as is. Except as required by applicable
law, no warranties of any kind, either express or implied, including, but not limited to,
the implied warranties of merchantability and fitness for a particular purpose, are made
in relation to the accuracy and reliability or contents of this document. Westermo
reserves the right to revise this document or withdraw it at any time without prior
notice.
Under no circumstances shall Westermo be responsible for any loss of data or income
or any special, incidental, and consequential or indirect damages howsoever caused.
More information about Westermo can be found at the following Internet address:
http://www.westermo.com
2
6651-2231
Safety
Before installation:
Read this manual completely and gather all information on the unit. Make sure
that you understand it fully. Check that your application does not exceed the safe
operating specifications for this unit.
This unit should only be installed by qualified personnel.
This unit should be built-in to an apparatus cabinet, or similar, where access is
restricted to service personnel only.
The power supply wiring must be sufficiently fused, and if necessary it must be
possible to disconnect manually from the power supply. Ensure compliance to
national installation regulations.
Branch circuit protection (fuse) is required for this unit with rating not
exceeding 20 A.
Product should be connected to UL Listed power supplies rated 12 48 VDC,
min 500 mA or 24 VAC, min 500 mA or reliably grounded DC SELV source*.
This unit uses convection cooling.To avoid obstructing the airflow around the
unit, follow the spacing recommendations (see Cooling section).
Maintenance
No maintenance is required, as long as the unit is used as intended within the specified
conditions.
Approval / Compliance
EMC
Safety
ATEX**
This equipment has been tested and found to comply with the limits for a Class A
digital device, pursuant to Part 15 of the FCC Rules. These limits are designed to provide
reasonable protection against harmful interference when the equipment is operated in a
commercial environment.
This equipment generates, uses, and can radiate radio frequency energy and, if not
installed and used in accordance with the instruction manual, may cause harmful interference to radio communications. Operation of this equipment in a residential area is likely
to cause harmful interference in which case the user will be required to correct the
interference at his own expense.
EN 55022 Notice: This is a class A product. In a domestic environment this product may cause radio interference in which case the user may be required to take adequate measures.
6651-2231
Marking
II 3 G
Ex nA IIC T4 Gc
SPECIAL CONDITION
WARNING DO NOT SEPARATE WHEN ENERGIZED
Indicate that this unit complies with relevant European standards that are
harmonised with the 94/9/EC Directive (ATEX).
II
G
Ex
nA
IIC
T4
Gc
SPECIAL
CONDITION
6651-2231
Ratings
Power
Ambient temperature
Ingress protection (IP)
Maximum surface temperatur
IP 21
40C to +60C
Minimum 25 mm above / below
Minimum 10 mm left / right
FP
Descripton
In & out / Relay contact (NO)
In & out / Relay contact (C)
In & out / Relay contact (NC)
Descripton
Out / Data Carrier Detect (DCD)
Out / Received Data (RD)
In / Transmitted Data (TD)
Not connected
/ Signal Ground (SG)
Out / Data Set Ready (DSR)
In / Request To Send (RTS)
Out / Clear To Send (CTS)
Not connected
Umax = 12 Vpk
Imax = 60 mA
Data rate:
300 bit/s to 250 kbit/s
123
Position
1
2
3
4
5
6
7
8
9
Position Descripton
Rx
In / Receive port
Tx
Out / Transmit port
Position Descripton
1
In / Common
2
3
4
In / +Voltage A
In / +Voltage B
In / Common
Output values
Max 0 dBm
Input values
Uin = (10 60) VDC
Iin = 550 mA max
PIn = Max 5.5 W
6651-2231
6651-2231
Declaration of Conformity
Westermo Teleindustri AB
Declaration of conformity
The manufacturer
Westermo Teleindustri AB
SE-640 40 Stora Sundby, Sweden
Model
Art no
ODW-700 series
3651-07xx
ODW-700EX series
3651-37xx
Short name
2004/108/EC
94/9/EC1
Title
Electromagnetic compatibility Immunity residential environments
Issue
2007
EN 61000-6-2
2005
EN 61000-6-3
2007
EN 61000-6-4
2007
EN 55022
EN 55024
EN 50121-4
1998 + A1:2001 +
A2:2003
2006
EN 60079-0
EN 60079-15
The last two digits of the year in which the CE marking was affixed:
2006 + A1:2007
2009
2005
11
Pierre berg
Technical Manager
15th June 2011
1
Postadress/Postal address
Tel.
Telefax
Postgiro
Bankgiro
Org.nr/
Corp. identity number
Registered office
016-428000
Int+46 16428000
016-428001
Int+46 16428001
52 72 79-4
5671-5550
556361-2604
Eskilstuna
6651-2231
IEC 61000-4-3
ENV 50204
EN 61000-4-4
Surge
EN 61000-4-5
RF conducted
EN 61000-4-6
EN 61000-4-9
EN 61000-4-11
Mains freq. 50 Hz
Mains freq. 50 Hz
Radiated emission
EN 61000-4-16
SS 436 15 03
EN 55022
FCC part 15
EN 55022
FCC part 15
EN 55022
EN 60950
Conducted emission
Dielectric strength
Environmental
Temperature
Shock
Packaging
Enclosure, ODW-720-F2
Enclosure,
ODW-720-F2 EX
Dimension W x H x D
Weight
Degree of protection
Cooling
Mounting
6651-2231
Enclosure
Signal ports
Power ports
Signal ports unbalanced
Signal ports balanced
Power ports
Signal ports
Power ports
Enclosure
AC power ports
Signal ports
Signal ports
Enclosure
AC power ports
AC power ports
DC power ports
Signal port to all other
isolated ports
Power port to other
isolated ports
IEC 60068-2-6
Operating
Storage & Transport
Maximum surface
temperature
Operating
Storage & Transport
Operating
Operating
Operating
IEC 60068-2-27
Operating
UL 94
PC / ABS
Cabelec 6141
Humidity
Altitude
Service life
Vibration
Description
Enclosure contact
Enclosure air
Enclosure
IEC 529
Enclosure
Level
6 kV
8 kV
10 V/m 80% AM (1 kHz), 80 800 MHz
20 V/m 80% AM (1 kHz), 800 1000 MHz
20 V/m 80% AM (1 kHz), 1400 2700 MHz
20 V/m pulse modulated 200 Hz, 900 5 MHz
2 kV
2 kV
2 kV line to earth, 2 kV line to line
2 kV line to earth, 1 kV line to line
2 kV line to earth, 2 kV line to line
10 V 80% AM (1 kHz), 0.15 80 MHz
10 V 80% AM (1 kHz), 0.15 80 MHz
300 A/m, 6.4 / 16 s pulse
10 & 5 000 ms, interruption
200 ms, 40% residual voltage
500 ms, 70% residual voltage
100 V 50 Hz line to earth
250 V 50 Hz line to line
Class B
Class A
Class B
Class B
Class A
2 kVrms 50 Hz 1min
3 kVrms 50 Hz 1min
2 kVrms 50 Hz 1min (@ rated power < 60V)
40 to +60C
40 to +70C
135C (temperature class T4)
5 to 95% relative humidity
5 to 95% relative humidity
2 000 m / 70 kPa
10 year
7.5 mm, 5 8 Hz
2 g, 8 500 Hz
15 g, 11 ms
Flammability class V-1
35 x 121 x 119 mm
0.26 kg
IP 21
Convection
Horizontal on 35 mm DIN-rail
Functional description
Switches
LEDs
POWER
+VA
+VB
COM
O
V
P
Internal
Electronics
COM
STATUS
ODW-720
O
V
P
NO
C
NC
RS -232
DCD
RD
TD
SG
DSR
RTS
CTS
SHIELD
CH 1
SFP
Fibre transceiver
TX
RX
SFP
Fibre transceiver
TX
RX
CH 2
10
6651-2231
Interface specifications
Power
Rated voltage
Operating voltage
Rated current
Rated frequency
Inrush current It
Startup current*
Polarity
Redundant power input
Isolation to
Connection
Connector size
Shielded cable
Status
Port type
Rated voltage
Operating voltage
Contact rating
Contact resistance
Isolation to
Connection
Connector size
Shielded cable
6651-2231
11
RS-232
Electrical specification
Data rate
Protocol
Data format
Data retiming
Transmission range
Isolation to
Connection
Shielded cable
Conductive housing
*
EIA RS-232
300 bit/s 250 kbit/s
Asynchronous or synchronous
9 12 bits in asynchronous mode
Any type in synchronous mode
Asynchronous mode only
15 m
Status and Power port
9-pin D-sub female (DCE)
Not required, except when installed in railway applications as
signalling and telecommunications apparatus and located close
to rails*
Isolated to all other circuits and housings
To minimise the risk of interference, a shielded cable is recommended when the cable is located inside 3 m
boundary to the rails and connected to this port.
The cable shield should be properly connected (360) to an earthing point within 1 m from this port.
This earthing point should have a low impedance connection to the conductive enclosure of the apparatus
cabinet, or similar, where the unit is built-in. This conductive enclosure should be connected to the earthing
system of an installation and may be directly connected to the protective earth.
12
6651-2231
LED Indicators
(for details see
page 15)
Status
screw terminal
Position
1
2
3
Description
Contact with C when fibre
optical links are in operation
Common
Open (no contact with C)
when fibre optical links are
not in operation
Product
marking
NO
C
NC
Power
screw terminal
FX(Fibre)
(for details
see page 1213)
Position
Direction*
In
2
3
4
In
In
In
Description
Common
voltage
Voltage A
Voltage B
Common
voltage
Product
marking
COM
+VA
+VB
COM
RS-232
D-sub
Position
1
2
3
4
5
6
7
8
9
Direction*
Out
Out
In
Out
In
Out
Description
Data Carrier Detect (DCD)
Received Data (RD)
Transmitted Data (TD)
Not connected
Signal Ground (SG)
Data Set Ready (DSR)
Request To Send (RTS)
Clear To Send (CTS)
Not connected
6651-2231
13
LED indicators
LED
Status
Description
PWR
ON
Power is on.
OFF
Power is off.
ON
Focal point
OFF
ON
Flashing
OFF
ON
Flashing
OFF
Flash
OFF
Flash
OFF
ON
Flashing
ON
Flashing
Power
FP
CH 2
Channel 2 link status
CH 1
Channel 1 link status
TD
RD
FL R
Failure link remote
FL L
Failure link local
Note: During power up, all LEDs will turn on for about 1 second.
14
6651-2231
! DIP-switch settings
Before DIP-switch settings:
Prevent damage to internal electronics from electrostatic discharges (ESD) by
discharging your body to a grounding point (e.g. use of wrist strap)
Note: Disconnect power before DIP-switch settings.
S1
S2
ON
1 2 3 4 5 6 7 8
300 bit/s
ON
1 2 3 4 5 6 7 8
ON
38.4 kbit/s
ON
1 2 3 4 5 6 7 8
1200 bit/s
ON
1 2 3 4 5 6 7 8
ON
57.6 kbit/s
ON
1 2 3 4 5 6 7 8
2400 bit/s
115.2 kbit/s
ON
1 2 3 4 5 6 7 8
4800 bit/s
125 kbit/s
ON
9600 bit/s
1 2 3 4 5 6 7 8
ON
1 2 3 4 5 6 7 8
ON
1 2 3 4 5 6 7 8
ON
1 2 3 4 5 6 7 8
ON
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8
ON
1 2 3 4 5 6 7 8
ON
1 2 3 4 5 6 7 8
187.5 kbit/s
1 2 3 4 5 6 7 8
250 kbit/s
9 bits data
format
10 bits data
format
11 bits data
format
12 bits data
format
ON
1 2 3 4 5 6 7 8
19.2 kbit/s
1 2 3 4 5 6 7 8
230.4 kbit/s
7 bit
8 bit
6651-2231
10
10
10
2 stop bit
Number of bit
Parity
1 stop bit
11
11
11
12
15
ON
1 2 3 4 5 6 7 8
1.6 ms
1 2 3 4 5 6 7 8
ON
ON
26 s
1 2 3 4 5 6 7 8
ON
1 2 3 4 5 6 7 8
416 s
1 2 3 4 5 6 7 8
ON
ON
13 s
1 2 3 4 5 6 7 8
ON
1 2 3 4 5 6 7 8
208 s
1 2 3 4 5 6 7 8
ON
2.6 s
2.1 s
ON
8.6 s
1 2 3 4 5 6 7 8
2 s
ON
1 2 3 4 5 6 7 8
104 s
1 2 3 4 5 6 7 8
ON
4.3 s
ON
1 2 3 4 5 6 7 8
52 s
1 2 3 4 5 6 7 8
4 s
ON
Y-mode
V-mode
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8
OR
OR
channel 2
channel 1
OR
channel 2
channel 1
RS-232
RS-232
If both fibre channels 1 and 2 are used
and not redundant ring focal point
OR
channel 2
channel 1
RS-232
If only fibre channel 2 is used
channel 2
channel 1
RS-232
For applications that only require half duplex communication it is recommended to use
Y-mode. Please see the ODW-720 Management Guide for further details.
16
6651-2231
S2 DIP-switch
ON
ON
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8
ON
ON
1 2 3 4 5 6 7 8
ON
ON
Multidrop mode.
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8
ON
ON
ON
1 2 3 4 5 6 7 8
ON
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8
ON
1 2 3 4 5 6 7 8
ON
ON
ON
Always OFF
1 2 3 4 5 6 7 8
* = RTS to CTS transport and secondary channel cannot be used at the same time.
Factory default
ON
1 2 3 4 5 6 7 8
6651-2231
ON
S1
1 2 3 4 5 6 7 8
S2
17
RS-232 interface
The RS-232 interface is a female 9-position D-sub. Pin assignments are compliance with
the EIA RS-232 standard.
Status port
The status port connects to an internal relay witch may be used to trigger an external
alarm if a fault condition occurs. During normal operation pins 1 and 2 are in contact
with each other, and pins 2 and 3 are isolated. During an optical link failure, or power
failure, pins 1 and 2 are isolated, and pins 2 and 3 are in contact with each other.
Optical link failures can be classified in to two categories, local or remote, as indicated by
the FL L and FL R LEDs. A local link failure is when an optical link is down at this particular unit. A remote link failure is when an optical link is down at some other unit.
From the factory, the status port is set to trigger on both types of link failures. However,
by setting DIP-switch S2:6 to the ON position, the status port will only trigger when a
local link failure has occurred.
18
6651-2231
Mounting
This unit should be mounted on 35 mm DIN-rail, which is
horizontally mounted inside an apparatus cabinet, or similar.
Snap on mounting, see figure.
CLICK!
CLICK!
Cooling
This unit uses convection cooling. To avoid obstructing the airflow around the unit, use the following spacing rules. Minimum
spacing 25 mm (1.0 inch) above /below and 10 mm (0.4 inches)
left /right the unit. Spacing is recommended for the use of unit
in full operating temperature range and service life.
10 mm *
(0.4 inches)
25 mm
25 mm
Removal
Press down the black support at the top of the unit. See figure.
Referring documents
For detailed information on how to configure the ODW-720-F2 for different applications.
Type
Management Guide
6651-2231
Description
Management Guide ODW-720-F2
Document number
6651-2235
19
Sales Units
North America
info@westermo.com
www.westermo.com
Singapore
sales@westermo.com.sg
www.westermo.com
Sweden
info.sverige@westermo.se
www.westermo.se
United Kingdom
sales@westermo.co.uk
www.westermo.co.uk
Other Offices
REV. G 6651-2231 2014-10 Westermo Teleindustri AB, Sweden A Beijer Electronics Group Company