GEOTHERMAL POWERPLANT
SEPARATOR, SCRUBBER AND BRINE
DISPOSAL SYSTEM
CONTROL NARRATIVE
PREPARED BY
CHECKED BY
APPROVED BY
NMB
SFF
DATE
RAT
01-15-15
01-17-2015
01-10-15
DOCUMENT NUMBER
PIC-E-NTV-627-002
REVISION
PAGE
1 of 19
Control Narrative
Sheet
GEOTHERMAL POWERPLANT
SEPARATOR, SCRUBBER AND
BRINE DISPOSAL SYSTEM
Rev.
No.
Doc.
No.
2 of 19
A
PIC-E-NTV-627002
This document deals with the process control per loop and the function of each
components in the process.
SEPARATOR TANK
Local Monitoring (Level and Pressure)
Large amount of vapor should not be permitted to enter steam line with pure
vapor, so to make sure that it will not happen level and pressure are monitored
locally. Level gauges (LG-VSS1102 and LG-VSS1103) are installed at the bridle
assembly to monitor the separator level, and a Pressure Indicator (PI) mounted
at the steam pressure nozzle is used to monitor the pressure inside the separator
tank.
The level in the separator tank can be automatically or manually controlled. Field
mounted capillary tubing level transmitters (LT-VSS1106A and LT-VSS1106B)
measures the level of the separator tank. LT-VSS1106A transmits the measured
value to a panel view indicator (LI-VSS1106A) for remote monitoring of separator
tank level; likewise LT-VSS1106B transmits its measured value to LI-VSS1106B
Control Narrative
Sheet
GEOTHERMAL POWERPLANT
SEPARATOR, SCRUBBER AND
BRINE DISPOSAL SYSTEM
Rev.
No.
Doc.
No.
3 of 19
A
PIC-E-NTV-627002
To maintain the level of the separator tank at set point, LIC-VSS1106 controls
and remotely display the opening of LCV-PSS1212 for flow control of brine to hot
brine injection or to wells. Set point of the LIC-VSS1106 is monitored and can be
Locally mounted level gauge (LG-VSS1106) is use to monitor if the level of tank
is low or very low. Thus, locally installed level switch low (LSL-VSS1106) and
level switch very low (LSLL-VSS1106) are installed for emergency tripping in
brine disposal pump. This switch is responsible for emergency closing of LCV-
Control Narrative
Sheet
GEOTHERMAL POWERPLANT
SEPARATOR, SCRUBBER AND
BRINE DISPOSAL SYSTEM
Rev.
No.
Doc.
No.
4 of 19
A
PIC-E-NTV-627002
VSS1104, and trip all 3 brine disposal pumps (P-SS12 A,B, and C) and force
VSS1104B).
Then the data from LAH-VSS1104B is linked to a logic OR function, that is link to
the interlock of diffuser sump valves (LCV-VSS105A and LCV-VSS1105B) to
open or close the valves.
Control Narrative
Sheet
GEOTHERMAL POWERPLANT
SEPARATOR, SCRUBBER AND
BRINE DISPOSAL SYSTEM
Rev.
No.
Doc.
No.
5 of 19
A
PIC-E-NTV-627002
diffuser sump.
And when the level reaches a very high alarm another level switch very high
(LSHH-VSS1104) will be triggered to send signal to the PLC to trigger a level
Control Narrative
Sheet
GEOTHERMAL POWERPLANT
SEPARATOR, SCRUBBER AND
BRINE DISPOSAL SYSTEM
Rev.
No.
Doc.
No.
6 of 19
A
PIC-E-NTV-627002
Pressure switch high (PSH-PSS1301) is installed along the sump pipe line to trip
the valve when there is a high pressure along the line. PSH-PSS1301 trigger the
pressure alarm high (PAH-PSS1301) and PAH-PSS1301 is displayed in a DCS
for monitoring upon stopping the pump in driving the brine to the cold brine
injection.
Control Narrative
Sheet
GEOTHERMAL POWERPLANT
SEPARATOR, SCRUBBER AND
BRINE DISPOSAL SYSTEM
Rev.
No.
Doc.
No.
7 of 19
A
PIC-E-NTV-627002
BRINE CONTROL
Pump P-PSS12A Control
Hot brine injection pump must be controlled and monitored efficiently, to avoid
destruction of the pump itself and to efficiently deliver the brine to the hot brine
injection and to the wells. All valves trip when there is a very low level alarm in
Control Narrative
Sheet
GEOTHERMAL POWERPLANT
SEPARATOR, SCRUBBER AND
BRINE DISPOSAL SYSTEM
Rev.
No.
Doc.
No.
8 of 19
A
PIC-E-NTV-627002
low.
Vibration of the motor is measured and locally monitored by a vibration indicating
transmitter (VIT-PSS1203). VIT-PSS1203 will transmit this signal to a panel view
HMI vibration indicator (VI-PSS1203), and link this data to a DCS display
the pump from running. PAH-PSS1222 is also linked and display via DCS.
Whichever signal link to an OR logic function such as LSLL-VSS1106, PAHPSS1222, PI-1221 for pressure high alarm, and dPAH-SS1-42 will trip PPSS12A.
Control Narrative
Sheet
GEOTHERMAL POWERPLANT
SEPARATOR, SCRUBBER AND
BRINE DISPOSAL SYSTEM
Rev.
No.
Doc.
No.
9 of 19
A
PIC-E-NTV-627002
Hot brine injection pump must be controlled and monitored efficiently, to avoid
destruction of the pump itself and to efficiently deliver the brine to the hot brine
injection and to the wells. All valves will trip when there is a very low level alarm
trip the pump when differential pressure at the strainer goes high.
A pressure indicating transmitter (PIT-SS1208) measures and locally indicates
the pressure at the inflow of the pump. PIT-SS1208 transmit the data to a panel
view HMI pressure indicator (PI-SS1208) for remote monitoring, then link the
data to DCS display pressure indicator (PI-SS1208) and monitor pressure alarm
low.
Vibration of the motor is measured and locally monitored by a vibration indicating
transmitter (VIT-PSS1206). VIT-PSS1206 will transmit this signal to a panel view
HMI vibration indicator (VI-PSS1206), and link the data to a DCS display
Control Narrative
Sheet
GEOTHERMAL POWERPLANT
SEPARATOR, SCRUBBER AND
BRINE DISPOSAL SYSTEM
Rev.
No.
Doc.
No.
10 of 19
A
PIC-E-NTV-627002
Along this pipe line a pressure switch alarm high (PSH-PSS1223) is installed,
than when it is triggered it will enable the pressure alarm high (PAH-PSS1223)
tripping the pump from running. PAH-PSS1223 is also linked and display via
DCS.
Whichever signal link to an OR logic function such as LSLL-VSS1106, PAHPSS1222, PI-1210 for pressure high alarm, and dPAH-SS1-42 will trips PPSS12A.
Hot brine injection pump must be controlled and monitored efficiently, to avoid
destruction of the pump itself and to efficiently deliver the brine to the hot brine
injection and to the wells. All valves will trip when there is a very low level alarm
trip the pump when differential pressure at the strainer goes high.
A pressure indicating transmitter (PIT-SS1214) measures and locally indicates
the pressure at the inflow of the pump, then PIT-SS1214 transmit the data to the
panel view HMI pressure indicator (PI-SS1214) for remote monitoring, then link
the data to DCS display pressure indicator (PI-SS1214) and monitor pressure
alarm low.
Vibration of the motor is measured and locally monitored by a vibration indicating
transmitter (VIT-PSS1215). VIT-PSS1215 will transmit this signal to the panel
Control Narrative
Sheet
GEOTHERMAL POWERPLANT
SEPARATOR, SCRUBBER AND
BRINE DISPOSAL SYSTEM
Rev.
No.
Doc.
No.
11 of 19
A
PIC-E-NTV-627002
view HMI vibration indicator (VI-PSS1215), then VI-PSS1215 link the data to a
measured .
Along this pipe line a pressure switch alarm high (PSH-PSS1218) is installed,
when it is triggered it will enable the pressure alarm high (PAH-PSS1218) tripping
the pump from running. PAH-PSS1218 is also linked and display via DCS.
Whichever signal link to an OR logic function such as LSLL-VSS1106, PAHPSS1218, PI-1217 for pressure high alarm, and dPAH-SS1-43 will trips PPSS12A.
The Level Control Valve (LCV-TSS1127) which is a solenoid valve, controls the
supply of fresh water going to Seal Water Tank (MKB-TSS11). Its opening/closing
position depends on the setpoint of Level Indicating Controller (LIC-TSS1101). A
Hand Switch (HS-TSS11227) is connected via data link to control LCV-TSS1127.
The control mode selected is sent to Hand Switch Indicator (HIS-TSS1127) for
HMI and DCS monitoring.
Control Narrative
Sheet
GEOTHERMAL POWERPLANT
SEPARATOR, SCRUBBER AND
BRINE DISPOSAL SYSTEM
Rev.
No.
Doc.
No.
12 of 19
A
PIC-E-NTV-627002
The State Indicator (YI-PSS1115) displays the status (Run/Stop) of Seal Water
Pump (MKB-PSS11B) through HMI and DCS Monitoring.
The State Indicator (YI-PSS1116) displays the status (Run/Stop) of Seal Water
Pump (MKB-PSS11A) through HMI and DCS Monitoring.
Control Narrative
Sheet
GEOTHERMAL POWERPLANT
SEPARATOR, SCRUBBER AND
BRINE DISPOSAL SYSTEM
Rev.
No.
Doc.
No.
13 of 19
A
PIC-E-NTV-627002
The Pressure Control Valve (PCV-PSS1106) controls and limits the downstream
pressure obtained in Seal Water Pump (MKB-PSS11B).
The Pressure Control Valve (PCV-PSS1107) controls and limits the pressure
obtained from Seal Water Tank (MKB-TSS11) and Seal Water Pump (MKBPSS11A).
The I/P Level Converter (LY-PSS1212) converts the signal of Level Indicating
Controller (LIC-VSS1106) from electrical to pneumatic which will be used by
Level Control Valve (LCV-PSS1212). The converted signal from LY-PSS1212 will
be sent to LCV-PSS1212 in order to manipulate the flow of brine from Separator
(V-SS11) and hot brine injection pumps (P-SS12A,P-SS12B,P-SS12C) to hot
brine injection. The position of LCV-PSS1212 can be manually controlled using
Hand Controller (HC-PSS1212). Also, it can be manually controlled by the Hand
Switch (HS-PSS1212). The control mode selected between local or remote is
sent to Hand Switch Indicator (HIS-TSS1127) for HMI and DCS monitoring.
The Position Transmitter (ZT-PSS1212) measures the position of LCV-PSS1212.
The measured position is sent to the Position Indicator (ZI-PSS1212) for HMI and
DCS monitoring.
Control Narrative
Sheet
GEOTHERMAL POWERPLANT
SEPARATOR, SCRUBBER AND
BRINE DISPOSAL SYSTEM
Rev.
No.
Doc.
No.
14 of 19
A
PIC-E-NTV-627002
An orifice plate flow sensor (FE-PSS1202) determines the flow rate of brine from
Separator (V-SS11) and hot brine injection pumps (P-SS12A,P-SS12B,P-SS12C)
to hot brine injection. The FE-PSS1202 will transmit signal to Flow Indicating
Transmitter (FIT-PSS1202) which locally measures and indicates the obtained
flow rate, and then send it to Flow indicator (FI-PSS1202) for HMI monitoring.
Flow Alarm Low (FAL-PSS1202) is connected via data link to DCS to activate low
and very low alarms when the flowrate is critical.
The Flow Switch Low (FSL-PSS1111) triggers and transmits signal to enable
Flow Alarm Low (FAL-PSS1111) through HMI and DCS when the flow deviates
from setpoint (0.5 GPM). FAL-PSS1111 is connected via data link to trip on Hot
Brine Injection Pump (P-SS12A).
Control Narrative
Sheet
GEOTHERMAL POWERPLANT
SEPARATOR, SCRUBBER AND
BRINE DISPOSAL SYSTEM
Rev.
No.
Doc.
No.
15 of 19
A
PIC-E-NTV-627002
The Pressure Indicator (PI-PSS1108) locally displays the pressure of seal water
from Seal Water Pumps (MKB-PS11A and MKB-PS11B) to Hot Brine Injection
Pump (P-SS12A).
The Flow Switch Low (FSL-PSS1111) triggers and transmits signal to enable
Flow Alarm Low (FAL-PSS1111) through HMI and DCS when the flow deviates
from setpoint (0.5 GPM). FAL-PSS1111 is connected via data link to trip on Hot
Brine Injection Pump (P-SS12B).
The Pressure Indicator (PI-PSS1109) locally displays the pressure of seal water
from Seal Water Pumps (MKB-PS11A and MKB-PS11B) to Hot Brine Injection
Pump (P-SS12B).
The Flow Switch Low (FSL-PSS1113) triggers and transmits signal to enable
Flow Alarm Low (FAL-PSS1113) through HMI and DCS when the flow deviates
from setpoint (0.5 GPM). FAL-PSS1113 is connected via data link to trip on Hot
Brine Injection Pump (P-SS12C).
The Pressure Indicator (PI-PSS1110) locally displays the pressure of seal water
from Seal Water Pumps (MKB-PS11A and MKB-PS11B) to Hot Brine Injection
Pump (P-SS12B).
Control Narrative
Sheet
GEOTHERMAL POWERPLANT
SEPARATOR, SCRUBBER AND
BRINE DISPOSAL SYSTEM
Rev.
No.
Doc.
No.
16 of 19
A
PIC-E-NTV-627002
The Pressure Indicator (PI-PSS1104) locally displays the pressure of seal water
from Seal Water Pumps (MKB-PS11A and MKB-PS11B) going to Hot Brine
Injection Pumps (P-SS12A, P-SS12B, and P-SS12C).
HP SCRUBBER
LOOP 1205 (Pressure: MKB-VSS12)
The Pressure Indicator (PI-VSS1205) locally displays the steam pressure from
HP Scrubber (MKB-VSS12).
DCS monitoring.
The Pressure P/I Transducer (PY-VSS1206B) converts the signal of Pressure
Indicating Controller (PIC-VPSA209) from pneumatic to electrical that will be
used by Low Selector (PY-VSS1206A). PY-VSS1206A selects the lowest setpoint
between PIC-VSS1206 and PIC-VPSA209 then, the signal will go to the 3-way
solenoid valve for split range control.
Control Narrative
Sheet
GEOTHERMAL POWERPLANT
SEPARATOR, SCRUBBER AND
BRINE DISPOSAL SYSTEM
Rev.
No.
Doc.
No.
17 of 19
A
PIC-E-NTV-627002
The Rotary and Butterfly Pressure Control Valves (PCV-VSS1206A) and (PCVVSS1206B) are in split range control wherein the PCV-VSS1206A allows the
steam to flow in order to reach 18-6 psi set point. When the pressure of steam
entering MKB-RSS11 is increasing beyond set point, PCV-VSS1206B will open to
compensate the increasing pressure, and if the pressure is decreasing beyond
set point, PCV-VSS1206B will be closed.
The Pitot Tube Flow Sensor (FE-VSS1207) measures the flowrate of the steam
along the pipeline from HP Scrubber (MKB-VSS12) and sends the measured
Control Narrative
Sheet
GEOTHERMAL POWERPLANT
SEPARATOR, SCRUBBER AND
BRINE DISPOSAL SYSTEM
Rev.
No.
Doc.
No.
18 of 19
A
PIC-E-NTV-627002
Control Narrative
Sheet
GEOTHERMAL POWERPLANT
SEPARATOR, SCRUBBER AND
BRINE DISPOSAL SYSTEM
Rev.
No.
Doc.
No.
19 of 19
A
PIC-E-NTV-627002
LEVEL DRUM
LOOP 1301 (Level: MKB-VSS13)
The Level Gauge (LG-VSS1301) locally displays the level inside Level Drum
(MKB-VSS13).